RTA DRAWINGS VOL2 .pdf
PDF 39 MB Posted
- Attached to
- Cyberspace Test Group Facility, Eglin AFB, FL Federal contract opportunity
- Solicitation number
- W9127820R0057
About this file
This document provides details for a federal contract solicitation to construct a new Cyberspace Test Group Facility at Eglin Air Force Base in Florida. The solicitation is for a multistory, 52,003 square foot sensitive compartmented information facility with a concrete foundation, split-faced concrete block construction over a steel frame, and a sloped standing seam metal roof. The facility will include fire suppression systems, all required utilities, pavements, communications infrastructure, site improvements, and support facilities to provide a complete and usable facility for the Cyberspace Test Group mission. The solicitation was issued by the Department of the Army Corps of Engineers Engineering District Mobile. The anticipated award date is not specified. Interested contractors are advised to review the full solicitation document available as attachment W9127820R0057 for detailed technical requirements, response instructions and deadlines, and other terms relevant to preparing a proposal for this construction project.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W9127820R0057 JA_Redacted.pdf | ||
| AM05 DRAWINGS.pdf | ||
| AM05.pdf | ||
| AM04.pdf | ||
| AM03 DRAWINGS.pdf | ||
| AM03.pdf | ||
| AM02 DRAWINGS.pdf | ||
| AM02.pdf | ||
| AM01 DRAWINGS.pdf | ||
| AM01.pdf | ||
| Site visit sign in sheet.pdf | ||
| VOL3.PDF | ||
| VOL1.PDF | ||
| VOL6.PDF | ||
| VOL4.PDF | ||
| RTA DRAWINGS VOL1.pdf | ||
| VOL5.PDF | ||
| VOL2.PDF | ||
| EM 385-1-1.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Army Corps of Engineers
MOBILE DISTRICT
109 SAINT JOSEPH STREET
MOBILE AL 36602
CYBERSPACE TEST GROUP FACILITY
EGLIN AIR FORCE BASE, FLORIDA
OKALOOSA COUNTY
JUNE 2020
MOBILE DISTRICT PROJECT CODE: MEF19017
RFP NUMBER: W9127820R0057
VOLUME 2 OF 2
A
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C
E R
V A
N T
E S
S T
R E
E T
P E
N S
A C
O L
A F
L O
R
ID
A
2 3 4 5
B
C
D
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
W
R
5/
/2
9:
:4
A
M
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y E
G L
IN
A
F B
, F L
O R
ID
A
G-002
IN
D
E X
O F
D R
A W
IN
G
S
B
M A
G G
IO
R
E
T
W A
L L
IS
B
M
A G
G
IO
R E
B T
A
M
A Y
M E
F
G
FTFA 16-3007
INDEX OF DRAWINGS - VOLUME 1 OF 2
SHEET
NUMBER SHEET NAME
A-602 SECOND FLOOR DOOR SCHEDULE
A-603 EXTERIOR DOOR DETAILS
A-604 INTERIOR DOOR DETAILS
A-610 CURTAINWALL, INTERIOR WINDOW, AND LOUVER ELEVATIONS
A-611 CURTAINWALL DETAILS
A-612 INTERIOR WINDOW DETAILS AND CABLE PASS THRU DETAIL
A-613 LOUVER DETAILS
A-700 ANTENNA PLATFORM DETAILS
INTERIOR
I-101 PARTIAL FIRST FLOOR FINISH PLAN - WEST
I-102 PARTIAL FIRST FLOOR FINISH PLAN - EAST
I-103 PARTIAL SECOND FLOOR FINISH PLAN - WEST
I-104 PARTIAL SECOND FLOOR FINISH PLAN - EAST
I-105 PARTIAL FIRST FLOOR MCT PATTERN PLAN - WEST
I-106 PARTIAL FIRST FLOOR MCT PATTERN PLAN - EAST
I-107 PARTIAL SECOND FLOOR MCT PATTERN PLAN - WEST
I-108 PARTIAL SECOND FLOOR MCT PATTERN PLAN - EAST
I-109 PARTIAL FIRST FLOOR FURNITURE PLAN - WEST
I-110 PARTIAL FIRST FLOOR FURNITURE PLAN - EAST
I-111 PARTIAL SECOND FLOOR FURNITURE PLAN - WEST
I-112 PARTIAL SECOND FLOOR FURNITURE PLAN - EAST
I-113 PARTIAL FIRST FLOOR SIGNAGE AND CORNER GUARD PLAN - WEST
I-114 PARTIAL FIRST FLOOR SIGNAGE AND CORNER GUARD PLAN - EAST
I-115 PARTIAL SECOND FLOOR SIGNAGE AND CORNER GUARD PLAN - WEST
I-116 PARTIAL SECOND FLOOR SIGNAGE AND CORNER GUARD PLAN - EAST
I-140 WORKSTATION GROUP TYPICALS
I-141 WORKSTATION GROUP TYPICALS
I-142 WORKSTATION GROUP TYPICALS
I-143 WORKSTATION GROUP TYPICALS
I-201 INTERIOR ELEVATIONS
I-202 INTERIOR ELEVATIONS
I-203 FFE ELEVATIONS
I-601 FIRST FLOOR ROOM FINISH SCHEDULE
I-602 SECOND FLOOR ROOM FINISH SCHEDULE
I-603 SIGNAGE SCHEDULE
I-604 SIGNAGE DETAILS
INDEX OF DRAWINGS - VOLUME 1 OF 2
SHEET
NUMBER SHEET NAME
S-306 SECTIONS AND DETAILS
S-307 SECTIONS AND DETAILS
S-401 FOUNDATION SECTIONS AND DETAILS
S-402 FOUNDATION SECTIONS AND DETAILS
S-403 FOUNDATION SECTIONS AND DETAILS
S-404 FOUNDATION SECTIONS AND DETAILS
S-501 TYPICAL MASONRY DETAILS
S-502 TYPICAL STEEL DETAILS
S-503 TYPICAL BASE PLATE, FOUNDATION AND SLAB DETAILS
S-504 TYPICAL ELEVATED FLOOR DETAILS
ARCHITECTURAL
A-001 LEGEND, NOTES AND ABBREVIATIONS
A-002 EXTERIOR WALL TYPES
A-003 INTERIOR WALL TYPES
A-004 INTERIOR WALL TYPES
A-005 INTERIOR WALL TYPES
A-101 OVERALL FIRST FLOOR PLAN
A-102 ENLARGED FIRST FLOOR PLAN WEST
A-103 ENLARGED FIRST FLOOR PLAN EAST
A-104 FIRST FLOOR OVERALL DIMENSION PLAN
A-105 PARTIAL FIRST FLOOR DIMENSION PLAN - WEST
A-106 PARTIAL FIRST FLOOR DIMENSION PLAN - EAST
A-107 OVERALL SECOND FLOOR PLAN
A-108 PARTIAL SECOND FLOOR PLAN - WEST
A-109 PARTIAL SECOND FLOOR PLAN - EAST
A-110 SECOND FLOOR OVERALL DIMENSION PLAN
A-111 PARTIAL SECOND FLOOR DIMENSION PLAN - WEST
A-112 PARTIAL SECOND FLOOR DIMENSION PLAN - EAST
A-140 ROOF PLAN
A-141 ROOF DETAILS
A-142 ROOF DETAILS
A-143 ROOF DETAILS
A-144 ROOF DETAILS
A-145 CANOPY DETAILS
A-150 OVERALL FIRST FLOOR REFLECTED CEILING PLAN
A-151 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - WEST
A-152 PARTIAL FIRST FLOOR REFLECTED CEILING PLAN - EAST
A-153 OVERALL SECOND FLOOR REFLECTED CEILING PLAN
A-154 PARTIAL SECOND FLOOR REFLECTED CEILING PLAN - WEST
A-155 PARTIAL SECOND FLOOR REFLECTED CEILING PLAN - EAST
A-156 FIRST FLOOR SECURITY/ STC 50 GYPSUM WALLBOARD REFLECTED CEILING
PLAN
A-157 SECOND FLOOR SECURITY/STC 50 GYPSUM WALLBOARD REFLECTED
CEILING PLAN
A-201 BUILDING ELEVATIONS
A-202 ENLARGED ELEVATIONS
A-203 BUILDING ELEVATIONS
A-301 BUILDING SECTIONS
A-302 BUILDING SECTIONS
A-303 TROLLEY HOIST SECTION @ AVIONICA LAB
A-310 WALL SECTIONS
A-311 WALL SECTIONS
A-312 WALL SECTIONS
A-313 WALL SECTIONS
A-314 TYPICAL SECURITY/STC ASSEMBLY SEALING DETAILS
A-410 ENLARGED PLANS - RESTROOMS
A-411 ENLARGED PLANS - STAIRS
A-412 ENLARGED STAIR SECTIONS
A-413 ENLARGED STAIRS SECTION
A-414 STAIR DETAILS AND SECTIONS
A-415 PASSENGER ELEVATOR PLANS AND SECTIONS
A-416 SERVICE ELEVATOR PLANS AND SECTION
A-417 EQUIPMENT ENCLOSURE PLANS AND SECTIONS
A-418 ENLARGED LOADING DOCK PLAN
A-450 CASEWORK ELEVATIONS
A-451 CASEWORK SECTIONS
A-501 EXTERIOR & INTERIOR PLAN DETAILS
A-502 INTERIOR PLAN DETAILS
A-510 SLAB/ACCESS FLOOR DETAILS @ FIRST FLOOR
A-511 SLAB/ACCESS FLOOR DETAILS @ SECOND FLOOR
A-520 SECURITY/STC CEILING DETAILS
A-521 CEILING DETAILS
A-522 SECURITY/STC CEILING DETAILS @ ROOF
A-601 FIRST FLOOR DOOR SCHEDULE AND DOOR AND FRAME ELEVATIONS
INDEX OF DRAWINGS - VOLUME 1 OF 2
SHEET
NUMBER SHEET NAME
CS127 ENLARGED EXISTING MANHOLE 2B1
CS501 PAVING DETAILS
CS502 CIVIL AND PAVING DETAILS
CS503 CIVIL DETAILS
CS504 CIVIL DETAILS
CS505 FENCE DETAILS
CS506 GATE DETAILS
CL101 GEOMETRIC LAYOUT PLAN - BUILDING NORTH
CL102 GEOMETRIC LAYOUT PLAN - BUILDING SOUTH
CL103 GEOMETRIC LAYOUT PLAN - EAST
CL104 GEOMETRIC LAYOUT PLAN - PARKING LOT NORTH
CL105 GEOMETRIC LAYOUT PLAN - PARKING LOT SOUTH
CL601 HORIZONTAL CONTROL TABLES
CG101 BUILDING GRADING PLAN - NORTH
CG102 BUILDING GRADING PLAN - SOUTH
CG103 EAST GRADING PLAN
CG104 PARKING LOT GRADING PLAN - NORTH
CG105 PARKING LOT GRADING PLAN - SOUTH
CG201 FACILITY PROFILES
CG202 BUILDING DRAINAGE PROFILES
CG203 SWMF PROFILES
CG211 PARKING LOT DRAINAGE PROFILES
CG212 PARKING LOT DRAINAGE PROFILES
CG213 PARKING LOT DRAINAGE PROFILES
CG214 PARKING LOT DRAINAGE PROFILES
CG501 DRAINAGE DETAILS
CG502 DRAINAGE DETAILS
CG601 STORM DRAIN STRUCTURE TABLE
CG602 STORM DRAIN PIPE TABLE
CE100 OVERALL EROSION AND SEDIMENT CONTROL PLAN
CE101 EROSION AND SEDIMENT CONTROL PLAN - NORTH
CE102 EROSION AND SEDIMENT CONTROL PLAN - SOUTH
CE501 EROSION CONTROL DETAILS
CE502 STORWATER POLLUTION PREVENTION PLAN
CU101 BUILDING UTILITY PLAN - NORTH
CU102 BUILDING UTILITY PLAN - SOUTH
CU103 ENLARGED UTILITY PLAN
CU201 SANITARY SERVICE PROFILES
CU501 UTILITY DETAILS
CATHODIC PROTECTION
X-101 CATHODIC LAYOUT
X-102 CATHODIC PROTECTION DETAILS
X-103 CATHODIC PROTECTION DETAILS
LANDSCAPE
L-100 LANDSCAPE PLAN
L-101 LANDSCAPE PLAN
L-102 LANDSCAPE PLAN
L-103 LANDSCAPE PLAN
L-104 LANDSCAPE DETAILS
STRUCTURAL
S-001 GENERAL NOTES
S-002 GENERAL NOTES CONTINUED AND WIND LOAD DIAGRAM
S-101 FOUNDATION AND SLAB-ON-GRADE PLAN - WEST
S-102 FOUNDATION AND SLAB-ON-GRADE PLAN - EAST
S-103 SECOND FLOOR FRAMING PLAN - WEST
S-104 SECOND FLOOR FRAMING PLAN - EAST
S-105 ROOF FRAMING PLAN - WEST
S-106 ROOF FRAMING PLAN - EAST
S-107 ANTENNA PLATFORM FRAMING PLAN
S-201 FRAMING ELEVATIONS
S-202 FRAMING ELEVATIONS
S-203 FRAMING ELEVATIONS
S-204 BRACED FRAME DETAILS
S-205 TRUSS ELEVATIONS
S-206 TRUSS BRACING ELEVATIONS
S-207 TYPICAL TRUSS CONNECTION DETAILS
S-208 TYPICAL TRUSS CONNECTION DETAILS
S-301 SECTIONS AND DETAILS
S-302 SECTIONS AND DETAILS
S-303 SECTIONS AND DETAILS
S-304 SECTIONS AND DETAILS
S-305 SECTIONS AND DETAILS
INDEX OF DRAWINGS - VOLUME 1 OF 2
SHEET
NUMBER SHEET NAME
GENERAL
G-001 TITLE SHEET
G-002 INDEX OF DRAWINGS
G-003 INDEX OF DRAWINGS
GC003 SITE LOCATION, ACCESS AND SAFETY PLAN
GC004 SITE USE AND WORK RESTRICTION PLAN
GC005 SITE WORK PHASING PLAN
G-004 SECURITY AND STC CONSTRUCTION NOTES
G-005 CODE SUMMARY
G-101 OVERALL FIRST FLOOR LIFE SAFETY PLAN
G-102 PARTIAL FIRST FLOOR LIFE SAFETY PLAN - WEST
G-103 PARTIAL FIRST FLOOR LIFE SAFETY PLAN - EAST
G-104 OVERALL SECOND FLOOR LIFE SAFETY PLAN
G-105 PARTIAL SECOND FLOOR LIFE SAFETY PLAN - WEST
G-106 PARTIAL SECOND FLOOR LIFE SAFETY PLAN - EAST
G-107 FIRST FLOOR SECURITY PLAN - WEST
G-108 FIRST FLOOR SECURITY PLAN - EAST
G-109 SECOND FLOOR SECURITY PLAN - WEST
G-110 SECOND FLOOR SECURITY PLAN - EAST
G-111 FIRST FLOOR AIR BARRIER PLAN
G-112 SECOND FLOOR AIR BARRIER PLAN
G-113 AIR BARRIER BUILDING SECTIONS
G-114 AIR BARRIER BUILDING SECTIONS
G-115 AIR BARRIER BUILDING SECTIONS
CIVIL
V-100 SURVEY NOTES AND LEGEND AND LEVEL A SURVEY VACUUM EXTRACTION
SITES DATA TABLE
V-101 SURVEY NOTES AND LEGEND AND LEVEL A SURVEY VACUUM EXTRACTION
SITES DATA TABLE
V-102 SURVEY NOTES AND LEGEND AND LEVEL A SURVEY VACUUM EXTRACTION
SITES DATA TABLE
V-103 SURVEY AREA KEY SHEET
V-104 SURVEY NOTES AND LEGEND AND LEVEL A SURVEY VACUUM EXTRACTION
SITES DATA TABLE
V-105 SURVEY AND SURVEY CONTROL PLAN
V-106 SURVEY AND SURVEY CONTROL PLAN
V-107 SURVEY AND SURVEY CONTROL PLAN
V-108 SURVEY AND SURVEY CONTROL PLAN
V-109 SURVEY AND SURVEY CONTROL PLAN
V-110 SURVEY AND SURVEY CONTROL PLAN
V-111 SURVEY AND SURVEY CONTROL PLAN
V-112 SURVEY AND SURVEY CONTROL PLAN
V-113 SURVEY AND SURVEY CONTROL PLAN
V-114 SURVEY AND SURVEY CONTROL PLAN
V-115 SURVEY AND SURVEY CONTROL PLAN
V-116 SURVEY AND SURVEY CONTROL PLAN
V-117 SURVEY AND SURVEY CONTROL PLAN
V-118 SURVEY AND SURVEY CONTROL PLAN
CI001 GENERAL CIVIL NOTES
CI002 ABBREVIATIONS AND LEGEND
CD101 OVERALL DEMOLITION PLAN
CD102 BUILDING DEMOLITION PLAN NORTH
CD103 BUILDING DEMOLITION PLAN SOUTH
CD104 PARKING DEMOLITION PLAN NORTH
CD105 PARKING DEMOLITION PLAN SOUTH
CS100 KEY MAP
CS101 BUILDING SITE PLAN - NORTH
CS102 BUILDING SITE PLAN - SOUTH
CS103 EAST SITE PLAN
CS104 PARKING LOT SITE PLAN - NORTH
CS105 PARKING LOT SITE PLAN - SOUTH
CS110 JOINT LAYOUT OVERALL KEY MAP
CS111 JOINT LAYOUT PLAN A
CS112 JOINT LAYOUT PLAN B
CS113 JOINT LAYOUT PLAN C
CS114 JOINT LAYOUT PLAN D
CS115 JOINT LAYOUT PLAN SOUTHEAST PARKING
CS120 REMOTE SITE KEY SHEET
CS121 ENLARGED PLAN EXISTING MANHOLE 73 AREA
CS122 ENLARGED EXISTING MANHOLE 7C AREA
CS123 ENLARGED EXISTING MANHOLE 8C AND NEW MANHOLE 2E-1 AREA
CS124 ENLARGED EXISTING MANHOLE 2E AREA
CS125 ENLARGED EXISTING MANHOLES 17, 18, AND 19
CS126 ENLARGED EXISTING MANHOLE 2B2
INDEX OF DRAWINGS THIS SHEET
INCLUDE VOLUME 1 DRAWINGS
A
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C
E R
V A
N T
E S
S T
R E
E T
P E
N S
A C
O L
A F
L O
R
ID
A
2 3 4 5
B
C
D
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
W
R
/2
/2
:4
:0
A
M
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B
F L
O R
ID
A
G-003
IN
D
E X
O F
D R
A W
IN
G
S
B
M A
G G
IO
R
E
T
W A
L L
IS
B
M
A G
G
IO
R E
B T
A
M
A Y
M E
F
G
FTFA 16-3007
INDEX OF DRAWINGS - VOLUME 2 OF 2
SHEET
NUMBER SHEET NAME
T-014 ENLARGED EXISTING MANHOLE 2B2
T-015 ENLARGED EXISTING MANHOLE 2B1
T-016 ENLARGED NEW MAINTENANCE HOLE 72 AND EX MH 73
T-017 ENLARGED NEW MAINTENANCE HOLE 71
T-018 ENLARGED BUILDING 90 MAINTENANCE HOLES
T-019 NON-CORE SERVICES COMMUNICATIONS SITE PLAN - BID OPTION 3
T-020 TELECOM SITE DETAILS
T-021 TELECOM SITE DETAILS
T-111 OVERALL FIRST FLOOR CONDUIT PATHWAY PLAN
T-112 OVERALL FIRST FLOOR OVERHEAD/ABOVE CEILING PATHWAY PLAN
T-113 OVERALL FIRST FLOOR BELOW FLOOR PATHWAY PLAN
T-114 OVERALL FIRST FLOOR CABLING DISTRIBUTION PLAN
T-115 ENLARGED FIRST FLOOR PLAN WEST
T-116 ENLARGED FIRST FLOOR PLAN EAST
T-121 OVERALL SECOND FLOOR CONDUIT PATHWAY PLAN
T-122 OVERALL SECOND FLOOR OVERHEAD/ ABOVE CEILING PATHWAY PLAN
T-123 OVERALL SECOND FLOOR BELOW FLOOR PATHWAY PLAN
T-124 OVERALL SECOND FLOOR CABLING DISTRIBUTION PLAN
T-125 ENLARGED SECOND FLOOR PLAN WEST
T-126 ENLARGED SECOND FLOOR PLAN EAST
T-201 TELECOM GROUNDING DETAILS
T-202 TELECOM OUTLET DETAILS
T-203 TELECOM OUTLET DETAILS
T-204 TELECOM DETAILS
T-205 TELECOM DETAILS
T-206 PROTECTIVE DISTRIBTION SYSTEM (PDS) DETAILS
T-207 PROTECTIVE DISTRIBTION SYSTEM (PDS) DETAILS
T-208 TELECOM MOUNTING DETAILS
T-301 CORE BACKBONE SINGLE LINE DIAGRAMS
T-302 NON-CORE BACKBONE AND UNCLASS SINGLE LINE DIAGRAMS
T-303 CLASS SIPR & NON CORE SINGLE LINE DIAGRAMS
T-304 NON-CORE SINGLE LINE DIAGRAMS
T-305 NON-CORE AND UNCLASS SINGLE LINE DIAGRAMS
T-306 LAB CLOSED NETWORKS SINGLE LINE DIAGAMS
T-307 OTHER, COMMERCIAL, AND LAB CLOSED NETWORK SINGLE LINE DIAGRAMS
T-308 CATV AND PA SINGLE LINE DIAGRAMS
T-401 TELECOM ENLARGED SERVER ROOM 114
T-402 TELECOM ENLARGED STORAGE ROOM 129
T-403 TELECOM ENLARGED ATL ANALYSIS ROOM 138
T-404 TELECOM ENLARGED C/EW ANALYSIS ROOM 140
T-405 TELECOM ENLARGED COMM ROOM 141 & AC SERVER ROOM 148
T-406 TELECOM ENLARGED COMM ROOM 152
T-407 TELECOM ENLARGED IDE SERVER ROOM 202
T-408 TELECOM ENLARGED 96 CTG. SEC. COMM ROOM 214
T-409 TELECOM ENLARGED COMM ROOM 234 & 240
T-501 TELECOM RACK ELEVATIONS- SERVER ROOM 114 & STORAGE ROOM 129
T-502 TELECOM RACK ELEVATIONS - ATL ANALYSIS ROOM 138
T-503 TELECOM RACK ELEVATIONS - C/EW ANALYSIS ROOM 140
T-504 TELECOM RACK ELEVATIONS - COMM. ROOM 141 & ACR SERVER ROOM 148
T-505 TELECOM RACK ELEVATIONS - COMM ROOM 152
T-506 TELECOM RACK ELEVATIONS - IDE SERVER ROOM 202
T-507 TELECOM RACK ELEVATIONS - ITS STORAGE ROOM 211 & 96 CTG. SEC, COMM ROOM 214
T-508 TELECOM RACK ELEVATIONS - COMM ROOM 234
T-509 TELECOM RACK ELEVATIONS - COMM. ROOM 240
TA001 AUDIO VISUAL LEGEND
TA111 AUDIO VISUAL FIRST FLOOR PLAN WEST
TA112 AUDIO VISUAL FIRST FLOOR PLAN EAST
TA121 AUDIO VISUAL SECOND FLOOR PLAN WEST
TA122 AUDIO VISUAL SECOND FLOOR PLAN EAST
TA201 AUDIO VISUAL DETAILS
TA301 AUDIO VISUAL DIAGRAMS
TY001 SECURITY LEGEND & NOTES
TY111 SECURITY FIRST FLOOR PLAN WEST
TY112 SECURITY FIRST FLOOR PLAN EAST
TY121 SECURITY SECOND FLOOR PLAN WEST
TY122 SECURITY SECOND FLOOR PLAN EAST
TY201 SECURITY DETAILS
TY202 SECURITY DOOR DETAILS
TY203 SECURITY DOOR DETAILS
TY204 SECURITY DOOR DETAILS
TY205 SECURITY DOOR DETAILS
TY301 SECURITY SINGLE LINE DIAGRAMS
TY302 SECURITY SINGLE LINE DIAGRAMS
INDEX OF DRAWINGS - VOLUME 2 OF 2
SHEET
NUMBER SHEET NAME
E-100 DEMO ELECTRICAL SITE PLAN
E-101 NEW WORK ELECTRICAL SITE PLAN
E-102 NEW WORK ELECTRICAL SITE LIGHTING PLAN
E-103 SITE LIGHTING DETAILS - BID OPTION 11
E-111 OVERALL FIRST FLOOR POWER PLAN & PATHWAYS
E-112 FIRST FLOOR POWER PLAN - WEST
E-113 FIRST FLOOR GROUNDING PLAN - WEST
E-114 FIRST FLOOR POWER PLAN - EAST
E-115 FIRST FLOOR GROUNDING PLAN - EAST
E-116 OVERALL SECOND FLOOR POWER PLAN
E-117 SECOND FLOOR POWER PLAN - WEST
E-118 SECOND FLOOR GROUNDING PLAN - WEST
E-119 SECOND FLOOR POWER PLAN - EAST
E-120 SECOND FLOOR GROUNDING PLAN - EAST
E-211 OVERALL FIRST FLOOR LIGHTING PLAN
E-212 FIRST FLOOR LIGHTING PLAN - WEST
E-213 FIRST FLOOR LIGHTING PLAN - EAST
E-214 OVERALL SECOND FLOOR LIGHTING PLAN
E-215 SECOND FLOOR LIGHTING PLAN - WEST
E-216 SECOND FLOOR LIGHTING PLAN - EAST
E-311 OVERALL FIRST FLOOR MECHANICAL POWER PLAN
E-312 FIRST FLOOR MECHANICAL POWER PLAN - WEST
E-313 FIRST FLOOR MECHANICAL POWER PLAN - EAST
E-314 OVERALL SECOND FLOOR MECHANICAL POWER PLAN
E-315 SECOND FLOOR MECHANICAL POWER PLAN - WEST
E-316 SECOND FLOOR MECHANICAL POWER PLAN - EAST
E-400 LIGHTNING PROTECTION PLAN
E-401 LIGHTNING PROTECTION DETAILS
E-500 DEV&RE LAB/THREAT DEVELOPMENT LAB ENLARGED 60Hz/00Hz & DC ROOM PLANS
E-501 CYBER/EW ENLARGED ROOM PLAN 60Hz
E-502 CYBER/EW ENLARGED ROOM PLAN 400Hz & DC
E-503 AVIONICS TEST LAB ENLARGED ROOM PLAN 60Hz
E-504 AVIONICS TEST LAB ENLARGED ROOM PLAN - 400Hz & DC
E-600 PANEL SCHEDULE INDEX
E-601 PANEL SCHEDULE
E-602 PANEL SCHEDULE
E-603 PANEL SCHEDULE
E-604 PANEL SCHEDULE
E-605 PANEL SCHEDULE
E-606 PANEL SCHEDULE
E-607 PANEL SCHEDULE
E-608 PANEL SCHEDULE
E-609 PANEL SCHEDULE
E-610 PANEL SCHEDULE
E-611 PANEL SCHEDULE
E-612 PANEL SCHEDULE
E-613 PANEL SCHEDULE
E-614 PANEL SCHEDULE
E-615 PANEL SCHEDULE
E-616 PANEL SCHEDULE
E-617 400Hz PANEL SCHEDULE
E-618 400Hz PANEL SCHEDULE
E-619 400Hz PANEL SCHEDULE
E-620 270VDC PANEL SCHEDULES
E-621 28VDC PANEL SCHEDULES
E-622 28VDC PANEL SCHEDULES
E-623 28VDC PANEL SCHEDULES
E-624 PANEL SCHEDULE
E-625 PANEL SCHEDULE
E-626 BUS DUCT PLUG SCHEDULES
E-627 BUS DUCT PLUG SCHEDULES
TELECOMMUNICATIONS
T-001 TELECOM LEGEND
T-002 GENERAL NOTES
T-003 TELECOM SITE NOTES
T-004 PARTIAL CORE SERVICES COMMUNICATIONS SITE PLAN
T-005 PARTIAL CORE SERVICES COMMUNICATIONS SITE PLAN
T-006 PARTIAL CORE SERVICES COMMUNICATIONS SITE PLAN
T-007 PARTIAL CORE SERVICES COMMUNICATIONS SITE PLAN
T-008 ENLARGED EXISTING MANHOLE 73 AREA
T-009 ENLARGED EXISTING MANHOLE 7C AREA
T-010 ENLARGED EXISTING MANHOLE 8C AND NEW MANHOLE 2E-1 AREA
T-011 ENLARGED EXISTING MANHOLE 2E AREA
T-012 ENLARGED EXISTING MANHOLE 2X AND 3X
T-013 ENLARGED EXISTING MANHOLE 17, 18, & 19
INDEX OF DRAWINGS - VOLUME 2 OF 2
SHEET
NUMBER SHEET NAME
FIRE PROTECTION
FA101 OVERALL FIRST FLOOR FIRE ALARM PLAN
FA102 PARTIAL FIRST FLOOR FIRE ALARM PLAN - WEST
FA103 PARTIAL FIRST FLOOR FIRE ALARM PLAN - EAST
FA104 OVERALL SECOND FLOOR FIRE ALARM PLAN
FA105 PARTIAL SECOND FLOOR FIRE ALARM PLAN - WEST
FA106 PARTIAL SECOND FLOOR FIRE ALARM PLAN - EAST
FA501 DETAILS - FIRE ALARM
FA502 FIRE ALARM SEQUENCE OF OPERATION
FX101 OVERALL FIRST FLOOR FIRE PROTECTION PLAN
FX102 PARTIAL FIRST FLOOR FIRE PROTECTION PLAN - WEST
FX103 PARTIAL FIRST FLOOR FIRE PROTECTION PLAN - EAST
FX104 OVERALL SECOND FLOOR FIRE PROTECTION PLAN
FX105 PARTIAL SECOND FLOOR FIRE PROTECTION PLAN - WEST
FX106 PARTIAL SECOND FLOOR FIRE PROTECTION PLAN - EAST
FX401 ENLARGED FIRE PUMP ROOM
FX501 DETAILS - FIRE PROTECTION
PLUMBING
P-001 PLUMBING LEGENDS, NOTES & ABBREVIATION
P-101 PARTIAL FIRST FLOOR PLAN WEST - PLUMBING BELOW SLAB
P-102 PARTIAL FIRST FLOOR PLAN EAST - PLUMBING BELOW SLAB
P-103 PARTIAL FIRST FLOOR PLAN WEST - PLUMBING ABOVE SLAB
P-104 PARTIAL FIRST FLOOR PLAN EAST - PLUMBING ABOVE SLAB
P-105 PARTIAL SECOND FLOOR PLAN WEST - PLUMBING BELOW SLAB
P-106 PARTIAL SECOND FLOOR PLAN EAST - PLUMBING BELOW SLAB
P-107 PARTIAL SECOND FLOOR PLAN WEST - PLUMBING ABOVE SLAB
P-108 PARTIAL SECOND FLOOR PLAN EAST - PLUMBING ABOVE SLAB
P-401 ENLARGED FIRST FLOOR PLAN - PLUMBING WASTE, VENT AND WATER
P-402 ENLARGED SECOND FLOOR PLAN - PLUMBING WASTE, VENT AND WATER
P-501 PLUMBING DETAILS-1
P-502 PLUMBING DETAILS-2
P-503 PLUMBING DETAILS-3
P-601 PLUMBING SCHEDULES-1
P-901 PLUMBING RISER EAST - WASTE AND VENT
P-902 PLUMBING RISER WEST - WASTE AND VENT
P-903 PLUMBING RISER - COMPRESSED AIR
MECHANICAL
M-001 HVAC LEGENDS, NOTES & ABBREVIATION
M-101 OVERALL FIRST FLOOR PLAN - HVAC
M-102 PARTIAL FIRST FLOOR PLAN - HVAC WEST
M-103 PARTIAL FIRST FLOOR PLAN - HVAC EAST
M-104 OVERALL SECOND FLOOR PLAN - HVAC
M-105 PARTIAL SECOND FLOOR PLAN - HVAC WEST
M-106 PARTIAL SECOND FLOOR PLAN - HVAC EAST
M-107 PARTIAL FIRST FLOOR PLAN - HVAC PIPING WEST
M-108 PARTIAL FIRST FLOOR PLAN - HVAC PIPING EAST
M-109 PARTIAL SECOND FLOOR PLAN - HVAC PIPING WEST
M-110 PARTIAL SECOND FLOOR PLAN - HVAC PIPING EAST
M-401 ENLARGED PLAN - HVAC
M-501 HVAC DETAILS-1
M-502 HVAC DETAILS-2
M-503 HVAC DETAILS-3
M-504 HVAC DETAILS-4
M-601 HVAC SCHEDULES-1
M-602 HVAC SCHEDULES-2
M-603 HVAC SCHEDULES-3
M-701 CHILLED WATER PIPING DIAGRAM - PRIMARY LOOP
M-702 CHILLED WATER PIPING DIAGRAM - SECONDARY LOOP
M-703 HVAC CONTROLS-1
M-704 HVAC CONTROLS-2
M-705 HVAC CONTROLS-3
ELECTRICAL
E-001 LEGEND AND ABBREVIATIONS
E-002 LIGHTING FIXTURE SCHEDULE
E-003 ELECTRICAL PRIMARY RISER
E-004 ELECTRICAL ONE-LINE DIAGRAM (277/480V) - BASE BID
E-005 BID OPTIONS ELECTRICAL ONE-LINE DIAGRAM (227/480V)
E-006 ELECTRICAL ONE-LINE DIAGRAM (120/280V)
E-007 400Hz, 28VDC, ONE LINE DIAGRAMS
E-008 GROUNDING SYSTEM RISER DIAGRAM
E-009 PENETRATION DETAILS
E-010 LIGHTING DETAILS
E-011 LIGHTING DETAILS
INDEX OF DRAWINGS THIS SHEET
INCLUDE VOLUME 2 DRAWINGS
MECHANICAL YARD
109 111
120121
128 129
130B
143 154
144C
145 146 147 148
108 110A
A B C.2C D D.4 E F G H J K M N P
2.8
1.6
144B
144A
MANUAL PULL STATION
FIRE ALARM AND MASS NOTIFICATION SPEAKER
(CEILING-MOUNTED)
FIRE ALARM AND MASS NOTIFICATION
CONTROL UNIT
MONITOR MODULE
PHOTOELECTRIC SMOKE DETECTOR
INDICATES WEATHERPROOFWP
DUCT SMOKE DETECTOR
LOCAL OPERATOR CONSOLE (RECESSED
OR SURFACE MOUNTED AS INDICATED)
W/REMOTE MICROPHONE AND HVAC
SHUTDOWN SWITCH
WATERFLOW SWITCH
TAMPER SWITCH
RELAY MODULE
LOC
MM
FACU
R
FIRE ALARM LEGEND
P
FSA
FIRE ALARM REMOTE ANNUNCIATION
PANEL (RECESSED)
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS XX
XX
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS
(CEILING-MOUNTED)
XX
FIRE ALARM AND MASS NOTIFICATION STROBE
WITH CLEAR LENS
(CEILING-MOUNTED)
XMIT MONACO TRANSCEIVER
CANDELA RATINGXX
AREA BELOW ACCESS FLOOR PROTECTED
WITH ULTRA SENSITIVE SMOKE DETECTION
USSD ULTRA SENSITIVE SMOKE DETECTION PANEL
FIRE ALARM AND MASS NOTIFICATION SPEAKER
TEXT SCROLLING LCD TEXT SIGNS
FIRE ALARM NOTES
1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION
SYSTEM NOTES AND DETAILS.
2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE
SELF-AMPLIFYING TYPE.
3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE
AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL
SECURE AREA NOTES.
4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS
SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE
RATING AS APPLICABLE.
5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE
AREA PERIMETER WALLS SHALL BE PROVIDED WITH
DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE
DETAIL 1/FA501.
6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO
PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL
TO ACCESS DUCTWORK INSPECTION PORTS.
7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED
SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED
BELOW THE SECURITY STC CEILING/FLOOR AND
CEILING/ROOF ASSEMBLIES.
8. SEE ENLARGED FLOOR PLANS FOR FIRE ALARM DEVICE
LOCATIONS.
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FA101
O V
E R
A L
L F
IR
S
T F
L O
O R
F
IR
E A
L A
R M
P L
A N
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F
A
FTFA 16-3007
SCALE: 1/16" = 1'-0"
0 8' 16' 32'
PLAN
NORTH
1/16" = 1'-0"FA101
1 OVERALL FIRST FLOOR FIRE ALARM PLAN
FIRST FLOOR
Room
Number Room Name
100 LOBBY
101 BREAKROOM
102 CORR.
103 ELEV.
104 JANITOR
105 ELEC.
106 MEN
106A SHOWER
107 WOMENS
107A SHOWER
108 ELEVATOR EQUIPMENT
109 SERVICE ELEVATOR
110 LOGISTICS/CE REP
110A RECYCLE ROOM
111 COMSEC
112 VESTIBULE
113 STAIR 2
114 NCR SERVER ROOM
115 SECURE STORAGE
116 SECURE CORRIDOR
117 CORR.
118 TEST SUITE
119 NCR SECURITY MGRS
120 RANGE OPS CENTER
121 TEST SUITE
122 TEST SUITE
123 TEST SUITE
124 TEST SUITE
125 TEST SUITE
126 TEST SUITE
127 NCR CONFERENCE ROOM
128 ACR GSSO
129 ACR STORAGE
130A CORR.
130B ACR ISSO
132 ACR ISSM
133 ACR SYSADM
134 CORRIDOR
135 ACR CONF. RM
136 AVIONICS TEST LAB
137 ATL STORAGE
138 ATL ANALYSIS
139 CYBER/EW LAB
140 C/EW ANALYSIS
141 COMM RM
142 CORR.
143 STAIR 1
144A POWER VESTIBULE
MANTRAP
144B DEV & RE LAB
144C THREAT DEVELOPMENT LAB
145 REPORT WRITING 1
146 REPORT WRITING 2
147 THREAT RESEARCH ROOM
148 ACR SERVER
149 COLLATERAL SECURITY
150 COLLATERAL SECURITY
LEAD
151 BADGE
152 COMM RM
153 MECH.
154 FIRE PUMP
FIRST FLOOR: 60
1 Room
Level 1: 1
L O
C U
S S
D U
S S
D
USSD
FIRE ALARM NOTES
1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION
SYSTEM NOTES AND DETAILS.
2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE
SELF-AMPLIFYING TYPE.
3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE
AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL
SECURE AREA NOTES.
4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS
SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE
RATING AS APPLICABLE.
5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE
AREA PERIMETER WALLS SHALL BE PROVIDED WITH
DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE
DETAIL 1/FA501.
6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO
PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL
TO ACCESS DUCTWORK INSPECTION PORTS.
7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED
SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED
BELOW THE SECURITY STC CEILING/FLOOR AND
CEILING/ROOF ASSEMBLIES.
MANUAL PULL STATION
FIRE ALARM AND MASS NOTIFICATION SPEAKER
(CEILING-MOUNTED)
FIRE ALARM AND MASS NOTIFICATION
CONTROL UNIT
MONITOR MODULE
PHOTOELECTRIC SMOKE DETECTOR
INDICATES WEATHERPROOFWP
DUCT SMOKE DETECTOR
LOCAL OPERATOR CONSOLE (RECESSED
OR SURFACE MOUNTED AS INDICATED)
W/REMOTE MICROPHONE AND HVAC
SHUTDOWN SWITCH
WATERFLOW SWITCH
TAMPER SWITCH
RELAY MODULE
LOC
MM
FACU
R
FIRE ALARM LEGEND
P
FSA
FIRE ALARM REMOTE ANNUNCIATION
PANEL (RECESSED)
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS XX
XX
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS
(CEILING-MOUNTED)
XX
FIRE ALARM AND MASS NOTIFICATION STROBE
WITH CLEAR LENS
(CEILING-MOUNTED)
XMIT MONACO TRANSCEIVER
CANDELA RATINGXX
AREA BELOW ACCESS FLOOR PROTECTED
WITH ULTRA SENSITIVE SMOKE DETECTION
USSD ULTRA SENSITIVE SMOKE DETECTION PANEL
FIRE ALARM AND MASS NOTIFICATION SPEAKER
TEXT SCROLLING LCD TEXT SIGNS
MECHANICAL YARD
ACR GSSO
128 ACR STORAGE
ACR ISSO
130B
ACR ISSM
ACR SYSADM
ACR CONF. RM
CORRIDOR
AVIONICS TEST
LAB
COMM RM
CYBER/EW LAB
STAIR 1
FIRE PUMP
THREAT
DEVELOPMENT
LAB
144C
REPORT WRITING
REPORT WRITING
THREAT
RESEARCH ROOM
ACR SERVER
C/EW ANALYSIS
ATL STORAGE
CORR.
A B C.2C D D.4 E F G
2.8
1.6
R
CRAC UNIT
SHUT DOWN RELAYS
R
R
CRAC UNIT
SHUT DOWN RELAYS
R
P
P
P
P
MM
MM
MM
MONITOR ANECHOIC CHAMBER
CLEAN AGENT FIRE
SUPPRESSION SYSTEM FOR
ALARM, SUPERVISORY,
AND TROUBLE CONDITIONS.
CLEAN AGENT SYSTEM IS BUILT-
IN/PROVIDED BY THE ANECHOIC
CHAMBER MANUFACTURER.
EXACT LOCATION OF MONITOR
MODULES IS TO BE
DETERMINED IN THE FIELD
MM MM
MM MM
MM
MONITOR ULTRA SENSITIVE SMOKE
DETECTION PANEL FOR MOST, SECOND,
AND LEAST SENSITIVE ALARM,
SUPERVISORY, AND TROUBLE CONDITIONS
MM
MM
MM
MM
MM
MM
MM
MM
MM
MM
MONITOR ULTRA SENSITIVE SMOKE
DETECTION PANEL FOR MOST, SECOND,
AND LEAST SENSITIVE ALARM,
SUPERVISORY, AND TROUBLE CONDITIONS
MM
MM
MONITOR SPRINKLER
WATERFLOW SWITCH
AND TAMPER SWITCH
75 75
15 15
30 30
MONITOR ULTRA SENSITIVE SMOKE
DETECTION PANEL FOR MOST, SECOND,
AND LEAST SENSITIVE ALARM,
SUPERVISORY, AND TROUBLE CONDITIONS
MM
MM
MM
FIRE PUMP RUNNING,
LOSS OF POWER,
AND PHASE REVERSAL
WP
WP
ATL ANALYSIS
DEV & RE LAB
144B
MM
MM
MM
MM
MM
MM
FIRE PROTECTION CONTROL
VALVES. SEE SHEET FX401
FOR VALVE LOCATIONS
TEXT
T E
X T
T E
X T
R R
R
SURFACE MOUNTED
M A
T C
H
LI
N E
1/ F
A
1/ F
A
M A
T C
H
LI
N E
1/ F
A
1/ F
A
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FA102
P A
R T
IA
L
F
IR
S T
F L
O O
R F
IR
E
A L
A R
M P
L A
N
W E
S T
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F
A
FTFA 16-3007
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
PLAN
NORTH
1/8" = 1'-0"FA102
1 PARTIAL FIRST FLOOR FIRE ALARM PLAN - WEST
X M
IT
F
A C
U
F S
A
LOC
L O
C
USSD
FIRE ALARM NOTES
1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION
SYSTEM NOTES AND DETAILS.
2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE
SELF-AMPLIFYING TYPE.
3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE
AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL
SECURE AREA NOTES.
4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS
SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE
RATING AS APPLICABLE.
5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE
AREA PERIMETER WALLS SHALL BE PROVIDED WITH
DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE
DETAIL 1/FA501.
6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO
PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL
TO ACCESS DUCTWORK INSPECTION PORTS.
7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED
SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED
BELOW THE SECURITY STC CEILING/FLOOR AND
CEILING/ROOF ASSEMBLIES.
MANUAL PULL STATION
FIRE ALARM AND MASS NOTIFICATION SPEAKER
(CEILING-MOUNTED)
FIRE ALARM AND MASS NOTIFICATION
CONTROL UNIT
MONITOR MODULE
PHOTOELECTRIC SMOKE DETECTOR
INDICATES WEATHERPROOFWP
DUCT SMOKE DETECTOR
LOCAL OPERATOR CONSOLE (RECESSED
OR SURFACE MOUNTED AS INDICATED)
W/REMOTE MICROPHONE AND HVAC
SHUTDOWN SWITCH
WATERFLOW SWITCH
TAMPER SWITCH
RELAY MODULE
LOC
MM
FACU
R
FIRE ALARM LEGEND
P
FSA
FIRE ALARM REMOTE ANNUNCIATION
PANEL (RECESSED)
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS XX
XX
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS
(CEILING-MOUNTED)
XX
FIRE ALARM AND MASS NOTIFICATION STROBE
WITH CLEAR LENS
(CEILING-MOUNTED)
XMIT MONACO TRANSCEIVER
CANDELA RATINGXX
AREA BELOW ACCESS FLOOR PROTECTED
WITH ULTRA SENSITIVE SMOKE DETECTION
USSD ULTRA SENSITIVE SMOKE DETECTION PANEL
FIRE ALARM AND MASS NOTIFICATION SPEAKER
TEXT SCROLLING LCD TEXT SIGNS
MECHANICAL YARD
LOBBY
BREAKROOM
CORR.
ELEV.
JANITOR
ELEC.
MEN
WOMENS
LOGISTICS/CE
REP
SERVICE
ELEVATOR
COMSEC
VESTIBULE
STAIR 2
NCR SERVER
ROOM
RANGE OPS
CENTER
TEST SUITE
TEST SUITE
TEST SUITE
TEST SUITE
SECURE
CORRIDOR
TEST SUITE
NCR SECURITY
MGRS
NCR
CONFERENCE
ROOM
MECH.
COLLATERAL
SECURITY LEAD
COMM RM
COLLATERAL
SECURITY
BADGE
ELEVATOR
EQUIPMENT
RECYCLE
ROOM
110A
SECURE
STORAGE
TEST SUITE
TEST SUITE
CORR.
F G H J K M N P
2.8
1.6
R
CRAC UNIT
SHUTDOWN RELAYS
R
R
P
PPPPP
P
MM MM
MM MM
MM
MONITOR ULTRA SENSITIVE SMOKE
DETECTION PANEL FOR MOST, SECOND,
AND LEAST SENSITIVE ALARM,
SUPERVISORY, AND TROUBLE CONDITIONS
15 30
15 75
WP WP
15 15
WP WP WP WP
WP
SMOKE DETECTOR MOUNTED ON
WALL ABOVE ELEVATOR DOOR
WITHIN 5 FEET OF ELEVATOR DOOR
R
AHU-1 SHUTDOWN
AHU-1 SUPPLY
MM
MM
MM
MM
ELEVATOR MACHINE
ROOM SPRINKLER
WATERFLOW AND
TAMPER SWITCH
ELEVATOR PIT
SPRINKLER TAMPER SWITCH
ELEVATOR PIT
SPRINKLER TAMPER SWITCH
TEXT
T E
X T
TEXT
SURFACE MOUNTED
RECESSED
M A
T C
H
LI
N E
1/ F
A
1/ F
A
M A
T C
H
LI
N E
1/ F
A
1/ F
A
R
R
R
R
MM R
R
R
R
MM
RELAYS PROVIDED FOR ELEVATOR
PRIMARY RECALL, SECONDARY RECALL,
SHUNT TRIP, AND FIRE FIGHTER HAT
FLASHING AND STEADY. MONITOR
MODULE PROVIDED FOR
SHUNT TRIP POWER MONITOR
R R
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FA103
P A
R T
IA
L
F
IR
S T
F L
O O
R F
IR
E
A L
A R
M P
L A
N
E A
S T
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F
A
FTFA 16-3007
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
PLAN
NORTH
1/8" = 1'-0"FA103
1 PARTIAL FIRST FLOOR FIRE ALARM PLAN - EAST
205 209
208204
220 219
237236235
239 240
241 242
243 210
231 230 229 228 227 226
224A
A B C.2C D D.4 E F G H J K M N P
2.8
1.6
221A
MANUAL PULL STATION
FIRE ALARM AND MASS NOTIFICATION SPEAKER
(CEILING-MOUNTED)
FIRE ALARM AND MASS NOTIFICATION
CONTROL UNIT
MONITOR MODULE
PHOTOELECTRIC SMOKE DETECTOR
INDICATES WEATHERPROOFWP
DUCT SMOKE DETECTOR
LOCAL OPERATOR CONSOLE (RECESSED
OR SURFACE MOUNTED AS INDICATED)
W/REMOTE MICROPHONE AND HVAC
SHUTDOWN SWITCH
WATERFLOW SWITCH
TAMPER SWITCH
RELAY MODULE
LOC
MM
FACU
R
FIRE ALARM LEGEND
P
FSA
FIRE ALARM REMOTE ANNUNCIATION
PANEL (RECESSED)
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS XX
XX
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS
(CEILING-MOUNTED)
XX
FIRE ALARM AND MASS NOTIFICATION STROBE
WITH CLEAR LENS
(CEILING-MOUNTED)
XMIT MONACO TRANSCEIVER
CANDELA RATINGXX
AREA BELOW ACCESS FLOOR PROTECTED
WITH ULTRA SENSITIVE SMOKE DETECTION
USSD ULTRA SENSITIVE SMOKE DETECTION PANEL
FIRE ALARM AND MASS NOTIFICATION SPEAKER
TEXT SCROLLING LCD TEXT SIGNS
FIRE ALARM NOTES
1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION
SYSTEM NOTES AND DETAILS.
2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE
SELF-AMPLIFYING TYPE.
3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE
AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL
SECURE AREA NOTES.
4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS
SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE
RATING AS APPLICABLE.
5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE
AREA PERIMETER WALLS SHALL BE PROVIDED WITH
DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE
DETAIL 1/FA501.
6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO
PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL
TO ACCESS DUCTWORK INSPECTION PORTS.
7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED
SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED
BELOW THE SECURITY STC CEILING/FLOOR AND
CEILING/ROOF ASSEMBLIES.
8. SEE ENLARGED FLOOR PLANS FOR FIRE ALARM DEVICE
LOCATIONS.
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FA104
O V
E R
A L
L S
E C
O N
D F
L O
O R
F
IR
E A
L A
R M
P L
A N
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F
A
FTFA 16-3007
SCALE: 1/16" = 1'-0"
0 8' 16' 32'
PLAN
NORTH
1/16" = 1'-0"FA104
1 OVERALL SECOND FLOOR FIRE ALARM PLAN
SECOND FLOOR
Room
Number Room Name
200 CORR.
201 VESTIBULE
202 IDE SERVER RM
203 EVENT DESIGN
COLLABORATION
204 EVENT DESIGN
COLLABORATION
205 ELEV.
206 ELECTRICAL
207 BREAKROOM
208 47 CTS CONFERENCE
209 SERVICE ELEVATOR
210 ITS WORKSTATIONS/WORK
BENCH/TRAINING
211 ITS STORAGE
212 ITS MISSION PREP
213 STAIRS
214 96 CTG. SEC. COMM.
215 WORK AREA
216 OFFICE
217 OFFICE
218 TEST TOOL/EQUIP. STAGING
219 MEN
220 WOMEN
220A LACTATION RM
221 GROUP CLASSROOM
221A STORAGE
222 INVESTMENT GROUP
223 INVESTMENT LEAD
224 WORK AREA
224A OFFICE
225 WORK AREA
226 OFFICE
227 OFFICE
228 OFFICE
229 OFFICE
230 OFFICE
231 OFFICE
232 CORR.
233 STAIRS
234 COMM RM
235 IDE OFFICE
236 IDE OFFICE
237 IDE OFFICE
238 IDE OFFICE
239 MECH.
240 COMM RM
241 JANITOR
242 STOR.
243 EVENT DESIGN CENTER
SECOND FLOOR: 47
L
C
FIRE ALARM NOTES
1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION
SYSTEM NOTES AND DETAILS.
2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE
SELF-AMPLIFYING TYPE.
3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE
AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL
SECURE AREA NOTES.
4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS
SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE
RATING AS APPLICABLE.
5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE
AREA PERIMETER WALLS SHALL BE PROVIDED WITH
DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE
DETAIL 1/FA501.
6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO
PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL
TO ACCESS DUCTWORK INSPECTION PORTS.
7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED
SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED
BELOW THE SECURITY STC CEILING/FLOOR AND
CEILING/ROOF ASSEMBLIES.
MANUAL PULL STATION
FIRE ALARM AND MASS NOTIFICATION SPEAKER
(CEILING-MOUNTED)
FIRE ALARM AND MASS NOTIFICATION
CONTROL UNIT
MONITOR MODULE
PHOTOELECTRIC SMOKE DETECTOR
INDICATES WEATHERPROOFWP
DUCT SMOKE DETECTOR
LOCAL OPERATOR CONSOLE (RECESSED
OR SURFACE MOUNTED AS INDICATED)
W/REMOTE MICROPHONE AND HVAC
SHUTDOWN SWITCH
WATERFLOW SWITCH
TAMPER SWITCH
RELAY MODULE
LOC
MM
FACU
R
FIRE ALARM LEGEND
P
FSA
FIRE ALARM REMOTE ANNUNCIATION
PANEL (RECESSED)
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS XX
XX
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS
(CEILING-MOUNTED)
XX
FIRE ALARM AND MASS NOTIFICATION STROBE
WITH CLEAR LENS
(CEILING-MOUNTED)
XMIT MONACO TRANSCEIVER
CANDELA RATINGXX
AREA BELOW ACCESS FLOOR PROTECTED
WITH ULTRA SENSITIVE SMOKE DETECTION
USSD ULTRA SENSITIVE SMOKE DETECTION PANEL
FIRE ALARM AND MASS NOTIFICATION SPEAKER
TEXT SCROLLING LCD TEXT SIGNS
STAIRS
COMM RM
234 MECH.
EVENT DESIGN
CENTER
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
WORK AREA
225 WORK AREA
INVESTMENT
GROUP
INVESTMENT
LEAD
CORR.
OFFICE
224A
A B C.2C D D.4 E F G
2.8
1.6
CORR.
P
MM
MM
MONITOR SPRINKLER
WATERFLOW SWITCH
AND TAMPER SWITCH
15 15 15
30 30 30
30 30 30
30 30 30
30 30
30 30
R
AHU-2 SHUTDOWN
AHU-2 SUPPLY
TEXT
SURFACE MOUNTED
M A
T C
H
LI
N E
1/ F
A
1/ F
A
M A
T C
H
LI
N E
1/ F
A
1/ F
A
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FA105
P A
R T
IA
L
S E
C O
N D
F L
O O
R F
IR
E
A L
A R
M P
L A
N
W E
S T
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F
A
FTFA 16-3007
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
PLAN
NORTH
1/8" = 1'-0"FA105
1 PARTIAL SECOND FLOOR FIRE ALARM PLAN - WEST
LOC
USSD
FIRE ALARM NOTES
1. SEE SHEET FA501 FOR FIRE ALARM AND MASS NOTIFICATION
SYSTEM NOTES AND DETAILS.
2. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE
SELF-AMPLIFYING TYPE.
3. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE
AREA BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL
SECURE AREA NOTES.
4. ALL CONDUIT PENETRATIONS THROUGH SECURITY WALLS
SHALL BE SEALED TO TO MAINTAIN STC RATING AND FIRE
RATING AS APPLICABLE.
5. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE
AREA PERIMETER WALLS SHALL BE PROVIDED WITH
DIELECTRIC UNIONS ON BOTH SIDES OF THE WALLS. SEE
DETAIL 1/FA501.
6. CONDUIT SHALL BE INSTALLED IN LOCATIONS SO AS TO
PROVIDE SUFFICIENT CLEARANCE FOR SECURITY PERSONEL
TO ACCESS DUCTWORK INSPECTION PORTS.
7. CONDUIT SHALL NOT BE INSTALLED WITHIN DESIGNATED
SECURITY WALL ASSEMBLIES AND SHALL BE INSTALLED
BELOW THE SECURITY STC CEILING/FLOOR AND
CEILING/ROOF ASSEMBLIES.
MANUAL PULL STATION
FIRE ALARM AND MASS NOTIFICATION SPEAKER
(CEILING-MOUNTED)
FIRE ALARM AND MASS NOTIFICATION
CONTROL UNIT
MONITOR MODULE
PHOTOELECTRIC SMOKE DETECTOR
INDICATES WEATHERPROOFWP
DUCT SMOKE DETECTOR
LOCAL OPERATOR CONSOLE (RECESSED
OR SURFACE MOUNTED AS INDICATED)
W/REMOTE MICROPHONE AND HVAC
SHUTDOWN SWITCH
WATERFLOW SWITCH
TAMPER SWITCH
RELAY MODULE
LOC
MM
FACU
R
FIRE ALARM LEGEND
P
FSA
FIRE ALARM REMOTE ANNUNCIATION
PANEL (RECESSED)
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS XX
XX
FIRE ALARM AND MASS NOTIFICATION SPEAKER /
STROBE WITH CLEAR LENS
(CEILING-MOUNTED)
XX
FIRE ALARM AND MASS NOTIFICATION STROBE
WITH CLEAR LENS
(CEILING-MOUNTED)
XMIT MONACO TRANSCEIVER
CANDELA RATINGXX
AREA BELOW ACCESS FLOOR PROTECTED
WITH ULTRA SENSITIVE SMOKE DETECTION
USSD ULTRA SENSITIVE SMOKE DETECTION PANEL
FIRE ALARM AND MASS NOTIFICATION SPEAKER
TEXT SCROLLING LCD TEXT SIGNS
STAIRS
ELEV.
SERVICE
ELEVATOR
ITS STORAGE
EVENT DESIGN
COLLABORATION
ELECTRICAL
IDE SERVER RM
47 CTS
CONFERENCE
EVENT DESIGN
COLLABORATION
BREAKROOM
OFFICE
96 CTG. SEC.
COMM.
TEST
TOOL/EQUIP.
STAGING
WORK AREA
WOMEN
MEN
IDE OFFICE
IDE OFFICE
IDE OFFICE
IDE OFFICE
GROUP
CLASSROOM
COMM RM
JANITOR
STOR.
ITS MISSION
PREP
CORR.
ITS
WORKSTATIONS/WORK
BENCH/TRAINING
INVESTMENT
GROUP
OFFICE
VESTIBULE
F G H J K M N P
2.8
1.6
R
R
CRAC UNIT
SHUTDOWN RELAYS
CRAC UNIT
SHUTDOWN RELAY
P
STORAGE
221A
MM
MM
MM
MM
MM
MONITOR ULTRA SENSITIVE SMOKE
DETECTION PANEL FOR MOST, SECOND,
AND LEAST SENSITIVE ALARM,
SUPERVISORY, AND TROUBLE CONDITIONS
15 15 15
30 30 30
15 15
15 15
30 30
T E
X T
R
RECESSED
M A
T C
H
LI
N E
1/ F
A
1/ F
A
M A
T C
H
LI
N E
1/ F
A
1/ F
A
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FA106
P A
R T
IA
L
S E
C O
N D
F L
O O
R F
IR
E
A L
A R
M P
L A
N
E A
S T
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F
A
FTFA 16-3007
SCALE: 1/8" = 1'-0"
0 4' 8' 16'
PLAN
NORTH
1/8" = 1'-0"FA106
1 PARTIAL SECOND FLOOR FIRE ALARM PLAN - EAST
" 5
T
MANUAL PULL
STATION
FACU
SPEAKER/STROBE
WALL-MOUNTED
SPEAKER
FSA
LOC
WALL-MOUNTED
SMOKE DETECTOR
AT SERVICE ELEVATOR
FACU
SPEAKER/
STROBES
SPEAKER/
STROBES SPEAKERS
MANUAL PULL
STATIONS
15 30 30
STROBES
MM
SPRINKLER
WATERFLOW
MM
CONTROL
VALVE
TO
VAC
SMOKE
DETECTORS
TO 120 VAC
PANEL / CIRCUIT
P P
XMIT
15 75
SPEAKER/
STROBES
SPEAKER/
STROBE
SPD
SPD
EXTERIOR
SPEAKERS
WP WP
LOCLOC
STROBE
R
AHU
SUPPLY
AHU
SHUTDOWN
MM MM
MM
FIRE PUMP
RUNNING
MM
FIRE PUMP
LOSS OF
POWER
MM
FIRE PUMP
PHASE
REVERSAL
MMMM
MMMM
MM
USSD
MMMM
MMMM
MM
USSD
ULTRA SENSITIVE
SMOKE DETECTION
MM
ANECHOIC
CHAMBER CLEAN
AGENT ALARM
MM
ANECHOIC
CHAMBER CLEAN
AGENT
SUPERVISORY
MM
ANECHOIC
CHAMBER CLEAN
AGENT TROUBLE
15 75
SPEAKER/
STROBES
WPWP
R R
ELEVATOR
PRIMARY
RECALL
R R
ELEVATOR
SECONDARY
RECALL
R R
ELEVATOR
SHUNT TRIP
R R
FIRE FIGHTER
HAT FLASHING
R
ELEVATOR
SHUNT TRIP
POWER
MMMM
R R
CRAC UNIT
SHUTDOWN
R
FIRE FIGHTER
HAT STEADY
R
FIRE ALARM NOTES
1. PROVIDE AN ADDRESSABLE FIRE ALARM AND VOICE EVACUATION SYSTEM IN
ACCORDANCE WITH NFPA 72, NFPA 101, UFC 3-600-01, UFC 4-021-01, THE
SPECIFICATION AND THE SCOPE OF WORK DOCUMENTS. THE FIRE ALARM
SYSTEM SHALL BE COMPATIBLE WITH THE MASS NOTIFICATION SYSTEM
RECEIVER AND BE ABLE TO RELAY OUTPUTS FROM THE RECEIVER OVER THE
VOICE EVACUATION SYSTEM TO THE SPEAKERS. MASS NOTIFICATION
SIGNALS SHALL TAKE PRECEDENCE OVER FIRE ALARM SIGNALS.
2. THE FIRE ALARM SYSTEM SHALL MONITOR ALL SPRINKLER SYSTEM ALARM,
SUPERVISORY AND TROUBLE CONDITIONS.
3. AIR HANDLING UNITS OVER 2000 CFM SHALL HAVE DUCT SMOKE DETECTORS
INSTALLED ON THE SUPPLY DUCTS.
4. ALL SOFTWARE, HARDWARE, PASSWORDS, ETC. REQUIRED FOR THE
MAINTENANCE, TESTING, AND REPROGRAMMING OF THE FIRE ALARM SYSTEM
SHALL BE UNCONDITIONALLY TURNED OVER TO THE GOVERNMENT, AND THE
ABOVE NOTED SOFTWARE, HARDWARE, PASSWORDS, ETC. WILL BECOME THE
UNCONDITIONAL PROPERTY OF THE GOVERNMENT. SOFTWARE TURNED
OVER TO THE GOVERNMENT SHALL BE ORIGINAL SOFTWARE ON COMPACT
DISK (CD) WITH JEWELED CASE. COPIES OF SOFTWARE SHALL NOT BE
ACCEPTABLE. SOFTWARE AND CD SHALL BE BRAND NEW AND UNUSED.
PROVIDE AN 8-HOUR BLOCK OF TRAINING ON THE SOFTWARE, REGARDING
MAINTENANCE, TESTING, AND REPROGRAMMING OF THE FIRE ALARM SYSTEM
FOR 6 PERSONNEL. TRAINING SHALL BE PROVIDED ON SITE AT EGLIN AFB, FL.
5. THE FIRE ALARM SYSTEM SHALL REPORT ALL CONDITIONS TO THE BASE-WIDE
REPORTING SYSTEM AS NECESSARY. THE CONTRACTOR SHALL COORDINATE
WITH THE BASE TO ENSURE THE SYSTEM IS COMPATIBLE WITH THE BASE
WIDE (MONACO BT-XF) SYSTEM AND THE PROPER TRANSMITTING EQUIPMENT
IS PROVIDED. THE TRANSCEIVER SHALL BE PROVIDED AND INSTALLED BY
THE CONTRACTOR AS PART OF THE COMPLETE FIRE ALARM SYSTEM.
6. ALL SPEAKERS LOCATED INSIDE SECURED AREAS SHALL BE SELF-
AMPLIFYING TYPE.
7. THE FIRE ALARM AND MNS LAYOUT IS DIAGRAMMATICAL ONLY. THE ACTUAL
BUILDING LAYOUT MAY VARY FROM THE DRAWINGS. THE CONTRACTOR
SHALL VERIFY CEILING HEIGHTS, WALL AND PARTITION LOCATIONS AND DOOR
LOCATIONS PRIOR TO INSTALLATION.
8. ALL INTERIOR AND EXTERIOR WALLS, CEILINGS AND FLOORS THAT ARE
DAMAGED OR ALTERED BY THE CONTRACTOR SHALL BE RESTORED TO
ORIGINAL CONDITION AND TO THE SATISFACTION OF THE CONTRACTING
OFFICER.
9. ALL FIRE ALARM AND MNS CONDUCTORS SHALL BE SOLID COPPER AND SHALL
BE INSTALLED IN CONDUIT. ALL CONDUIT SHALL BE FACTORY PAINTED RED.
10. ALL METALLIC CONDUIT PENETRATIONS THROUGH SECURE AREA PERIMETER
WALLS SHALL BE PROVIDED WITH DIELECTRIC UNIONS ON BOTH SIDES OF
THE WALLS. SEE ARCHITECTURAL DRAWINGS FOR SECURE WALL
LOCATIONS.
INSIDE
SECURE AREA
OUTSIDE
SECURE AREA
CONDUITCONDUIT
SECURITY WALL ASSEMBLY
DIELECTRIC UNION
NOTE: WHEN THE SECURE
WALL IS AN INTERNAL
COMPARTMENTED WALL
BOTH SIDES WILL BE WITHIN
SECURE AREA
DIELECTRIC UNION
CONDUIT
NOTE: PENETRATIONS THROUGH
FIRE RATED SECURITY WALLS
SHALL BE PROVIDED WITH A
UL-CLASSIFIED THROUGH-
PENETRATION FIRESTOP ASSEMBLY
SCALE: NONEFA501
2 FIRE ALARM ELEVATION (TYPICAL)
SCALE: NONEFA501
3 RISER DIAGRAM
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FA501
D E
T A
IL
S
F
IR
E
A L
A R
M
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F
A
FTFA 16-3007
SCALE: NONEFA501
1 DIELECTRIC UNION DETAIL
FIRE ALARM SYSTEM SEQUENCE OF OPERATION MATRIX
MANUAL PULL STATION
ALARM AT
FACU & FSA
SUPERVISORY
AT FACU &
FSA
TROUBLE AT
FACU & FSA
ALARM AT
RECEIVING
STATION
TROUBLE
AT
RECEIVING
STATION
SUPERVISORY
AT RECEIVING
STATION
ACTIVATE
SPEAKERS,
STROBES
& FIRE
ALARM
MESSAGE
SILENCE
SPEAKERS
& STROBES
SHUTDOWN
AHU / ERV
SMOKE DETECTOR
WATERFLOW SWITCH
INPUT RECEIVED FROM
MASS NOTIFICATION
SYSTEM (MNS)
TAMPER SWITCH
FIRE ALARM TROUBLE
CONDITION (OPENS,
SHORTS OR GROUNDS)
ALARM SILENCE AT
FACU OR FSA
DUCT SMOKE DETECTOR
MNS PANEL TROUBLE
OVERRIDE FA
MESSAGE
OVERRIDE PA
SYSTEM
MNS SYSTEM
TROUBLE AT
RECEIVING
STATION
*SEE SPECIFICATION SECTION 28 31 76, PARAGRAPH 2.20.2 FOR SPECIFIC SIGNALS REQUIRED TO BE TRANSMITTED TO THE RECEIVING STATION
ULTRA-SENSITIVE SMOKE
DETECTOR MOST
SENSITIVE ALARM
ULTRA-SENSITIVE SMOKE
DETECTOR SECOND
LEVEL ALARM
ULTRA-SENSITIVE SMOKE
DETECTOR LEAST
SENSITIVE ALARM
ULTRA-SENSITIVE SMOKE
DETECTOR SUPERVISORY
CONDITION
ULTRA-SENSITIVE SMOKE
DETECTOR TROUBLE
CONDITION
NOTE
ALARM LEVEL 1 DEFAULT
SETTING SHALL BE 0.025%
OBSCURATION PER FOOT
ALARM LEVEL 2 DEFAULT
SETTING SHALL BE 0.044%
OBSCURATION PER FOOT
ALARM LEVEL 3 DEFAULT
SETTING SHALL BE 0.062%
OBSCURATION PER FOOT
FIRE PUMP RUNNING
FIRE PUMP LOSS OF
POWER
FIRE PUMP PHASE
REVERSAL
ANECHOIC CHAMBER
CLEAN AGENT ALARM
ANECHOIC CHAMBER
CLEAN AGENT
SUPERVISORY
ANECHOIC CHAMBER
CLEAN AGENT TROUBLE
INITIATE
ELEVATOR
PRIMARY
RECALL
INITIATE
ELEVATOR
SECONDARY
RECALL
INITIATE
ELEVATOR
SHUNT TRIP
ACTIVATE
SPEAKERS,
STROBES
& MNS
MESSAGE
ELEVATOR MACHINE ROOM
WATERFLOW SWITCH
ACTIVATE
FLASHING
FIRE
FIGHTER'S
HAT
ELEVATOR MACHINE
ROOM SMOKE DETECTOR
ELEVATOR 1ST FLOOR
LOBBY SMOKE DETECTOR
ELEVATOR 2ND FLOOR
LOBBY SMOKE DETECTOR
SHUTDOWN
CRAC
UNITS
ACTIVATE
STEADY
FIRE
FIGHTER'S
HAT
CLEAN AGENT
DISCHARGE
ALARM AT
RECEIVING
STATION
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FA502
F
IR
E A
L A
R M
S E
Q U
E N
C E
O F
O P
E R
A T
IO
N
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F
A
FTFA 16-3007
SCALE: NONEFA502
1 SEQUENCE OF OPERATION MATRIX
100 101
103 104
109 111
120121
128 129
130B
144C
145 146 147 148
108 110A
SPRINKLER RISER
INCOMING WATER
SUPPLY
VERTICAL INLINE FIRE PUMP
RATED FOR 500 GPM AT
40 PSI TO BE PROVIDED
A B C.2C D D.4 E F G H J K M N P
2.8
1.6
144B
144A
SEE SHEET FX401 FOR
ENLARGED FLOOR PLAN
FIRE PROTECTION NOTES
1. SEE SHEET FX501 FOR FIRE PROTECTION NOTES AND DETAILS.
2. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE AREA
BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL SECURE AREA
CONSTRUCTION NOTES.
3. ALL PENETRATIONS THROUGH SECURITY WALLS SHALL BE SEALED TO
MAINTAIN STC RATING AND FIRE RATING AS APPLICABLE.
4. ALL METALLIC PIPE PENETRATIONS THROUGH SECURE AREA PERIMETER
WALLS SHALL BE PROPERLY GROUNDED. SEE DETAIL 2/FX501.
5. PIPING SHALL BE INSTALLED IN LOCATIONS SO AS TO PROVIDE SUFFICIENT
CLEARANCE FOR SECURITY PERSONEL TO ACCESS DUCTWORK
INSPECTION PORTS.
6. PIPING SHALL NOT BE INSTALLED WITHIN DESIGNATED SECURITY WALL
ASSEMBLIES AND SHALL BE INSTALLED BELOW THE SECURITY STC
CEILING/FLOOR AND CEILING/ROOF ASSEMBLIES.
7. LIGHT GAGE STEEL FRAMING OF THE SECURITY STC CEILING/FLOOR AND
CEILING/ROOF ASSEMBLIES SHALL NOT BE UTILIZED TO SUPPORT PIPE OR
PIPE SUPPORT ASSEMBLIES. ALL PIPE AND SUPPORT SHALL BE
SUPPORTED FROM THE BUILDING STRUCTURE.
LIGHT HAZARD
0.10 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 1,500 SF
WATER MOTOR GONG
ORDINARY HAZARD
0.20 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 2,500 SF
FIRE PROTECTION LEGEND
TEST HEADER
FIRE DEPARTMENT CONNECTION
SHEET
IDENTIFICATION
US Army Corps of
Engineers ®
Mobile District
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
D E
S
IG
N E
D B
Y
B U
L L
O C
K T
IC
E
A S
S O
C
IA
T E
S
E
C E
R V
A N
T E
S S
T R
E E
T
P E
N S
A C
O L
A F
L O
R
ID
A
D R
A W
N B
Y
S B
M T
B Y
P L
O T
S C
A L
E
S
IZ
E
C K
D B
Y
P L
O T
D A
T E
D A
T E
S O
L
IC
IT
A
T
IO
N N
O
C O
N T
R A
C T
N O
P R
O J E
C T
N U
M B
E R
F
IL
E N
A M
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
:1 x
M O
B
IL
E D
IS
T
R
IC
T
M O
B
IL
E A
L A
B A
M A
M E
F
M
A Y
A
2 3 4 5
B
C
D
W
R
C Y
B E
R S
P A
C E
T E
S T
G R
O U
P F
A C
IL
IT
Y
E G
L
IN
A F
B F
L O
R
ID
A
FX101
O V
E R
A L
L F
IR
S
T F
L O
O R
F
IR
E P
R O
T E
C T
IO
N
P L
A N
K
K E
L L
Y
K
K E
L L
Y J
J
O H
N
F E
I
M
A Y
M E
F
F X
FTFA 16-3007
SCALE: 1/16" = 1'-0"
0 8' 16' 32'
PLAN
NORTH
1/16" = 1'-0"FX101
1 OVERALL FIRST FLOOR FIRE PROTECTION PLAN
FIRST FLOOR
Room
Number Room Name
100 LOBBY
101 BREAKROOM
102 CORR.
103 ELEV.
104 JANITOR
105 ELEC.
106 MEN
106A SHOWER
107 WOMENS
107A SHOWER
108 ELEVATOR EQUIPMENT
109 SERVICE ELEVATOR
110 LOGISTICS/CE REP
110A RECYCLE ROOM
111 COMSEC
112 VESTIBULE
113 STAIR 2
114 NCR SERVER ROOM
115 SECURE STORAGE
116 SECURE CORRIDOR
117 CORR.
118 TEST SUITE
119 NCR SECURITY MGRS
120 RANGE OPS CENTER
121 TEST SUITE
122 TEST SUITE
123 TEST SUITE
124 TEST SUITE
125 TEST SUITE
126 TEST SUITE
127 NCR CONFERENCE ROOM
128 ACR GSSO
129 ACR STORAGE
130A CORR.
130B ACR ISSO
132 ACR ISSM
133 ACR SYSADM
134 CORRIDOR
135 ACR CONF. RM
136 AVIONICS TEST LAB
137 ATL STORAGE
138 ATL ANALYSIS
139 CYBER/EW LAB
140 C/EW ANALYSIS
141 COMM RM
142 CORR.
143 STAIR 1
144A POWER VESTIBULE
MANTRAP
144B DEV & RE LAB
144C THREAT DEVELOPMENT LAB
145 REPORT WRITING 1
146 REPORT WRITING 2
147 THREAT RESEARCH ROOM
148 ACR SERVER
149 COLLATERAL SECURITY
150 COLLATERAL SECURITY
LEAD
151 BADGE
152 COMM RM
153 MECH.
154 FIRE PUMP
FIRST FLOOR: 60
1 Room
Level 1: 1
ACR GSSO
ACR STORAGE
ACR ISSO
130B
ACR ISSM
ACR SYSADM
ACR CONF. RM
CORRIDOR
AVIONICS TEST
LAB
COMM RM
CYBER/EW LAB
STAIR 1
FIRE PUMP
THREAT
DEVELOPMENT
LAB
144C
REPORT WRITING
REPORT WRITING
THREAT
RESEARCH ROOM
ACR SERVER
C/EW ANALYSIS
ATL STORAGE
CORR.
INCOMING WATER
SUPPLY
VERTICAL INLINE FIRE PUMP
RATED FOR 500 GPM AT
40 PSI TO BE PROVIDED
SPRINKLER RISER
A B C.2C D D.4 E F G
2.8
1.6
FX401
DEV & RE LAB
144B
POWER
VESTIBULE
MANTRAP
144A
FLOOR CONTROL
ASSEMBLY CONSISTING OF
OS&Y CONTROL VALVE, CHECK
VALVE, AND WATERFLOW SWITCH
ATL ANALYSIS
SEE SHEET FX401 FOR
ENLARGED FLOOR PLAN
USER PROVIDED ANECHOIC
CHAMBER CLEAN AGENT SYSTEM
M A
T C
H L
IN
E
/F
X
/F
X
M A
T C
H L
IN
E
/F
X
/F
X
FIRE PROTECTION NOTES
1. SEE SHEET FX501 FOR FIRE PROTECTION NOTES AND DETAILS.
2. REFER TO DRAWINGS G-107 THROUGH G-110 FOR SECURE AREA
BOUNDARIES AND DRAWING G-004 FOR ADDITIONAL SECURE AREA
CONSTRUCTION NOTES.
3. ALL PENETRATIONS THROUGH SECURITY WALLS SHALL BE SEALED TO
MAINTAIN STC RATING AND FIRE RATING AS APPLICABLE.
4. ALL METALLIC PIPE PENETRATIONS THROUGH SECURE AREA PERIMETER
WALLS SHALL BE PROPERLY GROUNDED. SEE DETAIL 2/FX501.
5. PIPING SHALL BE INSTALLED IN LOCATIONS SO AS TO PROVIDE SUFFICIENT
CLEARANCE FOR SECURITY PERSONEL TO ACCESS DUCTWORK
INSPECTION PORTS.
6. PIPING SHALL NOT BE INSTALLED WITHIN DESIGNATED SECURITY WALL
ASSEMBLIES AND SHALL BE INSTALLED BELOW THE SECURITY STC
CEILING/FLOOR AND CEILING/ROOF ASSEMBLIES.
7. LIGHT GAGE STEEL FRAMING OF THE SECURITY STC CEILING/FLOOR AND
CEILING/ROOF ASSEMBLIES SHALL NOT BE UTILIZED TO SUPPORT PIPE OR
PIPE SUPPORT ASSEMBLIES. ALL PIPE AND SUPPORT SHALL BE
SUPPORTED FROM THE BUILDING STRUCTURE.
LIGHT HAZARD
0.10 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 1,500 SF
WATER MOTOR GONG
ORDINARY HAZARD
0.20 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 2,500…