Attachment_0015_--_Tech_Exhibit_1.3_--_Cooling_Towers.pdf

PDF 8 KB Posted

Attached to
Mechanical Services / HVAC
Solicitation number
W52P1J-19-R-5002
Issued by

About this file

Attachment 0015 -- TE 1.3

View the file

Other files

File Type Posted
W52P1J19C5009_--_final.pdf PDF
Amendment_0004.pdf PDF
Attachment_0028_--_Tech_Exhibit_6.0_--_Performance_Requirements_Summary_--_27JUN2019.xlsx XLSX spreadsheet
Attachment_0007_--_Price_Matrix_--_07JUN2019.xlsx XLSX spreadsheet
Amendment_0003.pdf PDF
Attachment_0025_--_Tech_Exhibit_3.0_--_PM_Requirements_--_06JUN2019.xls XLS spreadsheet
Attachment_0007_--_Price_Matrix_--_05JUN2019.xlsx XLSX spreadsheet
W52P1J-19-R-5002-0002.pdf PDF
Attachment_0031_--_Anticipated_Subcontractors_Form_--_28MAY2019.pdf PDF
Amendment_0001_to_W52P1J19R5002.pdf PDF
Attachment_0001_--_PWS_--_30MAY2019.pdf PDF
Attachment_0030_--_B348_Photos_--_22MAY2019.pdf PDF
Attachment_0029_--_Site_Visit_Attendee_List_--_22MAY2019.pdf PDF
Attachment_0010_--_Past_Performance_Questionnaire_--_HVAC-Mechanical_Services_Solicitation.docx DOCX document
Attachment_0006_--_RIA_Access_Control_Record_Check_Form_--_HVAC-Mechanical_Services_Solicitation.pdf PDF
Attachment_0028_--_Tech_Exhibit_6.0_--_Performance_Requirements_Summary.xls XLS spreadsheet
Attachment_0020_--_Tech_Exhibit_1.8_--_Local_Water_Composition.pdf PDF
Attachment_0007_--_Price_Matrix_--_29APR2019.xlsx XLSX spreadsheet
Attachment_0012_--_Tech_Exhibit_1.0_--_Comfort_Cooling_Chillers.pdf PDF
Attachment_0026_--_Tech_Exhibit_4.0_--_Predictive_PM_Requirements.pdf PDF
Attachment_0004_--_Government_Furnished_Property_--_HVAC-Mechanical_Services_Solicitation.pdf PDF
Attachment_0001_--_PWS_--_01MAR2019.pdf PDF
Attachment_0008_--_Accessing_Secure_Attachments_--_HVAC-Mechanical_Services_Solicitation.DOCX DOCX document
W52P1J-19-R-5011_--_Solicitation__--_10MAY2019.pdf PDF
Attachment_0017_--_Tech_Exhibit_1.5_--_Refrigeration_Removal_Certifications.pdf PDF
Attachment_0027_--_Tech_Exhibit_5.0_--_Historical_DMO_PWO_Data.pdf PDF
Attachment_0013_--_Tech_Exhibit_1.1_--_YRCL_Chillers.pdf PDF
Attachment_0014_--_Tech_Exhibit_1.2_--_Dry_Coolers.pdf PDF
Attachment_0023_--_Tech_Exhibit_2.2_--_Equipment_Datebase_Input_Forms.xls XLS spreadsheet
Attachment_0003_--_SCA_Wage_Rates_--_26DEC2018.pdf PDF
Attachment_0016_--_Tech_Exhibit_1.4_--_Refrigerant_Log_Tally.xls XLS spreadsheet
Attachment_0018_--_Tech_Exhibit_1.6_--_Side_Stream_Filters.pdf PDF
Attachment_0009_--_Small_Business_Questionnaire_--_HVAC-Mechanical_Services_Solicitation.docx DOCX document
Attachment_0024_--_Tech_Exhibit_2.3_--_ODC_Equipment_Tracker.xlsx XLSX spreadsheet
Attachment_0005_--_TE_List_--_HVAC-Mechanical_Services_Solicitation.docx DOCX document
Attachment_0002_--_Davis_Bacon_Wage_Rates_--_03MAY2019.pdf PDF
Attachment_0019_--_Tech_Exhibit_1.7_--_Chiller_Heat_Exchanger_Evaluation.pdf PDF
Attachment_0025_--_Tech_Exhibit_3.0_--_PM_Requirements.xls XLS spreadsheet
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Standard Eq Name Manufacturer Model Serial Area Served Location Assigned To Date Installed Nominal Size Units Normal Operation Type Voltage Indoor Sump Fan HP # of Motors VFD Number of Sections CT Flow Rate GPM Fan CFM EWT F LWT F Wet Bulb Temp F Control Type Control Manufacturer Control Panel Remarks

CT-025-G-1 Evapco AT 19-56 M005168 WCCU-25-1-1,2 East Side Chiller 2002 100 Tons Cooling Season Induced Draft 460V - 3ph Yes 5.00 1 1 180 95 85 78 Electric Trane

CT-073-R-1 Evapco AT 112-518 5-134079 CWCC-73-1-1 Roof Chiller 2006 600 Tons Cooling Season Induced Draft 460V - 3ph Yes 40.00 1 VFD-073-1-1 1 1800 95 85 79 DDC/BACnet Delta CP-73-1-1

CT-114-1-1 Ceramic C. T. Co. CT-969 CT-969 CWCC-114-1-1 West Side Chiller 1982 800 Tons Cooling Season Induced Draft 460V - 3ph No 40.00 1 VFD-114-1-1 1 1900 95 85 79 DDC/BACnet Delta CP-114-1-2

CT-114-1-2 Ceramic C. T. Co. CT-969 CT-960 CWCC-114-1-2 East Side Chiller 1982 800 Tons Cooling Season Induced Draft 460V - 3ph No 40.00 1 VFD-114-1-2 1 1900 95 85 79 DDC/BACnet Delta CP-114-1-3

CT-131-G-1 Baltimore Air Coil 15176 U096547903 CWCC-131-B-1 North Side Chiller 2010 176 Tons Cooling Season Induced Draft 460V - 3ph Yes 10.00 1 VFD-131-B-4 1 450 95 85 78 DDC/BACnet Delta

CT-212-R-1 Marley NC II 89103-1384 CWCC-212-2-2 Roof Chiller 1985 200 Tons Cooling Season Draw-Thru 460V - 3ph Yes 15.00 1 1 900 98 85 75 DDC/Pneumatic Trane CP-211-2M-2

CT-212-R-2 Marley NC 222-411-31095-87 CWCC-212-2-1 Roof Chiller 1987 300 Tons Cooling Season Draw-Thru 460V - 3ph Yes 20.00 1 1 1150 95 85 75 DDC/Pneumatic Trane CP-211-2M-1

CT-212-R-3 Evapco AT 19-58 7-312007 CWCR-212-1-1 Roof Chiller 2007 15 Tons Year Round Operation Draw-Thru 460V - 3ph Yes 7.50 1 1 400 95 85 79 DDC/Pneumatic Trane Belt - 3B144

CT-212-R-4 Marley NC 221-111 Furnaces Roof Mfg. Grp. 1986 300 Tons Cooling Season Draw-Thru 460V - 3ph yes 1 1 95 85 DDC/ Elect

CT-212-R-5 Marley MD 221-222 Plating Shop Roof Mfg. Grp. 1986 300 Tons Cooling Season Draw-Thru 460V - 3ph yes 1 1 95 85 75 DDC/ Elect

CT-220-R-1 Baltimore Air Coil VXT10R 831137 Compressor System Roof Mfg. Grp. 1990 186 Tons Cooling Season Induced Draft 460V - 3ph Yes 10.00 200 Electric Honeywell

CT-227-R-1 Whaley WP1250-30 CT29006 Cooling Water Roof BasOps 2009 30 Tons Cooling Season Induced Draft 460V - 3ph Yes 2.00 1 1 90 6500 95 85 78 PLC NA

CT-332-G-1 Baltimore Air Coil PT2-0412A-1H-1 U095019401 CWCR-332-1-1 West Side of Bldg Chiller 2009 100 Tons Cooling Season Induced Draft 460V - 3ph Yes VFD-332-1-1 300 95 85 78 DDC/BACnet Delta

CT-348-R-1 Evapco AT 212-536 5-128510 CWCC-348-1-1&2 Roof Chiller 2006 1200 Tons Cooling Season Induced Draft 460V - 3ph Yes 40.00 2 VFD-348-1-2&3 2 3600 95 85 79 DDC/BACnet Delta CLP-348-1-2

CT-350-R-2 Marley NC311 014546-001-91 CWCS-350-1-1 Roof Chiller 1992 515 Tons Cooling Season Draw-Thru 230V - 3ph Yes 20.00 1 VFD-350-1S-1 1 1238 95 85 79 DDC/BACnet Delta CLP-350-1S-2