This document is a 100% Owner Review construction drawing set prepared by Engineering Matrix, Inc. for the City of St. Petersburg, Florida, for Computer Room HVAC Upgrades at City Hall (Project No. 1937.08). The project involves the installation of additional HVAC equipment and associated electrical work, infill wall opening at HVAC unit removal, and associated finishes in the basement computer room located at 175 5th Street North, St. Petersburg, Florida 33701. The work is classified as an Alteration Level 2 under Construction Type VB (unprotected, fully sprinklered) and maintains existing occupancy classification as Group A, Assembly (A-3) and Group B, Business (B). The drawing set dated January 25, 2023, includes architectural floor plans, mechanical symbols and schedules, mechanical and electrical basement floor plans, and construction details. The project scope includes demolition of the existing 5-ton Liebert unit, installation of a 3.5-ton split-style AC system with floor-mounted indoor air handler and outdoor condenser unit, refrigerant piping, a separate standalone humidifier system with 5 pounds per hour capacity, and associated electrical connections. All work must comply with the 2020 Florida Building Code, 2020 Florida Fire Prevention Code, and applicable NFPA standards.
The contractor must field-verify all existing conditions prior to fabrication and is responsible for obtaining all necessary permits and inspections. The project requires coordination among mechanical, electrical, and architectural trades, with particular attention to maintaining building security and water tightness throughout construction. The contractor must protect existing finishes, seal all penetrations in walls, floors, and ceilings, and repair any existing surfaces left in disrepair. This is a sheltered bid contract requiring a Small Business Enterprise (SBE) prime contractor to self-perform at least 20 percent of the contracting effort, including supply costs. The project is funded by the City of St. Petersburg's Engineering and Capital Improvements Department and follows the Secretary of the Interior's Standards for Rehabilitation where applicable to this historic building alteration.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Computer_Room_HVAC_Upgrade.pdf | ||
| 1937.08_City_Hall_Computer_Room_HVAC_Drawings.pdf | ||
| Subcontractor_Summary_Spreadsheet.xlsx | XLSX spreadsheet | |
| SSC_-_SS-1-5_-_As_Built_Drawings.pdf | ||
| Light_Construction_Agreement.docx | DOCX document | |
| SSC_-_SS-1-5_-_Product_Report.pdf | ||
| Public_Construction_Bond.docx | DOCX document | |
| Subcontractor_Summary_-_Sheltered_.xlsx | XLSX spreadsheet | |
| Quote_Addendum.docx | DOCX document | |
| Subcontractor_Utilization_Plan.docx | DOCX document | |
| Performance_&_Payment_Bond_.DOCX | DOCX document |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INDEX OF DRAWINGS
I ARCHITECTURAL
00000- 01 - COVER
00000- 02 GA1.0 GENERAL ARCHITECTURAL
00000- 03 A1.0 BASEMENT FLOOR PLAN
II MECHANICAL
00000- 04 M0.0 MECHANICAL SYMBOLS LEGEND
00000- 05 M0.1 MECHANICAL DETAILS
00000- 06 M0.2 MECHANICAL SCHEDULES
00000- 07 M1.0 BASEMENT FLOOR PLANS - MECHANICAL
III ELECTRICAL
00000- 08 E0.0 ELECTRICAL GENERAL
00000- 09 E1.0 BASEMENT FLOOR PLANS - ELECTRICAL
CITY PROJECT NO.
BREJESH PRAYMAN, PE., ENV SP
E N G I N E E R I N G a n d C A P I T A L I M P R O V E M E N T S D E P A R T M E N T C I T Y o f S T . P E T E R S B U R G , F L .
APPROVED FOR BID
ENGINEERING DIRECTOR
DATE
CENTRAL
AV NO
AV NO
AV NO
AV NO
AV NO
AV
AV SO
AV SO
AV SO
AV SO
AV SO
AV SO
PINELLAS POINT DR
ST
ST
ST
ST
ST
ST
ST
ST
ST
54 AV NO
54 AV NO
83 AV NO
CITY LIMIT
TYRONE
PIN
ELLAS TR
AIL
PARK ST
BLVD
CITY LIMIT
PA
SA
D
EN
A
V
LAKE
MAGGIORE
CITY
L
IM
IT
PINELLAS
BAYWAY
HAINES
RD
ROOSEVELT BLVD
ULMERTON RD
CITY LIMIT
GANDY BLVD
B O C A C I E G A B A Y
T
M
P
B
Y
ALT
ALT
S C A L E :
1.00" = 4,000'
2000 0
4000 8000
GULFPORT
CITY HALL
175 5th STREET NORTH, ST. PETERSBURG, FL 33701
JANUARY 25, 2023
COMPUTER ROOM HVAC UPGRADES FOR
21203
100% OWNER REVIEW
00000- 01
PROJECT LOCATION
175 5TH STREET N
A1.1
TYP
*101
Name Elevation
A1.1
TYP
1i
N
1 DRAWING TITLE
1/8" = 1'-0"A1.1
A1.1
TYP
DRAWING TITLE
VIEW SCALE
SECTION NUMBER
LOCATION SHEET
DETAIL NUMBER
LOCATION SHEET
DETAIL NUMBER
LOCATION SHEET
ELEVATION MARK
DOOR TAG
SPECIFIC NOTE
PARTITION TYPE
1t WINDOW / LOUVER TYPE
?X
MECHANICAL, ELECTRICAL, PLUMBING ENGINEER
ENGINEERING MATRIX, INC.
2860 Scherer Drive, Suite 640 St. Petersburg, FL 33716
(t) 727.573.4656
ARCHITECT
RENKER EICH PARKS ARCHITECTS
1609 Dr. MLK Jr. Street North St. Petersburg, FL 33704
(t) 727.821.2986 reparch.com
PROJECT DESCRIPTION: ADDITIONAL HVAC EQUIPMENT & ASSOCIATED ELECTRICAL
WORK, INFILL WALL OPENING AT HVAC UNIT REMOVAL &
ASSOCIATED FINISHES
OCCUPANCY CLASSIFICATION:
GROUP A, ASSEMBLY (A-3) Community Hall GROUP B, BUSINESS (B) Civic Administration
(MAINTAINING EXISTING OCCUPANCY AND FIRE SEPARATION)
CLASSIFICATION OF WORK: ALTERATION LEVEL 2
THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
CONSTRUCTION TYPE: TYPE VB - UNPROTECTED, FULLY SPRINKLERED
FIRE RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS:
STRUCTURAL FRAME: 0 HOURS
BEARING WALLS: 0 HOURS
NONBEARING WALLS EXTERIOR: 0 HOURS
NONBEARING WALLS INTERIOR: 0 HOURS
FLOOR CONSTRUCTION: 0 HOURS
ROOF CONSTRUCTION: 0 HOURS
ENGINEERING and CAPITAL
IMPROVEMENTS DEPARTMENT
CITY of ST. PETERSBURG
DATE:
DATE:
DATE:DRAWN BY:
CHECKED BY:
DESIGNED BY: DATE:
DRAWING No.
SCALE:
R E V I S I O N S BY DATE
APPROVED BY:
SHEET NO.:
PROJECT NO.:
SHEET TITLE:
CITY PROJECT NO.
As indicatedCITY HALL
PCP
GA1.0
GENERAL
ARCHITECTURAL
175 5th STREET NORTH, ST. PETERSBURG, FL 33701
1937.08
JANUARY 25, 2023COMPUTER ROOM HVAC UPGRADES FOR
21203 00000- 02
100% OWNER REVIEW
ARCHITECTURAL ABBREVIATIONS
DRAWING LEGEND
DIMENSION NOTES
1 ALL DOOR FRAME OPENINGS IN MASONRY SHALL BE 3'-4" MO UNO
2 ALL DIMENSION STRINGS SHALL BE TO FACE OF WALL STRUCTURE (IE
CMU, MTL STUD FRAMING)
3 DIMENSION STRINGS NOTED AS CLEAR SHALL BE TO FACE OF FINISHED
WALL OR PARTITION (IE FACE OF GWB, PLASTER, OR TILE)
4 DOOR JAMB RETURNS IN MASONRY WALLS TO HINGE SIDE SHALL BE 8"
NOM UNO
5 DOOR JAMB RETURNS IN MTL FRAMING WALLS TO HINGE SIDE SHALL BE
4" NOM UNO
KIT KITCHEN
KW KILOWATT
L LENGTH
LAM LAMINATE
LAV LAVATORY
LF LINEAR FEET
LKR LOCKER
LL LEAD LINED
MFD MANUFACTURED
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MIR MORROR
MISC MISCELLANEOUS
MLDG MOLDING
MO MASONRY OPENING
MR MOISTURE RESISTANT
MT METAL THRESHOLD
MTD MOUNTED
MTL METAL
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLUMB PLUMBING
PLWD PLYWOOD
PNT PAINT
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PVC POLYVINYL CHLORIDE
QT QUARRY TILE
R RADIUS
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
REC RECEPTACLE
REF REFRIGERATOR
REG REGLET
REINF REINFORCED
REQD REQUIRED
RM ROOM
RO ROUGH OPENING
SCHD SCHEDULE
SCRN SCREEN
SEC SECTION
SH SHELF
SHT SHEET
SIM SIMILAR
SP SPACE
SPECS SPECIFICATIONS
SS STAINLESS STEEL
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
TB TOGGLE BOLT
TC TOILET COMPARTMENT
TEL TELEPHONE
TEMP TEMPERATURE
TPD TOILET PAPER DISPENSER
TYP TYPICAL
UC UNDERCOUNTER
UNO UNLESS NOTED OTHERWISE
UTIL UTILITY
VB VINYL BASE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VWC VINYL WALLCOVERING
W WIDTH
W/ WITH
WC WATER CLOSET
WD WOOD
WP WEATHER PROOF
WWF WELDED WIRE FABRIC
AB ANCHOR BOLT
ACOUST ACOUSTICAL
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AT ACOUSTICAL TILE
BD BOARD
BFE BASE FLOOD ELEVATION
BLDG BUILDING
BM BEAM
BOT BOTTOM
BUR BUILT-UP ROOFING
C.F.C.I. CONTRACTOR FURNISHED
AND CONTRACTOR
INSTALLED
CAB CABINET
CG CORNER GUARD
CI CAST IRON
CJ CORNER JOINT
CL CLEAR
CLO CLOSET
CMU CONCRETE MASONRY UNIT
CNT COUNTER
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CORR CORRIDOR
CPT CARPET
CT CERAMIC TILE
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DN DOWN
DWG DRAWING
EB EXPANSION BOLT
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATION
EP ELECTRICAL PANEL
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EX EXISTING
EXP EXPOSED
EXT EXTERIOR
FC FURRING CHANNEL
FD FLOOR DRAIN
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FHC FIRE HOSE CABINET
FIN FINISH
FL FLOOR
FR FIRE RATED
GA GUAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GFRC GLASS FIBER REINFORCED
CEMENT
GFRG GLASS FIBER REINFORCED
GYPSUM
GL GLASS
GR GRADE
GWB GYPSUM WALLBOARD
GYP GYPSUM
HB HOSE BIB
HT HEIGHT
HVAC HEATING, VENTILATING, & AIR
CONDITIONING
ID INSIDE DIAMETER
INSUL INSULATION
INT INTERIOR
JT JOINT
APPLICABLE CODES
2020 FLORIDA BUILDING CODE - BUILDING
2020 FLORIDA BUILDING CODE - EXISTING BUILDING
2020 FLORIDA BUILDING CODE - MECHANICAL
2020 FLORIDA BUILDING CODE - PLUMBING
2020 FLORIDA BUILDING CODE - FUEL GAS
2020 FLORIDA BUILDING CODE - TEST PROTOCOLS
2020 FLORIDA BUILDING CODE - ENERGY (Chapter 13)
2020 FLORIDA BUILDING CODE - ACCESSIBILITY
2020 FLORIDA FIRE PREVENTION CODE, 7th EDITION
2018 NFPA 70 NATIONAL ELECTRICAL CODE
2016 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE
2018 NFPA 101 FIRE SAFETY CODE
GENERAL PROJECT NOTES
THE FOLLOWING GENERAL NOTES PERTAIN TO THE ENTIRE SET OF
CONTRACT DOCUMENTS: DRAWINGS AND SPECIFICATIONS
1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE
FEDERAL, STATE, COUNTY, AND CITY CODES, RULES, REGULATIONS AND
ORDINANCES.
2. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, DETAILS,
AND DIMENSIONS OF THE WORK PRIOR TO FABRICATION. NOTIFY
ARCHITECT OF ANY DISCREPANCIES BETWEEN THESE CONDITIONS AND
THE DRAWINGS. ALL SUB-CONTRACTORS ARE REQUIRED TO
COORDINATE THEIR WORK WITH OTHER TRADES.
3. CONTRACTOR SHALL PROTECT EXISTING FINISHES AND DEVICES DURING
DEMOLITION AND CONSTRUCTION TYP. ALL EXISTING CEILING, FLOOR,
AND WALL FINISHES INDICATED TO REMAIN, THAT ARE LEFT IN A STATE
OF DISREPAIR BY THE DEMOLITION OR CONSTRUCTION PROCESS SHALL
BE REPAIRED TO MATCH SIMILAR AND/ OR ADJOINING SURFACES.
4. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND
INSPECTIONS REQUIRED, AND SHALL PAY FOR ALL.
5. THE CONTRACTOR IS TO ENSURE THAT THE BUILDING IS SEALED AND
SECURED AT THE END OF EACH WORK DAY. VERIFY BUILDING SPECIFIC
SECURITY REQUIREMENTS WITH OWNER PRIOR TO PROCEEDING WITH
WORK. THE CONTRACTOR SHALL MAINTAIN A CLEAN AND ORGANIZED
JOB SITE ACCEPTABLE TO THE OWNER.
6. THE CONTRACTOR SHALL SCHEDULE AND PERFORM ALL CONSTRUCTION
WORK SUCH THAT SECURITY AND WATER TIGHTNESS OF THE EXISTING
BUILDING IS MAINTAINED 100% OF THE TIME THROUGHOUT THE
CONSTRUCTION PERIOD. COORDINATE WITH AND FOLLOW THE OWNERS
DIRECTIONS.
7. THE CONTRACTOR IS TO COORDINATE ALL WORK WITH THE
REQUIREMENTS OF EACH OF THE CONTRACT DRAWINGS AND THE
PROJECT MANUAL CONTAINING THE TECHNICAL SPECIFICATIONS.
8. THE CONTRACTOR SHALL COORDINATE AND BE RESPONSIBLE FOR
FURNITURE AND EQUIPMENT RELOCATION/ PROTECTION AS REQUIRED
FOR THE COMPLETE RENOVATION WORK. THE GENERAL CONTRACTOR
SHALL COORDINATE WITH THE WORK OF ALL SUBCONTRACTORS.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR/ AND OVERSEE THE
PROPER AND NEAT INSTALLATION OF ALL NEW WORK BY HIS SUB
CONTRACTORS AND OTHER VENDORS. CONTRACTOR SHALL FURNISH
ALL LABOR, MATERIALS, AND EQUIPMENT AS REQUIRED TO COMPLETE
WORK.
10. SEAL ALL PENETRATIONS IN WALLS, FLOORS AND CEILINGS. SEALANTS
SHALL BE COMPATIBLE WHERE IN CONTACT WITH ONE ANOTHER.
ISOLATE ALL DISSIMILAR MATERIALS.
11. ALL FIRE RATED WALLS TO BE NOTED IN STENCIL ABOVE FINISHED
CEILING PER APPLICABLE CODE.
12. CONTRACTOR TO HAVE PORTABLE FIRE EXTINGUISHER PLACED ON
FLOOR DURING CONSTRUCTION.
13. TO THE GREATEST EXTENT POSSIBLE, THE RESTORATION WORK SHALL
BE IN ACCORDANCE WITH:
"THE SECRETARY OF THE INTERIOR'S STANDARDS FOR REHABILITATION
AND GUIDELINES FOR REHABILITATING HISTORIC BUILDINGS", U.S.
DEPARTMENT OF THE INTERIOR, NATIONAL PARK SERVICE. WHERE
DECISIONS REGARDING HISTORIC APPROPRIATENESS ARE REQUIRED,
THE ARCHITECT SHALL BE NOTIFIED AND BE REQUESTED TO PROVIDE
INTERPRETATION OF APPROPRIATENESS IN CONSULTATION WITH THE
OWNER, PRIOR TO PROCEEDING ON THE WORK IN QUESTION.
CONTRACTOR TO OBTAIN LOCAL C.O.A. FOR ALL EXTERIOR
MODIFICATIONS.
14. CONTRACTOR TO USE WIRE TRAYS IN CORRIDORS WHERE WIRE TRAYS
ARE INSTALLED.
BUILDING CODE SUMMARY
ET
P
P
V-5
V-4 6"�
4"�
6"� 6"�
4"�
VENDVEND
X X
X X
X X
X X
X X
X X
X X
X
DN
005A
ELECT.
005B
BATTERY
TELE/COMM.
ROOM
005C
ELECT/TELEPHONE
006A
CONTROL
STORAGE
TV
CONTROL
CORRIDOR
040403
NEW INFILL WALL
3-5/8" MTL STUD
(2) LAYERS 5/8" GWB, EACH SIDE
4" SOUND ATTENUATION BATT
MATCH EXIST WIDTH AND FINISH
005A
ELECT.
005B
BATTERY
TELE/COMM.
ROOM
005C
ELECT/TELEPHONE
006A
CONTROL
STORAGE
TV
CONTROL
CORRIDOR
D1
7' - 7"
TELE/COMM. ROOM
ELECT/TELEPHONE
005CCONTROL
006A
STORAGE
006 02
ENGINEERING and CAPITAL
IMPROVEMENTS DEPARTMENT
CITY of ST. PETERSBURG
DATE:
DATE:
DATE:DRAWN BY:
CHECKED BY:
DESIGNED BY: DATE:
DRAWING No.
SCALE:
R E V I S I O N S BY DATE
APPROVED BY:
SHEET NO.:
PROJECT NO.:
SHEET TITLE:
CITY PROJECT NO.
As indicatedCITY HALL
JMV
A1.0
BASEMENT FLOOR
PLAN
175 5th STREET NORTH, ST. PETERSBURG, FL 33701
1937.08
JANUARY 25, 2023COMPUTER ROOM HVAC UPGRADES FOR
21203 00000- 03
100% OWNER REVIEW
N
1/4" = 1'-0"A1.0
1 BASEMENT FLOOR PLAN
PLAN LEGEND
BASEMENT KEY
N
1/4" = 1'-0"A1.0
BASEMENT FLOOR
DEMOLITION PLAN
N
1/4" = 1'-0"A1.0
BASEMENT REFLECTED
CEILING PLAN
SPECIFIC DEMO NOTES
D1 DEMOLISH EXISTING LIEBART UNIT, REFER TO MECH
SPECIFIC NOTES
01 PROVIDE CARPET TILE TO MATCH EXIST
02 PROVIDE APC SYSTEM TO MATCH EXIST
03 ACOUSTICAL JOINT SEALANT, FULL PERIMETER AND PAINT NEW WALL, BOTH SIDES
04 NEW EQUIPMENT, REFER TO MECHANICAL AND ELECTRICAL
05 COORDINATE MANUFACTURER EQUIPMENT MOUNTING REQUIREMENTS AND PROVIDE
STUD WALL BLOCKING AS NECESSARY
XXX
M0.0
XXXX - XX
XXX
CITY PROJECT NO.
ENGINEERING and CAPITAL
IMPROVEMENTS DEPARTMENT
CITY of ST. PETERSBURG
DATE:
DATE:
DATE:DRAWN BY:
CHECKED BY:
DESIGNED BY: DATE:
DRAWING No.
SCALE:
R E V I S I O N S BY DATE
APPROVED BY:
© 2023 Engineering Matrix, Inc.
CONSULTING ENGINEERS
SHEET NO.:
PROJECT NO.:
SHEET TITLE:
CITY HALL
175 5th STREET NORTH, ST. PETERSBURG, FL 33701
COMPUTER ROOM HVAC UPGRADES FOR
21203
100% OWNER REVIEW
As Indicated
JANUARY 25, 2023
1937.08
GFB
MECHANICAL
SYMBOLS
LEGEND
XXX
M0.1
XXXX - XX
XXX
CITY PROJECT NO.
ENGINEERING and CAPITAL
IMPROVEMENTS DEPARTMENT
CITY of ST. PETERSBURG
DATE:
DATE:
DATE:DRAWN BY:
CHECKED BY:
DESIGNED BY: DATE:
DRAWING No.
SCALE:
R E V I S I O N S BY DATE
APPROVED BY:
© 2023 Engineering Matrix, Inc.
CONSULTING ENGINEERS
SHEET NO.:
PROJECT NO.:
SHEET TITLE:
CITY HALL
175 5th STREET NORTH, ST. PETERSBURG, FL 33701
COMPUTER ROOM HVAC UPGRADES FOR
21203
100% OWNER REVIEW
As Indicated
JANUARY 25, 2023
1937.08
GFB
MECHANICAL
DETAILS
XXX
M0.2
XXXX - XX
XXX
CITY PROJECT NO.
ENGINEERING and CAPITAL
IMPROVEMENTS DEPARTMENT
CITY of ST. PETERSBURG
DATE:
DATE:
DATE:DRAWN BY:
CHECKED BY:
DESIGNED BY: DATE:
DRAWING No.
SCALE:
R E V I S I O N S BY DATE
APPROVED BY:
© 2023 Engineering Matrix, Inc.
CONSULTING ENGINEERS
SHEET NO.:
PROJECT NO.:
SHEET TITLE:
CITY HALL
175 5th STREET NORTH, ST. PETERSBURG, FL 33701
COMPUTER ROOM HVAC UPGRADES FOR
21203
100% OWNER REVIEW
As Indicated
JANUARY 25, 2023
1937.08
GFB
MECHANICAL
SCHEDULES
005A
ELECT.
005B
BATTERY
TELE/COMM.
ROOM
005C
ELECT/TELEPHONE
006A
CONTROL
STORAGE
TV
CONTROL
CORRIDOR
VENDVEND
X X
X X
X X
X X
X X
X X
X X
X
DN
ET
P
P
V-5
V-4 6"∅
4"∅
6"∅ 6"∅
4"∅
005A
ELECT.
005B
BATTERY
TELE/COMM.
ROOM
005C
ELECT/TELEPHONE
006A
CONTROL
STORAGE
TV
CONTROL
CORRIDOR
SMW
M1.0
XXXX - XX
SMW
CITY PROJECT NO.
ENGINEERING and CAPITAL
IMPROVEMENTS DEPARTMENT
CITY of ST. PETERSBURG
DATE:
DATE:
DATE:DRAWN BY:
CHECKED BY:
DESIGNED BY: DATE:
DRAWING No.
SCALE:
R E V I S I O N S BY DATE
APPROVED BY:
© 2023 Engineering Matrix, Inc.
CONSULTING ENGINEERS
SHEET NO.:
PROJECT NO.:
SHEET TITLE:
CITY HALL
175 5th STREET NORTH, ST. PETERSBURG, FL 33701
COMPUTER ROOM HVAC UPGRADES FOR
21203
100% OWNER REVIEW
As Indicated
JANUARY 25, 2023
1937.08
GFB
BASEMENT
FLOOR PLANS -
MECHANICAL
N
1/4" = 1'-0"M1.0
1 BASEMENT FLOOR PLAN - MECHANICAL
BASEMENT KEY
N
1/4" = 1'-0"M1.0
BASEMENT FLOOR
DEMOLITION PLAN - MECHANICAL
| Sheets |
| - - COVER |
| A1.0 - BASEMENT FLOOR PLAN |
| GA1.0 - GENERAL ARCHITECTURAL |
| COSP City Hall Computer Room HVAC upgrades MEP Dwgs.pdf |
| M0.0 |
| Sheets and Views |
| M0.0 |
| M0.1 |
| Sheets and Views |
| M0.1 |
| M0.2 |
| Sheets and Views |
| M0.2 |
| M1.0 |
| Sheets and Views |
| M1.0 |
| E0.0 |
| E1.0 |
File details come from the government source that posted it. Updated .