UNH Memorial Union Building Hydraulic Improvement Spec 10-19-26.pdf

PDF 132 KB Posted

Attached to
UNH Memorial Union Building Elevator Controller Replacements
Solicitation number
2120271006
Issued by
New Hampshire

About this file

This document is a detailed specification section for hydraulic elevator improvements at the University of New Hampshire Memorial Union Building, prepared by USNH Facilities Project Management. The project involves the renovation of two oil-hydraulic elevators serving three to four floors with a travel range of 24 to 35.5 feet. The East Elevator will be a 4,500-pound capacity unit operating at 150 feet per minute with three stops, while the West Elevator will be a 2,000-pound capacity unit at 150 feet per minute with four stops. The scope of work includes replacement of controllers, power units, oil lines, traveling cables, wiring, car doors, door clutches, door operators, guide shoes, control switches, car operating panels, landing push button fixtures, and landing door interlocks. The specification allows for replacement of car door hangers, tracks, headers, and 2-speed side slide doors on the East Elevator's Level 1 rear opening and single-speed side slide doors on the West Elevator. Two alternates are included for complete car enclosure replacements on both elevators, featuring stainless steel finishes, LED lighting, emergency exit covers, and vinyl composition tile flooring. All bidders must visit the site prior to submission to examine existing conditions.

The elevator equipment must be manufactured by Canton Elevator, ESCO Elevator Products, Elevator Equipment Company, Inc., Motion Control, G.A.L. Manufacturing Corporation, EID, or PTL Equipment Co., Inc., or equal as approved by the owner. The installing firm must demonstrate at least three comparable installations within 50 miles of the site completed at least two years prior to bidding and must maintain a complete maintenance organization with trained mechanics and adequate parts inventory within 50 miles for at least five years prior to bidding. All work must comply with ASME/ANSI A17.1 safety codes, ANSI/NFPA 70 electrical codes, New Hampshire barrier-free design codes, and local requirements. The specification mandates non-proprietary equipment with microprocessor-based controllers accessible to any recognized service company and readily available aftermarket parts. The contractor must provide a 12-month warranty from final acceptance or state inspector certification and furnish monthly maintenance service and call-back support for one year, including all parts replacement at no cost to the owner except for damage from misuse or negligence. Payment and award terms are not specified in this specification document.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELEVATOR IMPROVEMENTS UNH

HYDRAULIC ELEVATORS MEMORIAL UNION BUILDING

14200- 1

SECTION 14200 – HYDRAULIC ELEVATORS

PART 1 – GENERAL

1.01 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.02 WORK INCLUDED

A. The work in this Section consists of all labor, materials, equipment and services necessary to complete the work of this Section, and without limiting the generality thereof includes:

1. The renovation of two (2) oil-hydraulic elevators, including transportation, insurance, temporary protection, supervision and incidental items essential for proper installation and operation even though not specifically mentioned or indicated in the Specifications, but which are usually provided or are essential for proper operation.

2. Furnish and maintain hoistway equipment, operating personnel and rigging to perform the work of this Section.

3. In all cases where a device or part of the equipment is referred to herein in the singular, it is intended that such reference shall apply to as many devices as required to complete the installation.

4. Scope of work:

a. East Elevator

Replace the controller, power unit, oil line, traveling cables, wiring, car door, car door clutches and related equipment, door operators, guide shoes, control switches located in each pit and hoistway, car operating panel, landing push button fixtures and landing door interlocks. Replace the car doors, hanger tracks, headers and rear landing door 2 speed side slide doors on Level 1.

The replacement of the entire car enclosure is an alternate and will be outlined in Alternate #1.

b. West Elevator

Replace the controller, power unit, oil line, traveling cables, wiring, car door, car door clutch and related equipment, door operators, guide shoes, control switches located in each pit and hoistway, car operating panel, landing push button fixtures and landing door interlocks. Replace the car doors, hanger tracks, headers and rear landing door 2 speed side slide doors.

The replacement of the entire car enclosure is an alternate and will be outlined in Alternate #2.

1.03 RELATED WORK SPECIFIED ELSEWHERE

A. The following items of work are not included in this Section and are specified under the designated

Sections.

1. WORK BY THE CONTRACTOR

a. Provide a dry, safe location for storage of the elevator materials.

14200- 2

b. Maintain two (2) hour fire rated hoistway walls, machine room walls and ceilings, with required legal ventilation.

c. Provide barricades and protection of hoistways during the time the elevator equipment is being installed.

d. Cut walls, floors, and partitions, together with any repairs made necessary thereby.

Provide and signal equipment such as indicators, push buttons, hall lanterns, etc.

e. Protect all finished installed work until Substantial Completion of Project, including installation of protective coverings at hoistway entrances.

2. Provide code required machine room ventilation, disconnect switches, light switches, 110 Volt breakers for car lights and fire rated machine room door and frame (B-Labeled).

A. MISCELLANEOUS METAL

a. Add metal grab bar to a required height of 48” (if not existing) and additional rungs to existing steel pit ladder to access elevator pit.

B. CEMENTITIOUS WATERPROOFING SECTION

NA

C. MECHANICAL SECTION

a. Ductwork and related work.

b. Venting of hoistways and machine rooms.

D. ELECTRICAL SECTION

a. Provide electrical power feeder for elevator controller and power unit, with main line fuse disconnect switch equipped with contacts to detect loss of power.

b. Provide separate fused electrical service for car lights in the machine room.

c. Provide fused electrical services, convenience outlets, switches and light fixtures in elevator pit and machine room.

d. Provide fused electrical service for elevator signal systems.

e. Network wiring for communication service to elevator.

f. Smoke detectors in elevator lobbies and machine room to initiate emergency recall operation.

g. Provide electrical service for the installation, testing and adjusting of the elevator equipment.

1.04 SUBMITTALS

A. General: Submit samples of all materials specified related to the elevator improvements.

B. Product Data: Include capacities, sizes, performances, operations, safety features, finishes and similar information. Provide manufacturer’s written specifications, installation and maintenance requirements for each product or material to be utilized in the elevator improvements.

C. Samples: Submit sample of finished materials and colors to Owner for approval, consisting of various exposed equipment and accessories, such as indicators, push buttons, etc., for selection and/or approval, as may be required.

D. Do not order materials or begin fabrications or installation of materials until approval has been obtained.

E. Maintenance Manuals: Include operation and maintenance instructions, part listing with sources indicated, recommended parts inventory listing, emergency instructions, and similar information.

14200- 3

Include diagnostic and repair information available to manufacturer's and Installer's maintenance personnel. Submit for Owner's information at Project closeout.

F. Inspection and Acceptance Certificates and Operating Permits: As required by authorities having jurisdiction for normal, unrestricted elevator use.

1.05 REQUIREMENTS OF REGULATORY AGENCIES

A. Comply with all State and Local Authorities having jurisdiction and obtain all necessary permits, pay all fees, obtain all required inspections, and carry out all required tests which are required by such Authorities.

1.06 STANDARDS, CODES AND REGULATIONS

A. Furnish all elevator equipment in accordance with most-stringent applicable provisions of the following Codes and/or Authorities, including revisions and changes in effect on date of these specifications:

1. American National Standards Institute “Standard Safety Code for Elevators, Dumbwaiters, Escalators and Moving Walks”, ASME/ANSI A17.1 (the ANSI Code).

2. Inspector’s Manual, ASME/ANSI A17.2.

3. National Electrical Code, No. ANSI/NFPA 70.

4. Requirements of any other Codes, Ordinances and Laws applicable with the governing jurisdiction.

5. Architectural Barrier-Free Design Code for New Hampshire.

1.07 COORDINATION

A. Coordinate locations and dimensions of other work relating to hydraulic elevators including pit ladders and sumps in pits; entrance sub-sills; and electrical service, electrical outlets, lights, and switches in pits and machine rooms.

1.08 WARRANTY

A. Provide written warranty agreeing to replace, repair, and restore defective materials and workmanship of elevator work for a period of 12 months from date of final acceptance by Owner or certification of the elevators by State Inspectors, whichever is later. “Defective” is hereby defined to include, but not limited to operation or control system failures, performances below required minimum, excessive wear, unusual deterioration or aging of materials or finishes, unsafe conditions, the need for excessive maintenance, abnormal noise or vibrations, and similar unusual, unexpected and unsatisfactory conditions.

B. This warranty is not intended to supplant maintenance service and shall not be construed to require free service for periodic examination, lubrication, or adjustment due to normal use, beyond that included in the Specification; nor correction without charge, or breakage, maladjustment, or other trouble arising from abuse, misuses, or any other causes beyond the control of the Elevator Manufacturer and Elevator Installing Firm.

1.09 MAINTENANCE

A. The Elevator Installing Firm shall furnish maintenance and call back service for a period of one (1) year following the date of final acceptance by the Owner or certification for operation by State

14200- 4 authorities, whichever is later. Maintenance services shall consist of at least monthly inspections, lubrication, and adjustment of equipment. Call back service will provide all intermediate service calls requested by the Owner. This shall consist of responding within one hour of notification provided such notification is during normal working hours of the elevator trade and within two hours outside of regular working hours of the trade.

B. The Elevator Manufacturer and/or Elevator Installing Firm shall furnish all labor, material, and equipment required for replacing all parts which become defective within one year (or as required by article 1.11 below) after date of Substantial Completion of Project at no cost to the Owner, except defects due to misuse, accidents, or negligence on the part of the Owner will not be considered to be covered under the maintenance guarantee.

C. Include, but do not limit to, replacement of all seals, packing and reservoir oil as often as necessary during the maintenance period to maintain adequate factor of safety and performance. Only genuine standard parts produced by the manufacturer of the equipment concerned shall be used for replacement.

D. All work under the maintenance provision shall be performed by trained, competent personnel under the supervision and in the direct employ of the Elevator Manufacturer and/or Elevator Installing Firm.

E. The maintenance service shall be performed solely by the Elevator Installing Firm and shall not be assigned or transferred to any agent or subcontractor.

1.10 ADDITIONAL REQUIREMENTS

A. It is the responsibility of the Elevator Installing Firm to examine all conditions in the Specifications and the governing laws and building code, and to assume all costs in connection with this Contract, including cost of any incidental work and equipment which may not be called for on the Drawings and Specifications but which are necessary for construction and proper operation of elevators or required by the governing laws and building codes.

1.11 PROPRIETARY EQUIPMENT

A. The intent of this specification is that all elevator equipment installed, including but not limited to the elevator controller, be non-proprietary in nature. Non-Proprietary shall be defined as that which can be easily serviced by any and all recognized service companies and for which all repair and replacement parts are readily accessible on the aftermarket within one year of the initial installation.

PART 2 – PRODUCTS

2.01 MANUFACTURER

A. The elevator equipment shall be manufactured by Canton Elevator. ESCO Elevator Products, Elevator Equipment Company, Inc., Motion Control, G.A.L. Manufacturing Corporation, EID and PTL Equipment Co., Inc. or equal as approved by the Owner.

1. The Elevator Installing Firm shall have been regularly engaged in the installation of elevators of the type specified herein and shall be able to demonstrate at least three installations of the type specified made by him within fifty (50) miles of the site, which have provided

14200- 5 satisfactory operation for a period of at least two years prior to the date of receipt of general bids for this project.

2. Also, the Elevator Installing Firm shall be able to demonstrate that they have provided satisfactory maintenance service for elevators of the type specified, that they have maintained a complete elevator maintenance organization comprised of regularly employed, competent, trained elevator mechanics, and that they have maintained an adequate stock of parts for replacement and emergency purposes, all within 50 miles of the site for a period of at least five years prior to the date of receipt of general bids.

2.02 DESCRIPTION OF EQUIPMENT

A. Elevator No. 1 East elevator Memorial Union Building NHE

1. Type: Passenger, holed hydraulic.

2. Capacity: 4500 pounds.

3. Speed: 150 feet per minute.

4. Entrances: Retain landing doors and frames Levels 2 and 3. Replace rear landing door on Level 1.

5. Hoistway Access: Drop key, all levels.

6. New Car Direction Lanterns with Audible Signals: Horizontal hall lanterns and vertical surface mounted pushbutton hall stations with brushed stainless steel trim.

7. Position Indicators: Car Operating Panel and Hall Call Button Fixtures.

8. Registration Lights: Car and Corridor Pushbuttons.

9. Travel and Stops: 24'- 0" travel, 3 stops in line. Floors Served: 1, 2 and 3.

10. Openings and Type: Four openings 42” w x 84" high; Two-speed Side Slide.

11. Power Supply: 460 volt, 3 Phase, 60 Cycle.

12. Motor: Submersible

13. Emergency Operation: Fireman’s Service – Phase I and II, with Yale Key 3502.

14. Car Ceiling: Alternate to Replace..

15. Car Enclosure: Alternate to Replace..

16. Hand Rails: Alternate to Replace..

17. Floor Designations: Retain.

18. Sills: Retain.

19. Special Features:

a. Disabilities Act (ADA) of 1990, effective 1/26/92

b. Car Door Full Length Detection Device

c. New Two-Way audio plus 1 way video Communication, one touch auto dial, built-in, by Rath.

d. Solid state closed transition starting.

e. Tank Heater to maintain temperature of oil at minimum of 100 degrees.

f. Battery backup for controlled descent to lowest level of egress in event of power loss.

g. Key switches for in-cab light, fan, door hold-open features – cylinders by BEST.

B. Elevator No. 2 West Elevator

1. Type: Passenger, holed hydraulic.

2. Capacity: 2,000 pounds.

3. Speed: 150 feet per minute.

4. Entrances: Retain landing door and frames.

5. Hoistway Access: Drop key, all levels.

14200- 6

6. New Car Direction Lanterns with Audible Signals: Horizontal hall lanterns and vertical surface mounted pushbutton hall stations with brushed stainless steel trim.

7. Position Indicators: Car Operating Panel and Hall Call Button Fixtures.

8. Registration Lights: Car and Corridor Pushbuttons.

9. Travel and Stops: 35’-6” travel, 4 stops in line, one rear opening. Floors Served: G, 1, 2, 3.

10. Openings and Type: 42” w x 84" high; Single-speed Side Slide.

11. Power Supply: 460 volt, 3 Phase, 60 Cycle.

12. Motor: Submersible

13. Emergency Operation: Fireman’s Service – Phase I and II, with Yale Key 3502.

14. Car Ceiling: Alternate to Replace.

15. Car Enclosure: Alternate to replace.

16. Hand Rails: Alternate to Replace.

17. Floor Designations: Retain.

18. Sills: Retain.

19. Special Features:

a. Disabilities Act (ADA) of 1990, effective 1/26/92

b. Car Door Full Length Detection Device

c. Two-Way audio plus 1 way video Communication, one touch auto dial, built-in by Rath.

d. Solid state closed transition starting.

e. Tank Heater to maintain temperature of oil at minimum of 100 degrees

f. Battery backup for controlled descent to lowest level of egress in event of power loss.

g. Key switches for in-cab light, fan, door hold-open features – cylinders by BEST

2.03 ELEVATOR MACHINERY

A. Type of Equipment:

1. The elevators are the oil hydraulic type with direct acting plungers, pumping units, storage tanks and control valves. The power units and associated control equipment are located in separate machine rooms

2. The pumps shall deliver oil directly to the cylinders at the necessary pressure and in sufficient quantity to lift a fully loaded elevator at the specified speed. The tanks shall act as a storage tanks only and the oil shall be pumped into the cylinder on the up trip and shall be returned into the tanks on the down trip.

B. Earth Casings for Cylinders: To be retained

C. Power Units:

1. The power units shall be compactly and neatly designed with all components combined in self-contained units and with all adjustment features accessible for adjustment. Each power unit shall include a constant displacement rotary screw type pump, motor designed for oil hydraulic elevator service, oil reservoir with an oil-level (glass gauge) indicator, control valve, tank strainer in suction line, and a blow-out proof muffler to reduce pulsations that may occur in the system. The power unit shall be tested and adjusted at the factory by operating a test elevator loaded to conform to the elevators specified here-in.

2. Control Valve Assembly: Shall be of compact design, equipped with filters to protect the valves and suitable for operation under the required pressures. It shall contain a metered bypass valve, a check valve, a relief valve, a manual lowering valve, metered lowering and leveling

14200- 7 valves and pilot valves. An isolated seal and coupling device, designed to reduce the transmission of vibrations and noise to the elevator car, shall be provided. The elevator speeds shall not vary more than 10% of the contract speed, in either direction, regardless of the load.

Operation of the manual lowering valve shall permit the elevators to be lowered at slow speed, in the event of a power failure.

3. Storage Tanks: The oil reservoirs shall be constructed of welded steel sheets, and shall be provided with a cover, a protected vent opening, a filtering screen mounted over the suction inlet and a drain connection and an initial supply of oil, sufficient for proper operation of the elevators, shall be provided. Each tank shall have a capacity equal to the volume of oil required to lift the elevator to the top terminal landing plus a reserve of not less than ten (10) gallons.

a. Each tank shall be provided with a sight gauge to meter the hydraulic fluid level. The permissible minimum hydraulic fluid level shall be clearly indicated.

b. Data plates shall be affixed to each tank indicating the characteristics of the hydraulic fluid used, the installation date, the name of the Contractor, the manufacturer’s name, the piston diameter, and manufacturer's designed head pressure.

4. Muffler: Blow-out muffler, designed to minimize the transmission of fluid pulsations, shall be furnished and installed in the pipe-line between the pumping units and the cylinder heads of each unit.

B. Sound Isolation Couplings: A minimum of two shall be installed in each machine room oil lines between the pump and jack.

C. Rubber Isolation: Rubber isolation mats shall be installed on the machine room floor and the tank reservoirs.

D. Oil Line:

1. New oil lines shall be furnished and installed between the pumping units and the cylinder heads complete with necessary fittings. Gate valves, one in each machine room and one in each pit, shall be provided in the line to facilitate maintaining and adjusting the elevators.

All hydraulic piping related to the elevator machinery shall be installed so that rigid contact between the piping and other building systems is avoided. Piping supports shall include Neoprene Isolators (1/4 inch static deflection) and Neoprene Filler Sleeves shall be used where piping penetrates walls.

2. Furnish and install new rupture valves on the oil lines adjacent to the in-ground jack.

E. Controllers:

1. The elevator controllers shall utilize a non-proprietary microprocessor based logic system that can be easily serviced by any and all recognized service companies with parts easily accessible on the aftermarket and shall comply with ANSI/ASME 17.1 safety code for elevators. The system shall provide comprehensive means to access the computer memory for elevator diagnostic purposes, and shall have permanent indicators to indicate important elevator statuses as an integral part of the controller. Systems that require hookup of external

14200- 8 devices for troubleshooting shall have the device provided to the Owner as part of the installation.

2. Failure of any single magnetically operated switch, contactor, or relay to release in the intended manner or the occurrence of a single accidental ground or short circuit shall not permit the car to start or run if any hoistway door or gate interlock is unlocked or if any hoistway door or car door or gate contact is not in the made position. Furthermore, while on car top inspection or hoistway access operation, failure of any single magnetically operated switch, contactor or relay to release in the intended manner or the occurrence of a single accidental ground shall not permit the car to move even with the hoistway door locks and the car door contacts in the closed or made position.

3. Dedicated permanent status indicators shall be provided on the controller to indicate the following: When the safety circuit is open, when the door locks are open, when the elevator is operating at high speed, when the elevator is on independent service, when the elevator is on fireman’s service, when the elevator out of service timer has elapsed or when the motor limit timer or valve limit timer has elapsed. In addition, provide means of displaying other special or error conditions that are protected by the microprocessor.

4. All available options or parameters shall be field programmable, without need for knowledge of any programming languages. Programmable options and parameters shall be stored in a nonvolatile memory. As a minimum there shall be a 32 character alphanumeric display to be used for programming and diagnostics. Programmable parameters and options shall include and not be limited to the following:

a. Number of stops/opening served (each car)

b. Simplex Selective Collective/Double Hall Button

c. Fire Floors (Main, Alternates)

d. Single Automatic Pushbutton

e. Floor Encoding (Absolute PI)

f. Digital PI’s/single wire PI’s

g. Programmable door times

h. Programmable Motor Limit Timer

i. Nudging

j. External Car Shutdown Input (e.g. Rescuvator)

k. External Low Oil Sensor Input

l. External Viscosity Control Input

m. Parking Floors

5. On power up the controller shall move the car to the closest floor to identify the position of the elevator.

6. The controllers shall have a real-time clock/calendar with battery backup.

7. The controllers shall have a serial port for communication with any data or computer terminal such as CRT terminal, modem, etc.

8. Overload relays shall be of the manual reset type of suitable size for the motor furnished.

9. A main line switch shall be provided on the controllers to avoid the possibility of pump churning.

F. Reduced Voltage Starting: Solid-state closed transition starter will be required.

G. Stop Switch in Pit: A stop switch shall be provided in the elevator pits and shall conform to the specified code. The pit switch, when in the off position, shall eliminate, along with other operations, car leveling.

H. Car Stall Protective Circuit: In the event the car should stall while ascending as the result of a relay or control failure, valve failure, low oil in the system, etc., a special circuit shall be provided which

14200- 9 shall automatically return the car to the bottom landing and perform a normal door operation, after which the elevator shall be completely shut down except for the door operation. Service will be restored by recycling the main line disconnect switch.

I. Motor Limit Timer: A motor limit timer function shall be provided which, in the event of the pump motor being energized longer than a predetermined time, shall cause the car to descent to the lowest landing, open the doors automatically and then reclose them. The car calls shall then be canceled and the car taken out of service automatically. Operation may be restored by cycling of the power disconnect switch.

J. Valve Limit Timer: A valve limit timer shall be provided which shall automatically cut off current to the valve solenoids if they have been energized longer than a predetermined time. The car calls shall then be canceled and the car taken out of service automatically. Operation may be restored by the cycling of the power disconnect switch.

K. Wiring: The Elevator Installing Firm shall furnish and install complete, all necessary insulated wiring to connect all parts of the equipment. All wire and traveling cables shall have a flame retarding and moisture resisting outer covering and shall be run in metal conduit, metallic tubing, wire ducts or raceways. Traveling cables shall be flexible and suitable suspended so that there is no strain on individual conductors. All electrical material and work shall, at minimum, comply with the latest enforcing electrical codes. Shielded telecommunication and 24V low voltage power wiring to be installed within traveling cables of each elevator Wiring to be 1 pair of #18 AWG conductors for 24V power, and 24 Ga. Shielded CAT-6 twisted pair cable for data.

L. Guide Rails:

1. Guide rails shall be retained.

2. Guide rails shall be free of any signs of rust or abrasion, and shall be filed to remove all rough edges prior to final inspection. All guide rail joints shall be filed to assure perfectly matching surfaces.

3. Unused sections of the rails shall be painted a flat black...

M. Guide Shoes: New guide shoes shall be mounted on the top and bottom of each car frame and shall be held in contact with the guide rails. Guides shall run on lubricated rails.

N. Buffers: Shall be retained. The buffers and pit channels shall be cleaned and painted with a flat black paint.

2.04 OPERATION AND CONTROL

A. Simplex Selective Collective Automatic Push Button Operation:

1. Control of the elevators shall be automatic in operation by means of push buttons in each elevator marked for each of the landing levels served and button boxes at each of the landing levels served. Car or hall calls shall be registered by the momentary pressing of landing or car buttons and shall be maintained until the car answers the call. Each landing station shall contain push buttons which shall “light up” when pressed to indicate that a call has been registered to bring the car to that particular landing (see Car and Hall Stations). A time delay, non-interference feature shall be incorporated in the control mechanism to allow ample time for opening and closing of the car and hoistway doors before it is again placed in motion.

2. The new car operating panels shall contain a keyed stop switch to interrupt the power supply to the valves and pump motor, independently of the regular operating devices. The opening

14200- 10 of the stop switch shall not cancel the registered calls or the leveling operation while the elevator is in the landing zone and, after the stop switch is closed the car shall continue to answer its various calls. The car operating panels shall also contain a key operated light and fan switch.

3. Hall or car call registration and lamp acknowledgment shall be by means of a single wire per call besides the power busses. Systems that register the call with one wire and light the call acknowledgment lamp with a separate wire are not acceptable.

4. Elevator Car and Hall Stations:

a. All the signal systems described herein will be manufactured by PTL Equipment Company, Inc.

b. All faceplates shall be surfaced mounted stainless steel with #4 satin finish and shall be .135 thick.

c. All engraved numbers and letters on the faceplate for floor buttons shall be 5/8” high.

d. All other buttons and switches shall be identified with engraved lettering approximately

5/16” high.

e. All symbols shall company with the latest ANSI Handicap Code.

f. Buttons shall be of the mushroom type bottoming out on the plate. Buttons shall be stainless steel with a maximum protrusion from the cover surface of 3/16”.

g. All floor buttons and switch assemblies requiring visual acknowledging light shall be

1/4-inch diameter clear Lexan Jewel replaceable insert type.

h. Hall push buttons shall have direction arrows and Lexan inserts.

i. Contact switch assembly shall be the Square D Class 9001 Type K contact.

j. Provide and install BEST MORTISE ELECTRIC SWITCH LOCKS with removable cores.

k. Provide one (1) control key and three (3) change keys for construction phase of project.

Control key and change keys to be turned over to UNH lockshop at completion of project.

l. The new landing push button stations must be provided with appropriately sized boxes to ensure that the face plate can be installed tight to the finished wall surface.

5. Operating Procedures:

a. The operation of each elevator shall be from a single riser of pushbutton boxes at each landing, with “UP” and “DOWN” pushbuttons at all intermediate landings, and a single pushbutton at each terminal landing.

b. If the hoistway door interlock and the car door contact circuits have been activated, the car door contact circuits have been activated, the car shall start automatically upon activation of one or more pushbuttons within the car or in the hallway. The car shall stop at any floor reached for which a car call or a hall call in the direction of travel has been registered. The car shall not respond to hall calls registered in the opposite direction of travel unless it is the last call reached in the direction ahead of the car. The car shall make stops in the natural order in which calls are reached, irrespective of the sequence of which the calls have been registered, if the call is registered sufficiently in advance of the arrival of the car at that particular floor to permit a stop to be made.

B. Firefighters Service: The elevators shall be equipped with Phase I, Emergency Recall Operation and Phase II, Emergency In-Car Operation. The Firefighters Service shall comply with A17.1;

211.3 through 211.8 and the Local Fire Fighters Code. Designated level shall be the 1st Floor and the Alternate level shall be 2nd Floor.

14200- 11

C. Independent Service: The elevator(s) shall be provided with a key switch to remove them from the “Automatic” operation where the elevator(s) shall operate in response to car calls only “in an independent mode of operation”. Final cylinder will be an ASSA cylinder furnished by the Owner.

D. Signals:

1. Car and Hall Buttons: When a call is registered by pressing a button, it shall illuminate to indicate that a call has been registered. The button shall remain lit until the elevator answers the call.

2. Alarm Bell: An alarm bell shall be provided in the hoistway, connected to the alarm bell button in the car.

3. Make all provisions to comply with State and Federal Disability Acts and codes referred to here.

E. Two-Way Leveling: The car shall be equipped with a two-way leveling to automatically bring the car sill level with the landing sill, with a minimum one-quarter (1/4) inch tolerance above or below the floor, regardless of load. The two-way leveling system feature shall be automatic and independent of the operating device.

F. Automatic Terminal Stops: Replace limit switches.

2.05 Car Frame, Platform Car Enclosure

A. Car Frames:

1. Car frames shall be retained.

B. Car Platform: to be retained.

C. Car Enclosures: East Elevator to be retained. West Elevator Cab is an Alternate

The car doors on the West elevator shall be replaced.

1. The car doors shall be horizontal sliding type construction not less than one (1) inch thick.

The car door panels shall be hung on two-point suspension sheave-type hangers similar to those specified for hoistway doors. Doors shall be especially design and reinforced for power operation. Face doors with Satin stainless steel with a # 4 finish.

D. Emergency communication systems shall be part of the new car operating panels along with the necessary communication wires from the car operating panel cabinet to a junction box, furnished and installed by other trades, on the new controller. The communication system shall be of the vandal-resistant, hands-free equipped with push button automatic dial system.

1. Provide an emergency light mounted above the car operating panels as required by code.

2.06 DOORS AND ENTRANCES

A. The new landing doors shall be as follows:

East Elevator: Two Speed Side Slide. West Elevator: Single Speed Side Slide.

The new landing doors shall be horizontal sliding type construction not less than one (1) inch thick.

The landing door panels shall be hung on two-point suspension sheave-type hangers.

14200- 12

The landing door panels shall be hung on two-point suspension sheave-type hanger.

East Elevator:

The landing doors on floor openings G, 1, 2, 3 shall be retained.

The two speed side slide door panels at the rear opening marked C shall be replaced. Panels shall be B-Labeled and painted to match door frame. The door frames and headers to be cleaned and repainted.

1. Sills: To be retained. Sills to be wire brushed and vacuumed clean.

2. Fascia Plates and Toe Guards: To be retained. Elevator Contractor to insure all fascia plates are in place and securely fastened.

3. Hanger Supports and Dust Covers: To be retained.

4. Struts and Closer Angles: To be retained.

5. Sight Guards: Sight guards to be replaced.

West Elevator:

The single speed side slide landing door panels shall be replaced.

1. The new landing doors shall be B-Labeled.

2. Sills: To be retained. Sills to be wire brushed and vacuumed clean.

3. Fascia Plates and Toe Guards: To be retained. Elevator Contractor to insure all fascia plates are in place and securely fastened.

4. Hanger Supports and Dust Covers: To be retained.

5. Struts and Closer Angles: To be retained.

6. Sight Guards: Sight guards to be retained

B. Door Operators:

1. Doors on the car and at each hoistway landing shall be operated quietly and smoothly by an electric operator, which shall open and close the car doors and hoistway doors simultaneously.

2. The car doors shall be provided with a non-contact detector system, which shall cause the door to reopen upon the detection of a person or object in the entrance of the elevator. The detector shall extend the full length of and not project beyond the leading edge of the car doors. The car door protection device shall be of the infrared type ray screen. The infrared ray screen, when interrupted, shall hold the door in the open position, permitting the door to close shortly after the closing and the infrared ray screen is interrupted. The door shall automatically reverse and return to the full open position, reclosing after a predetermined time interval. Pressing of car operating floor button, or “Door Close” button, shall cancel the door timing interval and cause the doors to close.

3. A door restrictor shall be installed on the car doors to prevent the opening of the doors from within the elevator unless the elevator is in the landing zone.

4. Each hoistway door opening shall be equipped with a new positive electromechanical interlock and auxiliary door closing device (sill mounted type) so that the elevator can be operated only after the interlock circuit is established. The interlock operations shall comply with the specified codes. Double interlocks shall be installed on center opening doors.

5. An electric contact for the car door shall be provided which shall prevent the elevator movement away from the landing unless the door is in the closed position as defined in the specified codes.

14200- 13

6. The door shall open automatically only after the elevator comes to a complete level stop, and close automatically either after the expiration of a time interval or the moment a car button call is registered. The door shall open only for the landing being served. A “Door Open” button, in the car station, shall cause the door to stop and reopen upon activation of that button. The activation of a landing or car station button, at the landing where the elevator is located shall cause the doors to stop and reopen.

7. Door protection timers shall be provided for both the open and close directions which will help protect the door motor and which will help prevent the car from getting stuck at a landing. The door open protection timer shall cease attempting to open the door after a predetermined time in the event that the doors are prevented from reaching the open position.

The door close protection timer will reopen the doors for a short time in the event that the door closing attempt fails to make up the door locks after a predetermined time.

8. A minimum of three different door standing open times shall be provided. A car call time value shall predominate when a car call only is canceled. A hall call time value shall predominate whenever a hall call is canceled. In the event of a door reopen from the safety edge, photo eye, or door open button, a separate short door time value shall predominate.

The timing value for these timers must be field adjusted.

C. West Elevator: Car Doors, Hangers and Tracks: To be replaced.

D. East Elevator: Landing Door Hangers and Tracks to be retained.

PART 3 – EXECUTION

3.01 INSTALLATION

A. The Elevator Installing Firm shall be responsible for making field measurements of the machine rooms, hoistway, and openings for entrances before submitting drawings. After approval of shop drawings, the Elevator Installing Firm shall be responsible for the installation of equipment without field changes. The elevator improvements cannot begin until all material is on-site or stored at the installing firms warehouse

B. Elevator Improvements shall be complete in all respects and in a first-class manner, in accordance with the approved shop drawings, and the requirements of the laws, rules, regulations, codes, and industry standards specified herein.

C. Elevator work shall be complete in all respects, with all components properly adjusted, and with all operating mechanisms and controls in proper working order.

D. All Bidders shall visit the building/site prior to bidding, to examine existing conditions.

3.02 GENERAL APPLICATION

A. General: Installation shall be in accordance with manufacturer’s instructions and shall comply with applicable codes.

B. Welded Construction: Provide welded connections for installing elevator work where bolted connections are not required for subsequent removal or for normal operation, adjustment, inspection, maintenance, and replacement of worn parts. Comply with AWS standards for workmanship and for qualifications of welding operators.

14200- 14

C. Sound Isolation: Mount rotating and vibrating equipment on vibration-isolating mounts designed to effectively prevent transmission of vibrations to structure and thereby eliminate sources of structure-borne noise from elevator system.

D. Lubricate operating parts of systems as recommended by manufacturer.

E. Leveling Tolerance: 1/4 inch (6mm), up or down, regardless of load and direction of travel.

3.03 WIRING

A. Furnish and install as work of this Section all wiring necessary to connect operating buttons, switches and signals in the hoistway and all electrical equipment on the car to the elevator control panel. The wiring shall be installed in a neat and orderly manner, and shall be installed in conduit, electrical metallic tubing or metal wireways, excluding traveling cables, except that flexible conduit may be used for short runs.

B. Traveling cables shall be of the best grade for service and shall be so installed to provide a proper size loop to the car. The traveling cables shall have a fire resistant outer braid. Protection against wear shall be provided on any structural surface where the traveling cables come in contact during the movement of the elevator.

C. Three complete sets of wiring diagrams containing any field corrections, if necessary, shall be provided to the Owner upon completion of the installation of elevator equipment.

3.04 DEMONSTRATION

A. Instruct Owner’s personnel in proper use, operations, and daily maintenance of elevators. Review emergency provisions, including emergency access and procedures to be followed at time of operational failure and other building emergencies. Train Owner's personnel in procedures to follow in identifying sources of operational failures or malfunctions. Confer with Owner on requirements for a complete elevator maintenance program.

B. Make a final check of each elevator operation with Owner’s personnel present and before date of

Substantial Completion. Determine that operation systems and devices are functioning properly.

END OF SECTION 14200

14200- 15

ALTERNATE #1

EAST ELEVATOR CAR ENCLOSURE

1. Remove and dispose of the existing car enclosure. Furnish and install new car enclosures as specified hereinafter:

2. Each canopy shall be constructed of reinforced 14-gauge furniture steel with a hinged emergency exit cover that can be opened from the car top only. The emergency exit cover shall be secured with a lock and a switch. The lock will be arranged to be opened by hand from the car top and opened from inside the car with the use of a key. A switch shall be mounted on the car top and arranged to remove power from the pump motor and controller when the emergency exit cover is in the open position. The switch must be of the manual reset type. The dome's interior finish shall be white reflective baked enamel. Lighting shall consist of down-light LED fixtures flush mounted in the car canopy.

3. Front return panels with integral entrance columns, stationary construction, and properly reinforced shall be provided. The finish shall consist of 16 gauge, 303 type, brushed stainless steel with a # 4 finish.

4. The transoms shall be constructed of 16 gauge, 303 type, stainless steel, with a # 4 finish, the full width of each cab enclosure.

5. The door panels shall be constructed of 16 gauge steel, sandwich construction. Provide a minimum of two gibs, one at the leading and one at the trailing edge of each car door. The gibs shall travel in the sill groove the entire length of the door travel. The finish shall consist of 16 gauge, 303 type, stainless steel with a # 4 finish.

6. The interior wall finish from the top of the handrails to the ceiling or dome shall consist of laminated panels and textured stainless steel from the finished floor to the bottom of the laminated panels and mounted on 3/4" plywood, colors and style to be selected by the Owners. The walls and return panels shall be bolted in place to the car platform. The bolt heads shall not be visible from inside the car, nor rise above the panels' support base. Welding, metal or wood screws shall not be considered acceptable fasteners.

7. Ventilation shall consist of a two-speed exhaust blower mounted to the car canopy on isolated rubber grommets. The blower shall be equipped with a diffuser and Grille.

8. Handrails shall be mounted on the side wall adjacent to the car operating panel. The handrails shall be equipped with 1 and 1/2" diameter stainless steel spacers and constructed as follows: 2" x 3/8" flat with a # 4 satin stainless steel finish. The return side shall face the cab wall. The handrail shall be free of any sharp edges.

9. The finished flooring shall consist of 3/8" thick vinyl composition tile. The subfloor shall be constructed of two (2) layers of ¾” Marine plywood and properly leveled before the finished flooring is installed. The tile shall meet the Specifications of Nora Rubber Flooring, Heavy Traffic, with a ten-year warranty. Colors shall be selected by the Owner.

10. The Elevator Contractor shall provide the General Contractor and UNH with a variety of floor samples and rendered elevations.

14200- 16

ALTERNATE #2

WEST ELEVATOR CAR ENCLOSURE

1. Remove and dispose of the existing car enclosure. Furnish and install new car enclosures as specified hereinafter:

2. Each canopy shall be constructed of reinforced 14-gauge furniture steel with a hinged emergency exit cover that can be opened from the car top only. The emergency exit cover shall be secured with a lock and a switch. The lock will be arranged to be opened by hand from the car top and opened from inside the car with the use of a key. A switch shall be mounted on the car top and arranged to remove power from the pump motor and controller when the emergency exit cover is in the open position. The switch must be of the manual reset type. The dome's interior finish shall be white reflective baked enamel. Lighting shall consist of down-light LED fixtures flush mounted in the car canopy.

3. Front return panels with integral entrance columns, stationary construction, and properly reinforced shall be provided. The finish shall consist of 16 gauge, 303 type, brushed stainless steel with a # 4 finish.

4. The transoms shall be constructed of 16 gauge, 303 type, stainless steel, with a # 4 finish, the full width of each cab enclosure.

5. The door panels shall be constructed of 16 gauge steel, sandwich construction. Provide a minimum of two gibs, one at the leading and one at the trailing edge of each car door. The gibs shall travel in the sill groove the entire length of the door travel. The finish shall consist of 16 gauge, 303 type, stainless steel with a # 4 finish.

6. The interior wall finish from the top of the handrails to the ceiling or dome shall consist of laminated panels and textured stainless steel from the finished floor to the bottom of the laminated panels and mounted on 3/4" plywood, colors and style to be selected by the Owners. The walls and return panels shall be bolted in place to the car platform. The bolt heads shall not be visible from inside the car, nor rise above the panels' support base. Welding, metal or wood screws shall not be considered acceptable fasteners.

7. Ventilation shall consist of a two-speed exhaust blower mounted to the car canopy on isolated rubber grommets. The blower shall be equipped with a diffuser and Grille.

8. Handrails shall be mounted on the side wall adjacent to the car operating panel. The handrails shall be equipped with 1 and 1/2" diameter stainless steel spacers and constructed as follows: 2" x 3/8" flat with a # 4 satin stainless steel finish. The return side shall face the cab wall. The handrail shall be free of any sharp edges.

9. The finished flooring shall consist of 3/8" thick vinyl composition tile. The subfloor shall be constructed of two (2) layers of ¾” Marine plywood and properly leveled before the finished flooring is installed. The tile shall meet the Specifications of Nora Rubber Flooring, Heavy Traffic, with a ten-year warranty. Colors shall be selected by the Owner.

10. The Elevator Contractor shall provide the General Contractor and UNH with a variety of floor samples and rendered elevations.