261030-26081- UNH ELEVATORS MUB CD - 11-5-26.pdf

PDF 2 MB Posted

Attached to
UNH Memorial Union Building Elevator Controller Replacements
Solicitation number
2120271006
Issued by
New Hampshire

About this file

Summary

This file is a comprehensive set of architectural, mechanical, and electrical construction documents for the University of New Hampshire's Memorial Union Building (MUB) Elevator Modernization project located at 83 Main Street, Durham, New Hampshire. The project scope includes replacement and upgrade of elevator equipment and controllers, along with associated architectural modifications, mechanical systems installation, and electrical infrastructure upgrades to support two new 40-horsepower elevator motors and controllers. The work encompasses selective demolition of existing elevator systems, modification of fire-rated wall and floor assemblies, installation of new mechanical ventilation systems (including exhaust fans and ductwork), new fire dampers and firestopping, hollow metal doors and frames, gypsum board finishing, and interior painting. The contract documents reference compliance with the 2024 International Building Code and 2023 National Electrical Code (with New Hampshire amendments), and include detailed specifications for HVAC systems, controls integration with the campus Building Automation System, fire protection systems, and testing and balancing requirements. The project involves work within an occupied facility requiring coordination with building operations and phased construction to minimize disruption to occupants.

The contract requires the contractor to verify existing site conditions prior to bidding, coordinate all work with the general contractor and owner, and comply with all state and local codes including the 2024 State Building Code and applicable fire protection standards. Contractors must provide record as-built drawings, operation and maintenance documentation, testing and commissioning services, and a one-year warranty period from substantial completion. The mechanical work includes installation of a Greenheck ceiling-mounted exhaust fan with ductwork, louvers, and fire dampers in the elevator machine rooms. Electrical work includes replacement of existing disconnect switches with new specialty elevator shunt-trip disconnects rated at 100 amperes, integration with the existing fire alarm system for elevator recall and shutdown functions, and provision of new lighting fixtures and receptacles in the hoistway and pit. The documents establish that all materials and equipment must be installed per manufacturer specifications, all permits are the contractor's responsibility, and all substitutions require written approval from the owner and architect prior to implementation.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E

E EAST

EA EACH

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

ENCL ENCLOSE

EP ELECTRICAL PANEL

EQ EQUAL

EQUIP EQUIPMENT

EXG EXISTING

EXH EXHAUST

EXP EXPOSED OR EXPANSION

EXPJT EXPANSION JOINT

EXT EXTERIOR

F

F FACE

FBO FURNISHED BY OTHERS

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER

CABINET

FF FINISH FACE

FIN FINISHED

FIXT FIXTURE

FL FLOOR

FLEX FLEXIBLE

FLG FLASHING

FLUOR FLUORESCENT

FM FILLED METAL

FND FOUNDATION

FO FACE OF

FOC FACE OF CONCRETE

FOS FACE OF STUD

FPRF FIREPROOFING

FR FRAMING

FRT FIRE RATED PLYWOOD

FT FEET

FTG FOOTING

FURR FURRED

G

GA GAUGE

GALV GALVANIZED

GL GLASS

GLZ GLAZING

GR GRADE

GT GROUT

GYP GYPSUM

GWB GYPSUM WALL BOARD

H

H HIGH

HC HOLLOW CORE

HD HAND OR HEAD

HDBD HARDBOARD

HDR HEADER

HDW HARDWARE

HM HOLLOW METAL

HOR HORIZONTIAL

HP HIGH POINT

HR HOUR

HT HEIGHT

HVAC HEATING/VENTILATING/AIR

CONDITIONING

HWD HARDWOOD

I

ICF INSULATED CONCRETE

FORMS

ID INSIDE DIAMETER

ILO IN LIEU OF

IN INCHES

INCL INCLUDED

INS INSULATED

INT INTERIOR

IR IMPACT RESISTANT

J

JF JOINT FILLER

JMB JAMB

JST JOIST

JT JOINT

K

KIT KITCHEN

KO KNOCKOUT

L

L LENGTH

LAB LABORATORY

LAM LAMINATE

LAV LAVATORY

LBL LABEL

LG LONG

LH LEFT-HAND

LL LIVE LOAD

LO LOW

LOC LOCATION

LT LIGHT

S

S SOUTH OR SILL

SC SOLID CORE

SCH SCHEDULE

SECT SECTION

SH SHELF

SHT SHEET

SHTHG SHEATHING

SHWR SHOWER

SIM SIMILIAR

SL SLID

SLV SLEEVE

SNT SEALANT

SPC SPACER

SPEC SPECIFIED OR SPECIFICATION

SPK SPRINKLER

SQ SQUARE

SS STAINLESS STEEL

SSD SEE STRUCTURAL DRAWINGS

STA STATION

STC SOUND TRANSMISSION

COEFFICIENT

STD STANDARD

STL STEEL

STOR STORAGE

STR STRAIGHT

STRUC STRUCTURAL

SUSP SUSPENDED

SYM SYMMETRICAL

SYS SYSTEM

T

T TREAD

TB TOWEL BAR

T&B TOP AND BOTTOM

T&G TONGUE AND GROOVE

TEL TELEPHONE

TEMP TEMPORARY

TH THRESHOLD

THK THICKNESS

TLT TOILET

TO TOP OF

TOC TOP OF CONCRETE

TOL TOLERANCE

TOS TOP OF STEEL

TOP TOP OF PLATE

TOW TOP OF WALL

TP TOILET PAPER DISPENSER

TR TRANSOM

TS TOP OF SLAB

TYP TYPICAL

U

UC UNDERCOUNTER

UNO UNLESS NOTED OTHERWISE

US UNDERSIDE

V

VAL VALANCE

VARN VARNISH

VB VAPOR BARRIER

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VNL VINYL

VNR VENEER

VP VISION PANEL

W

W WEST

W/ WITH

W/O WITHOUT

W/W WALL TO WALL

WB WOOD BASE

WC WATER CLOSET

WD WOOD

WL WALL

WM WIRE MESH

WP WATERPROOFING

WS WATERSTOP

WWF WELDED WIRE FABRIC

SYMBOLS

3D THREE DIMENSIONAL

& AND

@ AT

+/- PLUS OR MINUS

M

MAX MAXIMUM

MBR MASTER BEDROOM

MC MEDICINE CABINET

MECH MECHANICAL

MEMB MEMBRANE

MET METAL

MFR MANUFACTURER

MIN MINIMUM

MIR MIRROR

MISC MISCELLANEOUS

MO MASONRY OPENING

MR MOISTURE RESISTANT

MT METAL THRESHOLD

MTD MOUNTED

MTG MOUNTING

MTL MATERIAL OR METAL

MULL MULLION

N

N NORTH

NA NOT APPLICABLE

NAT NATURAL

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NR NOT REQUIRED

NRC NOISE REDUCTION

COEFFICIENT

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OFF OFFICE

OH OVERHEAD

OPNG OPENING

OPP OPPOSITE

OPPH OPPOSITE HAND

OZ OUNCE

P

PAR PARALLEL

PBD PARTICLEBOARD

PCC PRE-CAST CONCRETE

PED PEDESTAL

PERIM PERIMETER

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLUMB PLUMBING

PNL PANEL

PNT PAINT/PAINTED

PR PAIR

PRES PRESSURE

PT PRESSURE TREATED

PTN PARTITION

PVC POLYVINYL CHLORIDE

PVG PAVING

PVMT PAVEMENT

PWD PLYWOOD

R

R RISER

RAD RADIUS

RB RESILIENT BASE

RBR RUBBER

RBT RABBET

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REBAR REINFORCING BARS

REC RECESSED

REF REFERENCE

REINF REINFORCED

REQD REQUIRED

RESIL RESILIENT

REV REVISION

RH RIGHT-HAND

RLG RAILING

RM ROOM

RO ROUGH OPEING

RVL REVEAL

RVS REVERSE SIDE

A

AB ANCHOR BOLT

ABV ABOVE

ABR AIR BARRIER

ACOUST ACOUSTICAL

ACT ACOUSTIC CEILING TILE

ADA AMERICAN DISABILITIES ACT

ADH ADHESIVE

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AGG AGGREGATE

AHR ANCHOR, ANCHORAGE

ALT ALTERNATE

ALUM ALUMINUM

ANOD ANODIZED

AP ACCESS PANEL

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASB ASBESTOS

ASPH ASPHALT

AUTO AUTOMATIC

A/V AUDIO VISUAL

B

BD BOARD

BEL BELOW

BET BETWEEN

BEY BEYOND

BIT BITUMINOUS

BKSPL BACKSPLASH

BLDG BUILDING

BLK BLOCK

BLKG BLOCKING

BM BEAM

BOT BOTTOM

BPL BEARING PLATE

BR BEDROOM

BRCG BRACING

BRG BEARING

BRK BRICK

BRZ BRONZE

BS BOTH SIDES

BSMT BASEMENT

BVL BEVELED

BW BOTH WAYS

BYND BEYOND

C

C CHANNEL

CAB CABINET

CAP CAPACITY

CEM CEMENT

CER CERAMIC

CI CAST IRON

CIP CAST IN PLACE

CIPC CAST IN PLACE CONCRETE

CG CORNER GUARD

CHNL CHANNEL

CJ CONTROL JOINT

CK CAULKING

CLG CEILING

CLO CLOSET

CLOS CLOSURE

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CNTR COUNTER

COL COLUMN

COMPR COMPRESSIBLE

CONC CONCRETE

CONST CONSTRUCTION

CONT CONTINUOUS

CPT CARPET

CSK COUNTERSINK

CSMT CASEMENT

CT CERAMIC TILE

CTR CENTER

CTYD COURTYARD

D

DBL DOUBLE

DEMO DEMOLISH

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DISP DISPENSER

DN DOWN

DR DOOR

DS DOWNSPOUT

DWG DRAWING

A101

A101

SIM

Room name

1t

SHEET NO

INTERIOR

ELEVATION NO

SHEET NO

DETAIL NO

SHEET NO

FLOOR ELEVATION

MARKER

DOOR NUMBER

ROOM NUMBER

WINDOW TYPE

WALL TYPE

SECTION DETAIL NO

/1 A101 MATCHLINE REFERENCE

1 Ref

R ef

1 Ref

R ef

A101

SIM

KEYNOTE

EQUIPMENT / FURNITURE TAGA

LIGHT FIXTURE TAGLT-#

A LETTER: ROOF TYPE TAG

NUMBER: FLOOR/CEILING

ASSEMBLY TAG

1i

REVISION CLOUD

REVISION TAG

1. WORK INCLUDED IN THIS CONTRACT SHALL CONFORM TO THE STATE,

NATIONAL, AND OTHER CODES AND ORDINANCES THAT APPLY TO

THIS PROJECT.

2. DO NOT SCALE DRAWINGS OR DIMENSIONS. FOR MISSING

DIMENSIONS OR DIMENSIONAL CONFLICTS, CONTACT THE ARCHITECT

IMMEDIATELY BEFORE CONTINUING WITH THE WORK.

3. BRING ANY DISCREPANCIES IN THESE PLANS TO THE ARCHITECT'S

ATTENTION IMMEDIATELY.

4. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE

PROTECTION DRAWINGS AND SPECIFICATIONS FOR LOCATIONS OF

ALL BLOCK OUTS, INSERTS, OPENINGS, CURBS, BASES, AND PADS

THAT ARE NOT DIMENSIONED OR SHOWN ON ARCHITECTURAL OR

STRUCTURAL DRAWINGS, TYP.

5. STRUCTURAL STEEL, MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE

PROTECTION DRAWINGS AND SPECIFICATIONS SHALL BE PROVIDED

AND ARE THE RESPONSIBILITY OF THEIR RESPECTIVE

SUBCONTRACTORS AND THEIR DESIGN BUILD ENGINEER.

6. DIMENSIONS ARE FROM FACE OF FRAMING TO FACE OF FRAMING

UNLESS NOTED OTHERWISE. DIMENSIONS INDICATED AS "CLEAR"

SHALL MAINTAIN A CLEAR OPENING WIDTH FROM FACE OF FINISHES.

DIMENSIONS TO EXISTING CONSTRUCTION ARE TO FACE OF FINISH

UNLESS NOTED OTHERWISE.

7. WORK FROM GIVEN DIMENSIONS AND LARGE SCALE DETAILS ONLY.

DO NOT SCALE DRAWINGS.

8. ROOM NUMBERS ON PLANS ARE FOR REFERENCE ONLY AND MAY

NOT CORRESPOND TO ACTUAL ROOM NUMBERS AT THE SITE.

9. BEFORE PENETRATING JOISTS, BEAMS, OR OTHER STRUCTURAL

MEMBERS, OBTAIN APPROVAL FROM THE ARCHITECT.

10. THE LOCATION OF DOOR OPENINGS NOT DIMENSIONED SHALL BE 6"

FROM ADJACENT WALL (FACE OF FRAMING TO ROUGH OPENING).

11. PROVIDE BLOCKING BEHIND SURFACE APPLIED FIXTURES, TRIM, GRAB

BARS, SHELVING, CHAIR RAILS, PICTURE RAILS, WOOD TRIM AND

BASE, AND OTHER ACCESSORIES WHEN MOUNTED ON STUD WALLS.

12. WHERE WALLS OR INFILLS ABUT OR INTERSECT EXISTING WALLS,

TAPE AND FINISH JOINTS AT INTERSECTIONS SMOOTH AND

CONTINUOUS. USE METAL TRIM WHERE GYPSUM BOARD INTERSECTS

OTHER MATERIALS.

13. PERMITS ARE THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL

BE COORDINATED WITH PHASING AND WITH THE LOCAL BUILDING

COMMISSIONER.

14. DURING THE ENTIRE CONTRACT PERIOD, MAINTAIN THE

CONSTRUCTION SITE IN A SECURE, NEAT CLEAN, AND SAFE MANNER.

15. DISPOSE OF AND/OR RECYCLE CONSTRUCTION DEBRIS FROM THE

PROJECT SITE AS REQUIRED BY THE CONTRACT AND AS INSTRUCTED

BY THE OWNER. OBTAIN DISPOSAL PERMITS AS REQUIRED.

16. PROVIDE AND COORDINATE TEMPORARY UTILITY CONNECTIONS WITH

THE OWNER.

17. WORK SHALL BE COMPLETED IN COMPLIANCE WITH INDUSTRY

STANDARDS AND PERFORMED IN A WORKMANLIKE PROFESSIONAL

MANNER.

CONTINUOUS

LUMBER

NON-CONTINUOUS

LUMBER

BATT INSULATION

RIGID INSULATION

CONCRETE

MASONRY UNITS

CONCRETE

EARTH

METAL

GYPSUM, PLASTER,

MORTAR, GROUT, ETC.

PLYWOOD

FINISHED WOOD

BRICK

COURSE GRAVEL

STONE

SPRAY FOAM CLOSED

CELL INSULATION

: EXISTING

: PROPOSED

: TO BE REMOVED

DIMENSION FROM FINISH

FACE TO FINISH FACE

DIMENSION FROM FACE OF

STUD TO FACE OF STUD

XX' - XX"

XX' - XX"

FIRE - 1Hr Sep.

FIRE - 2Hr Sep.

Scale:

Project Number:

Date:

Drawn By:

Checked By:

ARCHITECT:

PORTSMOUTH ARCHITECTS

4 MARKET STREET

PORTSMOUTH NH, 03801

PHONE: (603) 430-0274

NOT TO SCALE

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street Portsmouth, New Hampshire

603.430.0274

/3

0/

:4 2:

A

M Z:

\A ct iv e

Pr oj ec t F ile s\

1- U

N H

E

LE

VA

TO

R S\

D w gs \4

-C D

\2

- U

N H

E

LE

VA

TO

R S

M U

B C

D .rv t

T1

26081 10/30/2026

MM

MG

UNIVERSITY OF NEW HAMPSHIRE

83 MAIN STREET

DURHAM, NH 03824

U N

IV

ER

SI

TY

O F

N

EW

H

AM

PS

H

IR

E

M

AI

N

S

TR

EE

T

D U

R H

AM

, N

H

M

EM

O R

IA

L

U N

IO

N

B U

IL

D

IN

G

ABBREVIATIONS,

LEGENDS, GENERAL

NOTES AND LIST OF

DRAWINGS

UNIVERSITY OF NEW

HAMPSHIRE

ABBREVIATIONS

ARCHITECTURAL SYMBOLS

GENERAL NOTESMATERIAL KEY

GRAPHIC KEY

DIMENSION KEY

SHEET LIST

Sheet Number Sheet Name

GENERAL INFORMATION

T1 ABBREVIATIONS, LEGENDS, GENERAL NOTES AND LIST OF

DRAWINGS

T2 GENERAL SPECIFICATIONS

ARCHITECTURAL DRAWINGS

A101 FLOOR PLANS & SECTION

A102 FLOOR PLANS & SECTION

MECHANICAL DRAWINGS

M000 MECHANICAL ABBREVIATIONS, NOTES, & SYMBOLS

M201 MECHANICAL DUCTWORK FLOOR PLAN, DETAILS, AND

SCHEDULES

M400 MECHANICAL SPECIFICATIONS

ELECTRICAL DRAWINGS

E000 ELECTRICAL ABBREVIATIONS, NOTES, AND SYMBOLS

E201 ELECTRICAL

E300 ELECTRICAL SPECIFICATIONS

FIRE PROTECTION

FP000 FP ABBREVIATIONS, NOTES, AND SYMBOLS

FP101 FIRE PROTECTION FLOOR PLAN, DETAILS, AND SCHEDULES

FP300 FIRE PROTECTION SPECIFICATIONS

MECHANICAL AND ELECTRICAL

ENGINEER

CONSULTING ENGINEERING SERVICES, INC.

811 MIDDLE STREET

MIDDLETOWN, CT 06457

Office: (860) 632-1682

FIRE RATING KEY

83 MAIN STREET

DURHAM, NH 03824

MEMORIAL UNION BUILDING - ELEVATOR MODERNIZATION

No. Description Date

010000 – GENERAL CONDITIONS

A. IT IS THE RESPONSIBILITY OF EACH CONTRACTOR, SUB-CONTRACTOR, SUPPLIER AND

BIDDER TO VERIFY THEIR SCOPE OF WORK WITH THE GENERAL CONTRACTOR (GC)

PRIOR TO SUBMITTING A FINAL BID.

B. ALL WORK TO COMPLY WITH THE STATE BUILDING CODE, INTERNATIONAL BUILDING

CODE, AND ALL APPLICABLE LOCAL, STATE AND FEDERAL CODES AND REGULATIONS.

NOTHING IN THESE DRAWINGS OR SPECIFICATIONS IS TO BE CONSIDERED AS

REQUIRING OR PERMITTING WORK THAT IS CONTRADICTORY TO THE CODES AND

REGULATIONS IN FORCE ON THE DATE OF THE CONSTRUCTION CONTRACT. SHOULD

ANY CONDITION DEVELOP WHICH IS NOT COVERED BY THE CONTRACT DOCUMENTS,

WHEREIN THE FINISHED WORK WILL NOT COMPLY WITH APPLICABLE CODES, A

CHANGE ORDER DETAILING AND SPECIFYING THE WORK REQUIRED SHALL BE

SUBMITTED AND APPROVED BEFORE PROCEEDING WITH WORK.

C. PRIOR TO START OF CONSTRUCTION, GC SHALL COORDINATE SCHEDULING OF

MEETING WITH HIS PROJECT PERSONNEL, THE BUILDING OWNER, REP(S), AND

OTHERS, FOR REVIEW OF PROJECT SCOPE, PROCEDURES, DESIGN INTENT,

CONSTRUCTION QUALITY EXPECTED, & FINAL DISCUSSION OF

DRAWINGS/DETAILS/QUESTIONS.

D. DIMENSIONS ON DRAWINGS ARE FINISH FACE TO FINISH FACE OF PARTITIONS,

COLUMNS ETC. OR TO WHERE SHOWN, UNLESS OTHERWISE NOTED. DO NOT SCALE

DRAWINGS.

E. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER GRAPHIC REPRESENTATION. DETAIL

DIMENSIONS TAKE PRECEDENCE OVER PLAN DIMENSIONS.

F. CONTRACTOR IS RESPONSIBLE FOR FIELD MEASURING OF EXISTING CONDITIONS

PRIOR TO START OF WORK AND DURING CONSTRUCTION, AS NECESSARY, TO ASSURE

CONSTRUCTION ADHERENCE TO DRAWINGS. BY ENTERING INTO A CONSTRUCTION

CONTRACT FOR THIS WORK THE CONTRACTOR SHALL INDICATE HIS FAMILIARITY WITH

THE SITE/FIELD CONDITIONS. ALL 'HOLD' DIMENSIONS SHALL BE MONITORED TO

ASSURE CORRECTNESS. ANY DIMENSIONAL MODIFICATIONS/CONFLICTS ARE TO BE

BROUGHT TO ATTENTION OF ARCHITECT FOR REVIEW/APPROVAL.

G. ALL VERTICAL DIMENSIONS SHALL BE TAKEN FROM 'BENCH MARK' OR OTHER SIMILAR

GUIDE ESTABLISHED PRIOR TO START OF CONSTRUCTION, HIGH POINTS, LOW POINTS,

IRREGULARITIES IN FLOOR SLAB, PARTICULARLY, WHICH COULD IN ANY WAY AFFECT

FABRICATION/INSTALLATION WORK OF OTHER TRADES OR VENDORS (EG. CABINET

CONTRACTORS) SHALL BE BROUGHT TO ATTENTION OF ARCHITECT.

H. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL CONSTRUCTION

DEBRIS AND FOR THE RETURN OF ANY BUILDING STANDARD COMPONENTS IF

REQUESTED BY THE OWNER.

I. ALL EXISTING HOLES/CRACKS IN SLAB AND THOSE RESULTING FROM THE

CONSTRUCTION PROCESS SHALL BE FILLED/REPAIRED AND THE SURFACE PATCHED

SMOOTH AND LEVEL WITH ADJACENT FLOOR SURFACE, IN A MANNER ACCEPTABLE TO

THE OWNER.

J. ALL NECESSARY WOOD BLOCKING/GROUNDS, ETC., ARE TO BE SUPPLIED AS

FIREPROOFED ELEMENTS. CONTRACTOR SHALL FULLY COORDINATE SETTING

PLACEMENT OF THESE ELEMENTS AS REQUIRED BY LOCAL CODE/BUILDING OR

SURROUNDING CONSTRUCTION CONDITIONS. GROUNDS/GROUNDS/BLOCKING MAY

NOT BE WHOLLY SHOWN ON DRAWINGS AND GOOD CONSTRUCTION PRACTICE SHALL

GOVERN SAID USE WHERE A QUESTION ARISES. DRYWALL CONTRACTOR TO PAY

PARTICULAR ATTENTION TO ALL LOCATIONS OF DRYWALL PARTITION CONSTRUCTION

THAT ABUT OR RECEIVE MILLWORK OR CABINETWORK CONSTRUCTION. INTERNAL

WOOD BLOCKING SHALL BE SUPPLIED FOR STURDY ANCHORAGE OF MILLWORK AND

AT INTERSECTIONS OF WOOD/GLASS BORROWED LIGHT PARTITIONS AND ADJACENT

DRYWALL CONSTRUCTION.

K. CONTRACTORS, AND VENDORS, ARE TO VERIFY ALL CLEARANCES (CORRIDORS,

STAIRS, ELEVATORS, ETC.) REQUIRED FOR DELIVERIES, PASSAGE OF ALL JOB

MATERIALS/EQUIPMENT.

L. ALL SUBSTITUTIONS, I.E., "EQUALS" MUST BE SUBMITTED TO THE OWNER & ARCHITECT

FOR WRITTEN APPROVAL PRIOR TO SUBSTITUTION BEING MADE.

M. PROVIDE RECORD AS-BUILT DRAWINGS THAT SHALL INCLUDE ALL CHANGES AND

DEVIATIONS FROM THE CONTRACT DOCUMENTS.

N. ALL MATERIALS, FINISHES, AND SYSTEMS INDICATED ON CONTRACT DOCUMENTS ARE

TO BE INSTALLED PER MANUFACTURER'S REQUIREMENTS AND RECOMMENDATIONS.

FOLLOW CONSTRUCTION INDUSTRY STANDARDS.

O. CONTRACTOR AND VENDORS SHALL DETERMINE AVAILABILITY OF FINISH MATERIALS.

ANY DELIVERY SCHEDULE THAT POTENTIALLY MAY CAUSE COORDINATION PROBLEMS

DURING THE FINAL STAGES OF CONSTRUCTION/INSTALLATION SHALL BE BROUGHT TO

THE ATTENTION OF GC, EARLY ON, FOR POSSIBLE REEVALUATION OF MATERIAL

DESIGNATION.

P. FINAL CLEAN - CLEAN ALL SURFACES, EQUIPMENT AND FURNISHINGS AFTER

COMPLETION OF CONSTRUCTION.

Q. PRIOR TO COMPLETION OF THE PROJECT SUBMIT OPERATION AND MAINTENANCE

(O&M) DATA FOR THE PROVIDED EQUIPMENT, PRODUCT, OR SYSTEM, DEFINING THE

IMPORTANCE OF SYSTEM INTERACTIONS, TROUBLESHOOTING, AND LONG-TERM

PREVENTIVE OPERATION AND MAINTENANCE AND WARRANTY INFORMATION.

COMPILE, PREPARE, AND AGGREGATE O&M DATA TO INCLUDE CLARIFYING AND

UPDATING THE ORIGINAL SEQUENCES OF OPERATION TO AS-BUILT CONDITIONS.

ORGANIZE AND PRESENT INFORMATION IN SUFFICIENT DETAIL TO CLEARLY EXPLAIN

O&M REQUIREMENTS AT THE SYSTEM, EQUIPMENT, COMPONENT, AND SUBASSEMBLY

LEVEL.

R. THE CONTRACTOR IS RESPONSIBLE FOR TAKING PHOTOS OF THE CONDITIONS OF

THE PROJECT SITE/SURROUNDING PROPERTIES, EXISTING CONDITIONS TO BE

REMOVED, AND EXISTING CONDITIONS TO REMAIN PRIOR TO THE COMMENCEMENT OF

WORK.

a. THE CONTRACTOR TO MAINTAIN A WEEKLY PHOTOGRAPHIC LOG OF THE

PROGRESS OF WORK UNTIL FINAL COMPLETION.

020000- SELECTIVE DEMO

A. OWNER WILL OCCUPY PORTIONS OF BUILDING IMMEDIATELY ADJACENT TO SELECTIVE

DEMOLITION AREA. CONDUCT SELECTIVE DEMOLITION SO BUILDING OCCUPANTS

OPERATIONS WILL NOT BY DISRUPTED.

B. NOTIFY OWNERS AND ARCHITECT OF DISCREPANCIES BETWEEN EXISTING

CONDITIONS AND DRAWINGS BEFORE PROCEEDING WITH SELECTIVE DEMOLITION.

C. IF MATERIALS ARE SUSPECTED OF CONTAINING HAZARDOUS MATERIALS ARE

UNCOVERED OR DISCOVERED, DO NOT DISTURB. IMMEDIATELY NOTIFY THE OWNER.

OWNER WILL REMOVE HAZARDOUS MATERIALS UNDER A SEPARATE CONTRACT.

D. LOCATE, IDENTIFY, DISCONNECT, AND SEAL OR CAP OFF UTILITY SERVICES AND

MECHANICAL/ELECTRICAL SYSTEMS SERVING AREAS TO BE SELECTIVELY

DEMOLISHED.

E. CONDUCT SELECTIVE DEMOLITION AND DEBRIS-REMOVAL OPERATIONS TO ENSURE

MINIMUM INTERFERENCE WITH FACILITY. DO NOT CLOSE OR OBSTRUCT STREETS,

WALKS, WALKWAYS, VEHICULAR ENTRANCES TO THE SITE OR ADJACENT OCCUPIED

OR USED FACILITIES WITHOUT PERMISSION FROM THE OWNER AND AUTHORITIES

HAVING JURISDICTION.

F. PROVIDE TEMPORARY BARRICADES & PROTECTION TO ENSURE SAFE PASSAGE OF

PEOPLE AROUND DEMOLITION AREA AND TO AND FROM OCCUPIED PORTIONS OF THE

BUILDING.

G. DEMOLITION SHALL BE LIMITED TO NON-STRUCTURAL BUILDING CONSTRUCTION, UNO.

IF STRUCTURAL ELEMENTS ARE DAMAGED OR AFFECTED BY DEMOLITION, PROVIDE

TEMPORARY SHORING AND BRACING AS REQUIRED TO PREVENT MOVEMENT,

SETTLEMENT OR COLLAPSE OF CONSTRUCTION BEING DEMOLISHED OR ADJACENT

FACILITIES TO REMAIN, CEASE OPERATIONS IMMEDIATELY AND NOTIFY THE OWNER &

ARCHITECT.

H. NEATLY CUT OPENINGS AND HOLES PLUMB, SQUARE AND TRUE TO DIMENSIONS

REQUIRED. USE HAND TOOLS OR SMALL POWER TOOLS DESIGNED FOR SAWING OR

GRINDING, NOT HAMMERING AND CHOPPING, TO MINIMIZE DISTURBANCE OF

ADJACENT SURFACES.

I. LOCATE SELECTIVE DEMOLITION EQUIPMENT AND REMOVE DEBRIS AND MATERIALS

SO AS NOT TO IMPOSE EXCESSIVE LOADS ON SUPPORTING WALLS, FLOORS OR

FRAMING.

J. PROTECT CONSTRUCTION INDICATED TO REMAIN AGAINST DAMAGE AND SOILING

DURING SELECTION DEMOLITION.

K. ERECT TEMPORARY DUST PARTITIONS, USE WATER MIST AND OTHER SUITABLE

METHODS TO LIMIT SPREAD OF DUST AND DIRT.

L. TRANSPORT AND DISPOSE OF DEMOLISHED ITEMS AND MATERIALS LEGALLY AND IN

EPA-APPROVED LANDFILL. DO NOT BURN DEMOLISHED MATERIALS.

M. CLEAN ADJACENT STRUCTURES AND IMPROVEMENTS OF DUST, DIRT AND DEBRIS

CAUSED BY SELECTIVE DEMOLITION OPERATIONS. RETURN ADJACENT AREAS TO

CONDITION EXISTING BEFORE SELECTIVE DEMOLITION.

042000 – UNIT MASONRY

A. ALL FACE BRICK IS NOTED ON THE DRAWINGS AND SHALL BE INSTALLED AS

RECOMMENDED BY THE BRICK INSTITUTE OF AMERICA FOR THE APPLICATIONS

SHOWN.

B. EXPOSED MASONRY WORK SHALL BE THOROUGHLY WASHED AND CLEANED WITH

CLEAR WATER AND FIBER BRUSH TO REMOVE MORTAR STAINS, DIRT, ETC.

C. PROVIDE METAL FLASHING AT OPENINGS AS REQUIRED.

D. PROVIDE STEEL ANGLE LINTELS AT NEW OR MODIFIED OPENINGS.

054000 - COLD-FORMED METAL FRAMING

A. STEEL STUDS AND RUNNERS ARE TO BE A MINIMUM OF 20-GA. STEEL AND SHALL

CONFORM TO ASTM C645. BRACE WALL FRAMING TO SUITABLE STRUCTURE.

061000 - ROUGH CARPENTRY

A. WOOD BLOCKING - MIN. 2" NOMINAL DIMENSIONAL LUMBER.

B. PLYWOOD BACKING PANELS - MIN. 3/4" FIRE RETARDANT TREATED.

C. ALL LUMBER MATERIAL EXPOSED TO THE WEATHER OR IN CONTACT WITH CONCRETE

OR MASONRY SHALL BE PRESSURE TREATED.

PROVIDE ALL ROUGH HARDWARE INCLUDING NAILS, SCREWS, FRAMING ANCHORS,

HANGERS, CLIPS AND OTHER RELATED ITEMS TO COMPLETE THE WORK.

078413 – PENETRATION FIRESTOPPING

A. FIRESTOPPING SYSTEMS FOR THROUGH-PENETRATIONS OF FIRE-RESISTANCE-RATED

WALLS, PARTITIONS, FLOORS, FLOOR-CEILING ASSEMBLIES, AND ROOF-CEILING

ASSEMBLIES.

B. PROVIDE TESTED AND LISTED PENETRATION FIRESTOP SYSTEMS COMPLYING WITH

ASTM E814 OR UL 1479.

C. PROVIDE SYSTEMS LISTED FOR THE ACTUAL TYPE, SIZE, AND CONFIGURATION OF

PENETRATING ITEMS AND THE CONSTRUCTION BEING PENETRATED.

D. FIRESTOP SYSTEM SUBMITTALS: IDENTIFY THE TESTED AND LISTED SYSTEM FOR

EACH PENETRATION CONDITION.

E. PROVIDE THIRD PARTY INSPECTIONS FOR ALL FIRE STOPPING ASSEMBLIES AND

LOCATIONS.

081113 - HOLLOW METAL DOORS AND FRAMES

A. MANUFACTURERS

1. CECO DOOR; ASSA ABLOY

2. CURRIES COMPANY; ASSA ABLOY

3. DERONDE PRODUCTS

4. MESKER DOOR INC.

5. PHILIPP MANUFACTURING CO

6. REPUBLIC DOORS AND FRAMES

7. STEELCRAFT; AN ALLEGION BRAND

B. STANDARD STEEL DOORS AND FRAMES

1. CONSTRUCT HOLLOW-METAL DOORS AND FRAMES TO COMPLY WITH

STANDARDS INDICATED FOR MATERIALS, FABRICATION, HARDWARE LOCATIONS,

HARDWARE REINFORCEMENT, TOLERANCES, AND CLEARANCES, AND AS

SPECIFIED.

2. DOORS AND FRAMES: SDI A250.8, LEVEL 2; SDI A250.4, LEVEL B.

3. DOORS: TYPE - AS INDICATED IN THE DOOR AND FRAME SCHEDULE; THICKNESS:

1-3/4 INCHES

A. FACE: UNCOATED OR METALLIC-COATED STEEL SHEET, MINIMUM THICKNESS

OF 0.042 INCH.

B. EDGE CONSTRUCTION: MODEL 1, FULL FLUSH.

C. EDGE BEVEL: PROVIDE MANUFACTURER'S STANDARD BEVELED OR SQUARE

EDGES.

D. CORE: MANUFACTURER'S STANDARD KRAFT-PAPER HONEYCOMB,

POLYSTYRENE, POLYURETHANE, OR VERTICAL STEEL STIFFENER.

E. EXTERIOR DOORS - TOP EDGE CLOSURES: CLOSE TOP EDGES OF DOORS

WITH FLUSH CLOSURES OF SAME MATERIAL AS FACE SHEETS. SEAL JOINTS

AGAINST WATER PENETRATION. BOTTOM EDGES: PROVIDE WEEP-HOLE

OPENINGS IN BOTTOMS OF EXTERIOR DOORS TO PERMIT MOISTURE TO

ESCAPE.

4. FRAMES:

A. MATERIALS: UNCOATED OR METALLIC-COATED STEEL SHEET, MINIMUM

THICKNESS OF 0.053 INCH.

B. SIDELITE AND TRANSOM FRAMES: FABRICATED FROM SAME THICKNESS

MATERIAL AS ADJACENT DOOR FRAME.

C. CONSTRUCTION: WELDED.

5. EXPOSED FINISH: PRIME FACTORY.

6. FIRE LOUVER: METALLIC-COATED STEEL FUSIBLE LINK FIRE RATED LOUVER.

A. UL LISTED, FUSIBLE LINK ACTIVATES AT 135˚F

B. FREE FLOW AREA: 50% FREE MINIMUM.

087100 - DOOR HARDWARE

A. SEE DOOR SCHEDULE FOR HARDWARE SETS

B. COORDINATE LOCK CORES AND KEYING WITH THE OWNER AND ARCHITECT. KEYING

TO MATCH EXISTING MASTER KEY SYSTEM.

C. SUBMITTALS - PROVIDE MANUFACTURER'S PRODUCT DATA, DOOR SCHEDULE, AND

KEYING SCHEDULE.

D. STANDARD WARRANTY PERIOD: ONE YEAR FROM DATE OF SUBSTANTIAL

COMPLETION, UNLESS OTHERWISE INDICATED. SPECIAL WARRANTY PERIODS - SEVEN

YEARS FOR HEAVY DUTY CYLINDRICAL (BORED) LOCKS AND LATCHES, FIVE YEARS

FOR EXIT HARDWARE, TWENTY FIVE YEARS FOR MANUAL SURFACE DOOR CLOSER

BODIES, AND TWO YEARS FOR ELECTROMECHANICAL DOOR HARDWARE.

E. SUBSTITUTIONS: REQUESTS FOR SUBSTITUTION AND PRODUCT APPROVAL FOR

INCLUSIVE MECHANICAL AND ELECTROMECHANICAL DOOR HARDWARE IN

COMPLIANCE WITH THE SPECIFICATIONS MUST BE SUBMITTED IN WRITING. APPROVAL

OF REQUESTS IS AT THE DISCRETION OF THE ARCHITECT, OWNER, AND THEIR

DESIGNATED CONSULTANTS.

092900 - GYPSUM BOARD

A. FIRE-RESISTANCE-RATED ASSEMBLIES: FOR FIRE-RESISTANCE-RATED ASSEMBLIES,

PROVIDE MATERIALS AND CONSTRUCTION IDENTICAL TO THOSE TESTED IN ASSEMBLY

INDICATED ACCORDING TO ASTM E 119 BY AN INDEPENDENT TESTING AGENCY.

B. 5/8" TYPE X, TAPERED EDGES THROUGHOUT UNLESS NOTED OTHERWISE.

C. "WET" AREAS:

1. PROVIDE MOLD-RESISTANT GYPSUM BOARD WITH MOISTURE- AND MOLD-

RESISTANT CORE AND PAPER SURFACES.

D. ALL EXTERIOR CORNERS SHALL RECEIVE GALVANIZED OR ALUMINUM-COATED STEEL

SHEET OR ROLLED ZINC CORNER BEAD.

E. TREAT GYPSUM BOARD JOINTS, INTERIOR ANGLES, EDGE TRIM, CONTROL JOINTS,

PENETRATIONS, FASTENER HEADS, SURFACE DEFECTS, AND ELSEWHERE AS

REQUIRED TO PREPARE GYPSUM BOARD SURFACES FOR DECORATION. PROMPTLY

REMOVE RESIDUAL JOINT COMPOUND FROM ADJACENT SURFACES. PREFILL OPEN

JOINTS AND DAMAGED SURFACE AREAS. APPLY JOINT TAPE OVER GYPSUM BOARD

JOINTS, EXCEPT FOR TRIM PRODUCTS SPECIFICALLY INDICATED AS NOT INTENDED TO

RECEIVE TAPE.

F. GYPSUM BOARD FINISH LEVELS: FINISH PANELS TO LEVELS INDICATED BELOW AND

ACCORDING TO ASTM C 840:

1. LEVEL 1: CEILING PLENUM AREAS, CONCEALED AREAS, AND WHERE INDICATED.

2. LEVEL 2: PANELS THAT ARE SUBSTRATE FOR TILE.

3. LEVEL 4: AT PANEL SURFACES THAT WILL BE EXPOSED TO VIEW UNLESS

OTHERWISE INDICATED.

G. SOUND ATTENUATION BLANKETS (ASTM C665) SHALL BE INSTALLED WHERE

INDICATED. BLANKETS SHALL CONFORM WITH FIRE RESISTANCE RATING REQUIRED

FOR WALL TYPE AND SHALL BE MANUFACTURERS STANDARD MATERIAL UTILIZING

MINERAL FIBERS.

099123 - INTERIOR PAINTING

A. PAINT FOR WALL FINISHES SHALL BE PROVIDED AS A THREE (3) COAT EGGSHELL

LATEX ENAMEL PAINT INSTALLATION, ONE (1) PRIME AND TWO (2) FINISH COATS,

COLORS AS SPECIFIED.

B. PAINT FOR METAL ELEMENTS, DOOR AND FRAMES AND WINDOW FRAMES SHALL HAVE

A THREE COAT SEMI-GLOSS LATEX ENAMEL FINISH. ONE (1) PRIME AND TWO (2) FINISH

COATS, COLORS AS SPECIFIED.

C. PAINTING CONTRACTOR SHALL ASSURE THAT NO ELECTRIC RECEPTACLE OR

TELECOM. OUTLET COVERPLATES HAVE BEEN INSTALLED PRIOR TO CONTEMPLATION

OF APPLICATION TO ANY WALL FINISH MATERIALS. ANY SUCH COVERPLATED OR

SURFACE HARDWARE, ETC., IN PLACE, SHALL BE REMOVED PRIOR TO WALL FINISH

APPLICATION.

D. UPON COMPLETION OF FINISH PHASE OF JOB, PAINTING CONTRACTOR SHALL

REMOVE ALL PAINT, WALLCOVERING PASTE ETC. FROM WHERE IT HAS SPILLED,

SPLASHED OR SPATTERED.

14200 – HYDRAULIC ELEVATORS.

A. WORK TO REPLACE AND UPGRADE ELEVATOR EQUIPMENT AND ELEVATOR CABS BY

OTHERS. COORDINATE WITH OWNER’S ELEVATOR SCOPE OF WORK.

Scale:

Project Number:

Date:

Drawn By:

Checked By:

NOT TO SCALE

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street Portsmouth, New Hampshire

603.430.0274

/3

0/

:4 2:

A

M Z:

\A ct iv e

Pr oj ec t F ile s\

1- U

N H

E

LE

VA

TO

R S\

D w gs \4

-C D

\2

- U

N H

E

LE

VA

TO

R S

M U

B C

D .rv t

T2

26081 10/30/2026

MM

MG

U N

IV

ER

SI

TY

O F

N

EW

H

AM

PS

H

IR

E

M

AI

N

S

TR

EE

T

D U

R H

AM

, N

H

M

EM

O R

IA

L

U N

IO

N

B U

IL

D

IN

G

GENERAL

SPECIFICATIONS

UNIVERSITY OF NEW

HAMPSHIRE

GENERAL SPECIFICATIONS

STATE BUILDING CODE:

2024 INTERNATIONAL BUILDING

CODE (2024 IBC) WITH NEW

HAMPSHIRE AMENDMENTS

LIFE SAFETY AND FIRE CODE:

2024 NATIONAL FIRE PROTECTION

AGENCY 101 (NFPA 101) AMENDED

BY SAF-FMO300

2024 FIRE CODE NFPA 1 AMENDED

BY SAF-FMO300

STATE ENERGY CODE:

2018 INTERNATIONAL ENERGY

CONSERVATION CODE

(2018 IECC) WITH NEW

HAMPSHIRE AMENDMENTS

STATE MECHANICAL CODE:

2024 INTERNATIONAL

MECHANICAL CODE (2021 IMC)

WITH NEW HAMPSHIRE

AMENDMENTS

STATE ELECTRICAL CODE:

2023 NATIONAL ELECTRICAL

CODE (NEC 2023 NFPA70) WITH

NEW HAMPSHIRE AMENDMENTS

STATE PLUMBING CODE:

2024 INTERNATIONAL PLUMBING

CODE (2024 IPC) WITH NEW

HAMPSHIRE AMENDMENTS

STATE ACCESSIBILITY CODE:

THE ARCHITECTURAL BARRIER

FREE DESIGN CODE FOR THE

STATE OF NEW HAMPSHIRE

A117.1, 2017

EXISTING BUILDING CODE:

2024 INTERNATIONAL EXISTING

BUILDING CODE (2024 IEBC) WITH

NEW HAMPSHIRE AMENDMENTS

APPLICABLE CODES:

D F

DMUB-AP-CR115

DMUB-AP-CR108

DMUB-AP-133AA-1

DMUB-AP-A140-1

DMUB-AP-145-1

DMUB-AP-154-1

DMUB-AP-160-1

DMUB-AP-164-1

DMUM-AP-120-1

DMUM-AP-119-1

EQ000370

NHE 3475

OUTDOOR 154A

133BB

A140A

133AA133AB

RAMP DN

RAMP DN

RAMP DN

UP

DN

DN

DN

UP

UP

UP

DN

DN

UP

DN

DN

UP

A101

8' - 8 3/4"

8'

0"

/4

7' - 4"

A101

ELEVATOR

HOISTWAY

100ESC

MECH. ROOM

130G

100LBC

100CRC

100CRD

A101

5 EBU

EXISTING LIGHT FIXTURE

EXISTING CONCRETE DECK

MECH. ROOM

130G

ELEVATOR

HOISTWAY

100ESC

100LBC

100CRC 100CRD

ELEV. ROOF

107'-10"

LOW ROOF

104'-6"

LEVEL 3

94'-0"

LEVEL 2

82'-0"

LEVEL 1

70'-0"

PIT

66'-0"

4'

0"

3'

4"

ELEVATOR HOISTWAY

Scale:

Project Number:

Date:

Drawn By:

Checked By:

AS INDICATED

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street Portsmouth, New Hampshire

603.430.0274

/3

0/

:4 2:

A

M Z:

\A ct iv e

Pr oj ec t F ile s\

1- U

N H

E

LE

VA

TO

R S\

D w gs \4

-C D

\2

- U

N H

E

LE

VA

TO

R S

M U

B C

D .rv t

A101

26081 10/30/2026

MM

MG/RD

U N

IV

ER

SI

TY

O F

N

EW

H

AM

PS

H

IR

E

M

AI

N

S

TR

EE

T

D U

R H

AM

, N

H

M

EM

O R

IA

L

U N

IO

N

B U

IL

D

IN

G

FLOOR PLANS & SECTION

UNIVERSITY OF NEW

HAMPSHIRE

PLAN

NORTH

1/4" = 1' - 0" 0 5' 10' 15'1'

GENERAL NOTES

GRAPHIC SCALE(S)

KEY PLAN

KEYNOTES#

© 2026 Portsmouth Architects

KEYPLAN MUB FIRST FLOOR

1/4" = 1'-0"1 EAST ELEVATOR LEVEL 1 MUB

1/4" = 1'-0"3 EAST ELEVATOR LEVEL 1 MUB RCP

1/4" = 1'-0"2 EAST ELEVATOR LEVEL 1 MUB SECTION

1. REMOVE EXISTING DOOR, FRAME, AND HARDWARE.

2. PROVIDE HOLLOW METAL DOOR AND FRAME AND DOOR HARDWARE.

PROVIDE METAL VENTILATION LOUVER AND FIRE DAMPER.

3. CUT AND PATCH EXISTING GWB CEILING TO ACCOMMODATE MECHANICAL

EXHAUST FAN.

4. REMOVE, SALVAGE AND REINSTALL EXISTING ACT CEILING SYSTEM TO

ALLOW FOR REPLACEMENT OF MECHANICAL DUCTWORK. REPLACE AND

MATCH EXISTING CEILING TILES DAMAGED DURING CONSTRUCTION.

5. PROVIDE FIRE STOPPING ASSEMBLY AT EXISTING METAL CONDUIT

PENETRATIONS.

6. MODIFY EXISTING MASONRY WALL TO ACCOMMODATE MECHANICAL

LOUVER/DUCT. COORDINATE OPENING SIZE WITH MECHANICAL DRAWINGS.

1. WORK TO REPLACE AND UPGRADE ELEVATOR EQUIPMENT AND CABS BY

OTHERS. COORDINATE WITH OWNER’S ELEVATOR SCOPE OF WORK.

2. PROVIDE FIRE STOPPING AT PENETRATIONS IN FIRE RATED ASSEMBLIES.

3. EXISTING RATED ASSEMBLIES SHALL BE MAINTAINED. ANY MODIFICATIONS

TO ASSEMBLIES WILL NEED TO MAINTAIN FIRE-RESISTANCE RATING.

DMUB-AP-221-3

DMUB-AP-221-4

DMUB-AP-221-1

DMUB-AP-221-5

DMUB-AP-CR223

DMUB-AP-203-1

DMUB-AP-223-2DMUB-AP-223-1

DMUB-AP-225-3

DMUB-AP-224-1

DMUB-AP-225-1

DMUB-AP-225-2

DMUB-AP-231-1

DMUB-AP-240-1

DMUB-AP-240-2

DMUB-AP-CR213

DMUB-AP-218-1

DMUB-AP-213-1

WALK-IN COOLER

LADDER

ROOF

OUTDOOR PATIO

OUTDOOR

PATIO

DNUP

DN

UP

DN

DN

DN

DN

DN

DN

UP

UP

A102

5'

0"

7' - 2"

7'

4"

A102

ELEVATOR

HOISTWAY

200ESA

MECH. ROOM

6 6

CORRIDOR

A102 6

A102

A102

EXISTING GWB CEILING

EXISTING ACCESS PANEL

EXISTING ACT

6 64 3

EXIST. ACT

ELEVATOR

HOISTWAY

200ESA

MECH. ROOM

/2

4'

0"

BASEMENT LEVEL

58-5 5/8"

LEVEL 1

70'-0 +/-

LEVEL 2

82'-0" +/-

LEVEL 3

94'-0" +/-

SUMP PIT LEVEL

54-5 5/8"

REAR

OPENING

ELEV.

DOOR

BEHIND

ELEVATOR

HOISTWAY

EXIST. GWB CEILING

EXIST. HOISTWAY VENT

TYPE A:

1-1/2 HR FIRE

RATED DOOR

WITH 18"X18"

LOUVER W/ F.D.

DOOR TYPES

0' - 2"

CMU WALL

SEALANT

WELDED H.M. DOOR FRAME,

PAINTED, SEE DOOR

SCHEDULE FOR RATING

V.

I.F

HARDWARE SET 1

- 3 HINGES

- 1 LOCKSET, FUNCTION: STORAGE, KNURLED LEVER

- 1 CLOSER

- 1 DOOR STOP

DOOR NOTES AND DOOR HARDWARE

1.

2.

3.

4.

5.

A.

B.

6.

7.

8.

9.

10.

11.

DOOR HARDWARE NOTES:

HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERABLE PARTS

ON DOORS AND GATES SHALL HAVE A SHAPE THAT IS EASY TO

GRASP WITH ONE HAND AND DOES NOT REQUIRE TIGHT

GRASPING, PINCHING OR TWISTING OF THE WRIST TO OPERATE.

THE BOTTOM MOST PORTION OF OPERABLE PARTS O F ALL DOOR

HARDWARE SHALL BE MOUNTED 34" ABOVE THE FINISHED FLOOR

AND THE UPPER MOST PORTION OF OPERABLE PARTS SHALL BE

MOUNTED BELOW 48" ABOVE THE FINISHED FLOOR.

HARDWARE OPERATION BY A FORWARD, PUSHING OR PULLING

MOTION: 15 POUNDS MAXIMUM.

HARDWARE OPERATION BY A ROTATIONAL MOTION: 28 INCH-

POUNDS MAXIMUM.

ALL SELF CLOSING DEVICES:

DOOR AND GATE CLOSERS SHALL BE ADJUSTED SO THAT

FROM AN OPEN POSITION OF 90 DEGREES, THE TIME

REQUIRED TO MOVE THE DOOR OR GATE TO AN OPEN

POSITION OF 12 DEGREES SHALL BE 5 SECONDS MINIMUM.

DOOR AND GATE SPRING HINGES SHALL BE ADJUSTED SO

THAT FROM AN OPEN POSITION OF 70 DEGREES, THE DOOR

OR GATE SHALL MOVE TO THE CLOSED POSITION IN 1.5

SECONDS MINIMUM.

DOOR SURFACES WITHIN 10 INCHES OF THE FINISHED FLOOR,

SHALL BE SMOOTH SURFACES ON THE PUSH SIDE EXTENDING THE

FULL WIDTH OF THE DOOR. PARTS CREATING JOINTS IN THE

SURFACE SHALL BE WITHIN 1/16" OF THE SAME PLANE.

ALL DOOR HARDWARE FINISH TO MATCH EXISTING.

PROVIDE MIN. 3 HINGES PER DOOR.

HARDWARE DESIGN SHALL BE AS APPROVED BY THE OWNER AND

THE ARCHITECT. PROVIDE ALL HARDWARE NECESSARY FOR THE

PROPER OPERATION OF ALL WORK ON THIS PROJECT. REFER TO

THE DRAWINGS FOR HARDWARE FUNCTIONS. CONFIRM DOOR

KEYING AND SECURITY WITH THE OWNER.

REFER TO SCHEDULE FOR FIRE RATINGS, TYP.

MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED THE

FOLLOWING:

INTERIOR DOORS: 5 POUNDS.

EXTERIOR DOORS: 8.5 POUNDS.

FIRE DOORS: 15 POUNDS.

EXISTING BRICK VENEER,

WALL CONSTRUCTION TO BE

VERIFIED IN THE FIELD

PROVIDE ENLARGED

OPENING FOR MECH

LOUVER, COOR SIZE WITH

MECH DWGS

MTL THROUGH WALL

FLASHING WITH DRIP EDGE,

EXTEND UP WALL BACKUP

8", SEAL TOP EDGE

GLAV STEEL ANGLE

LINTEL, GC TO ENGINEER

SIZE

VI

F

MTL PAN FLASHING WITH

DRIP EDGE, SET IN SEALANT

BED

WEEP VENT AT 24" OC MAX

EXISTING CMU, WALL

CONSTRUCTION TO BE

VERIFIED IN THE FIELD

PROVIDE ENLARGED

OPENING FOR MECH DUCT

AND FIRE DAMPER, COOR

SIZE WITH MECH DWGS

STEEL ANGLE LINTEL, GC

TO ENGINEER SIZE

VI

F

Scale:

Project Number:

Date:

Drawn By:

Checked By:

AS INDICATED

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street Portsmouth, New Hampshire

603.430.0274

/5

/2

:3 2:

P

M Z:

\A ct iv e

Pr oj ec t F ile s\

1- U

N H

E

LE

VA

TO

R S\

D w gs \4

-C D

\2

- U

N H

E

LE

VA

TO

R S

M U

B C

D .rv t

A102

26081 10/30/2026

MM

MG/RD

U N

IV

ER

SI

TY

O F

N

EW

H

AM

PS

H

IR

E

M

AI

N

S

TR

EE

T

D U

R H

AM

, N

H

M

EM

O R

IA

L

U N

IO

N

B U

IL

D

IN

G

FLOOR PLANS & SECTION

UNIVERSITY OF NEW

HAMPSHIRE

PLAN

NORTH

1/4" = 1' - 0" 0 5' 10' 15'1'

GENERAL NOTES

GRAPHIC SCALE(S)

KEY PLAN

KEYNOTES#

© 2026 Portsmouth Architects

KEYPLAN MUB SECOND FLOOR

1/4" = 1'-0"

1 WEST ELEVATOR LEVEL 2 MUB

1/4" = 1'-0"

2 WEST ELEVATOR LEVEL 2 MUB RCP

1/4" = 1'-0"

3 WEST ELEVATOR LEVEL 2 MUB SECTION

1 1/2" = 1'-0"

4 INTERIOR DOOR DETAILS

DOOR SCHEDULE

Mark

Size Door Frame Fire

Rating Door

Hardware CommentsHeight Width Type Mark Material Finish Frame

Material Frame Finish

235 7' - 0" 3' - 6" A HM PNT HM PNT 1.5 HR 1 PAINT TO MATCH EXISTING

1.

2.

3.

4.

5.

6.

REMOVE EXISTING DOOR, FRAME, AND HARDWARE.

PROVIDE HOLLOW METAL DOOR AND FRAME AND DOOR HARDWARE.

PROVIDE METAL VENTILATION LOUVER AND FIRE DAMPER.

CUT AND PATCH EXISTING GWB CEILING TO ACCOMMODATE MECHANICAL

EXHAUST FAN.

REMOVE, SALVAGE AND REINSTALL EXISTING ACT CEILING SYSTEM TO

ALLOW FOR REPLACEMENT OF MECHANICAL DUCTWORK. REPLACE AND

MATCH EXISTING CEILING TILES DAMAGED DURING CONSTRUCTION.

PROVIDE FIRE STOPPING ASSEMBLY AT EXISTING METAL CONDUIT

PENETRATIONS.

MODIFY EXISTING MASONRY WALL TO ACCOMMODATE MECHANICAL

LOUVER/DUCT. COORDINATE OPENING SIZE WITH MECHANICAL DRAWINGS.

PROVIDE STEEL LINTEL(S).

1.

2.

3.

WORK TO REPLACE AND UPGRADE ELEVATOR EQUIPMENT AND CABS BY

OTHERS. COORDINATE WITH OWNER ’S ELEVATOR SCOPE OF WORK.

PROVIDE FIRE STOPPING AT PENETRATIONS IN FIRE RATED ASSEMBLIES.

EXISTING RATED ASSEMBLIES SHALL BE MAINTAINED. ANY MODIFICATIONS

TO ASSEMBLIES WILL NEED TO MAINTAIN FIRE-RESISTANCE RATING.

No. Description Date

1 1/2" = 1'-0"

5 LINTEL DETAIL - BRICK

1 1/2" = 1'-0"

6 LINTEL DETAIL - CMU

Mark Gianniny NH Arch Stamp

DUCTWORK LEGEND

SYMBOL DESCRIPTION

RECTANGULAR DUCTWORK

ACOUSTICALLY LINED DUCTWORK

RECTANGULAR SUPPLY DUCTWORK TOWARDS (UP IN PLAN)

RECTANGULAR SUPPLY DUCTWORK AWAY (DOWN IN PLAN)

RECTANGULAR RETURN DUCTWORK TOWARDS (UP IN PLAN)

RECTANGULAR RETURN DUCTWORK AWAY (DOWN IN PLAN)

RECTANGULAR EXHAUST DUCTWORK TOWARDS (UP IN PLAN)

RECTANGULAR EXHAUST DUCTWORK AWAY (DOWN IN PLAN)

FLEXIBLE DUCT

12x6

ROUND DUCTWORK12"ø

OVAL DUCTWORK12/6

ROUND SUPPLY DUCTWORK TOWARDS (UP IN PLAN)

ROUND SUPPLY DUCTWORK AWAY (DOWN IN PLAN)

ROUND RETURN DUCTWORK TOWARDS (UP IN PLAN)

ROUND RETURN DUCTWORK AWAY (DOWN IN PLAN)

ROUND EXHAUST DUCTWORK TOWARDS (UP IN PLAN)

ROUND EXHAUST DUCTWORK AWAY (DOWN IN PLAN)

DUCTWORK SHOWN SINGLE LINE

CAPPED DUCT

OPEN ENDED DUCT WITH WIRE MESH SCREEN

DUCT TRANSITION

ACOUSTICALLY LINED DUCTWORK (SINGLE LINE)

12x6

AIR DEVICE LEGEND

SYMBOL DESCRIPTION

SIDEWALL SUPPLY GRILLE

SIDEWALL RETURN OR EXHAUST GRILLE OR REGISTER

DAMPER LEGEND

SYMBOL DESCRIPTION

BACKDRAFT DAMPER

FIRE DAMPER W/ACCESS DOOR

SMOKE DAMPER W/SMOKE DETECTOR AND ACCESS DOOR

COMBINATION FIRE/SMOKE DAMPER W/SMOKE DETECTOR

AND ACCESS DOOR

MOTORIZED CONTROL DAMPER W/ACCESS DOOR

MANUAL VOLUME DAMPER

BD

FD

MD

RADIATION DAMPERRD

AUTOMATIC VOLUME DAMPER (PRESSURE INDEPENDENT)AVD

SD

FSD

TAG SYMBOLS

DIFFUSER

TAG

6"

A

NECK SIZE /

LINEAR LENGTH

AIRFLOW (CFM)

UNIT TYPE

EQUIPMENT TAG-#

T# TYPICAL OF #

AIR SYSTEM GENERAL NOTES

1. REFER TO SPECIFICATIONS FOR DUCTWORK CONSTRUCTION CLASSES, SEAL, AND

LEAKAGE CLASSES.

2. EXTERIOR LOUVERS ARE INDICATED FOR LOCATION ONLY. DETAILED DESCRIPTIONS ARE

PROVIDED IN ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.

3. PROVIDE UL FIRE DAMPERS OR SMOKE/FIRE DAMPERS AND ASSOCIATED ACCESS PANELS

WHERE SHOWN ON DRAWINGS IN COMPLIANCE WITH NFPA 90A. FOR DUCTS THAT

PENETRATE FIRE-RATED WALLS, AND FLOORS.

4. REFER TO REFLECTED CEILING PLANS FOR LOCATIONS OF AIR TERMINAL DEVICES.

5. INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. INCREASE SHEETMETAL SIZE

FOR LINER IF APPLICABLE.

6. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZE ARE NOMINAL.

ROUND RUN OUTS TO DIFFUSERS SHALL BE THE SAME NOMINAL SIZE AS THE SCHEDULED

NECK SIZE, UNLESS NOTED AS LARGER. DUCT TRANSITIONS SHALL BE PROVIDED AS

NECESSARY AT INLET TO DIFFUSER.

7. PROVIDE FLEXIBLE CONNECTIONS ON DUCTS CONNECTING TO FANS AND AIR HANDLING

UNITS.

8. THE INSIDE OF DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE PAINTED

FLAT BLACK.

9. OPEN ENDED DUCTS SHALL BE PROVIDED WITH A 1/4"x1/4" MESH ALUMINUM OR

GALVANIZED SCREEN (80% FREE AREA MINIMUM).

10. ELBOWS IN DUCT SYSTEMS SHALL BE FULL RADIUS (CENTERLINE RADIUS = 1.5 DUCT

WIDTH) WHERE SPACE PERMITS. WHERE LIMITED CLEARANCE OCCURS, PROVIDE SHORT

RADIUS ELBOW WITH FULL LENGTH SPLITTER VANES PER SMACNA OR MITERED ELBOW

WITH TURNING VANES PER SMACNA.

11. NOT ALL MANUAL DAMPERS ARE SHOWN ON THE DRAWINGS. PROVIDE MANUAL

ADJUSTABLE DAMPERS ON EACH LOW-PRESSURE SUPPLY, RETURN, AND EXHAUST DUCT

TAKE-OFF, AND AT TAKE-OFFS TO REGISTERS, GRILLES, DIFFUSERS, AND OED; AS

REQUIRED FOR PROPER BALANCE OF SYSTEM. PROVIDE CABLE-OPERATED DAMPERS

WHERE MANUAL DAMPER IS INACCESSIBLE. EACH DAMPER IN DUCTS 12" AND MORE SHALL

BE OPPOSED BLADE TYPE.

12. WHERE DUCTS PENETRATE WALLS WITH SOUND ISOLATION PERFORMANCE RATINGS,

PROVIDE DUCT SLEEVE SIZED TO PROVIDE 1/4" GAP BETWEEN THE SLEEVE AND DUCT. FILL

THE GAP WITH FIBEROUS MATERIAL AND SEAL AIRTIGHT WITH NON-HARDENING ACOUSTIC

SEALANT

13. HVAC EQUIPMENT AND DUCTS SHALL NOT BE USED FOR TEMPORARY HEATING, COOLING

OR VENTILATION.

14. PROVIDE FLEXIBLE CONNECTIONS AT ALL LOCATIONS WHERE DUCTS CROSS EXPANSION

OR SEISMIC JOINTS. COORDINATE WITH ARCHITECTURAL DRAWINGS.

DEMOLITION NOTES

DEMOLITION NOTES

1. SITE VISIT: THIS PROJECT INVOLVES CONSTRUCTION INSIDE AN EXISTING STRUCTURE.

BEFORE SUBMITTING BID, VISIT AND CAREFULLY EXAMINE SITE TO IDENTIFY EXISTING

CONDITIONS AND DIFFICULTIES THAT WILL AFFECT WORK OF THIS SECTION. NO EXTRA

PAYMENT WILL BE ALLOWED FOR ADDITIONAL WORK CAUSED BY UNFAMILIARITY WITH

SITE CONDITIONS THAT ARE VISIBLE OR READILY CONSTRUED BY EXPERIENCED

OBSERVER.

2. PREPARATORY WORK: BEFORE STARTING WORK IN A PARTICULAR AREA OF THE

PROJECT, VISIT SITE AND EXAMINE CONDITIONS UNDER WHICH WORK MUST BE

PERFORMED INCLUDING PREPARATORY WORK DONE UNDER OTHER SECTIONS OR

CONTRACTS BY OWNER. REPORT CONDITIONS THAT MIGHT AFFECT WORK ADVERSELY IN

WRITING TO ARCHITECT AND OWNER. DO NOT PROCEED WITH WORK UNTIL DEFECTS

HAVE BEEN CORRECTED AND CONDITIONS ARE SATISFACTORY. COMMENCEMENT OF

WORK SHALL BE CONSTRUED AS COMPLETE ACCEPTANCE OF EXISTING CONDITIONS AND

PREPARATORY WORK.

3. PHASING: DEMOLITION WORK SHALL COMPLY WITH THE PHASING REQUIREMENTS OF THE

PROJECT AND BE COORDINATED WITH THE OWNER, ARCHITECT, CM AND ENGINEER. NO

REMOVALS SHALL BE IMPLEMENTED WITHOUT A THOROUGH UNDERSTANDING OF THE

PHASING REQUIREMENTS.

4. ABANDONING OF DUCTWORK, PIPING OR EQUIPMENT IN PLACE WITHIN SCOPE AREA IS

PROHIBITED.

5. PROVIDE 2 WEEKS NOTICE TO OWNER FOR SHUT DOWN OF ANY SERVICES AND/OR

SYSTEMS.

6. COORDINATE EXISTING EQUIPMENT AND MATERIALS THAT SHALL REMAIN THE PROPERTY

OF THE OWNER. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO BE RETURNED TO THE

OWNER, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED

FROM SITE AND LEGALLY DISPOSED OF. STORAGE OR SALE OF ITEMS ON THE PROJECT

SITE IS PROHIBITED.

7. PROTECTION: ENSURE THE SAFE PASSAGE OF PERSONS IN AND AROUND THE BUILDING

DURING DEMOLITION. PREVENT INJURY TO PERSONS AND DAMAGE TO PROPERTY.

PROVIDE ADEQUATE SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY

REPAIR DAMAGED PROPERTY TO THE CONDITION BEFORE BEING DAMAGED. TAKE

EFFECTIVE MEASURES TO PREVENT WINDBLOWN DUST.

8. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING REMOVAL OR RELOCATION.

KEEP UTILITIES IN SERVICE AND PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES

SERVING OCCUPIED AREAS WITHOUT FIRST OBTAINING PERMISSION FROM THE OWNER IN

WRITING. PROVIDE TEMPORARY SERVICES AS REQUIRED.

9. INFORMATION CONTAINED ON THESE DRAWINGS WAS OBTAINED FROM ARCHIVED

DRAWINGS AND SITE VISITS. DRAWINGS ARE DIAGRAMMATIC ONLY AND REFLECT OVERALL

SYSTEM REMOVAL. NOT EVERY ITEM OR COMPONENT OF A SYSTEM IS SHOWN. PROVIDE

COMPLETE REMOVAL OF ASSOCIATED ANCILLARY PIPES, HANGERS, VALVES AND

ACCESSORIES SERVING SYSTEM SHOWN.

10. DEMOLITION WORK SHALL COMPLY WITH OSHA, EPA AND APPLICABLE STATE AND LOCAL

CODES. COMPLY WITH HAULING AND DISPOSAL REGULATIONS.

11. REFER TO SPECIFICATIONS FOR ADDITIONAL DEMOLITION REQUIREMENTS AND

PROCEDURES.

FIRESTOPPING GENERAL NOTES

1. PROVIDE FIRE STOPPING AND SMOKE BARRIER SEALING OF PENETRATIONS THROUGH FIRE

OR SMOKE WALLS, BARRIERS AND PARTITIONS AS REQUIRED TO MAINTAIN RATING. REFER

TO ARCHITECTURAL FLOOR PLANS AND CODE SHEETS FOR WALL RATINGS. REFER TO

SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

GENERAL NOTES

1. GENERAL NOTES, SYMBOLS, AND DETAILS ARE APPLICABLE TO DRAWINGS WITHIN DIVISION 23.

2. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL

COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED, AND AS REQUIRED BY CODES.

3. DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO INDICATE CAPACITY, SIZE,

APPROXIMATE LOCATION AND GENERAL ARRANGEMENT. COORDINATE LOCATIONS OF

SYSTEMS AND COMPONENTS.

4. COORDINATE ROOF AND WALL PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH

FLASHING REQUIREMENTS. COORDINATE SLAB PENETRATIONS WITH WORK OF OTHER

SECTIONS.

5. RUN DUCTS AND PIPING CONCEALED UNLESS SPECIFIED OTHERWISE NOTED.

6. INSTALL SENSORS (THERMOSTATS) AT LOCATIONS SHOWN ON PLANS OR AS DIRECTED BY

ARCHITECT. MOUNTING HEIGHT AFF SHALL COMPLY WITH ADA AND SHALL BE MOUNTED

LEVEL WITH ADJACENT SWITCHES (IE LIGHT SWITCHES).

7. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS AND WITH ALL

TRADES INVOLVED. PROVIDE OFFSETS IN PIPING AND DUCTS (INCLUDING DIVIDED DUCTS)

AND TRANSITIONS AROUND OBSTRUCTIONS.

8. NOT ALL ACCESS DOORS HAVE BEEN SHOWN ON THE PLANS. PROVIDE ACCESS PANELS

THROUGH BUILDING ASSEMBLIES TO SERVICE AND MAINTAIN EQUIPMENT UNLESS SUCH

EQUIPMENT IS INSTALLED IN EXPOSED LOCATIONS OR ABOVE LAY-IN CEILINGS. COORDINATE

THE LOCATION OF ACCESS DOORS AND PANELS AND VERIFY THE QUANTITY, SIZE, AND

LOCATIONS AFTER THE SYSTEMS AND EQUIPMENT REQUIRING ACCESS HAVE BEEN

INSTALLED AND PRIOR TO THE CLOSURE OF THE AFFECTED CEILINGS AND BUILDING

ASSEMBLIES. SUBMIT ACCESS PANEL LOCATIONS FOR REVIEW.

9. AT SUBSTANTIAL COMPLETION, THE FOLLOWING ITEMS, NEW OR EXISTING, SHALL BE FULLY

AND REASONABLY ACCESSIBLE: HVAC CONTROL BOXES, JUNCTION BOXES, VALVES, DDC

CONTROL BOXES, ELECTRICAL PANELS, FILTERS, BELTS, WATER COILS, DISCONNECT

SWITCHES AND ELEMENTS OF EQUIPMENT REQUIRING MAINTENANCE. "FULLY AND

REASONABLY ACCESSIBLE" SHALL BE DEFINED AS NATIONAL ELECTRIC CODE REQUIRED

CLEARANCE FOR POWERED EQUIPMENT AND CAPABLE OF BEING ACCESSED OR SERVICED

WITHOUT REMOVING, MODIFYING OR DISTORTING OTHER COMPONENTS OF THE WORK.

PROVIDE MANUFACTURER'S RECOMMENDED CLEARANCE FOR ALL EQUIPMENT.

10. SUPPORT EQUIPMENT, PIPING AND DUCTWORK FROM BUILDING STRUCTURE OR WITH STEEL

SUPPORTS AND PLATFORMS AS REQUIRED. PROVIDE VIBRATION ISOLATION FOR ROTATING

EQUIPMENT, DUCTWORK, AND PIPING IN ACCORDANCE WITH THE SPECIFICATIONS.

11. CONTROL WIRING METHODS SHALL COMPLY WITH NEC, AND DIVISION 26 SPECIFICATIONS.

12. VERIFY EQUIPMENT CONNECTIONS WITH MANUFACTURER'S DRAWINGS. VERIFY AND

PROVIDE FITTINGS TO TRANSITION TO FURNISHED EQUIPMENT. FIELD VERIFY AND

COORDINATE DIMENSIONS BEFORE FABRICATION.

13. PERFORM PRESSURE AND LEAKAGE TESTS BEFORE INSULATING DUCTWORK AND PIPING

14. MAINTAIN 6’-8” CLEARANCE TO THE UNDERSIDE OF PIPES, DUCTS, CONDUITS, SUSPENDED

EQUIPMENT, ETC., THROUGHOUT ROUTES IN MECHANICAL ROOMS. MAINTAIN 3’-0” WIDE

MEANS OF EGRESS IN MECHANICAL ROOMS.

15. MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND, AS SHOWN IN

THE DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT, SHALL BE FURNISHED BY THE

MECHANICAL CONTRACTOR.

16. INSTALL UNITS WITH CLEARANCE FOR SERVICE AS REQUIRED BY THE MANUFACTURER.

EQUIPMENT ABBREVIATIONS

LOUVER

EXHAUST FAN

L

EF

GENERAL ABBREVIATIONS

ACCESS DOOR

ADJUSTABLE

ABOVE FINISHED FLOOR

ALTERNATE

AUTHORITY HAVING JURISDICTION

ACCESS PANEL

CONVECTOR

AIR PRESSURE DROP

AVERAGE WATER TEMPERATURE

BUILDING AUTOMATION SYSTEM

BYPASS FEEDER

BREAK HORSEPOWER

BUILDING MANAGEMENT SYSTEM

BRITISH THERMAL UNIT

BTU / HOUR

BOTTOM OF DUCT

BOTTOM OF PIPE

CEILING RADIATION DAMPER

CAPACITY

COEFFICIENT OF PERFORMANCE

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CUBIC FEET PER MINUTE

CUBIC FEET

DECIBELS

DRY BULB TEMPERATURE

DIRECT DIGITAL CONTROL

DIAMETER

DOWN

DIRECT EXPANSION

EXHAUST AIR

ENTERING AIR TEMPERATURE (DRY BULB)

ENTERING DRY BULB

ENERGY EFFICIENCY RATIO

ELECTRICAL

EXTERNAL STATIC PRESSURE

ENTERING WET BULB

ENTERING WATER TEMPERATURE

DEGREES FAHRENHEIT

FIRE DAMPER

FEET

FEET WATER GAUGE

FULL LOAD AMPS

FEET PER MINUTE

COMBINATION FIRE SMOKE DAMPER

GALLONS PER HOUR

GALLONS PER MINUTE

GRILLE, REGISTER, DIFFUSER

HEAD

HORSEPOWER

HEATING SEASON PERFORMANCE FACTOR

HERTZ

HEATING, VENTILATION AND AIR CONDITIONING

HOT WATER RETURN

HOT WATER SUPPLY

INCHES

INCHES WATER GAUGE

INTEGRATED PART LOAD VALUE

KILOWATTS

LOUVER

LEAVING AIR TEMPERATURE

LEAVING DRY BULB

LEAVING WET BULB

LEAVING WATER TEMPERATURE

MAXIMUM

MECHANICAL

THOUSANDS OF BTU / HOUR

MINIMUM CIRCUIT AMPACITY

MINIMUM

NOT IN CONTRACT

NOT TO SCALE

OUTSIDE AIR TEMPERATURE

OUTER DIAMETER

OPEN ENDED DUCT

PUMP

PHASE

PLUMBING

PRESSURE REDUCING VALVE

POUNDS PER SQUARE INCH GAUGE

QUANTITY

RETURN AIR

REVOLUTIONS PER MINUTE

REDUCED PRESSURE ZONE BACKFLOW PREVENTER

RADON VENT

SUPPLY AIR

SEASONAL ENERGY EFFICIENCY RATIO

SIGHT GLASS

STATIC PRESSURE

STATIC PRESSURE DROP

STAINLESS STEEL

SATURATED SUCTION PRESSURE

SQUARE FEET

TEMPERATURE

TOTAL STATIC PRESSURE

THERMOSTAT

TYPICAL

UNLESS OTHERWISE INDICATED

VARIABLE AIR VOLUME

VARIABLE FREQUENCY DRIVE

VENT THRU ROOF

WITH

WITHOUT

WET BULB

WATER COLUMN

WATER GAUGE

WIRE MESH SCREEN

WATER PRESSURE DROP

AD

ADJ

AFF

ALT

AHJ

AP

CNV

APD

AWT

BAS

BF

BHP

BMS

BTU

BTUH

BOD

BOP

CRD

CAP

COP

CHWS

CHWR

CFM

CUFT

dB

DB

DDC

DIA

DN

DX

EA

EAT

EDB

EER

ELEC

ESP

EWB

EWT

°F

FD

FT

FT WG

FLA

FPM

FSD

GPH

GPM

GRD

HD

HP

HSPF

HZ

HVAC

HWR

HWS

IN

IN WG

IPLV

KW

L

LAT

LDB

LWB

LWT

MAX

MECH

MBH

MCA

MIN

NIC

NTS

OAT

OD

OED

P

PH

PLBG

PRV

PSIG

QTY

RA

RPM

RPZ

RV

SA

SEER

SG

SP

SPD

SS

SST

SQFT / SF

TEMP

TSP

TSTAT

TYP

UOI

VAV

VFD

VTR

W W/O

WB

WC

WG

WMS

WPD

CONTROLS LEGEND

DIGITAL INPUT

DIGITAL OUTPUT

ANALOG INPUT

ANALOG OUTPUT

DO

DI

AO

AI

T

PLAN

SYMBOL DESCRIPTION

DIAGRAM

SYMBOL

BAS TEMPERATURE SENSORTE

ELECTRICALLY COMMUTATED MOTORECM

ACTUATOR LEGEND

SYMBOL DESCRIPTION

DAMPER WITH TWO POSITION ACTUATOR

POSITION SWITCHZS

CURRENT TRANSMITTERIT

Scale:

Project Number:

Date:

Drawn By:

Checked By:

CONSTRUCTION SET

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street

Portsmouth, New Hampshire

603.430.0274

NTS

/2 /2

:4

:4

A M

C U s e rs \n h ill

\D o c u m e n ts

\R

-2

.0 -M

E P

C e n tr a l- U

N H

E le v a to r M a c h in e R o o m

M

U B n h ill R

Z E

J .r v t

M000

261202.00

10/30/2026

NGH

PTC

U N

H E

L E

V A

T O

R R

E N

O V

A T

IO

N

M E

M O

R

IA

L U

N

IO

N B

U

IL

D

IN

G

M A

IN

S

T R

E

T

U

R H

A M

N

H

U N

IV

E

R S

IT

Y

O F

N E

W H

A M

P S

H

IR

E

MECHANICAL

ABBREVIATIONS, NOTES

AND SYMBOLS

UNH ELEVATOR

RENOVATION MEMORIAL

UNION BUILDING

261202.00

DMUB-AP-221-3

DMUB-AP-221-4

DMUB-AP-221-1

DMUB-AP-221-5

DMUB-AP-CR223

DMUB-AP-203-1

DMUB-AP-223-2DMUB-AP-223-1

DMUB-AP-225-3

DMUB-AP-224-1

DMUB-AP-225-1

DMUB-AP-225-2

DMUB-AP-231-1

DMUB-AP-240-1

DMUB-AP-240-2

DMUB-AP-CR213

DMUB-AP-218-1

DMUB-AP-213-1

WALK-IN COOLER

LADDER

ROOF

OUTDOOR PATIO

OUTDOOR

PATIO

DNUP

DN

UP

DN

DN

DN

DN

DN

DN

UP

UP

FD EF-1

18x6 EA L-1

EXISTING EXHAUST FAN,

ASSOCIATED DUCTWORK,

CONTROLS, AND ACCESSORIES

TO BE DEMOLISHED.EXISTING 10x3 EA DUCTWORK

AND WALL CAP TO BE

DEMOLISHED T

MD

INSULATE FIRST 6' OF

DUCTWORK FROM

LOUVER

EXISTING HOISTWAY

ROOF VENT TO

REMAIN

18x18 DOOR TRANSFER

GRILLE WITH INTEGRAL FIRE

DAMPER BY ARCHITECT

6' - 0"

ELEVATOR

HOISTWAY

200ESA

MECH. ROOM

SUPPORT FROM

STRUCTURE ABOVE

SPRING VIBRATION ISOLATOR

WITH DOUBLE DEFLECTION

NEOPRENE HANGERS

HANGER ROODS. SIZE IN

ACCORDANCE WITH

MANUFACTURERS

RECOMMENDATIONS

EXHAUST DUCTWORK

SEE PLAN FOR SIZE

AND ROUTING

FLEXIBLE CONNECTION

FINISHED CEILING

EXHAUST GRILLE

CEILING MOUNTED

EXHAUST FAN

EXISTING WALL FACADE (TYP.)

LOUVER

STRUCTURE

PROVIDE FLANGED DRIP CAP MOUNTING

FRAME BETWEEN LOUVER AND WALL. SEAL

WEATHERPROOF AND INSTALL ACCORDING

TO MANUFACTURER'S INSTRUCTIONS.

LOUVER INSTALL ACCORDING TO

MANUFACTURES INSTRUCTIONS

PAINT TO MATCH EXTERIOR WALL.

SEAL WEATHERPROOF ALL SEAMS AND

OPENINGS AROUND FRAME AND INSTALL

ACCORDING TO MANUFACTURER'S

INSTRUCTIONS.

PROVIDE FLASHING/DRIP EDGE BETWEEN

WALL AND PROVIDE EXTENDED SILL WITH

END DAMS (TYPICAL)DUCT

PITCH

CLIP ANGLES &

FASTENERS

(TYPICAL)

NOTES:

1. DAMPER STYLE & SLEEVE CONFIGURATION IS GOVERNED BY MAINTAINING A MAX. .06

STATIC PRESSURE @ 2500 F.P.M. FACE VELOCITY.

2. DEPTH OF DAMPER TO BE COORDINATED WITH WALL THICKNESS.

3. INSTALLATIONS & MATERIALS PER U.L. 555.

FASTEN DAMPER TO SLEEVE

W/BOLTS, SCREWS, RIVETS, OR

TACK WELDS, MAX. 8" O.C.

ACCESS DOOR IN

CEILING. COORDINATE

ARCHITECTURAL

DRAWINGS

ACCESS DOOR IN DUCT.

[COORDINATE WITH LOCATION

OF ACCESS DOOR IN CEILING.]

CONTINUOUS "S" JOINT

SLEEVE

1-1/2" X 1-1/2" X 16 GAUGE

CONTINUOUS STEEL ANGLE

FASTENED TO SLEEVE WITH

BOLTS, SCREWS, RIVETS,

OR TACK WELDS, MAX. 8" O.C.

INSULATED DUCT, BUTT

INSULATION UP TO WALL

DAMPER

MAXIMUM CLEARANCE SHALL

BE IN ACCORDANCE WITH LATEST

EDITION OF SMACNA STANDARDS

1" MIN. 4 SIDES

FIRE DAMPER NOTE

PROVIDE FIRE DAMPERS (,COMBINATION FIRE AND SMOKE DAMPERS) (AND SMOKE

DAMPERS) AT ALL LOCATIONS WHERE DUCTS AND OUTLETS PASS THROUGH FIRE RATED

COMPONENTS, WHERE INDICATED ON CONTRACT DOCUMENTS, AND WHERE REQUIRED

BY AUTHORITIES HAVING JURISDICTION. INSTALL WITH REQUIRED PERIMETER MOUNTING

ANGLES, SLEEVES, BREAKAWAY DUCT CONNECTIONS, CORROSION RESISTANT SPRINGS,

BEARINGS, BUSHINGS AND HINGES.

SEQUENCE OF OPERATION

GENERAL

1. PROVIDE BAS CONTROLS THOUGH THE CAMPUS BAS.

2. WHERE ADJUSTABLE TEMPERATURE SETPOINTS ARE INDICATED, THE

TEMPERATURE RANGE SHALL BE CAPABLE OF SETPOINTS BETWEEN

50°F AND 100 °F.

3. ALL ALARMS SHALL HAVE A 5 MIN. (ADJ.) DELAY BEFORE ACTIVATING AT

THE BAS.

SAFETIES AND ALARMS

1. IF THE FAN IS COMMANDED ON AND IT DOES NOT ACTIVATE, AN ALARM

SHALL BE GENERATED THROUGH THE BAS.

2. IF THE DAMPER IS COMMANDED OPEN AND IT DOES NOT PROVE OPEN:

A. AN ALARM SHALL BE GENERATED THROUGH THE BAS.

B. THE FAN SHALL NOT ACTIVATE.

3. IF THE DAMPER IS COMMANDED CLOSED AND IT DOES NOT PROVE

CLOSED, AN ALARM SHALL BE GENERATED THROUGH THE BAS.

4. IF THE SPACE TEMPERATURE SENSOR FAILS OR LOSES

COMMUNICATION FOR 5 MIN (ADJ.)

OPERATION

1. IF THE SPACE TEMPERATURE RISES ABOVE SETPOINT 85°F (ADJ.):

A. THE BAS SHALL FULLY OPEN THE DAMPER.

B. ONCE THE DAMPER IS PROVEN OPEN, THE BAS SHALL ACTIVATE

THE FAN.

1. IF THE SPACE TEMPERATURE DROPS BELOW THE SETPONT 80°F (ADJ.):

A. THE BAS SHALL DEACTIVATE THE FAN.

B. THE BAS SHALL FULLY CLOSE THE DAMPER.

FIRE ALARM SHUTDOWN

1. UPON THE BUILDING FIRE ALARM SYSTEM BEING ACTIVATED, THE FAN

SHALL SHUT OFF AND THE DAMPER SHALL CLOSE.

2. NOTE: FIRE ALARM SHUTDOWN SHALL BE A HARDWIRED LIFE-SAFETY

FUNCTION PROVIDED BY OTHERS AND NOT THROUGH THE BAS.

BAS

TEMPERATURE

SENSOR

EXH

EXH

TYPICAL FOR: EF-1

TE

DO AI

DO

ZS

DI

IT DI

ESP

(IN WG)

FAN SCHEDULE

GENERAL

TAG MANUFACTURER MODEL LOCATION SERVICE

WEIGHT

(LBS)

PHYSICAL

CFM

ELECTRICAL REMARKS

TYPE

1. EC MOTOR, DIRECT DRIVE, CEILING EXHAUST FAN

MOP RATINGSRPM VOLTAGE FEATURESBHP PHASE INSTALL

REMARKS - TYPE REMARKS - RATINGS REMARKS - FEATURES REMARKS - INSTALL

1. AMCA CERTIFIED 1. FAN MOUNTED VARI-GREEN DIAL FOR BALANCING 1. SEE DETAIL

PERFORMANCE

EF-1 GREENHECK SP-A510-VG

MECHANICAL

ROOM

MECHANICAL

ROOM

36 540 0.5 1392 0.23 15 115 1 1 1 1 1

DRIVE

DIRECT

ACOUSTICAL DATA

INLET SONES

7.5

MCA

6.2

LOUVER SCHEDULE

GENERAL

TAG MANUFACTURER MODEL LOCATION SERVICE

WIDTH

(IN)

PHYSICAL PERFORMANCE

CFM

REMARKS

TYPE

1. STATIONARY BLADE, DRAINABLE, 0.125"

THICK EXTRUDED ALUMINUM FRAME & BLADES,

4" DEEP

RATINGS FEATURESFPM INSTALL

SPD

(IN WG)

REMARKS - TYPE REMARKS - RATINGS REMARKS - FEATURES REMARKS - INSTALL

HEIGHT

(IN)

FREE

AREA

(SQ FT)

1. AMCA 511 CERTIFIED FOR WATER AND AIR

PERFORMANCE

1. BIRD SCREEN

2. COLOR/FINISH SELECTABLE BY ARCHITECT

1. SEE DETAIL

L-1 1GREENHECK ESD-635

MECHANICAL

ROOM

EF-1 20 12 0.5 540 984 0.14 1 1,2 1

WEST ELEVATOR

MACHINE ROOM

WEST ELEVATOR

Scale:

Project Number:

Date:

Drawn By:

Checked By:

CONSTRUCTION SET

Drawing Name:

Project Name:

© 2026 Portsmouth Architects

4 Market Street

Portsmouth, New Hampshire

603.430.0274

As indicated

/2 /2

:4

:4

A M

C U s e rs \n h ill

\D o c u m e n ts

\R

-2

.0 -M

E P

C e n tr a l- U

N H

E le v a to r M a c h in e R o o m

M

U B n h ill R

Z E

J .r v t

M101

261202.00

10/30/2026

NGH

PTC

U N

H E

L E

V A

T O

R R

E N

O V

A T

IO

N

M E

M O

R

IA

L U

N

IO

N B

U

IL

D

IN

G

M A

IN

S

T R

E

R H

A M

N

H

U N

IV

E

R S

IT

Y

O F

N E

W H

A M

P S

H

IR

E

MECHANICAL

DUCTWORK FLOOR

PLAN, DETAILS, AND

SCHEDULES

UNH ELEVATOR

RENOVATION MEMORIAL

UNION BUILDING

261202.00

1/4" = 1'-0"

MECHANICAL DUCT - WEST ELEVATOR - LEVEL 2

NTS

CEILING MOUNTED EXHAUST FAN DETAIL

NTS

LOUVER MOUNTING DETAIL

NTS

FIRE DAMPER DETAIL - HORIZONTAL

NTS

FANS - EXHAUST

1" = 30'-0"

MUB MECHANICAL KEY PLAN - LEVEL 2

23 00 00 - GENERAL

A. THESE SPECIFICATIONS ARE APPLICABLE TO ALL MECHANICAL DRAWINGS UNLESS NOTED

OTHERWISE. REVIEW THE ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR NOTES,

DIMENSIONS, ETC., AND COORDINATE WITH OTHER TRADES INVOLVED.

B. DESCRIPTION

1. THIS PROJECT COMPRISES ALTERATIONS AND RENOVATIONS TO THE EXISTING…

This is the start of the file's text. The full file is on GovTribe.