This asbestos survey report documents the findings of an inspection conducted at Building 32010 on Fort Hood Army Base in preparation for renovation work. The survey identified black mastic under brown vinyl floor tiles, wallboard joint compound throughout the building, and window caulk and glazing containing asbestos. These asbestos-containing materials will require removal by a licensed abatement contractor according to applicable regulations prior to renovation given their presence in areas that may be disturbed. Solicitation W91151-23-B-0020 is for the renovation of Building 32010 at Fort Hood and will require the contractor to remove identified asbestos-containing materials during the project in accordance with applicable standards.

View the file

Other files for this federal contract opportunity

Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Clean Environments, inc.

Industrial Hygiene & Environmental Consultants

April 6, 2011

Sonny Gomez Kickapoo Empire, LLC 1003 Paulson Drive San Antonio, Texas 78219

RE: Asbestos Survey-DSHS Notification Building 32010 Fort Hood Army Base Fort Hood, Texas 76544 CEI Project N2: 8997

Dear Mr. Gomez:

An asbestos survey was conducted at the referenced property on March 24, 2011. The survey was accomplished by Mr. Ray Keeble, Asbestos Inspector, Texas DSHS License N2 60-2505, working with Mr Craig Nelson, Individual Asbestos Consultant, DSHS License N2 10-5726 of Clean Environments, Inc Asbestos Consultant Agency, DSHS License N2 10-0005. The ACBM survey was conducted in accordance with the EPA Guidance for Controlling Asbestos-Containing Materials in Buildings (EPA 560/5-85-024) June 1985 and the Texas Asbestos Health Protection Rules (25 TAC 295) March 2003, which requires that an asbestos survey be accomplished prior to demolition, renovation, and/or alterations that include the demolition of interior building materials and/or remodeling for any commercial structure.

The asbestos survey was limited to readily accessible building materials inside the building, unless otherwise noted. No destructive sampling was accomplished. Asbestos surveys accomplished for renovation or demolition activities are generally limited to materials identified (by the owner representative) as materials that will be disturbed during renovation or demolition activities. If any suspect asbestos materials, not identified in this survey, are uncovered during any demolition or renovation activity, please contact Clean Environments, Inc. immediately for further assessment.

BACKGROUND

Construction materials containing asbestos have been used extensively in buildings. Asbestos possesses excellent properties for fireproofing and insulation materials. Asbestos may be found in: (1) cement products; (2) spray applied or trowel applied materials on ceiling, walls, and other surfaces; (3) insulation on pipes', boilers, tanks, ducts, and other equipment; (4) vinyl floor tiles; (5) roofing felts; (6) flooring coatings- and (7) other miscellaneous products. Friable asbestos material is any materials that contain more than 1 percent asbestos by weight, which can be crumbled, pulverized, or reduced to powder, when dry, by hand pressure. Some of these asbestos-containing materials are not considered friable now, but could become friable if not properly managed and maintained under an asbestos management program.

The concern about exposure to asbestos is based on evidence linking various respiratory diseases with occupational exposure in the shipbuilding, mining, milling, and fabricating industries. The presence of asbestos does not mean that there is a significant health risk to the property occupants. As long as asbestos-containing materials remain in good condition and are not disturbed, exposure is unlikely.

Through proper control of building operations and maintenance activities, disturbance or damages to asbestos-containing materials in buildings are minimized, thus limiting the occupant's exposure to

10803 Gulfdale, Suite 210 • San Antonio, Texas 78216 • 210/349-7242 • Fax 210/349-1132

CLEAN ENVIRONMENTS, Inc.

Asbestos Survey for DSHS Notification Building 32010 Fort Hood Army Base Fort Hood, Texas 76544 airborne asbestos fibers. Building alterations and/or demolition require knowledge of what materials contain asbestos and if they will be removed or disturbed during the project. Under the Clean Air Act, the EPA has issued a National Emission Standard for Asbestos (40 CFR 61.140 - 61.156). This Standard regulates reporting requirements, work practices, waste disposal, and emissions from facility modification and/or demolition operations. The Standard applies only to materials containing more than 1% friable asbestos. Asbestos containing material according to the State of Texas Asbestos Health Rules is any building material containing greater than 1% asbestos.

Initially, a visual walk-thru inspection was conducted on the building. Based on this initial survey, areas were identified for physical assessment and bulk sample analysis. Then a detailed inspection was accomplished together with bulk sampling, as necessary. Material sampling conforms to the requirements in the 40 CFR 763.88. The sampling methods and strategies are outlined below for the three basic classifications of asbestos materials: friable surfacing materials, thermal system insulation, and miscellaneous material. The sampling scheme Clean Environments utilizes for selecting sampling locations in buildings is the EPA method identified in their document, "Asbestos in Buildings: Simplified Sampling Scheme for Friable Materials," EPA 560/5-85-030a, October 1985. Samples are selected according to homogenous areas. "Homogenous area" means an area of surfacing material, thermal system insulation, and miscellaneous asbestos materials that is uniform in color and texture, construction/application date and general appearance. At least three randomly distributed samples are collected from each homogeneous thermal insulation system. Samples are also collected on patched and fitting areas of thermal system insulation. At least one sample is collected in homogeneous miscellaneous materials. The miscellaneous materials, which are most likely sampled in buildings, are ceiling and floor tiles.

Revisions to the asbestos National Emissions Standard for Hazardous Air Pollutants (NESHAP) were promulgated on November 20, 1990. These include a requirement to point count in order to quantify asbestos in samples where the content is below 10%. The intent of the revision is to improve quantitative analysis of asbestos for all applications. Samples where no asbestos is detected do not have to be point counted. If asbestos is detected, but is less than 10%, the owner or operator of the building may elect to

(1) assume the amount to be greater than 1% and treat the material as asbestos or (2) require verification of the amount by point counting. It is a Clean Environments, Inc. policy to treat all samples with detectable levels of asbestos fibers as asbestos-containing material and to recommend a point count, using a mechanical stage and random point reticule, for all samples found to be 1% or less. The owner or operator of the building may elect to conduct further testing of samples that range from greater than 1% to 10% before treating the material as asbestos.

FINDINGS

Renovation and/or demolition are scheduled at the above referenced location. The building has a brick and glass facade with a tar & gravel roof. The walls & ceilings are sheetrock bound by joint compound.

The floors were found to have brown vinyl tiles with black mastic in the SVC SEC office adhered to the concrete foundation. The windows were found to have caulk or glazing throughout the building. Thermal systems insulation (TSI) was observed in the mechanical room and in building. The exterior of the structure has a tar & gravel built up roof. Ten suspect ACBMs were identified and sampled for a total of 30 samples.

CLEAN ENVIRONMENTS, Inc.

Asbestos Survey for DSHS Notification Building 32010 Fort Hood Army Base Fort Hood, Texas 76544

The samples were analyzed at Environmental Analytical Services, L.L.C., Asbestos Laboratory, Houston, Texas, DSHS License N2 30-0373, using polarized light microscopy (PLM) analysis.

PLM laboratory analysis indicates that the following materials are positive for asbestos:

• Black mastic (5%) under brown vinyl tile in the SVC SEC office. There is approximately

120 square feet of vinyl tile in the office.

• Wallboard/joint compound (3%) throughout the building. There is approximately 8,000 square feet of wallboard/joint compound in the building.

• Window caulk/glazing (5%) on all windows.

All other suspect materials are negative for asbestos fibers.

The client requested that point count analysis not be performed.

RECOMMENDATIONS

The black mastic under brown vinyl tile, wallboard/joint compound and window caulk/glazing must be removed prior to any operations that may disturb the asbestos fibers in the material. Abatement must be accomplished according to the guidelines set forth in 40 CFR 61, the National Emission Standard for Hazardous Air Pollutants (NESHAP) and/or DSHS, Texas Asbestos Health Protection Rules, March 2003. This includes removal by a licensed asbestos abatement contractor and project management by a licensed asbestos consultant firm.

We will be happy to answer any questions concerning the report. It has been a pleasure to work with you on this project. We look forward to being of continued service to you.

Very tarty yours, CrVrg'Nelsot/ Individual Asbestos Consultant DSHS License N2 10-5726

Attached: Chain of Custody Laboratory Results Sample locations

Clean Environments, Inc.

10803 Gulfdale, Suite 210 San Antonio, Texas 78216

"": £ 5 3 e n l - 13201 Northwest Freewav Suite 503

. Scrvi«.s, u-c Houston, Texas 77040 , g ^ ' (713)343-4017 • Fax:(713)934-9942 trr~-?' easlabs@aol.com • LSOAcct* 123757

CHAIN OF CUSTODY

Page_/_ of ^

Sample Type & Quantity:

Project No.

& Name

Ft Hood, Bldg. 32010

: J&, 4r TURNAROUND: LJ Clean Environments STANDARD R U S H Y | OTHER: PLM - Positive Stop Contact Person: /£. /(*<!>[a. p h o n e : 210-349-7242 Fax: 210-349-i"i32

E-Mail Results to: cei@cteanenvironments.com and ibs@cleanenvironments.com Comments:

SAMPLE No.

Tsz 1-3

Tc /-/

Tc y-2.

Tc j-3>

Zfci- 1

Tc'z-3

SAMP

(m

SAMPLE:

LE DESCRIPTION

a ten a 1 type, color, etc.)

Yellow tile w/black mastic

£/~ /^f'^ok/sv ~yo,',*JJ Co^"!/3, SAMPLE LOCATION

(Room, Floor, Wall, Window, Door, etc.)

SAMPLE: Front Office - North Wall - flooring

I

1 :

F ria bl e

(F

No n-

F ria bl e

(NF

(£)l NF

IS? 1 NF

£?l NF

<£) 1 NF

[f)l NF

<£)/ NF

dD / NF

CD/ NF

OL?1 NF

CONDITION

(Circle Most Applicable)

Good/ Fair ^-Poo^

Good/ Fair /£o$>P Significant Damaged

Good/Fair/ffiS?

Significant Damaged

Good/Fair i£oo?

Significant Damaged

Good/ Fair ifo^r1

Significant Damaged

Good/Fair/c^oj?

Significant Damaged

Good/Fair ^Poj?

Significant Damaged

Good / Fair / ?20^ Significant Damaged

Good / Fair / PaS?

Significant Damaged

E st im at ed Sq

Ftg

Li ne ar

F t.

:-^*rA*/jr£ Accepted By: ^VVvJU^-i^ I' ^^WjJL^ ^-ZS-\( (Signature, Date, and Time)

Relinquished By fc^l (Signature, Date, and Time)

Clean Environments, Inc.

San Antonio, Texas 78216

~t Environmental ' Anal-jtical j.^JUniut, vu. Houston, Texas 77040 JA§ (713) 343-4017 • Fax: (713) 934-9942 %~~^ easlabs@aol.com • LSOAcct* 123757

13201 Northwest Freeway Suite 503

CHAIN OF CUSTODY

Page X of LJ

Sample Type & Quantity:

Project No.

& Name;

Ft. Hood, Bldg. 32010

TURNAROUND: D Clean Environments STANDARD • R U S H g f OTHER: <3 JO V PLM - Positive Stop Contact Person: KZ e / / l

Phone: 210-349-724? Fax: 210-349-113?

E-Mail Results to: cei@fcleanenwronments.nom and jbs@cleanenvironmente mm Comments:

SAMPLE No. SAMPLE DESCRIPTION (material type, color, etc.)

SAMPLE: Yellow tile w/black mastic

SAMPLE LOCATION

(Room, Floor, Wall, Window, Door, etc.)

SAMPLE: Front Office - North Wall - flooring

CONDITION

(Circle Most Applicable)"S z *c

J~C 3 ' / " g / Z / > j r y^v - , / ^ / ^ .

JC3-

Jc 1-3

7S2T2-/ Good I Fair^^opt Significant DamagedCOsstte* U//L4P f/fz ZWSfl-

I NF

15ZZ-2 O / NF Good/ Fair l^ot Significant Damaged

TSZ2-3 (£)l NF Good/Fair/&oc5 Significant Damaged

Pi NF tk-:J QQ/ <%i(/'-l .

IAJ£-2

<Pl NF Good / FaitiEnor ^StgiflTlcant-Damaged)U/C-^

Relinquished By: ^ ^ ^ * ^ JL-^d~eJ*^ Accepted By:

fSk Clean Environments, Inc.

San Antonio, Texas 78216

Environmental Analytical tervictft. U-6

13201 Northwest Freeway Suite 503

Houston, Texas 77040

(713)343-4017 • Fax:(713)934-9942 easlabs@aol.com • LSO Acct # 123757

CHAIN OF CUSTODY

Page 3 of V

Sample Type

& Quantity ?

Project No.

& Name:

Ft. Hood, Bldg. 32010

EAS

Job#

TURNAROUND: D Clean Environments STANDARD Q R U S H fffiOTHER: <3 {& *f Contact Person: A ' K*-*•{,£t- Phone: 210-349-7242 Fax: 210-349-1132

E-Maii Results to: cei@cleanenvironments.com and ibs@cleanenvironments.com Comments:

PLM - Positive Stop

SAMPLE No.

rr-i rr-z

FT'3

TsX-l

/fecit- AS?

SA-/

SAMPLE DESCRIPTION

(material type, color, etc.)

SAMPLE: Yellow tile w/black mastic grto^^ flo^ 7 ^ yilfcir/VAT* i .

i1

SAMPLE LOCATION

(Room, Floor, Wall, Window, Door, etc.)

SAMPLE: Front Office - North Wall - flooring

SVC Sz c of/r, c A

Ii

F ria bl e

(F

N on

F ria bl e

<N F)

F \(SP

F 1®

F l(tf£)

£> / NF

&> 1 NF

tf> 1 NF

£>\ NF

£> 1 NF

@ 1 NF

CONDITION

(Circle Most Applicable)

Good / Fair^Poojy

Significant Damaged

Good/Fair /€S?

Significant Damaged

Good/ Fair IQ^> Significant Damaged

Good /Fair/ £5^?

Significant Damaged

Good /Fair l ^ r Significant Damaged

Good/ Fair/ fjoj?

Significant Damaged

Good / Fair/Poor ^•Oiynifi&ant Damaged^

Good / Fairi£o_or Significant Damage^

Good / Fair/Poor Sigjiifieant-Bamagecp

E st im at ed S q.

F ig

Li ne ar F t.

Relinquished By: j 7 ^ ^ £ ^ JrAy>- 1-^V-// (Signature, Date, and Time)

Accepted By:

= ! Clean Environments, Inc. , I tZ7™ 13201 Northwest Freeway Suite 503 ^ S M V J O * , u ^ Houston, Texas 77040 iK4 (713) 343-4017 . Fax: (713) 934-9942 easlabs@aol.com • LSOAcct# 123757

CHAIN OF CUSTODY

Page_$/_ of V

10803 Gulfdale, Suite 210 San Antonio, Texas 78216

Sample Type

& Quantity:

Project No.

&Name:

ff //oe>J 4/^ . 3 Z&/&

EAS

Job#

RUSH fD?fOTHER: <J JOTURNAROUND: [

Contact Person: j£. /C- l <•/ / -*•

E-Mail Results to: cei@cleanenvironments.com and jbs(5),cleanenvironments.com Comments:

Clean Environments STANDARD

Phone: 210-349-7242 Fax: 210-349-1132

PLM - Positive Stop

SAMPLE No.

SV-Lck. /loo*"

•re-1 sun J^c-I Slick, SAMPLE DESCRIPTION

(material type, color, etc.)

SAMPLE: Yellow tile w/black mastic

SAMPLE LOCATION

{Room, Floor, Wall, Window, Door, etc.)

SAMPLE: Front Office - North Wall - flooring

/vtcAx^crfl A-ofs+i rt;t>'^*) /xtftt

Fr ia bl e

(F

N on

F ria bl e

(N F)

&l NF

<P / NF

& 1 NF

F / NF

F / NF

F / NF

F / NF

F / NF

F / NF

CONDITION

(Circle Most Applicable)

Good /Fair /Poor

Good / Fair/Papr gjgrrificant DimagSS7

Good/ Fair /j^oor Significant Damages'

Good/Fair/Poor Significant Damaged

Good/Fair/Poor Significant Damaged

Good/Fair/Poor Significant Damaged

Good/Fair/Poor Significant Damaged

Good/Fair/Poor Significant Damaged

Good /Fair /Poor Significant Damaged

E st im at ed Sq

Ft g.

Li ne ar F t.

Relinquished By: ^ 7 ^ ^ , fr^-~ Accepted By:

(Signature, Date, and Time) (Signature, Date, and Time)

~r environmental \ Analytical . Services, LU1

13201 Northwest Freeway Suite 503 Houston, Texas 77040

Phone: 713-343-4017 / Fax: 713-934-9942 E-Mail:easlabs@aol.com

Polarized Light Microscopy Analysis (EPA-600/M4-82-020; 600/R-93/116)^s

Client Information:

Clean Environments 10803 Gulfdale Suite 210 San Antonio, Texas 78216

Phone: 210-349-7242 Fax: 210-349-1132 E-Mail: cei@cleanenvironments.com

Project:

Ft. Hood, Building 32010

Job: CEI11.215

Attn: Ray Keeble

Date Analyzed: April 2, 2011

Date Received: March 25, 2011

Microscope: Olympus-CH-40 Analysis Time Requested: 4-Days

Sampled

TSI1-1

TSI1-2

TSI1-3

JC1-1

JC1-2

JC1-3

JC2-1

Layer A

B

A

B

A

B

A

A

Sample Description White Mastic

Wrapping

Yellow Insulation

White Mastic Wrapping

Yellow Insulation

White Mastic Wrapping

Yellow Insulation

White Joint Compound

Tan Joint Compound

Homo- Geneous

(Y/N)

YES

YES

YES

YES

YES

YES

YES

YES

Asbestos Detected?

Yes/No

NO

NO

NO

NO

NO

NO

YES

NO

Asbestos Mineral Percent

None Detected

None Detected

None Detected

None Detected

None Detected

None Detected

3% Chrysotile

Not Analyzed Positive Stop

None Detected

Non-Asbestos Fibers

20% Cellulose 20% Fiberglass

100% Fiberglass

20% Cellulose 20% Fiberglass

100% Fiberglass

20% Cellulose 20% Fiberglass

100% Fiberglass

2% Cellulose

Non-Fibrous Material

60% Other

60% Other

60% Other

97% Other

98% Other

NVLAP # 200784-0

DSHS # 300373 Control # 95392

Page 1 of4 Notes:

Some samples (floor tiles, surfacing, etc.) may contain fibers too small too be detectable by PLM. TEM Chalfield analysis of bulk material is recommended in this case. All asbestos percentages are based on calibrated visual estimates traceable to NIST standards for regulated asbestos types. Analysts' percentages fall within a range of acceptable percentages, depending on the actual concentration of asbestos.

This test reports relates only to the items tested. Neither NVLAP nor EPA accreditation implies endorsement by any US Government agency. This report may not be reproduced except in full without written permission from Environmental Analytical Services.

These results are submitted pursuant to EAS current terms and condition of sale, including the company's standard warranty and limitation of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return the samples covered by this report, EAS will store the samples for a period of ninety (90) days before discarding. Percent ranges reported are estimates and not absolute percent range values.

Analyzed by: Approved Signatory:

Arthur Hernandez Lisa Crain

Environmental

Services, \XC

13201 Northwest Freeway Suite 503 Houston, Texas 77040

Phone: 713-343-4017 / Fax: 713-934-9942 E-Mail:easlabs@aol.com

Polarized Light Microscopy Analysis

(EPA-600/M4-82-020; 600/R-93/116)

Client Information:

Clean Environments 10803 Gulfdale Suite 210 San Antonio, Texas 78216

Phone:210-349-7242 Fax: 210-349-1132 E-Mail: cei@eleanenvironments.com

Project:

Ft. Hood, Building 32010

Job:CEI11.215

Attn: Ray Keeble

Date Analyzed: April 2,2011

Date Received: March 25, 2011

Microscope: Olympus-CH-40 Analysis Time Requested: 4-Days

Sampled

JC2-2

JC2-3

JC3-1

JC3-2

JC3-3

TSI2-1

TSI2-2

TSI2-3

Layer A

A

A

A

B

A

B

A

Sample Description Tan Joint Compound

Tan Joint Compound

White Joint Compound

Gray Mastic Wrapping

Yellow Insulation

Gray Mastic Wrapping

Yellow Insulation

Gray Mastic Wrapping

Homo- Geneous

(Y/N)

YES

YES

YES

YES

YES

YES

YES

YES

Asbestos Detected?

Yes/No

NO

NO

YES

NO

NO

NO

NO

NO

Asbestos Mineral Percent

None Detected

None Detected

3% Chrysotile

Not Analyzed Positive Stop

None Detected

None Detected

None Detected

None Detected

None Detected

Non-Asbestos Fibers

2% Cellulose

2% Cellulose

20% Cellulose 20% Fiberglass

100% Fiberglass

20% Cellulose 20% Fiberglass

100% Fiberglass

20% Cellulose 20% Fiberglass

Non-Fibrous Material

98% Other

98% Other

97% Other

60% Other

60% Other

60% Other

NVLAP# 200784-0

DSHS # 300373 Control # 95392

Notes:

Some samples (floor tiles, surfacing, etc ) may contain fibers too small too be delectable by PLM. TEM Chalfield analysis of bulk material is recommended in this case. All asbestos percentages are based on calibrated visual estimates Iraceable to NIST slandards for regulated asbestos types. Analysis' percentages fall within a range of acceptable percentages, depending on the actual concentralion of asbestos This test reports relates only to Ihe items tested. Neither NVLAP nor EPA accreditation implies endorsement by any US Government agency. This report may not be reproduced except in full without written permission from Environmental Analytical Services.

These results are submitted pursuant to EAS current terms and condition of sale, including the company's standard warranty and limitation of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted. Unless notified in writing to return Ihe samples covered by this report, EAS will store the samples for a period of ninety (90) days before discarding Percent ranges reported are estimates and not absolute percent range values.

Analyzed by: Approved Signatory:^->--

^ ^ Services, li~C

13201 Northwest Freeway Suite 503 Houston, Texas 77040

Phone: 713-343-4017/Fax: 713-934-9942 E-Mail:easlabs@aol.com

Polarized Light Microscopy Analysis

(EPA-600/M4-82-020; 600/R-93/116)

£3, Client Information:

Clean Environments 10803 Gulfdaie Suite 210 San Antonio, Texas 78216

Phone: 210-349-7242 Fax: 210-349-1132 E-Mail: cei@cleanenvironments.com

Project:

Ft. Hood, Building 32010

Job: CEI11.215

Attn: Ray Keeble

Date Analyzed: April 2,2011

Date Received: March 25, 2011

Microscope: Olympus-CH-40 Analysis Time Requested: 4-Days

Sample#

TSI2-3

WG-1

WG-2

WG-3

FT-1

FT-2

FT-3

Mech. Rm.

TSI-1

Mech. Rm.

TSI-2

Layer B

A

A

B

A

B

A

Sample Description Yellow Insulation

Gray Window Glazing

Brown Floor Tile

Black Mastic

White Mastic Wrapping

Yellow Insulation

White Mastic Wrapping

Homo- Geneous

(Y/N)

YES

YES

YES

YES

YES

YES

YES

Asbestos Detected?

Yes/No

NO

YES

NO

YES

NO

NO

NO

Asbestos Mineral Percent

None Detected

5% Chrysotile

Not Analyzed Positive Stop

None Detected

5% Chrysotile

Not Analyzed Positive Stop

None Detected

None Detected

None Detected

Non-Asbestos Fibers

100% Fiberglass

20% Cellulose 20% Fiberglass

100% Fiberglass

20% Cellulose 20% Fiberglass

Non-Fibrous Material

95% Other

100% Other

95% Other

60% Other

60% Other

NVLAP # 200784-0

DSHS # 300373 Control # 95392

Notes:

Some samples (floor tiles, surfacing, etc.) may contain fibers too small loo be detectable by PLM. TEM Chalfield analysis of bull; material is recommended in this case. All asbestos percentages are based on calibrated visual estimates traceable to NIST standards for regulated asbestos types. Analysts' percentages fall within a range of acceptable percentages, depending on the actual concentration of asbestos Tins lest reports relates only lo the items tested Neither NVLAP nor EPA accreditation implies endorsement by any US Government agency. This report may not be reproduced except in full without written permission from Environmental Analytical Services

These results are submitted pursuant to EAS current terms and condition of sale, including the company's standard warranty and limitation of liability provisions and no responsibility or liability is assumed for the manner ill which the results are used or interpreted Unless notified in wriling to return the samples covered by this report, EAS will store the samples for a period of ninety (90) days before discarding Percent ranges reported are estimates and not absolute percent range values

Services, L-LC

13201 Northwest Freeway Suite 503 Houston, Texas 77040

Phone: 713-343-4017/Fax: 713-934-9942 E-Mail:easlabs@aol.com

Polarized Light Microscopy Analysis

(EPA-600/M4-82-020; 600/R-93/116)-C^

Client Information:

Clean Environments 10803 Gulfdale Suite 210 San Antonio, Texas 78216

Phone: 210-349-7242 Fax: 210-349-1132 E-Mail: cei@cleanenvironments.com

Project:

Ft. Hood, Building 32010

Job: CEI11.215

Attn: Ray Keeble

Date Analyzed: April 2, 2011

Date Received: March 25, 2011

Microscope: Olympus-CH-40 Analysis Time Requested: 4-Days

Sampled Mech. Rm.

TSI-2

Mech. Rm.

TSI-3

Mech. Rm.

SR-1

Mech. Rm.

SR-2

Mech. Rm.

SR-3

Mech. Rm.

JC-1

Mech. Rm.

JC-2

Mech. Rm.

JC-3

Layer B

A

B

A

A

A

A

A

A

Sample Description Yellow Insulation

White Mastic Wrapping

Yellow Insulation

White/Brown Sheetrock

White/Brown Sheetrock

White/Brown Sheetrock

White Joint Compound

White Joint Compound

White Joint Compound

Homo- Geneous

(Y/N)

YES

YES

YES

YES

YES

YES

YES

YES

YES

Asbestos Detected?

Yes/No

NO

NO

NO

NO

NO

NO

NO

NO

NO

Asbestos Mineral Percent

None Detected

None Detected

None Detected

None Detected

None Detected

None Detected

None Detected

None Detected

None Detected

Non-Asbestos Fibers

100% Fiberglass

20% Cellulose 20% Fiberglass

100% Fiberglass

30% Cellulose

30% Cellulose

30% Cellulose

2% Cellulose

2% Cellulose

2% Cellulose

Non-Fibrous Material

60% Other

70% Other

70% Other

70% Other

98% Other

98% Other

98% Other

NVLAP # 200784-0

DSHS # 300373 Control # 95392

Notes:

Some samples (floor tiles, surfacing, etc.) may contain fibers too small too be delectable by PLM. TEM Chatfield analysis of bulk material is recommended in this case. All asbestos percentages are based on calibrated visual estimates traceable to NIST standards for regulated asbestos types. Analysts' percentages fall within a range of acceptable percentages, depending on the actual concentration of asbestos.

This lest reports relates only to the items tested. Neither NVLAP nor EPA accreditation implies endorsement by any US Government agency. This report may not be reproduced except in full without written permission from Environmental Analytical Services.

These results are submitted pursuant to EAS current terms and condition of sale, including the company's standard warranty and limitation of liability provisions and no responsibility or liability is assumed for the manner in which the results are used or interpreted Unless notified in writing to return the samples covered by this report, EAS will store the samples for a period of ninety (90) days before discarding. Percent ranges reported are estimates and not absolute percent range values.

^ c^U

1234567890 1234567890 1234567890 1234567890 1234567890

123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789 123456789

BUILDING 32008- FLOOR PLAN

Fort Hood, Texas 76544

Clean Environments, Inc.

10803 Gulfdale, Suite 210 San Antonio, Texas 78216 CEI Project: 8995

ACM LOCATION PLAN and LEGEND

4/14/2011 Scale: N.T.S.

Suspect building materials tested POSITIVE for asbestos fibers.

Window Caulk

12345678 12345678 12345678 12345678

1234567 1234567 1234567 1234567 Wallboard and Joint Compound

White Vinyl Tile with Black Mastic 1234567 1234567 1234567 1234567

Sprayed-On Acoutstical Ceiling Texture

SHOP AREA

STORAGE

TOOLS

MECHANICAL

ROOM

RR

123456789 123456789 123456789 123456789 123456789

White Vinyl Tile w/ Black Mastic is POSITIVE for asbestos fibers.

NOTE:

12345678901 12345678901 12345678901 12345678901 12345678901 12345678901

ALL Exterior WINDOW CAULK is POSITIVE for asbestos fibers.

NOTE:

12345678901 12345678901 12345678901

123456789012345 123456789012345 123456789012345 123456789012345 123456789012345 123456789012345 123456789012345

MAINTENANCE

OFFICE

File details come from the government source that posted it. Updated .