Water test results.pdf

PDF 835 KB Posted

Attached to
Replace Building 7 Boilers - Stratton Air National Guard Base
Solicitation number
W50S8J26QA017
Issued by

About this file

This is a laboratory analysis report from Adirondack Environmental Services, Inc. for Stratton Air National Guard documenting water quality testing conducted on a sample collected from Hangar 7 Boiler Room on May 6, 2026 at 3:30 PM. Work Order No. 260507031 was issued to Carissa Bastiani at Stratton ANG located in Scotia, New York.

The drinking water sample underwent comprehensive testing across multiple analytical methods including coliform bacteria detection (SM 9223B), heavy metals analysis (ICP/MS EPA 200.8 and ICP Metals EPA 200.7), hardness measurement (SM 2340B), anion analysis via ion chromatography (EPA 300.0), alkalinity testing (SM 2320B), nitrite analysis (SM 4500), pH measurement, and turbidity assessment (EPA 180.1). Key results indicate total coliform and E. coli tested negative, arsenic and lead were not detected at reporting limits of 0.0010 mg/L, total hardness measured 184 mg/L CaCO3, and sodium measured 34.0 mg/L. Chloride, nitrate nitrogen, and sulfate measured 75.0, 0.836, and 25.1 mg/L respectively. Total alkalinity was 180 mgCaCO3/L, pH was 7.6, and turbidity was 0.3 NTU. All analyses were completed between May 7 and May 19, 2026. The report includes standard qualifiers defining detection limits and analytical flags, with a liability limitation capping damages at twice the amount billed for services.

View the file

Other files

File Type Posted
Vent pipe tag picture.jpg JPG image
QandA 2.pdf PDF
Revised Solicitation (Amendment 01).pdf PDF
QandA 1.docx DOCX document
Site Visit Sign In Sheet.pdf PDF
Statement of Work Amendment 01.docx DOCX document
Amendment 01.pdf PDF
Statement of Work.docx DOCX document
Wage Determination.txt TXT text file
Solicitation - W50S8J26QA017.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

May 20, 2026

Stratton ANG Carissa Bastiani

RE:

Work Order No: 260507031

TEL: (518) 478-3394

1 Air National Guard Rd

Scotia, NY 12302

Experience is the solution 314 North Pearl Street Albany, New York 12207

(800) 848-4983 (518) 434-4546 Fax (518) 434-0891

Hangar 7 Boiler Room

Adirondack Environmental Services, Inc received 1 sample on 5/7/2026 for the analyses presented in the following report.

Tara Daniels

Please see case narrative for specifics on analysis.

If you have any questions regarding these tests results, please feel free to call.

Sincerely, ELAP#: 10709

Laboratory Director

20-May-26Date:Stratton ANG

Lab WorkOrder: 260507031

CASE NARRATIVEAdirondack Environmental Services, Inc

Hangar 7 Boiler Room

Sample containers were supplied by Adirondack Environmental Services.

Qualifiers:

J: Analyte detected below quantitation limit

B: Analyte detected in Blank

ND : Not Detected at reporting limit

S: LCS Spike recovery is below acceptable limits

Z: Duplication outside acceptable limits

T : Tentatively Identified Compound-Estimated

X : Exceeds maximum contamination limit

E :Above quantitation range-Estimated

H: Hold time exceeded

N: Matrix Spike below acceptable limits

Note : All Results are reported as wet weight unless noted

C: CCV below acceptable Limits

The results relate only to the items tested. Information supplied by the client is assumed to be correct.

S+: LCS Spike recovery is above acceptable limits

N+: Matrix Spike is above acceptable limits

C+: CCV above acceptable Limits

Definitions - RL: Reporting Limit DF: Dilution factor

Project:

CLIENT: Stratton ANG LabWork Order: 260507031

Adirondack Environmental Services, Inc Date: 20-May-26

PO#:

Hangar 7 Boiler Room

Client Sample ID: Hangar 7 Boiler Room

Lab SampleID: 260507031-001 Collection Date: 5/6/2026 3:30:00 PM

Matrix: DRINKING WATER

Analyses Result Qual Units Date AnalyzedRL DF

SM 9223B(-04)COLILERT Analyst: TMC

( Prep: - 5/7/2026 5:18:00 PM )

Total Coliform 5/8/2026 12:20:00 PM0 1Negative

Escherichia coli 5/8/2026 12:20:00 PM0 1Negative

ICP/MS - EPA 200.8 REV 5.4 Analyst: SM

( Prep: - 5/11/2026 9:43:27 AM )

Arsenic 5/14/2026 3:50:56 PM0.0010 mg/L 1ND

Lead 5/14/2026 3:50:56 PM0.0010 mg/L 1ND

HARDNESS - SM 2340B-2011 Analyst: KH

( Prep: - 5/11/2026 9:43:27 AM )

Total Hardness (As CaCO3) 5/13/20265 mg/L CaCO3 1184

ICP METALS - EPA 200.7 REV 4.4 Analyst: KH

( Prep: - 5/11/2026 9:43:27 AM )

Iron 5/13/2026 11:45:35 AM0.0500 mg/L 1ND

Manganese 5/13/2026 11:45:35 AM0.0100 mg/L 1ND

Sodium 5/13/2026 11:45:35 AM0.100 mg/L 134.0

ANIONS BY ION CHROMATOGRAPHY - EPA 300.0 REV 2.1 Analyst: GK

Fluoride 5/7/2026 6:40:13 PM0.100 mg/L 1ND

Chloride 5/7/2026 6:40:13 PM1.00 mg/L 175.0

Nitrate, Nitrogen (As N) 5/7/2026 6:40:13 PM0.010 mg/L 10.836

Sulfate 5/7/2026 6:40:13 PM1.00 mg/L 125.1

ALKALINITY TO PH 4.5 - SM 2320B-97 Analyst: CRS

Alkalinity, Total (As CaCO3) 5/19/202610 mgCaCO3/L 1180

NITRITE - SM4500 NO2 B-2011 Analyst: CRS

5/8/2026 10:20:00 AM )

Nitrite Nitrogen (as N) 5/8/2026 10:35:00 AM0.01 mg/L 1ND

PH - SM4500 H B - NOT CERTIFIABLE PARAMETER Analyst: CRS pH H 5/7/2026 2:20:00 PM1.0 pH Units@20C 17.6

TURBIDITY - EPA 180.1 REV 2.0 Analyst: CL

Turbidity 5/7/2026 2:12:00 PM0.1 NTU 10.3

File details come from the government source that posted it. Updated .