Attachment 0005 - PBA Tower 2 Inspection Report.pdf
PDF 23 MB Posted
- Attached to
- PBA Water Tank Cleaning, Painting, and Repair
- Solicitation number
- W519TC24B2001
About this file
This solicitation seeks proposals for water tank cleaning, painting, and repair services at Pine Bluff Arsenal in Arkansas. The Army Contracting Command - Rock Island is requesting these services in accordance with FAR Part 14. The contractor shall perform work in accordance with the attached performance work statement. This is a 100% set-aside for small businesses with a NAICS code of 238320. Interested contractors must visit the site by January 31, 2024 to be eligible for award. Firm fixed price proposals are due by the response date specified in the solicitation. The award of a subsequent contract is subject to availability of funds.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MIT DIVING AND COATING
Quadrant 1
Quadrant 1
Quadrant 1
Quadrant 1
Quadrant 1
Quadrant 1
SSPC Rating’s Key Description - Good Condition 10 - No Rusting, or <0.01% of surface is rusted 9 - Minor rusting, or <0.03% of surface is rusted 8 - Isolated rust, <.01% of surface is rusted
Description - Fair Condition 7 - Isolated rust, <.03% of surface is rusted 6 - Extensive rusting, <1% of surface is rusted 5 - Approximately 3% of the surface is rusted
Description - Poor Condition 4 - Approximately 10% of the surface is rusted 3 - Approximately 17% of the surface is rusted 2 - Approximately 33% of the surface is rusted 1 - Approximately 50% of the surface is rusted 0 - Approximately 100% of the surface is rusted
Quadrant 2
Exterior Upper Wall Panel Condition
Quadrant 3 Quadrant 4
Quadrant 2
Exterior Middle Wall Panel Condition
Quadrant 3 Quadrant 4
Quadrant 2
Exterior Lower Wall Panel Condition
Quadrant 3 Quadrant 4
Quadrant 2
Interior Upper Wall Panel Condition
Quadrant 3 Quadrant 4
Quadrant 2
Interior Middle Wall Panel Condition
Quadrant 3 Quadrant 4
Quadrant 2
Interior Lower Wall Panel Condition
Quadrant 3 Quadrant 4
Delamination Blistering
Chalking Staining
Cracking Pinholes
Cratering Sags/Runs
Additional Comments
Overall Coating Condition
Overall Coating Deficiency’s
Int. Roof Ext. Roof
Overall Weld Condition
Ext. Floor
Int. Roof Ext. Roof
Int. Floor Ext. Floor
Utility Name Date
Dive Control/Supervisor Diver/Inspector Tender
. Floor
Tower 2 Pine Bluff Arsenal 8/13/2020
Phoenix Murphy Benjamin Pisocki Nick Blumenblat
8 8 8 8
Good Good Good Good
8 8 8 8
Good Good Good Good
8 8 8 8
Good Good Good Good
8 8 8 8
Good Good Good Good
8 8 8 8
Good Good Good Good
8 8 8 8
Good Good Good Good
Good Good
Good Good
Exterior: Minor staining, chalking, and delamination. Less than one percent corrosion.
One large dent at the seven O'Clock.
Interior: Minor staining, sediment ranges from one inch to around eighteen inches.
Quadrant 1
Quadrant 1
Quadrant 1
Quadrant 1
Quadrant 1
Quadrant 1
Utility Name Date
Dive Control/Supervisor Diver/Inspector Tender
SSPC Rating’s Key Description - Good Condition 10 - No Rusting, or <0.01% of surface is rusted 9 - Minor rusting, or <0.03% of surface is rusted 8 - Isolated rust, <.01% of surface is rusted
Description - Fair Condition 7 - Isolated rust, <.03% of surface is rusted 6 - Extensive rusting, <1% of surface is rusted 5 - Approximately 3% of the surface is rusted
Description - Poor Condition 4 - Approximately 10% of the surface is rusted 3 - Approximately 17% of the surface is rusted 2 - Approximately 33% of the surface is rusted 1 - Approximately 50% of the surface is rusted 0 - Approximately 100% of the surface is rusted
Quadrant 2
Interior Roof Panel Condition
Quadrant 3 Quadrant 4
Quadrant 2
Exterior Roof Panel Condition
Quadrant 3 Quadrant 4
Quadrant 2
Internal Roof Support
Quadrant 3 Quadrant 4
Quadrant 2
Interior Floor Panel Condition
Quadrant 3 Quadrant 4
Quadrant 2
Exterior Floor Panel Condition
Quadrant 3 Quadrant 4
Quadrant 2
Support Columns
Quadrant 3 Quadrant 4
Overall Coating Condition
Int. Roof Ext. Roof
Int. Floor Ext. Floor
Overall Weld Condition
Int. Roof Ext. Roof
Int. Floor Ext. Floor
Overall Coating Deficiency’s
Delamination Blistering
Chalking Staining
Cracking Pinholes
Cratering Sags/Runs
Additional Comments
Tower 2 Pine Bluff Arsenal 8/13/2020
Phoenix Murphy Benjamin Pisocki Nick Blumenblat
5 5 5 5
Fair Fair Fair Fair
8 8 8 8
Good Good Good Good
N/A N/A N/A N/A
N/A N/A N/A N/A
8 8 8 8
Good Good Good Good
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
Good Good
Good Good
Plumbing Locations and Condition
Quadrant One Quadrant Two Quadrant Three Quadrant Four
SSPC Rating Corrosion SSPC Rating Corrosion SSPC Rating Corrosion SSPC Rating Corrosion
Inlet Plumbing
Outlet Plumbing
Manways
Interior Overflow
Floor Drains
Sediment Depths & Plumbing Locations
Sediment Depths
Average Depth of sediment
Sediment Type
Plumbing Locations & Plumbing Identification Key
O = Outlet I = Inlet M = Manway V = Vent D = Drain S = Sump L = Ladder H = Hatch X = Overflow F = Float Level Indicator T = Telemetry C = Column
Additional Comments
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
6"
16"6"
6"
30" 6"
6" 16"
6"
30" 6"
6"
- Center Inlet/Outlet covered with large grate. Grate is dislodged roughly 4" from original resting point.
- Float level indicator appears to be non-functional. Hanging above waterline.
Additional Reservoir Components
Primary Manway Condition Size Location
Primary Air Vent Type Condition
Exterior Overflow Location
Cathodic Protection Installed
Water Level Indicator Condition
Primary Access hatch Condition
Exterior Ladder Condition Rail to Rail Rung to Rung
Rail Width Rail Length
Railings
Roof Integrity Cracks Structural Condition
Wall Integrity Cracks Structural Condition
Antennas
Holes
Holes
Present Obstructs Work Site Antennas Offline
Hypalon Floating Cover Present Condition
Inspection Supplemental Report and Additional Information
Condition
Amount of Penetrations
Size
Condition
N/A N/A N/A
Mushroom Yes Good
Quadrant 3 Good
N/A Yes
Poor Float
Good 24"
Fair 14" 12" 9"
2" 1/4"
Yes Fair
No No Good
No No Good
No N/A N/A
No N/A
Upon initial entry, the tank appeared to be in moderate condition, with minor levels of corrosion along the floor, with moderate staining on the walls. Sediment was measured at 30" deep in places during the cleaning process. After cleaning, the floor appeared to be in moderate condition, with staining, blistering, and surface corrosion.
The grate on the center Inlet/Outlet appears to be dislodged roughly 4" from the original resting place. The Telemetry units appear to be in good condition, with minor staining and corrosion on rigging points located on the walls. The ladder appeared to be in fair condition, with staining, blistering, and concentrated cell corrosion. The walls appeared to be in good condition, with minor staining, blistering, and surface corrosion on the hardware. The overflow appeared to be in good condition, with minor staining.
the hatch appeared to be in fair condition, with staining and corrosion on the hardware.
We would like to thank you for choosing MIT diving, and we recommend having your tanks cleaned and inspected every three to five years.