46_ITEM 01.3-32_ADD 02_02700EP601.pdf

PDF 425 KB Posted

Attached to
F-35 THREE BAY SPECIALIZED HANGAR Federal contract opportunity
Solicitation number
W50S9F-22-B-0001
Issued by
Department of the Army National Guard

About this file

This is an invitation for bid for construction services to build a new three-bay hangar at Dane County Regional Airport - Truax Field in Madison, Wisconsin. The project scope includes demolishing an existing 19,875 square foot building and constructing a new 31,000 square foot three-bay hangar compatible with the F-35 mission, along with associated shop and administrative spaces. The hangar bays will provide pre-conditioned aircraft air, 270 VDC aircraft power, fire suppression, and HVAC. The facility will also require a lightning protection system, fall protection, and an Advantor security system.

The solicitation includes a base CLIN for construction of the new hangar and two option CLINs, one for a paint/mix addition and one for aircraft-rated pavement. The contract duration is 550 days from notice to proceed. Interested contractors must register in SAM and can access solicitation documents on SAM.gov. The pre-bid conference will be held on-site at Truax Field and bids are due in accordance with FAR Subpart 14.4. The estimated value of construction is between $25-100 million. The NAICS code is 236220 and small business subcontracting plans are required.

View the file

Other files for this federal contract opportunity

Other files attached to F-35 THREE BAY SPECIALIZED HANGAR, newest first.
File Type Posted
Questions and Answers 4.pdf PDF
08_ITEM 01.2-8_ADD 04_Section 11 94 10.pdf PDF
13_ITEM 01.3-3_ADD 04_02700C-601.pdf PDF
21_ITEM 01.3-11_ADD 04_02700A-501.pdf PDF
FSB2020-270-00 - WI-ANG - 3-Bay Hangar - Addendum 004 COMBINED DRAWINGS.pdf PDF
22_ITEM 01.3-12_ADD 04_02700A-502.pdf PDF
Questions and Answers 3.pdf PDF
W50S9F22B0001 Solicitation - Amend 0003.pdf PDF
08_ITEM 01.2-8_ADD 03_Section 21 13 18.pdf PDF
10_ITEM 01.2-10_ADD 03_Section 26 08 00.pdf PDF
12_ITEM 01.3-2_ADD 03_02700C-100.pdf PDF
25_ITEM 01.3-15_ADD 03_02700A-505.pdf PDF
27_ITEM 01.3-17_ADD 03_02700A-511.pdf PDF
32_ITEM 01.3-22_ADD 03_02700A-702.pdf PDF
35_ITEM 01.3-25_ADD 03_02700FA101.pdf PDF
01_ITEM 01.2-1_ADD 03_Section 02 65 00.pdf PDF
07_ITEM 01.2-7_ADD 03_Section 21 13 13.pdf PDF
W50S9F22B0001 Solicitation - Amend 0002.pdf PDF
02_ITEM 01.2-2_ADD 03_Section 03 30 00.pdf PDF
06_ITEM 01.2-6_ADD 03_Section 10 51 13.pdf PDF
Bid Opening Directions.pdf PDF
02_ITEM 01.2-1_ADD 02_PROJECT TOC.pdf PDF
08_ITEM 01.2-9_ADD 02_Section 08 87 35.pdf PDF
17_ITEM 01.3-3_ADD 02_02700C-301.pdf PDF
27_ITEM 01.3-13_ADD 02_02700SF106.pdf PDF
39_ITEM 01.3-25_ADD 02_02700FA101.pdf PDF
40_ITEM 01.3-26_ADD 02_02700FA102.pdf PDF
41_ITEM 01.3-27_ADD 02_02700FA601.pdf PDF
47_ITEM 01.3-33_ADD 02_02700EP701.pdf PDF
31_ITEM 01.3-17_ADD 02_02700A-103.pdf PDF
04_ITEM 01.2-3_ADD 02_Section 01 78 00.pdf PDF
12_ITEM 01.2-13_ADD 02_Section 32 12 15.13.pdf PDF
13_ITEM 01.2-14_ADD 02_Section 32 12 16.16.pdf PDF
21_ITEM 01.3-7_ADD 02_02700S-002.pdf PDF
23_ITEM 01.3-9_ADD 02_02700SF102.pdf PDF
24_ITEM 01.3-10_ADD 02_02700SF103.pdf PDF
25_ITEM 01.3-11_ADD 02_02700SF104.pdf PDF
32_ITEM 01.3-18_ADD 02_02700A-140.pdf PDF
33_ITEM 01.3-19_ADD 02_02700A-201.pdf PDF
45_ITEM 01.3-31_ADD 02_02700EP102.pdf PDF
48_ITEM 01.3-34_ADD 02_02700EP702.pdf PDF
49_ITEM 01.3-35_ADD 02_02700ET101.pdf PDF
FSB2020-270-00 - WI-ANG - 3-Bay Hangar - Addendum 002 Combined Drawings.pdf PDF
ATTACHMENT 7 - 20220208 Single Source Determination - Monaco - Redacted.pdf PDF
W50S9F22B0001 Solicitation - F-35 3-Bay Hangar.pdf PDF
ATTACHMENT 4 - 20220208 Single Source Determination - Advantor - Redacted.pdf PDF
ATTACHMENT 1a - FSB2020-270-00 - WI-ANG - 3-Bay Hangar - ADD 01 COMBINED DRAWINGS (1 of 2).pdf PDF
ATTACHMENT 1b - FSB2020-270-00 - WI-ANG - 3-Bay Hangar - ADD 01 COMBINED DRAWINGS (2 of 2).pdf PDF
ATTACHMENT 3 - Volume 4 - WI ANG F-35 3-Bay CD Specs ADD 01 (2 of 2).pdf PDF
ATTACHMENT 5 - 20220208 Single Source Determination - Andover - Redacted.pdf PDF
Show all 50

F-35 THREE BAY SPECIALIZED HANGAR has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2500A

LSIG

"MDP" 2500A, 480V/277V, 3PH, 4W

ROOM 145

600A

LSI

600A

LSI

600A

LSI

MG&E UTILITY

PADMOUNT

XFMR

1HDP" 600A, 480V/277V, 3PH, 4W

H1

400A

L1-1

150A

TL1

75KVA

480-

208/120V

LTG: HANGAR

BAYS & EXT.

1L1

50A 125A

T1L1

30KVA

480-

208/120V

HYDRAULIC

CART

150A

J

CONV.

#1

270VDC

CONVERTER #1

2HDP" 600A, 480V/277V, 3PH, 4W

2L1

60A

T2L1

30KVA

480-

208/120V

150A

3HDP" 600A, 480V/277V, 3PH, 4W

3L1

50A

T3L1

30KVA

480-

208/120V

150A

PAO

CART

125A

HYDRAULIC

CART

PAO

CART

125A

HYDRAULIC

CART

PAO

CART

PCA #2

100 FLA

PCA #1

100 FLA

PCA #3

100 FLA

150A125A

150A125A 150A125A

HANGAR

DOOR

POWER

30A

LCP

LIGHTING

CONTROL

PANEL

SPD

60A

"HD1" 100A, 480V/277V, 3PH, 4W

HANGAR

DOOR

POWER

30A

30302 SETS-

17 17 17

17 17 17

17 17 17

41 41

52 52

100A

SPD

60A

FA1

L2-1

150A

TL2

75KVA

480-

208/120V

HANGAR

DOOR

POWER

30A

2 SETS-

2 SETS-

100A

EH1

60A

G

PORTABLE

GENERATOR

100A

L2-2

EL1

ETL1

30KVA

480-

208/120V

L1-2

ITC1

100KVA

J

CONV.

#3

270VDC

CONVERTER #3

ITC3

100KVA

J

CONV.

#2

270VDC

CONVERTER #2

ITC2

100KVA

7 7

LINV

80KA

80KA

SPD

40KA

SPD

40KA

SPD

40KA

FEED SHALL BE IN GRC CONDUIT,10 FT MAX

ONCE INDOORS.

SPD

30A

40KA

SPD

30A

40KA

SPD

30A

40KA

60A

TLP1

SPD

30A

40KA

N L

MALE CAM LOCK

SERIES (16)

INTEGRAL PHASE

ROTATION MONITOR

3 POSITION ON-0FF-ON

TRANSFER SWITCH

MTS-1

480/277V,3PHASE,

3 POLE,100A,

COMBINATION GENERATOR

DOCKING STATION /

TRANSFER SWITCH. NEMA 3R ENCLOSURE.

SPD

30A

40KA

SPD

30A

40KA

G

PORTABLE

GENERATOR

N L

MALE CAM LOCK

SERIES (16)

INTEGRAL PHASE

ROTATION MONITOR

3 POSITION ON-0FF-ON

TRANSFER SWITCH

MTS-HD

480/277V,3PHASE,

3 POLE,100A,

COMBINATION GENERATOR

DOCKING STATION /

TRANSFER SWITCH.

NEMA 3R ENCLOSURE.

SPD

30A

40KA

SPD

30A

40KA

SPD

30A

40KA

NEMA 3R, 3000A

CT CABINET.

BOTTOM ENTRY

BOTTOM EXIT.

DM

13 14

WIRE AND CONDUIT

FEEDER SCHEDULE

NO

3-#12 & 1-#12 EG, 3/4"C

3-#10 & 1-#10 EG, 3/4"C

3-#8 & 1-#10 EG, 1"C

3-#6 & 1-#10 EG, 1"C

3-#4 & 1-#8 EG, 1 1/4"C

3-#3 & 1-#8 EG, 1 1/4"C

3-#2 & 1-#8 EG, 1 1/4"C

3-#1 & 1-#6 EG, 1 1/2"C

3-#1/0 & 1-#6 EG, 1 1/2"C

3-#2/0 & 1-#6 EG, 2"C

3-#3/0 & 1-#6 EG, 2"C

3-#4/0 & 1-#4 EG, 2"C

3-#250kcmil & 1-#4 EG, 2 1/2"C

3-#300kcmil & 1-#4 EG, 2 1/2"C

3-#350kcmil & 1-#3 EG, 2 1/2"C

3-#400kcmil & 1-#3 EG, 2 1/2"C

3-#500kcmil & 1-#3 EG, 3"C

AMPS

380 380

AMPSNO WIRE AND CONDUIT

4-#12 & 1-#12 EG, 3/4"C

4-#10 & 1-#10 EG, 3/4"C

4-#8 & 1-#10 EG, 1"C

4-#6 & 1-#10 EG, 1"C

4-#4 & 1-#8 EG, 1 1/4"C

4-#3 & 1-#8 EG, 1 1/4"C

4-#2 & 1-#8 EG, 1 1/4"C

4-#1 & 1-#6 EG, 1 1/2"C

4-#1/0 & 1-#6 EG, 1 1/2"C

4-#2/0 & 1-#6 EG, 2"C

4-#3/0 & 1-#6 EG, 2"C

4-#4/0 & 1-#4 EG, 2 1/2"C

4-#250kcmil & 1-#4 EG, 2 1/2"C

4-#300kcmil & 1-#4 EG, 3"C

4-#350kcmil & 1-#3 EG, 3"C

4-#400kcmil & 1-#3 EG, 3"C

4-#500kcmil & 1-#3 EG, 3 1/2"C

SCHEDULE NOTES :

1. RESIZE GROUND CONDUCTOR FOR PARALLEL FEEDERS AS REQUIRED PER

SECTION #250-122 OF THE NEC. INCREASE SIZE OF CONDUIT AS

REQUIRED FOR ADDITIONAL GROUNDING.

2. ALL AMPACITIES INDICATED ARE COPPER BASED ON TEMPERATURE

RATING OF 60°C INSULATION ON CONDUCTORS #1 AND SMALLER AND 75°C

INSULATION ON CONDUCTORS #1/0 AND LARGER.

3-#600kcmil & 1-#3 EG, 3 1/2"C 420 4204-#600kcmil & 1-#3 EG, 4"C35 36

WIRE AND CONDUIT

SEPARATELY DERIVED SERVICE

FEEDER SCHEDULE

NO

3-#12 & 1-#8 EG, 3/4"C

3-#10 & 1-#8 EG, 3/4"C

3-#8 & 1-#8 EG, 1"C

3-#6 & 1-#8 EG, 1"C

3-#4 & 1-#8 EG, 1 1/4"C

3-#3 & 1-#8 EG, 1 1/4"C

3-#2 & 1-#8 EG, 1 1/4"C

3-#1 & 1-#6 EG, 1 1/2"C

3-#1/0 & 1-#6 EG, 1 1/2"C

3-#2/0 & 1-#4 EG, 2"C

3-#3/0 & 1-#2 EG, 2"C

3-#4/0 & 1-#2 EG, 2"C

3-#250kcmil & 1-#2 EG, 2 1/2"C

3-#300kcmil & 1-#2 EG, 2 1/2"C

3-#350kcmil & 1-#2 EG, 2 1/2"C

3-#400kcmil & 1-#1/0 EG, 2 1/2"C

3-#500kcmil & 1-#1/0 EG, 3"C

AMPS

380 380

AMPSNO WIRE AND CONDUIT

4-#12 & 1-#8 EG, 3/4"C

4-#10 & 1-#8 EG, 3/4"C

4-#8 & 1-#8 EG, 1"C

4-#6 & 1-#8 EG, 1"C

4-#4 & 1-#8 EG, 1 1/4"C

4-#3 & 1-#8 EG, 1 1/4"C

4-#2 & 1-#8 EG, 1 1/4"C

4-#1 & 1-#6 EG, 1 1/2"C

4-#1/0 & 1-#6 EG, 1 1/2"C

4-#2/0 & 1-#4 EG, 2"C

4-#3/0 & 1-#4 EG, 2"C

4-#4/0 & 1-#2 EG, 2 1/2"C

4-#250kcmil & 1-#2 EG, 2 1/2"C

4-#300kcmil & 1-#2 EG, 3"C

4-#350kcmil & 1-#2 EG, 3"C

4-#400kcmil & 1-#1/0 EG, 3"C

4-#500kcmil & 1-#1/0 EG, 3 1/2"C

SCHEDULE NOTES :

1. RESIZE GROUND CONDUCTOR FOR PARALLEL SERVICE FEEDERS AS REQUIRED PER

TABLE 250.66 OF THE NEC. INCREASE SIZE OF CONDUIT AS REQUIRED FOR

ADDITIONAL GROUNDING.

2. ALL AMPACITIES INDICATED ARE COPPER BASED ON TEMPERATURE RATING OF 60°C

INSULATION ON CONDUCTORS #1 AND SMALLER AND 75°C INSULATION ON

CONDUCTORS #1/0 AND LARGER.

3. THIS TABLE APPLIES TO THE DERIVED CONDUCTORS OF SEPARATELY DERIVED

SYSTEMS.

3-#600kcmil & 1-#1/0 EG, 3 1/2"C 420 4204-#600kcmil & 1-#1/0 EG, 4"C71 72

5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436

405.840.2931 | fsb-ae.com

D

SHEET NUMBER:

ISSUE DATE:

SHEET TITLE:

PROJECT NUMBER:

PROJECT INFORMATION:

REVISION HISTORY:

FSB2020-270-00

DATEDESCRIPTION

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT MANAGER:

NWC / JBC

F-

3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin

Ai r N at io na l G ua rd

C

B

A

D

C

B

A

54321

DECEMBER 23, 2021

C :\U sers\aoo\D o cum ents\M y R evit\02700_Elec_A O genche.rvt

6/7/2022 11:01: 19 AM

ELECTRICAL ONE-LINE

DIAGRAMS

EP601

JTL

GPN

GPN

SCALE: NTS

ELECTRICAL ONE-LINE DIAGRAMA1

GENERAL NOTES

SHEET KEYNOTES

A. UTILITY COMPANY IS RESPONSIBLE FOR PRIMARY

SIDE OF TRANSFORMER CONDUIT AND

CONDUCTORS, TRANSFORMER, TRANSFORMER

PAD, SECONDARY SIDE OF TRANSFORMER

CONDUIT, CONDUCTOR AND FINAL TERMINATIONS

TO DISCONNECTING MEANS IN MAIN

SWITCHBOARD. CONTRACTOR IS RESPONSIBLE

FOR DISCONNECTING MEANS AND CT'S IN

SWITCHBOARD.

1. CONTRACTOR TO PROVIDE (8) 4" CONDUITS IN

CONCRETE ENCASED DUCTBANK, (6) CONDUITS,

EACH WITH 4 - #600KCMIL CONDUCTORS, (2) SPARE

CONDUITS.

2. NOT USED

3. ENCLOSED CIRCUIT BREAKER; SERVICE ENTRANCE

RATED.

4. DEDICATED FIRE PROTECTION PANELBOARD.

5. MG&E PROVIDED TRANSFOMER. TRANSFORMER

AND PAD ARE UTILITY'S RESPONSIBILITY.

6. NOT USED.

7. 100KVA AUTOMATIC VOLTAGE REGULATOR SHALL

HAVE OUTPUT VOLTAGE OF 460V +/- 4%.

8. NOT USED.

9. 2-#3 & 1- #8 EG, 1-1/4C .

10. TAP HANGAR DOOR POWER IN THE CT CABINET.

PROVIDE EXTRA LUGS IN THE CT CABINET TO

FACILITATE CONNECTION.

11. NOT USED

12. (1) 01- 1/2" CONDUIT WITH (4) #1 AND 1 E.G.

13. 3000A , NEMA 3R, MG&E APPROVED CT CABINET. CT

CABINET IS CFCI PER MG&E GUIDELINES. CURRENT

TRANSFORMERS WITHIN THE CABINET ARE

PROVIDED BY MG&E AND INSTALLED BY

CONTRACTOR PER MG&E GUIDELINES

14. CONTRACTOR TO PROVIDE MG&E APPROVED CT

RATED METER SOCKET, ON OPPOSITE SIDE OF

WIREWAY , HELD OFF ON STRUT. COORDINATE

EXACT METER SOCKET LOCATION WITH MG&E.

15. ELECTRIC METER AND WIRING TO TEST SWITCH

ARE MG&E PROVIDED AND FURNISHED.

16. MG&E SECONDARY FEEDS FROM UTILITY

TRANSFOMER TO CT CABINET. SECONDARY FEEDS

FROM TRANSFOMER TO CT CABINET ARE UTILITY'S

RESPOSIBILITY. CONTRACTOR TO PROVIDE (8) 4"

CONDUIT SWEEPS , STUBBED UP IN CABINET 3" MAX

ABOVE PAD TOWARDS TRANSFORMER, USE 36" 90

DEGREE BENDS AND EXTEND 3' BELOW GRADE TO

3' PAST CONCRETE PAD TOWARDS TRANSFORMER.

CONDUITS SHALL BE CENTERED IN MG&E

PULLSPACE UNDER THE LINE LUGS.

17. CFCI SWITCHBOARD MDP INTEGRAL

MULTIFUNCTION DIGITAL METER.

1 ADDENDUM 1 04/22/2022

2 ADDENDUM 2 06/08/2022

W

IS C O NS IN

P R

O F

E

S S I O N A L

E N G

I N E

E R

JOHN T

LITTLE

E-47833

EDMOND

OK