valusine_TS Specifications.pdf

PDF 452 KB Posted

Attached to
Z1NZ--UPS Maintenance - SF
Solicitation number
36C26324Q0373
Issued by

About this file

This document includes a technical specifications guide and a related federal contract opportunity solicitation. The technical specifications guide outlines the requirements for single-phase uninterruptible power supply systems to provide emergency lighting, including solid-state electronics, battery subsystems, inverters, chargers, and monitoring panels. Specified models range in capacity from 500 to 2100 watts, with 90-minute battery runtimes.

The related federal contract opportunity is a solicitation from the Department of Veterans Affairs seeking preventative maintenance services for uninterruptible power supply systems at the Sioux Falls VA Health Care System. Quotes are due by March 28, 2024 for the base year covering May 1, 2024 to April 30, 2025, with four optional one-year extensions. The solicitation is set aside for small businesses with a NAICS code of 811310 and size standard of $12.5 million.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

6005-199P Rev D. ECO# 11896 Page 1 of 5

TECHNICAL GUIDE SPECIFICATIONS

VALUSINE

Single Phase, (500 to 2100 Watts) UL924 Central Lighting Inverter

1. SCOPE

The Emergency Lighting Power System shall be a solid-state single phase unit designed to provide regulated and conditioned sinusoidal power for emergency lighting applications. The Emergency Lighting Power System shall provide uninterrupted power during all modes of operation. There shall be no interruption of power to the lighting system when the unit transfers to and from battery operation. The Emergency Lighting Power System and battery subsystem shall be listed to UL 924 Standard for Emergency Lighting and Power Equipment by a nationally recognized organization.

2. MODES OF OPERATION

NORMAL: During normal operation, utility (or generator) power is thoroughly conditioned and regulated by solid state electronics. The Solid-State Electronics in conjunction with the input filter, filters noise and transients from the incoming power.

Additionally, the Solid-State Electronics regulates its output voltage to within specified limits. The rectifier section maintains the batteries in a fully charged state.

EMERGENCY: Upon loss of input power or when power exceeds the specified input limits, the control logic shall transfer to operation and disconnect the input line. The transfer to battery shall be an uninterrupted or "no break" power transfer. The inverter shall supply power from the batteries and through the Solid-State Electronics to the lighting system. The output shall be sinusoidal and within specified limits. If power is not restored before the batteries have been exhausted, the Inverter shall completely shutdown, protecting the batteries from possible damage.

RECHARGE: Upon restoration of input power and before the batteries are completely exhausted, the Inverter shall automatically return to normal operation. This retransfer to normal operation shall be uninterrupted. The battery charger shall automatically recharge the batteries to full capacity. The battery charger shall recharge the batteries as set forth in U.L. Standard 924

3. MAJOR SYSTEM COMPONENTS

Emergency Lighting Power System shall consist of the following major subsystems:

SOLID STATE ELECTRONICS: The Solid-State Electronics shall provide regulation and conditioning from incoming power aberrations. Power to the critical load shall be supplied by the Solid-State Electronics whether the Inverter is in normal mode or emergency mode. The output wave shape shall be sinusoidal for all modes of operation.

BATTERY SUBSYSTEM: Sealed, maintenance-free batteries shall be provided. The batteries shall have an expected life of ten (10) years. The batteries shall be fully wired and contained within its own section. Battery run time (based on 100% full load) shall be no less than ninety

(90) minutes. Optional Extended battery run times greater then ninety (90) minutes shall be available.

INVERTER: The Emergency Lighting Power System shall convert DC power supplied from the batteries into AC power.

6005-199P Rev D. ECO# 11896 Page 2 of 5

CHARGER: A battery charger shall be provided. The battery charger shall maintain the batteries at full charge. The battery charger shall be sized such that it recharges the batteries as set forth in UL Standard 924.

POWER CONNECTIONS: The Emergency Lighting Power System input and output shall be hard wired. A main Input, Output and DC circuit breaker shall be provided. The main Input circuit breaker provides over-current protection and a means to easily disconnect power form the lighting system.

TRANSFORMER: Unit shall utilize auto transformer for 277 Volt input & output only.

MONITORING PANEL:

MONITORING PANEL:

(1) LCD DISPLAY: This Indicates the UPS operation information, including UPS status, input/output voltage, input/output frequency, battery voltage, battery capacity left, output load, inside temperature, and the times of history events. Besides, UPS output voltage and output frequency can be set from the LCD panel.

(2) KEY SELECT UP: It is pressed to select upward the UPS status on LCD Display. When this key is pressed with the LCD Select Down-key simultaneously for 3 seconds, the UPS will be switched off.

(3) KEY SELECT DOWN: It is pressed to select downward the UPS status on LCD Display.

(4) KEY ON-OFF CONTROL (only available during maintenance and or repair):

When this key is pressed with the LCD Select Down-Key simultaneously for 3 seconds, the UPS will be switched on. Besides, in the mode of battery back-up, press both of this key and LCD Select UP-key at the same time to disable the beeps.

(5) FAULT LED: This red LED indicates the UPS is in fault condition because of inverter abnormal or over-temperature or DC_BUS fault.

(6) WARNING LED: This yellow LED indicates the UPS is the status of overload, bypass or battery back-up.

(7) NORMAL LED: This green LED indicates the UPS is operating normally.

6005-199P Rev D. ECO# 11896 Page 3 of 5

4. OPTIONS:

Norm ON C.B options: Unit shall provide up to 12 optional 1 pole 20amp din-rail output circuit breakers.

Norm OFF or Norm ON W/delay C.B options: Unit shall provide up to 12 Normally OFF or Normally ON with time delay din rail Circuit Breakers.

MBS (Maintenance by-pass manual).

Communication interface: Unit shall have RS232 and USP communication port Option.

SNMP/Web Card: SNMP shall allow direct monitoring in SNMP based networks for monitoring of the Unit through web browser.

External Auxiliary TVSS: Input Transient voltage suppressor shall comply with UL1449 third edition.

Remote status panel (AS400C W/ RELAY CARD & REMOTE MONITOR).

Floor mount brackets: Unit shall be floor mountable.

RS232.

Battery Exerciser and event logger: Unit shall provide battery testing to comply with UL924.

Thermal runaway control by shutting of charger: Unit shall provide a

“BATT OVER TEMP” alarm.

6005-199P Rev D. ECO# 11896 Page 4 of 5

5. SPECIFICATIONS:

Specifications for 120VVAC /277VAC

Capacity (W) Description 500 750 1000 1250 1500 2100

Input Voltage Single Phase 120Vac or 277Vac Voltage Range 120Vac ±10% or or 277Vac Frequency 60Hz +/- 4Hz

Output

Voltage (on battery) Single Phase 120Vac or 277Vac

Voltage Range 120Vac ±2% or 277Vac

Frequency (on battery) 60 Hz +/-0.5%

Transfer Time 0 ms

Overload Recovery Auto transfer to UPS

High Efficiency mode (AC to AC)

> 95 %

UPS Design Technology On-Line / Fully digitized microprocessor controlled

Output Wave Form Sine wave

Harmonic distortion < 3% of T.H.D. at linear load

Protection and Filtering

Overload Protection 125% for 1 minutes and 150% for 10 seconds

Short Circuit Protection Circuit breaker

System/Display/ Warning

Visual Display (LED model)

UPS on(green), line-mode(green), battery mode(yellow), bypass(yellow), fault(red)

Visual Display (LCD model)

Input / output voltage, input / output frequency, on-line mode, back up mode, battery capacity, load level Audible Alarm (Battery back-up)

Beep every 5 sec

UPS Fault Continuous beeping sound and LCD display

Communication RS-232 Serial Port and USB

Battery 90 min. UL924 (Sealed, maintenance free lead acid battery

8X26 A/H 8X35 A/H 8X35 A/H 8X50 A/H 8X65 A/H 8X65A/H

Dimensions (Inches) Width x Height x Depth 23.5 X 34.25 X 18.25

Environmental

Operating Temperature 0 - 40ºC / 32 ~ 104ºF Storage Temperature -20 ~ 50ºC / -4 ~ 122ºF Audible Noise (1 meter from surface)

< 40 dBA

Relative Humidity 0 ~ 95% humidity, non-condensing Note: Due to continuous improvement specifications are subject to change without prior notice

6005-199P Rev D. ECO# 11896 Page 5 of 5

Floor Mount Lighting Inverter 90 minute battery backup

Total/ WATT Model Numbers

Input/Output Voltages

BTU/

Hr

Cabinet Dimension (W”xH”xD”)

VS.50A0100N1-S 120V/120V 478

23.5x34.25x18.25

500W VS.50R0100T1-S 277V/120V 550

VS.50R2500T1-S 277V/277V 550

VS.50A2500T1-S 120V/277V 550

750W

VS.75A0100N1-S 120V/120V 492

VS.75R0100T1-S 277V/120V 575

VS.75R2500T1-S 277V/277V 575

VS.75A2500T1-S 120V/277V 575

1000W

VS1.0A0100N1-S 120V/120V 615

VS1.0R0100T1-S 277V/120V 675

VS1.0R2500T1-S 277V/277V 675

VS1.0A2500T1-S 120V/277V 675

1250W

VS1.2A0100N1-S 120V/120V 780

VS1.2R0100T1-S 277V/120V 890

VS1.2R2500T1-S 277V/277V 890

VS1.2A2500T1-S 120V/277V 890

1500W

VS1.5A0100N1-S 120V/120V 925

VS1.5R0100T1-S 277V/120V 1100

VS1.5R2500T1-S 277V/277V 1100

VS1.5A2500T1-S 120V/277V 1100

2100W

VS2.1A0100N1-S 120V/120V 1175

VS2.1R0100T1-S 277V/120V 1525

VS2.1R2500T1-S 277V/277V 1525

VS2.1A2500T1-S 120V/277V 1525

(NOTE)

** BTU/HR ARE APROX. NUMBER WITH TOLERANCE ± 15% FOR ALL

MODELS