This asbestos survey report documents the findings of an inspection conducted at Building 32010 on Fort Hood Army Base in preparation for renovation work. The survey identified black mastic under brown vinyl floor tiles, wallboard joint compound throughout the building, and window caulk and glazing containing asbestos. These asbestos-containing materials will require removal by a licensed abatement contractor according to applicable regulations prior to renovation given their presence in areas that may be disturbed. Solicitation W91151-23-B-0020 is for the renovation of Building 32010 at Fort Hood and will require the contractor to remove identified asbestos-containing materials during the project in accordance with applicable standards.
View the file
Other files for this federal contract opportunity
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Clean Environments, inc.
Industrial Hygiene & Environmental Consultants
April 6, 2011
Sonny Gomez Kickapoo Empire, LLC 1003 Paulson Drive San Antonio, Texas 78219
RE: Asbestos Survey-DSHS Notification Building 32010 Fort Hood Army Base Fort Hood, Texas 76544 CEI Project N2: 8997
Dear Mr. Gomez:
An asbestos survey was conducted at the referenced property on March 24, 2011. The survey was accomplished by Mr. Ray Keeble, Asbestos Inspector, Texas DSHS License N2 60-2505, working with Mr Craig Nelson, Individual Asbestos Consultant, DSHS License N2 10-5726 of Clean Environments, Inc Asbestos Consultant Agency, DSHS License N2 10-0005. The ACBM survey was conducted in accordance with the EPA Guidance for Controlling Asbestos-Containing Materials in Buildings (EPA 560/5-85-024) June 1985 and the Texas Asbestos Health Protection Rules (25 TAC 295) March 2003, which requires that an asbestos survey be accomplished prior to demolition, renovation, and/or alterations that include the demolition of interior building materials and/or remodeling for any commercial structure.
The asbestos survey was limited to readily accessible building materials inside the building, unless otherwise noted. No destructive sampling was accomplished. Asbestos surveys accomplished for renovation or demolition activities are generally limited to materials identified (by the owner representative) as materials that will be disturbed during renovation or demolition activities. If any suspect asbestos materials, not identified in this survey, are uncovered during any demolition or renovation activity, please contact Clean Environments, Inc. immediately for further assessment.
BACKGROUND
Construction materials containing asbestos have been used extensively in buildings. Asbestos possesses excellent properties for fireproofing and insulation materials. Asbestos may be found in: (1) cement products; (2) spray applied or trowel applied materials on ceiling, walls, and other surfaces; (3) insulation on pipes', boilers, tanks, ducts, and other equipment; (4) vinyl floor tiles; (5) roofing felts; (6) flooring coatings- and (7) other miscellaneous products. Friable asbestos material is any materials that contain more than 1 percent asbestos by weight, which can be crumbled, pulverized, or reduced to powder, when dry, by hand pressure. Some of these asbestos-containing materials are not considered friable now, but could become friable if not properly managed and maintained under an asbestos management program.
The concern about exposure to asbestos is based on evidence linking various respiratory diseases with occupational exposure in the shipbuilding, mining, milling, and fabricating industries. The presence of asbestos does not mean that there is a significant health risk to the property occupants. As long as asbestos-containing materials remain in good condition and are not disturbed, exposure is unlikely.
Through proper control of building operations and maintenance activities, disturbance or damages to asbestos-containing materials in buildings are minimized, thus limiting the occupant's exposure to
10803 Gulfdale, Suite 210 • San Antonio, Texas 78216 • 210/349-7242 • Fax 210/349-1132
CLEAN ENVIRONMENTS, Inc.
Asbestos Survey for DSHS Notification Building 32010 Fort Hood Army Base Fort Hood, Texas 76544 airborne asbestos fibers. Building alterations and/or demolition require knowledge of what materials contain asbestos and if they will be removed or disturbed during the project. Under the Clean Air Act, the EPA has issued a National Emission Standard for Asbestos (40 CFR 61.140 - 61.156). This Standard regulates reporting requirements, work practices, waste disposal, and emissions from facility modification and/or demolition operations. The Standard applies only to materials containing more than 1% friable asbestos. Asbestos containing material according to the State of Texas Asbestos Health Rules is any building material containing greater than 1% asbestos.
Initially, a visual walk-thru inspection was conducted on the building. Based on this initial survey, areas were identified for physical assessment and bulk sample analysis. Then a detailed inspection was accomplished together with bulk sampling, as necessary. Material sampling conforms to the requirements in the 40 CFR 763.88. The sampling methods and strategies are outlined below for the three basic classifications of asbestos materials: friable surfacing materials, thermal system insulation, and miscellaneous material. The sampling scheme Clean Environments utilizes for selecting sampling locations in buildings is the EPA method identified in their document, "Asbestos in Buildings: Simplified Sampling Scheme for Friable Materials," EPA 560/5-85-030a, October 1985. Samples are selected according to homogenous areas. "Homogenous area" means an area of surfacing material, thermal system insulation, and miscellaneous asbestos materials that is uniform in color and texture, construction/application date and general appearance. At least three randomly distributed samples are collected from each homogeneous thermal insulation system. Samples are also collected on patched and fitting areas of thermal system insulation. At least one sample is collected in homogeneous miscellaneous materials. The miscellaneous materials, which are most likely sampled in buildings, are ceiling and floor tiles.
Revisions to the asbestos National Emissions Standard for Hazardous Air Pollutants (NESHAP) were promulgated on November 20, 1990. These include a requirement to point count in order to quantify asbestos in samples where the content is below 10%. The intent of the revision is to improve quantitative analysis of asbestos for all applications. Samples where no asbestos is detected do not have to be point counted. If asbestos is detected, but is less than 10%, the owner or operator of the building may elect to
(1) assume the amount to be greater than 1% and treat the material as asbestos or (2) require verification of the amount by point counting. It is a Clean Environments, Inc. policy to treat all samples with detectable levels of asbestos fibers as asbestos-containing material and to recommend a point count, using a mechanical stage and random point reticule, for all samples found to be 1% or less. The owner or operator of the building may elect to conduct further testing of samples that range from greater than 1% to 10% before treating the material as asbestos.
FINDINGS
Renovation and/or demolition are scheduled at the above referenced location. The building has a brick and glass facade with a tar & gravel roof. The walls & ceilings are sheetrock bound by joint compound.
The floors were found to have brown vinyl tiles with black mastic in the SVC SEC office adhered to the concrete foundation. The windows were found to have caulk or glazing throughout the building. Thermal systems insulation (TSI) was observed in the mechanical room and in building. The exterior of the structure has a tar & gravel built up roof. Ten suspect ACBMs were identified and sampled for a total of 30 samples.
CLEAN ENVIRONMENTS, Inc.
Asbestos Survey for DSHS Notification Building 32010 Fort Hood Army Base Fort Hood, Texas 76544
The samples were analyzed at Environmental Analytical Services, L.L.C., Asbestos Laboratory, Houston, Texas, DSHS License N2 30-0373, using polarized light microscopy (PLM) analysis.
PLM laboratory analysis indicates that the following materials are positive for asbestos:
• Black mastic (5%) under brown vinyl tile in the SVC SEC office. There is approximately
120 square feet of vinyl tile in the office.
• Wallboard/joint compound (3%) throughout the building. There is approximately 8,000 square feet of wallboard/joint compound in the building.
• Window caulk/glazing (5%) on all windows.
All other suspect materials are negative for asbestos fibers.
The client requested that point count analysis not be performed.
RECOMMENDATIONS
The black mastic under brown vinyl tile, wallboard/joint compound and window caulk/glazing must be removed prior to any operations that may disturb the asbestos fibers in the material. Abatement must be accomplished according to the guidelines set forth in 40 CFR 61, the National Emission Standard for Hazardous Air Pollutants (NESHAP) and/or DSHS, Texas Asbestos Health Protection Rules, March 2003. This includes removal by a licensed asbestos abatement contractor and project management by a licensed asbestos consultant firm.
We will be happy to answer any questions concerning the report. It has been a pleasure to work with you on this project. We look forward to being of continued service to you.
Very tarty yours, CrVrg'Nelsot/ Individual Asbestos Consultant DSHS License N2 10-5726
Attached: Chain of Custody Laboratory Results Sample locations
Clean Environments, Inc.
10803 Gulfdale, Suite 210 San Antonio, Texas 78216
"": £ 5 3 e n l - 13201 Northwest Freewav Suite 503
. Scrvi«.s, u-c Houston, Texas 77040 , g ^ ' (713)343-4017 • Fax:(713)934-9942 trr~-?' easlabs@aol.com • LSOAcct* 123757
CHAIN OF CUSTODY
Page_/_ of ^
Sample Type & Quantity:
Project No.
& Name
Ft Hood, Bldg. 32010
: J&, 4r TURNAROUND: LJ Clean Environments STANDARD R U S H Y | OTHER: PLM - Positive Stop Contact Person: /£. /(*<!>[a. p h o n e : 210-349-7242 Fax: 210-349-i"i32
E-Mail Results to: cei@cteanenvironments.com and ibs@cleanenvironments.com Comments:
SAMPLE No.
Tsz 1-3
Tc /-/
Tc y-2.
Tc j-3>
Zfci- 1
Tc'z-3
SAMP
(m
SAMPLE:
LE DESCRIPTION
a ten a 1 type, color, etc.)
Yellow tile w/black mastic
£/~ /^f'^ok/sv ~yo,',*JJ Co^"!/3, SAMPLE LOCATION
(Room, Floor, Wall, Window, Door, etc.)
SAMPLE: Front Office - North Wall - flooring
I
1 :
F ria bl e
(F
No n-
F ria bl e
(NF
(£)l NF
IS? 1 NF
£?l NF
<£) 1 NF
[f)l NF
<£)/ NF
dD / NF
CD/ NF
OL?1 NF
CONDITION
(Circle Most Applicable)
Good/ Fair ^-Poo^
Good/ Fair /£o$>P Significant Damaged
Good/Fair/ffiS?
Significant Damaged
Good/Fair i£oo?
Significant Damaged
Good/ Fair ifo^r1
Significant Damaged
Good/Fair/c^oj?
Significant Damaged
Good/Fair ^Poj?
Significant Damaged
Good / Fair / ?20^ Significant Damaged
Good / Fair / PaS?
Significant Damaged
E st im at ed Sq
Ftg
Li ne ar
F t.
:-^*rA*/jr£ Accepted By: ^VVvJU^-i^ I' ^^WjJL^ ^-ZS-\( (Signature, Date, and Time)
Relinquished By fc^l (Signature, Date, and Time)
Clean Environments, Inc.
San Antonio, Texas 78216
~t Environmental ' Anal-jtical j.^JUniut, vu. Houston, Texas 77040 JA§ (713) 343-4017 • Fax: (713) 934-9942 %~~^ easlabs@aol.com • LSOAcct* 123757
13201 Northwest Freeway Suite 503
CHAIN OF CUSTODY
Page X of LJ
Sample Type & Quantity:
Project No.
& Name;
Ft. Hood, Bldg. 32010
TURNAROUND: D Clean Environments STANDARD • R U S H g f OTHER: <3 JO V PLM - Positive Stop Contact Person: KZ e / / l
Phone: 210-349-724? Fax: 210-349-113?
E-Mail Results to: cei@fcleanenwronments.nom and jbs@cleanenvironmente mm Comments:
SAMPLE No. SAMPLE DESCRIPTION (material type, color, etc.)
SAMPLE: Yellow tile w/black mastic
SAMPLE LOCATION
(Room, Floor, Wall, Window, Door, etc.)
SAMPLE: Front Office - North Wall - flooring
CONDITION
(Circle Most Applicable)"S z *c
J~C 3 ' / " g / Z / > j r y^v - , / ^ / ^ .
JC3-
Jc 1-3
7S2T2-/ Good I Fair^^opt Significant DamagedCOsstte* U//L4P f/fz ZWSfl-
I NF
15ZZ-2 O / NF Good/ Fair l^ot Significant Damaged
TSZ2-3 (£)l NF Good/Fair/&oc5 Significant Damaged
Pi NF tk-:J QQ/ <%i(/'-l .
IAJ£-2
<Pl NF Good / FaitiEnor ^StgiflTlcant-Damaged)U/C-^
Relinquished By: ^ ^ ^ * ^ JL-^d~eJ*^ Accepted By:
fSk Clean Environments, Inc.
San Antonio, Texas 78216
Environmental Analytical tervictft. U-6
13201 Northwest Freeway Suite 503
Houston, Texas 77040
(713)343-4017 • Fax:(713)934-9942 easlabs@aol.com • LSO Acct # 123757
CHAIN OF CUSTODY
Page 3 of V
Sample Type
& Quantity ?
Project No.
& Name:
Ft. Hood, Bldg. 32010
EAS
Job#
TURNAROUND: D Clean Environments STANDARD Q R U S H fffiOTHER: <3 {& *f Contact Person: A ' K*-*•{,£t- Phone: 210-349-7242 Fax: 210-349-1132
E-Maii Results to: cei@cleanenvironments.com and ibs@cleanenvironments.com Comments:
PLM - Positive Stop
SAMPLE No.
rr-i rr-z
FT'3
TsX-l
/fecit- AS?
SA-/
SAMPLE DESCRIPTION
(material type, color, etc.)
SAMPLE: Yellow tile w/black mastic grto^^ flo^ 7 ^ yilfcir/VAT* i .
i1
SAMPLE LOCATION
(Room, Floor, Wall, Window, Door, etc.)
SAMPLE: Front Office - North Wall - flooring
SVC Sz c of/r, c A
Ii
F ria bl e
(F
N on
F ria bl e
<N F)
F \(SP
F 1®
F l(tf£)
£> / NF
&> 1 NF
tf> 1 NF
£>\ NF
£> 1 NF
@ 1 NF
CONDITION
(Circle Most Applicable)
Good / Fair^Poojy
Significant Damaged
Good/Fair /€S?
Significant Damaged
Good/ Fair IQ^> Significant Damaged
Good /Fair/ £5^?
Significant Damaged
Good /Fair l ^ r Significant Damaged
Good/ Fair/ fjoj?
Significant Damaged
Good / Fair/Poor ^•Oiynifi&ant Damaged^
Good / Fairi£o_or Significant Damage^
Good / Fair/Poor Sigjiifieant-Bamagecp
E st im at ed S q.
F ig
Li ne ar F t.
Relinquished By: j 7 ^ ^ £ ^ JrAy>- 1-^V-// (Signature, Date, and Time)
Accepted By:
= ! Clean Environments, Inc. , I tZ7™ 13201 Northwest Freeway Suite 503 ^ S M V J O * , u ^ Houston, Texas 77040 iK4 (713) 343-4017 . Fax: (713) 934-9942 easlabs@aol.com • LSOAcct# 123757
CHAIN OF CUSTODY
Page_$/_ of V
10803 Gulfdale, Suite 210 San Antonio, Texas 78216
Sample Type
& Quantity:
Project No.
&Name:
ff //oe>J 4/^ . 3 Z&/&
EAS
Job#
RUSH fD?fOTHER: <J JOTURNAROUND: [
Contact Person: j£. /C- l <•/ / -*•
E-Mail Results to: cei@cleanenvironments.com and jbs(5),cleanenvironments.com Comments:
Clean Environments STANDARD
Phone: 210-349-7242 Fax: 210-349-1132
PLM - Positive Stop
SAMPLE No.
SV-Lck. /loo*"
•re-1 sun J^c-I Slick, SAMPLE DESCRIPTION
(material type, color, etc.)
SAMPLE: Yellow tile w/black mastic
SAMPLE LOCATION
{Room, Floor, Wall, Window, Door, etc.)
SAMPLE: Front Office - North Wall - flooring
/vtcAx^crfl A-ofs+i rt;t>'^*) /xtftt
Fr ia bl e
(F
N on
F ria bl e
(N F)
&l NF
<P / NF
& 1 NF
F / NF
F / NF
F / NF
F / NF
F / NF
F / NF
CONDITION
(Circle Most Applicable)
Good /Fair /Poor
Good / Fair/Papr gjgrrificant DimagSS7
Good/ Fair /j^oor Significant Damages'
Good/Fair/Poor Significant Damaged
Good/Fair/Poor Significant Damaged
Good/Fair/Poor Significant Damaged
Good/Fair/Poor Significant Damaged
Good/Fair/Poor Significant Damaged
Good /Fair /Poor Significant Damaged
E st im at ed Sq
Ft g.
Li ne ar F t.
Relinquished By: ^ 7 ^ ^ , fr^-~ Accepted By:
(Signature, Date, and Time) (Signature, Date, and Time)
~r environmental \ Analytical . Services, LU1
13201 Northwest Freeway Suite 503 Houston, Texas 77040
Phone: 713-343-4017 / Fax: 713-934-9942 E-Mail:easlabs@aol.com
Polarized Light Microscopy Analysis (EPA-600/M4-82-020; 600/R-93/116)^s
Client Information:
Clean Environments 10803 Gulfdale Suite 210 San Antonio, Texas 78216
Phone: 210-349-7242 Fax: 210-349-1132 E-Mail: cei@cleanenvironments.com
Project:
Ft. Hood, Building 32010
Job: CEI11.215
Attn: Ray Keeble
Date Analyzed: April 2, 2011
Date Received: March 25, 2011
Microscope: Olympus-CH-40 Analysis Time Requested: 4-Days
Sampled
TSI1-1
TSI1-2
TSI1-3
JC1-1
JC1-2
JC1-3
JC2-1
Layer A
B
A
B
A
B
A
A
Sample Description White Mastic
Wrapping
Yellow Insulation
White Mastic Wrapping
Yellow Insulation
White Mastic Wrapping
Yellow Insulation
White Joint Compound
Tan Joint Compound
Homo- Geneous
(Y/N)
YES
YES
YES
YES
YES
YES
YES
YES
Asbestos Detected?
Yes/No
NO
NO
NO
NO
NO
NO
YES
NO
Asbestos Mineral Percent
None Detected
None Detected
None Detected
None Detected
None Detected
None Detected
3% Chrysotile
Not Analyzed Positive Stop
None Detected
Non-Asbestos Fibers
20% Cellulose 20% Fiberglass
100% Fiberglass
20% Cellulose 20% Fiberglass
100% Fiberglass
20% Cellulose 20% Fiberglass
100% Fiberglass
2% Cellulose
Non-Fibrous Material
60% Other
60% Other
60% Other
97% Other
98% Other
NVLAP # 200784-0
DSHS # 300373 Control # 95392
Page 1 of4 Notes:
Some samples (floor tiles, surfacing, etc.) may contain fibers too small too be detectable by PLM. TEM Chalfield analysis of bulk material is recommended in this case. All asbestos percentages are based on calibrated visual estimates traceable to NIST standards for regulated asbestos types. Analysts' percentages fall within a range of acceptable percentages, depending on the actual concentration of asbestos.
This test reports relates only to the items tested. Neither NVLAP nor EPA accreditation implies endorsement by any US Government agency. This report may not be reproduced except in full without written permission from Environmental Analytical Services.
These results are submitted pursuant to EAS current terms and condition of sale, including the company's standard warranty and limitation of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, EAS will store the samples for a period of ninety (90) days before discarding. Percent ranges reported are estimates and not absolute percent range values.
Analyzed by: Approved Signatory:
Arthur Hernandez Lisa Crain
Environmental
Services, \XC
13201 Northwest Freeway Suite 503 Houston, Texas 77040
Phone: 713-343-4017 / Fax: 713-934-9942 E-Mail:easlabs@aol.com
Polarized Light Microscopy Analysis
(EPA-600/M4-82-020; 600/R-93/116)
Client Information:
Clean Environments 10803 Gulfdale Suite 210 San Antonio, Texas 78216
Phone:210-349-7242 Fax: 210-349-1132 E-Mail: cei@eleanenvironments.com
Project:
Ft. Hood, Building 32010
Job:CEI11.215
Attn: Ray Keeble
Date Analyzed: April 2,2011
Date Received: March 25, 2011
Microscope: Olympus-CH-40 Analysis Time Requested: 4-Days
Sampled
JC2-2
JC2-3
JC3-1
JC3-2
JC3-3
TSI2-1
TSI2-2
TSI2-3
Layer A
A
A
A
B
A
B
A
Sample Description Tan Joint Compound
Tan Joint Compound
White Joint Compound
Gray Mastic Wrapping
Yellow Insulation
Gray Mastic Wrapping
Yellow Insulation
Gray Mastic Wrapping
Homo- Geneous
(Y/N)
YES
YES
YES
YES
YES
YES
YES
YES
Asbestos Detected?
Yes/No
NO
NO
YES
NO
NO
NO
NO
NO
Asbestos Mineral Percent
None Detected
None Detected
3% Chrysotile
Not Analyzed Positive Stop
None Detected
None Detected
None Detected
None Detected
None Detected
Non-Asbestos Fibers
2% Cellulose
2% Cellulose
20% Cellulose 20% Fiberglass
100% Fiberglass
20% Cellulose 20% Fiberglass
100% Fiberglass
20% Cellulose 20% Fiberglass
Non-Fibrous Material
98% Other
98% Other
97% Other
60% Other
60% Other
60% Other
NVLAP# 200784-0
DSHS # 300373 Control # 95392
Notes:
Some samples (floor tiles, surfacing, etc ) may contain fibers too small too be delectable by PLM. TEM Chalfield analysis of bulk material is recommended in this case. All asbestos percentages are based on calibrated visual estimates Iraceable to NIST slandards for regulated asbestos types. Analysis' percentages fall within a range of acceptable percentages, depending on the actual concentralion of asbestos This test reports relates only to Ihe items tested. Neither NVLAP nor EPA accreditation implies endorsement by any US Government agency. This report may not be reproduced except in full without written permission from Environmental Analytical Services.
These results are submitted pursuant to EAS current terms and condition of sale, including the company's standard warranty and limitation of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return Ihe samples covered by this report, EAS will store the samples for a period of ninety (90) days before discarding Percent ranges reported are estimates and not absolute percent range values.
Analyzed by: Approved Signatory:^->--
^ ^ Services, li~C
13201 Northwest Freeway Suite 503 Houston, Texas 77040
Phone: 713-343-4017/Fax: 713-934-9942 E-Mail:easlabs@aol.com
Polarized Light Microscopy Analysis
(EPA-600/M4-82-020; 600/R-93/116)
£3, Client Information:
Clean Environments 10803 Gulfdaie Suite 210 San Antonio, Texas 78216
Phone: 210-349-7242 Fax: 210-349-1132 E-Mail: cei@cleanenvironments.com
Project:
Ft. Hood, Building 32010
Job: CEI11.215
Attn: Ray Keeble
Date Analyzed: April 2,2011
Date Received: March 25, 2011
Microscope: Olympus-CH-40 Analysis Time Requested: 4-Days
Sample#
TSI2-3
WG-1
WG-2
WG-3
FT-1
FT-2
FT-3
Mech. Rm.
TSI-1
Mech. Rm.
TSI-2
Layer B
A
A
B
A
B
A
Sample Description Yellow Insulation
Gray Window Glazing
Brown Floor Tile
Black Mastic
White Mastic Wrapping
Yellow Insulation
White Mastic Wrapping
Homo- Geneous
(Y/N)
YES
YES
YES
YES
YES
YES
YES
Asbestos Detected?
Yes/No
NO
YES
NO
YES
NO
NO
NO
Asbestos Mineral Percent
None Detected
5% Chrysotile
Not Analyzed Positive Stop
None Detected
5% Chrysotile
Not Analyzed Positive Stop
None Detected
None Detected
None Detected
Non-Asbestos Fibers
100% Fiberglass
20% Cellulose 20% Fiberglass
100% Fiberglass
20% Cellulose 20% Fiberglass
Non-Fibrous Material
95% Other
100% Other
95% Other
60% Other
60% Other
NVLAP # 200784-0
DSHS # 300373 Control # 95392
Notes:
Some samples (floor tiles, surfacing, etc.) may contain fibers too small loo be detectable by PLM. TEM Chalfield analysis of bull; material is recommended in this case. All asbestos percentages are based on calibrated visual estimates traceable to NIST standards for regulated asbestos types. Analysts' percentages fall within a range of acceptable percentages, depending on the actual concentration of asbestos Tins lest reports relates only lo the items tested Neither NVLAP nor EPA accreditation implies endorsement by any US Government agency. This report may not be reproduced except in full without written permission from Environmental Analytical Services
These results are submitted pursuant to EAS current terms and condition of sale, including the company's standard warranty and limitation of liability provisions and no responsibility or liability is assumed for the manner ill which the results are used or interpreted Unless notified in wriling to return the samples covered by this report, EAS will store the samples for a period of ninety (90) days before discarding Percent ranges reported are estimates and not absolute percent range values
Services, L-LC
13201 Northwest Freeway Suite 503 Houston, Texas 77040
Phone: 713-343-4017/Fax: 713-934-9942 E-Mail:easlabs@aol.com
Polarized Light Microscopy Analysis
(EPA-600/M4-82-020; 600/R-93/116)-C^
Client Information:
Clean Environments 10803 Gulfdale Suite 210 San Antonio, Texas 78216
Phone: 210-349-7242 Fax: 210-349-1132 E-Mail: cei@cleanenvironments.com
Project:
Ft. Hood, Building 32010
Job: CEI11.215
Attn: Ray Keeble
Date Analyzed: April 2, 2011
Date Received: March 25, 2011
Microscope: Olympus-CH-40 Analysis Time Requested: 4-Days
Sampled Mech. Rm.
TSI-2
Mech. Rm.
TSI-3
Mech. Rm.
SR-1
Mech. Rm.
SR-2
Mech. Rm.
SR-3
Mech. Rm.
JC-1
Mech. Rm.
JC-2
Mech. Rm.
JC-3
Layer B
A
B
A
A
A
A
A
A
Sample Description Yellow Insulation
White Mastic Wrapping
Yellow Insulation
White/Brown Sheetrock
White/Brown Sheetrock
White/Brown Sheetrock
White Joint Compound
White Joint Compound
White Joint Compound
Homo- Geneous
(Y/N)
YES
YES
YES
YES
YES
YES
YES
YES
YES
Asbestos Detected?
Yes/No
NO
NO
NO
NO
NO
NO
NO
NO
NO
Asbestos Mineral Percent
None Detected
None Detected
None Detected
None Detected
None Detected
None Detected
None Detected
None Detected
None Detected
Non-Asbestos Fibers
100% Fiberglass
20% Cellulose 20% Fiberglass
100% Fiberglass
30% Cellulose
30% Cellulose
30% Cellulose
2% Cellulose
2% Cellulose
2% Cellulose
Non-Fibrous Material
60% Other
70% Other
70% Other
70% Other
98% Other
98% Other
98% Other
NVLAP # 200784-0
DSHS # 300373 Control # 95392
Notes:
Some samples (floor tiles, surfacing, etc.) may contain fibers too small too be delectable by PLM. TEM Chatfield analysis of bulk material is recommended in this case. All asbestos percentages are based on calibrated visual estimates traceable to NIST standards for regulated asbestos types. Analysts' percentages fall within a range of acceptable percentages, depending on the actual concentration of asbestos.
This lest reports relates only to the items tested. Neither NVLAP nor EPA accreditation implies endorsement by any US Government agency. This report may not be reproduced except in full without written permission from Environmental Analytical Services.
These results are submitted pursuant to EAS current terms and condition of sale, including the company's standard warranty and limitation of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted Unless notified in writing to return the samples covered by this report, EAS will store the samples for a period of ninety (90) days before discarding. Percent ranges reported are estimates and not absolute percent range values.
^ c^U
1234567890 1234567890 1234567890 1234567890 1234567890
123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789
BUILDING 32008- FLOOR PLAN
Fort Hood, Texas 76544
Clean Environments, Inc.
10803 Gulfdale, Suite 210 San Antonio, Texas 78216 CEI Project: 8995
ACM LOCATION PLAN and LEGEND
4/14/2011 Scale: N.T.S.
Suspect building materials tested POSITIVE for asbestos fibers.
Window Caulk
12345678 12345678 12345678 12345678
1234567 1234567 1234567 1234567 Wallboard and Joint Compound
White Vinyl Tile with Black Mastic 1234567 1234567 1234567 1234567
Sprayed-On Acoutstical Ceiling Texture
SHOP AREA
STORAGE
TOOLS
MECHANICAL
ROOM
RR
123456789 123456789 123456789 123456789 123456789
White Vinyl Tile w/ Black Mastic is POSITIVE for asbestos fibers.
NOTE:
12345678901 12345678901 12345678901 12345678901 12345678901 12345678901
ALL Exterior WINDOW CAULK is POSITIVE for asbestos fibers.
NOTE:
12345678901 12345678901 12345678901
123456789012345 123456789012345 123456789012345 123456789012345 123456789012345 123456789012345 123456789012345
MAINTENANCE
OFFICE
File details come from the government source that posted it. Updated .