Attachment 0003 - LBP Water Tanks Survey.pdf

PDF 120 KB Posted

Attached to
PBA Water Tank Cleaning, Painting, and Repair
Solicitation number
W519TC24B2001
Issued by

About this file

This document contains an industrial hygiene memorandum and a related federal contract opportunity notice. The industrial hygiene memorandum details lead and asbestos surveys performed at water tanks located at Pine Bluff Arsenal in Arkansas. Laboratory testing found that white paint samples from tanks 53-180 and 54-180 contained 6.4% and 5.6% lead by weight, respectively.

The related federal contract opportunity is a solicitation issued by the Army Contracting Command - Rock Island for water tank cleaning, painting, and repair services at Pine Bluff Arsenal. Interested contractors must schedule a mandatory site visit by 31 January 2024 and submit bids in response to the solicitation. The 100% small business set-aside contract will be awarded as a firm fixed price contract to the responsive, responsible bidder offering the lowest price and technically acceptable proposal.

View the file

Other files

File Type Posted
Attachment 0010 - Water Tower Map.pdf PDF
Attachment 0011 - Drawings - Tanks 1-2-3.pdf PDF
Attachment 0014 - Tank C Altitude Valve Specification.pdf PDF
Attachment 0015 - Water Tank Structure Pictures.pdf PDF
Attachment 0013 - PBA Steel Tank Maintenance Specifications.pdf PDF
Attachment 0012 - Drawings - Tanks A-B-C.pdf PDF
Attachment 0014 - Water Tank Structure Pictures.pdf PDF
Attachment 0013 - Tank C Altitude Valve Specification.pdf PDF
W519TC24B2001 Conformed to AMD 0007.pdf PDF
Attachment 0012 - PBA Steel Tank Maintenance Specifications.pdf PDF
Attachment 0002 - Wage Determination AR20240036.pdf PDF
Attachment 0001 - Performance Work Statement 5 March 2024.docx DOCX document
W519TC24B2001 Conformed to AMD 0006.pdf PDF
W519TC24B2001 AMD 0005.pdf PDF
W519TC24B2001 AMD 0004.pdf PDF
W519TC24B2001 AMD 0003.pdf PDF
Attachment 0005 - PBA Tower 2 Inspection Report.pdf PDF
W519TC24B2001 AMD 0002.pdf PDF
Attachment 0009 - PBA Tower C Inspection Report.pdf PDF
Attachment 0007 - PBA Tower A Inspection Report.pdf PDF
Attachment 0010 - Drawings - Tanks 1-2-3.pdf PDF
Attachment 0004 - PBA Tower 1 Inspection Report.pdf PDF
Attachment 0006 - PBA Tower 3 Inspection Report.pdf PDF
Attachment 0008 - PBA Tower B Inspection Report.pdf PDF
Attachment 0011 - Drawings - Tanks A-B-C.pdf PDF
W519TC24B2001 AMD 0001.pdf PDF
Attachment 0001 - Performance Work Statement.docx DOCX document
W519TC24B2001.pdf PDF
Attachment 0002 - Wage Determination 15-5121.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10 October 2017 INDUSTRIAL HYGIENE OFFICE

MEMORANDUM FOR SHANE MARRIOTT

SUBJECT: Industrial Hygiene Lead/Asbestos Surveys

On 30 August 2017, Industrial Hygiene performed lead and asbestos surveys at locations referenced below. These inspections were performed to comply with EPA, Arkansas Regulation 25, Arkansas Regulation 21, and OSHA Regulations. These regulations require that Lead Based Materials and Asbestos materials be identified prior to renovation or demolition.

No asbestos containing material were present.

Samples of suspected lead containing materials were collected per your instructions.

These samples were shipped under a proper chain-of-custody to an approved laboratory for lead analysis. A copy of the complete laboratory report is located in the Pine Bluff Arsenal Industrial Hygiene Office. Based on the laboratory reports, the lead results indicated the following:

Sample # Location Results 20170830WY38 53-180 WHITE PAINT FROM TANK 6.4% by Weight 20170830WY39 54-180 WHITE PAINT FROM TANK <0.004% by Weight 20170830WY40 54-480 WHITE PAINT FROM TANK <0.0035% by Weight 20170830WY41 Yellow Paint - GAS LINE SOUTH END 1.7% by Weight

Lead-free paint is defined as <0.06% by Weight. According to HUD (Housing and Urban Development) regulatory standards, a paint chip sample result above 0.5% by weight is an action level whereby the risk of lead exposures is increased and action must be taken if it is a child occupied facility. The OSHA Lead Construction Standard, 29 CFR 1926.62, is invoked if any lead is present in the sample. The higher the percentage of lead by weight, the higher the potential for worker exposure and is used to indicate the preventive measures required while operations are in progress and until personnel sampling is completed.

If you have any questions, please contact the undersigned at 3450 or 329-3070.

LENA M. BOHANNAN

Sr. Industrial Hygienist US Army Occupational Health Clinic ADH Licensed Lead Inspector/Risk Assessor #000339/000340 ADEQ Licensed Asbestos Inspector #011541