This is a solicitation for uninterruptible power source preventive maintenance services in support of the VA Sioux Falls Health Care System. The solicitation will result in a firm-fixed price contract to provide preventive maintenance to UPS units. The period of performance is one base year from May 1, 2024 to April 30, 2025, with four one-year option periods. The solicitation is set aside for small businesses with a NAICS code of 811310 and size standard of $12.5 million. Quotes are due by March 28, 2024 and shall be emailed to the contracting officer. Technical questions are due by March 13, 2024 and shall be emailed to the contracting officer. The contractor will perform preventive maintenance on UPS units to support the VA medical center in Sioux Falls, South Dakota.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Perfect Power System

❖ Phone: (800)-786-6915

❖ FAX no: (800)-246-2346

❖ Technical Assistance: service@800pwrsrvc.com

Document No.: 710-MAN, Rev. E

All trademarks and registered trademarks are the property of their respective owners.

Due to continuous product improvement, this document is subject to change without prior notice

POWER RIDE 1 Standard Units 2.1-17KW and OSHPD/HCAI Certified Seismic Series Units 3.0-17KW Emergency Lighting Inverter

OSHPD/HCAI CERTIFICATION: (OSP-0501-10)

Operation and Installation Manual mailto:service@800pwrsrvc.com

710-MAN Page 2 of 102

Notice of Rights

This document contains proprietary and confidential information of the Perfect Power Systems. No part of this manual may be reproduced, copied, translated or transmitted, in any form or by any means, without the prior written permission of the company.

Notice of Liability

Information provided in this manual is intended to be accurate and reliable. However, manufacturer.

assumes no responsibility for its use, nor for any infringement of rights of third parties which may result from its use. THIS DOCUMENT IS PROVIDED “AS IS” AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL MANUAFACTURER BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES;

LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS DOCUMENT, EVEN IF ADVISED OF THE

POSSIBILITY OF SUCH DAMAGE.

Trademarks

All trademarks and registered trademarks are the property of their respective owners.

Emergency Lighting Inverter Installation and Operation Manual

Document No.: 710-MAN, Rev. E

September 12, 2023

Table of Contents

710-MAN Page 3 of 102

Table of Contents

Introduction

Scope and Audience

Safety and Warnings

Warranty Registration and Warranty Certificate Request

Service

Chapter 1. Safety

Chapter 2. Overview

2.1 Product Description

2.2 Models

2.3 Product Features

Chapter 3. Hardware Overview

3.1 Key Components

3.2 Functional Description

3.3 Theory of Operation

Chapter 4. Installation

4.1 Delivery Space Requirements

4.2 Site Considerations

4.3 Delivery and Handling

Chapter 5. Operation

5.1 Starting the Unit

Chapter 6. Maintenance

6.1 Safety Precautions

6.2 Preventative Maintenance

6.3 FRU Replacement

6.4 Calling for Service

6.5 Customer Service and Support

Chapter 7. Troubleshooting

7.1 Reset Instruction

7.2 Guide and System Alarms

7.3 Using the LCD Display Panel

7.4 Default Screen 1

7.5 Default Screen 2

7.6 Default Screen 3

710-MAN Page 4 of 102

Chapter 8. Specifications

APPENDIX A - Battery Connections

APPENDIX B - Options

B.1 Internal Manual Bypass Switch (Make Before Break)

B.2 External Wrap-around Manual Bypass Switch (same Input and Output Voltage)

B.3 Audio Alarms with Silence Switch

B.4 Remote Status Panel

B.5 Transient Voltage Surge-Suppressor (TVSS)

B.6 Offline Inverter Operation

B.7 Normally ON/OFF Output Aux. Circuit Breakers

B.8 Main Input CB Standard/Higher KAIC

B.9 Main Output CB Standard/Higher KAIC

B.10 Higher KAIC Normally ON/OFF Aux Output Circuit Breaker

B.11 Power Flow Mimic

B.12 Global Monitoring System (GMS)

B.12.1 Local Monitoring via PC with RS-232

B.12.2 Local Monitoring via PC with RS-485

B.12.3 RJ45 Ethernet connection

B.13 Simple Network Management Protocol

B.14 Seismic Mounting Bracket

B.15 Battery String Monitoring (Wireless)

B.16 Battery (Individual) Monitoring (Wireless)

B.17 Form “C” N/O Contacts for Alarms

B.18 Dry Contact, N/O or N/C Contact with Isolated Common Connections

B.19 Battery Thermal Runaway Control

B.20 Battery Breaker alarm

Index

Safety

710-MAN Page 5 of 102

Introduction

This manual tells you how to install, start and operate your unit and lets you know how to get more information for special situations, and provide contact information

Scope and Audience This guide is intended to be used as a reference for users responsible for installing, operating, and maintaining this equipment.

Safety and Warnings This guide uses the following symbols to draw your attention to certain information.

Symbol Meaning Description

Note Notes emphasize or supplement important points of the main text.

Tip Tips provide helpful information, guidelines, or suggestions for performing tasks more effectively.

Caution Cautions indicate that failure to take a specified action could result in damage to the hardware.

DANGER The Danger symbol warns users of possible injury or death if instructions are not followed.

Electrostatic Sensitive

This symbol warns users that the equipment is sensitive to electrostatic discharge (ESD) and could be damaged if users do not take appropriate precautions such as using a grounded wrist strap when touching or handling the equipment.

Electrostatic sensitive

Components are Electrostatic Discharge Susceptible (ESDS), Use a grounded ESD wrist strap.

Warranty Registration and Warranty Certificate Request Visit our web site at: www.800pwrsrvc.com under download tab

Service If you require assistance, fill out a Service Report Form at www.800pwrsrvc.com, email us at service@800pwrsrvc.com, or call our 24-hour toll free hot line (800-797-7782). Please have the unit’s SERIAL NO. from the Start-Up label located on the top left corner of the front door for speed assistance http://www.800pwrsrvc.com/

710-MAN Page 6 of 102

Chapter 1. Safety

This chapter contains safety precautions to observe when operating or servicing electrical equipment. The symbols shown are used extensively throughout this manual. Always heed these precautions because they are essential to the safe operation and servicing of this product.

710-MAN Page 7 of 102

DANGER: This Equipment is intended to be permanently connected. Only factory-trained or authorized personnel should attempt to install or repair the unit or its battery system.

Improper installation has proven to be the single most significant cause of start-up problems. High AC and DC electrical voltages are present throughout the unit(s) and incorrect installation or servicing could result in electrocution, fire, explosion, or equipment failure.

DANGER: Read this manual in its entirety before performing the installation, start-up, operation, or maintenance of the UPS unit or battery systems. Failure to do so could result in electrocution, fire, explosion, or equipment failure.

If you require assistance, email l service@800pwrsrvc.com to speed assistance, have the information from your unit's nameplate.

DANGER: All power connections must be completed by a licensed electrician who is experienced in wiring this type of equipment. Wiring must be installed in accordance with all applicable national and local electrical codes. Improper wiring may cause damage to the equipment, injury or death of personnel. Verify that all high and low voltage input power circuits are de-energized and locked out before installing cables or making any electrical connections.

DANGER: Exercise extreme care when handling unit and its batteries to avoid equipment damage or injury to personnel. Cabinets weigh several hundred pounds.

DANGER: Test lift and balance the cabinets before moving. Maintain minimum tilt from vertical at all times. The bottom structure will support the unit only if the forklift forks are completely underneath the unit.

DANGER: Observe all battery safety precautions during installation or service of the unit or batteries. Even with the battery circuit breaker in the off position, the danger of electrocution may still be present. The battery power to the unit must be locked and tagged “off” before performing any service or work on the unit. The battery manufacturer’s safety information and material safety data sheet are located in a pocket attached to the inside of door of each unit. Failure to follow those instructions and the instruction listed above and elsewhere in this manual could result in an explosion, fire, equipment failure, or electrocution.

mailto:ervice@800pwrsrvc.com

710-MAN Page 8 of 102

DANGER: All power to the unit must be locked and tagged "off" before performing any service or work on the unit. failure to do so could result in electrocution.

DANGER: In case of fire involving electrical equipment, only carbon dioxide fire extinguishers, or those approved for use on electrical equipment, should be used. Use of water on fires involving live high voltage electrical circuits could present an electrocution hazard.

DANGER: Extreme caution is required when performing maintenance. Lethal voltages exist within the equipment during operation. Observe all warnings and cautions in this manual. Failure to comply may result in serious injury or death. Obtain qualified service for this equipment as instructed.

DANGER: Be constantly aware that the unit system contains high DC as well as AC voltages. With input power, off and the battery disconnected, high voltage at the filter capacitors and power circuits should discharge within 30 seconds. However, power circuit failures can occur, so you should always assume that high voltage might still exist after shutdown. Verify that power is off using AC and DC voltmeters before making contact.

DANGER: Some components within the cabinets are not connected to chassis ground. Any contact between floating circuits and the chassis is a lethal shock hazard.

DANGER: Internal battery strapping must be verified by the customer prior to moving this unit.

This unit contains non-spillable batteries. Keep the unit upright. Do not stack. Do not tip.

Always follow the battery manufacturer’s safety information, located in a pocket attached to the inside of the door of your unit, to prevent an accident that could result in injury or death.

710-MAN Page 9 of 102

DANGER: Lead-acid batteries contain hazardous materials. Batteries must be handled, transported, and recycled or discarded in accordance with federal, state, and local regulations. Because lead is a toxic substance, lead-acid batteries should be recycled rather than discarded.

Do not dispose of batteries in a fire, the batteries may explode.

Do not open or mutilate the batteries. Released electrolytes are harmful to the skin and eyes and may be toxic.

A battery can have a high short circuit current and present a risk of electrical shock. The following precautions should be observed when working on batteries:

1. Remove watches, rings, or other metal objects.

2. Use tools with insulated handles.

3. Wear rubber gloves and boots.

4. Do not lay tools or metal parts on top of batteries.

5. Disconnect charging source prior to connecting or disconnecting battery terminals.

6. Determine whether battery is inadvertently grounded. if so, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance.

7. Lead-acid batteries can present a risk of fire because they generate hydrogen gas. The following procedures should be followed:

– Do not smoke when near batteries.

– Do not cause flame or spark in battery area.

8. Discharge static electricity from your body before touching batteries by first touching a grounded surface.

Overview

710-MAN Page 10 of 102

Chapter 2. Overview

This chapter provides an overview of the Single-Phase Lighting Inverter Standard Series.

710-MAN Page 11 of 102

2.1 Product Description

The Single-Phase Lighting Inverter is manufactured to provide critical power for lighting during a power outage. The Lighting Inverter meets or exceeds the life safety codes of UL924 and UL1778.

These codes were established to allow emergency lighting inverters to provide critical power to the lighting circuits during a power failure.

If input power to the inverter is lost during a power outage, the system draws clean sine wave power automatically from its internal battery supply without any interruption. Power is provided for 90 minutes, sufficient time for safe and orderly evacuation from the facility.

An optional output transformer allows multiple output voltages as well as input voltages that are different from output voltages. The internal valve regulated lead-acid (VRLA), maintenance-free batteries provide 90 minutes of backup power. When input power is restored, the Lighting Inverter resumes normal operation automatically and begins recharging the batteries immediately.

An internal bypass circuit maintains power to the load in case an internal unit failure occurs.

Comprehensive monitoring capabilities include a Liquid Crystal Display (LCD) panel and Optional dry relay contacts for remote monitoring.

2.2 Models

The Single-Phase Lighting Inverters are available in two series:

❖ Standard series

❖ Seismic series

2.2.1 Standard Series

The Standard Series Single-Phase Lighting Inverters are on-line single phase PWM inverters. The systems support power ratings from 2.1 to 17KW power ratings.

All Standard Series systems comply with UL1778, UL924, UL924A, and CSA107.1 standards. They are available with input or output voltages of 120, 208, 240, 277 or 480 VAC, single phase. This information is shown on the nameplate located on the inside front door of the unit.

Table 2-1 lists the cabinet dimension and types, and Figure 2-1 shows them.

710-MAN Page 12 of 102

Table 2-1. Standard Series Cabinet Dimensions and Types

KW Cabinet Size (Including Battery) (H x W x D in Inches)

Cabinet Height

Cabinet Type

Zone 4 Approved

2.1 ~ 3KW

48 x 39 x 18

48” See Figure 4-1

48 x 46.75 x 18 (including brackets) See Figure 4-6

*3.5KW ~ 8KW

68 x 39 x 18

68” See Figure 4-2

68 x 46.75 x 18 (including brackets) See Figure 4-6

All other 70 x 51 x 30.5

70” See Figure 4-3

70 x 58.75 x 30.5 (including brackets) See Figure 4-7

*Consult factory for all other configurations per requirements

Figure 2-1. Standard Series Single-Phase Lighting Inverter Cabinets

2.2.2 Seismic Series

The Seismic Series are OSHPD/HCAI-certified Single-Phase PWM Lighting Inverters that support power ratings from 3kw to 17kw. In addition to complying with UL1778, UL924, and CSA107.1 standards, these models meet the requirements for CBC 2016 and IBC 2015. They have been shake table-tested in accordance with the ICC-ES AC156 procedure to SDS level 3.0g. The systems have received special seismic certification from the Heath Care Access and Information (HCAI), formally known as California Office of Statewide Health Planning and Development (OSHPD), which are the most rigid seismic standards available.

Table 2-2 lists the cabinet dimensions and types, and Figure 2-2 shows them.

Note: All Seismic Series models have an SV- prefix in their model number.

710-MAN Page 13 of 102

Table 2-2. Seismic Series Cabinet Dimensions and Types

KW Cabinet Size (Including Battery) (H x W x D in Inches)

Cabinet Height Cabinet Type

3KW, 5KW, 6KW, 8KW 68 X 46 X 18 (including brackets) 68” See Figure 4-4

All Others 70 X 58.75 X 30.5 (including brackets) 70” See Figure 4-5

Figure 2-2. Seismic Series Lighting Inverter Cabinets

710-MAN Page 14 of 102

Table 2-3. Shock- and Vibration-Approved Model Numbers

KW Input/Output Voltage Model Number

Inverter Battery

Weight (lbs.) Mounting Dim

(H x W x D) in Inches

3.0

120 / 120 SV-PD3.0A0100N1

1,284 68 X 46 X 18 (including brackets)

120 / 120, 208, 240, 277 SV-PD3.0A5800T1

208 / 208 SV-PD3.0B1300N1

208 / 120, 208, 240, 277 SV-PD3.0B5800T1

240 / 240 SV-PD3.0D0400N1

240 / 120, 208, 240, 277 SV-PD3.0D5800T1

277 / 277 SV-PD3.0R2500N1

277 / 120, 208, 240, 277 SV-PD3.0R5800T1

480 / 480 SV-PD3.0H1100T1

480 / 277 SV-PD3.0H2500T1

480 / 120, 208, 240, 277 SV-PD3.0H5800T1

277 / 480 SV-PD3.0R1100T1

5.0

120 / 120 SV-PD5.0A0100N1

1,284 68 X 46 X 18 (including brackets)

120 / 120, 208, 240, 277 SV-PD5.0A5800T1

208 / 208 SV-PD5.0B1300N1

208 / 120, 208, 240, 277 SV-PD5.0B5800T1

240 / 240 SV-PD5.0D0400N1

240 / 120, 208, 240, 277 SV-PD5.0D5800T1

277 / 277 SV-PD5.0R2500N1

277 / 120, 208, 240, 277 SV-PD5.0R5800T1

480 / 480 SV-PD5.0H1100T1

480 / 277 SV-PD5.0H2500T1

480 / 120, 208, 240, 277 SV-PD5.0H5800T1

277 / 480 SV-PD5.0R1100T1

6.0

120 / 120 SV-PD6.0A0100N1

1,340 68 X 46 X 18 (including brackets)

120 / 120, 208, 240, 277 SV-PD6.0A5800T1

208 / 208 SV-PD6.0B1300N1

208 / 120, 208, 240, 277 SV-PD6.0B5800T1

240 / 240 SV-PD6.0D0400N1

240 / 120, 208, 240, 277 SV-PD6.0D5800T1

277 / 277 SV-PD6.0R2500N1

277 / 120, 208, 240, 277 SV-PD6.0R5800T1

480 / 480 SV-PD6.0H1100T1

480 / 277 SV-PD6.0H2500T1

480 / 120, 208, 240, 277 SV-PD6.0H5800T1

277 / 480 SV-PD6.0R1100T1

7.5

120 / 120 SV-PD7.5A0100N1

1,340 68 X 46 X 18 (including brackets) 120 / 120, 208, 240, 277 SV-PD7.5A5800T1

710-MAN Page 15 of 102

Inverter Battery

Weight (lbs.) Mounting Dim

(H x W x D) in Inches

208 / 208 SV-PD7.5B1300N1

208 / 120, 208, 240, 277 SV-PD7.5B5800T1

240 / 240 SV-PD7.5D0400N1

240 / 120, 208, 240, 277 SV-PD7.5D5800T1

277 / 277 SV-PD7.5R2500N1

277 / 120, 208, 240, 277 SV-PD7.5R5800T1

480 / 480 SV-PD7.5H1100T1

480 / 277 SV-PD7.5H2500T1

480 / 120, 208, 240, 277 SV-PD7.5H5800T1

277 / 480 SV- PD7.5R1100T1

8.0

120 / 120 SV-PD8.0A0100N1

1,795 68 X 46 X 18 (including brackets)

120 / 120, 208, 240, 277 SV-PD8.0A5800T1

208 / 208 SV-PD8.0B1300N1

208 / 120, 208, 240, 277 SV-PD8.0B5800T1

240 / 240 SV-PD8.0D0400N1

240 / 120, 208, 240, 277 SV-PD8.0D5800T1

277 / 277 SV-PD8.0R2500N1

277 / 120, 208, 240, 277 SV-PD8.0A0100N1

480 / 480 SV-PD8.0A5800T1

480 / 277 SV-PD8.0B1300N1

480 / 120, 208, 240, 277 SV-PD8.0B5800T1

277 / 480 SV-PD8.0D0400N1

10.0

120 / 120 SV-PD010A0100N1

2,438

70 X 58.75 X 30.5

(including brackets)

120 / 120, 208, 240, 277 SV-PD010A5800T1

208 / 208 SV-PD010B1300N1

208 / 120, 208, 240, 277 SV-PD010B5800T1

240 / 240 SV-PD010D0400N1

240 / 120, 208, 240, 277 SV-PD010D5800T1

277 / 277 SV-PD010R2500N1

277 / 120, 208, 240, 277 SV-PD010R5800T1

480 / 480 SV-PD010H1100T1

480 / 277 SV-PD010H2500T1

480 / 120, 208, 240, 277 SV-PD010H5800T1

277 / 480 SV-PD010R1100T1

12.5

120 / 120 SV-PD012A0100N1

3,681

120 / 120, 208, 240, 277 SV-PD012A5800T1

208 / 208 SV-PD012B1300N1

208 / 120, 208, 240, 277 SV-PD012B5800T1

240 / 240 SV-PD012D0400N1

240 / 120, 208, 240, 277 SV-PD012D5800T1

710-MAN Page 16 of 102

Inverter Battery

Weight (lbs.) Mounting Dim

(H x W x D) in Inches

277 / 277 SV-PD012R2500N1

277 / 120, 208, 240, 277 SV-PD012R5800T1

480 / 480 SV-PD012H1100T1

480 / 277 SV-PD012H2500T1

480 / 120, 208, 240, 277 SV-PD012H5800T1

277 / 480 SV-PD012R1100T1

15.0

120 / 120 SV-PD015A0100N1

3,852

120 / 120, 208, 240, 277 SV-PD015A5800T1

208 / 208 SV-PD015B1300N1

208 / 120, 208, 240, 277 SV-PD015B5800T1

240 / 240 SV-PD015D0400N1

240 / 120, 208, 240, 277 SV-PD015D5800T1

277 / 277 SV-PD015R2500N1

277 / 120, 208, 240, 277 SV-PD015R5800T1

480 / 480 SV-PD015H1100T1

480 / 277 SV-PD015H2500T1

480 / 120, 208, 240, 277 SV- PD015H5800T1

277 / 480 SV- PD015R1100T1

17.0

120 / 120 SV-PD017A0100N1

4,512

120 / 120, 208, 240, 277 SV-PD017A5800T1

208 / 208 SV-PD017B1300N1

208 / 120, 208, 240, 277 SV-PD017B5800T1

240 / 240 SV-PD017D0400N1

240 / 120, 208, 240, 277 SV-PD017D5800T1

277 / 277 SV-PD017R2500N1

277 / 120, 208, 240, 277 SV-PD017R5800T1

480 / 480 SV-PD017H1100T1

480 / 277 SV-PD017H2500T1

480 / 120, 208, 240, 277 SV-PD017H5800T1

277 / 480 SV-PD017R1100T1

710-MAN Page 17 of 102

2.3 Product Features

The following describes the major blocks within the System. See Figure 3-1. Key Components on page 20 to find specific components.

Components Function

1 Input Contactor K1 The input contactor is multifunctional. First, it provides connections for the input power to the unit. Secondly, the contactor disconnects the input line when an outage occurs so that there is no back feeding of power into the power line. Finally, the contactor allows for automatic unit operation upon a complete discharge of the batteries. No operator intervention is required when power to the unit is restored after a complete battery discharge.

2 Battery Charger The battery charger maintains the batteries at full charge. After a battery discharge, the charger will automatically recharge the batteries upon restoration of input power. This circuit is on the Power Board.

3 Power Board Assembly with IGBTs The Power Board is bolted onto the IGBT (Insulated Gate Bipolar Transistor) blocks that are mounted on a heat sink. The complete Heat Sink Assembly with IGBTs and Power Board is replaceable as a single part. This FRU (Field Replaceable Assembly) converts all the power, i.e.

input AC power converted to DC bus, battery power boosted to DC bus, and finally DC bus power converted to output AC power using PWM technology for a smooth AC sine wave. In case of a catastrophic failure, the complete Heat Sink Assembly is easily replaceable using only a screwdriver. The Power Board also contains the housekeeping power supplies and drivers for the IGBTs.

The entire assembly provides the landing place for all internal input, output, DC cables and metering devices for control and monitoring of the unit input and output currents.

4 Control Board The microprocessor with unit specific firmware and control circuitry is located on the Control Board. The Control Board is mounted on the cabinet door and communicates with the Power Board (A2) via a ribbon cable. It monitors the input and output voltages and generates the command to close or open the input contactor and to sense and change the status of the bypass static switch. The Control Board sends data to the LCD panel located on the door where actual status and parameters are displayed. It additionally has AS400, RS232, and RS485 output capabilities and supports various communication including SNMP options.

5 Output Static Switch This SCR solid-state switch connects the output of the inverter (UPS) to the load. It is connected on the primary side of the optional output isolation transformer. This switch shuts off in case of a problem or failure within the unit and transfers the load directly to the utility input via the bypass static switch. It maintains its status opposite to that of bypass switch.

710-MAN Page 18 of 102

Components Function

6 LCD Display Panel The LCD (Liquid Crystal Display) panel provides all the input, output, battery metering and alarm data, and UPS status for customer use on a constantly scrolling set of 2 default screens with continuous update.

7 Optional Output Isolation Transformer The output isolation transformer provides isolation between the inverter and protected output. The power to the primary of this transformer is received from the unit and is transformed to required output voltage levels. It will also add another screen to the main menu.

8 Optional Maintenance Bypass Switch The MBS (Maintenance Bypass Switch) removes the critical load from the backup power and provides utility input directly to the load in case of a unit malfunction or during system maintenance.

9 Battery Bank

The battery bank consists of sealed, maintenance-free batteries. The batteries provide emergency power during power outages. The battery bank includes a breaker for over current protection and DC disconnect.

Hardware Overview

710-MAN Page 19 of 102

Chapter 3. Hardware Overview

This chapter provides an overview of the system hardware. It includes a description of the system’s theory of operation.

710-MAN Page 20 of 102

3.1 Key Components

Figure 3-1 shows the key system components and Table 3-1 describes them.

Figure 3-1. Key Components (3.5KW ~ 8KW) typical

710-MAN Page 21 of 102

Figure 3-2. Key Components (all other KW) typical

710-MAN Page 22 of 102

Table 3-1. Key Components description

Callout Component Name Description

Heatsink FRU Assembly for 3.5KW ~ 8KW

Behind hinged panel for all others

Power board (A1) The power board is bolted onto the Insulated Gate Bipolar Transistor (IGBT) blocks mounted on a heat sink.

The complete heat sink assembly with IGBTs and power board is a single Field Replaceable Unit (FRU) that converts all the power:

Input AC power converted to DC bus

Battery power boosted to DC bus

DC bus power converted to output AC power using PWM technology for a smooth AC sine wave

If a catastrophic failure occurs, the heat sink assembly can be replaced using only a screwdriver. The power board also has the housekeeping power supplies and drivers for the IGBTs. The entire assembly provides the landing place for all internal input, output, DC cables, and metering devices for controlling and monitoring the unit input and output currents.

Bypass static switch

(PB2)

Bypass static switch is closed only upon inverter fault or output overload condition.

Inverter static switch

(PB1)

The SCR solid-state switch connects the output of the inverter (UPS) to the load. It is connected on the primary side of the optional output isolation transformer. If problem or failure occurs in the unit, this switch shuts off and transfers the load directly to the utility input via the bypass static switch. It maintains its status opposite to that of the bypass switch.

2 Input 2-Pole terminal block (TB1) Customer Input power connection. See Figure 4-8 on page 44.

3 Ground Lug (Input and Output) 2-barrel lug for Input and Output Ground See Figure 4-8 on page 44.)

4 Output 2-Pole / 3-pole terminal block (TB1) Customer output connection. See Figure 4-11 and 4-12 on page 47 and 48.

5 Control board (A2) The microprocessor with unit specific firmware and control circuitry is located on the Control Board. The Control Board is mounted on the cabinet door and communicates with the Power Board (A2) via a ribbon cable. It monitors the input and output voltages and generates the command to close or open the input contactor and to sense and change the status of the bypass static switch. The Control Board sends data to the LCD panel located on the door where actual status and parameters are displayed. It additionally provides optional AS400, RS232, and RS485 output capabilities and supports various communication including SNMP options.

6 LCD display panel Provides continuously updated input, output, battery metering and alarm data, and UPS status for customer use on a constantly scrolling set of 2 default screens.

7 Terminal block for removing heat sink assembly (TB4) for 3.5KW ~ 8KW

Behind hinged panel for all others

5-position terminal block (TB4). This terminal block provides quick and easy removal of power assembly.

710-MAN Page 23 of 102

Callout Component Name Description

8 Fan transformer, Control power transformer (T2) for 3.5KW ~ 8KW

Behind hinged panel for all others

Provides 120 VAC to the fans, with taps to match unit output voltages.

9 Control transformer fuse (F1) for 3.5KW ~ 8KW

Behind hinged panel for all others

Control transformer over current protection

10 Fan fuse (F2) for 3.5KW ~ 8KW

Behind hinged panel for all others

Fan overcurrent protection.

11 Fan(s) and under heatsink Provides system cooling.

12 Output isolation transformer T1, as required Provides isolation between the inverter and protected output. Power to the primary of this transformer is received from the unit and is transformed to the appropriate output voltage levels. It also adds a screen to the main menu.

13 Inverter test switch (S2) Push-button switch for testing the Lighting Inverter and its batteries for proper operation. When the unit is operating, pressing and holding in switch SW-2 transfers the system to battery operation. The system continues to run on batteries until the switch is released. When the switch is released, the system returns to normal operation so long as input power is present.

14 (Optional) Main Input breaker (CB3) Provides input overcurrent protection (optional).

15 Battery breaker (CB1) Provides overcurrent protection for battery bank.

16 (Optional) Main output breaker (CB2) Provides output overcurrent protection (optional).

17 (Optional) Output Auxiliary Breakers Normally ON/OFF Output Auxiliary Breakers (Optional)

18 (Optional) Gnd/Neu terminals Gnd/Neu terminals for optional auxiliary output breakers.

19 (Optional) bypass switch Optional: Removes the critical load from the backup power and provides utility input directly to the load in case the unit malfunctions or during system maintenance (optional).

20 (Optional) TVSS (Transient Voltage Surge Suppressor)

This option is a no-fuse, fail-safe surge suppressor featuring a fail-safe self-protected design, visual indicator.

21 (Optional) Interfaces terminal blocks for customer connection (General location)

Options customer connections i.e. form “C” contact terminals, RS232….each terminal is marked accordingly for proper connection refer to each option for connection details in each cabinet size.

22 Maintenance free lead acid battery(s) Batteries are sealed, maintenance-free, self-regulated lead acid construction, to provide emergency power during power outages. Other battery options are available upon request.

710-MAN Page 24 of 102

3.2 Functional Description

Figure 3-3 shows the major blocks within the system and the sections following the figure describe them.

Figure 3-3. Major System Blocks

3.2.1 Inverter

The inverter accepts the available DC power from the rectifier or the battery banks and converts it to AC power for the critical load.

3.2.2 Battery Charger

The battery charger converts AC power into regulated DC power to recharge and maintain the charge on the battery bank. The charger is fully automatic, with a current-limiting feature that prevents battery damage in case of a charger malfunction. The charger is sized so that the batteries are maintained at full charge, even when the input voltage is at the low line limit for indefinite periods of time.

710-MAN Page 25 of 102

3.2.3 Battery

The battery bank consists of 8, 10, 16, or 20 12-Volt batteries. These batteries provide the reserve energy to sustain the load when suitable AC input power is not present. The batteries are sealed, maintenance-free, valve-regulated lead acid (VRLA) construction.

3.2.4 Output Transformer

The output transformer is used for multiple output voltage units only. It performs the following functions:

❖ It provides excellent common mode and normal mode noise isolation of the load from the input or inverter power.

❖ It provides voltage transformation and tight regulation of the output voltage, while the system operates from its internal inverter.

❖ It can be used to provide a different voltage from the input source voltage.

3.2.5 Internal Maintenance Bypass Switch, MBS Switch – Optional

Internal Manual Maintenance Bypass Switch is a (3) position “UPS”, “SBS” and “BYPASS” rotary switch, when set to “BYPASS” provides power directly from UPS main input feed to the load which ensures continuous power to critical load without interruption.

Caution: Do not leave the switch in the SBS position; otherwise, a loss of power to the critical load will occur when the inverter is de-energized.

3.2.6 Efficiency Optimizer Function: (OFF Line Inverter Mode

When input power is available, the batteries are charged and AC output from the inverter supports the critical load via the inverter static switch. This is normal mode, during which the inverter static switch is closed, and the bypass static switch is opened. The bypass static switch is closed only during inverter faults or manual operation, in which case the critical load is supported by output power from the bypass static switch.

This is normal operation for true-double convention UPS. However, higher efficiency UPS operation can be achieved to reduce electricity costs by operating the unit as an “off-line inverter.” This scenario reverses the normal operating mode. Normally, the bypass static switch is closed as long as the input voltage and input frequency are within ±10% of the normal input voltage range and ±3 Hz of the normal input frequency range, and the inverter static switch is opened. In off-line inverter mode, the inverter static switch is closed only if input power fails or when and out-of-voltage and frequency condition exists.

By eliminating the requirement for an output voltage regulation of ±10% (voltage window range) or ± 15% (selectable) voltage window range:

710-MAN Page 26 of 102

❖ System efficiency increases by 2% to 4% depending on the model

❖ Total power loss is reduced.

❖ The output AC voltage in the mode of operation follows proportionally to the input line voltage.

3.3 Theory of Operation

The following section describes the system’s theory of operation.

3.3.1 Standby Mode and Normal Mode

After power is applied to the system, the system enters standby mode and performs a self-test.

During this period, the start subroutine checks for input voltage, and proper operation of the inverter and bypass SCRs. After the self-test completes successfully, the system enters normal mode.

During normal mode:

1. Input contactor K1 receives a closing signal that connects input power to the DC supply transformer.

2. The DC rectifier supplies the battery charger, control board, and the DC/AC inverter circuit.

3. The battery charger is activated, allowing the batteries to be charged continuously.

4. The on-line DC/AC inverter converts the DC voltage to a PWM waveform. This waveform is filtered and reconstructed to a desired AC output.

3.3.2 Response to Input Power Failure

If the system controller senses a change in input frequency greater than ± 3 Hz or an out-of-range input voltage, it:

❖ Considers the event as an input failure and opens the input contactor immediately, isolating the unit from the facility.

❖ Turns off the charger and makes the battery bank a DC supply source to the inverter circuit, maintaining an uninterrupted AC supply to the protected load.

❖ Issues a UPS ALARM message on the LCD display panel.

When the facility power returns, stabilizes, and is in phase with the backup power, the system controller closes the input contactor and the system returns to normal mode. If the battery voltage drops below 16% of its nominal value and the facility power remains off, the system enters into alert mode.

710-MAN Page 27 of 102

3.3.3 UPS Alert

The system controller issues an ALERT message on the LCD display panel if any of the following conditions occurs:

❖ Internal failure

❖ System overheats

❖ Battery bank under-voltage

During an alert:

❖ The system stops its backup operation.

❖ The inverter SCRs are switched OFF.

❖ Bypass SCRs are switched ON.

❖ A summary alarm 5V signal is sent to the hardwired interface.

The system remains in this mode until power is cycled or the system is repaired.

3.3.4 UPS Alarm

The system controller issues a UPS ALARM message on the LCD display panel if any of the following conditions occurs:

❖ Input power failure

❖ Output overload

When the system is in alarm mode, inverter IGBs remain on and an alarm signal may be sent to the signal interface. The system resets itself when the problem no longer exists.

3.3.5 Output Loads

The system is designed to power any fluorescent or incandescent HID lighting. However, certain types of loads exhibit an excessive inrush current when first turned on or at other times during operation.

As a result, the capacity of the system might need to be greater than the capacity that is estimated based on requirements shown on the system’s nameplate. If you have questions about powering unusual loads from your system, contact your dealer or the factory.

Installation

710-MAN Page 28 of 102

Chapter 4. Installation

This chapter describes how to install the system. It includes pre-installation information along with guidelines for storing the system for future use.

710-MAN Page 29 of 102

4.1 Delivery Space Requirements

The following figures show the dimensions of the system cabinets as well as key components used for cable access and mounting.

Verify that the delivery area, the destination, and the path between them meet the standard delivery clearance and weight requirements of the system.

The delivery area must provide enough space and floor strength to support the packaged equipment cartons for the system. Doorways and hallways must provide enough clearance to move the equipment safely from the delivery area to the destination. Permanent obstructions such as pillars or narrow doorways can cause equipment damage. If necessary, plan for the removal of walls or doors.

Verify that all floors, stairs, and elevators you use when moving the system to its destination can support the weight and size of the equipment. Failure to do so could damage the equipment or your site.

710-MAN Page 30 of 102

Figure 4-1. 48-inch-high Cabinet Access and Mounting (Standard Series)

710-MAN Page 31 of 102

Figure 4-2. 68-inch-high Cabinet Access and Mounting (Standard Series)

710-MAN Page 32 of 102

Figure 4-3. 70-inch-high Cabinet Access and Mounting (Standard Series)

710-MAN Page 33 of 102

Figure 4-4. 68-inch-high Cabinet Access and Mounting (OSHPD/HCAI-Certified Seismic Series)

710-MAN Page 34 of 102

Figure 4-5. 70-inch-high Cabinet Access and Mounting (OSHPD/HCAI-Certified Seismic Series)

710-MAN Page 35 of 102

Figure 4-6. 48, 68-inch-high Cabinet Mounting Standard Series (Optional Zone 4 Seismic Brackets)

710-MAN Page 36 of 102

Figure 4-7. 70-inch-high Cabinet Mounting Standard Series (Optional Zone 4 Seismic Brackets)

Note: Do not remove any knockouts that will not be used

710-MAN Page 37 of 102

4.2 Site Considerations

Planning the proper location and layout of the system prior to installing it is essential for successful operation. To ensure normal operation and to avoid unnecessary maintenance, plan your site configuration and prepare your site before installation, refer to Table 4-1, for facility recommendation.

The system is designed for indoor installation and meets NEMA specifications for operating temperature, humidity, and utility voltage. The system enclosures are rugged and corrosion resistant.

All servicing is performed through the front of the unit; therefore, leave sufficient room in the front of the unit for service access.

The following precautions will help you plan an acceptable operating environment for the system:

❖ Select a flat location that is clean, with no dust or exposure to direct sunlight or vibrations. The location should provide a sturdy, level surface that can support the system. Avoid locations with inclined floors.

❖ The location should not be prone to variations in temperature and humidity or be close to strong magnetic fields or a device that generates electric noise.

❖ The unit should not be placed next to, on top of, or below any device that generates heat or will block the free flow of air through the system’s ventilation slots.

❖ The Lighting Inverter cabinets provide cable and conduit openings on the top and sides of the cabinet. Be sure these areas are not blocked and can be easily accessed to expedite installation.

❖ Electrical equipment generates heat. Ambient air temperature might not be adequate to cool equipment to acceptable operating temperatures without adequate circulation. Ensure that the room in which the system will operate has adequate air circulation.

Caution: Always follow proper ESD-prevention procedures to avoid damage to equipment. Damage from static discharge can cause immediate or intermittent equipment failure.

Caution: For sites with Generator and Automatic Transfer Switch (ATS) in conjunction with the unit, make sure the ATS has an open transition with minimum 20 milli-seconds transfer time (gap) in both directions

710-MAN Page 38 of 102

4.2.1 Recommended Facility Protective Device Ratings, BTU/HR, & Floor Loading.

Table 4-1

U n it R at in g

K W

In p u t

V o lt

U n it In p u t C ir cu it B re ak e r

(A m s)

O P

T

IO

N A

L

R ec o m m e n d e d

F ac ili ty

In p u t

C ir cu it

B re ak e r O ve r

C u rr en t

P ro te ct io n

A M

P

O u tp u t V o lt

U n it O u tp u t

C ir cu it

B re ak e r

(A m p s)

O P

T

IO

N A

L

R ec o m m e n d e d

F ac ili ty

O u tp u t

C ir cu it

B re ak e r O ve r

C u rr en t

P ro te ct io n

A

M P

B at t.

V o lt

M ax

B

D is ch

A

*B

TU

/H R u b le C o n ve rs io

(T yp ic al

*B

TU

Fa st

T ra n sf er

T yp ic al

U n it W ei gh t (i n cl u d in g

B at te ri es lb s.

A p p ro x.

Fl o o r

Lo ad in g

LB

/S

Q

FT

ab in et

D im e n si o n s

W x

H x es

2.1KW

120 50

R e co m m en d ed

F ac ili ty

In p u t

C ir cu it

B re ak er

S h o u ld B e E q u al t o o r La rg e r T h an t h e U n it

In p u t

C ir cu it

B re ak er

A m p ac it y

120 30

R e co m m en d ed

F ac ili ty

O u tp u t C ir cu it B re ak er S h o u ld

N o t B e L ar ge r Th an t h e

U n it O u tp u t

C ir cu it

B re ak er

A m p ac it y

96 30 1037

R e d u ce

B

TU

/H R p e r

896 230 39 x 48 x 18

208 30 208 20 96 30 1037 896 230 39 x 48 x 18

240 25 240 15 96 30 1037 896 230 39 x 48 x 18

277 25 277 15 96 30 1037 896 230 39 x 48 x 18

480 15 480 15 96 30 1037 896 230 39 x 48 x 18

3KW

120 50 120 30 96 43 1037 1066 273 39 x 48 x 18

208 30 208 20 96 43 1037 1066 273 39 x 48 x 18

240 25 240 15 96 43 1037 1066 273 39 x 48 x 18

277 25 277 15 96 43 1037 1066 273 39 x 48 x 18

480 15 480 15 96 43 1037 1066 273 39 x 48 x 18

3.5KW

120 60 120 50 120 35 1146 1171 300 39 x 68 x 18

208 50 208 30 120 35 1146 1171 300 39 x 68 x 18

240 40 240 25 120 35 1146 1171 300 39 x 68 x 18

277 30 277 25 120 35 1146 1171 300 39 x 68 x 18

480 20 480 20 120 35 1146 1171 300 39 x 68 x 18

5KW

120 60 120 50 120 59 1419 1284 329 39 x 68 x 18

208 50 208 30 120 59 1419 1284 329 39 x 68 x 18

240 40 240 25 120 59 1419 1284 329 39 x 68 x 18

277 30 277 25 120 59 1419 1284 329 39 x 68 x 18

480 20 480 20 120 56 1419 1284 329 39 x 68 x 18

5.25KW

120 60 120 80 120 52.5 1620 1666 193 51 x 70 x 30.5

208 60 208 50 120 52.5 1620 1666 193 51 x 70 x 30.5

240 50 240 40 120 52.5 1620 1666 193 51 x 70 x 30.5

277 50 277 35 120 52.5 1620 1666 193 51 x 70 x 30.5

480 30 480 20 120 52.5 1620 1666 193 51 x 70 x 30.5

6KW

120 80 120 80 144 56 1965 1284 329 39 x 68 x 18

208 50 208 50 144 56 1965 1284 329 39 x 68 x 18

240 50 240 40 144 56 1965 1284 329 39 x 68 x 18

277 40 277 30 144 56 1965 1284 329 39 x 68 x 18

480 30 480 20 144 56 1965 1284 329 39 x 68 x 18

710-MAN Page 39 of 102 it R at u t

V o lt

U n it In p u t C ir cu it B re ak e r

(A m

T

IO

N A

L

R ec o m m e n d e d

F ac ili ty

In p cu it

B re ak e r O ve r

C u rr en t

P ro te ct io n

A M

P

O u tp u t V o lt

U n it O u tp u t

C ir cu it

B re ak e r

(A m p s)

O P

T

IO

N A

L

R ec o m m e n d e d

F ac ili ty

O u tp u t

C ir cu it

B re ak e r O ve r

C u rr en t

P ro te ct io n

A

M P

B

B u b le C o n ve rs ic al

*B

TU

T ra n sf er

T yp ic al

U n it W ei gh t (i n cl u d in g

B at te ri es lb s.

A p p ro x.

Fl o o r

Lo ad in g

LB

/S in et

D im e n si o n s

W x

H

7KW

120 90

R e co m m en d ed

F ac ili ty

In p u t

C ir cu it

B re ak er

S h o u ld B e E q u al t o o r La rg e r T h an t h e U n it

In p u t

C ir cu it

B re ak er m p ac it y

120 100 e co m m en d ed

F ac ili ty

O u tp u t C ir cu it B re ak er S h o u ld

N o t B e L ar ge r Th an t h e

U n it O u tp u t

C ir cu it

B re m p ac it y

192 52 2800

R e d u ce

B

TU

/H R p e r

2042 236 51 x 70 x 30.5

208 70 208 50 192 52 2800 2042 236 51 x 70 x 30.5

240 60 240 50 192 52 2800 2042 236 51 x 70 x 30.5

277 50 277 40 192 52 2800 2042 236 51 x 70 x 30.5

480 40 480 30 192 52 2800 2042 236 51 x 70 x 30.5

7.5KW

120 100 120 100 120 88 2300 1074 236 51 x 70 x 30.5

208 70 208 50 120 88 2300 1074 236 51 x 70 x 30.5

240 60 240 50 120 88 2300 1074 236 51 x 70 x 30.5

277 50 277 40 120 88 2300 1074 236 51 x 70 x 30.5

480 40 480 30 120 88 2300 1074 236 51 x 70 x 30.5

8KW

120 100 120 100 192 56 2600 1464 375 39 x 68 x 18

208 70 208 50 192 56 2600 1464 375 39 x 68 x 18

240 60 240 50 192 56 2600 1464 375 39 x 68 x 18

277 50 277 40 192 56 2600 1464 375 39 x 68 x 18

480 40 480 30 192 56 2600 1464 375 39 x 68 x 18

8.75KW

120 150 120 100 192 64.5 2702 2572 298 51 x 70 x 30.5

208 80 208 60 192 64.5 2702 2572 298 51 x 70 x 30.5

240 60 240 60 192 64.5 2702 2572 298 51 x 70 x 30.5

277 60 277 50 192 64.5 2702 2572 298 51 x 70 x 30.5

480 40 480 30 192 64.5 2702 2572 298 51 x 70 x 30.5

10KW

120 150 120 100 192 74 3057 2870 332 51 x 70 x 30.5

208 90 208 60 192 74 3057 2870 332 51 x 70 x 30.5

240 70 240 60 192 74 3057 2870 332 51 x 70 x 30.5

277 60 277 50 192 74 3057 2870 332 51 x 70 x 30.5

480 40 480 35 192 74 3057 2870 332 51 x 70 x 30.5

10.5KW

120 150 120 150 240 76 3212 3132 363 51 x 70 x 30.5

208 125 208 80 240 76 3212 3132 363 51 x 70 x 30.5

240 125 240 60 240 76 3212 3132 363 51 x 70 x 30.5

277 80 277 60 240 76 3212 3132 363 51 x 70 x 30.5

480 40 480 35 240 76 3212 3132 363 51 x 70 x 30.5

12.5KW

120 175 120 150 192 92 3700 3777 437 51 x 70 x 30.5

208 125 208 80 192 92 3700 3777 437 51 x 70 x 30.5

240 125 240 70 192 92 3700 3777 437 51 x 70 x 30.5

277 80 277 60 192 92 3700 3777 437 51 x 70 x 30.5

480 45 480 40 192 92 3700 3777 437 51 x 70 x 30.5

710-MAN Page 40 of 102 it R at u t

V o lt

U n it In p u t C ir cu it B re ak e r

(A m

T

IO

N A

L

R ec o m m e n d e d

F ac ili ty

In p cu it

B re ak e r O ve r

C u rr en t

P ro te ct io n

A M

P

O u tp u t V o lt

U n it O u tp u t

C ir cu it

B re ak e r

(A m p s)

O P

T

IO

N A

L

R ec o m m e n d e d

F ac ili ty

O u tp u t

C ir cu it

B re ak e r O ve r

C u rr en t

P ro te ct io n

A

M P

B

B u b le C o n ve rs ic al

*B

TU

T ra n sf er

T yp ic al

U n it W ei gh t (i n cl u d in g

B at te ri es lb s.

A p p ro x.

Fl o o r

Lo ad in g

LB

/S in et

D im e n si o n s

W x

H

14KW

120 175

R e co m m e n d e d

F ac ili ty

In p u t

C ir cu it

B re

Sh u ld B e E q u al t o o r La rg er

T h an t h e

U u t

C ir cu it

B re ak er

A m p ac y

120 200 e co m m e n d e d

F ac ili ty

O u tp u t C ir cu

B re ak er

S h o u ld N o t

B e

L ar ge r

Th an t h e U tp u t

C ir cu it

B re ak er

A m p ac it y

240 103 5200

R e d u ce

B

TU

/H R p er

4512 522 51 x 70 x 30.5

208 125 208 125 240 103 5200 4512 522 51 x 70 x 30.5

240 125 240 125 240 103 5200 4512 522 51 x 70 x 30.5

277 100 277 100 240 103 5200 4512 522 51 x 70 x 30.5

480 45 480 40 240 103 5200 4512 522 51 x 70 x 30.5

15KW

120 200 120 150 240 109 5000 4512 522 51 x 70 x 30.5

208 125 208 90 240 109 5000 4512 522 51 x 70 x 30.5

240 125 240 80 240 109 5000 4512 522 51 x 70 x 30.5

277 100 277 70 240 109 5000 4512 522 51 x 70 x 30.5

480 60 480 60 240 109 5000 4512 522 51 x 70 x 30.5

17.0KW

120 200 120 200 240 121 5400 4512 522 51 x 70 x 30.5

208 125 208 125 240 121 5400 4512 522 51 x 70 x 30.5

240 125 240 125 240 121 5400 4512 522 51 x 70 x 30.5

277 100 277 100 240 121 5400 4512 522 51 x 70 x 30.5

480 60 480 60 240 121 5400 4512 522 51 x 70 x 30.5

1. For all wire sizes consult local codes and NEC based on unit current requirements.

2. For Different Input / Output voltage units, add 100 BTU/HR per KW for Transformer.

3. Input / Output power connections (terminal blocks), accepting 14 AWG to 2/O AWG.

4.The external input circuit breaker protecting the unit must be a delayed trip type. this is due to magnetic inrush current drawn during application of AC power.

4.2.2 Operating Environment

The location you choose for installation should confirm to the following conditions.

Table 4-2. Inverter Environmental Specifications

Inverter Environment Description

Operating Temperature: 0 to 40C (0 to 104F)

Battery compartment to be kept at battery operating temperature

Altitude: 1,829 meters (6,000 feet) de-rate 10% for each additional 305 meters (1,000 feet) up to 2,744 meters (9,000 feet)

Relative humidity: 0% to 95% (non-condensing)

Audible Noise: 57 dBA, typical

710-MAN Page 41 of 102

Caution: Operating batteries outside of the specifications shown above will shorten battery life significantly.

Table 4-3. Battery Environmental Specifications

Battery Environment Description

Ambient temperature: 20 to 25C (68 to 77 °F)

Relative humidity: 0% to 95% (non-condensing)

Operating altitude: 1,829 meters (6,000 feet) de-rate 10% for each additional 305 meters (1,000 feet) up to 2,744 meters (9,000 feet)

4.2.3 Floor Load Ratings

The floor space at the installation site must be strong enough to support the combined weight of the Lighting Inverter unit and its batteries. To ensure adequate load-bearing capacity, plan for the maximum configuration.

4.3 Delivery and Handling

4.3.1 Inspecting the Shipment

The equipment included in your shipment consists of one Lighting Inverter cabinet. Batteries will typically ship separately unless specified otherwise. The contents are covered with protective wrapping and packaged in heavy-duty cardboard. Each item is labeled with the component name for easy identification.

When the equipment arrives, count the number of items delivered to ensure that you have the complete shipment. Inspect all protective wrapping or crates and any boxes for signs of rough handling or damage, such as punctures and crushed sides, preferably without moving the equipment. If the shipping container or equipment itself shows evidence of damage, record the damage on the receiving document before signing for receipt of the equipment. Damage claims should be filed directly with the carrier.

Thoroughly inspect each battery for any signs of damage. If there is any damage, reject the shipment and notify the manufacturer by email services@800pwrsrvc.com. If possible, photograph the damage for future reference. As you unpack the pallet or container, check each battery box for damage on all sides, the top and bottom. If there is any sign of damage, photograph the damage if possible, and email services@800pwrsrvc.com.

4.3.2 Offloading the System

Because the system is designed for pad mounting, it is not accompanied by casters. At the user’s discretion, a forklift can be used to off load the unit from the shipping pallet. Always be sure that the load capacity of the forklift is sufficient to support the weight of the unit and its batteries.

mailto:services@800pwrsrvc.com

710-MAN Page 42 of 102

DANGER: Exercise extreme care when handling the cabinets to avoid equipment damage or injury to personnel. Each cabinet weighs several hundred pounds. Test lift and balance the cabinets before moving. Maintain minimum tilt from vertical at all times. The bottom structure will support the unit only if the forklift forks are completely underneath the unit.

4.3.3 Climatization

Units that are shipped or stored at extreme temperatures require time to adjust to operating temperatures before startup. If the unit arrives in hot or cold weather, do not unpack it until it has been allowed to reach room temperature (one to two hours).

Immediately exposing the unit to warm temperature can cause condensation to occur, which could damage the electronics. If you notice any condensation, allow the unit to stand unattended for one to two hours, and then unpack it.

4.3.4 Unpacking the Equipment

After checking the cartons for signs of damage, perform the following steps to unpack the equipment:

1. Open all cartons.

2. Compare the items received to the packing list.