RTA DRAWINGS VOL2 .pdf

PDF 39 MB Posted

Attached to
Cyberspace Test Group Facility, Eglin AFB, FL Federal contract opportunity
Solicitation number
W9127820R0057
Issued by
Department of the Army Corps of Engineers Engineering District Mobile

About this file

This document provides details for a federal contract solicitation to construct a new Cyberspace Test Group Facility at Eglin Air Force Base in Florida. The solicitation is for a multistory, 52,003 square foot sensitive compartmented information facility with a concrete foundation, split-faced concrete block construction over a steel frame, and a sloped standing seam metal roof. The facility will include fire suppression systems, all required utilities, pavements, communications infrastructure, site improvements, and support facilities to provide a complete and usable facility for the Cyberspace Test Group mission. The solicitation was issued by the Department of the Army Corps of Engineers Engineering District Mobile. The anticipated award date is not specified. Interested contractors are advised to review the full solicitation document available as attachment W9127820R0057 for detailed technical requirements, response instructions and deadlines, and other terms relevant to preparing a proposal for this construction project.

View the file

Other files for this federal contract opportunity

Other files attached to Cyberspace Test Group Facility, Eglin AFB, FL, newest first.
File Type Posted
W9127820R0057 JA_Redacted.pdf PDF
AM05 DRAWINGS.pdf PDF
AM05.pdf PDF
AM04.pdf PDF
AM03 DRAWINGS.pdf PDF
AM03.pdf PDF
AM02 DRAWINGS.pdf PDF
AM02.pdf PDF
AM01 DRAWINGS.pdf PDF
AM01.pdf PDF
Site visit sign in sheet.pdf PDF
VOL3.PDF PDF
VOL1.PDF PDF
VOL6.PDF PDF
VOL4.PDF PDF
RTA DRAWINGS VOL1.pdf PDF
VOL5.PDF PDF
VOL2.PDF PDF
EM 385-1-1.pdf PDF
Show all 19

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers

MOBILE DISTRICT

109 SAINT JOSEPH STREET

MOBILE AL 36602

CYBERSPACE TEST GROUP FACILITY

EGLIN AIR FORCE BASE, FLORIDA

OKALOOSA COUNTY

JUNE 2020

MOBILE DISTRICT PROJECT CODE: MEF19017

RFP NUMBER: W9127820R0057

VOLUME 2 OF 2

A

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C

E R

V A

N T

E S

S T

R E

E T

P E

N S

A C

O L

A F

L O

R

ID

A

2 3 4 5

B

C

D

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

W

R

5/

/2

9:

:4

A

M

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y E

G L

IN

A

F B

, F L

O R

ID

A

G-002

IN

D

E X

O F

D R

A W

IN

G

S

B

M A

G G

IO

R

E

T

W A

L L

IS

B

M

A G

G

IO

R E

B T

A

M

A Y

M E

F

G

FTFA 16-3007

INDEX OF DRAWINGS - VOLUME 1 OF 2

SHEET

NUMBER SHEET NAME

A-602 SECOND FLOOR DOOR SCHEDULE

A-603 EXTERIOR DOOR DETAILS

A-604 INTERIOR DOOR DETAILS

A-610 CURTAINWALL, INTERIOR WINDOW, AND LOUVER ELEVATIONS

A-611 CURTAINWALL DETAILS

A-612 INTERIOR WINDOW DETAILS AND CABLE PASS THRU DETAIL

A-613 LOUVER DETAILS

A-700 ANTENNA PLATFORM DETAILS

INTERIOR

I-101 PARTIAL FIRST FLOOR FINISH PLAN - WEST

I-102 PARTIAL FIRST FLOOR FINISH PLAN - EAST

I-103 PARTIAL SECOND FLOOR FINISH PLAN - WEST

I-104 PARTIAL SECOND FLOOR FINISH PLAN - EAST

I-105 PARTIAL FIRST FLOOR MCT PATTERN PLAN - WEST

I-106 PARTIAL FIRST FLOOR MCT PATTERN PLAN - EAST

I-107 PARTIAL SECOND FLOOR MCT PATTERN PLAN - WEST

I-108 PARTIAL SECOND FLOOR MCT PATTERN PLAN - EAST

I-109 PARTIAL FIRST FLOOR FURNITURE PLAN - WEST

I-110 PARTIAL FIRST FLOOR FURNITURE PLAN - EAST

I-111 PARTIAL SECOND FLOOR FURNITURE PLAN - WEST

I-112 PARTIAL SECOND FLOOR FURNITURE PLAN - EAST

I-113 PARTIAL FIRST FLOOR SIGNAGE AND CORNER GUARD PLAN - WEST

I-114 PARTIAL FIRST FLOOR SIGNAGE AND CORNER GUARD PLAN - EAST

I-115 PARTIAL SECOND FLOOR SIGNAGE AND CORNER GUARD PLAN - WEST

I-116 PARTIAL SECOND FLOOR SIGNAGE AND CORNER GUARD PLAN - EAST

I-140 WORKSTATION GROUP TYPICALS

I-141 WORKSTATION GROUP TYPICALS

I-142 WORKSTATION GROUP TYPICALS

I-143 WORKSTATION GROUP TYPICALS

I-201 INTERIOR ELEVATIONS

I-202 INTERIOR ELEVATIONS

I-203 FFE ELEVATIONS

I-601 FIRST FLOOR ROOM FINISH SCHEDULE

I-602 SECOND FLOOR ROOM FINISH SCHEDULE

I-603 SIGNAGE SCHEDULE

I-604 SIGNAGE DETAILS

INDEX OF DRAWINGS - VOLUME 1 OF 2

SHEET

NUMBER SHEET NAME

S-306 SECTIONS AND DETAILS

S-307 SECTIONS AND DETAILS

S-401 FOUNDATION SECTIONS AND DETAILS

S-402 FOUNDATION SECTIONS AND DETAILS

S-403 FOUNDATION SECTIONS AND DETAILS

S-404 FOUNDATION SECTIONS AND DETAILS

S-501 TYPICAL MASONRY DETAILS

S-502 TYPICAL STEEL DETAILS

S-503 TYPICAL BASE PLATE, FOUNDATION AND SLAB DETAILS

S-504 TYPICAL ELEVATED FLOOR DETAILS

ARCHITECTURAL

A-001 LEGEND, NOTES AND ABBREVIATIONS

A-002 EXTERIOR WALL TYPES

A-003 INTERIOR WALL TYPES

A-004 INTERIOR WALL TYPES

A-005 INTERIOR WALL TYPES

A-101 OVERALL FIRST FLOOR PLAN

A-102 ENLARGED FIRST FLOOR PLAN WEST

A-103 ENLARGED FIRST FLOOR PLAN EAST

A-104 FIRST FLOOR OVERALL DIMENSION PLAN

A-105 PARTIAL FIRST FLOOR DIMENSION PLAN - WEST

A-106 PARTIAL FIRST FLOOR DIMENSION PLAN - EAST

A-107 OVERALL SECOND FLOOR PLAN

A-108 PARTIAL SECOND FLOOR PLAN - WEST

A-109 PARTIAL SECOND FLOOR PLAN - EAST

A-110 SECOND FLOOR OVERALL DIMENSION PLAN

A-111 PARTIAL SECOND FLOOR DIMENSION PLAN - WEST

A-112 PARTIAL SECOND FLOOR DIMENSION PLAN - EAST

A-140 ROOF PLAN

A-141 ROOF DETAILS

A-142 ROOF DETAILS

A-143 ROOF DETAILS

A-144 ROOF DETAILS

A-145 CANOPY DETAILS

A-150 OVERALL FIRST FLOOR REFLECTED CEILING PLAN

A-151 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - WEST

A-152 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - EAST

A-153 OVERALL SECOND FLOOR REFLECTED CEILING PLAN

A-154 PARTIAL SECOND FLOOR REFLECTED CEILING PLAN - WEST

A-155 PARTIAL SECOND FLOOR REFLECTED CEILING PLAN - EAST

A-156 FIRST FLOOR SECURITY/ STC 50 GYPSUM WALLBOARD REFLECTED CEILING

PLAN

A-157 SECOND FLOOR SECURITY/STC 50 GYPSUM WALLBOARD REFLECTED

CEILING PLAN

A-201 BUILDING ELEVATIONS

A-202 ENLARGED ELEVATIONS

A-203 BUILDING ELEVATIONS

A-301 BUILDING SECTIONS

A-302 BUILDING SECTIONS

A-303 TROLLEY HOIST SECTION @ AVIONICA LAB

A-310 WALL SECTIONS

A-311 WALL SECTIONS

A-312 WALL SECTIONS

A-313 WALL SECTIONS

A-314 TYPICAL SECURITY/STC ASSEMBLY SEALING DETAILS

A-410 ENLARGED PLANS - RESTROOMS

A-411 ENLARGED PLANS - STAIRS

A-412 ENLARGED STAIR SECTIONS

A-413 ENLARGED STAIRS SECTION

A-414 STAIR DETAILS AND SECTIONS

A-415 PASSENGER ELEVATOR PLANS AND SECTIONS

A-416 SERVICE ELEVATOR PLANS AND SECTION

A-417 EQUIPMENT ENCLOSURE PLANS AND SECTIONS

A-418 ENLARGED LOADING DOCK PLAN

A-450 CASEWORK ELEVATIONS

A-451 CASEWORK SECTIONS

A-501 EXTERIOR & INTERIOR PLAN DETAILS

A-502 INTERIOR PLAN DETAILS

A-510 SLAB/ACCESS FLOOR DETAILS @ FIRST FLOOR

A-511 SLAB/ACCESS FLOOR DETAILS @ SECOND FLOOR

A-520 SECURITY/STC CEILING DETAILS

A-521 CEILING DETAILS

A-522 SECURITY/STC CEILING DETAILS @ ROOF

A-601 FIRST FLOOR DOOR SCHEDULE AND DOOR AND FRAME ELEVATIONS

INDEX OF DRAWINGS - VOLUME 1 OF 2

SHEET

NUMBER SHEET NAME

CS127 ENLARGED EXISTING MANHOLE 2B1

CS501 PAVING DETAILS

CS502 CIVIL AND PAVING DETAILS

CS503 CIVIL DETAILS

CS504 CIVIL DETAILS

CS505 FENCE DETAILS

CS506 GATE DETAILS

CL101 GEOMETRIC LAYOUT PLAN - BUILDING NORTH

CL102 GEOMETRIC LAYOUT PLAN - BUILDING SOUTH

CL103 GEOMETRIC LAYOUT PLAN - EAST

CL104 GEOMETRIC LAYOUT PLAN - PARKING LOT NORTH

CL105 GEOMETRIC LAYOUT PLAN - PARKING LOT SOUTH

CL601 HORIZONTAL CONTROL TABLES

CG101 BUILDING GRADING PLAN - NORTH

CG102 BUILDING GRADING PLAN - SOUTH

CG103 EAST GRADING PLAN

CG104 PARKING LOT GRADING PLAN - NORTH

CG105 PARKING LOT GRADING PLAN - SOUTH

CG201 FACILITY PROFILES

CG202 BUILDING DRAINAGE PROFILES

CG203 SWMF PROFILES

CG211 PARKING LOT DRAINAGE PROFILES

CG212 PARKING LOT DRAINAGE PROFILES

CG213 PARKING LOT DRAINAGE PROFILES

CG214 PARKING LOT DRAINAGE PROFILES

CG501 DRAINAGE DETAILS

CG502 DRAINAGE DETAILS

CG601 STORM DRAIN STRUCTURE TABLE

CG602 STORM DRAIN PIPE TABLE

CE100 OVERALL EROSION AND SEDIMENT CONTROL PLAN

CE101 EROSION AND SEDIMENT CONTROL PLAN - NORTH

CE102 EROSION AND SEDIMENT CONTROL PLAN - SOUTH

CE501 EROSION CONTROL DETAILS

CE502 STORWATER POLLUTION PREVENTION PLAN

CU101 BUILDING UTILITY PLAN - NORTH

CU102 BUILDING UTILITY PLAN - SOUTH

CU103 ENLARGED UTILITY PLAN

CU201 SANITARY SERVICE PROFILES

CU501 UTILITY DETAILS

CATHODIC PROTECTION

X-101 CATHODIC LAYOUT

X-102 CATHODIC PROTECTION DETAILS

X-103 CATHODIC PROTECTION DETAILS

LANDSCAPE

L-100 LANDSCAPE PLAN

L-101 LANDSCAPE PLAN

L-102 LANDSCAPE PLAN

L-103 LANDSCAPE PLAN

L-104 LANDSCAPE DETAILS

STRUCTURAL

S-001 GENERAL NOTES

S-002 GENERAL NOTES CONTINUED AND WIND LOAD DIAGRAM

S-101 FOUNDATION AND SLAB-ON-GRADE PLAN - WEST

S-102 FOUNDATION AND SLAB-ON-GRADE PLAN - EAST

S-103 SECOND FLOOR FRAMING PLAN - WEST

S-104 SECOND FLOOR FRAMING PLAN - EAST

S-105 ROOF FRAMING PLAN - WEST

S-106 ROOF FRAMING PLAN - EAST

S-107 ANTENNA PLATFORM FRAMING PLAN

S-201 FRAMING ELEVATIONS

S-202 FRAMING ELEVATIONS

S-203 FRAMING ELEVATIONS

S-204 BRACED FRAME DETAILS

S-205 TRUSS ELEVATIONS

S-206 TRUSS BRACING ELEVATIONS

S-207 TYPICAL TRUSS CONNECTION DETAILS

S-208 TYPICAL TRUSS CONNECTION DETAILS

S-301 SECTIONS AND DETAILS

S-302 SECTIONS AND DETAILS

S-303 SECTIONS AND DETAILS

S-304 SECTIONS AND DETAILS

S-305 SECTIONS AND DETAILS

INDEX OF DRAWINGS - VOLUME 1 OF 2

SHEET

NUMBER SHEET NAME

GENERAL

G-001 TITLE SHEET

G-002 INDEX OF DRAWINGS

G-003 INDEX OF DRAWINGS

GC003 SITE LOCATION, ACCESS AND SAFETY PLAN

GC004 SITE USE AND WORK RESTRICTION PLAN

GC005 SITE WORK PHASING PLAN

G-004 SECURITY AND STC CONSTRUCTION NOTES

G-005 CODE SUMMARY

G-101 OVERALL FIRST FLOOR LIFE SAFETY PLAN

G-102 PARTIAL FIRST FLOOR LIFE SAFETY PLAN - WEST

G-103 PARTIAL FIRST FLOOR LIFE SAFETY PLAN - EAST

G-104 OVERALL SECOND FLOOR LIFE SAFETY PLAN

G-105 PARTIAL SECOND FLOOR LIFE SAFETY PLAN - WEST

G-106 PARTIAL SECOND FLOOR LIFE SAFETY PLAN - EAST

G-107 FIRST FLOOR SECURITY PLAN - WEST

G-108 FIRST FLOOR SECURITY PLAN - EAST

G-109 SECOND FLOOR SECURITY PLAN - WEST

G-110 SECOND FLOOR SECURITY PLAN - EAST

G-111 FIRST FLOOR AIR BARRIER PLAN

G-112 SECOND FLOOR AIR BARRIER PLAN

G-113 AIR BARRIER BUILDING SECTIONS

G-114 AIR BARRIER BUILDING SECTIONS

G-115 AIR BARRIER BUILDING SECTIONS

CIVIL

V-100 SURVEY NOTES AND LEGEND AND LEVEL A SURVEY VACUUM EXTRACTION

SITES DATA TABLE

V-101 SURVEY NOTES AND LEGEND AND LEVEL A SURVEY VACUUM EXTRACTION

SITES DATA TABLE

V-102 SURVEY NOTES AND LEGEND AND LEVEL A SURVEY VACUUM EXTRACTION

SITES DATA TABLE

V-103 SURVEY AREA KEY SHEET

V-104 SURVEY NOTES AND LEGEND AND LEVEL A SURVEY VACUUM EXTRACTION

SITES DATA TABLE

V-105 SURVEY AND SURVEY CONTROL PLAN

V-106 SURVEY AND SURVEY CONTROL PLAN

V-107 SURVEY AND SURVEY CONTROL PLAN

V-108 SURVEY AND SURVEY CONTROL PLAN

V-109 SURVEY AND SURVEY CONTROL PLAN

V-110 SURVEY AND SURVEY CONTROL PLAN

V-111 SURVEY AND SURVEY CONTROL PLAN

V-112 SURVEY AND SURVEY CONTROL PLAN

V-113 SURVEY AND SURVEY CONTROL PLAN

V-114 SURVEY AND SURVEY CONTROL PLAN

V-115 SURVEY AND SURVEY CONTROL PLAN

V-116 SURVEY AND SURVEY CONTROL PLAN

V-117 SURVEY AND SURVEY CONTROL PLAN

V-118 SURVEY AND SURVEY CONTROL PLAN

CI001 GENERAL CIVIL NOTES

CI002 ABBREVIATIONS AND LEGEND

CD101 OVERALL DEMOLITION PLAN

CD102 BUILDING DEMOLITION PLAN NORTH

CD103 BUILDING DEMOLITION PLAN SOUTH

CD104 PARKING DEMOLITION PLAN NORTH

CD105 PARKING DEMOLITION PLAN SOUTH

CS100 KEY MAP

CS101 BUILDING SITE PLAN - NORTH

CS102 BUILDING SITE PLAN - SOUTH

CS103 EAST SITE PLAN

CS104 PARKING LOT SITE PLAN - NORTH

CS105 PARKING LOT SITE PLAN - SOUTH

CS110 JOINT LAYOUT OVERALL KEY MAP

CS111 JOINT LAYOUT PLAN A

CS112 JOINT LAYOUT PLAN B

CS113 JOINT LAYOUT PLAN C

CS114 JOINT LAYOUT PLAN D

CS115 JOINT LAYOUT PLAN SOUTHEAST PARKING

CS120 REMOTE SITE KEY SHEET

CS121 ENLARGED PLAN EXISTING MANHOLE 73 AREA

CS122 ENLARGED EXISTING MANHOLE 7C AREA

CS123 ENLARGED EXISTING MANHOLE 8C AND NEW MANHOLE 2E-1 AREA

CS124 ENLARGED EXISTING MANHOLE 2E AREA

CS125 ENLARGED EXISTING MANHOLES 17, 18, AND 19

CS126 ENLARGED EXISTING MANHOLE 2B2

INDEX OF DRAWINGS THIS SHEET

INCLUDE VOLUME 1 DRAWINGS

A

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C

E R

V A

N T

E S

S T

R E

E T

P E

N S

A C

O L

A F

L O

R

ID

A

2 3 4 5

B

C

D

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

W

R

/2

/2

:4

:0

A

M

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y

E G

L

IN

A F

B

F L

O R

ID

A

G-003

IN

D

E X

O F

D R

A W

IN

G

S

B

M A

G G

IO

R

E

T

W A

L L

IS

B

M

A G

G

IO

R E

B T

A

M

A Y

M E

F

G

FTFA 16-3007

INDEX OF DRAWINGS - VOLUME 2 OF 2

SHEET

NUMBER SHEET NAME

T-014 ENLARGED EXISTING MANHOLE 2B2

T-015 ENLARGED EXISTING MANHOLE 2B1

T-016 ENLARGED NEW MAINTENANCE HOLE 72 AND EX MH 73

T-017 ENLARGED NEW MAINTENANCE HOLE 71

T-018 ENLARGED BUILDING 90 MAINTENANCE HOLES

T-019 NON-CORE SERVICES COMMUNICATIONS SITE PLAN - BID OPTION 3

T-020 TELECOM SITE DETAILS

T-021 TELECOM SITE DETAILS

T-111 OVERALL FIRST FLOOR CONDUIT PATHWAY PLAN

T-112 OVERALL FIRST FLOOR OVERHEAD/ABOVE CEILING PATHWAY PLAN

T-113 OVERALL FIRST FLOOR BELOW FLOOR PATHWAY PLAN

T-114 OVERALL FIRST FLOOR CABLING DISTRIBUTION PLAN

T-115 ENLARGED FIRST FLOOR PLAN WEST

T-116 ENLARGED FIRST FLOOR PLAN EAST

T-121 OVERALL SECOND FLOOR CONDUIT PATHWAY PLAN

T-122 OVERALL SECOND FLOOR OVERHEAD/ ABOVE CEILING PATHWAY PLAN

T-123 OVERALL SECOND FLOOR BELOW FLOOR PATHWAY PLAN

T-124 OVERALL SECOND FLOOR CABLING DISTRIBUTION PLAN

T-125 ENLARGED SECOND FLOOR PLAN WEST

T-126 ENLARGED SECOND FLOOR PLAN EAST

T-201 TELECOM GROUNDING DETAILS

T-202 TELECOM OUTLET DETAILS

T-203 TELECOM OUTLET DETAILS

T-204 TELECOM DETAILS

T-205 TELECOM DETAILS

T-206 PROTECTIVE DISTRIBTION SYSTEM (PDS) DETAILS

T-207 PROTECTIVE DISTRIBTION SYSTEM (PDS) DETAILS

T-208 TELECOM MOUNTING DETAILS

T-301 CORE BACKBONE SINGLE LINE DIAGRAMS

T-302 NON-CORE BACKBONE AND UNCLASS SINGLE LINE DIAGRAMS

T-303 CLASS SIPR & NON CORE SINGLE LINE DIAGRAMS

T-304 NON-CORE SINGLE LINE DIAGRAMS

T-305 NON-CORE AND UNCLASS SINGLE LINE DIAGRAMS

T-306 LAB CLOSED NETWORKS SINGLE LINE DIAGAMS

T-307 OTHER, COMMERCIAL, AND LAB CLOSED NETWORK SINGLE LINE DIAGRAMS

T-308 CATV AND PA SINGLE LINE DIAGRAMS

T-401 TELECOM ENLARGED SERVER ROOM 114

T-402 TELECOM ENLARGED STORAGE ROOM 129

T-403 TELECOM ENLARGED ATL ANALYSIS ROOM 138

T-404 TELECOM ENLARGED C/EW ANALYSIS ROOM 140

T-405 TELECOM ENLARGED COMM ROOM 141 & AC SERVER ROOM 148

T-406 TELECOM ENLARGED COMM ROOM 152

T-407 TELECOM ENLARGED IDE SERVER ROOM 202

T-408 TELECOM ENLARGED 96 CTG. SEC. COMM ROOM 214

T-409 TELECOM ENLARGED COMM ROOM 234 & 240

T-501 TELECOM RACK ELEVATIONS- SERVER ROOM 114 & STORAGE ROOM 129

T-502 TELECOM RACK ELEVATIONS - ATL ANALYSIS ROOM 138

T-503 TELECOM RACK ELEVATIONS - C/EW ANALYSIS ROOM 140

T-504 TELECOM RACK ELEVATIONS - COMM. ROOM 141 & ACR SERVER ROOM 148

T-505 TELECOM RACK ELEVATIONS - COMM ROOM 152

T-506 TELECOM RACK ELEVATIONS - IDE SERVER ROOM 202

T-507 TELECOM RACK ELEVATIONS - ITS STORAGE ROOM 211 & 96 CTG. SEC, COMM ROOM 214

T-508 TELECOM RACK ELEVATIONS - COMM ROOM 234

T-509 TELECOM RACK ELEVATIONS - COMM. ROOM 240

TA001 AUDIO VISUAL LEGEND

TA111 AUDIO VISUAL FIRST FLOOR PLAN WEST

TA112 AUDIO VISUAL FIRST FLOOR PLAN EAST

TA121 AUDIO VISUAL SECOND FLOOR PLAN WEST

TA122 AUDIO VISUAL SECOND FLOOR PLAN EAST

TA201 AUDIO VISUAL DETAILS

TA301 AUDIO VISUAL DIAGRAMS

TY001 SECURITY LEGEND & NOTES

TY111 SECURITY FIRST FLOOR PLAN WEST

TY112 SECURITY FIRST FLOOR PLAN EAST

TY121 SECURITY SECOND FLOOR PLAN WEST

TY122 SECURITY SECOND FLOOR PLAN EAST

TY201 SECURITY DETAILS

TY202 SECURITY DOOR DETAILS

TY203 SECURITY DOOR DETAILS

TY204 SECURITY DOOR DETAILS

TY205 SECURITY DOOR DETAILS

TY301 SECURITY SINGLE LINE DIAGRAMS

TY302 SECURITY SINGLE LINE DIAGRAMS

INDEX OF DRAWINGS - VOLUME 2 OF 2

SHEET

NUMBER SHEET NAME

E-100 DEMO ELECTRICAL SITE PLAN

E-101 NEW WORK ELECTRICAL SITE PLAN

E-102 NEW WORK ELECTRICAL SITE LIGHTING PLAN

E-103 SITE LIGHTING DETAILS - BID OPTION 11

E-111 OVERALL FIRST FLOOR POWER PLAN & PATHWAYS

E-112 FIRST FLOOR POWER PLAN - WEST

E-113 FIRST FLOOR GROUNDING PLAN - WEST

E-114 FIRST FLOOR POWER PLAN - EAST

E-115 FIRST FLOOR GROUNDING PLAN - EAST

E-116 OVERALL SECOND FLOOR POWER PLAN

E-117 SECOND FLOOR POWER PLAN - WEST

E-118 SECOND FLOOR GROUNDING PLAN - WEST

E-119 SECOND FLOOR POWER PLAN - EAST

E-120 SECOND FLOOR GROUNDING PLAN - EAST

E-211 OVERALL FIRST FLOOR LIGHTING PLAN

E-212 FIRST FLOOR LIGHTING PLAN - WEST

E-213 FIRST FLOOR LIGHTING PLAN - EAST

E-214 OVERALL SECOND FLOOR LIGHTING PLAN

E-215 SECOND FLOOR LIGHTING PLAN - WEST

E-216 SECOND FLOOR LIGHTING PLAN - EAST

E-311 OVERALL FIRST FLOOR MECHANICAL POWER PLAN

E-312 FIRST FLOOR MECHANICAL POWER PLAN - WEST

E-313 FIRST FLOOR MECHANICAL POWER PLAN - EAST

E-314 OVERALL SECOND FLOOR MECHANICAL POWER PLAN

E-315 SECOND FLOOR MECHANICAL POWER PLAN - WEST

E-316 SECOND FLOOR MECHANICAL POWER PLAN - EAST

E-400 LIGHTNING PROTECTION PLAN

E-401 LIGHTNING PROTECTION DETAILS

E-500 DEV&RE LAB/THREAT DEVELOPMENT LAB ENLARGED 60Hz/00Hz & DC ROOM PLANS

E-501 CYBER/EW ENLARGED ROOM PLAN 60Hz

E-502 CYBER/EW ENLARGED ROOM PLAN 400Hz & DC

E-503 AVIONICS TEST LAB ENLARGED ROOM PLAN 60Hz

E-504 AVIONICS TEST LAB ENLARGED ROOM PLAN - 400Hz & DC

E-600 PANEL SCHEDULE INDEX

E-601 PANEL SCHEDULE

E-602 PANEL SCHEDULE

E-603 PANEL SCHEDULE

E-604 PANEL SCHEDULE

E-605 PANEL SCHEDULE

E-606 PANEL SCHEDULE

E-607 PANEL SCHEDULE

E-608 PANEL SCHEDULE

E-609 PANEL SCHEDULE

E-610 PANEL SCHEDULE

E-611 PANEL SCHEDULE

E-612 PANEL SCHEDULE

E-613 PANEL SCHEDULE

E-614 PANEL SCHEDULE

E-615 PANEL SCHEDULE

E-616 PANEL SCHEDULE

E-617 400Hz PANEL SCHEDULE

E-618 400Hz PANEL SCHEDULE

E-619 400Hz PANEL SCHEDULE

E-620 270VDC PANEL SCHEDULES

E-621 28VDC PANEL SCHEDULES

E-622 28VDC PANEL SCHEDULES

E-623 28VDC PANEL SCHEDULES

E-624 PANEL SCHEDULE

E-625 PANEL SCHEDULE

E-626 BUS DUCT PLUG SCHEDULES

E-627 BUS DUCT PLUG SCHEDULES

TELECOMMUNICATIONS

T-001 TELECOM LEGEND

T-002 GENERAL NOTES

T-003 TELECOM SITE NOTES

T-004 PARTIAL CORE SERVICES COMMUNICATIONS SITE PLAN

T-005 PARTIAL CORE SERVICES COMMUNICATIONS SITE PLAN

T-006 PARTIAL CORE SERVICES COMMUNICATIONS SITE PLAN

T-007 PARTIAL CORE SERVICES COMMUNICATIONS SITE PLAN

T-008 ENLARGED EXISTING MANHOLE 73 AREA

T-009 ENLARGED EXISTING MANHOLE 7C AREA

T-010 ENLARGED EXISTING MANHOLE 8C AND NEW MANHOLE 2E-1 AREA

T-011 ENLARGED EXISTING MANHOLE 2E AREA

T-012 ENLARGED EXISTING MANHOLE 2X AND 3X

T-013 ENLARGED EXISTING MANHOLE 17, 18, & 19

INDEX OF DRAWINGS - VOLUME 2 OF 2

SHEET

NUMBER SHEET NAME

FIRE PROTECTION

FA101 OVERALL FIRST FLOOR FIRE ALARM PLAN

FA102 PARTIAL FIRST FLOOR FIRE ALARM PLAN - WEST

FA103 PARTIAL FIRST FLOOR FIRE ALARM PLAN - EAST

FA104 OVERALL SECOND FLOOR FIRE ALARM PLAN

FA105 PARTIAL SECOND FLOOR FIRE ALARM PLAN - WEST

FA106 PARTIAL SECOND FLOOR FIRE ALARM PLAN - EAST

FA501 DETAILS - FIRE ALARM

FA502 FIRE ALARM SEQUENCE OF OPERATION

FX101 OVERALL FIRST FLOOR FIRE PROTECTION PLAN

FX102 PARTIAL FIRST FLOOR FIRE PROTECTION PLAN - WEST

FX103 PARTIAL FIRST FLOOR FIRE PROTECTION PLAN - EAST

FX104 OVERALL SECOND FLOOR FIRE PROTECTION PLAN

FX105 PARTIAL SECOND FLOOR FIRE PROTECTION PLAN - WEST

FX106 PARTIAL SECOND FLOOR FIRE PROTECTION PLAN - EAST

FX401 ENLARGED FIRE PUMP ROOM

FX501 DETAILS - FIRE PROTECTION

PLUMBING

P-001 PLUMBING LEGENDS, NOTES & ABBREVIATION

P-101 PARTIAL FIRST FLOOR PLAN WEST - PLUMBING BELOW SLAB

P-102 PARTIAL FIRST FLOOR PLAN EAST - PLUMBING BELOW SLAB

P-103 PARTIAL FIRST FLOOR PLAN WEST - PLUMBING ABOVE SLAB

P-104 PARTIAL FIRST FLOOR PLAN EAST - PLUMBING ABOVE SLAB

P-105 PARTIAL SECOND FLOOR PLAN WEST - PLUMBING BELOW SLAB

P-106 PARTIAL SECOND FLOOR PLAN EAST - PLUMBING BELOW SLAB

P-107 PARTIAL SECOND FLOOR PLAN WEST - PLUMBING ABOVE SLAB

P-108 PARTIAL SECOND FLOOR PLAN EAST - PLUMBING ABOVE SLAB

P-401 ENLARGED FIRST FLOOR PLAN - PLUMBING WASTE, VENT AND WATER

P-402 ENLARGED SECOND FLOOR PLAN - PLUMBING WASTE, VENT AND WATER

P-501 PLUMBING DETAILS-1

P-502 PLUMBING DETAILS-2

P-503 PLUMBING DETAILS-3

P-601 PLUMBING SCHEDULES-1

P-901 PLUMBING RISER EAST - WASTE AND VENT

P-902 PLUMBING RISER WEST - WASTE AND VENT

P-903 PLUMBING RISER - COMPRESSED AIR

MECHANICAL

M-001 HVAC LEGENDS, NOTES & ABBREVIATION

M-101 OVERALL FIRST FLOOR PLAN - HVAC

M-102 PARTIAL FIRST FLOOR PLAN - HVAC WEST

M-103 PARTIAL FIRST FLOOR PLAN - HVAC EAST

M-104 OVERALL SECOND FLOOR PLAN - HVAC

M-105 PARTIAL SECOND FLOOR PLAN - HVAC WEST

M-106 PARTIAL SECOND FLOOR PLAN - HVAC EAST

M-107 PARTIAL FIRST FLOOR PLAN - HVAC PIPING WEST

M-108 PARTIAL FIRST FLOOR PLAN - HVAC PIPING EAST

M-109 PARTIAL SECOND FLOOR PLAN - HVAC PIPING WEST

M-110 PARTIAL SECOND FLOOR PLAN - HVAC PIPING EAST

M-401 ENLARGED PLAN - HVAC

M-501 HVAC DETAILS-1

M-502 HVAC DETAILS-2

M-503 HVAC DETAILS-3

M-504 HVAC DETAILS-4

M-601 HVAC SCHEDULES-1

M-602 HVAC SCHEDULES-2

M-603 HVAC SCHEDULES-3

M-701 CHILLED WATER PIPING DIAGRAM - PRIMARY LOOP

M-702 CHILLED WATER PIPING DIAGRAM - SECONDARY LOOP

M-703 HVAC CONTROLS-1

M-704 HVAC CONTROLS-2

M-705 HVAC CONTROLS-3

ELECTRICAL

E-001 LEGEND AND ABBREVIATIONS

E-002 LIGHTING FIXTURE SCHEDULE

E-003 ELECTRICAL PRIMARY RISER

E-004 ELECTRICAL ONE-LINE DIAGRAM (277/480V) - BASE BID

E-005 BID OPTIONS ELECTRICAL ONE-LINE DIAGRAM (227/480V)

E-006 ELECTRICAL ONE-LINE DIAGRAM (120/280V)

E-007 400Hz, 28VDC, ONE LINE DIAGRAMS

E-008 GROUNDING SYSTEM RISER DIAGRAM

E-009 PENETRATION DETAILS

E-010 LIGHTING DETAILS

E-011 LIGHTING DETAILS

INDEX OF DRAWINGS THIS SHEET

INCLUDE VOLUME 2 DRAWINGS

MECHANICAL YARD

109 111

120121

128 129

130B

143 154

144C

145 146 147 148

108 110A

A B C.2C D D.4 E F G H J K M N P

2.8

1.6

144B

144A

MANUAL PULL STATION

FIRE ALARM AND MASS NOTIFICATION SPEAKER

(CEILING-MOUNTED)

FIRE ALARM AND MASS NOTIFICATION

CONTROL UNIT

MONITOR MODULE

PHOTOELECTRIC SMOKE DETECTOR

INDICATES WEATHERPROOFWP

DUCT SMOKE DETECTOR

LOCAL OPERATOR CONSOLE (RECESSED

OR SURFACE MOUNTED AS INDICATED)

W/REMOTE MICROPHONE AND HVAC

SHUTDOWN SWITCH

WATERFLOW SWITCH

TAMPER SWITCH

RELAY MODULE

LOC

MM

FACU

R

FIRE ALARM LEGEND

P

FSA

FIRE ALARM REMOTE ANNUNCIATION

PANEL (RECESSED)

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS XX

XX

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS

(CEILING-MOUNTED)

XX

FIRE ALARM AND MASS NOTIFICATION STROBE

WITH CLEAR LENS

(CEILING-MOUNTED)

XMIT MONACO TRANSCEIVER

CANDELA RATINGXX

AREA BELOW ACCESS FLOOR PROTECTED

WITH ULTRA SENSITIVE SMOKE DETECTION

USSD ULTRA SENSITIVE SMOKE DETECTION PANEL

FIRE ALARM AND MASS NOTIFICATION SPEAKER

TEXT SCROLLING LCD TEXT SIGNS

FIRE ALARM NOTES

1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION

SYSTEM NOTES AND DETAILS.

2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE

SELF-AMPLIFYING TYPE.

3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE

AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL

SECURE AREA NOTES.

4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS

SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE

RATING AS APPLICABLE.

5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE

AREA PERIMETER WALLS SHALL BE PROVIDED WITH

DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE

DETAIL 1/FA501.

6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO

PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL

TO ACCESS DUCTWORK INSPECTION PORTS.

7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED

SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED

BELOW THE SECURITY STC CEILING/FLOOR AND

CEILING/ROOF ASSEMBLIES.

8. SEE ENLARGED FLOOR PLANS FOR FIRE ALARM DEVICE

LOCATIONS.

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C E

R V

A N

T E

S S

T R

E E

T

P E

N S

A C

O L

A F

L O

R

ID

A

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

A

2 3 4 5

B

C

D

W

R

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y

E G

L

IN

A F

B F

L O

R

ID

A

FA101

O V

E R

A L

L F

IR

S

T F

L O

O R

F

IR

E A

L A

R M

P L

A N

K

K E

L L

Y

K

K E

L L

Y J

J

O H

N

F E

I

M

A Y

M E

F

F

A

FTFA 16-3007

SCALE: 1/16" = 1'-0"

0 8' 16' 32'

PLAN

NORTH

1/16" = 1'-0"FA101

1 OVERALL FIRST FLOOR FIRE ALARM PLAN

FIRST FLOOR

Room

Number Room Name

100 LOBBY

101 BREAKROOM

102 CORR.

103 ELEV.

104 JANITOR

105 ELEC.

106 MEN

106A SHOWER

107 WOMENS

107A SHOWER

108 ELEVATOR EQUIPMENT

109 SERVICE ELEVATOR

110 LOGISTICS/CE REP

110A RECYCLE ROOM

111 COMSEC

112 VESTIBULE

113 STAIR 2

114 NCR SERVER ROOM

115 SECURE STORAGE

116 SECURE CORRIDOR

117 CORR.

118 TEST SUITE

119 NCR SECURITY MGRS

120 RANGE OPS CENTER

121 TEST SUITE

122 TEST SUITE

123 TEST SUITE

124 TEST SUITE

125 TEST SUITE

126 TEST SUITE

127 NCR CONFERENCE ROOM

128 ACR GSSO

129 ACR STORAGE

130A CORR.

130B ACR ISSO

132 ACR ISSM

133 ACR SYSADM

134 CORRIDOR

135 ACR CONF. RM

136 AVIONICS TEST LAB

137 ATL STORAGE

138 ATL ANALYSIS

139 CYBER/EW LAB

140 C/EW ANALYSIS

141 COMM RM

142 CORR.

143 STAIR 1

144A POWER VESTIBULE

MANTRAP

144B DEV & RE LAB

144C THREAT DEVELOPMENT LAB

145 REPORT WRITING 1

146 REPORT WRITING 2

147 THREAT RESEARCH ROOM

148 ACR SERVER

149 COLLATERAL SECURITY

150 COLLATERAL SECURITY

LEAD

151 BADGE

152 COMM RM

153 MECH.

154 FIRE PUMP

FIRST FLOOR: 60

1 Room

Level 1: 1

L O

C U

S S

D U

S S

D

USSD

FIRE ALARM NOTES

1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION

SYSTEM NOTES AND DETAILS.

2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE

SELF-AMPLIFYING TYPE.

3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE

AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL

SECURE AREA NOTES.

4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS

SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE

RATING AS APPLICABLE.

5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE

AREA PERIMETER WALLS SHALL BE PROVIDED WITH

DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE

DETAIL 1/FA501.

6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO

PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL

TO ACCESS DUCTWORK INSPECTION PORTS.

7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED

SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED

BELOW THE SECURITY STC CEILING/FLOOR AND

CEILING/ROOF ASSEMBLIES.

MANUAL PULL STATION

FIRE ALARM AND MASS NOTIFICATION SPEAKER

(CEILING-MOUNTED)

FIRE ALARM AND MASS NOTIFICATION

CONTROL UNIT

MONITOR MODULE

PHOTOELECTRIC SMOKE DETECTOR

INDICATES WEATHERPROOFWP

DUCT SMOKE DETECTOR

LOCAL OPERATOR CONSOLE (RECESSED

OR SURFACE MOUNTED AS INDICATED)

W/REMOTE MICROPHONE AND HVAC

SHUTDOWN SWITCH

WATERFLOW SWITCH

TAMPER SWITCH

RELAY MODULE

LOC

MM

FACU

R

FIRE ALARM LEGEND

P

FSA

FIRE ALARM REMOTE ANNUNCIATION

PANEL (RECESSED)

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS XX

XX

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS

(CEILING-MOUNTED)

XX

FIRE ALARM AND MASS NOTIFICATION STROBE

WITH CLEAR LENS

(CEILING-MOUNTED)

XMIT MONACO TRANSCEIVER

CANDELA RATINGXX

AREA BELOW ACCESS FLOOR PROTECTED

WITH ULTRA SENSITIVE SMOKE DETECTION

USSD ULTRA SENSITIVE SMOKE DETECTION PANEL

FIRE ALARM AND MASS NOTIFICATION SPEAKER

TEXT SCROLLING LCD TEXT SIGNS

MECHANICAL YARD

ACR GSSO

128 ACR STORAGE

ACR ISSO

130B

ACR ISSM

ACR SYSADM

ACR CONF. RM

CORRIDOR

AVIONICS TEST

LAB

COMM RM

CYBER/EW LAB

STAIR 1

FIRE PUMP

THREAT

DEVELOPMENT

LAB

144C

REPORT WRITING

REPORT WRITING

THREAT

RESEARCH ROOM

ACR SERVER

C/EW ANALYSIS

ATL STORAGE

CORR.

A B C.2C D D.4 E F G

2.8

1.6

R

CRAC UNIT

SHUT DOWN RELAYS

R

R

CRAC UNIT

SHUT DOWN RELAYS

R

P

P

P

P

MM

MM

MM

MONITOR ANECHOIC CHAMBER

CLEAN AGENT FIRE

SUPPRESSION SYSTEM FOR

ALARM, SUPERVISORY,

AND TROUBLE CONDITIONS.

CLEAN AGENT SYSTEM IS BUILT-

IN/PROVIDED BY THE ANECHOIC

CHAMBER MANUFACTURER.

EXACT LOCATION OF MONITOR

MODULES IS TO BE

DETERMINED IN THE FIELD

MM MM

MM MM

MM

MONITOR ULTRA SENSITIVE SMOKE

DETECTION PANEL FOR MOST, SECOND,

AND LEAST SENSITIVE ALARM,

SUPERVISORY, AND TROUBLE CONDITIONS

MM

MM

MM

MM

MM

MM

MM

MM

MM

MM

MONITOR ULTRA SENSITIVE SMOKE

DETECTION PANEL FOR MOST, SECOND,

AND LEAST SENSITIVE ALARM,

SUPERVISORY, AND TROUBLE CONDITIONS

MM

MM

MONITOR SPRINKLER

WATERFLOW SWITCH

AND TAMPER SWITCH

75 75

15 15

30 30

MONITOR ULTRA SENSITIVE SMOKE

DETECTION PANEL FOR MOST, SECOND,

AND LEAST SENSITIVE ALARM,

SUPERVISORY, AND TROUBLE CONDITIONS

MM

MM

MM

FIRE PUMP RUNNING,

LOSS OF POWER,

AND PHASE REVERSAL

WP

WP

ATL ANALYSIS

DEV & RE LAB

144B

MM

MM

MM

MM

MM

MM

FIRE PROTECTION CONTROL

VALVES. SEE SHEET FX401

FOR VALVE LOCATIONS

TEXT

T E

X T

T E

X T

R R

R

SURFACE MOUNTED

M A

T C

H

LI

N E

1/ F

A

1/ F

A

M A

T C

H

LI

N E

1/ F

A

1/ F

A

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C E

R V

A N

T E

S S

T R

E E

T

P E

N S

A C

O L

A F

L O

R

ID

A

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

A

2 3 4 5

B

C

D

W

R

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y

E G

L

IN

A F

B F

L O

R

ID

A

FA102

P A

R T

IA

L

F

IR

S T

F L

O O

R F

IR

E

A L

A R

M P

L A

N

W E

S T

K

K E

L L

Y

K

K E

L L

Y J

J

O H

N

F E

I

M

A Y

M E

F

F

A

FTFA 16-3007

SCALE: 1/8" = 1'-0"

0 4' 8' 16'

PLAN

NORTH

1/8" = 1'-0"FA102

1 PARTIAL FIRST FLOOR FIRE ALARM PLAN - WEST

X M

IT

F

A C

U

F S

A

LOC

L O

C

USSD

FIRE ALARM NOTES

1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION

SYSTEM NOTES AND DETAILS.

2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE

SELF-AMPLIFYING TYPE.

3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE

AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL

SECURE AREA NOTES.

4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS

SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE

RATING AS APPLICABLE.

5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE

AREA PERIMETER WALLS SHALL BE PROVIDED WITH

DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE

DETAIL 1/FA501.

6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO

PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL

TO ACCESS DUCTWORK INSPECTION PORTS.

7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED

SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED

BELOW THE SECURITY STC CEILING/FLOOR AND

CEILING/ROOF ASSEMBLIES.

MANUAL PULL STATION

FIRE ALARM AND MASS NOTIFICATION SPEAKER

(CEILING-MOUNTED)

FIRE ALARM AND MASS NOTIFICATION

CONTROL UNIT

MONITOR MODULE

PHOTOELECTRIC SMOKE DETECTOR

INDICATES WEATHERPROOFWP

DUCT SMOKE DETECTOR

LOCAL OPERATOR CONSOLE (RECESSED

OR SURFACE MOUNTED AS INDICATED)

W/REMOTE MICROPHONE AND HVAC

SHUTDOWN SWITCH

WATERFLOW SWITCH

TAMPER SWITCH

RELAY MODULE

LOC

MM

FACU

R

FIRE ALARM LEGEND

P

FSA

FIRE ALARM REMOTE ANNUNCIATION

PANEL (RECESSED)

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS XX

XX

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS

(CEILING-MOUNTED)

XX

FIRE ALARM AND MASS NOTIFICATION STROBE

WITH CLEAR LENS

(CEILING-MOUNTED)

XMIT MONACO TRANSCEIVER

CANDELA RATINGXX

AREA BELOW ACCESS FLOOR PROTECTED

WITH ULTRA SENSITIVE SMOKE DETECTION

USSD ULTRA SENSITIVE SMOKE DETECTION PANEL

FIRE ALARM AND MASS NOTIFICATION SPEAKER

TEXT SCROLLING LCD TEXT SIGNS

MECHANICAL YARD

LOBBY

BREAKROOM

CORR.

ELEV.

JANITOR

ELEC.

MEN

WOMENS

LOGISTICS/CE

REP

SERVICE

ELEVATOR

COMSEC

VESTIBULE

STAIR 2

NCR SERVER

ROOM

RANGE OPS

CENTER

TEST SUITE

TEST SUITE

TEST SUITE

TEST SUITE

SECURE

CORRIDOR

TEST SUITE

NCR SECURITY

MGRS

NCR

CONFERENCE

ROOM

MECH.

COLLATERAL

SECURITY LEAD

COMM RM

COLLATERAL

SECURITY

BADGE

ELEVATOR

EQUIPMENT

RECYCLE

ROOM

110A

SECURE

STORAGE

TEST SUITE

TEST SUITE

CORR.

F G H J K M N P

2.8

1.6

R

CRAC UNIT

SHUTDOWN RELAYS

R

R

P

PPPPP

P

MM MM

MM MM

MM

MONITOR ULTRA SENSITIVE SMOKE

DETECTION PANEL FOR MOST, SECOND,

AND LEAST SENSITIVE ALARM,

SUPERVISORY, AND TROUBLE CONDITIONS

15 30

15 75

WP WP

15 15

WP WP WP WP

WP

SMOKE DETECTOR MOUNTED ON

WALL ABOVE ELEVATOR DOOR

WITHIN 5 FEET OF ELEVATOR DOOR

R

AHU-1 SHUTDOWN

AHU-1 SUPPLY

MM

MM

MM

MM

ELEVATOR MACHINE

ROOM SPRINKLER

WATERFLOW AND

TAMPER SWITCH

ELEVATOR PIT

SPRINKLER TAMPER SWITCH

ELEVATOR PIT

SPRINKLER TAMPER SWITCH

TEXT

T E

X T

TEXT

SURFACE MOUNTED

RECESSED

M A

T C

H

LI

N E

1/ F

A

1/ F

A

M A

T C

H

LI

N E

1/ F

A

1/ F

A

R

R

R

R

MM R

R

R

R

MM

RELAYS PROVIDED FOR ELEVATOR

PRIMARY RECALL, SECONDARY RECALL,

SHUNT TRIP, AND FIRE FIGHTER HAT

FLASHING AND STEADY. MONITOR

MODULE PROVIDED FOR

SHUNT TRIP POWER MONITOR

R R

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C E

R V

A N

T E

S S

T R

E E

T

P E

N S

A C

O L

A F

L O

R

ID

A

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

A

2 3 4 5

B

C

D

W

R

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y

E G

L

IN

A F

B F

L O

R

ID

A

FA103

P A

R T

IA

L

F

IR

S T

F L

O O

R F

IR

E

A L

A R

M P

L A

N

E A

S T

K

K E

L L

Y

K

K E

L L

Y J

J

O H

N

F E

I

M

A Y

M E

F

F

A

FTFA 16-3007

SCALE: 1/8" = 1'-0"

0 4' 8' 16'

PLAN

NORTH

1/8" = 1'-0"FA103

1 PARTIAL FIRST FLOOR FIRE ALARM PLAN - EAST

205 209

208204

220 219

237236235

239 240

241 242

243 210

231 230 229 228 227 226

224A

A B C.2C D D.4 E F G H J K M N P

2.8

1.6

221A

MANUAL PULL STATION

FIRE ALARM AND MASS NOTIFICATION SPEAKER

(CEILING-MOUNTED)

FIRE ALARM AND MASS NOTIFICATION

CONTROL UNIT

MONITOR MODULE

PHOTOELECTRIC SMOKE DETECTOR

INDICATES WEATHERPROOFWP

DUCT SMOKE DETECTOR

LOCAL OPERATOR CONSOLE (RECESSED

OR SURFACE MOUNTED AS INDICATED)

W/REMOTE MICROPHONE AND HVAC

SHUTDOWN SWITCH

WATERFLOW SWITCH

TAMPER SWITCH

RELAY MODULE

LOC

MM

FACU

R

FIRE ALARM LEGEND

P

FSA

FIRE ALARM REMOTE ANNUNCIATION

PANEL (RECESSED)

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS XX

XX

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS

(CEILING-MOUNTED)

XX

FIRE ALARM AND MASS NOTIFICATION STROBE

WITH CLEAR LENS

(CEILING-MOUNTED)

XMIT MONACO TRANSCEIVER

CANDELA RATINGXX

AREA BELOW ACCESS FLOOR PROTECTED

WITH ULTRA SENSITIVE SMOKE DETECTION

USSD ULTRA SENSITIVE SMOKE DETECTION PANEL

FIRE ALARM AND MASS NOTIFICATION SPEAKER

TEXT SCROLLING LCD TEXT SIGNS

FIRE ALARM NOTES

1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION

SYSTEM NOTES AND DETAILS.

2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE

SELF-AMPLIFYING TYPE.

3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE

AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL

SECURE AREA NOTES.

4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS

SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE

RATING AS APPLICABLE.

5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE

AREA PERIMETER WALLS SHALL BE PROVIDED WITH

DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE

DETAIL 1/FA501.

6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO

PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL

TO ACCESS DUCTWORK INSPECTION PORTS.

7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED

SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED

BELOW THE SECURITY STC CEILING/FLOOR AND

CEILING/ROOF ASSEMBLIES.

8. SEE ENLARGED FLOOR PLANS FOR FIRE ALARM DEVICE

LOCATIONS.

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C E

R V

A N

T E

S S

T R

E E

T

P E

N S

A C

O L

A F

L O

R

ID

A

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

A

2 3 4 5

B

C

D

W

R

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y

E G

L

IN

A F

B F

L O

R

ID

A

FA104

O V

E R

A L

L S

E C

O N

D F

L O

O R

F

IR

E A

L A

R M

P L

A N

K

K E

L L

Y

K

K E

L L

Y J

J

O H

N

F E

I

M

A Y

M E

F

F

A

FTFA 16-3007

SCALE: 1/16" = 1'-0"

0 8' 16' 32'

PLAN

NORTH

1/16" = 1'-0"FA104

1 OVERALL SECOND FLOOR FIRE ALARM PLAN

SECOND FLOOR

Room

Number Room Name

200 CORR.

201 VESTIBULE

202 IDE SERVER RM

203 EVENT DESIGN

COLLABORATION

204 EVENT DESIGN

COLLABORATION

205 ELEV.

206 ELECTRICAL

207 BREAKROOM

208 47 CTS CONFERENCE

209 SERVICE ELEVATOR

210 ITS WORKSTATIONS/WORK

BENCH/TRAINING

211 ITS STORAGE

212 ITS MISSION PREP

213 STAIRS

214 96 CTG. SEC. COMM.

215 WORK AREA

216 OFFICE

217 OFFICE

218 TEST TOOL/EQUIP. STAGING

219 MEN

220 WOMEN

220A LACTATION RM

221 GROUP CLASSROOM

221A STORAGE

222 INVESTMENT GROUP

223 INVESTMENT LEAD

224 WORK AREA

224A OFFICE

225 WORK AREA

226 OFFICE

227 OFFICE

228 OFFICE

229 OFFICE

230 OFFICE

231 OFFICE

232 CORR.

233 STAIRS

234 COMM RM

235 IDE OFFICE

236 IDE OFFICE

237 IDE OFFICE

238 IDE OFFICE

239 MECH.

240 COMM RM

241 JANITOR

242 STOR.

243 EVENT DESIGN CENTER

SECOND FLOOR: 47

L

C

FIRE ALARM NOTES

1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION

SYSTEM NOTES AND DETAILS.

2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE

SELF-AMPLIFYING TYPE.

3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE

AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL

SECURE AREA NOTES.

4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS

SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE

RATING AS APPLICABLE.

5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE

AREA PERIMETER WALLS SHALL BE PROVIDED WITH

DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE

DETAIL 1/FA501.

6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO

PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL

TO ACCESS DUCTWORK INSPECTION PORTS.

7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED

SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED

BELOW THE SECURITY STC CEILING/FLOOR AND

CEILING/ROOF ASSEMBLIES.

MANUAL PULL STATION

FIRE ALARM AND MASS NOTIFICATION SPEAKER

(CEILING-MOUNTED)

FIRE ALARM AND MASS NOTIFICATION

CONTROL UNIT

MONITOR MODULE

PHOTOELECTRIC SMOKE DETECTOR

INDICATES WEATHERPROOFWP

DUCT SMOKE DETECTOR

LOCAL OPERATOR CONSOLE (RECESSED

OR SURFACE MOUNTED AS INDICATED)

W/REMOTE MICROPHONE AND HVAC

SHUTDOWN SWITCH

WATERFLOW SWITCH

TAMPER SWITCH

RELAY MODULE

LOC

MM

FACU

R

FIRE ALARM LEGEND

P

FSA

FIRE ALARM REMOTE ANNUNCIATION

PANEL (RECESSED)

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS XX

XX

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS

(CEILING-MOUNTED)

XX

FIRE ALARM AND MASS NOTIFICATION STROBE

WITH CLEAR LENS

(CEILING-MOUNTED)

XMIT MONACO TRANSCEIVER

CANDELA RATINGXX

AREA BELOW ACCESS FLOOR PROTECTED

WITH ULTRA SENSITIVE SMOKE DETECTION

USSD ULTRA SENSITIVE SMOKE DETECTION PANEL

FIRE ALARM AND MASS NOTIFICATION SPEAKER

TEXT SCROLLING LCD TEXT SIGNS

STAIRS

COMM RM

234 MECH.

EVENT DESIGN

CENTER

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

WORK AREA

225 WORK AREA

INVESTMENT

GROUP

INVESTMENT

LEAD

CORR.

OFFICE

224A

A B C.2C D D.4 E F G

2.8

1.6

CORR.

P

MM

MM

MONITOR SPRINKLER

WATERFLOW SWITCH

AND TAMPER SWITCH

15 15 15

30 30 30

30 30 30

30 30 30

30 30

30 30

R

AHU-2 SHUTDOWN

AHU-2 SUPPLY

TEXT

SURFACE MOUNTED

M A

T C

H

LI

N E

1/ F

A

1/ F

A

M A

T C

H

LI

N E

1/ F

A

1/ F

A

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C E

R V

A N

T E

S S

T R

E E

T

P E

N S

A C

O L

A F

L O

R

ID

A

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

A

2 3 4 5

B

C

D

W

R

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y

E G

L

IN

A F

B F

L O

R

ID

A

FA105

P A

R T

IA

L

S E

C O

N D

F L

O O

R F

IR

E

A L

A R

M P

L A

N

W E

S T

K

K E

L L

Y

K

K E

L L

Y J

J

O H

N

F E

I

M

A Y

M E

F

F

A

FTFA 16-3007

SCALE: 1/8" = 1'-0"

0 4' 8' 16'

PLAN

NORTH

1/8" = 1'-0"FA105

1 PARTIAL SECOND FLOOR FIRE ALARM PLAN - WEST

LOC

USSD

FIRE ALARM NOTES

1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION

SYSTEM NOTES AND DETAILS.

2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE

SELF-AMPLIFYING TYPE.

3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE

AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL

SECURE AREA NOTES.

4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS

SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE

RATING AS APPLICABLE.

5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE

AREA PERIMETER WALLS SHALL BE PROVIDED WITH

DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE

DETAIL 1/FA501.

6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO

PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL

TO ACCESS DUCTWORK INSPECTION PORTS.

7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED

SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED

BELOW THE SECURITY STC CEILING/FLOOR AND

CEILING/ROOF ASSEMBLIES.

MANUAL PULL STATION

FIRE ALARM AND MASS NOTIFICATION SPEAKER

(CEILING-MOUNTED)

FIRE ALARM AND MASS NOTIFICATION

CONTROL UNIT

MONITOR MODULE

PHOTOELECTRIC SMOKE DETECTOR

INDICATES WEATHERPROOFWP

DUCT SMOKE DETECTOR

LOCAL OPERATOR CONSOLE (RECESSED

OR SURFACE MOUNTED AS INDICATED)

W/REMOTE MICROPHONE AND HVAC

SHUTDOWN SWITCH

WATERFLOW SWITCH

TAMPER SWITCH

RELAY MODULE

LOC

MM

FACU

R

FIRE ALARM LEGEND

P

FSA

FIRE ALARM REMOTE ANNUNCIATION

PANEL (RECESSED)

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS XX

XX

FIRE ALARM AND MASS NOTIFICATION SPEAKER /

STROBE WITH CLEAR LENS

(CEILING-MOUNTED)

XX

FIRE ALARM AND MASS NOTIFICATION STROBE

WITH CLEAR LENS

(CEILING-MOUNTED)

XMIT MONACO TRANSCEIVER

CANDELA RATINGXX

AREA BELOW ACCESS FLOOR PROTECTED

WITH ULTRA SENSITIVE SMOKE DETECTION

USSD ULTRA SENSITIVE SMOKE DETECTION PANEL

FIRE ALARM AND MASS NOTIFICATION SPEAKER

TEXT SCROLLING LCD TEXT SIGNS

STAIRS

ELEV.

SERVICE

ELEVATOR

ITS STORAGE

EVENT DESIGN

COLLABORATION

ELECTRICAL

IDE SERVER RM

47 CTS

CONFERENCE

EVENT DESIGN

COLLABORATION

BREAKROOM

OFFICE

96 CTG. SEC.

COMM.

TEST

TOOL/EQUIP.

STAGING

WORK AREA

WOMEN

MEN

IDE OFFICE

IDE OFFICE

IDE OFFICE

IDE OFFICE

GROUP

CLASSROOM

COMM RM

JANITOR

STOR.

ITS MISSION

PREP

CORR.

ITS

WORKSTATIONS/WORK

BENCH/TRAINING

INVESTMENT

GROUP

OFFICE

VESTIBULE

F G H J K M N P

2.8

1.6

R

R

CRAC UNIT

SHUTDOWN RELAYS

CRAC UNIT

SHUTDOWN RELAY

P

STORAGE

221A

MM

MM

MM

MM

MM

MONITOR ULTRA SENSITIVE SMOKE

DETECTION PANEL FOR MOST, SECOND,

AND LEAST SENSITIVE ALARM,

SUPERVISORY, AND TROUBLE CONDITIONS

15 15 15

30 30 30

15 15

15 15

30 30

T E

X T

R

RECESSED

M A

T C

H

LI

N E

1/ F

A

1/ F

A

M A

T C

H

LI

N E

1/ F

A

1/ F

A

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C E

R V

A N

T E

S S

T R

E E

T

P E

N S

A C

O L

A F

L O

R

ID

A

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

A

2 3 4 5

B

C

D

W

R

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y

E G

L

IN

A F

B F

L O

R

ID

A

FA106

P A

R T

IA

L

S E

C O

N D

F L

O O

R F

IR

E

A L

A R

M P

L A

N

E A

S T

K

K E

L L

Y

K

K E

L L

Y J

J

O H

N

F E

I

M

A Y

M E

F

F

A

FTFA 16-3007

SCALE: 1/8" = 1'-0"

0 4' 8' 16'

PLAN

NORTH

1/8" = 1'-0"FA106

1 PARTIAL SECOND FLOOR FIRE ALARM PLAN - EAST

" 5

T

MANUAL PULL

STATION

FACU

SPEAKER/STROBE

WALL-MOUNTED

SPEAKER

FSA

LOC

WALL-MOUNTED

SMOKE DETECTOR

AT SERVICE ELEVATOR

FACU

SPEAKER/

STROBES

SPEAKER/

STROBES SPEAKERS

MANUAL PULL

STATIONS

15 30 30

STROBES

MM

SPRINKLER

WATERFLOW

MM

CONTROL

VALVE

TO

VAC

SMOKE

DETECTORS

TO 120 VAC

PANEL / CIRCUIT

P P

XMIT

15 75

SPEAKER/

STROBES

SPEAKER/

STROBE

SPD

SPD

EXTERIOR

SPEAKERS

WP WP

LOCLOC

STROBE

R

AHU

SUPPLY

AHU

SHUTDOWN

MM MM

MM

FIRE PUMP

RUNNING

MM

FIRE PUMP

LOSS OF

POWER

MM

FIRE PUMP

PHASE

REVERSAL

MMMM

MMMM

MM

USSD

MMMM

MMMM

MM

USSD

ULTRA SENSITIVE

SMOKE DETECTION

MM

ANECHOIC

CHAMBER CLEAN

AGENT ALARM

MM

ANECHOIC

CHAMBER CLEAN

AGENT

SUPERVISORY

MM

ANECHOIC

CHAMBER CLEAN

AGENT TROUBLE

15 75

SPEAKER/

STROBES

WPWP

R R

ELEVATOR

PRIMARY

RECALL

R R

ELEVATOR

SECONDARY

RECALL

R R

ELEVATOR

SHUNT TRIP

R R

FIRE FIGHTER

HAT FLASHING

R

ELEVATOR

SHUNT TRIP

POWER

MMMM

R R

CRAC UNIT

SHUTDOWN

R

FIRE FIGHTER

HAT STEADY

R

FIRE ALARM NOTES

1. PROVIDE AN ADDRESSABLE FIRE ALARM AND VOICE EVACUATION SYSTEM IN

ACCORDANCE WITH NFPA 72, NFPA 101, UFC 3-600-01, UFC 4-021-01, THE

SPECIFICATION AND THE SCOPE OF WORK DOCUMENTS. THE FIRE ALARM

SYSTEM SHALL BE COMPATIBLE WITH THE MASS NOTIFICATION SYSTEM

RECEIVER AND BE ABLE TO RELAY OUTPUTS FROM THE RECEIVER OVER THE

VOICE EVACUATION SYSTEM TO THE SPEAKERS. MASS NOTIFICATION

SIGNALS SHALL TAKE PRECEDENCE OVER FIRE ALARM SIGNALS.

2. THE FIRE ALARM SYSTEM SHALL MONITOR ALL SPRINKLER SYSTEM ALARM,

SUPERVISORY AND TROUBLE CONDITIONS.

3. AIR HANDLING UNITS OVER 2000 CFM SHALL HAVE DUCT SMOKE DETECTORS

INSTALLED ON THE SUPPLY DUCTS.

4. ALL SOFTWARE, HARDWARE, PASSWORDS, ETC. REQUIRED FOR THE

MAINTENANCE, TESTING, AND REPROGRAMMING OF THE FIRE ALARM SYSTEM

SHALL BE UNCONDITIONALLY TURNED OVER TO THE GOVERNMENT, AND THE

ABOVE NOTED SOFTWARE, HARDWARE, PASSWORDS, ETC. WILL BECOME THE

UNCONDITIONAL PROPERTY OF THE GOVERNMENT. SOFTWARE TURNED

OVER TO THE GOVERNMENT SHALL BE ORIGINAL SOFTWARE ON COMPACT

DISK (CD) WITH JEWELED CASE. COPIES OF SOFTWARE SHALL NOT BE

ACCEPTABLE. SOFTWARE AND CD SHALL BE BRAND NEW AND UNUSED.

PROVIDE AN 8-HOUR BLOCK OF TRAINING ON THE SOFTWARE, REGARDING

MAINTENANCE, TESTING, AND REPROGRAMMING OF THE FIRE ALARM SYSTEM

FOR 6 PERSONNEL. TRAINING SHALL BE PROVIDED ON SITE AT EGLIN AFB, FL.

5. THE FIRE ALARM SYSTEM SHALL REPORT ALL CONDITIONS TO THE BASE-WIDE

REPORTING SYSTEM AS NECESSARY. THE CONTRACTOR SHALL COORDINATE

WITH THE BASE TO ENSURE THE SYSTEM IS COMPATIBLE WITH THE BASE

WIDE (MONACO BT-XF) SYSTEM AND THE PROPER TRANSMITTING EQUIPMENT

IS PROVIDED. THE TRANSCEIVER SHALL BE PROVIDED AND INSTALLED BY

THE CONTRACTOR AS PART OF THE COMPLETE FIRE ALARM SYSTEM.

6. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE SELF-

AMPLIFYING TYPE.

7. THE FIRE ALARM AND MNS LAYOUT IS DIAGRAMMATICAL ONLY. THE ACTUAL

BUILDING LAYOUT MAY VARY FROM THE DRAWINGS. THE CONTRACTOR

SHALL VERIFY CEILING HEIGHTS, WALL AND PARTITION LOCATIONS AND DOOR

LOCATIONS PRIOR TO INSTALLATION.

8. ALL INTERIOR AND EXTERIOR WALLS, CEILINGS AND FLOORS THAT ARE

DAMAGED OR ALTERED BY THE CONTRACTOR SHALL BE RESTORED TO

ORIGINAL CONDITION AND TO THE SATISFACTION OF THE CONTRACTING

OFFICER.

9. ALL FIRE ALARM AND MNS CONDUCTORS SHALL BE SOLID COPPER AND SHALL

BE INSTALLED IN CONDUIT. ALL CONDUIT SHALL BE FACTORY PAINTED RED.

10. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE AREA PERIMETER

WALLS SHALL BE PROVIDED WITH DIELECTRIC UNIONS ON BOTH SIDES OF

THE WALLS. SEE ARCHITECTURAL DRAWINGS FOR SECURE WALL

LOCATIONS.

INSIDE

SECURE AREA

OUTSIDE

SECURE AREA

CONDUITCONDUIT

SECURITY WALL ASSEMBLY

DIELECTRIC UNION

NOTE: WHEN THE SECURE

WALL IS AN INTERNAL

COMPARTMENTED WALL

BOTH SIDES WILL BE WITHIN

SECURE AREA

DIELECTRIC UNION

CONDUIT

NOTE: PENETRATIONS THROUGH

FIRE RATED SECURITY WALLS

SHALL BE PROVIDED WITH A

UL-CLASSIFIED THROUGH-

PENETRATION FIRESTOP ASSEMBLY

SCALE: NONEFA501

2 FIRE ALARM ELEVATION (TYPICAL)

SCALE: NONEFA501

3 RISER DIAGRAM

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C E

R V

A N

T E

S S

T R

E E

T

P E

N S

A C

O L

A F

L O

R

ID

A

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

A

2 3 4 5

B

C

D

W

R

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y

E G

L

IN

A F

B F

L O

R

ID

A

FA501

D E

T A

IL

S

F

IR

E

A L

A R

M

K

K E

L L

Y

K

K E

L L

Y J

J

O H

N

F E

I

M

A Y

M E

F

F

A

FTFA 16-3007

SCALE: NONEFA501

1 DIELECTRIC UNION DETAIL

FIRE ALARM SYSTEM SEQUENCE OF OPERATION MATRIX

MANUAL PULL STATION

ALARM AT

FACU & FSA

SUPERVISORY

AT FACU &

FSA

TROUBLE AT

FACU & FSA

ALARM AT

RECEIVING

STATION

TROUBLE

AT

RECEIVING

STATION

SUPERVISORY

AT RECEIVING

STATION

ACTIVATE

SPEAKERS,

STROBES

& FIRE

ALARM

MESSAGE

SILENCE

SPEAKERS

& STROBES

SHUTDOWN

AHU / ERV

SMOKE DETECTOR

WATERFLOW SWITCH

INPUT RECEIVED FROM

MASS NOTIFICATION

SYSTEM (MNS)

TAMPER SWITCH

FIRE ALARM TROUBLE

CONDITION (OPENS,

SHORTS OR GROUNDS)

ALARM SILENCE AT

FACU OR FSA

DUCT SMOKE DETECTOR

MNS PANEL TROUBLE

OVERRIDE FA

MESSAGE

OVERRIDE PA

SYSTEM

MNS SYSTEM

TROUBLE AT

RECEIVING

STATION

*SEE SPECIFICATION SECTION 28 31 76, PARAGRAPH 2.20.2 FOR SPECIFIC SIGNALS REQUIRED TO BE TRANSMITTED TO THE RECEIVING STATION

ULTRA-SENSITIVE SMOKE

DETECTOR MOST

SENSITIVE ALARM

ULTRA-SENSITIVE SMOKE

DETECTOR SECOND

LEVEL ALARM

ULTRA-SENSITIVE SMOKE

DETECTOR LEAST

SENSITIVE ALARM

ULTRA-SENSITIVE SMOKE

DETECTOR SUPERVISORY

CONDITION

ULTRA-SENSITIVE SMOKE

DETECTOR TROUBLE

CONDITION

NOTE

ALARM LEVEL 1 DEFAULT

SETTING SHALL BE 0.025%

OBSCURATION PER FOOT

ALARM LEVEL 2 DEFAULT

SETTING SHALL BE 0.044%

OBSCURATION PER FOOT

ALARM LEVEL 3 DEFAULT

SETTING SHALL BE 0.062%

OBSCURATION PER FOOT

FIRE PUMP RUNNING

FIRE PUMP LOSS OF

POWER

FIRE PUMP PHASE

REVERSAL

ANECHOIC CHAMBER

CLEAN AGENT ALARM

ANECHOIC CHAMBER

CLEAN AGENT

SUPERVISORY

ANECHOIC CHAMBER

CLEAN AGENT TROUBLE

INITIATE

ELEVATOR

PRIMARY

RECALL

INITIATE

ELEVATOR

SECONDARY

RECALL

INITIATE

ELEVATOR

SHUNT TRIP

ACTIVATE

SPEAKERS,

STROBES

& MNS

MESSAGE

ELEVATOR MACHINE ROOM

WATERFLOW SWITCH

ACTIVATE

FLASHING

FIRE

FIGHTER'S

HAT

ELEVATOR MACHINE

ROOM SMOKE DETECTOR

ELEVATOR 1ST FLOOR

LOBBY SMOKE DETECTOR

ELEVATOR 2ND FLOOR

LOBBY SMOKE DETECTOR

SHUTDOWN

CRAC

UNITS

ACTIVATE

STEADY

FIRE

FIGHTER'S

HAT

CLEAN AGENT

DISCHARGE

ALARM AT

RECEIVING

STATION

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C E

R V

A N

T E

S S

T R

E E

T

P E

N S

A C

O L

A F

L O

R

ID

A

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

A

2 3 4 5

B

C

D

W

R

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y

E G

L

IN

A F

B F

L O

R

ID

A

FA502

F

IR

E A

L A

R M

S E

Q U

E N

C E

O F

O P

E R

A T

IO

N

K

K E

L L

Y

K

K E

L L

Y J

J

O H

N

F E

I

M

A Y

M E

F

F

A

FTFA 16-3007

SCALE: NONEFA502

1 SEQUENCE OF OPERATION MATRIX

100 101

103 104

109 111

120121

128 129

130B

144C

145 146 147 148

108 110A

SPRINKLER RISER

INCOMING WATER

SUPPLY

VERTICAL INLINE FIRE PUMP

RATED FOR 500 GPM AT

40 PSI TO BE PROVIDED

A B C.2C D D.4 E F G H J K M N P

2.8

1.6

144B

144A

SEE SHEET FX401 FOR

ENLARGED FLOOR PLAN

FIRE PROTECTION NOTES

1. SEE SHEET FX501 FOR FIRE PROTECTION NOTES AND DETAILS.

2. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE AREA

BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL SECURE AREA

CONSTRUCTION NOTES.

3. ALL PENETRATIONS THROUGH SECURITY WALLS SHALL BE SEALED TO

MAINTAIN STC RATING AND FIRE RATING AS APPLICABLE.

4. ALL METALLIC PIPE PENETRATIONS THROUGH SECURE AREA PERIMETER

WALLS SHALL BE PROPERLY GROUNDED. SEE DETAIL 2/FX501.

5. PIPING SHALL BE INSTALLED IN LOCATIONS SO AS TO PROVIDE SUFFICIENT

CLEARANCE FOR SECURITY PERSONEL TO ACCESS DUCTWORK

INSPECTION PORTS.

6. PIPING SHALL NOT BE INSTALLED WITHIN DESIGNATED SECURITY WALL

ASSEMBLIES AND SHALL BE INSTALLED BELOW THE SECURITY STC

CEILING/FLOOR AND CEILING/ROOF ASSEMBLIES.

7. LIGHT GAGE STEEL FRAMING OF THE SECURITY STC CEILING/FLOOR AND

CEILING/ROOF ASSEMBLIES SHALL NOT BE UTILIZED TO SUPPORT PIPE OR

PIPE SUPPORT ASSEMBLIES. ALL PIPE AND SUPPORT SHALL BE

SUPPORTED FROM THE BUILDING STRUCTURE.

LIGHT HAZARD

0.10 GPM/SF OVER HYDRAULICALLY

MOST REMOTE 1,500 SF

WATER MOTOR GONG

ORDINARY HAZARD

0.20 GPM/SF OVER HYDRAULICALLY

MOST REMOTE 2,500 SF

FIRE PROTECTION LEGEND

TEST HEADER

FIRE DEPARTMENT CONNECTION

SHEET

IDENTIFICATION

US Army Corps of

Engineers ®

Mobile District

U .S

A

R M

Y C

O R

P S

O F

E N

G

IN

E E

R S

D E

S

IG

N E

D B

Y

B U

L L

O C

K T

IC

E

A S

S O

C

IA

T E

S

E

C E

R V

A N

T E

S S

T R

E E

T

P E

N S

A C

O L

A F

L O

R

ID

A

D R

A W

N B

Y

S B

M T

B Y

P L

O T

S C

A L

E

S

IZ

E

C K

D B

Y

P L

O T

D A

T E

D A

T E

S O

L

IC

IT

A

T

IO

N N

O

C O

N T

R A

C T

N O

P R

O J E

C T

N U

M B

E R

F

IL

E N

A M

E

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E A

P P

R

:1 x

M O

B

IL

E D

IS

T

R

IC

T

M O

B

IL

E A

L A

B A

M A

M E

F

M

A Y

A

2 3 4 5

B

C

D

W

R

C Y

B E

R S

P A

C E

T E

S T

G R

O U

P F

A C

IL

IT

Y

E G

L

IN

A F

B F

L O

R

ID

A

FX101

O V

E R

A L

L F

IR

S

T F

L O

O R

F

IR

E P

R O

T E

C T

IO

N

P L

A N

K

K E

L L

Y

K

K E

L L

Y J

J

O H

N

F E

I

M

A Y

M E

F

F X

FTFA 16-3007

SCALE: 1/16" = 1'-0"

0 8' 16' 32'

PLAN

NORTH

1/16" = 1'-0"FX101

1 OVERALL FIRST FLOOR FIRE PROTECTION PLAN

FIRST FLOOR

Room

Number Room Name

100 LOBBY

101 BREAKROOM

102 CORR.

103 ELEV.

104 JANITOR

105 ELEC.

106 MEN

106A SHOWER

107 WOMENS

107A SHOWER

108 ELEVATOR EQUIPMENT

109 SERVICE ELEVATOR

110 LOGISTICS/CE REP

110A RECYCLE ROOM

111 COMSEC

112 VESTIBULE

113 STAIR 2

114 NCR SERVER ROOM

115 SECURE STORAGE

116 SECURE CORRIDOR

117 CORR.

118 TEST SUITE

119 NCR SECURITY MGRS

120 RANGE OPS CENTER

121 TEST SUITE

122 TEST SUITE

123 TEST SUITE

124 TEST SUITE

125 TEST SUITE

126 TEST SUITE

127 NCR CONFERENCE ROOM

128 ACR GSSO

129 ACR STORAGE

130A CORR.

130B ACR ISSO

132 ACR ISSM

133 ACR SYSADM

134 CORRIDOR

135 ACR CONF. RM

136 AVIONICS TEST LAB

137 ATL STORAGE

138 ATL ANALYSIS

139 CYBER/EW LAB

140 C/EW ANALYSIS

141 COMM RM

142 CORR.

143 STAIR 1

144A POWER VESTIBULE

MANTRAP

144B DEV & RE LAB

144C THREAT DEVELOPMENT LAB

145 REPORT WRITING 1

146 REPORT WRITING 2

147 THREAT RESEARCH ROOM

148 ACR SERVER

149 COLLATERAL SECURITY

150 COLLATERAL SECURITY

LEAD

151 BADGE

152 COMM RM

153 MECH.

154 FIRE PUMP

FIRST FLOOR: 60

1 Room

Level 1: 1

ACR GSSO

ACR STORAGE

ACR ISSO

130B

ACR ISSM

ACR SYSADM

ACR CONF. RM

CORRIDOR

AVIONICS TEST

LAB

COMM RM

CYBER/EW LAB

STAIR 1

FIRE PUMP

THREAT

DEVELOPMENT

LAB

144C

REPORT WRITING

REPORT WRITING

THREAT

RESEARCH ROOM

ACR SERVER

C/EW ANALYSIS

ATL STORAGE

CORR.

INCOMING WATER

SUPPLY

VERTICAL INLINE FIRE PUMP

RATED FOR 500 GPM AT

40 PSI TO BE PROVIDED

SPRINKLER RISER

A B C.2C D D.4 E F G

2.8

1.6

FX401

DEV & RE LAB

144B

POWER

VESTIBULE

MANTRAP

144A

FLOOR CONTROL

ASSEMBLY CONSISTING OF

OS&Y CONTROL VALVE, CHECK

VALVE, AND WATERFLOW SWITCH

ATL ANALYSIS

SEE SHEET FX401 FOR

ENLARGED FLOOR PLAN

USER PROVIDED ANECHOIC

CHAMBER CLEAN AGENT SYSTEM

M A

T C

H L

IN

E

/F

X

/F

X

M A

T C

H L

IN

E

/F

X

/F

X

FIRE PROTECTION NOTES

1. SEE SHEET FX501 FOR FIRE PROTECTION NOTES AND DETAILS.

2. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE AREA

BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL SECURE AREA

CONSTRUCTION NOTES.

3. ALL PENETRATIONS THROUGH SECURITY WALLS SHALL BE SEALED TO

MAINTAIN STC RATING AND FIRE RATING AS APPLICABLE.

4. ALL METALLIC PIPE PENETRATIONS THROUGH SECURE AREA PERIMETER

WALLS SHALL BE PROPERLY GROUNDED. SEE DETAIL 2/FX501.

5. PIPING SHALL BE INSTALLED IN LOCATIONS SO AS TO PROVIDE SUFFICIENT

CLEARANCE FOR SECURITY PERSONEL TO ACCESS DUCTWORK

INSPECTION PORTS.

6. PIPING SHALL NOT BE INSTALLED WITHIN DESIGNATED SECURITY WALL

ASSEMBLIES AND SHALL BE INSTALLED BELOW THE SECURITY STC

CEILING/FLOOR AND CEILING/ROOF ASSEMBLIES.

7. LIGHT GAGE STEEL FRAMING OF THE SECURITY STC CEILING/FLOOR AND

CEILING/ROOF ASSEMBLIES SHALL NOT BE UTILIZED TO SUPPORT PIPE OR

PIPE SUPPORT ASSEMBLIES. ALL PIPE AND SUPPORT SHALL BE

SUPPORTED FROM THE BUILDING STRUCTURE.

LIGHT HAZARD

0.10 GPM/SF OVER HYDRAULICALLY

MOST REMOTE 1,500 SF

WATER MOTOR GONG

ORDINARY HAZARD

0.20 GPM/SF OVER HYDRAULICALLY

MOST REMOTE 2,500…