Solicitation Attachment B - Drawings.pdf
PDF 9 MB Posted
- Solicitation number
- 36C24823R0040
About this file
This document package includes construction drawings and specifications for a renovation project at a Department of Veterans Affairs medical center. The project involves renovating existing rooms to create an emergency management site that complies with security requirements. Work includes demolition, new walls, finishes, life safety equipment, mechanical and electrical system upgrades. Construction types, codes and standards are identified along with occupancy classifications, allowable heights and areas, means of egress requirements. The drawings depict existing conditions, demolition plans, new construction plans, life safety diagrams, architectural details, and mechanical, electrical and telecommunications plans.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXTERIOR ELEVATION
INTERIOR ELEVATION
SECTION/DETAIL NUMBER
DRAWING NUMBER
EQUIPMENT TAG
COLUMN GRID
NOTE
WINDOW OPENING
DOOR OPENING
ROOM NAME
ROOM NUMBER
WALL TYPE
CEILING HEIGHT
FINISH DESIGNATION
X
10'-8"
X
X
XX.X-X
XX
X
1/A101
X
A101
XX
TOILET ACCESSORY TAGX SIGNAGE TAG
A101
SIM
X
PROJECT LOCATION
N
PROJECT AREA
N
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
R O G E
R
A. REP
S T I E N
AR0012462
VA Project No.
RDC/JPA Project No.
Department of Veterans Affairs Medical Center
ABOVE GROUP, INC.
MECHANICAL ELECTRICAL PLUMBING
305 EAST DRIVE, SUITE H
MELBOURNE, FL 32904
321.345.9026 P
ARCHITECTURE PLANNING INTERIOR DESIGN
524 FERNWOOD AVENUE
ALTAMONTE SPRINGS, FLORIDA 32701
407.830.6522 P
RDC / JOHN POE ARCHITECTS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/2
/2
:2
:5
P
M
Lakemont Emergency Management Buildout
06/23/2022
COVER SHEET
G001
NSJR
675-21-803
Orlando, Florida
Lakemont Emergency Management Buildout 2500 S. Lakemont Avenue Orlando, Florida PROJECT #: 675-21-803
Frank Wales - Facilities Deputy Chief
CONSTRUCTION
DOCUMENTS
21020.00
G001 COVER SHEET
G100 CODE DATA/ LIFE SAFETY DRAWING
AD101 DEMOLITION PLAN
A101 NEW WORK PLAN
A121 REFLECTED CEILING PLAN
A201 SHIELDING DETAILS
AF101 FINISH PLAN
AS101 SIGNAGE PLAN
FP001 FIRE PROTECTION LEGENDS, SYMBOLS, & GENERAL NOTES
FPD101 FIRE PROTECTION FLOOR PLAN - DEMO
FP101 FIRE PROTECTION FLOOR PLAN - NEW WORK
FP501 FIRE PROTECTION DETAILS
M-001 MECHANICAL LEGENDS AND SYMBOLS
MD111 HVAC DEMO PLAN - 1ST FLOOR
MH111 DUCTWORK PLAN - 1ST FLOOR
M-501 MECHANICAL DETAILS
M-801 MECHANICAL SCHEDULES & CONTROLS
E-001 ELECTRICAL LEGENDS & SYMBOLS
E-002 ELECTRICAL GENERAL NOTES
ED101 ELECTRICAL FLOOR PLAN - DEMO
EP100 ELECTRICAL OVERALL PLAN - FEEDER ROUTING
EL101 ELECTRICAL FLOOR PLAN - LIGHTING
EP101 ELECTRICAL FLOOR PLAN - POWER
E-501 ELECTRICAL DETAILS
E-601 ELECTRICAL SCHEDULES
E-901 ELECTRICAL DIAGRAMS
FA001 FIRE ALARM LEGEND & SYMBOLS
FAD101 FIRE ALARM FLOOR PLAN - DEMO
FA100 FIRE ALARM FLOOR PLAN - OVERALL
FA101 FIRE ALARM FLOOR PLAN - NEW
T-001 TELECOM LEGENDS & SYMBOLS
TD101 TELECOM FLOOR PLAN - DEMO
TN100 TELCOM FLOOR PLAN - OVERALL PLAN
TN101 TELECOM FLOOR PLAN - DATA/ACCESS
TS101 TELECOM FLOOR PLAN - INTRUSION/ACCESS
T-501 TELECOM DETAILS
GENERAL CONSTRUCTION NOTES
7. CONTRACTOR IS RESPONSIBLE TO VERIFY SIZES OF ALL EQUIPMENT, ETC. TO
BE INSTALLED AS PART OF THIS PROJECT, AND WHERE NECESSARY, MAKE
SPECIAL PROVISIONS TO INSTALL EQUIPMENT THAT IS TOO LARGE TO FIT
THROUGH FINISHED OPENINGS.
8. CONTRACTOR SHALL PROVIDE WOOD BLOCKING AT TOILET ACCESSORIES,
HAND RAILS, BUMPER RAILS, SHELVING, CASEWORK, MOUNTING BRACKETS
AND OTHER WALL MOUNTED ITEMS, AS INDICATED IN THE CONTRACT
DOCUMENTS AND AS RECOMMENDED BY PRODUCT MANUFACTURERS. ALL
WOOD BLOCKING SHALL BE FIRE RETARDANT TREATED.
9. ALL EXPOSED NEW WORK IS TO RECEIVE NEW FINISHES UNLESS
SPECIFICALLY NOTED OTHERWISE. iF NO FINISH IS INDICATED AT A
PARTICULAR SURFACE, CONTRACTOR SHALL PROVIDE FINISH(S) AS
INDICATED AT SIMILAR CONDITIONS.
10. CONTRACTOR SHALL PROVIDE COMPLETE AND FULLY OPERATIONAL
SYSTEMS WHICH COMPLY WITH STATED CODES AND REGULATIONS. WHERE
THE OMISSION OF A PART OR ELEMENT OF A SYSTEM WOULD RESULT IN THE
NON-OPERATION, OR INCORRECT OPERATION OF A SYSTEM, CONTRACTOR
SHALL INCLUDE SAID PART OR ELEMENT AS PART OF THE WORK.
11. ALL PENETRATIONS THROUGH NEW AND/OR EXISTING SMOKE OR FIRE RATED
WALLS SHALL BE SMOKE/FIRE STOPPED AS REQUIRED BY THE RATING OF
THE WALL.
12. FIRE PROTECTION CONTRACTOR'S SPRINKLER DESIGN WILL BE SUBJECT TO
AN INDEPENDENT REVIEW BY A CERTIFIED FIRE PROTECTION ENGINEER
RETAINED BY THE OWNER. THE FIRE PROTECTION CONTRACTOR IS
RESPONSIBLE FOR MAKING ANY REQUIRED CHANGES TO THE DESIGN AS
IDENTIFIED BY THE OWNER'S FIRE PROTECTION ENGINEER AS NECESSARY
FOR COMPLIANCE WITH SPECIFIED NFPA REQUIREMENTS.
* PLEASE NOTE THAT THE TERM PROJECT ENGINEER REFERS TO THE
CONTRACTING OFFICER'S REPRESENTATIVE (C.O.R.).
1. ALL WORK SHALL COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE,
INTERNATIONAL BUILDING CODE, ICD 705, AND OTHER CODES AS IDENTIFIED
IN VHA PROGRAM GUIDE PG-18-3, TOPIC 01, CODES, STANDARDS AND
EXECUTIVE ORDERS WHICH CAN BE FOUND ON THE DEPARTMENT OF
VETERAN AFFAIRS, TECHNICAL INFORMATION LIBRRARY WEBSITE.
2. ALL WORK SHALL COMPLY WITH REQUIREMENTS OF THE LATEST
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARD (ABAAS) AND
DEPARTMENT OF VETERANS AFFAIRS BARRIER FREE DESIGN GUIDE PG-18-13
WHICH CAN BE FOUND ON THE DEPARTMENT OF VETERANS AFFAIRS
TECHNICAL INFORMATION LIBRARY WEBSITE.
3. CONTRACTOR IS RESPONSIBLE TO VISIT THE SITE, EXAMINE AND ACCEPT
EXISTING CONDITIONS PRIOR TO BIDDING. SITE VISITS TO BE COORDINATED
WITH THE CONTRACTING OFFICER AND CONTRACTING OFFICER'S
REPRESENTATIVE.
4. CONTRACTOR IS RESPONSIBLE TO REPAIR AND/OR REFINISH, TO MATCH
ADJACENT EXISTING SURFACES, ANY EXISTING MATERIALS TO REMAIN THAT
ARE DAMAGED DURING THE COURSE OF DEMOLITION OR NEW WORK.
5. WHERE REMOVAL OF EXISTING WORK IS REQUIRED FOR INSTALLATION OF
NEW WORK, CONTRACTOR SHALL REPAIR EXISTING CONSTRUCTION TO
REMAIN OR PROVIDE NEW CONSTRUCTION TO MATCH EXISTING ADJACENT
SURFACES TO REMAIN.
6. CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY ALL CONDITIONS AND
DIMENSIONS PRIOR TO ORDERING, FABRICATING OR INSTALLING NEW
MATERIALS.
DRAWING INDEXVICINITY MAP
KEY PLAN - FIRST FLOOR
RECORDS MANAGEMENT LANGUAGE FOR CONTRACTS (NARA)
7. The Government Agency owns the rights to all electronic information (electronic data, electronic information systems, electronic databases, etc.) and all supporting documentation created as part of this contract. Contractor must deliver sufficient technical documentation with all data deliverables to permit the agency to use the data.
8. Contractor agrees to comply with Federal and Agency records management policies, including those policies associated with the safeguarding of records covered by the Privacy Act of 1974. These policies include the preservation of all records created or received regardless of format [paper, electronic, etc.] or mode of transmission [e-mail, fax, etc.] or state of completion [draft, final, etc.].
9. No disposition of documents will be allowed without the prior written consent of the Contracting Officer. The Agency and its contractors are responsible for preventing the alienation or unauthorized destruction of records, including all forms of mutilation. Willful and unlawful destruction, damage or alienation of Federal records is subject to the fines and penalties imposed by 18 U.S.C. 2701. Records may not be removed from the legal custody of the Agency or destroyed without regard to the provisions of the agency records schedules.
10. Contractor is required to obtain the Contracting Officer's approval prior to engaging in any contractual relationship (sub-contractor) in support of this contract requiring the disclosure of information, documentary material and/or records generated under, or relating to, this contract. The Contractor (and any sub-contractor) is required to abide by Government and Agency guidance for protecting sensitive and proprietary information.
The following standard items relate to records generated in executing the contract and should be included in a typical Electronic Information Systems (EIS) procurement contract:
1. Citations to pertinent laws, codes and regulations such as 44 U.S.C chapters 21, 29, 31 and 33; Freedom of Information Act (5 U.S.C. 552); Privacy Act (5 U.S.C. 552a); 36 CFR Part 1222 and Part 1228.
2. Contractor shall treat all deliverables under the contract as the property of the U.S.
Government for which the Government Agency shall have unlimited rights to use, dispose of, or disclose such data contained therein as it determines to be in the public interest.
3. Contractor shall not create or maintain any records that are not specifically tied to or authorized by the contract using Government IT equipment and/or Government records.
4. Contractor shall not retain, use, sell, or disseminate copies of any deliverable that contains information covered by the Privacy Act of 1974 or that which is generally protected by the Freedom of Information Act.
5. Contractor shall not create or maintain any records containing any Government Agency records that are not specifically tied to or authorized by the contract.
6. The Government Agency owns the rights to all data/records produced as part of this contract.
Revisions Date
Bid Set 06/23/2022
Attachment - B Drawings
0-HR Smoke Partition - NFPA 101-8.4
1-HR Smoke Barrier - NFPA 101-8.5
1-HR Fire Barrier - NFPA 101-8.3
2-HR Fire Barrier - NFPA 101-8.3
Means of Egress
Existing Wall to Remain
New Wall
Area Not In Contract
Fire Extinguisher Location
Exit Sign Location
LIFE SAFETY LEGEND
F.E.
Mechanical
Mechanical
Electrical
Mechanical
Storage
Receiving
Storage
Storage
Storage
Storage
Janitor
Mechanical
Common Path of Travel Max. Allowable = 100'
Actual = 90'
Travel Distance to Exit Max. Allowable = 300'
Actual = 193'
Travel Distance to Exit Max. Allowable = 300'
Actual = 230'
F.E.
F.E.
F.E.
Travel Distance to Exit Max. Allowable = 300'
Actual = 63'
Project Data Project Name: Lakemont Emergency Management Buildout Project Number: VA# 675-21-803 / RDCJPA# 21020.00 Project Address: Orlando VA Medical Center
Lakemont Facility 2500 S. Lakemont Ave.
Orlando, FL 32814
Project Description: Renovation of existing rooms to create a space that complies with ICD/ICS 705 security requirements and the installation of required communications platforms IAW OSTP/OMB Directive 16-1.
Applicable Building Codes Authority Having Jurisdiction: Orlando – Veterans Affairs Medical Center Building Code: NFPA 101, Life Safety Code, 2021 Edition
NFPA 96, Standard for Ventilation Control and Fire International Building Code, 2015 Edition
Accessibility Code: Architectural Barriers Act Accessibility Standards w. VA supplement PG 18-13
Structural Code: N/A Elevator Code: N/A Energy Code: ASHRAE 90.1-2013 (target 30% better than baseline) Mechanical Code: 2015 International Mechanical Code Plumbing Code: 2015 International Plumbing Code
2015 Fuel Gas Code Electrical Code: 2017 NFPA 70 National Electrical Code Fire Code: 2019 NFPA 72 National Fire Alarm Code
2010 NFPA 13, 13D & 13R
Life Safety Summary Occupancy: Business (Concentrated) Construction Type: I (332) (NFPA 5000, Table 7.2.1.1) Allowable Height/Stories: Unlimited (NFPA 5000, Table 7.4.1.4.5.1) Actual Height: 58'-8" Allowable Area: Unlimited (NFPA 5000, Table 7.4.1.4.5.1) Actual Area: 1,737 SF Occupant Load: 1,737 sf @ 50 sf / occupant = 34 occupants Hazard of Content: Ordinary Hazard Contents Sprinkler System: Fully suppressed (NFPA 13) Seismic Design Category: Category A Required Separations: Storage Rooms > 100 sf: 1 HR Fire Barrier
Boiler/Furnace Rooms: 1 HR Fire Barrier Electrical Rooms: 1 HR Fire Barrier Stairs: Existing Shafts: 1 HR connecting <4 stories
Travel Distance Restrictions: Dead-End Corridor Limit: 50 ft.
Common Path of Travel: 100 ft.
Travel Distance to Exits: 300 ft.
Travel Distance from Room: 300 ft.
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
R O G E
R
A. REP
S T I E N
AR0012462
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/2
/2
:1
:3
P
M
Lakemont Emergency Management Buildout
06/23/2022
CODE DATA/ LIFE SAFETY
DRAWING
G100
NSJR
675-21-803
Orlando, Florida
Frank Wales - Facilities Deputy Chief
CONSTRUCTION
DOCUMENTS
21020.00
N Scale: 1/16" = 1'-0"
Code Plan
Revisions Date
Bid Set 06/23/2022
UP
D
E
1 2
MAIL ROOM
117C
MAIL ROOM
117B
OFFICE
117A
LOADING
DOCK
2.51
2.53
2.532.53
2.53
2.53
2.54
2.542.54
2.54
2.54
2.56
2.56
2.55
2.55
2.55
2.57
2.57
2.57
2.58
2.58
2.60
2.60
1'-1"
1' -1
" T1.0
7'-6" 5'-6" 1'-0" 5'-6"
2.62
2.52
DEMOLITION LEGEND
Wall to be Demolished
Existing Wall to Remain
Door and Frame to be Demolished
Not in Contract Area
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
R O G E
R
A. REP
S T I E N
AR0012462
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/1
/2
:5
:1
P
M
Lakemont Emergency Management Buildout
06/23/2022
DEMOLITION PLAN
AD101
NSJR
675-21-803
Orlando, Florida
Frank Wales - Facilities Deputy Chief
CONSTRUCTION
DOCUMENTS
21020.00
A. Remove all existing partitions shown with dashed line. Repair wall and floor finishes to match adjacent surfaces at areas of removal or scheduled new surfaces as required.
B. Remove all existing borrowed lights, doors and hollow metal frames where indicated with dashed line. Unused hardware shall be turned over to Owner. Box hardware before giving to Owner.
C. Prepare walls and floor slabs as required to receive new finish materials where existing finish is indicated to be removed.
D. See Plumbing, HVAC and Electrical Drawings for removal work associated with those trades.
E. Computer and communication cables and/or other wiring, piping, tubing, etc. serving other areas and functions located above ceiling or in walls of areas 117A, 117B, 117F, 117G shall be maintained during demolition/construction process. Coordinate any required changes to these systems with the C.O.R.
F. Repair existing walls to match adjacent undisturbed wall where cabinets, countertops, etc. are shown to be removed.
G. Protect existing finishes surrounding temporary partition. Repair damaged areas upon removal of temporary partion.
H. All existing items to be removed from walls. floors, and ceilings to allow for installation of continuous sheet metal directly to those surfaces.
N Scale: 1/4" = 1'-0"
Demolition Plan
2.51 Remove existing plastic laminate counter and supports.
2.52 Remove existing shelves and supports.
2.53 Remove existing carpet tiles and rubber base. Prepare slab for new finishes.
2.54 Remove existing suspended acoustical ceiling tile, grid, and hangers. See MEP Drawings.
2.55 Remove existing door. Hollow metal frame to remain.
2.56 Remove existing hollow metal frame.
2.57 Remove existing metal wall furring and gypsum board.
2.58 Remove portion of concrete wall from flush with floor slab to a height of 10'-0" A.F.F. Repair/infill slab at removed wall to provide flush surface for new floor finishes.
2.60 Sawcut and remove existing concrete slab to allow for new construction. See Electrical Drawings.
2.62 Remove portion of brick and CMU wall as required for
installation of new louver. See Mechanical Drawings.
PLAN NOTES
GENERAL DEMOLITION NOTES
D
E
1 2
Open Office
117C
Server Room
117D
Open Office
117B
Office
117A
S1.0
S1.0
S2.4
S2.4
S4.0
S2.4
S4.1
S4.1
S4.1S4.1
S4.1
S4.1S4.1S4.1
S4.1S4.0
S4.0
S4.0 117C
117D
21'-7" 4 7/8" 17'-1 5/8"
/8
/8
" 3
S1.0-F
117F
117E
Vestibule
117E
Vestibule
117F
S3.0
S3.0 S3.0
S3.0
S3.0S3.0
Closet
117G
ALIGN
ALIGN
9.18
9.18
9.18
9.18
9.18
9.18
8.158.158.15
117B
7.88
7.88
A121
A121
A121
Sim
S2.0
S4.0
S5.0
S5.0
2.04
A121
A121
Sim
9.16
9.169.16
5.01
5.03
5.03
5.03
S2.4
S3.0
A121
TYP.
A121
Sim
T1.0
10.41
10.41
8.15
10.41
Mechanical
117H
117H
S1.0
ALIGN
S1.0
4 7/8"
9.219.21
9.02
9.80
7.82
7.82
STRUCTURE ABOVE
FIN. CEILING
FLOOR SLAB
SEE SCHED.
S E
E S
C H
E D
U L E
F
2"
SEE
SCHED. 2"
S E
E S
C H
E D
U L E
8.08
SEE PLAN
1/2" 1/2"
H1
J1
8.02
9.21
9.80
8.02
9.09
9.21
9.80
9.08
7.82
7.82 1/2" 1/2"
S2.4
9.21
9.01
7.82
2 1/8"
S4.0
2 1/8"
AIRSPACE
1 1/2"
9.21
9.01
7.82
9.23
4.29
4 1/4"
5.02
5.03
S3.0
1 1/2"
9.05
9.21
S1.0-F
1-HR RATED
FIRE BARRIER
U.L. #U465
4 7/8"
9.219.21
9.02
9.80
7.82
7.82
8"
8.078.07
2 1/8" 1 1/2"
S2.4
S2.4 9.21
9.21
7.827.82
2.03
2.03
9.23
5.01
/2
7.82
7.82
9.09
9.17
9.17
9.19
9.19
8.08
2.02
9.17
5.01
S5.0
9.21
9.21
9.80
7.82
7.82
5.11
9.02
6 1/4"
5.02
5.03
9.21
S2.0
9.21
9.02
7.82
7.82
4 1/4"
9.80
S4.1
2 1/8"
AIRSPACE
1 1/2"
9.21
9.01
7.82
7.82
9.23
4.29
4 1/4"
5.02
5.03
T1.0
9.21
9.02
9.80
9.16
4 7/8"
6.15
Construction Side
Public Side
1-HR RATED
FIRE BARRIER
U.L. #U465
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
R O G E
R
A. REP
S T I E N
AR0012462
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/1
/2
:5
:1
P
M
Lakemont Emergency Management Buildout
06/23/2022
NEW WORK PLAN
A101
NSJR
675-21-803
Orlando, Florida
Frank Wales - Facilities Deputy Chief
CONSTRUCTION
DOCUMENTS
21020.00
A. All dimensions are taken to face of gypsum wallboard or unit masonry.
B. Edge of all door jambs at hinge side not otherwise indicated are to be 6" from the face of intersecting walls. Edge of all door jambs at strike side not otherwise located are to be 18" minimum from the face of intersecting walls.
C. All wood blocking to be fire retardent treated.
D. Infill all openings in existing walls within RF-shielding boundary with wall type S5.0. See Wall Types for details.
E. Comply with requirements found in Best Practice Guidelines for Architectural Radio Frequency Shielding document and Technical Specifications for Construction and Management of Sensitive Compartmented Information Facilities version 1.5.
F. Reference sheet A201 for RF shielding details.
G. Protect existing finishes surrounding temporary partition. Repair damaged areas upon removal of temporary partion.
N Scale: 1/4" = 1'-0"1 Dimension Plan
2.02 Existing structure to remain.
2.03 Existing concrete wall to remain.
2.04 Existing card reader to remain.
4.29 Airspace.
5.01 26 GA. sheet metal shielding with RF shielding grade foil tape at seams.
5.02 Install continuous 26 ga. Sheet metal to underside of concrete slab with flush mount screws at 8" o.c. Joints shall be covered with bent metal seam plates. All seams and screws to be sealed with RF shielding grade foil tape. Metal shall overlap the walls and corners at least 12" to allow for electrical bonding.
5.03 Install continuous 26 ga. Sheet metal to concrete slab with flush mount screws at 8" o.c. Joints shall be covered with bent metal seam plates. All seams and screws to be sealed with RF shielding grade foil tape. Metal shall overlap the walls and corners at least 12" to allow for electrical bonding.
5.11 3/4" #9 10 gauge expanded metal mesh. Spot weld or screw with washers or fastener system at 6" o.c. to studs, deck, and floor.
6.15 5/8" fire-rated plywood. Paint to match existing adjacent wall color.
7.82 Continuous acoustic sealant @ non-rated walls / fire-rated sealant @ rated walls each side.
7.88 New expansion joint cover at existing building expansion joint.
Color to match wall color.
8.02 Hollow metal frame.
8.07 RF-shielded hollow metal frame.
8.08 Threshold at RF door, set in bed of acoustic sealant.
8.15 New card reader. See technology drawings for details.
9.01 1 1/2" non-structural metal framing @ 16" o.c.
9.02 3 5/8" non-structural metal framing @ 16" o.c.
9.05 7/8" furring channel @ 16" o.c.
9.08 Metal framing box header.
9.09 Double metal framing at jambs, typ.
9.16 Infill hole with wall type S5.0. See Wall Types and sheet A121 for details.
9.17 Provide continuous RF shielding at door frame. Overlap the connection between door frame/sill shielding and wall/floor shielding with RF shielding grade foil tape. Refer to door manufacturer's installation instruction for details.
9.18 Boundary of RF shielding. Provide continuous layer of RF shielding throughout room. See Wall Types for wall shielding.
Provide 26 ga. sheet metal at floors and underside of deck above. All joints shall be finished to provide a continuous RF shielding barrier.
9.19 Install 6" wide RF shielding grade foil tape around entire perimeter of rough opening.
9.21 5/8" Type 'X' gypsum board.
9.23 5/8" Type 'X' RF-shielded gypsum board. Attach to existing concrete walls with construction adhesive. Cover all joints with RF shielding grade foil tape per manufacturer's guidelines.
9.80 Acoustic insulation
10.41 Semi-recessed fire extinguisher cabinet.
PLAN NOTES
GENERAL NOTES
Scale: 1" = 1'-0"
Wall Types
DOOR SCHEDULE
DOOR
BETWEEN DOOR DESCRIPTION FRAME DESCRIPTION
FIRE
RATING
HDWE
SET REMARKSRM RM TYPE MAT'L
SIZE
TYPE MAT'L HEAD JAMB SILL# W H T
117B 117B LD-1 F HM 1 3'-6" 7'-0" 1 3/4" EX EX EX EX EX 45 MIN. 02 Card Reader
117C 117C 117E F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 -- -- 04 Card Reader
117D 117E 117D F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 -- -- 03 Card Reader
117E 117E 117B F WD 1 3'-0" 7'-0" 1 3/4" 1 HM J2, SIM. J2 S1 -- 01 Card Reader, STC 50 min., RF Shielded Door & Frame
117F C-1 117F F WD 1 3'-0" 7'-0" 1 3/4" EX EX EX EX EX 45 MIN. 05 Existing Card Reader
117H 117H 117F F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 -- -- 06
Scale: 1/4" = 1'-0"
Door Types Scale: 1/4" = 1'-0"
H.M. Frame Types
Scale: 1 1/2" = 1'-0"
H.M. Frame Details
J2
S1
117C
117D 117B
117A
9'-0"
9'-0"
8'-0"
117E
117F
8'-0"
8'-0"
117G
ACT-1
ACT-1
ACT-1
ACT-1
ACT-1
1.02
2.052.05
5.02
5.02
5.02
9.18
9.18
9.18
9.18
7.87
7.87
A121
1.02
117H
REFLECTED CEILING PLAN LEGEND
Recessed downlight fixture
Supply Air Diffuser
Return Air Grille2' x 4' light fixture
2' x 2' acoustical tile ceiling
Gypsum board / portland cement plaster ceiling / soffit - painted
Pendant light fixture
Chain-hung light fixture
Access panel
Recessed wall-wash fixture
Surface-mounted strip light fixture
Area Not in Contract
S1.0
S4.0 S4.1
2.03
/8
/2
4.29
9.23
S4.1 S2.0
2.03
9.23
1/
8"
1/
2"
4.29
S4.0
S2.4
6.03
9.23
1/
8"
1/
2"
9.23
S4.1 S3.0
S2.0
2 1/8"
AIRSPACE
1 1/2"
9.23
9.219.21
5.11
9.02
2.03
9.809.80
9.21
S5.0
2.09
5.03
9.50
26.02
2.60
3.01
5.04
3.03
2"
8.61
7.81
7.81
4.01
4.28
4.26
2.10
1"
7.87
9.41
S3.0 S3.0
1"
7.88
6.03
2.06
7.13
6.03
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
R O G E
R
A. REP
S T I E N
AR0012462
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/1
/2
:5
:1
P
M
Lakemont Emergency Management Buildout
06/23/2022
REFLECTED CEILING PLAN
A121
NSJR
675-21-803
Orlando, Florida
Frank Wales - Facilities Deputy Chief
CONSTRUCTION
DOCUMENTS
21020.00
N Scale: 1/4" = 1'-0"
Reflected Ceiling Plan
A. All wood blocking shall be fire retardant.
B. Light fixtures, sprinkler heads, speakers, and HVAC devices shall be located as close as possible to the center of acoustical ceiling panels. Confirm any deviation from this with the Project Engineer.
C. See P, M, E and FP drawings for additional information regarding final information and quantites of fixtures/devices to be installed in ceiling.
D. See Electrical Drawings for lighting specifications.
1.02 No ceiling work this area.
2.03 Existing concrete wall to remain.
2.05 Rework existing ceiling around new wall.
2.06 Existing CMU wall to remain.
2.09 Existing concrete slab.
2.10 Existing brick and CMU wall to remain.
2.60 Sawcut and remove existing concrete slab to allow for new construction. See Electrical Drawings.
3.01 Fill damaged areas with high-strength, fast setting, single component concrete repair material to provide smooth uniform surface.
3.03 Infill trench with high-strength, fast setting, single component concrete repair material after trench is lined with sheet metal and conduits have been placed.
4.01 Remove and reinstall existing brick veneer as required for installation of new flashing, weeps, and mortar mesh.
4.26 Thru wall flashing. Run new flashing under existing air and moisture barrier. If no moisture barrier is present, then seal top edge of flashing to existing building insulation with flashing tape.
4.28 Cavity drainage mesh.
4.29 Airspace.
5.02 Install continuous 26 ga. Sheet metal to underside of concrete slab with flush mount screws at 8" o.c. Joints shall be covered with bent metal seam plates. All seams and screws to be sealed with RF shielding grade foil tape. Metal shall overlap the walls and corners at least 12" to allow for electrical bonding.
5.03 Install continuous 26 ga. Sheet metal to concrete slab with flush mount screws at 8" o.c. Joints shall be covered with bent metal seam plates. All seams and screws to be sealed with RF shielding grade foil tape. Metal shall overlap the walls and corners at least 12" to allow for electrical bonding.
5.04 Line the inside of trench with 26 GA. sheet metal. Seal all seams and gaps with RF shielding grade foil tape.
5.11 3/4" #9 10 gauge expanded metal mesh. Spot weld or screw with washers or fastener system at 6" o.c. to studs, deck, and floor.
6.03 2" x fire-treated wood blocking.
7.13 Batt thermal wall insulation. R-11 min.
7.81 Continuous sealant over backer rod.
7.87 Ceiling expansion joint assembly.
7.88 New expansion joint cover at existing building expansion joint.
Color to match wall color.
8.61 Prefinished aluminum louver. See Mechanical Drawings.
9.02 3 5/8" non-structural metal framing @ 16" o.c.
9.18 Boundary of RF shielding. Provide continuous layer of RF shielding throughout room. See Wall Types for wall shielding.
Provide 26 ga. sheet metal at floors and underside of deck above. All joints shall be finished to provide a continuous RF shielding barrier.
9.21 5/8" Type 'X' gypsum board.
9.23 5/8" Type 'X' RF-shielded gypsum board. Attach to existing concrete walls with construction adhesive. Cover all joints with RF shielding grade foil tape per manufacturer's guidelines.
9.41 Suspended acoustic ceiling tile/grid. See Room Finish
Schedule.
9.50 Carpet tile.
9.80 Acoustic insulation
26.02 Conduit. See Electrical and Telecom Drawings for details.
PLAN NOTES
GENERAL NOTES
Scale: 1 1/2" = 1'-0"1 Plan Detail
Scale: 1 1/2" = 1'-0"2 Plan Detail
Scale: 1 1/2" = 1'-0"3 Plan Detail
Scale: 1 1/2" = 1'-0"4 Trench Detail
Scale: 1 1/2" = 1'-0"5 Louver Detail
Scale: 3" = 1'-0"6 Expansion Joint Detail
Scale: 3" = 1'-0"7 Expansion Joint Detail
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
R O G E
R
A. REP
S T I E N
AR0012462
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/1
/2
:5
:1
P
M
Lakemont Emergency Management Buildout
06/23/2022
SHIELDING DETAILS
A201
NSJR
675-21-803
Orlando, Florida
Frank Wales - Facilities Deputy Chief
CONSTRUCTION
DOCUMENTS
21020.00
Scale: N.T.S.
Typical Joint: Gypsum Board Scale: N.T.S.
2-Way Horizontal Joint: Gypsum Board Scale: N.T.S.
2-Way Vertical Joint: Gypsum Board Scale: N.T.S.
Inside & Outside Corners: Gypsum Board Scale: N.T.S.
Insulated Pipe Penetration: Gypsum Board Scale: N.T.S.
Air Vent Wave Guide: Gypsum Board
Scale: N.T.S.
Fiber-Optic Penetration: Gypsum Board Scale: N.T.S.
Waveguide Beyond Cutoff Pipe Penetration:
Gypsum Board
Scale: N.T.S.
Typical Joint: Sheet Metal Scale: N.T.S.
2-Way Horizontal Joint: Sheet Metal Scale: N.T.S.
2-Way Vertical Joint: Sheet Metal Scale: N.T.S.
Inside Corner: Sheet Metal Scale: N.T.S.
Outside Corner: Sheet Metal
Open Office
117C Server Room
117D
Vestibule
117E
Open Office
117B
Office
117A
Vestibule
117F
Closet
117G
CPT-1
CPT-1
CPT-1
CPT-1
CPT-1
LVT-1
2.07 5.03
5.03
5.03
8.08
2.082.08Mechanical
117H
SC-1
8 8 8 8
11 10
1 2
Open Office
117C
Server Room
117D
Vestibule
117E
Open Office
117B
Vestibule
117F
Closet
117G
Office
117A
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
R O G E
R
A. REP
S T I E N
AR0012462
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/1
/2
:5
:2
P
M
Lakemont Emergency Management Buildout
06/23/2022
FINISH PLAN
AF101
NSJR
675-21-803
Orlando, Florida
Frank Wales - Facilities Deputy Chief
CONSTRUCTION
DOCUMENTS
21020.00
ROOM FINISH SCHEDULE
ROOM # ROOM NAME FLOOR BASE
WALLS CASEWORK
CEILINGNorth South East West Cabinet Countertop
117A Office CPT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
117B Open Office CPT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
117C Open Office CPT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
117D Server Room LVT-1 RB-1 P-1 P-1 P-1 P-1 --
117E Vestibule CPT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
117F Vestibule CPT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
117G Closet CPT-1 RB-1 P-1 P-1 P-1 P-1 ACT-1
117H Mechanical SC-1 RB-1 P-1 P-1 P-1 P-1 --
C-1 Corridor Existing RB-2 -- -- -- P-2 Existing
FINISH LEGEND
CODE FINISH TYPE MANUFACTURER PRODUCT / COLOR COMMENTS
ACT-1 ACOUSTICAL CEILING TILE ARMSTRONG CEILING SOLUTIONS ULTIMA 1912, 2' X 2', BEVELED TEGULAR, WHITE SUPRAFINE 9/16" EXPOSED TEE GRID
CPT-1 CARPET TILES INTERFACE RAW, FOUNDRY 101057, 50cm x 50cm INSTALLATION: QUARTER TURN
LVT-1 LUXURY VINYL TILE EF CONTRACT STAINED CONCRETE, LIMESTONE 00002, 18" X 36" INSTALLATION: ASHLAR
P-1 PAINT (FIELD) SHERWIN WILLIAMS SHIELD INTERIOR LATEX WALL PAINT, SW7021 SIMPLE WHITE GLOSS LEVEL 3
P-2 PAINT - - MATCH EXISTING PAINT IN CORRIDOR
RB-1 RUBBER BASE JOHNSONITE 6" COVE BASE, 32 PEBBLE WG
RB-2 RUBBER BASE - - MATCH EXISTING BASE IN CORRIDOR
SC-1 SEALED CONCRETE EUCLID CHEMICAL INCRETE CRYSTAL CLEAR, LOW VOC
N Scale: 1/4" = 1'-0"1 Finish Plan
N Scale: 1/8" = 1'-0"2 Furniture Plan
FURNITURE & EQUIPMENT SCHEDULE
Type Mark Description Count
Supplier / Installer Comments
1 Adjustable height electric pedestal table. 8 VA/VA
2 Chair 21 VA/VA
3 CRIPTO 1 VA/VA
4 File Cabinet 3 VA/VA
5 Flat Screen TV 7 VA/VA
6 Floor Copier/Printer 2 VA/VA
7 Mobile pedestal file with three drawers and casters. 8 VA/VA
8 Server Rack 7 VA/VA
9 Table-Rectangular 1 VA/VA
10 Table-round 1 VA/VA
11 Microwave 1 VA/VA
12 Side by Side Refrigerator 1 VA/VA
13 Transformer 1 GC/GC
14 Access Control Cabinet 1 GC/GC
15 Access Control Door Power Supply 1 GC/GC
2.07 Existing carpet to remain.
2.08 Patch and repair existing carpet at new wall location.
5.03 Install continuous 26 ga. Sheet metal to concrete slab with flush mount screws at 8" o.c. Joints shall be covered with bent metal seam plates. All seams and screws to be sealed with RF shielding grade foil tape. Metal shall overlap the walls and corners at least 12" to allow for electrical bonding.
8.08 Threshold at RF door, set in bed of acoustic sealant.
PLAN NOTES
Open Office
117C Server Room
117D
Open Office
117B
Office
117A
Vestibule
117E
Closet
117G
Vestibule
117F
A
AA
F
B
A
BB
C
F
AF
B
A
Mechanical
117H
A
.F .F
A
.F .F
A
.F .F
T y p ic a l L ig h t S w it c h M o u n ti n g H e ig h t
M in
A
D A
M o u n ti n g
H e ig h t
M a x A
D A
M o u n ti n g
H e ig h t
A
.F .F
A B C D
Finished Floor
S T A
T E
OF FLO
R
I D A
R E G
IS
TERED ARC
H
IT
E C T
R O G E
R
A. REP
S T I E N
AR0012462
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
/1
/2
:5
:2
P
M
Lakemont Emergency Management Buildout
06/23/2022
SIGNAGE PLAN
AS101
NSJR
675-21-803
Orlando, Florida
Frank Wales - Facilities Deputy Chief
CONSTRUCTION
DOCUMENTS
21020.00
N Scale: 1/8" = 1'-0"
Signage Plan
Scale: 3/4" = 1'-0"
Signage Mounting Heights
AB
CF
FIRE PROTECTION LEGEND GENERAL LEGEND
SYMBOL DESCRIPTION
OS&Y VALVE
FIRE DEPARTMENT CONNECTION
FIRE PROTECTION RISER
GATE VALVE
ALARM CHECK VALVE
BALL VALVE
PRESSURE REGULATING VALVE
BUTTERFLY VALVE
FLOW SWITCH
SYMBOL DESCRIPTION
PIPE TURNING DOWN
PIPE TURNING UP
FS FLOW SWITCH
TS TAMPER SWITCH
HOSE HOSE LINE CABINET
LH LIGHT HAZARD
OH-1 ORDINATY HAZARD - GROUP 1
OH-2 ORDINATY HAZARD - GROUP 2
FLUSHING CONNECTION OR CAP
A
B
SIM
FP
SECTION SYMBOL:
A = IDENTIFYING LETTER
B = SHEET WHERE SECTION IS SHOWN
SIM = SIMILAR
(ONLY NOTED IF IT APPLIES)
FIRE PROTECTION RISER DESIGNATION:
A = RISER IDENTIFYING SYSTEM TYPE
1 =
REVISION CLOUD AND
REVISION NUMBER
A
TITLE SYMBOL ON SHEET WHERE SHOWN
A = IDENTIFYING NUMBER/LETTER
RISER IDENTIFYING SYSTEM NUMBER
SYMBOL DESCRIPTION
FIRE PROTECTION COMPLIANCE NOTES
FIRE PROTECTION ABBREVIATIONS
AS ABOVE SLAB
AHJ AUTHORITY HAVING JURISDICTION
AFF ABOVE FINISHED FLOOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ASTM AMERICAN STANDARDS TESTING MATERIALS
BFP BACKFLOW PREVENTER
BLDG BUILDING
BOR BOTTON OF RISER
BS BELOW SLAB
CAP CAPACITY
CONN CONNECTION
CONT CONTINUOUS
CV CHECK VALVE
DIA DIAMETER
DN DOWN
DP DRY PENDENT
DS DRY SIDE WALL
DWG DRAWING
ELEV ELEVATION
ºF DEGREES FAHRENHEIT
FDC FIRE DEPARTMENT CONNECTION
FDV FIRE DEPARTMENT VALVE
FM FACTORY MUTUAL
FP FIRE PROTECTION
FS FLOW SWITCH
FT FEET
GA GAUGE
GAL GALLON(S)
GALV GALVANIZED
GPM GALLONS PER MINUTE
HD HEAD
HP HORSEPOWER
HR HOUR
HYD HYDRANT
HZ HERTZ
IE INVERT ELEVATION
ID INTERNAL DIAMETER
IN INCHES
IPS INTERNATIONAL PIPE STANDARD
ABBR. DESCRIPTION ABBR. DESCRIPTION
KW KILOWATT
LF LINEAR FEET
MAX MAXIMUM
MFG. MANUFACTURER
MIN MINIMUM
NA NOT APPLICABLE
NC NORMALLY CLOSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
ORF ORRIFICE
OS&Y OUTSIDE SCREW AND YOLK
P PUMP
PH PHASE
POC POINT OF CONNECTION
PSI POUNDS PER SQUARE INCH
PS PRESSURE SWITCH
QR QUICK RESPONSE
RM ROOM
RPM REVOLUTIONS PER MINUTE
SIN SPRINKLER IDENTIFICATION NUMBER
SF SQUARE FEET
SPEC SPECIFICATIONS
STD STANDARD
TEMP TEMPERATURE
TDH TOTAL DYNAMIC HEAD
TOR TOP OF RISER
TS TAMPER SWITCH
TYP TYPICAL
UG UNDERGROUND
UL UNDERWRITER'S LABORATORY
UNO UNLESS NOTED OTHERWISE
V VOLTS
VIV VALVE IN VERTICAL
VLV VALVE
VOL VOLUME
W/ WITH
FIRE PROTECTION GENERAL NOTES
BUILDING DESIGN:
THE LAKEMONT VA IS UTILIZED AS A THREE STORY OFFICE BUILDING TO SUPPORT
VARIOUS ADMINISTRATIVE NEEDS. THE EMERGENCY MANAGEMENT BUILDOUT
PROJECT IS LOCATED ON THE FIRST FLOOR AND IS LOCATED WITHIN THE EXISTING
MAIL ROOM. THE EXISTING FACILITY DOES NOT HAVE A FIRE PUMP.
SCOPE OF WORK:
MODIFY THE EXISTING AUTOMATIC WET SPRINKLER SYSTEM IN ACCORDANCE WITH
NFPA 13 2022 EDITION. ALL SPRINKLER HEADS SHALL BE QUICK RESPONSIVE TYPE
EXCEPT FOR THE SERVER ROOM, WHICH SHALL BE STANDARD RESPONSE TYPE.
SPRINKLER HEADS SHALL BE INSTALLED IN CENTER OF CEILING TILES. SPRINKLER
CONTRACTOR SHALL USE EXTRAPOLATED FLOW DATA WHEN PERFORMING
HYDRAULIC CALCULATIONS.
FIRE PROTECTION SPRINKLER CONTRACTOR SHALL COORDINATE THE DESIGN AND
INSTALLATION OF THE FIRE PROTECTION SPRINKLER SYSTEM AND DELIVER A
COMPLETE, FULLY FUNCTIONAL, AND TESTED FIRE PROTECTION SYSTEM THAT
MEETS THE REQUIREMENTS OF THE FIRE PROTECTION DRAWINGS, FIRE PROTECTION
SPECIFICATIONS, LISTED CODES AND STANDARDS, AND THE REQUIREMENTS OF THE
AHJ. THE FIRE PROTECTION SPRINKLER CONTRACTOR SHALL PROVIDE AND INSTALL
NEW MATERIALS THAT ARE UL LISTED AND\OR FM APPROVED AS REQUIRED BY THE
FIRE PROTECTION DRAWINGS AND THE FIRE PROTECTION SPECIFICATIONS.
CHARACTERISTICS OF THE WATER SUPPLY TO BE USED:
A CURRENT HYDRANT FLOW TEST SHALL BE PERFORMED AND VERIFIED PRIOR TO
PRODUCTION OF LAYOUT DOCUMENTS.
FLOW TEST DATA:
CONTRACTOR SHALL COORDINATE WITH THE VA AND AQUIRE A FLOW TEST WITHIN 12
MONTHS OF SUBMITTING WORKING DOCUMENTS.
ACCEPTANCE TEST CRITERIA:
FIRE SPRINKLER SYSTEM SHALL BE DESIGNED PER NFPA 13, 2022 EDITION AND SHALL
COMPLY THE AUTHORITY HAVING JURISDICTION. THE ACCEPTANCE TESTING OF THE
FIRE SPRINKLER SYSTEM AND IT'S COMPONENTS SHALL CONSIST OF ALL APPLICABLE
ITEMS SHOWN ON THESE TWO FORMS, NFPA 13, 2022 EDITION, ANNEX FIG. A.29.1
CONTRACTOR'S MATERIAL AND TEST CERTIFICATE FOR ABOVE GROUND PIPING. SEE
NFPA 13, 2022 EDITION CHAPTER 29 FOR SYSTEM ACCEPTANCE AND NFPA 25, 2020
INSPECTION, TESTING, AND MAINTENANCE.
A. CHAPTER 29, SYSTEM ACCEPTANCE
B. 29.1 APPROVAL OF SPRINKLER SYSTEM
C. 29.2 ACCEPTANCE REQUIREMENTS
D. 29.2.7 AUTOMATED INSPECTION AND TESTING DEVICES AND EQUIPMENT
E. 29.3 INSTRUCTION
F. 29.4 HYDRAULIC DESIGN INFORMATION SIGNS
APPLICABLE NFPA STANDARDS TO BE APPLIED:
A. U.S. DEPARTMENT OF VETERAN AFFAIRS FIRE PROTECTION DESIGN MANUAL -
EIGTH EDITION (JUNE 1, 2021)
B. NFPA 13, 2022 EDITION, STANDARD FOR THE INSTALLATION OF SPRINKLER
SYSTEMS
C. NFPA 14, 2019 EDITION, STANDARD FOR THE INSTALLATION OF STANDPIPE AND
HOSE SYSTEMS
D. NFPA 24, 2022 EDITION, STANDARD FOR THE INSTALLATION OF FIRE SERVICE
MAINS
E. NFPA 25, 2020 EDITION, INSPECTION, TESTING AND MAINTENANCE OF WATER
BASED FIRE PROTECTION SYSTEM.
F. NFPA 55, 2020 EDITION, COMPRESSED GASES AND CRYOGENIC FLUIDS
G. NFPA 101, 2021 EDITION, LIFE SAFETY CODE
CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR AREA:
LIGHT HAZARD:
SPACES WITH LOW QUANTITY AND COMBUSTIBILITY OF CONTENTS
I.E. OFFICES, EXAM ROOMS, CORRIDORS, MEETING ROOMS, BREAK ROOMS,
AND RESTROOMS.
ORDINARY HAZARD GROUP 1:
SPACES WITH MODERATE QUANTITY AND LOW COMBUSTIBILITY OF CONTENTS
I.E. LABORATORIES, MECHANICAL ROOMS, AND ELECTRICAL ROOMS.
DESIGN APPROACH:
SPRINKLER SYSTEM TO EXTEND INTO ALL AREAS IN ACCORDANCE WITH NFPA 13
HAZARD CLASSIFICATIONS AS NOTED. FM APPROVED SIDEWALL, PENDENT, AND
UPRIGHT HEADS WITH APPROPRATE K-FACTORS TO BE PROVIDED WHERE NOTED ON
DRAWINGS.
LIGHT HAZARD:
SYSTEM TYPE: WET PIPE AUTOMATIC SPRINKLER SYSTEM, USING STEEL SUPPLY
PIPING TO NEW QUICK RESPONSE, PENDENT OR UPRIGHT HEADS.
K-FACTOR: 5.6 (EXTENDED COVERAGE SPRINKLER HEADS ARE ACCEPTABLE).
DENSITY: 0.10 GPM/SQ.FT.
AREA OF OPERATION: 1500 SQ FT (DESIGN AREA REDUCTION MAY ONLY BE USED IF
CEILING HEIGHT AND AREA CLASSIFICATION PERMITS PER NFPA 13 2022 EDITION.
HEAD TEMPERATURE RATING: 155 DEGREES F.
SPACING: 225 SQ. FT. MAX. PER SPRINKLER HEAD OR BY MANUFACTURER
LITERATURE.
HOSE ALLOWANCE: 100 GPM
ORDINARY HAZARD GROUP 1:
SYSTEM TYPE: WET PIPE AUTOMATIC SPRINKLER SYSTEM, USING STEEL SUPPLY
PIPING TO NEW STANDARD RESPONSE, PENDENT OR UPRIGHT HEADS.
K-FACTOR: 5.6, 8.0, 11.2, OR 14.0 (EXTENDED COVERAGE SPRINKLER HEADS ARE
ACCEPTABLE).
DENSITY: 0.15 GPM/SQ.FT.
AREA OF OPERATION: 1500 SQ FT MAX
HEAD TEMPERATURE RATING: 200 DEGREES F.
SPACING: 130 SQ. FT. MAX. PER SPRINKLER HEAD OR BY MANUFACTURER
LITERATURE.
HOSE ALLOWANCE: 250 GPM
1. FIRE PROTECTION SYSTEM SHALL COMPLY WITH NFPA 13 (2022 EDITION) FOR
INSTALLATION OF SPRINKLER SYSTEMS. INSPECTION, TESTING, AND MAINTENANCE
SHALL COMPLY TO NFPA 25 (2020 EDITION). IN ADDITION, INSTALLATION AND
INSPECTION, TESTING, AND MAINTENANCE SHALL COMPLY WITH THE PROJECT
SPECIFICATIONS AND AHJ REQUIREMENTS.
2. FINAL INSPECTION AND APPROVAL BY AHJ.
3. SPRINKLER SHOP DRAWINGS AND MATERIAL SUBMITTALS SHALL BE SUBMITTED TO
THE ARCHITECT/ENGINEER AND STATE FIRE MARSHALL AND SHALL BE APPROVED
PRIOR TO ANY INSTALLATION. THE ENGINEER OF RECORD SHALL HAVE THE RIGHT TO
REJECT ANY SUBMITTALS.
4. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS TO BE DONE ONLY WITH
THE WRITTEN APPROVAL OF THE ARCHITECT AND STRUCTURAL ENGINEER.
5. FITTINGS REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER
EXISTING TRADES, AND/OR TO MAINTAIN PROPER CLEARANCES SHALL BE PROVIDED.
VERIFY STRUCTURAL, MECHANICAL, ELECTRICAL INSTALLATIONS AND AVOID AN/ALL
OBSTRUCTIONS OR INTERFERENCES WITH FIRE PROTECTION PIPE ROUTING.
6. CONTRACTOR SHALL MAKE A FIELD VISIT TO VERIFY ARCHITECTURAL REFLECTED
CEILING CONDITIONS AND ELECTRICAL LIGHTING, CEILING CONFIGURATIONS AND
HEIGHTS.
7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, CEILINGS, FLOORS, ROOFS,
ETC., FLASH AND COUNTERFLASH ROOF PENETRATIONS.
8. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON-ACCESSIBLE CEILINGS AND
CHASES.
9. SPRINKLER HEADS ARE TO BE COORDINATED WITH ALL LOCATIONS OF DIFFUSERS,
SPEAKERS, LIGHTING FIXTURES, CEILING SYSTEMS AND STRUCTURAL SYSTEM.
10. INDICATE CENTER TO CENTER DIMENSIONS AND/OR PIPE CUT LENGTHS AND NOMINAL
PIPE DIAMETERS ON ALL PIPING. INDICATE PIPE TYPE, SCHEDULE OF WALL THICKNESS
AND METHOD OF JOINING ON SHOP DRAWING.
11. PROVIDE STOCK OF EXTRA SPRINKLERS IN ACCORDANCE WITH NFPA 13.
12. PROVIDE DETAIL AND INDICATE TYPE OF HANGERS TO BE INSTALLED FOR SPRINKLER
PIPING. METHODS OF HANGING PIPES, HEADERS AND BRANCHES SHALL BE IN
ACCORDANCE WITH NFPA 13. ALL HANGERS ON 4" PIPE AND LARGER SHALL BE CLEVIS-
TYPE HANGERS. HANGERS SHALL NOT INTERFERE WITH ANY OTHER TRADE. POWDER
DRIVEN STUDS SHALL NOT BE USED.
13. ALL GROOVED & SCREWED FITTINGS SHALL BE UL AND/OR FM APPROVED AND
SUBMITTED TO THE ENGINEER OF RECORD FOR APPROVAL PRIOR TO ANY
INSTALLATION. THE ENGINEER OF RECORD RESERVES THE RIGHT TO DISAPPROVE ANY
FITTING.
14. WELD-O-LETS SHALL BE TWO SIZES SMALLER THAN CROSS MAIN, NO LENGTH OF
CROSS MAIN SHALL BE GREATER THAN 10'-0". ALL SPRINKLER PIPING & FITTINGS SHALL
BE INSTALLED ABSOLUTELY RUST-FREE.
15. SPRINKLER HEADS SHALL BE FM APPROVED.
16. AUTOMATIC SPRINKLER TEMPERATURE RATINGS OF FUSIBLE ELEMENTS TO BE IN
ACCORDANCE WITH NFPA 13.
17. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S
LABORATORIES, INC. AND THE FACTORY MUTUAL LABORATORIES. VALVES SHALL BE
FACTORY MARKED "UL" OR "FM", AND RATED FOR 175 WORKING PRESSURE.
18. SPRINKLER COVERAGE SHALL COMPLY WITH NFPA 13. SPRINKLER LOCATIONS WITH
RESPECT TO OBSTRUCTIONS SHALL COMPLY WITH THE APPROPRIATE CHAPTER
BASED ON SPRINKLER TYPE IN NFPA 13-2022.
19. IMMEDIATELY NOTIFY THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOUND
BETWEEN THESE PLANS, OTHER ENGINEERING PLANS, THE ARCHITECTURAL PLANS
AND/OR FIELD CONDITIONS PRIOR TO FINAL BID PRICE OR FINAL PERMITTING.
20. IN CASE OF DISPUTE OR DOUBT AS TO INTENT OF DRAWINGS OR SPECIFICATIONS,
OBTAIN ARCHITECT/ENGINEER'S WRITTEN DECISION BEFORE PROCEEDING WITH BID
OR WORK INVOLVED.
21. BEFORE SUBMITTING PROPOSAL OR BID, EXAMINE ALL DRAWINGS AND
SPECIFICATIONS RELATING TO THIS PROJECT, THE AMOUNT OF SPACE AVAILABLE FOR
PIPING, EQUIPMENT AND CONNECTING SERVICES, THE SCOPE OF SITE OF THE WORK,
THE REQUIREMENTS TO CORRELATE THE FIRE PROTECTION WORK WITH THAT OF
OTHER TRADES AND THE TIME SCHEDULE NECESSARY TO PERFORM THAT WORK.
22. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY, AND AFTER ASSEMBLY THE
ENTIRE PIPING SYSTEM SHALL BE FLUSHED CLEAN.
23. ADJUST NEW SPRINKLER PIPING AND SPRINKLER HEAD PLACEMENT TO ACCOMMODATE
EXISTING CEILING HEIGHTS AND STRUCTURAL CONFIGURATIONS.
24. PROVIDE SPRINKLERS ABOVE AND BELOW EXPOSED DUCTWORK 4 FEET OR WIDER.
25. PROVIDE HAZARD COVERAGE FOR THE FUNCTIONS FOR EACH AREA.
26. ALL PENDENT SPRINKLERS SHALL BE CENTER OF TILE, UNLESS MAXIMUM DISTANCES FROM
WALLS OR BETWEEN HEADS IS EXCEEDED OR UNLESS SHOWN DIFFERENTLY ON
DRAWINGS. IF NOT POSSIBLE ALL SPRINKLER HEADS MOUNTED IN CEILING SHALL BE
LOCATED A MINIMUM OF 4" AWAY FROM ANY WALLS, CEILING GRID MEMBERS, CEILING
HEIGHT CHANGES OR ANY OTHER VERTICAL INTERSECTING STRUCTURAL SURFACE.
27. FIRE PROTECTION CONTRACTOR SHALL ASSIST IN PREPARATION OF COORDINATION
DRAWINGS FOR ALL LEVELS WHICH INDICATE ALL THE ENGINEERING DISCIPLINES & FIRE
PROTECTION PIPING. THESE DRAWINGS SHALL BE PREPARED & APPROVED BY THE
ENGINEER OF RECORD PRIOR TO ANY INSTALLATION.
28. FIRE SPRINKLER PIPING SHALL NOT TRAVEL OVER THE TOPS OF ELECTRICAL
PANELBOARDS, SERVER RACKS, OR ANY ELECTRICAL EQUIPMENT.
29. PROVIDE TEFLON COATING FOR ALL SPRINKLERS IN ANY CORROSIVE AREA.
30. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING HEIGHTS IN EACH AREA.
31. ALL EXPOSED PIPING SHALL BE SHALL BE PAINTED RED.
32. ALL MATERIALS, WHERE APPLICABLE, SHALL BE U.L. LISTED OR FACTORY MUTUAL
APPROVED FOR USE IN AUTOMATIC SPRINKLER SYSTEMS. ALL NEW PIPING SHALL BE
HYDROSTATICALLY TESTED FOR TWO HOURS IN ACCORDANCE WITH NFPA 13. MINIMUM
HYDROSTATIC TEST PRESSURE SHALL BE 200 PSI.
33. FLEXIBLE SPRINKLER CONNECTIONS SHALL ONLY BE PERMITTED UPON VA APPROVAL. IF
FLEXIBLE SPRINKLER CONNECTIONS ARE PERMITTED AND USED, HYDRAULIC
CALCULATIONS MUST BE PERFORMED AND SUBMITTED TO THE ENGINEER OF RECORD.
34. THE SMALL ROOM RULE SHALL BE ACCEPTABLE FOR PLACEMENT OF SPRINKLERS PER
NFPA 13-2022, 10.2.5.2.3.
35. UPON SPRINKLER SYSTEM IMPAIRMENT, NFPA 25-2020, 15.5.2 SHALL BE FOLLOWED DURING
SPRINKLER SYSTEM DOWNTIME. APPROVED PERSONNEL SHALL COORDINATE
REQUIREMENTS PER NFPA 25, SUCH AS AN APPROVED FIRE WATCH IF REQUIRED.
IMPAIRMENT PROCEDURES REQUIRED TO BE TAKEN SHALL BE INCLUDED IN
CONTRACTOR'S BUDGET.
PENDENT SPRINKLER HEAD
RESPONSETEMPMFG. STYLEFINISHK-FACORFSYMBOL
FIRE SPRINKLER LEGEND
MODEL SIN NPT
QUICK155° 5.6 BRASS PENDENT1/2"TYCO TY-FRB TY323 1/2"
-SHEET NOTE CALLOUT
-CONNECT TO EXISTING
-DEMOLISH TO POINT INDICATED
XX
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
Bid Set 06/23/2022
B
IM
/0
V
A M
C L a k e m o n t
E m e rg e n c y M a n a g e m e n t B u ild o u t/
V A
M C
L a k e m o n t E m e rg e n c y M g m t.
R
D iv
-2
-2
.r v t
/2
/2
:3
:0
P
M
FP001
FIRE PROTECTION LEGENDS,
SYMBOLS, & GENERAL NOTES
Lakemont Emergency Management Buildout
Orlando, Florida
Frank Wales - Facilities Deputy Chief
06/23/2022 MHL MRK
CONSTRUCTION
DOCUMENTS
VA Project No. 675-21-803 Above Grp Project No. 0121036
SHEET LIST
Sheet Number Sheet Name
FP001 FIRE PROTECTION LEGENDS, SYMBOLS, & GENERAL NOTES
FPD101 FIRE PROTECTION FLOOR PLAN - DEMO
FP101 FIRE PROTECTION FLOOR PLAN - NEW WORK
FP501 FIRE PROTECTION DETAILS
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SI
VAD.JELY
K
B
C
C.2
D
E
1 1 1
EXISTING FIRE MAIN POINT OF
ENTRY INTO BUILDING AND RISER
EXISTING FIRE
SPRINKLER PIPING
3 3
Keyplan N.T.S.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
Bid Set 06/23/2022
B
IM
/0
V
A M
C L a k e m o n t
E m e rg e n c y M a n a g e m e n t B u ild o u t/
V A
M C
L a k e m o n t E m e rg e n c y M g m t.
R
D iv
-2
-2
.r v t
/2
/2
:3
:1
P
M
FPD101
FIRE PROTECTION FLOOR PLAN -
DEMO
Lakemont Emergency Management Buildout
Orlando, Florida
Frank Wales - Facilities Deputy Chief
06/23/2022 MHL MRK
CONSTRUCTION
DOCUMENTS
VA Project No. 675-21-803 Above Grp Project No. 0121036
CODED NOTES:
DEMOLISH EXISTING SPRINKLER HEAD AND ASSOCIATED BRANCH PIPING.
DEMOLISH FIRE MAIN TO BACK TO OUTSIDE OF ROOM AND PREPARE FOR NEW CONNECTION.
DEMOLISH EXISTING SPRINKLER HEAD AND ADJUST BRANCH PIPING AS REQUIRED TO MATCH NEW CEILING HEIGHTS. PREPARE FOR NEW SPRINKLER HEAD IN PLACE OF EXISTING SPRINKLER HEAD.
PIPING CONTINUED TO FIRE MAIN IN CORRIDOR.
DRAWING NOTES:
1. EXISTING FIRE PROTECTION SYSTEM SHALL REMAIN ACTIVE AT ALL TIMES. FIRE MAIN AND BRANCH
PIPING ROUTED THROUGH SPACE SHALL REMAIN ACTIVE.
1/4" = 1'-0"1
LEVEL 1 - FIRE PROTECTION PLAN - DEMO
0 2' 4' 8' 12'
1/4" = 1'-0"
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SI
VAD.JELY
B
C
C.2
D
E
Open Office
117C
Server Room
117D
Vestibule
117E
Open Office
117B
Office
117A
Vestibule
117F
EXISTING FIRE MAIN POINT OF
ENTRY INTO BUILDING AND RISER
3 3 3 3
EXISTING FIRE
SPRINKLER PIPING
Keyplan N.T.S.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
FULLY SPRINKLERED305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
Bid Set 06/23/2022
B
IM
/0
V
A M
C L a k e m o n t
E m e rg e n c y M a n a g e m e n t B u ild o u t/
V A
M C
L a k e m o n t E m e rg e n c y M g m t.
R
D iv
-2
-2
.r v t
/2
/2
:3
:0
P
M
FP101
FIRE PROTECTION FLOOR PLAN -
NEW WORK
Lakemont Emergency Management Buildout
Orlando, Florida
Frank Wales - Facilities Deputy Chief
06/23/2022 MHL MRK
CONSTRUCTION
DOCUMENTS
VA Project No. 675-21-803 Above Grp Project No. 0121036
CODED NOTES:
PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC SPRINKLER SYSTEM FOR A LIGHT HAZARD
OCCUPANCY WITH A MINIMUM DENSITY/AREA OF 0.10 GPM/SF OVER 1500 SF PER NFPA 13.
PROVIDE A HYDRAULICALLY CALCULATED AUTOMATIC SPRINKLER SYSTEM FOR A ORDINARY HAZARD GROUP 1 OCCUPANCY WITH A MINIMUM DENSITY/AREA OF 0.15 GPM/SF OVER 1500 SF PER NFPA 13.
PROVIDE NEW SPRINKLER HEAD IN PLACE OF EXISTING SPRINKLER HEAD AND CONNECT TO
EXISTING BRANCH PIPING.
AUTOMATIC SPRINKLER SYSTEM SHALL BE DESIGNED FOR A LIGHT HAZARD OCCUPANCY WITH A
MINIMUM DENSITY/AREA OF 0.10 GPM/SF OVER 1500 SF PER NFPA 13.
EXISTING FIRE SPRINKLER SYSTEM SHALL BE EXTEND TO SECURE AREA. PIPING SHALL PENETRATE THE SECURE WALL AS A SINGLE PIPE AND EXISTING UNUSED PIPING SHALL BE CAPPED. IN ADDITION, PIPING PENETRATING THE SECURE PERIMETER WALL SHALL PENETRATE AT A SINGLE POINT ALONG WITH OTHER UTILITIES TO MEET THE REQUIREMENTS OUTLINED IN ICD/ICS 705. PIPING AT SECURE WALL PENETRATION SHALL BE PROVIDED WITH A NON-CONDUCTIVE BREAK (REFER TO DETAIL 5 /
FP501).
PIPING CONTINUED TO FIRE MAIN IN CORRIDOR.
PROVIDE NEW SPRINKLER HEAD IN PLACE OF EXISTING SPRINKLER HEAD AND CONNECT TO
EXISTING BRANCH PIPING. SPRINKLER HEAD TYPE SHALL BE ACCORDING TO NEW HAZARD
CLASSIFICATION. UPSIZE BRANCH PIPING TO SPRINKLER IF REQUIRED.
AUTOMATIC SPRINKLER SYSTEM SHALL BE DESIGNED FOR A ORDINARY HAZARD GROUP 1
OCCUPANCY WITH A MINIMUM DENSITY/AREA OF 0.15 GPM/SF OVER 1500 SF PER NFPA 13.
PROVIDE NEW SPRINKLER HEAD IN PLACE OF EXISTING SPRINKLER HEAD AND CONNECT TO
EXISTING BRANCH PIPING. SPRINKLER HEAD TYPE SHALL BE ACCORDING TO NEW HAZARD
CLASSIFICATION.
DRAWING NOTES:
1. ALL FIRE PROTECTION SPRINKLER PIPING PENETRATING THE SECURE PERIMETER WALL SHALL
PENETRATE AT A SINGLE POINT ALONG WITH OTHER UTILITIES TO MEET THE REQUIREMENTS
OUTLINED IN ICD/ICS 705.
2. RF SHIELDING PIPE PENETRATIONS SHALL BE PROVIDED WITH A FOIL FLANGE AT A MINIMUM OF 3".
APPLY RF GRADE ALUMNINUM FOIL TAPE OVER THE FLANGE AND EXTEND A MINIMIMUM OF 3".
1/4" = 1'-0"1
LEVEL 1 - FIRE PROTECTION PLAN - NEW WORK 0 2' 4' 8' 12'
1/4" = 1'-0"
P R
O F
E S
S
I O NA L
E N G
I N
E E
R
L I CENSE
F L O R I DA
STATE
No. 84275
SI
VAD.JELY
K
CONCRETE FASTENER (U.L. LISTED
OR F.M. APPROVED)
PIPE HANGER RING (U.L. LISTED
OR F.M. APPROVED)
ALL THREAD ROD
ALL THREAD ROD
PIPE
MODEL 300 WICHLGAN TOP
BEAM CLAMP OR EQUAL
W/LOCK NUT
SWIVEL RING
STEEL I-BEAM OR
BAR JOIST
CONCRETE BEAM CLAMP
SPRINKLER HEAD
CEILING
1-1/2"REDUCER
BRANCH LINE
1" 90° ELL1" 90° ELL
1" DROP
1. WALL ASSEMBLY--THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM
WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE
MATERIALS AND IN THE MANNER…
This is the start of the file's text. The full file is on GovTribe.