This is a solicitation for uninterruptible power source preventive maintenance services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23 is seeking these services for the VA Sioux Falls Health Care System. The period of performance is from May 1, 2024 to April 30, 2025 for the base year with four optional one-year periods. The NAICS code is 811310 with a size standard of $12.5 million. This procurement is set aside for small businesses. Quotes are due by March 28, 2024 and shall be emailed to the contracting officer. The solicitation includes provisions for fixed price contracts and standard clauses for commercial items under FAR Part 12 and Part 13.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Galaxy VS

UPS

Operation

5/2020 www.schneider-electric.com

Legal Information The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners.

This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.

Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is" basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel.

As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice.

To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or consequences arising out of or resulting from the use of the information contained herein.

Go to IEC: https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_iec/ or UL: https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_ul/ or scan the QR code above for digital experience and translated manuals.

Table of Contents

Important Safety Instructions — SAVE THESE

INSTRUCTIONS

FCC Statement Electromagnetic Compatibility Safety Precautions ENERGY STAR Qualification

Overview of User Interface Display

Menu Tree Controller Section

Operation Modes UPS Modes System Modes

Configuration Configure the UPS Input Configure the Output

Output Transformer Voltage Compensation Configure the Battery Solution Configure High Efficiency Mode Configure the Breakers Configure the Input Contacts Configure the Output Relays Configure the Network Configure the Modbus Set the UPS Name Set the Date and Time Configure the Display Preferences Configure the Air Filter Reminder Save the UPS Settings on a USB Device Restore the UPS Settings from a USB Device Set the Display Language Change the Password

Operation Procedures Start Up the UPS System from Off Mode Transfer the UPS from Normal Operation to Static Bypass Operation Transfer the UPS from Static Bypass Operation to Normal Operation Turn the Inverter OFF Turn the Inverter ON Set the Charger Mode Shut Down the UPS System into Maintenance Bypass Operation Shut Down into Maintenance Bypass Operation for Single UPS System with Kirk Key Installed Start Up the UPS System from Maintenance Bypass Operation Start Up from Maintenance Bypass Operation for Single UPS System with Kirk Key Installed

990-5910D-001 3

Access a Configured Network Management Interface Enable HTTP/HTTPS Protocols Enable SNMP Protocols

View the Logs View the System Status Information

View the Modular Battery Status

Tests Start a Runtime Calibration Test Stop a Runtime Calibration Test Start a Battery Test Stop a Battery Test

Maintenance Connect Temperature/Humidity Sensor (Option) Replace the Air Filter (GVSOPT001 and GVSOPT015) Replace the Air Filters (GVSOPT014) Replace or Install a Modular Battery String Determine if you need a Replacement Part

Find the Serial Numbers Return Parts to Schneider Electric

Troubleshooting Status LED Lighting per UPS Operation Mode Status LEDs on the Modular Battery Cabinet Alarm Messages Export UPS Report to a USB Device

4 990-5910D-001

Important Safety Instructions — SAVE THESE

INSTRUCTIONS UPS

Important Safety Instructions — SAVE THESE

INSTRUCTIONS

Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following safety messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of this symbol to a “Danger” or “Warning” safety message indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages with this symbol to avoid possible injury or death.

DANGER

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

Failure to follow these instructions will result in death or serious injury.

WARNING

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

CAUTION

CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.

Failure to follow these instructions can result in injury or equipment damage.

NOTICE

NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this type of safety message.

Failure to follow these instructions can result in equipment damage.

Please Note Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.

990-5910D-001 5

Important Safety Instructions — SAVE THESE

INSTRUCTIONS

FCC Statement NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

Electromagnetic Compatibility

NOTICE

RISK OF ELECTROMAGNETIC DISTURBANCE

This is a product category C2 UPS product. In a residential environment, this product may cause radio inference, in which case the user may be required to take additional measures.

Failure to follow these instructions can result in equipment damage.

Safety Precautions

DANGER

HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH

All safety instructions in this document must be read, understood and followed.

Failure to follow these instructions will result in death or serious injury.

DANGER

HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH

After the UPS system has been electrically wired, do not start up the system.

Start-up must only be performed by Schneider Electric.

Failure to follow these instructions will result in death or serious injury.

ENERGY STAR Qualification

Select models are ENERGY STAR® qualified.

For more information on your specific model go to www.se.

com.

6 990-5910D-001

Overview of User Interface UPS

Overview of User Interface

Display

Overview of the Home Screen

A. Home button - tap here on any screen to return to the home screen.

B. Main menu button - tap here to access the menus.

C. Mimic diagram button - tap here to access the mimic diagram.

D. Alarm status symbol - tap here to access the active alarms log.

You can tap on the output or battery fields on the home screen to go directly to the detailed measurement pages.

Main Menu

Tap the main menu button on the home screen to access the menus.

990-5910D-001 7

UPS Overview of User Interface

Mimic Diagram

The mimic diagram will adapt to your system configuration – the mimic diagrams shown here are just examples.

The green power line (gray in illustration) in the mimic diagram shows the power flow through the UPS system. Active modules (inverter, rectifier, battery, static bypass switch, etc.) are framed in green and inactive modules are framed in black.

Modules framed in red are inoperable or in an alarm condition.

In mimic diagrams for parallel systems, tap on the gray UPS to see the mimic diagram on UPS level.

NOTE: The mimic diagram only shows one battery breaker BB even if more battery breakers have been connected and configured for monitoring. If one or more of the monitored battery breakers are in the closed position, the BB on the mimic diagram will show as closed. If all of the monitored battery breakers are in the open position, the BB on the mimic diagram will show as open.

Example of Single UPS System – Dual Mains

Example of Simplified 1+1 Parallel System – Dual Mains

8 990-5910D-001

Example of Parallel System – Dual Mains

Alarm Status Symbol

The alarm status symbol (gray in illustration) in the top right corner of the display changes depending on the alarm status of the UPS system.

Green: No alarms present in the UPS system.

Blue: Informational alarm(s) present in the UPS system. Tap the alarm status symbol to open the active alarms log.

Yellow: Warning alarm(s) present in the UPS system. Tap the alarm status symbol to open the active alarms log.

Red: Critical alarm(s) present in the UPS system. Tap the alarm status symbol to open the active alarms log.

990-5910D-001 9

UPS Overview of User Interface

Menu Tree

Tap the main menu button on the home screen to access the menus.

• Status

◦ Input

◦ Output

◦ Bypass

◦ Battery

◦ Temperature

◦ Parallel

• Logs

• Control1

◦ Operation mode

◦ Inverter

◦ Charger

◦ Guided sequences

• Configuration1

◦ UPS

◦ Output

◦ Battery

◦ High efficiency

◦ Breakers

◦ Contacts and relays

◦ Network

◦ Modbus

◦ General

◦ Reminder

◦ Save/restore

◦ Update status

• Maintenance

◦ Buzzer

◦ Status LEDs

◦ Breaker lamp

◦ Battery1

◦ Runtime calibration1

◦ Battery replacement1

◦ UPS report1

• About

• Logout

• Flag button – See Set the Display Language, page 33.

Some menus contain more submenus than described in this manual. These submenus are grayed out and are only for use by Schneider Electric to avoid unwanted load impacts. Other menu items can also be grayed out if they are not relevant for this particular UPS system.

10 990-5910D-001

1. This menu requires administrator login to access.

Controller Section NOTE: Remove the front panel to access the controller section.

Front View of the Controller Section

A. Inverter ON/OFF buttons B. USB ports2

C. Universal I/O2

D. Modbus port2

E. USB Micro-B port2

F. Network port2

G. Reset button2

H. Input status LED3

I. Inverter status LED3

J. Output status LED3

K. Bypass status LED3

L. Battery status LED3

M. Display power supply N. Display port O. Service port4

P. For future use Q. For future use

R. PBUS 15

S. PBUS 25

990-5910D-001 11

2. Built-in network management card.

3. See Status LED Lighting per UPS Operation Mode, page 56.

4. The service port can only be used by a Schneider Electric Field Service Representative with approved Schneider Electric tools to configure the unit, retrieve logs, and upgrade firmware. The service port cannot be used for any other purpose. The service port is only active when the Field Service Representative is within physical proximity to the UPS and manually activates the connection. Do not connect to a network. The connection is not intended for network operation and may cause inoperability of the network.

5. Do not disconnect during operation of the UPS. Do not connect to a network. The connection is not intended for network operation and may cause inoperability of the network.

UPS Operation Modes

Operation Modes The Galaxy UPS has two different levels of operation modes:

• UPS mode: The operation mode of the individual UPS. See UPS Modes, page 12.

• System mode: The operation mode of the complete UPS system that supplies the load. See System Modes, page 14.

UPS Modes

Normal Operation

In normal operation, the UPS supports the load with conditioned power.

Battery Operation

If the utility/mains supply fails, the UPS transfers to battery operation and supports the load with conditioned power from the DC source.

Requested Static Bypass Operation

The UPS can be transferred to requested static bypass operation following a command from the display. During requested static bypass operation, the load is supplied from the bypass source. If a fault is detected, the UPS will transfer to normal operation or forced static bypass operation. If there is an interruption to the utility/mains supply during requested static bypass operation, the UPS will transfer to battery operation.

Forced Static Bypass Operation

The UPS is in forced static bypass operation following a command from the UPS or because the user has pressed the inverter OFF button on the UPS. During forced static bypass operation, the load is supplied from the bypass source.

NOTE: The batteries are not available as an alternate power source while the UPS is in forced static bypass operation.

Internal Maintenance Bypass Operation via the Internal Maintenance Breaker IMB

When the internal maintenance breaker IMB is closed, the UPS transfers to internal maintenance bypass operation. The load is supplied with unconditioned power from the bypass source. Service and replacement can be performed on power modules, the static bypass switch module, and on the controller box during internal maintenance bypass operation via the internal maintenance breaker IMB.

The internal maintenance breaker IMB can only be used in single systems and in simplified 1+1 parallel systems with no external maintenance bypass breaker.

NOTE: The batteries are not available as an alternate power source while the UPS is in internal maintenance bypass operation.

External Maintenance Bypass Operation via the Maintenance Bypass Breaker MBB

When the maintenance bypass breaker MBB is closed in the external maintenance bypass panel/cabinet or third party switchgear, the UPS transfers to external maintenance bypass operation. The load is supplied with unconditioned power from the bypass source. Service and replacement can be performed on the entire UPS during external maintenance bypass operation via the maintenance bypass breaker MBB.

12 990-5910D-001

Operation Modes UPS

NOTE: The batteries are not available as an alternate power source while the UPS is in external maintenance bypass operation.

Static Bypass Standby Operation

Static bypass standby is only applicable to an individual UPS in a parallel system.

The UPS enters static bypass standby operation if the UPS is prevented from entering forced static bypass operation and the other UPSs of the parallel system can support the load. In static bypass standby the output of the specific UPS is OFF. The UPS automatically transfers to the preferred operation mode when possible.

NOTE: If the other UPSs cannot support the load, the parallel system transfers to forced static bypass operation. The UPS in static bypass standby operation will then transfer to forced static bypass operation.

Battery Test

The UPS is in battery test mode when the UPS is performing a battery self-test or a runtime calibration.

NOTE: The battery test will be aborted if the utility/mains supply is interrupted or if a critical alarm is present and the UPS will return to normal operation upon return of utility/mains.

ECO Mode

ECO mode allows the UPS to be configured to use requested static bypass, with the load supplied through the bypass, as the preferred operation mode under predefined circumstances. If a fault is detected (bypass voltage out of tolerance, output voltage out of tolerance, etc), the UPS will immediately transfer to normal operation or forced static bypass. The main advantage of ECO mode is a reduction in the consumption of electrical power. In case of interruption to the utility/mains supply, the UPS transfers to battery operation for an uninterrupted supply of the load. The batteries are charged when the UPS is in ECO mode.

NOTE:When changes to ECO mode settings are made on one UPS in a parallel system, the settings are shared to all UPSs in the parallel system.

ECOnversion Mode

ECOnversion allows the UPS to supply the active part of the load through the static bypass. The inverter is kept running in parallel with the bypass source and supplies the reactive part of the load. The input power factor of the UPS is, regardless of the load power factor, maintained close to unity as the reactive part of the load is significantly reduced in the UPS input current. In case of an interruption to the utility/mains supply, the inverter immediately maintains the output voltage so that breaks or drops during the transfer from ECOnversion mode are practically eliminated. The batteries are charged when the UPS is in ECOnversion mode.

NOTE:When changes to ECOnversion mode settings are made on one UPS in a parallel system, the settings are shared to all UPSs in the parallel system.

OFF Mode

The UPS is not supplying the load with power. The batteries are charged and the display is on.

990-5910D-001 13

UPS Operation Modes

System Modes The system mode indicates the output status of the complete UPS system including the surrounding switchgear and indicates which source supplies the load.

Inverter Operation

In inverter operation the load is supplied by the inverters. The UPS mode can be in either normal or battery operation when the system operation mode is inverter operation.

Requested Static Bypass Operation

When the system is in requested static bypass operation, the load is supplied from the bypass source. If a fault is detected, the system will transfer to inverter operation or forced static bypass operation.

Forced Static Bypass Operation

The system is in forced static bypass operation following a command from the UPS system or because the user has pressed the inverter OFF button on the UPSs. During forced static bypass operation, the load is supplied directly by the bypass source with unconditioned power.

NOTE: The batteries are not available as an alternate power source while the system is in forced static bypass operation.

Maintenance Bypass Operation

In maintenance bypass operation, the load is supplied directly by the bypass source with unconditioned power.

NOTE: The batteries are not available as an alternate power source in maintenance bypass operation.

ECO Mode

ECO mode allows the system to be configured to use requested static bypass operation, with the load supplied through the bypass, as the preferred operation mode under predefined circumstances. The main advantage of ECO mode is a reduction in the consumption of electrical power. In case of interruption to the utility/mains supply, the UPS transfers to inverter operation for an uninterrupted supply of the load.

NOTE:When changes to ECO mode settings are made on one UPS in a parallel system, the settings are shared to all UPSs in the parallel system.

ECOnversion Mode

ECOnversion allows the system to supply the active part of the load through the bypass. The inverter is kept running in parallel with the bypass source and supplies the reactive part of the load. The input power factor of the UPS is, regardless of the load power factor, maintained close to unity as the reactive part of the load is significantly reduced in the UPS input current. In case of an interruption to the utility/mains supply, the inverter immediately maintains the output voltage so that breaks or drops during the transfer from ECOnversion mode are practically eliminated.

NOTE:When changes to ECOnversion mode settings are made on one UPS in a parallel system, the settings are shared to all UPSs in the parallel system.

14 990-5910D-001

Operation Modes UPS

OFF Mode

The system is not supplying the load with power. The batteries are charged and the display is on.

990-5910D-001 15

UPS Configuration

Configuration

Configure the UPS Input NOTE: This configuration is mandatory for correct UPS operation.

1. Tap Configuration > UPS.

a. Set theMains configuration to Single mains or Dual mains.

b. Select Autostart of the inverter if you want to enable this function.

When Autostart of the inverter has been enabled, the inverter will start up automatically when input voltage returns, after a shutdown due to drained battery.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Always perform correct Lockout/Tagout before working on the UPS. A UPS with autostart enabled will automatically restart when the mains supply returns.

Failure to follow these instructions will result in death or serious injury.

c. Set Transformer present to No transformer present, Input transformer, or Output transformer.

2. Tap OK to save your settings.

16 990-5910D-001

Configuration UPS

Configure the Output NOTE: This configuration is mandatory for correct UPS operation.

1. Tap Configuration > Output.

a. Set the AC voltage ph-ph to 200VAC, 208VAC, 220VAC, 380VAC, 400VAC, 415VAC, or 480VAC depending on your configuration. (Not all voltages are available in all regions.)

b. Set the Frequency to 50Hz ±1.0, 50Hz ±3.0, 50Hz ±10.0, 60Hz ±1.0, 60Hz ±3.0, or 60Hz ±10.0 depending on your configuration.

c. Tap OK to save your settings and tap the arrow symbol to go to the next page.

990-5910D-001 17

d. Set the Bypass and output tolerance (%). The bypass and output tolerance range is +3% to +10%, default is +10%.

e. Set the Voltage compensation (%). The output voltage of the UPS can be adjusted up to ±3% to compensate for different cable lengths.

f. Set the Overload threshold (%). The overload range is 0% to 100%, default is 75%.

g. Set the Transformer voltage compensation (%). The transformer voltage compensation range is 0% to 3%, default is 0%. See Output Transformer Voltage Compensation, page 18 for more details and Configure the UPS Input, page 16 for configuring that an output transformer is present.

h. Tap OK to save your settings.

Output Transformer Voltage Compensation

It is possible to compensate for an output transformer and balance the output voltage drop (0-3%). The output transformer voltage compensation works without having the UPS to measure the voltage on the secondary side of the transformer.

1. At 0% load you must measure the voltage on the secondary side of the transformer, and the output voltage of the UPS is then manually adjusted via the Voltage compensation (%) setting to offset compensation if necessary.

2. Then load must be applied on the UPS. You must measure the voltage on the secondary side of the transformer again, and the output voltage of the UPS must be adjusted via the Transformer voltage compensation (%) setting to compensate for the voltage drop in the transformer.

The voltage compensation required at the specific load is used to make an automatic linear output voltage adjustment on the UPS according to the output load percentage.

18 990-5910D-001

Configure the Battery Solution

DANGER

HAZARD OF ELECTRICAL SHOCK, EXPLOSION, OR ARC FLASH

Battery settings must only be entered by qualified personnel knowledgeable of batteries, battery configuration, and the required precautions.

Failure to follow these instructions will result in death or serious injury.

1. Tap Configuration > Battery.

2. Select your battery solution type:

a. Select Standard if you have a standard Galaxy VS battery solution and choose the commercial reference for your specific battery configuration from the drop-down list.

b. SelectModular if you have a modular Galaxy VS battery solution.

c. Select Custom if you have a custom battery solution.

990-5910D-001 19

3. Tap General settings and set up the following parameters:

NOTE: On each page, tap OK to save your settings and tap the arrow symbol to go to the next page. Only the first three settings are available for modular battery solutions.

Number of battery cabinets connected to the battery breaker/Number of modular battery cabinets

Set the number of battery cabinets connected to each battery breaker/Set the number of modular battery cabinets connected to the UPS.

Low runtime warning (sec) Set the threshold for remaining runtime in seconds that will activate the low runtime warning.

Charge capacity (%) Set the maximum charge capacity in percentage of the UPS nominal power rating.

Minimum threshold (°C) Set the minimum acceptable battery temperature in Celsius or Fahrenheit. Temperatures below this threshold will activate an alarm.

Maximum threshold (°C) Set the maximum acceptable battery temperature in Celsius or Fahrenheit. Temperatures above this threshold will activate an alarm.

Charger autoboost mode Select to enable charger autoboost mode. This function will automatically transfer the charger to boost charger mode after the system has been in battery operation.

Cyclic charge mode Select to enable cyclic charge mode.

During a cyclic charge, the system cycles between periods of float charging and resting. This function will continuously maintain the battery charge status without stressing the batteries by conducting a permanent float charging.

Test interval every Set how often the UPS should run a battery test.

Test day of the week Set on which day of the week the battery test should run.

Test start time (hh:mm) Set which time of day the battery test should run.

20 990-5910D-001

4. Only for custom battery solution: Tap Specific settings and set up the following parameters:

NOTE: On each page, tap OK to save your settings and tap the arrow symbol to go to the next page.

Battery type Select the battery type.

Battery midpoint connected Select if a battery midpoint is connected.

Disable temperature monitoring Select to disable battery temperature monitoring.

Battery capacity per block (Ah) Set the battery capacity per battery block in ampere hours for the battery bank connected to each battery breaker.

Number of parallel battery strings Set the number of battery strings connected in parallel for the battery bank connected to each battery breaker.

Number of battery blocks per string Set the number of battery blocks per battery string.

Number of battery cells per block Set the number of battery cells in a battery block.

DC voltage per battery cell (V) Set the charging voltage per battery cell for Float charging.

Float charging is the basic charging function available on all types of batteries and automatically initiated by the charger.

Set the charging voltage per battery cell for Boost charging.

Boost charging makes it possible to conduct a fast charging in order to quickly restore a discharged battery.

Set the charging voltage per battery cell for Equalization charging.

Equalization charging is used when equalizing skewed open cell batteries. This is the charging method available using the highest possible charging voltage level. When equalization charging is conducted, water is evaporated from the open cell batteries which must be replaced when charging is completed.

Charge duration (sec) Set the duration in seconds of the charge for Boost charging and Equalization charging.

DC shutdown voltage per battery cell (V) Set the voltage level per battery cell for when the battery must be shut down.

Nominal temperature (°C)/Nominal temperature (° F)

Set the nominal temperature in Celsius or Fahrenheit.

Charge current rate Set the charge current rate.

Allow boost charge Select to allow boost charge of the batteries.

Boost charging makes it possible to conduct a fast charging in order to quickly restore a discharged battery.

990-5910D-001 21

Allow battery deep discharge Select to allow deep discharge of the batteries when the UPS is in battery operation. This function allows to discharge the batteries to an even lower voltage level than the normally recommended value. Note that this may damage the batteries.

Enable battery automatic disconnect Select to enable automatic disconnection of the batteries. When the UPS system is left with output off and no ability to charge the batteries, this function will trip the battery breakers to avoid battery deep discharge after a period of:

• Two weeks.

• 10 minutes with the battery cell voltage below the low battery shutdown level.

22 990-5910D-001

Configure High Efficiency Mode

1. Tap Configuration > High efficiency.

2. Select the High efficiency mode: Disable, ECO mode, or ECOnversion.

NOTE: Contact Schneider Electric to enable ECO mode.

3. Select ECOnversion harmonics compensator, if relevant.

4. Select the High efficiency schedule: Active on schedule, Always active, or Never active.

a. For Active on schedule, tap Schedule and set up and enable the schedule(s) as needed.

990-5910D-001 23

Configure the Breakers NOTE: This configuration is mandatory for correct UPS operation.

1. Tap Configuration > Breakers.

2. Tap the different breakers in the mimic diagram to configure which breakers are present in the UPS system. Square with a √ means that the breaker is present, empty square means that the breaker is not present, grayed out square means that the breaker is automatically configured in your UPS system.

NOTE: The UPS can monitor up to two battery breakers in a standard battery solution. The UPS can monitor up to four battery breakers in a modular battery solution – this is configured automatically by the UPS.

The mimic diagram only shows one battery breaker BB even if more battery breakers have been connected and configured for monitoring. If one or more of the monitored battery breakers are in the closed position, the BB on the mimic diagram will show as closed. If all of the monitored battery breakers are in the open position, the BB on the mimic diagram will show as open.

3. Tap OK to save your settings.

24 990-5910D-001

Configure the Input Contacts

1. Tap Configuration > Contacts and relays and select the input contact that you want to configure.

2. Select a function from the drop-down list for the selected input contact:

None: No action assigned to this input contact. Genset is supplying the UPS: Input to indicate that the UPS is being supplied by a generator. You must also select the reduction in battery charge current while the UPS is being supplied by a generator. Set Battery charge power during genset supply to 0% (no battery charging), 10%, 25%, 50%, 75%, or 100% (full battery charging). Battery charge power during genset supply is only selectable for this function.

Ground fault: Input to indicate that a ground fault is present.

Battery room ventilation is inoperable: Input to indicate that the battery room ventilation is inoperable.

When the input is active, the battery charger will turn

OFF.

User-defined 1: General purpose input. External battery monitoring detected a fault: Input to indicate that the external battery monitoring has detected a fault. When the input is active, the UPS will post an alarm (no other action).

User-defined 2: General purpose input. High efficiency mode is disabled: If this input is activated, the UPS is prevented from entering high efficiency mode (ECO mode and ECOnversion mode) or will exit any active high efficiency mode.

External energy storage monitoring detected a minor fault: Input to indicate that the external energy storage monitoring has detected a minor fault.

External signal turns charger off: If this input is activated, the charger will turn OFF on a signal from external equipment, e.g. on a signal from the external energy storage.

External energy storage monitoring detected a major fault: Input to indicate that the external energy storage monitoring has detected a major fault.

Transformer temperature is too high: Input to indicate that there is a high temperature alarm for the transformer.

3. Tap OK to save your settings.

990-5910D-001 25

Configure the Output Relays

1. Tap Configuration > Contacts and relays and select the output relay that you want to configure.

2. Set the Delay (sec).

3. Select to enable Energized check mode (disabled as default).

When Energized check mode is enabled, the output relay is activated, and will deactivate when the events assigned to the output relay occurs (normally activated).

When Energized check mode is disabled, the output relay is deactivated, and will activate when the events assigned to the output relay occurs (normally deactivated).

Energized check mode must be individually enabled for each output relay and makes it possible to detect if the output relay is inoperable:

• If the power supply to the output relays is lost, the events assigned to all the output relays will be indicated as present.

• If a single output relay has become inoperable, the events assigned to the single output relay will be indicated as present.

4. Select the event(s) you want to assign to the output relay. On each page, tap OK to save your settings and tap the arrow symbol to go to the next page.

26 990-5910D-001

NOTE: It is possible to assign several functions to the same output relay.

UPS common alarm: The output is triggered when any alarm is present for the UPS.

UPS in maintenance mode: The output is triggered when the unit output breaker UOB has been opened which transfers the UPS to maintenance mode. The UPS is not supplying the load.

UPS informational alarm: The output is triggered when an information alarm is present for the UPS.

External fault: The output is triggered the UPS detects an external fault.

UPS warning alarm: The output is triggered when a warning alarm is present for the UPS.

Fan inoperable: The output is triggered when one or more fans are inoperable.

UPS critical alarm: The output is triggered when a critical alarm is present for the UPS.

Battery voltage low: The output is triggered when the battery voltage is below the threshold.

System common alarm: The output is triggered when any alarm is present for the system.

Battery is not working correctly: The output is triggered when the batteries are not working correctly.

System informational alarm: The output is triggered when an information alarm is present for the system.

Battery is disconnected: The output is triggered when the batteries have been disconnected or the battery breaker(s) are open.

System warning alarm: The output is triggered when a warning alarm is present for the system.

Inverter overload: The output is triggered when there is an overload condition, while the UPS is in inverter operation.

System critical alarm: The output is triggered when a critical alarm is present for the system.

Output overload: The output is triggered when there is an overload condition, while the UPS is in inverter operation or bypass operation.

UPS in normal operation: The output is triggered when the UPS is in normal operation.

Input out of tolerance: The output is triggered when the input is out of tolerance.

UPS in battery operation: The output is triggered when the UPS is in battery operation.

Bypass out of tolerance: The output is triggered when the bypass is out of tolerance.

UPS in static bypass operation: The output is triggered when the UPS is in forced static bypass operation or requested static bypass operation.

EPO active: The output is triggered when the EPO has been activated.

UPS in maintenance bypass operation: The output is triggered when the UPS is in internal maintenance bypass operation or external maintenance bypass operation.

5. Tap OK to save your settings.

990-5910D-001 27

Configure the Network The network can be configured for the integrated and the optional network management card (NMC).

1. Tap Configuration > Network > IPv4 and select Integrated NMC to configure the integrated network management card or Optional NMC to configure the optional network management card.

a. Set the Address mode toManual, BOOTP, or DCHP.

b. You can also disable the network by selecting Disable integrated NMC IPv4/Disable optional NMC IPv4.

c. Tap OK to save your settings.

28 990-5910D-001

2. Tap Configuration > Network > IPv6 and select Integrated NMC to configure the integrated network management card or Optional NMC to configure the optional network management card.

a. Set the DHCPV6 mode to Address and other information, Non-address information only, or IPv6 never.

b. Select Auto configuration orManual.

c. You can also disable the network by selecting Disable integrated NMC IPv6/Disable optional NMC IPv6.

d. Tap OK to save your settings.

Configure the Modbus The Modbus can be configured for the integrated and the optional network management card (NMC).

990-5910D-001 29

1. Tap Configuration > Modbus and select Integrated NMC to configure the integrated network management card or Optional NMC to configure the optional network management card.

a. Enable or disable Serial Modbus.

b. Set the Parity to None, Even, or Odd.

c. Set the Baud rate to 9600 or 19200.

d. Set the Target unique ID to a number between 1 and 247.

NOTE: Every device on the bus must have exactly the same settings except the device address Target unique ID, which must be unique for every device. No two devices on the bus can have the same address.

e. Tap OK to save your settings and tap the arrow symbol to go to the next page.

f. Enable or disable TCP Modbus.

g. Select Port 502 or Port [5000 to 32768].

h. Tap OK to save your settings.

30 990-5910D-001

Set the UPS Name

1. Tap Configuration > General > UPS name.

2. Set the UPS name.

3. Tap OK to save your settings.

Set the Date and Time

1. Tap Configuration > General > Date and time.

2. Set the Year, Month, Day, Hour, Minute, and Second.

3. Tap OK to save your settings.

Configure the Display Preferences

1. Tap Configuration > General > Display.

a. Set the temperature unit to Celsius or Fahrenheit.

b. Tap the - or + to set the display brightness.

c. Set the Alarm sound to Enable or Disable. This will enable/mute all alarm sounds.

d. Set the Touch screen sound to Enable or Disable. This will enable/ mute all display sounds (excluding alarm sounds).

990-5910D-001 31

Configure the Air Filter Reminder When the air filter has been replaced, reset the air filter reminder.

1. Tap Configuration > Reminder.

a. Select Enable reminder to get reminders about replacing the air filter.

b. Select the reminder interval: 1 month, 3 months, 6 months, or 1 year based on the installation room environment.

Under Remaining time (weeks) you can see how much service life the air filter in use has left.

c. Tap Reset to reset the air filter service life counter.

2. Tap OK to save your settings.

Save the UPS Settings on a USB Device NOTE: The UPS can only accept settings that were originally saved from the same UPS. Settings saved from other UPSs can not be reused.

1. Tap Configuration > Save/restore.

2. Open the front panel.

3. Insert your USB device in USB port 1 on the UPS.

4. Tap Save to save the present UPS settings on the USB device.

NOTE: Do not remove the USB device until the save process has finished.

32 990-5910D-001

Restore the UPS Settings from a USB Device NOTE: The UPS can only accept settings that were originally saved from the same UPS. Settings saved from other UPSs cannot be reused.

Settings can only be restored when the UPS is in maintenance bypass operation or off mode.

NOTE: Do not open the unit input breaker UIB at the end of the shutdown sequence as this will turn off the power to the display.

1. Tap Control > Guided sequences > Shut down UPS system or Control > Guided sequences > Shut down a UPS in a parallel system, and follow the steps which appear on the display.

2. Select Configuration > Save/restore.

3. Open the front panel.

4. Insert your USB device in one of the USB ports on the UPS.

5. Tap Restore to implement saved UPS settings from the USB device. Wait for the controller to reboot automatically.

NOTE: Do not remove the USB device until the restore process has finished.

6. Select Control > Guided sequences > Start up UPS system or Control > Guided sequences > Start up a UPS in a parallel system, and follow the steps which appear on the display.

Set the Display Language

1. Tap the flag symbol in the bottom right corner.

2. Tap your language.

990-5910D-001 33

Change the Password

1. Tap Logout.

2. Tap Configuration.

3. Enter your password.

NOTE: The default administrator username and password is admin.

4. Tap Change password and enter the new password.

34 990-5910D-001

Operation Procedures UPS

Operation Procedures

Start Up the UPS System from Off Mode NOTE: Use this procedure to start up a UPS from Off mode with no supplied load. If you are starting up the UPS with load supplied via MBB or IMB, please follow the procedure described in Start Up the UPS System from Maintenance Bypass Operation, page 38.

1. Close the unit input breaker UIB.

The display turns on. The rebooting sequence lasts approximately 3 minutes.

2. Close the static switch input breaker SSIB (if present).

3. Close the battery breakers (if present).

4. Close the unit output breaker UOB.

5. Close the system isolation breaker SIB (if present).

6. Turn on the inverter by pressing the inverter ON button on the controller box or by following Turn the Inverter ON, page 35.

Transfer the UPS from Normal Operation to Static Bypass Operation

1. Select Control > Operation mode > Transfer to bypass operation.

2. Tap OK on the confirmation screen.

Transfer the UPS from Static Bypass Operation to Normal Operation

1. Select Control > Operation mode > Transfer to normal operation.

2. Tap OK on the confirmation screen.

Turn the Inverter OFF IMPORTANT: This will turn off the supply to the load.

1. Select Control > Inverter > Inverter off.

2. Tap OK on the confirmation screen.

Turn the Inverter ON

1. Select Control > Inverter > Inverter on.

2. Tap OK on the confirmation screen.

990-5910D-001 35

UPS Operation Procedures

Set the Charger Mode

1. Tap Control > Charger.

2. Tap Float, Boost, or Equalization.

3. Tap OK on the confirmation screen.

Shut Down the UPS System into Maintenance Bypass Operation NOTE: Only operate a breaker when the associated breaker indicator lamp is illuminated.

1. Tap Control > Guided sequences > Shut down UPS system or Control > Guided sequences > Shut down a UPS in a parallel system, and follow the steps which appear on the display.

2. Generic shutdown procedure for a UPS system with external maintenance bypass breaker MBB:

NOTE: The following are generic shutdown procedures. Always follow the steps of the Guided sequences which are specific to your system

a. Select Control > Operation mode > Transfer to bypass operation if possible.

b. Close the maintenance bypass breaker MBB.

c. Open the system isolation breaker SIB (if present).

d. Open the unit output breaker UOB.

e. Select Control > Inverter > Inverter off or press the inverter OFF button (hold for five seconds) on the controller section.

f. Open the static switch input breaker SSIB (if present).

g. Open the battery breaker(s).

h. Open the unit input breaker UIB.

i. Repeat step d to h for other UPSs in a parallel system.

3. Generic shutdown procedure for a UPS system using the internal maintenance breaker IMB (no MBB present):

NOTE: The following are generic shutdown procedures. Always follow the steps of the Guided sequences which are specific to your system

a. Select Control > Operation mode > Transfer to bypass operation if possible.

b. Close the internal maintenance breaker IMB.

c. Open the battery breaker(s).

d. Repeat step c for other UPS in a simplified 1+1 parallel system.

36 990-5910D-001

Shut Down into Maintenance Bypass Operation for Single UPS System with Kirk Key Installed

NOTE: Only operate a breaker when the associated breaker indicator lamp is illuminated.

1. Select Control > Operation mode > Transfer to bypass operation.

2. Hold down the SKRU push-button, turn and remove key A from the SKRU interlock.

3. Insert key A in the interlock for the maintenance bypass breaker MBB and turn the key.

4. Close the maintenance bypass breaker MBB.

5. Open the unit output breaker UOB.

6. Turn and remove key B from the interlock for the unit output breaker UOB.

7. Insert key B in the SKRU interlock and turn the key to the locked position.

8. Select Control > Inverter > Inverter off.

9. Open the static switch input breaker SSIB (if present).

10. Open the battery breaker(s).

11. Open the unit input breaker UIB.

990-5910D-001 37

Start Up the UPS System from Maintenance Bypass Operation NOTE: Only operate a breaker when the associated breaker indicator lamp is illuminated.

1. If open, close the unit input breaker UIB.

The display turns on. The rebooting sequence lasts approximately 3 minutes.

2. Select Control > Guided sequences > Start up UPS system or Control > Guided sequences > Start up a UPS in a parallel system, and follow the steps which appear on the display.

3. Generic start-up procedure for a UPS system with external maintenance bypass breaker MBB:

NOTE: The following are generic shutdown procedures. Always follow the steps of the Guided sequences which are specific to your system

a. If open, close the unit input breaker UIB.

b. Close the static switch input breaker SSIB (if present).

c. Close the battery breaker(s).

d. Select Control > Operation mode > Transfer to bypass operation if possible.

e. Close the unit output breaker UOB.

f. Repeat step a to e for other UPSs in a parallel system.

g. Close the system isolation breaker SIB (if present).

h. Open the maintenance bypass breaker MBB.

i. Select Control > Inverter > Inverter on or press the inverter ON button (hold for five seconds) on the controller section.

4. Generic start-up procedure for a UPS system using the internal maintenance breaker IMB (no MBB present):

NOTE: The following are generic shutdown procedures. Always follow the steps of the Guided sequences which are specific to your system

a. If open, close the unit input breaker UIB.

b. Close the battery breaker(s).

c. Repeat step a to b for other UPS in a simplified 1+1 parallel system.

d. Open the internal maintenance breaker IMB.

e. Select Control > Inverter > Inverter on or press the inverter ON button (hold for five seconds) on the controller section.

38 990-5910D-001

Start Up from Maintenance Bypass Operation for Single UPS System with Kirk Key Installed

NOTE: Only operate a breaker when the associated breaker indicator lamp is illuminated.

1. Close the unit input breaker UIB.

The display turns on. The rebooting sequence lasts approximately three minutes.

2. Close the static switch input breaker SSIB (if present).

3. Close the battery breakers.

4. Select Control > Operation mode > Transfer to bypass operation.

5. Hold down the SKRU push-button, turn and remove key B from the SKRU interlock.

6. Insert key B in the interlock for the unit output breaker UOB and turn the key.

7. Close the unit output breaker UOB.

8. Open the maintenance bypass breaker MBB.

9. Turn and remove key A from the interlock for the maintenance bypass breaker MBB.

10. Insert key A in the SKRU interlock and turn the key to the locked position.

11. Select Control > Inverter > Inverter on.

990-5910D-001 39

Access a Configured Network Management Interface The network management card web interface is compatible with:

Windows® operating systems:

• Microsoft® Internet Explorer® (IE) 10.x or higher, with compatibility view turned on.

• The latest release of Microsoft Edge

All operating systems:

• The latest releases of Mozilla® Firefox® or Google® Chrome® The below procedure describes how to access the network management interface from a web interface. If enabled, it is also possible to use the following interfaces:

• SSH

• SNMP

• FTP

• SFTP

NOTE: Please visit www.schneider-electric.com to view the Security Deployment Guidelines and Security Handbook for the product.

The network management card supports NTP connection for synchronization of time. Ensure that only one network management interface in the entire UPS system (single or parallel) is set to synchronize time.

You can use either of the following protocols when you use the web interface:

• The HTTP protocol (disabled by default), which provides authentication by user name and Pin but no encryption.

• The HTTPS protocol (enabled by default), which provides extra security through Secure Socket Layer (SSL); encrypts user names, Pin, and data being transmitted; and authenticates network management cards by means of digital certificates.

See Enable HTTP/HTTPS Protocols, page 40.

By default, SNMP protocols are disabled on the network management card to avoid cybersecurity risks. SNMP protocols must be enabled to use the monitoring functions of the network management card, or to connect to EcoStruxure IT Gateway or StruxureWare Data Center Expert. You can enable and use either of these SNMP protocols:

• SNMPv1, which provides minimal security. If using this protocol, Schneider

Electric recommends customizing the access control parameters to enhance security.

• SNMPv3, which provides extra security through both encryption and authentication. Schneider Electric recommends using this protocol for better security and customizing the access control parameters.

See Enable SNMP Protocols, page 41.

Enable HTTP/HTTPS Protocols

1. Access the network management interface by its IP address (or its DNS name, if a DNS name is configured).

2. Enter the user name and password. The default user name and password is apc. You will be prompted to change this password on the first login.

3. To enable or disable the HTTP or HTTPS protocol, go to Configuration > Network > Web > Access, select the protocol, set the parameters, and click on Apply.

40 990-5910D-001 http://www.schneider-electric.com

Enable SNMP Protocols

1. Access the network management interface by its IP address (or its DNS name, if a DNS name is configured).

2. Enter the user name and password. The default user name and password is apc. You will be prompted to change this password on the first login.

3. To enable SNMPv1 protocol:

a. Go to Configuration > Network > SNMPv1 > Access, select Enable and click on Apply

b. Go to Configuration > Network > SNMPv1 > Access Control and set up the parameters.

4. To enable SNMPv3 protocol:

a. Go to Configuration > Network > SNMPv3 > Access, select Enable and click on Apply.

b. Go to Configuration > Network > SNMPv3 > Access Control and set up the parameters.

c. Go to Configuration > Network > SNMPv3 > User Profiles and set…