This is an invitation for bid for construction services to build a new three-bay hangar at Dane County Regional Airport - Truax Field in Madison, Wisconsin. The project scope includes demolishing an existing 19,875 square foot building and constructing a new 31,000 square foot three-bay hangar compatible with the F-35 mission, along with associated shop and administrative spaces. The hangar bays will provide pre-conditioned aircraft air, 270 VDC aircraft power, fire suppression, and HVAC. The facility will also require a lightning protection system, fall protection, and an Advantor security system.
The solicitation includes a base CLIN for construction of the new hangar and two option CLINs, one for a paint/mix addition and one for aircraft-rated pavement. The contract duration is 550 days from notice to proceed. Interested contractors must register in SAM and can access solicitation documents on SAM.gov. The pre-bid conference will be held on-site at Truax Field and bids are due in accordance with FAR Subpart 14.4. The estimated value of construction is between $25-100 million. The NAICS code is 236220 and small business subcontracting plans are required.
View the file
Other files for this federal contract opportunity
Show all 50
F-35 THREE BAY SPECIALIZED HANGAR has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2500A
LSIG
"MDP" 2500A, 480V/277V, 3PH, 4W
ROOM 145
600A
LSI
600A
LSI
600A
LSI
MG&E UTILITY
PADMOUNT
XFMR
1HDP" 600A, 480V/277V, 3PH, 4W
H1
400A
L1-1
150A
TL1
75KVA
480-
208/120V
LTG: HANGAR
BAYS & EXT.
1L1
50A 125A
T1L1
30KVA
480-
208/120V
HYDRAULIC
CART
150A
J
CONV.
#1
270VDC
CONVERTER #1
2HDP" 600A, 480V/277V, 3PH, 4W
2L1
60A
T2L1
30KVA
480-
208/120V
150A
3HDP" 600A, 480V/277V, 3PH, 4W
3L1
50A
T3L1
30KVA
480-
208/120V
150A
PAO
CART
125A
HYDRAULIC
CART
PAO
CART
125A
HYDRAULIC
CART
PAO
CART
PCA #2
100 FLA
PCA #1
100 FLA
PCA #3
100 FLA
150A125A
150A125A 150A125A
HANGAR
DOOR
POWER
30A
LCP
LIGHTING
CONTROL
PANEL
SPD
60A
"HD1" 100A, 480V/277V, 3PH, 4W
HANGAR
DOOR
POWER
30A
30302 SETS-
17 17 17
17 17 17
17 17 17
41 41
52 52
100A
SPD
60A
FA1
L2-1
150A
TL2
75KVA
480-
208/120V
HANGAR
DOOR
POWER
30A
2 SETS-
2 SETS-
100A
EH1
60A
G
PORTABLE
GENERATOR
100A
L2-2
EL1
ETL1
30KVA
480-
208/120V
L1-2
ITC1
100KVA
J
CONV.
#3
270VDC
CONVERTER #3
ITC3
100KVA
J
CONV.
#2
270VDC
CONVERTER #2
ITC2
100KVA
7 7
LINV
80KA
80KA
SPD
40KA
SPD
40KA
SPD
40KA
FEED SHALL BE IN GRC CONDUIT,10 FT MAX
ONCE INDOORS.
SPD
30A
40KA
SPD
30A
40KA
SPD
30A
40KA
60A
TLP1
SPD
30A
40KA
N L
MALE CAM LOCK
SERIES (16)
INTEGRAL PHASE
ROTATION MONITOR
3 POSITION ON-0FF-ON
TRANSFER SWITCH
MTS-1
480/277V,3PHASE,
3 POLE,100A,
COMBINATION GENERATOR
DOCKING STATION /
TRANSFER SWITCH. NEMA 3R ENCLOSURE.
SPD
30A
40KA
SPD
30A
40KA
G
PORTABLE
GENERATOR
N L
MALE CAM LOCK
SERIES (16)
INTEGRAL PHASE
ROTATION MONITOR
3 POSITION ON-0FF-ON
TRANSFER SWITCH
MTS-HD
480/277V,3PHASE,
3 POLE,100A,
COMBINATION GENERATOR
DOCKING STATION /
TRANSFER SWITCH.
NEMA 3R ENCLOSURE.
SPD
30A
40KA
SPD
30A
40KA
SPD
30A
40KA
NEMA 3R, 3000A
CT CABINET.
BOTTOM ENTRY
BOTTOM EXIT.
DM
13 14
WIRE AND CONDUIT
FEEDER SCHEDULE
NO
3-#12 & 1-#12 EG, 3/4"C
3-#10 & 1-#10 EG, 3/4"C
3-#8 & 1-#10 EG, 1"C
3-#6 & 1-#10 EG, 1"C
3-#4 & 1-#8 EG, 1 1/4"C
3-#3 & 1-#8 EG, 1 1/4"C
3-#2 & 1-#8 EG, 1 1/4"C
3-#1 & 1-#6 EG, 1 1/2"C
3-#1/0 & 1-#6 EG, 1 1/2"C
3-#2/0 & 1-#6 EG, 2"C
3-#3/0 & 1-#6 EG, 2"C
3-#4/0 & 1-#4 EG, 2"C
3-#250kcmil & 1-#4 EG, 2 1/2"C
3-#300kcmil & 1-#4 EG, 2 1/2"C
3-#350kcmil & 1-#3 EG, 2 1/2"C
3-#400kcmil & 1-#3 EG, 2 1/2"C
3-#500kcmil & 1-#3 EG, 3"C
AMPS
380 380
AMPSNO WIRE AND CONDUIT
4-#12 & 1-#12 EG, 3/4"C
4-#10 & 1-#10 EG, 3/4"C
4-#8 & 1-#10 EG, 1"C
4-#6 & 1-#10 EG, 1"C
4-#4 & 1-#8 EG, 1 1/4"C
4-#3 & 1-#8 EG, 1 1/4"C
4-#2 & 1-#8 EG, 1 1/4"C
4-#1 & 1-#6 EG, 1 1/2"C
4-#1/0 & 1-#6 EG, 1 1/2"C
4-#2/0 & 1-#6 EG, 2"C
4-#3/0 & 1-#6 EG, 2"C
4-#4/0 & 1-#4 EG, 2 1/2"C
4-#250kcmil & 1-#4 EG, 2 1/2"C
4-#300kcmil & 1-#4 EG, 3"C
4-#350kcmil & 1-#3 EG, 3"C
4-#400kcmil & 1-#3 EG, 3"C
4-#500kcmil & 1-#3 EG, 3 1/2"C
SCHEDULE NOTES :
1. RESIZE GROUND CONDUCTOR FOR PARALLEL FEEDERS AS REQUIRED PER
SECTION #250-122 OF THE NEC. INCREASE SIZE OF CONDUIT AS
REQUIRED FOR ADDITIONAL GROUNDING.
2. ALL AMPACITIES INDICATED ARE COPPER BASED ON TEMPERATURE
RATING OF 60°C INSULATION ON CONDUCTORS #1 AND SMALLER AND 75°C
INSULATION ON CONDUCTORS #1/0 AND LARGER.
3-#600kcmil & 1-#3 EG, 3 1/2"C 420 4204-#600kcmil & 1-#3 EG, 4"C35 36
WIRE AND CONDUIT
SEPARATELY DERIVED SERVICE
FEEDER SCHEDULE
NO
3-#12 & 1-#8 EG, 3/4"C
3-#10 & 1-#8 EG, 3/4"C
3-#8 & 1-#8 EG, 1"C
3-#6 & 1-#8 EG, 1"C
3-#4 & 1-#8 EG, 1 1/4"C
3-#3 & 1-#8 EG, 1 1/4"C
3-#2 & 1-#8 EG, 1 1/4"C
3-#1 & 1-#6 EG, 1 1/2"C
3-#1/0 & 1-#6 EG, 1 1/2"C
3-#2/0 & 1-#4 EG, 2"C
3-#3/0 & 1-#2 EG, 2"C
3-#4/0 & 1-#2 EG, 2"C
3-#250kcmil & 1-#2 EG, 2 1/2"C
3-#300kcmil & 1-#2 EG, 2 1/2"C
3-#350kcmil & 1-#2 EG, 2 1/2"C
3-#400kcmil & 1-#1/0 EG, 2 1/2"C
3-#500kcmil & 1-#1/0 EG, 3"C
AMPS
380 380
AMPSNO WIRE AND CONDUIT
4-#12 & 1-#8 EG, 3/4"C
4-#10 & 1-#8 EG, 3/4"C
4-#8 & 1-#8 EG, 1"C
4-#6 & 1-#8 EG, 1"C
4-#4 & 1-#8 EG, 1 1/4"C
4-#3 & 1-#8 EG, 1 1/4"C
4-#2 & 1-#8 EG, 1 1/4"C
4-#1 & 1-#6 EG, 1 1/2"C
4-#1/0 & 1-#6 EG, 1 1/2"C
4-#2/0 & 1-#4 EG, 2"C
4-#3/0 & 1-#4 EG, 2"C
4-#4/0 & 1-#2 EG, 2 1/2"C
4-#250kcmil & 1-#2 EG, 2 1/2"C
4-#300kcmil & 1-#2 EG, 3"C
4-#350kcmil & 1-#2 EG, 3"C
4-#400kcmil & 1-#1/0 EG, 3"C
4-#500kcmil & 1-#1/0 EG, 3 1/2"C
SCHEDULE NOTES :
1. RESIZE GROUND CONDUCTOR FOR PARALLEL SERVICE FEEDERS AS REQUIRED PER
TABLE 250.66 OF THE NEC. INCREASE SIZE OF CONDUIT AS REQUIRED FOR
ADDITIONAL GROUNDING.
2. ALL AMPACITIES INDICATED ARE COPPER BASED ON TEMPERATURE RATING OF 60°C
INSULATION ON CONDUCTORS #1 AND SMALLER AND 75°C INSULATION ON
CONDUCTORS #1/0 AND LARGER.
3. THIS TABLE APPLIES TO THE DERIVED CONDUCTORS OF SEPARATELY DERIVED
SYSTEMS.
3-#600kcmil & 1-#1/0 EG, 3 1/2"C 420 4204-#600kcmil & 1-#1/0 EG, 4"C71 72
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
FSB2020-270-00
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
NWC / JBC
F-
3- Ba y S pe cia liz ed H an ga r M ad iso n, W isc on sin
Ai r N at io na l G ua rd
C
B
A
D
C
B
A
54321
DECEMBER 23, 2021
C :\U sers\aoo\D o cum ents\M y R evit\02700_Elec_A O genche.rvt
6/7/2022 11:01: 19 AM
ELECTRICAL ONE-LINE
DIAGRAMS
EP601
JTL
GPN
GPN
SCALE: NTS
ELECTRICAL ONE-LINE DIAGRAMA1
GENERAL NOTES
SHEET KEYNOTES
A. UTILITY COMPANY IS RESPONSIBLE FOR PRIMARY
SIDE OF TRANSFORMER CONDUIT AND
CONDUCTORS, TRANSFORMER, TRANSFORMER
PAD, SECONDARY SIDE OF TRANSFORMER
CONDUIT, CONDUCTOR AND FINAL TERMINATIONS
TO DISCONNECTING MEANS IN MAIN
SWITCHBOARD. CONTRACTOR IS RESPONSIBLE
FOR DISCONNECTING MEANS AND CT'S IN
SWITCHBOARD.
1. CONTRACTOR TO PROVIDE (8) 4" CONDUITS IN
CONCRETE ENCASED DUCTBANK, (6) CONDUITS,
EACH WITH 4 - #600KCMIL CONDUCTORS, (2) SPARE
CONDUITS.
2. NOT USED
3. ENCLOSED CIRCUIT BREAKER; SERVICE ENTRANCE
RATED.
4. DEDICATED FIRE PROTECTION PANELBOARD.
5. MG&E PROVIDED TRANSFOMER. TRANSFORMER
AND PAD ARE UTILITY'S RESPONSIBILITY.
6. NOT USED.
7. 100KVA AUTOMATIC VOLTAGE REGULATOR SHALL
HAVE OUTPUT VOLTAGE OF 460V +/- 4%.
8. NOT USED.
9. 2-#3 & 1- #8 EG, 1-1/4C .
10. TAP HANGAR DOOR POWER IN THE CT CABINET.
PROVIDE EXTRA LUGS IN THE CT CABINET TO
FACILITATE CONNECTION.
11. NOT USED
12. (1) 01- 1/2" CONDUIT WITH (4) #1 AND 1 E.G.
13. 3000A , NEMA 3R, MG&E APPROVED CT CABINET. CT
CABINET IS CFCI PER MG&E GUIDELINES. CURRENT
TRANSFORMERS WITHIN THE CABINET ARE
PROVIDED BY MG&E AND INSTALLED BY
CONTRACTOR PER MG&E GUIDELINES
14. CONTRACTOR TO PROVIDE MG&E APPROVED CT
RATED METER SOCKET, ON OPPOSITE SIDE OF
WIREWAY , HELD OFF ON STRUT. COORDINATE
EXACT METER SOCKET LOCATION WITH MG&E.
15. ELECTRIC METER AND WIRING TO TEST SWITCH
ARE MG&E PROVIDED AND FURNISHED.
16. MG&E SECONDARY FEEDS FROM UTILITY
TRANSFOMER TO CT CABINET. SECONDARY FEEDS
FROM TRANSFOMER TO CT CABINET ARE UTILITY'S
RESPOSIBILITY. CONTRACTOR TO PROVIDE (8) 4"
CONDUIT SWEEPS , STUBBED UP IN CABINET 3" MAX
ABOVE PAD TOWARDS TRANSFORMER, USE 36" 90
DEGREE BENDS AND EXTEND 3' BELOW GRADE TO
3' PAST CONCRETE PAD TOWARDS TRANSFORMER.
CONDUITS SHALL BE CENTERED IN MG&E
PULLSPACE UNDER THE LINE LUGS.
17. CFCI SWITCHBOARD MDP INTEGRAL
MULTIFUNCTION DIGITAL METER.
1 ADDENDUM 1 04/22/2022
2 ADDENDUM 2 06/08/2022
W
IS C O NS IN
P R
O F
E
S S I O N A L
E N G
I N E
E R
JOHN T
LITTLE
E-47833
EDMOND
OK
File details come from the government source that posted it. Updated .