ATTACHMENT 11 - 22 00 00_AM07 20Jul26.pdf
PDF 202 KB Posted
- Solicitation number
- W50S8326BA001
- Issued by
-
Department of the Army National Guard
About this file
This is a federal plumbing specification section (Section 22 00 00) for the ME ANG Fuel Cell Hangar project (PN: FKNN159044), established in May 2024.
The specification establishes comprehensive requirements for plumbing system design, materials, installation, and testing. Materials must comply with industry standards including ASME, ASTM, ANSI, AWWA, MSS, and NSF certifications. Pipe materials vary by service type: PVC is specified for drainage, waste, and vent systems; copper tubing (Types K, L, or M per ASTM B88) for potable water; and steel pipe for compressed air systems. All materials must be NSF-certified for potable water applications, with lead content certification per NSF 372. Fixtures include wall-hung lavatories, kitchen sinks, service sinks, flush valve water closets and urinals, drinking water coolers, emergency eyewash stations, and showerheads—all with WaterSense labeling where applicable. Water heaters must meet energy efficiency standards per 10 CFR 430, with electric storage types requiring specific Uniform Energy Factor (UEF) ratings based on capacity and draw patterns. The specification mandates point-of-use mixing valves limiting water to 110°F at lavatories and backflow prevention devices at locations required by the International Plumbing Code.
Installation requirements include proper pipe support using MSS SP-58 hangers, expansion provisions for hot water lines, isolation valves on equipment supplies, and seismic bracing per applicable standards. All piping must undergo pressure testing, flushing with potable water at 4 feet per second velocity, operational testing over minimum 8-hour periods, and disinfection via chlorination to 50 ppm minimum with 24-hour residual monitoring. Backflow prevention assemblies require third-party certification testing with documented gauge calibration. The contractor must provide system flushing at fixture end-points (0.25 gallons per 24-hour period over 14 days), vibration isolation for mechanical equipment, and comprehensive operation and maintenance documentation before system acceptance.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ME ANG FUEL CELL HANGAR PN: FKNN159044
SECTION 22 00 00
PLUMBING, GENERAL PURPOSE
05/24
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI Z21.22/CSA 4.4 (2015; R 2020) Relief Valves for Hot Water Supply Systems
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ANSI/ASHRAE 18 (2008; R 2013) Methods Of Testing For Rating Drinking Water Coolers With Self-Contained Mechanical Refrigeration
ASHRAE 90.1 - IP (2019) Energy Standard for Buildings Except Low-Rise Residential Buildings
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME A112.1.2 (2012; R 2017; R 2022) Air Gaps in Plumbing Systems (For Plumbing Fixtures and Water-Connected Receptors)
ASME A112.6.1M (1997; R 2017) Floor Affixed Supports for Off-the-Floor Plumbing Fixtures for Public Use
ASME A112.6.3 (2022) Floor Drains
ASME A112.19.2/CSA B45.1 (2018; ERTA 2018) Standard for Vitreous China Plumbing Fixtures and Hydraulic Requirements for Water Closets and Urinals
ASME A112.19.3/CSA B45.4 (2022) Stainless Steel Plumbing Fixtures
ASME A112.36.2M (2022) Cleanouts
ASME B1.20.1 (2013; R 2018) Pipe Threads, General Purpose (Inch)
ASME B16.5 (2020) Pipe Flanges and Flanged Fittings NPS 1/2 Through NPS 24 Metric/Inch Standard
ASME B16.15 (2018) Cast Copper Alloy Threaded Fittings Classes 125 and 250
ASME B16.18 (2021) Cast Copper Alloy Solder Joint
SECTION 22 00 00 Page 1
Pressure Fittings
ASME B16.22 (2021) Wrought Copper and Copper Alloy Solder Joint Pressure Fittings
ASME B16.24 (2022) Cast Copper Alloy Pipe Flanges, Flanged Fittings, and Valves Classes 150, 300, 600, 900, 1500, and 2500
ASME B16.34 (2021) Valves - Flanged, Threaded and Welding End
ASME B16.39 (2020) Standard for Malleable Iron Threaded Pipe Unions; Classes 150, 250, and 300
ASME B16.50 (2021) Wrought Copper and Copper Alloy Braze-Joint Pressure Fittings
ASME B31.1 (2022) Power Piping
ASME B31.5 (2022) Refrigeration Piping and Heat Transfer Components
ASME B40.100 (2022) Pressure Gauges and Gauge Attachments
ASME BPVC SEC IV (2017) BPVC Section IV-Rules for Construction of Heating Boilers
ASME BPVC SEC VIII D1 (2019) BPVC Section VIII-Rules for Construction of Pressure Vessels Division 1
ASME CSD-1 (2021) Control and Safety Devices for Automatically Fired Boilers
AMERICAN SOCIETY OF SANITARY ENGINEERING (ASSE)
ASSE 1001 (2021) Performance Requirements for Atmospheric Type Vacuum Breakers
ASSE 1003 (2020) Performance Requirements for Water Pressure Reducing Valves for Domestic Water Distribution Systems - (ANSI approved 2010)
ASSE 1010 (2021) Performance Requirements for Water Hammer Arresters
ASSE 1011 (2017) Performance Requirements for Hose Connection Vacuum Breakers
ASSE 1012 (2023) Performance Requirements for Backflow Preventer with an Intermediate Atmospheric Vent
ASSE 1013 (2021) Performance Requirements for Reduced Pressure Principle Backflow Prevention Assemblies
SECTION 22 00 00 Page 2
ASSE 1018 (2023) Performance Requirements for Trap Seal Primer Valves - Potable Water Supplied (ANSI Approved 2002
ASSE 1019 (2023) Performance Requirements for Wall Hydrant with Backflow Protection and Freeze Resistance
ASSE 1020 (2020) Performance Requirements for Pressure Vacuum Breaker Assemblies
ASSE 1037 (2015; R 2020) Performance Requirements for Pressurized Flushing Devices for Plumbing Fixtures
ASSE 1070 (2020) Performance Requirements for Water Temperature Limiting Devices
ASSE 1072 (2020) Performance Requirements for Barrier Type Trap Seal Protection for Floor Drains
AMERICAN WATER WORKS ASSOCIATION (AWWA)
AWWA B300 (2018) Hypochlorites
AWWA B301 (2018) Liquid Chlorine
AWWA C203 (2020) Coal-Tar Protective Coatings and Linings for Steel Water Pipelines - Enamel and Tape - Hot-Applied
AWWA C651 (2014) Standard for Disinfecting Water Mains
AWWA C652 (2019) Disinfection of Water-Storage Facilities
AWWA C700 (2020) Cold-Water Meters - Displacement Type, Metal Alloy Main Case
AWWA C701 (2019) Cold-Water Meters - Turbine Type for Customer Service
AWWA D100 (2021) Welded Steel Tanks for Water Storage
AMERICAN WELDING SOCIETY (AWS)
AWS A5.8/A5.8M (2019) Specification for Filler Metals for Brazing and Braze Welding
AWS B2.2/B2.2M (2016) Specification for Brazing Procedure and Performance Qualification
ASTM INTERNATIONAL (ASTM)
ASTM A53/A53M (2024) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, SECTION 22 00 00 Page 3
Welded and Seamless
ASTM A105/A105M (2021) Standard Specification for Carbon Steel Forgings for Piping Applications
ASTM A193/A193M (2023) Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials for High-Temperature Service and Other Special Purpose Applications
ASTM A515/A515M (2017; R2022) Standard Specification for Pressure Vessel Plates, Carbon Steel, for Intermediate- and Higher-Temperature Service
ASTM A516/A516M (2017) Standard Specification for Pressure Vessel Plates, Carbon Steel, for Moderate-and Lower-Temperature Service
ASTM A733 (2016; R 2022) Standard Specification for Welded and Seamless Carbon Steel and Austenitic Stainless Steel Pipe Nipples
ASTM B32 (2020) Standard Specification for Solder Metal
ASTM B42 (2020) Standard Specification for Seamless Copper Pipe, Standard Sizes
ASTM B43 (2020) Standard Specification for Seamless Red Brass Pipe, Standard Sizes
ASTM B88 (2022) Standard Specification for Seamless Copper Water Tube
ASTM B88M (2020) Standard Specification for Seamless Copper Water Tube (Metric)
ASTM B117 (2019) Standard Practice for Operating Salt Spray (Fog) Apparatus
ASTM B370 (2022) Standard Specification for Copper Sheet and Strip for Building Construction
ASTM B584 (2022) Standard Specification for Copper Alloy Sand Castings for General Applications
ASTM B813 (2016) Standard Specification for Liquid and Paste Fluxes for Soldering of Copper and Copper Alloy Tube
ASTM B828 (2023) Standard Practice for Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings
ASTM C564 (2020a) Standard Specification for Rubber Gaskets for Cast Iron Soil Pipe and Fittings
SECTION 22 00 00 Page 4
ASTM C920 (2018) Standard Specification for Elastomeric Joint Sealants
ASTM D638 (2014) Standard Test Method for Tensile Properties of Plastics
ASTM D1004 (2013) Initial Tear Resistance of Plastic Film and Sheeting
ASTM D1248 (2016) Standard Specification for Polyethylene Plastics Extrusion Materials for Wire and Cable
ASTM D2235 (2004; R 2016) Standard Specification for Solvent Cement for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe and Fittings
ASTM D2564 (2020) Standard Specification for Solvent Cements for Poly(Vinyl Chloride) (PVC) Plastic Piping Systems
ASTM D2665 (2014) Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings
ASTM D2855 (2015) Standard Practice for Making Solvent-Cemented Joints with Poly(Vinyl Chloride) (PVC) Pipe and Fittings
ASTM D3138 (2004; R 2016) Standard Specification for Solvent Cements for Transition Joints Between Acrylonitrile-Butadiene-Styrene (ABS) and Poly(Vinyl Chloride) (PVC) Non-Pressure Piping Components
ASTM D3139 (2019) Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals
ASTM D3212 (2020) Standard Specification for Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals
ASTM D3311 (2017) Standard Specification for Drain, Waste, and Vent (DWV) Plastic Fittings Patterns
ASTM D4551 (2017) Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Flexible Concealed Water-Containment Membrane
ASTM D4586/D4586M (2007; R 2018) Asphalt Roof Cement, Asbestos-Free
ASTM E1 (2014) Standard Specification for ASTM Liquid-in-Glass Thermometers
SECTION 22 00 00 Page 5
ASTM E96/E96M (2024) Standard Test Methods for Gravimetric Determination of Water Vapor Transmission Rate of Materials
ASTM F409 (2022) Standard Specification for Thermoplastic Accessible and Replaceable Plastic Tube and Tubular Fittings
ASTM F477 (2014; R 2021) Standard Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe
ASTM F493 (2022) Standard Specification for Solvent Cements for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe and Fittings
ASTM F891 (2023) Standard Specification for Coextruded Poly (Vinyl Chloride) (PVC) Plastic Pipe with a Cellular Core
ASTM F1760 (2016; R 2020) Standard Specification for Coextruded Poly(Vinyl Chloride) (PVC) Non-Pressure Plastic Pipe Having Reprocessed-Recycled Content
ASTM F2389 (2023) Standard Specification for Pressure-rated Polypropylene (PP) Piping Systems
COPPER DEVELOPMENT ASSOCIATION (CDA)
CDA A4015 (2016; 14/17) Copper Tube Handbook
INTERNATIONAL CODE COUNCIL (ICC)
ICC A117.1 (2017) Standard And Commentary Accessible and Usable Buildings and Facilities
ICC IPC (2024) International Plumbing Code
INTERNATIONAL SAFETY EQUIPMENT ASSOCIATION (ISEA)
ANSI/ISEA Z358.1 (2014; R 2020) American National Standard for Emergency Eyewash and Shower Equipment
MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
MSS SP-25 (2018) Standard Marking System for Valves, Fittings, Flanges and Unions
MSS SP-58 (2018) Pipe Hangers and Supports - Materials, Design and Manufacture, Selection, Application, and Installation
MSS SP-67 (2022) Butterfly Valves
MSS SP-70 (2011) Gray Iron Gate Valves, Flanged and Threaded Ends
SECTION 22 00 00 Page 6
MSS SP-71 (2018) Gray Iron Swing Check Valves, Flanged and Threaded Ends
MSS SP-72 (2010a) Ball Valves with Flanged or Butt-Welding Ends for General Service
MSS SP-78 (2011) Cast Iron Plug Valves, Flanged and Threaded Ends
MSS SP-80 (2019) Bronze Gate, Globe, Angle and Check Valves
MSS SP-83 (2014) Class 3000 Steel Pipe Unions Socket Welding and Threaded
MSS SP-85 (2011) Gray Iron Globe & Angle Valves Flanged and Threaded Ends
MSS SP-110 (2010) Ball Valves Threaded, Socket-Welding, Solder Joint, Grooved and Flared Ends
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA MG 1 (2021) Motors and Generators
NEMA MG 11 (1977; R 2012) Energy Management Guide for Selection and Use of Single Phase Motors
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 90A (2024) Standard for the Installation of Air Conditioning and Ventilating Systems
NSF INTERNATIONAL (NSF)
NSF 372 (2022) Drinking Water System Components - Lead Content
NSF/ANSI 14 (2023) Plastics Piping System Components and Related Materials
NSF/ANSI 61 (2022) Drinking Water System Components - Health Effects
PLASTIC PIPE AND FITTINGS ASSOCIATION (PPFA)
PPFA Fire Man (2016) Firestopping: Plastic Pipe in Fire Resistive Construction
PLUMBING AND DRAINAGE INSTITUTE (PDI)
PDI WH 201 (2010) Water Hammer Arresters Standard
SECTION 22 00 00 Page 7
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE J1508 (2023) Hose Clamp Specifications
U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)
EPA SM 9223 (2004) Enzyme Substrate Coliform Test
PL 93-523 (1974; A 1999) Safe Drinking Water Act
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
10 CFR 430 Energy Conservation Program for Consumer Products
40 CFR 141.80 National Primary Drinking Water Regulations; Control of Lead and Copper;
General Requirements
UNDERWRITERS LABORATORIES (UL)
UL 174 (2004; Reprint Oct 2023) UL Standard for Safety Household Electric Storage Tank Water Heaters
UL 399 (2017; Reprint May 2019) UL Standard for Safety Drinking Water Coolers
UL 499 (2014; Reprint May 2023) UL Standard for Safety Electric Heating Appliances
UL 1951 (2011; Reprint Jun 2020) UL Standard for Safety Electric Plumbing Accessories
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. When used, a code following the "G" classification identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-03 Product Data
Backflow Prevention Assemblies ; G
Fixtures
Shower Faucets ; G
Flush Valve Water Closets
WaterSense Label for Flush Valve Water Closet ; S
Flush Valve Urinals
WaterSense Label for Urinal ; S
SECTION 22 00 00 Page 8
Wall Hung Lavatories
Kitchen Sinks
Service Sinks
Drinking-Water Coolers ; G
WaterSense Label for Showerhead ; S
Water Heaters ; G
Pumps; G
Vibration-Absorbing Features ; G
Plumbing System
Point-Of-Use Mixing Valve
Watersense Label For Lavatory Faucet ; S
SD-06 Test Reports
Tests, Flushing and Disinfection
Test of Backflow Prevention Assemblies ; G.
SD-07 Certificates
Materials and Equipment
SD-10 Operation and Maintenance Data
Plumbing System ; G
1.3 SHOP DRAWINGS
Submit Plumbing System Detail drawings consisting of schedules, performance charts, instructions, diagrams, and other information to illustrate the requirements and operations of systems that are not covered by the Plumbing Code. Submit Plumbing System Detail drawings for the complete plumbing system including piping layouts and locations of connections ; dimensions for roughing-in, foundation, and support points;
schematic diagrams and wiring diagrams or connection and interconnection diagrams. Detail drawings must indicate clearances required for maintenance and operation. Where piping and equipment are to be supported other than as indicated, details must include loadings and proposed support methods. Mechanical drawing plans, elevations, views, and details, must be drawn to scale.
1.4 STANDARD PRODUCTS
Specified materials and equipment must be standard products of a manufacturer regularly engaged in the manufacture of such products.
Specified equipment must essentially duplicate equipment that has performed satisfactorily at least 2 years prior to bid opening. Standard products must have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year use must include applications of
SECTION 22 00 00 Page 9 equipment and materials under similar circumstances and of similar size.
The product must have been for sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2 year period.
Where equipment is specified to conform to requirements of the ASME Boiler and Pressure Vessel Code, the design, fabrication, and installation must conform to the code and a certificate must be submitted for the equipment.
1.4.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturer's factory or laboratory tests, can be shown.
1.4.2 Service Support
The equipment items must be supported by service organizations. Submit a certified list of qualified permanent service organizations for support of the equipment which includes their addresses and qualifications. These service organizations must be reasonably convenient to the equipment installation and able to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
1.4.3 Manufacturer's Nameplate
Each item of equipment must have a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
1.4.4 Modification of References
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction", or words of similar meaning, to mean the Contracting Officer.
1.4.4.1 Definitions
For the International Code Council (ICC) Codes referenced in the contract documents, advisory provisions must be considered mandatory, the word "should" must be interpreted as "must." Reference to the "code official" must be interpreted to mean the "Contracting Officer." For Navy owned property, references to the "owner" must be interpreted to mean the "Contracting Officer." For leased facilities, references to the "owner" must be interpreted to mean the "lessor." References to the "permit holder" must be interpreted to mean the "Contractor."
1.4.4.2 Administrative Interpretations
For ICC Codes referenced in the contract documents, the provisions of Chapter 1, "Administrator," do not apply. These administrative requirements are covered by the applicable Federal Acquisition Regulations (FAR) included in this contract and by the authority granted to the Officer in Charge of Construction to administer the construction of this project. References in the ICC Codes to sections of Chapter 1, must be
SECTION 22 00 00 Page 10 applied appropriately by the Contracting Officer as authorized by his administrative cognizance and the FAR.
1.5 DELIVERY, STORAGE, AND HANDLING
Handle, store, and protect equipment and materials to prevent damage before and during installation in accordance with the manufacturer's recommendations, and as approved by the Contracting Officer. Replace damaged or defective items.
1.6 PERFORMANCE REQUIREMENTS
1.7 REGULATORY REQUIREMENTS
Unless otherwise required herein, plumbing work must be in accordance with
ICC IPC .
1.8 PROJECT/SITE CONDITIONS
The Contractor must become familiar with details of the work, verify dimensions in the field, and advise the Contracting Officer of any discrepancy before performing any work.
1.9 INSTRUCTION TO GOVERNMENT PERSONNEL
Furnish the services of competent instructors to give full instruction to the designated Government personnel in the adjustment, operation, and maintenance, including pertinent safety requirements, of the specified equipment or system. Instructors must be thoroughly familiar with all parts of the installation and must be trained in operating theory as well as practical operation and maintenance work. Submit Plumbing System Operation and Maintenance Data in accordance with Section 01 78 23
OPERATION AND MAINTENANCE DATA.
Instruction must be given during the first regular work week after the equipment or system has been accepted and turned over to the Government for regular operation. The number of man-days (8 hours per day) of instruction furnished must be as specified in the individual section.
When more than 4 man-days of instruction are specified, use approximately half of the time for classroom instruction. Use other time for instruction with the equipment or system. When significant changes or modifications in the equipment or system are made under the terms of the contract, provide additional instruction to acquaint the operating personnel with the changes or modifications.
1.10 ACCESSIBILITY OF EQUIPMENT
Install all work so that parts requiring periodic inspection, operation, maintenance, and repair are readily accessible. Install concealed valves, expansion joints, controls, dampers, and equipment requiring access, in locations freely accessible through access doors.
PART 2 PRODUCTS
2.1 MATERIALS
Materials for various services must be in accordance with TABLES I and II.
Cement pipe must contain recycled content as specified in Section 03 30 00 CAST-IN-PLACE CONCRETE. Pipe schedules must be selected based on
SECTION 22 00 00 Page 11 service requirements. Pipe fittings must be compatible with the applicable pipe materials. Plastic pipe, fittings, and solvent cement must meet NSF/ANSI 14 and must be NSF listed for the service intended.
Plastic pipe, fittings, and solvent cement used for potable hot and cold water service must bear the NSF seal "NSF-PW." Polypropylene pipe and fittings must conform to dimensional requirements of Schedule 40, Iron Pipe size and must comply with NSF/ANSI 14 , NSF/ANSI 61 and ASTM F2389.
Polypropylene piping that will be exposed to UV light must be provided with a Factory applied UV resistant coating. Pipe threads (except dry seal) must conform to ASME B1.20.1 . Material or used in any potable water system intended for human consumption be certified in accordance with NSF 372 with the exception of brazing materials. In line devices such as water meters, building valves, check valves, meter stops, valves, fittings and back flow preventers must comply with PL 93-523 and NSF/ANSI 61 , Section 8. End point devices such as drinking water fountains, lavatory faucets, kitchen and bar faucets, residential ice makers, supply stops and end point control valves used to dispense water for drinking must meet the requirements of NSF/ANSI 61 , Section 9. Hubless cast-iron soil pipe must not be installed underground, under concrete floor slabs, or in crawl spaces below kitchen floors (for Air Force/Army/Navy projects). Plastic pipe must not be installed in air plenums. Plastic pipe must not be installed in a pressure piping system in buildings greater than three stories including any basement levels.
2.1.1 Pipe Joint Materials
Grooved pipe and hubless cast-iron soil pipe must not be used underground. Solder containing lead must not be used with copper pipe.
Cast iron soil pipe and fittings must be marked with the collective trademark of the Cast Iron Soil Institute. Joints and gasket materials must conform to the following:
a. Brazing Material: Brazing material must conform to AWS A5.8/A5.8M , BCuP-5.
b. Brazing Flux: Flux must be in paste or liquid form appropriate for use with brazing material. Flux must be as follows: lead-free; have a 100 percent flushable residue; contain slightly acidic reagents;
contain potassium borides; and contain fluorides.
c. Solder Material: Solder metal must conform to ASTM B32.
d. Solder Flux: Flux must be liquid form, non-corrosive, and conform to ASTM B813, Standard Test 1.
e. PTFE Tape: PTFE Tape, for use with Threaded Metal or Plastic Pipe.
f. Flexible Elastomeric Seals: ASTM D3139, ASTM D3212 or ASTM F477.
g. Solvent Cement for Transition Joints between ABS and PVC Nonpressure Piping Components: ASTM D3138.
h. Plastic Solvent Cement for ABS Plastic Pipe: ASTM D2235.
i. Plastic Solvent Cement for PVC Plastic Pipe: ASTM D2564 and ASTM D2855.
j. Plastic Solvent Cement for CPVC Plastic Pipe: ASTM F493.
k. Flanged fittings including, but not limited to, flanges, bolts, nuts
SECTION 22 00 00 Page 12 and bolt patterns must be in accordance with ASME B16.5 class 150 and must have the manufacturer's trademark affixed in accordance with MSS SP-25 . Flange material must conform to ASTM A105/A105M . Blind flange material must conform to ASTM A516/A516M cold service and ASTM A515/A515M for hot service. Bolts must be high strength or intermediate strength with material conforming to ASTM A193/A193M .
Submit written certification by the bolt manufacturer that the bolts furnished comply with the specified requirements.
l. Copper tubing must conform to ASTM B88, Type K, L or M.
2.1.2 Miscellaneous Materials
Miscellaneous materials must conform to the following:
a. Water Hammer Arrester: PDI WH 201 . Water hammer arrester must be diaphragm or piston type.
b. Copper, Sheet and Strip for Building Construction: ASTM B370.
c. Asphalt Roof Cement: ASTM D4586/D4586M .
d. Hose Clamps: SAE J1508 .
e. Supports for Off-The-Floor Plumbing Fixtures: ASME A112.6.1M .
f. Metallic Cleanouts: ASME A112.36.2M .
g. Plumbing Fixture Setting Compound: A preformed flexible ring seal molded from hydrocarbon wax material. The seal material must be nonvolatile nonasphaltic and contain germicide and provide watertight, gastight, odorproof and verminproof properties.
h. Coal-Tar Protective Coatings and Linings for Steel Water Pipelines:
AWWA C203.
i. Hypochlorites: AWWA B300.
j. Liquid Chlorine: AWWA B301.
k. Gauges - Pressure and Vacuum Indicating Dial Type - Elastic Element:
ASME B40.100 .
l. Thermometers: ASTM E1. Mercury must not be used in thermometers.
2.1.3 Pipe Insulation Material
Insulation must be as specified in Section 23 07 00 THERMAL INSULATION FOR
MECHANICAL SYSTEMS.
2.2 PIPE HANGERS, INSERTS, AND SUPPORTS
Pipe hangers, inserts, and supports must conform to MSS SP-58 .
2.3 VALVES
Valves must be provided on supplies to equipment and fixtures. Valves 2-1/2 inches and smaller must be bronze with threaded bodies for pipe and solder-type connections for tubing . Valves 3 inches and larger must have
SECTION 22 00 00 Page 13 flanged iron bodies and bronze trim. Pressure ratings must be based upon the application. Grooved end valves may be provided if the manufacturer certifies that the valves meet the performance requirements of applicable MSS standard. Valves must conform to the following standards:
Description Standard
Butterfly Valves MSS SP-67
Cast-Iron Gate Valves, Flanged and Threaded Ends
MSS SP-70
Cast-Iron Swing Check Valves, Flanged and Threaded Ends
MSS SP-71
Ball Valves with Flanged Butt-Welding Ends for General Service
MSS SP-72
Ball Valves Threaded, Socket-Welding, Solder Joint, Grooved and Flared Ends
MSS SP-110
Cast-Iron Plug Valves, Flanged and Threaded Ends
MSS SP-78
Bronze Gate, Globe, Angle, and Check Valves
MSS SP-80
Steel Valves, Socket Welding and Threaded Ends
ASME B16.34
Cast-Iron Globe and Angle Valves, Flanged and Threaded Ends
MSS SP-85
Vacuum Relief Valves ANSI Z21.22/CSA 4.4
Water Pressure Reducing Valves ASSE 1003
Water Heater Drain Valves ASME BPVC SEC IV , Part HLW-810:
Requirements for Potable-Water Heaters Bottom Drain Valve
Trap Seal Primer Valves ASSE 1018
SECTION 22 00 00 Page 14
Temperature and Pressure Relief Valves for Hot Water Supply Systems
ANSI Z21.22/CSA 4.4
Temperature and Pressure Relief Valves for Automatically Fired Hot Water Boilers
ASME CSD-1
Safety Code No., Part CW, Article 5
2.3.1 Wall Faucets
Wall faucets with vacuum-breaker backflow preventer must be brass with 3/4 inch male inlet threads, hexagon shoulder, and 3/4 inch hose connection.
Faucet handle must be securely attached to stem.
2.3.2 Wall Hydrants (Frostproof)
ASSE 1019 with vacuum-breaker backflow preventer must have a nickel-brass or nickel-bronze wall plate and flange with nozzle and detachable key handle. A brass or bronze operating rod must be provided within a galvanized iron casing of sufficient length to extend through the wall so that the valve is inside the building, and the portion of the hydrant between the outlet and valve is self-draining. A brass or bronze valve with coupling and union elbow having metal-to-metal seat must be provided. Valve rod and seat washer must be removable through the face of the hydrant. The hydrant must have 3/4 inch exposed hose thread on spout and 3/4 inch male pipe thread on inlet.
2.3.3 Outlet Boxes
2.3.3.1 Washer Box
One-piece, recessed, high-impact plastic box with quarter turn shut-off valves, 1/2 inch hot and cold supplies, 2 inch drain.
2.3.3.2 Ice Maker Box
One-piece, recessed, high impact plastic box with quarter turn shut-off valves, 1/2 inch supply.
2.3.4 Relief Valves
Water heaters and hot water storage tanks must have a combination pressure and temperature (P&T) relief valve. The pressure relief element of a P&T relief valve must have adequate capacity to prevent excessive pressure buildup in the system when the system is operating at the maximum rate of heat input. The temperature element of a P&T relief valve must have a relieving capacity which is at least equal to the total input of the heaters when operating at their maximum capacity. Relief valves must be rated according to ANSI Z21.22/CSA 4.4 . Relief valves for systems where the maximum rate of heat input is less than 200,000 Btuh must have 3/4 inch minimum inlets, and 3/4 inch outlets. Relief valves for systems where the maximum rate of heat input is greater than 200,000 Btuh must have 1 inch minimum inlets, and 1 inch outlets. The discharge pipe from the relief valve must be the size of the valve outlet.
SECTION 22 00 00 Page 15
2.3.5 Point-of-Use Mixing Valve
Provide a point-of-use mixing valve in accordance with ASSE 1070 at lavatories, hand-wash sinks, and washfountain locations. Point-of-use mixing valve must limit the tempered water to not greater than 110 degrees F.
2.4 FIXTURES
Submit list of fixtures with manufacturer, model, and flow rate. Fixtures for use by the physically handicapped must be in accordance with ICC A117.1 .
Vitreous China, nonabsorbent, hard-burned, and vitrified throughout the body must be provided. Porcelain enameled ware must have specially selected, clear white, acid-resisting enamel coating evenly applied on surfaces. No fixture will be accepted that shows cracks, crazes, blisters, thin spots, or other flaws. Fixtures must be equipped with appurtenances such as traps, faucets, stop valves, and drain fittings.
Each fixture and piece of equipment requiring connections to the drainage system, except grease interceptors, must be equipped with a trap. Brass expansion or toggle bolts capped with acorn nuts must be provided for supports, and polished chromium-plated pipe, valves, and fittings must be provided where exposed to view. Fixtures with the supply discharge below the rim must be equipped with backflow preventers. Internal parts of flush valves and flushometer valves, shower mixing valves, shower head face plates,must be copper alloy with all visible surfaces chrome plated.
Plastic in contact with hot water must be suitable for 180 degrees F water temperature.
2.4.1 Lavatories
Vitreous china lavatories shall be provided with two integral molded lugs on the back-underside of the fixture and drilled for bolting to the wall in a manner similar to the hanger plate. Provide WaterSense labeled metering faucet with a maximum flow rate of 0.25 gal per metering cycle.
Provide data identifying WaterSense label for lavatory faucet .
2.4.2 Automatic Controls
Provide hard wired automatic, sensor operated faucets and flush valves to comply with ASSE 1037 and UL 1951 for lavatory faucets, urinals, and water closets. Flushing and faucet systems must consist of solenoid-activated valves with light beam sensors. Flush valve for water closet must include an override pushbutton. Flushing devices must be provided as described in paragraph FIXTURES AND FIXTURE TRIMMINGS.
2.4.3 Flush Valve Water Closets
2.4.3.1 Flush Valve Water Closet Type and Mount
ASME A112.19.2/CSA B45.1 , white vitreous china, siphon jet, elongated bowl, wall mounted, wall outlet, provide with carrier. Top of toilet seat height above floor must be 14 to 15 inches, except 17 to 19 inches for wheelchair water closets. Provide wax bowl ring including plastic sleeve. Provide white solid plastic elongated open-front seat.
2.4.3.2 Flush Valve Water Closet Flush and Flow
Water flushing volume of the water closet and flush valve combination must not exceed 1.28 gallons per flush. Water closets must meet the EPA
SECTION 22 00 00 Page 16
WaterSense product definition and must be EPA WaterSense labeled products. Provide data identifying WaterSense label for flush valve water closet .
2.4.3.3 Flush Valve Water Closet Control Valve
Provide large diameter flush valve including angle control-stop valve, vacuum breaker, tail pieces, slip nuts, and wall plates; exposed to view components must be chromium-plated or polished stainless steel. Flush valves must be nonhold-open type. Mount flush valves not less than 11 inches above the fixture. Mounted height of flush valve must not interfere with the hand rail in ADA stalls. Provide solenoid-activated flush valves including electrical-operated light-beam-sensor to energize the solenoid.
2.4.4 Flush Valve Urinals
ASME A112.19.2/CSA B45.1 , white vitreous china, wall-mounted, wall outlet, siphon jet, integral trap, and extended side shields. Provide urinal with the rim 24 inches above the floor. Water flushing volume of the urinal and flush valve combination must not exceed 0.5 gallons per flush.
Urinals must be EPA WaterSense labeled products. Provide data identifying WaterSense label for urinal .
Provide ASME A112.6.1M concealed chair carriers with vertical steel pipe supports. Provide large diameter flush valve including angle control-stop valve, vacuum breaker, tail pieces, slip nuts, and wall plates; exposed to view components must be chromium-plated or polished stainless steel.
Flush valves must be nonhold-open type. Mount flush valves not less than 11 inches above the fixture. Provide solenoid-activated flush valves including electrical-operated light-beam-sensor to energize the solenoid.
2.4.5 Wall Hung Lavatories
ASME A112.19.2/CSA B45.1 , white vitreous china, straight back type, minimum dimensions of 19 inches wide by 17 inches front to rear, with supply openings for use with top mounted centerset faucets, and openings for concealed arm carrier installation. Provide aerator with faucet.
Provide lavatory faucets and accessories meeting the flow rate and product requirements of the paragraph LAVATORIES. Provide ASME A112.6.1M concealed chair carriers with vertical steel pipe supports and concealed arms for the lavatory. Mount lavatory with the front rim 34 inches above floor and with 29 inches minimum clearance from bottom of the front rim to floor. Provide top-mounted solenoid-activated lavatory faucets including electrical-operated light-beam-sensor to energize the solenoid. Provide piping covers for P-traps, valves, and exposed drain piping per ADA requirement.
2.4.6 Kitchen Sinks
ASME A112.19.3/CSA B45.4 , double compartment, 20 gage stainless steel with integral mounting rim for flush installation, minimum dimensions of 30 inches wide by 21 inches front to rear, with undersides fully sound deadened, with supply openings for use with top mounted washerless sink faucets with hose spray, and with 3.5 inch drain outlet. Provide aerator with faucet. Water flow rate must not exceed 2.2 gpm when measured at a flowing water pressure of 60 psi. Provide stainless steel drain outlets and stainless steel cup strainers. Provide separate 1.5 inch P-trap and drain piping to vertical vent piping from each compartment. Provide top
SECTION 22 00 00 Page 17 mounted washerless sink faucets with hose spray.
2.4.7 Service Sinks
ASME A112.19.2/CSA B45.1 , ASME A112.19.3/CSA B45.4 302 stainless steel with integral back and wall hanger supports, minimum dimensions of 22 inches wide by 20 inches front to rear, with two supply openings in 10 inch high back. Provide floor supported wall outlet cast iron P-trap and stainless steel rim guards as recommended by service sink manufacturer.
Provide back mounted washerless service sink faucets with vacuum breaker and 0.75 inch external hose threads.
2.4.8 Drinking-Water Coolers
ANSI/ASHRAE 18 , UL 399 , NSF/ANSI 61 , ADA and ICC A117.1 . Dual or Bi-Level water coolers to conform to the requirements of DRINKING-WATER COOLER FOR STANDING PERSON and WHEELCHAIR DRINKING WATER COOLER conforming to ICC A117.1 , ANSI/ASHRAE 18 , UL 399 , NSF/ANSI 61 . Wall mounted height water cooler with more than a single thickness of metal between the potable water and the refrigerant in the heat exchanger, wall-hung, bubbler style, air-cooled condensing unit, 8 gph minimum capacity, stainless steel splash receptor and basin, bottle filler, and stainless steel cabinet. Bubblers must be controlled by push levers or push bars, front mounted or side mounted near the front edge of the cabinet. Bubbler spouts must be mounted at maximum of 38 inches to 43 inches above floor.
Spouts must direct water flow at least 4 inches above unit basin and trajectory parallel or nearly parallel to the front of unit. Provide ASME A112.6.1M concealed steel pipe chair carriers.
2.4.9 Shower Faucets
Provide ball joint self-cleaning shower heads. Provide WaterSense labeled showerhead with a maximum flow rate of 1.75 gpm. Provide data identifying WaterSense label for showerhead .
2.4.10 Emergency Eyewash and Shower
ANSI/ISEA Z358.1 , floor supported free standing unit with privacy curtain. Provide deluge shower head, stay-open ball valve operated by pull rod and ring or triangular handle. Provide eyewash dust caps and stay-open ball valve operated by foot treadle or push handle. Unit must deliver a minimum of 20 gpm of water at 30 psig flow pressure for 15 minutes. Eye wash unit must have a minimum of 0.4 gpm of water at 30 psig flow pressure for 15 minutes. Position eye wash nozzles 33 inches to 45 inches above finished floor. Provide copper alloy control valves. Provide an air-gap with the lowest potable eye wash water outlet located above the overflow rim by not less than the International Plumbing Code minimum.
Provide a pressure-compensated tempering valve, with leaving water temperature setpoint adjustable throughout the range 60 degrees F to 95 degrees F. Provide packaged, UL listed, alarm system; including an amber strobe lamp, horn with externally adjustable loudness and horn silencing switch, mounting hardware, and waterflow service within NEMA Type 3 or 4 enclosures and for explosion proof service within NEMA Type 7 or 9 enclosures. Provide electric instantaneous water heter, packaged with fixture, where indicated on plans.
2.5 BACKFLOW PREVENTERS
Backflow prevention devices must be approved by the State or local regulatory agencies. If there is no State or local regulatory agency
SECTION 22 00 00 Page 18 requirements, the backflow prevention devices must be listed by the Foundation for Cross-Connection Control & Hydraulic Research, or any other approved testing laboratory having equivalent capabilities for both laboratory and field evaluation of backflow prevention devices and assemblies. Reduced pressure principle assemblies, double check valve assemblies, atmospheric (nonpressure) type vacuum breakers, and pressure type vacuum breakers must be meet the above requirements.
Backflow preventers with intermediate atmospheric vent must conform to ASSE 1012 . Reduced pressure principle backflow preventers must conform to ASSE 1013 . Hose connection vacuum breakers must conform to ASSE 1011 .
Pipe applied atmospheric type vacuum breakers must conform to ASSE 1001 .
Pressure vacuum breaker assembly must conform to ASSE 1020 . Air gaps in plumbing systems must conform to ASME A112.1.2 .
2.6 DRAINS
2.6.1 Floor and Shower Drains
Floor and shower drains must consist of a galvanized body, integral seepage pan, and adjustable perforated or slotted chromium-plated bronze, nickel-bronze, or nickel-brass strainer, consisting of grate and threaded collar. Floor drains must be cast iron except where metallic waterproofing membrane is installed. Drains must be of double drainage pattern for embedding in the floor construction. The seepage pan must have weep holes or channels for drainage to the drainpipe. The seepage pan and weep holes must not be filled or plugged and have pervious materials (such as pea gravel) or a weep hole protection device to allow drainage. The strainer must be adjustable to floor thickness. A clamping device for attaching flashing or waterproofing membrane to the seepage pan without damaging the flashing or waterproofing membrane must be provided when required. Drains must be provided with threaded connection. Between the drain outlet and waste pipe, a neoprene rubber gasket conforming to ASTM C564 may be installed, provided that the drain is specifically designed for the rubber gasket compression type joint. Floor and shower drains must conform to ASME A112.6.3 . Provide drain with trap primer connection, trap primer, and connection piping. Primer must meet ASSE 1018 .
2.6.1.1 Metallic Shower Pan Drains
Where metallic shower pan membrane is installed, polyethylene drain with corrosion-resistant screws securing the clamping device must be provided.
Polyethylene drains must have fittings to adapt drain to waste piping.
Polyethylene for floor drains must conform to ASTM D1248. Drains must have separate cast-iron "P" trap, circular body, seepage pan, and strainer, unless otherwise indicated.
2.6.1.2 Drains and Backwater Valves
Drains and backwater valves installed in connection with waterproofed floors or shower pans must be equipped with bolted-type device to securely clamp flashing.
2.6.2 Shower Faucets and Drain Fittings
Provide single control pressure equalizing shower faucets with body mounted from behind the wall with threaded connections. Provide ball joint self-cleaning shower heads. Provide WaterSense labeled showerhead with a maximum flow rate of 1.75 gpm. Provide showerheads meeting the
SECTION 22 00 00 Page 19 requirements in the paragraph SHOWER FAUCETS. Provide separate globe valves or angle valves with union connections in each supply to faucet.
2.6.3 Area Drains
Area drains must be plain pattern with polished stainless steel perforated or slotted grate and bottom outlet. The drain must be circular or square with a 12 inch nominal overall width or diameter and 10 inch nominal overall depth. Drains must be cast iron with manufacturer's standard coating. Grate must be easily lifted out for cleaning. Outlet must be suitable for inside caulked connection to drain pipe. Drains must conform to ASME A112.6.3 .
2.6.4 Floor Sinks
Floor sinks must be square, with 12 inch nominal overall width or diameter and 10 inch nominal overall depth. Floor sink must have an acid-resistant enamel interior finish with cast-iron body, ABS sediment bucket, and perforated grate of cast iron in industrial areas and stainless steel in finished areas. The outlet pipe size must be as indicated or of the same size as the connecting pipe.
2.6.5 Trap Seal Protection
2.6.5.1 Barrier-Type Trap Seal Protection Device
Trap must be protected with a barrier-type trap seal protection device conforming to ASSE 1072 and must be installed in accordance with the manufacturer's instructions.
2.7 SHOWER PAN
Shower pan may be copper, or nonmetallic material.
2.7.1 Sheet Copper
Sheet copper must be 16 ounce weight.
2.7.2 Plasticized Polyvinyl Chloride Shower Pan Material
Material must be sheet form. The material must be 0.040 inch minimum thickness of plasticized polyvinyl chloride or chlorinated polyethylene and must be in accordance with ASTM D4551.
2.7.3 Nonplasticized Polyvinyl Chloride (PVC) Shower Pan Material
Material must consist of a plastic waterproofing membrane in sheet form.
The material must be 0.040 inch minimum thickness of nonplasticized PVC and must have the following minimum properties:
a. or ASTM D638:
Ultimate Tensile Strength: 2600 psi Ultimate Elongation: 398 percent 100 Percent Modulus: 445 psi
b. ASTM D1004:
Tear Strength: 300 pounds per inch
SECTION 22 00 00 Page 20
c. ASTM E96/E96M:
Permeance: 0.008 perms
d. Other Properties:
Specific Gravity: 1.29 PVC Solvent: Weldable Cold Crack: minus 53 degrees F Dimensional stability 212 degrees F minus 2.5 percent Hardness, Shore A: 89
2.8 TRAPS
Unless otherwise specified, traps must be plastic per ASTM F409 or copper-alloy adjustable tube type with slip joint inlet and swivel. Traps must be without a cleanout. Provide traps with removable access panels for easy clean-out at sinks and lavatories. Tubes must be copper alloy with walls not less than 0.032 inch thick within commercial tolerances, except on the outside of bends where the thickness may be reduced slightly in manufacture by usual commercial methods. Inlets must have rubber washer and copper alloy nuts for slip joints above the discharge level.
Swivel joints must be below the discharge level and must be of metal-to-metal or metal-to-plastic type as required for the application.
Nuts must have flats for wrench grip. Outlets must have internal pipe thread, except that when required for the application, the outlets must have sockets for solder-joint connections. The depth of the water seal must be not less than 2 inches. The interior diameter must be not more than 1/8 inch over or under the nominal size, and interior surfaces must be reasonably smooth throughout. A copper alloy "P" trap assembly consisting of an adjustable "P" trap and threaded trap wall nipple with cast brass wall flange must be provided for lavatories. The assembly must be a standard manufactured unit and may have a rubber-gasketed swivel joint.
2.9 WATER HEATERS
Water heater types and capacities must be as indicated. Each water heater must have replaceable anodes. Each primary water heater must have controls with an adjustable range that includes 90 to 160 degrees F. Hot water systems utilizing recirculation systems must be tied into building off-hour controls. The thermal efficiencies and standby heat losses must conform to TABLE III in PART 3 of this Section for each type of water heater specified. The only exception is that storage water heaters and hot water storage tanks having more than 500 gallons storage capacity need not meet the standard loss requirement if the tank surface area is insulated to R-12.5 and if a standing light is not used. Plastic materials polyetherimide (PEI) and polyethersulfone (PES) are forbidden to be used for vent piping of combustion gases. A factory pre-charged expansion tank must be installed on the cold water supply to each water heater. Expansion tanks must be specifically designed for use on potable water systems and must be rated for 200 degrees F water temperature and 150 psi working pressure. The expansion tank size and acceptance volume must be as indicated.
2.9.1 Automatic Storage Type
Heaters must be complete with control system, and must have ASME rated
SECTION 22 00 00 Page 21 combination pressure and temperature relief valve.
2.9.1.1 Electric Type
Electric type water heaters must conform to UL 174 with dual heating elements.
2.9.2 Electric Instantaneous Water Heaters (Tankless)
UL 499 and UL listed flow switch activated, tankless electric instantaneous water heater for wall mounting below sink or lavatory.
Temperature rise at Flow Rate: as indicated on drawings.
2.10 HOT-WATER STORAGE TANKS
Hot-water storage tanks must be constructed by one manufacturer, ASME stamped for the working pressure, and must have the National Board (ASME) registration. The specification AWWA D100 provides standards for water storage tanks, not domestic hot water storage tanks under domestic water pressure. The statement prior describes the tanks being ASME, it must be ASME BPVC (Boiler and Pressure Vessel Code), stamped for working pressure. The two statements combined describe a hot water storage tank under domestic water pressure. The tank must be cement-lined or glass-lined steel type in accordance with AWWA D100. The heat loss must conform to TABLE III in PART 3 of this Section as determined by the requirements of ASHRAE 90.1 - IP . Each tank must be equipped with a thermometer, conforming to ASTM E1, Type I, Class 3, Range C, style and form as required for the installation, and with 7 inch scale. Thermometer must have a separable socket suitable for a 3/4 inch tapped opening.
Tanks must be equipped with a pressure gauge 6 inch minimum diameter face. Insulation must be as specified in Section 23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS. Storage tank capacity must be as shown. Install hot water storage tanks with access hatches in order to facilitate annual cleaning and inspections.
2.11 PUMPS
2.11.1 Circulating Pumps
Domestic hot water circulating pumps must be electrically driven, single-stage, centrifugal, with mechanical seals, suitable for the intended service. Pump and motor must be supported by the piping on which it is installed. The shaft must be one-piece, heat-treated, corrosion-resisting steel with impeller and smooth-surfaced housing of bronze.
2.11.1.1 Circulating Pump Enclosure
Motor must be totally enclosed, fan-cooled and must have sufficient horsepower for the service required. Each pump motor must be equipped with an across-the-line magnetic controller in a NEMA 250, Type 1 enclosure with "START-STOP" switch in cover.
2.11.1.2 Circulating Pump Size and Efficiency
Integral size motors must be premium efficiency type in accordance with NEMA MG 1. Pump motors smaller than 1 hp Fractional horsepower pump motors must have integral thermal overload protection in accordance with Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Guards must shield exposed moving parts.
SECTION 22 00 00 Page 22
2.12 COMPRESSED AIR SYSTEM
2.12.1 Air Compressors
Air compressor unit must be a factory-packaged assembly, including 3 phase, 460 volt motor controls, switches, wiring, accessories, and motor controllers, in a NEMA 250, Type 1 enclosure. Tank-mounted air compressors must be manufactured to comply with UL listing requirements.
Air compressors must have manufacturer's name and address, together with trade name, and catalog number on a nameplate securely attached to the equipment. Each compressor must start and stop automatically at upper and lower pressure limits of the system. Guards must shield exposed moving parts. Each compressor motor must be provided with an across-the-line-type magnetic controller, complete with low-voltage release. An intake air filter and silencer must be provided with each compressor. Aftercooler and moisture separator must be installed between compressors and air receiver to remove moisture and oil condensate before the air enters the receiver. Aftercoolers must be either air- or water-cooled, as indicated. The air must pass through a sufficient number of tubes to affect cooling. Tubes must be sized to give maximum heat transfer. Water to unit must be controlled by a solenoid or pneumatic valve, which opens when the compressors start and closes when the compressors shut down. Cooling capacity of the aftercooler must be sized for the total capacity of the compressors. Means must be provided for draining condensed moisture from the receiver by an automatic float type trap. Capacities of air compressors and receivers must be as indicated.
2.12.2 Air Receivers
Receivers must be designed for 200 psi working pressure. Receivers must be factory air tested to 1-1/2 times the working pressure. Receivers must be equipped with safety relief valves and accessories, including pressure gauges and automatic and manual drains. The outside of air receivers may be galvanized or supplied with commercial enamel finish. Receivers must be designed and constructed in accordance with ASME BPVC SEC VIII D1 and must have the design working pressures specified herein.
This is the start of the file's text. The full file is on GovTribe.