Specifications Part 3 07073.pdf

PDF 5 MB Posted

Attached to
Belgravia - Remediation System Construction Support
Solicitation number
RFQ 171 180000000015 6
Issued by
Van Buren County, South Haven City, Michigan

About this file

This technical specifications document pertains to an electromagnetic thermal remediation system project for the Belgravia Site in South Haven, Michigan, involving well construction, completion details, and electrical infrastructure requirements. The project involves the installation of 84 to 95 electrode wells (WFL-01), 6 digitam temperature sensor wells, 54 to 62 multiphase extraction wells, 6 to 8 horizontal extraction wells (WLF-01), and contingency extraction wells as determined in the field. The electrode wells feature 8-inch diameter electrodes with 10-inch inside diameter tooling, water return lines, and sand/graphite mixture backfill. Temperature wells consist of 1.5-inch carbon steel casing extending to 37.5 feet below ground surface with male NPT completion. Extraction wells utilize 4-inch nominal diameter wire-wrapped 304 stainless steel screens with 0.010-inch slots for contingency wells and 0.006-inch slots for multiphase wells. Horizontal extraction wells are 2-inch diameter high-temperature fiberglass with 0.010-inch slot size. All materials specifications include high-temperature Portland Type II/IV grout, various grades of silica sand, bentonite chips, and fiberglass pipe with specific thread configurations and compression requirements.

The electrical infrastructure consists of a 2500 kilovolt-ampere utility transformer connected to a power distribution panel serving four power distribution substations with a total estimated load of 2,214 kilovolt-amperes and 2,668 amperes to support 168 electrodes and process equipment. The system includes two 240-kilowatt Electrosteam generators, three treatment systems capable of supplying 56 electrodes each at 462 kilowatts and 586 amperes, and comprehensive cabling specifications using 350 to 750 kilovil-circular mil copper and aluminum conductors with appropriate insulation ratings. All electrical equipment must comply with applicable federal, state, and local building codes and the National Electrical Code, with grounding systems installed at minimum 25 feet from the electrode wellfield. The project documentation includes well construction summaries detailing existing monitoring wells with depths ranging from 6.5 to 72 feet, various casing materials including PVC and galvanized steel, and seal configurations using bentonite chips or cement grout.

View the file

Other files

File Type Posted
Specifications Part 4 07073.pdf PDF
07073 Addemdum 3.pdf PDF
Addendum 2 07073.pdf PDF
Specifications Part 2 07073.pdf PDF
Specifications Part 7 07073.pdf PDF
IMPORTANT NOTICE - SIGMA VSS.docx DOCX document
Specifications Part 5 07073.pdf PDF
Addendum 1.pdf PDF
Addendum 4.pdf PDF
Specifications Part 1 07073.pdf PDF
Advertisement 07073.pdf PDF
Specifications Part 6 07073.pdf PDF
Addendum 5.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES:

1. MATERIAL TYPES

A. GROUT

- HIGH TEMPERATURE PORTLAND TYPE II/IV OR EQUIVALENT (NO

BENTONITE)

B. SAND

- ELECTRODE WELLS: 10 / 20 SILICA SAND OR EQUIVALENT

- FINE SAND SEAL: 40/60 SILICA SAND

- EXTRACTION WELLS: 40/60 SILICA SAND

C. GRAPHITE / SAND MIXTURE

- 1:7 GRAPHITE TO SAND RATIO BY VOLUME

D. BENTONITE: MEDIUM CHIPS

2. ELECTRODE WELLS

A. MINIMUM 10" INSIDE DIAMETER TOOLING TO ACCOMMODATE 8" DIAMETER

ELECTRODE

B. WATER RETURN LINE INCLUDED TO ALLEVIATE

POSSIBLE LOCALIZED PRESSURE BUILD UP WITHIN ELECTRODE WELL.

3. TEMPERATURE WELLS

A. MINIMUM 4" DIAMETER BOREHOLE

B. 1.5" CARBON STEEL CASING

C. THREADS CAN BE NPT OR FLUSH JOINT, EXCEPT STICKUP MUST BE MALE

NPT

D. ALL JOINTS TO BE TIGHTENED WITH PIPE WRENCH USING PIPE THREAD

COMPOUND AND PTFE TAPE

4. EXTRACTION WELLS

A. MINIMUM 8" DIAMETER BOREHOLE

B. 4" CASING SIZE SCREEN

C. 4" NPT FEMALE X WELD PLATE ENDS

D. NOMINAL 4" DIAMETER WIRE-WRAPPED 304 STAINLESS STEEL

0.010''-SLOTTED SCREEN ON CONTINGENCY EXTRACTION WELLS AND

0.006"-SLOTTED SCREEN ON MULTIPHASE EXTRACTION WELLS

E. FITTINGS BETWEEN PIPE SECTIONS ARE 4 THREAD PER INCH (TPI) FLUSH

THREADED UNLESS SPECIFIED OTHERWISE (IE M NPT OR PLUG)

Water Return Line (1)

Electrode Power Leads (2)

Water Injection Lines (2)

Top of Electrode

5' BGS

8"-Dia x 10' Long Electrode

Water Return Slots

Water Injection Slots

Water Injection Slots

Fine Sand Seal 2' to 2'6" BGS

Wood 2''x4''-2' Long

Grout 0' to 2' BGS

ELECTRODE WELL

W/ 2 ELECTRODES

WFL-01 QUANTITY - 84

WFL-01 ALT. QUANTITY - 95

Sand/Graphite Mixture 5'6" to 14'6" BGS

4' X 2'' Schedule 40 PVC Pipe Electrode Suspension Ropes (2)

2 [ft]

4 [ft]

6 [ft]

8 [ft]

10 [ft]

12 [ft]

14 [ft]

16 [ft]

18 [ft]

20 [ft]

36 [ft]

2' Stick Up 1.5" Male NPT Completion

1.5" Carbon Steel Casing

Grout Surface to 37'6" BGS

Bottom of Carbon Steel Casing

37' BGS

Bottom of Well

37'6" BGS

Carbon Steel Cap

DIGITAM™ TEMPERATURE

SENSOR WELL

WFL-01 QUANTITY - 6

WFL-01 ALT. QUANTITY - 6

6 [ft]

Bottom of Electrode

15' BGS

12 [ft]

2 [ft]

8 [ft]

4 [ft]

10 [ft]

14 [ft]

16 [ft]

18 [ft]

20 [ft]

22 [ft]

24 [ft]

26 [ft]

28 [ft]

30 [ft]

32 [ft]

34 [ft]

38 [ft]

40 [ft]

2' Stick Up 4" Male NPT Completion

36 [ft]

34 [ft]

26 [ft]

30 [ft]

38 [ft]

4" Carbon Steel Pipe

4" 304 Stainless Steel 0.006''-Slotted Screen

Top of Electrode

23' BGS

Bottom of Screen

36' BGS

Bottom of 1' CS Sump

37' BGS

40 [ft]

28 [ft]

24 [ft]

22 [ft]

32 [ft]

Grout 0' to 3' BGS

Top of Screen

4' BGS

Sand 3' to 36' BGS

Bentonite

36'-37'6" BGS

Bottom of Well

37'6" BGS

Electrode Power Leads (1)

Electrode Ropes (1)

Water Return Slots

8"-Dia x 10' Long Electrode

Water Injection Slots

Water Injection Slots

Sand/Graphite Mixture 23'6" to 32'6" BGS

Bottom of Electrode

33' BGS

MULTIPHASE

EXTRACTION WELL

WFL-01 QUANTITY - 54

WFL-01 ALT. QUANTITY - 62

Sand 14'6" to 23'6" BGS

Bottom of Boring

33.6' BGS

Sand 2'6" to 5'6" BGS

2' Stick Up 4" Male NPT Completion

4" Carbon Steel Pipe

Bottom of Screen 2' Below Sand / Gravel Layer (~26 ft

BGS Where Encountered) Bottom of 1' CS Sump

29' BGS

Grout 0' to 23' BGS

Bentonite

28'-29'6" BGS

Bottom of Well

29'6" BGS

CONTINGENCY

EXTRACTION WELL

QUANTITY - TBD IN FIELD

4" 304 Stainless Steel 0.010''-Slotted Screen

Top of Screen 2' Above Sand / Gravel Layer (~26 ft BGS Where Encountered)

Sand 23' to 28' BGS

WCD-01

McMillan-McGee Corp.

Electromagnetic Systems and Services

For the Energy and Environmental Industries

4895 - 35B Street SE Calgary, AB T2B 3M9 Canada www.mcmillan-mcgee.com Ph: 403.569.5100, Fx: 403.272.7201

Global Remediation Technologies Inc.

Belgravia Site

South Haven, MI

ET-DSP™ Well Completion Drawing

2' FIBERGLASS STICK UP

2" MALE NPT COMPLETION

2" FIBERGLASS

FEMALE TEE

2" CAP OR PLUG

A

A'

2" CAP OR PLUG

SECTION A-A'

GEOFABRIC

CLEAR STONE

FILTER PACK

(AASHTO #8)

2" NATIVE MATERIAL

2" NATIVE MATERIALGEOFABRIC

2" DIAMETER FIBERGLASS WELL

SCREEN, 0.010" SLOT SIZE

6 IN

VARYING LENGTHS

CLEAR STONE

FILTER PACK

2 IN DIAMETER FIBERGLASS

WELL SCREEN, 0.010 IN SLOT

SIZE; Bottom of Pipe Placed at

1.5' BGS

GENERAL NOTES:

1. MATERIAL TYPES

A. FILTER PACK

- 1/4 IN CLEAR STONE (AASHTO #8)

B. GEOFABRIC

- COMMERCIAL GRADE NON-WOVEN POLYESTER

2. HORIZONTAL WELLS

A. 2 IN DIAMETER HIGH TEMPERATURE FIBERGLASS

0.010 IN SLOT SIZE

B. 6 IN WIDE TRENCH, OR AS APPROPRIATE WITH

MACHINERY AVAILABLE

C. BOTTOM OF PIPE PLACED AT 1.5 FT BGS

D. 2 IN CLEAN NATIVE MATERIAL TO BE PLACED ON

TOP OF GEOFABRIC AND COMPACTED

E. REFER TO DRAWING WFL-01 OR WFL-01 ALT FOR

TRENCH/WELL LENGTHS

HORIZONTAL EXTRACTION WELLS

WLF-01 QUANTITY - 6

WLF-01 ALT. QUANTITY - 8

VAPOR CAP

VAPOR CAP

WCD-02

McMillan-McGee Corp.

Electromagnetic Systems and Services For the Energy and Environmental Industries

4895 - 35B Street SE Calgary, AB T2B 3M9 Canada www.mcmillan-mcgee.com Ph: 403.569.5100, Fx: 403.272.7201

Global Remediation Technologies Inc.

Belgravia Site

ET-DSP™ Well Completion Drawing

WHD-01

McMillan-McGee Corp.

Electromagnetic Systems and Services

For the Energy and Environmental Industries

4895 - 35B Street SE Calgary, AB T2B 3M9 Canada www.mcmillan-mcgee.com Ph: 403.569.5100, Fx: 403.272.7201

Global Remediation Technologies Inc.

Belgravia Site

ET-DSP™ Well Head Details

V

T

WHD-02

McMillan-McGee Corp.

Electromagnetic Systems and Services

For the Energy and Environmental Industries

4895 - 35B Street SE Calgary, AB T2B 3M9 Canada www.mcmillan-mcgee.com Ph: 403.569.5100, Fx: 403.272.7201

Global Remediation Technologies Inc.

Belgravia Site

ET-DSP™ Well Head Details

CELLULAR CONCRETE VAPOR CAP

CROSS SECTION

WOOD FORMS

EDGE OF VAPOR

CAP

VCD-01

McMillan-McGee Corp.

Electromagnetic Systems and Services

For the Energy and Environmental Industries

4895 - 35B Street SE Calgary, AB T2B 3M9 Canada www.mcmillan-mcgee.com Ph: 403.569.5100, Fx: 403.272.7201

Global Remediation Technologies Inc.

Belgravia Site

ET-DSP™ Vapor Cap Detail

Note 2

LV Multi-tap

HV 480V

666 KVA

Z = 8.1%

Note 7

BUS A

ABB 3P-MCS

T6H800DW

XFRMR AB-T1

ABB SACE E3S-A 32

480V/3000A

Main Breaker

Trip Level 3000A

Transformer A-B-T1

PDS-01A

800A

CB-A01

CB-T1

400A

CB-01

BUS B

CB-T2

CB-B01

400A

LV Multi-tap

HV 480V

666 KVA

Z = 8.1%

LP 01

Note 7

ABB 3P-MCS

T6H800DW

XFRMR CD-T2

BUS C

CB-C01

400A

BUS D

CB-D01

400A

Transformer C-D-T2

PDS-01B

800A

CB-02

Note 2

PDP XXX-01

TOTAL ESTIMATED LOAD

168 Electrodes, Process Equip. = 2214kVA / 2668 A

1. Construction and material shall comply with applicable Federal, State and Local building codes and the NEC.

2. Cable from PDP XXX-01 Distribution Breakers to PDS XXX-01, 02 &

03; Two (2) parallel 3C-350 kcmil c/w #2 AWG AL Ground to each A-B-T1 and

C-D-T2 transformer: STR AL NUAL Alcan Type ACWU90 XLPE INS AIA BLK

PVC JKT 600V 90C HL CSA C22.2 NO.51. Above ground.

3. Cable from PDS units to Wellfield Electrodes: 1C, No. 1/0 AWG CU

Type DAA1048B EXANE XLPE STR TNC 110C FT4 600V CSA CSA/UL or equivalent. Above ground.

4. ET-DSP neutral cables to wellfield: 1C, No. 1/0 AWG CU Type

DAA1048B EXANE XLPE STR TNC 110C FT4 600V CSA CSA/UL or equivalent. Above ground.

5. Maximum estimated operating load for ET-DSP: (168 electrodes) during operations is 1386 kW, maximum 8.25 kW to any electrode.

6. All electrical equipment shall be grounded in accordance with NEC.

Equipment is NOT to be earth grounded within 25 ft of electrode wellfield.

7. ET-DSP neutral grounding configuration determined during system commissioning and shall include all metal constructed extraction wells.

ET-DSP neutral will originate from the secondary XO point of the PDS "A" and

"B" transformers and is isolated from the electrical service ground.

8. Cable from the 2500 kVA Utility transformer (XFR-01) to Power

Distribution Panel (PDP XXX-01) main breaker; eight (8) parallel sets of 3 conductor 750 kcmil CU + one (1) 350 kcmil CU conductor in a conductor/conduit or teck cable installation.

9. Cable from Power Distribution Panel (PDP XXX-001) to Field

Disconnect 01 (FD-01); Two (2) parallel 3c-250 kcmil c/w #2 awg Al ground.

STR AL NUAL Alcan Type ACWU XLPE INS AIA BLK PVC JKT 600V 90C HL

CSA C22.2 NO.51. Above ground.

10. Service ground to be installed at PDP XXX-01 with ground rod(s).

Ground rod(s) are NOT to be installed within 25 feet of the electrode wellfield.

Install a 3/0 ground wire from the PDP XXX-01 ground lug to the service ground. Install an additional 2/0 ground wire from the PDP XXX-01 skid base to the skid base of PDP XXX-02, PDS XXX-01, 02, 03, 04, ESG 01, ESG 02 and Treatment skids.

11. Utility transformer (XFR-01) secondary neutral conductor (grounded conductor) to PDP XXX-01; Minimum of one (1) 350 kcmil CU conductor per parallel set of conductors. The neutral connection point inside the PDP will be bonded to the ground connection point of the PDP with a 350 kcmil CU ground wire.

12. Cable from Power Distribution Panel (PDP XXX-01) distribution breakers to Electrosteam Generators 01 & 02: Two (2) parallel 3c-250 kcmil c/w #2 awg Al ground. STR AL NUAL Alcan Type ACWU XLPE INS AIA BLK

PVC JKT 600V 90C HL CSA C22.2 NO.51. Above ground.

13. Cable from Field Disconnect 01 (FD-01) to the Treatment System

(TRT-01): Two (2) 3c-250 kcmil c/w #2 awg Al ground. STR AL NUAL Alcan

Type ACWU XLPE INS AIA BLK PVC JKT 600V 90C HL CSA C22.2 NO.51.

Above ground.

General Notes

Note 8 Note 11

Note 10

Note 10

PDS 60E XXX-01

Note 2

LV Multi-tap

HV 480V

666 KVA

Z = 8.1%

Note 7

BUS A

ABB 3P-MCS

T6H800DW

XFRMR AB-T1

Transformer A-B-T1

PDS-02A

800A

CB-A01

CB-T1

400A

CB-05

BUS B

CB-T2

CB-B01

400A

LV Multi-tap

HV 480V

666 KVA

Z = 8.1%

LP 01

Note 7

ABB 3P-MCS

T6H800DW

XFRMR CD-T2

BUS C

CB-C01

400A

BUS D

CB-D01

400A

Transformer C-D-T2

PDS-02B

800A

CB-06

Note 2

PDS 60E XXX-02

Pad Mount

Utility Transformer

Power Distribution from Utility

L.V 277/480, 3012 A

H.V. (TBD) kV, (TBD) A

2500 KVA 3P 60HZ 65C Rise

Transformer

Z = 5.5% Minimum

(TBD)A

XFR-01

Electrosteam #1

ESG - 01

400A

CB-03

ELECTROSTEAM

GENERATOR #1

MAXIMUM 400A/480V

FLA = 300A

240kW

ESG - 01

Electrosteam #2

ESG - 02

400A

CB-04

ELECTROSTEAM

GENERATOR #2

MAXIMUM 400A/480V

FLA = 300A

240kW

ESG - 02

Note 12

Note 12

Transformer A-B-T1

PDS-03A

800A

CB-07

Transformer C-D-T2

PDS-03B

800A

CB-08

LV Multi-tap

HV 480V

666 KVA

Z = 8.1%

LV Multi-tap

HV 480V

666 KVA

Z = 8.1%

ABB 3P-MCS

T6H800DW

XFRMR AB-T1

ABB 3P-MCS

T6H800DW

XFRMR CD-T2

CB-A01

400A

CB-C01

400A

CB-B01

400A

CB-D01

400A

BUS A

BUS B

BUS C

BUS D

Note 7

Note 7

CB-T1

CB-T2

LP 01

PDS XXX-03

(56 Electrodes, 462kW, 586A)

TREATMENT SYSTEM #1

MAXIMUM 400A/480V

FLA = 301A

250kVA

TRT - 01

Note 9

Note 2

Note 2

Treatment System 01

TRT - 01

400A

FD-01

Note 13

(56 Electrodes, 462kW, 586A)

(56 Electrodes, 462kW, 586A)

APEGA PERMIT NUMBER:

ESL-01

McMillan-McGee Corp.

Electromagnetic Systems and Services

For the Energy and Environmental Industries

4895 - 35B Street SE Calgary, AB T2B 3M9 Canada www.mcmillan-mcgee.com Ph: 403.569.5100, Fx: 403.272.7201

Global Remediation Technologies Inc.

SCALE:P09178

PROJECT:

Belgravia Site

South Haven, MI

NOT TO SCALE

ET-DSP™ Electrical Single line

TITLE:

CLIENT:

SHEET:

REV. DWN

DESCRIPTION

(YR/MM/DD)

B1

RVD APRD

DP CC EJR

95% EXPANDED DESIGN - NFC

16/09/14

C1

DP CC ER

100% DESIGN

17/06/13

Bidding and Contract Document (R 9/16) Project Name: Belgravia File No. 761/07073.SAR

APPENDIX XI

SITE PHOTOGRAPHS

125 Elkenburg, Bike Path, Overton Property Pre‐Thermal Treatment Condition

Belgravia Site Back Yard Looking North

Belgravia Site Back Yard Looking North‐East

Belgravia Site Back Yard Looking North‐West

Bike Path Landscape Looking South‐West to Belgravia Site

Overton Property and Bike Path Looking South

Bike Path Looking South, Belgravia Site in Back Ground South‐West

Underground Piping Associated with Existing SVE System

Bidding and Contract Document (R 9/16) Project Name: Belgravia File No. 761/07073.SAR

APPENDIX XII

SITE REPORTS

Table 1: Well Construction Summary Belgravia Site

South Haven, Van Buren County, Michigan

Well ID Well Depth

(feet) Nominal Well

Diameter (Inches) Well Riser Material

Upper Annulus Seal Permanent Casing

MW-1R 7 2 PVC Bentonite Chip No MW-10R 8 2 PVC Bentonite Chip No MW-11R 7 2 PVC Bentonite Chip No MW-16R 7 2 PVC Bentonite Chip No MW-17R 7 2 PVC Bentonite Chip No MW-18R 7 2 PVC Bentonite Chip No MW-19R 7 2 PVC Bentonite Chip No MW-20R 7 2 PVC Bentonite Chip No MW-30 14.5 2 PVC Cement Grout No MW-31 70 2 PVC Cement Grout Yes, 7" DIA Steel MW-32 67 2 PVC Bentonite Chip No

MW-33D 68 2 PVC Cement Grout Yes, 7" DIA Steel MW-33I 32 2 Galv. Steel Cement Grout Yes, 7" DIA Steel MW-33S 7 2 PVC Cement Grout No MW-34 13 2 PVC Bentonite Chip No

MW-35S 7 2 PVC Bentonite Chip No MW-35D 67 2 PVC Cement Grout No MW-36S 6.5 2 PVC Bentonite Chip No MW-36D 66 2 PVC Cement Grout Yes, 7" DIA Steel MW-37I 27 2 Galv. Steel Cement Grout No MW-37D 64 2 PVC Cement Grout No MW-38 72 2 PVC Cement Grout No MW-39 29 2 PVC Cement Grout Yes, 7" DIA Steel MW-40 7 2 PVC Bentonite Chip No MW-41 7 2 PVC Bentonite Chip No MW-42I 32 2 Galv. Steel Cement Grout Yes, 7" DIA Steel MW-43I 29 2 Galv. Steel Cement Grout Yes, 7" DIA Steel MW-44I 32 2 Galv. Steel Cement Grout Yes, 7" DIA Steel MW-45I 30 2 PVC Bentonite Chip No MW-45S 7.3 2 PVC Bentonite Chip No MW-46I 32 2 Galv. Steel Bentonite Chip Yes, 7" DIA Steel MW-47I 23 2 PVC Cement Grout No MW-48I 27 2 PVC Cement Grout No MW-49I 23 2 PVC Cement Grout No MW-49S 10 2 PVC Cement Grout No MW-50I 31 2 PVC Bentonite Chip No MW-50S 7 2 PVC Bentonite Chip No MW-51 7 2 PVC Bentonite Chip No MW-52 7 2 PVC Bentonite Chip No MW-53 7.5 2 PVC Bentonite Chip No MW-54 7 2 PVC Bentonite Chip No PSW-1 33 2 Galv. Steel Cement Grout Yes, 7" DIA Steel PSW-2 33 2 Galv. Steel Cement Grout Yes, 7" DIA Steel PSW-3 28 2 Galv. Steel Cement Grout Yes, 7" DIA Steel PSW-4 28 2 Galv. Steel Cement Grout Yes, 7" DIA Steel PSW-5 31 2 Galv. Steel Bentonite Chip Yes, 7" DIA Steel RW-1 32 4 Galv. Steel Cement Grout Yes, 7" DIA Steel RW-2 32 4 Galv. Steel Cement Grout Yes, 7" DIA Steel RW-3 32 4 Galv. Steel Cement Grout Yes, 7" DIA Steel cweber Typewritten Text