SSC_-_SS-1-5_-_Product_Report.pdf
PDF 34 KB Posted
- Attached to
- Computer Room HVAC Upgrade
- Solicitation number
- Quote- 26 - 205
- Issued by
- Pinellas County, Florida
About this file
This file contains a product specification report and a related state and local contract opportunity for the City of St. Petersburg, Florida, regarding HVAC system upgrades. The City is requesting quotes from qualified vendors for the installation of a conventional split-style air conditioning system sized for 3.5 tons to replace an existing 5-ton Libert unit in a computer room application. The project, identified as "COSP - City Hall HVAC Renovations," requires installation of a new outdoor condenser unit, indoor air handler unit, and associated refrigerant piping, with the vendor responsible for uninstallation and disposal of the existing equipment. Additionally, a standalone humidifier system with a capacity of 5 pounds per hour must be installed separately, as conventional split-style AC units lack humidifier capability. The specification document provided details a 1.5-5 ton unitary split system unit (model SS-1-5) with cooling capacity of 39,000 Btuh at AHRI rating and 35,873 Btuh net cooling capacity, featuring R-454B refrigerant and a SEER2 rating of 14.30.
This is a sheltered bid contract opportunity, which requires that at least 20 percent of the contracting effort, including the cost of supplies, be self-performed by the SBE (Small Business Enterprise) prime contractor. No specific response deadline, due date, site visit requirements, bidder's conference, or award date is provided in the available documentation. The contract pricing terms, funding sources, total contract value, and term length are not specified in the materials reviewed. The project location is the City of St. Petersburg, Florida.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Computer_Room_HVAC_Upgrade.pdf | ||
| 1937.08_City_Hall_Computer_Room_HVAC_Drawings.pdf | ||
| Subcontractor_Summary_Spreadsheet.xlsx | XLSX spreadsheet | |
| SSC_-_SS-1-5_-_As_Built_Drawings.pdf | ||
| Light_Construction_Agreement.docx | DOCX document | |
| Public_Construction_Bond.docx | DOCX document | |
| 1937.08_City_Hall_-_Computer_Room_HVAC_-_Drawings_100%_CD's_Review.pdf | ||
| Subcontractor_Summary_-_Sheltered_.xlsx | XLSX spreadsheet | |
| Quote_Addendum.docx | DOCX document | |
| Subcontractor_Utilization_Plan.docx | DOCX document | |
| Performance_&_Payment_Bond_.DOCX | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1.5 - 5 Ton Unitary Split System Unit Overview
System Type A/C with Air Handler Outdoor Unit Model 1.5-5 Ton Split Sys Clg R-454B
Outdoor Unit Nominal Capacity 042 Indoor Unit Model
Indoor Unit Nominal Capacity 36 - 48K Cooling Capacity
AHRI Data AHRI Reference Number 215440465
Airflow @ AHRI 1155 cfm Capacity @ AHRI 39000.00 Btuh
EER2 @ AHRI 12
SEER2 @ AHRI 14.30
Unit Electrical Outdoor Unit 5TTR4042A1
Power Supply 200-230/60/1 Indoor Unit 5TEM4D05AC41
Power Supply 208- 230/60/1
Cooling Performance Cooling Airflow 1375 cfm
Cooling EDB 72.00 F Cooling EWB 59.00 F
Cooling Outdoor Temp. 95.00 F
Net Cooling Capacity 35873.00 Btuh Net Sensible Capacity 29370.00 Btuh
Net Latent Capacity 6503.00 Btuh Cooling LDB 52.20 F Cooling LWB 49.10 F
Job Name: COSP - City Hall HVAC Renovations Prepared For:
Unit Tag: SS-1-5 Quantity: 1
2026/04/08 10:27:40 Page 1 of 1