The file's text, extracted by GovTribe without its formatting.
TE-10
Infrared Testing Requirements
Ogden, Utah
January 2010
TECHNICAL EXHIBIT TE -10
Infrared Testing Requirements
IRS PM
CHECK
| E-28 |
| Motor Starters Less Than 100 Hp |
| One time in three years |
| E-30A |
| Switchboards, Medium Voltage, (per cubicle) |
| One time in three years |
| E-30B |
| Switchboards Low Voltage, (per cubicle), |
| One time in three years |
| E-37C |
| Bus Duct, Low Voltage, & Connectors Copper - Per disconnect |
| One time in three years |
| E-37D |
| Bus Duct, Low Voltage, & Connectors Copper - Per 10 foot bus duct section |
| One time in three years |
| E-36 |
| Automatic Transfer Switch |
| One time in three years |
| E-33A |
| High Voltage Network and, Power Type Transformer Dry Type Transformer - - Power Type |
| Annual |
| E-33B |
| High Voltage Network and, Power Type Transformer Dry Type Transformer - - Network Type |
| Annual |
| E-34A |
| Disconnects or Isolating Switch, Per Switch, Under 200 amps >600 VOLTS |
| Annual |
| E-34B |
| Disconnect or isolating switch, low voltage (fused/non- fused, 200 amps and up) - - 200 To 500 Amps |
| Annual |
| E-34C |
| Disconnect or isolating switch, low voltage (fused/non- fused, 200 amps and up) - - Over 500 Amps |
| Annual |
| E-37A |
| Bus Duct, Low Voltage, & Connectors Aluminum - Per disconnect |
| Annual |
| E-37B |
| Bus Duct, Low Voltage, & Connectors Aluminum - Per 10 foot bus duct section |
| Annual |
| E-37AA |
| Bus Duct, Metal Enclosed, & Connectors Aluminum: - Per disconnect |
| Annual |
| E37BB |
| Bus Duct, Metal Enclosed, & Connectors Aluminum: - Per 10 foot bus duct section |
| Annual |
| E-37CC |
| Bus Duct, Metal Enclosed, & Connectors Aluminum: - Outdoors: Per disconnect |
| Annual |
| E-37DD |
| Bus Duct, Metal Enclosed, & Connectors Aluminum: - Outdoors: Per 10 foot bus duct section |
| Annual |
| E-59 |
| Uninterruptible Power System, Static |
| Annual |
| E-35A |
| Motor Control Center (MCC), under 100 hp - - 5 or fewer starters |
| Annual |
| E-35B |
| Motor Control Center (MCC), under 100 hp - - Each additional motor starter |
| Annual |
| E-58 |
| Power Distribution Unit |
| Annual |