Solicitation Attachment 2 - Drawings Vol 2 of 2 - Mechanical - Plumbing - Fire Protection - Electrical.pdf
PDF 10 MB Posted
- Attached to
- Munitions Storage Area (MSA) Expansion
- Solicitation number
- W50S87-21-B-5003
About this file
This solicitation attachment provides drawings for a Munitions Storage Area (MSA) Expansion project being undertaken by the Department of the Army North Carolina Army National Guard. The drawings include details for mechanical, plumbing, fire protection, and electrical systems. Interested parties are encouraged to attend a pre-bid conference on May 27, 2021 to register and obtain additional project details outlined in Section 00100 of the solicitation. The purpose of the solicitation is to receive bids to complete the MSA Expansion in accordance with the specifications and drawings provided in the attachments.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. ALL WORK, MATERIALS AND WORKMANSHIP SHALL BE PERFORMED IN STRICT
ACCORDANCE WITH, AND SHALL CONFORM WITH ALL FEDERAL, STATE AND LOCAL
CODES, ORDINANCES, RULES AND REGULATIONS, SPECIFICATIONS AND
RECOMMENDED PRACTICES OF THE MANUFACTURERS AND THE APPROPRIATE
APPLICABLE STANDARDS. WHERE SUCH CODES, RULES AND REGULATIONS ARE AT
VARIANCE WITH THE PLANS AND NOTES, SAID CODES, RULES AND REGULATIONS,
ETC. SHALL TAKE PRECEDENCE OVER THE PLANS AND NOTES.
2. THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE BUILDING CODES AND
REGULATIONS AND SHALL PAY FOR AND OBTAIN ALL NECESSARY AND REQUIRED
INSPECTIONS, APPROVALS AND PERMITS, NECESSARY TO PERFORM ALL WORK AND
SERVICES HEREIN NOTED OR INDICATED ON THE DRAWINGS.
3. THE CONTRACTOR SHALL FULLY INFORM HIMSELF OF THE CONDITIONS RELATING TO
THE CONSTRUCTION AND LABOR UNDER WHICH THE WORK WILL BE PERFORMED AND
COMPARE THE DRAWINGS AND SPECIFICATIONS WITH THE WORK IN PLACE. FAILURE
TO DO SO WILL NOT RELIEVE CONTRACTOR OF HIS OBLIGATION TO FURNISH ALL
LABOR AND MATERIALS NECESSARY TO CARRY OUT THE PROVISIONS OF THE
CONTRACT DOCUMENTS AND TO COMPLETE THE CONTEMPLATED WORK FOR THE
CONSIDERATION SET FORTH IN HIS BID. CONTRACTOR, IN THE CARRYING OUT OF HIS
WORK, SHALL EMPLOY SUCH METHODS OR MEANS THAT WILL NOT CAUSE ANY
INTERRUPTIONS OR INTERFERENCE WITHIN THE WORK OF ANY OTHER.
4. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND PROPOSED PIPE
CONNECTIONS AT THE JOB SITE AND SHALL REPORT ANY DISCREPANCIES TO THE
ENGINEER PRIOR TO STARTING CONSTRUCTION. COMMENCEMENT OF THE WORK BY
THE CONTRACTOR SHALL IMPLY HIS ACCEPTANCE OF ALL CONDITIONS.
5. MINOR DETAILS NOT USUALLY SHOWN OR SPECIFIED BUT NECESSARY FOR PROPER
CONSTRUCTION OF ANY PART OF THE WORK SHALL BE INCLUDED AS IF THEY WERE
INDICATED ON THE DRAWINGS.
6. DUE TO THE SMALL SCALE OF THE DRAWINGS THE PIPING SHOWN IS DIAGRAMMATIC.
THE CONTRACTOR SHALL PROVIDE ALL NECESSARY OFFSETS TO AVOID CONFLICTS
WITH STRUCTURAL ELEMENTS, LIGHTING FIXTURES, PLUMBING, ETC.
7. ALL WORK SHALL BE EXECUTED IN A CAREFUL AND ORDERLY MANNER WITH THE
LEAST POSSIBLE NOISE, DUST, OR DISTURBANCE TO OCCUPANTS IN ADJACENT SITES
OR BUILDINGS.
8. THE CONTRACTOR SHALL PROVIDE PROTECTION FOR THE GENERAL PUBLIC AND
CONSTRUCTION WORKERS IN AND AROUND THE CONSTRUCTION SITE.
9. THE CONSTRUCTION AREA SHALL BE THOROUGHLY CLEANED PRIOR, DURING AND
AFTER THE CONSTRUCTION.
10. SUBMITTALS SHALL BE IN COMPLIANCE WITH CONTRACT REQUIREMENTS AND
ACTUAL FIELD CONDITIONS.
11. DETAILS ON THE DRAWINGS ARE SHOWN AT SPECIFIC LOCATIONS AND ARE
INTENDED TO SHOW GENERAL REQUIREMENTS THROUGHOUT. DETAILS NOTED "TYP."
IMPLY ALL CONDITIONS TREATED SIMILARLY.
12. SHOULD DISCREPANCIES OCCUR BETWEEN CONTRACT DRAWINGS AND CONTRACT
SPECIFICATIONS, THE MORE STRINGENT REQUIREMENTS IN CONJUNCTION WITH
APPLICABLE LOCAL CODES, STANDARDS, RULES, REGULATIONS, LAWS, ETC. SHALL
APPLY.
ABBREVIATIONS
NOTES
NEW WORK
EXISTING SYSTEM TO REMAIN
LEGEND
MOTORIZED DAMPER
DUCT MOUNTED SMOKE DETECTOR
MANUAL VOLUME DAMPER
FIRE DAMPER WITH ACCESS DOOR
WITH ACCESS DOOR
1" UNDERCUT DOOR
DUCT SECTION - SUPPLY
COMBINATION FIRE / SMOKE DAMPER
M
SD
ELBOW DOWN
OPENING IN WALL ABOVE CEILING
FLOW DIRECTION
ELBOW UP
MOUNT 5'-0" ABOVE FINISHED FLOOR
MOUNT 5'-0" ABOVE FINISHED FLOOR
TWO WAY MOTORIZED CONTROL VALVE
WALL MOUNTED THERMOSTAT,
T
UNION FOR PIPE SIZES 2" AND SMALLER,
FLANGE FOR PIPE SIZES 2-1/2" AND
LARGER
S
WALL MOUNTED DDC SENSOR,
NEW WORK NOTE REFERENCE. NUMBER 1 IS THE NOTE NUMBER
INDICATES POINT OF CONNECTION BETWEEN
NEW AND EXISTING
DUCT SECTION - RETURN OR EXHAUST
SG SIZE
CFM
WALL MOUNTED SUPPLY REGISTER
RR SIZE
CFM
WALL MOUNTED RETURN OR EXHAUST REGISTER
CFM
WALL MOUNTED RETURN OR EXHAUST GRILLE
CFM
LD-# CEILING MOUNTED LINEAR SLOT SUPPLY DIFFUSER,
REFER TO SCHEDULE FOR CORRESPONDING NUMBER
RG SIZE
SUPPLY DUCT ELBOW WITH TURNING VANES
(PLAN, UP, DOWN)
RETURN OR EXHAUST DUCT ELBOW WITH TURNING VANES
(PLAN, UP, DOWN)
TG
TRANSFER GRILLE
MOUNT 5'-0" ABOVE FINISHED FLOOR
WALL MOUNTED EMERGENCY FAN SHUTOFF SWITCH,
SW
SIZE
AC AIR CONDITIONING UNIT
ACC AIR COOLED CONDENSING UNIT
AD ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AL ACOUSTICAL LINING
AMP AMPERE
ANCH ANCHOR
APD AIR PRESSURE DROP
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AS AIR SEPERATOR
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
ATC AUTOMATIC TEMPERATURE CONTROL
AUTO AUTOMATIC
B BOILER
BB BASEBOARD RADIATOR
BCPR BRANCH CIRCUIT PROTECTION
RATING
B/D BELT DRIVE
BDD BACK DRAFT DAMPER
BHP BREAK HORSEPOWER
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BOTEL BOTTOM ELEVATION
BSA BOARD OF STANDARDS AND APPEALS
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
C CONVECTOR
CAP CAPACITY
CAV CONSTANT AIR VOLUME
CB CABINET HEATER
CC COOLING COIL
CD CONDENSATE DRAIN
CF CIRCULATING FAN
CFM CUBIC FEET PER MINUTE
CG CIELING GRILLE
CH CHILLER
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CL CENTER LINE
CLO CLEAN OUT
CO CARBON MONOXIDE
COND CONDENSATE DRAIN
CONN CONNECTION
CONT CONTINUATION
COP COEFFICIENT OF PERFORMANCE
CP CONTROL PANEL
CR CEILING REGISTER
CU CONDENSING UNIT
CU FT CUBIC FEET
CUH CABINET UNIT HEATER
CV CONTROL VALVE FLOW COEFFICIENT
CW DOMESTIC COLD WATER
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DRAIN
DB DRY BULB
DCP DUPLEX CONDENSATE PUMP
PACKAGE
dBA DECIBELS
DD DIRECT DRIVE
DDC DIRECT DIGITAL CONTROLS
DF DEGREE, FAHRENHEIT
DHC DUCT HEATING COIL
DIA DIAMETER
DMC DUCT MOUNTED COIL
DN DOWN
DWG DRAWING
DX DIRECT EXPANSION
E EXISTING
EA EACH
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFT ENTERING FLUID TEMPERATURE
EG EXHAUST GRILLE
EL ELEVATION
ELEC ELECTRICAL
EQUIP EQUIPMENT
ER EXHAUST REGISTER
ERV ENERGY RECOVERY UNIT
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
DF DEGREE, FAHRENHEIT
FAB FACED BYPASS DAMPER
FBL FIXED BLADE LOUVER
FC FLEXIBLE CONNECTION
FCL FAIL CLOSED
FCU FAN COIL UNIT
FD/AD FIRE DAMPER WITH ACCESS DOOR
FLA FULL LOAD AMPERES
FLEX FLEXIBLE
FLG FLANGED
FLO FLOOR
FO FAIL OPEN
FPM FEET PER MINUTE
FSD COMBINATION FIRE / SMOKE DAMPER
FT FEET
FTR FINNED TUBE RADIATION
FT WG FEET OF WATER COLUMN GAUGE
G GAS
GA GAUGE
GAL GALLONS
GPM GALLONS PER MINUTE
GRV GRAVITY ROOF VENTILATOR
H HEIGHT
HC HEATING COIL
HP HORSEPOWER
HR HOURS
HRU HEAT RECOVERY UNIT
HV HEATING AND VENTILATING UNIT
HW HOT WATER
HWP HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HX HEAT EXCHANGER
HZ HERTZ
ID INSIDE DIAMETER
IN INCHES
IN WG INCHES OF WATER COLUMN GAUGE
JC JANITORS CLOSET
KW KILOWATT
L LENGTH
LAT LEAVING AIR TEMPERATURE
LBG LINEAR BAR GRILLE
LBS POUNDS
LF LINEAR FEET
LFT LEAVING FLUID TEMPERATURE
LPS LOW PRESSURE STEAM
LRA LOCKED ROTOR AMPERES
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MB MIXING BOX
MBCA MINIMUM BRANCH CIRCUIT
AMPACITY
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPERES
MD MOTORIZED DAMPER
MECH MECHANICAL
MED MEDIUM
MER MECHANICAL EQUIPMENT ROOM
MFR MANUFACTURER
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT
PROTECTION
MOD MOTOR OPERATED DAMPER
MVD MOTORIZED VANE DAMPER
NC NORMALLY CLOSED
NFA NET FREE AREA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
NYC NEW YORK CITY
OA OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OC ON CENTER
OED OPEN ENDED DUCT
OPNG OPENING
OSA OUTSIDE SUPPLY AIR
P PUMP
PD PRESSURE DROP
PE POLYETHYLENE
PH PHASE
PRESS PRESSURIZATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH, GAUGE
QTY QUANTITY
R RADIATOR
RA RETURN AIR
RD RETURN DIFFUSER
RED REDUCER
REQD REQUIRED
RF RETURN FAN
RG RETURN GRILL
RH RELATIVE HUMIDITY
RLA RUNNING LOAD AMPERES
RM ROOM
RO ROOF OPENING
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RTU ROOF TOP UNIT
SA SUPPLY AIR
SAD SELF ACTING DAMPER
SD SMOKE DETECTOR
SEER SEASONAL ENERGY EFFICIENCY
RATIO
SENS SENSIBLE
SF SUPPLY FAN
SFNFA SQUARE FEET NET FREE AREA
SG SUPPLY GRILL
SHT SHEET
SMD SMOKE DETECTOR
SQ FT SQUARE FEET
SP STATIC PRESSURE
TEF TOILET EXHAUST FAN
TG TRANSFER GRILLE
TI TEMPERATURE INDICATOR
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UH UNIT HEATER
UON UNLESS OTHERWISE NOTED
V VOLT
VAV VARIABLE AIR VOLUME
VD MANUAL VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
W WIDTH
W/ WITH
WB WET BULB
WC WATER COLUMN
WG WATER GAUGE
WPD WATER PRESSURE DROP
WMS WIRE MESH SCREEN
WTR WATER TEMPERATURE RISE
FLEX DUCT
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
ETB
P r o j e c t
N o
F
J R
P
C h a r l o t t e
A
N G
B a s e
C
D I A
N
C
N o r h
C r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C
M
S
E x p a n s i o n
SHEET OF 53
M001
TYPE B-3 SUBMISSION
MECHANICAL SYMBOLS,
ABBREVIATIONS, AND NOTES
JW
MK
ML
D W
G
N
A M
E
C
U
S E
R S
E
M M
A
P P
D A
T A
L O
C A
L P
R O
J E
C T
W I S
E W
O R
K D
I R
M
O T
T U
S E
P
W D
M S
N
C A
N G
M
S A
B
M
D
W
V
E
D
A T
E
P
M
Y
E
M M
L O
T
D
A T
E
P
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
ETB
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C
M p a n s i o n
SHEET OF 53
BRANCH
DUCT
D = THROAT DIAMETER
OF DIFFUSER
END OF DUCT
BALANCING DAMPER IN BRANCH DUCT DUCT & COLLAR
INSULATION
DIFFUSER
BRANCH DUCT
INSULATED
FLEXIBLE DUCT,
MAX. VERTICAL
OFFSET = D/8
1/2" WIDE STAINLESS STEEL CLAMP
INSULATIONCEILING
CLINCH CONNECTION
BALANCING
DAMPER IN
BRANCH DUCT
DIFFUSER
CEILING
STAINLESS STEEL WORM DRIVEN CLAMPS AND
U.L. APPROVED MASTIC SEALANT FOR
ATTACHING FLEXIBLE DUCT TO CLINCH
COLLAR
END BEARING
LOCKING TYPE QUADRANT
OPERATOR/INDICATOR
16 GA. GALVANIZED BLADE 1/4" LESS THAN
DUCT DIAMETER
3/4" SQUARE ROD
D = MIN
SUPPLY AIR DIFFUSER DETAIL
NOT TO SCALE
NOTE:
DISTANCE BETWEEN DUCT HANGERS
SHALL BE IN ACCORDANCE WITH
SMACNA STANDARD
RETAINING
CLIP
DUCT HANGER DETAIL
NOT TO SCALE
DUCT
C-CLAMP
HANGER ROD (TYP.)
SIZES PER
SMACNA
STANDARDS
ANGLE
ISOLATION PAD (TYP.)
1" SLOPE IN 7"
1" SLOPE IN 7"
EXTERNALLY
ADJUSTABLE
EXTRACTOR
1"
DOUBLE VANE
1" SLOPE IN 7"
T
W
45°
VOLUME DAMPER
VOLUME DAMPER
HEEL RADIUS T + 3/4 T
3/4 T
AIR
FLOW
W/4 (MINIMUM 5")
ROUND TAKE-OFF TAP TAKE-OFF
SQUARE ELBOW VANES SQUARE TAP TAKE-OFF
AIR
FLOW
AIR
FLOW
DUCT DETAILS
NOT TO SCALE
A B
VENT
PITCH DOWN TOWARD
CONDENSATE PUMP
3/4" TO COIL
DRAIN PAN
BLOW THRU
DRAW THRU
X
1/2" MINIMUM
1/2X+1"
X+1"
WHERE X=STATIC PRESSURE AT PAN IN INCHES OF WATER
CONDENSATE
PUMP
RUN TO NEAREST
FLOOR DRAIN
M A
X
LOCATE IN AUX DRAIN PAN. 115V,
1.5A, 6 FT CORD W/ GROUNDED
PLUG, MIN. 50 GPM @ 10' LIFT.
DISCHARGE CHECK VALVE AND
SAFETY HIGH LEVEL SWITCH.
CONDENSATE DRAIN P-TRAP DETAIL
NOT TO SCALE
LIQUID SOLENOID VALVE
EXPANSION VALVE
TO FLOOR DRAIN
MANUAL
ISOLATION
VALVE (TYP.)
HOT GAS
BYPASS VALVE
LIQUID LINE
CHARGING VALE
PACKLESS GLOBE
WITH SEAL CAP
SUCTION LINE
HOT GAS BY-PASS
SIGHT GLASS MOISTURE & LIQUID INDICATOR
COMPRESSOR
CONDENSATE DRAIN
REFRIGERANT PIPING SCHEMATIC DIAGRAM
NOT TO SCALE
NOTES:
PIPING ROUTING SHALL BE DESIGNED TO:
1. MINIMIZE THE ACCUMULATION OF LIQUID REFRIGERANT IN THE
COMPRESSOR CRANKCASE.
2. RETURN OIL TO THE COMPRESSOR AT SAME RATE AT WHICH IT
LEAVES
CONDENSATE DRAIN PAN
EVAPORATOR COIL
SHELL & CORE FILTER DRYER
WITH REPLACEABLE CORE & 3
VALVE BY-PASS
CONDENSER
CONDENSING UNIT AND MECHANICAL PAD DETAIL
NOT TO SCALE
MINIMUM 36" ON SERVICE SIDE
AND IN FRONT OF CONTROL BOX
PAD.
PAD WITH 6 x 6, # 8
6" THICK CONCRETE
REINFORCEMENT
GAUGE WIRE MESH
BOLT TO CONCRETE
DISCONNECT SWITCH
SUBCONTRACTOR.
BOLT TO WALL.
CONDENSING UNIT.
BY ELECTRICAL
TO BE INSTALLED
(4) EQUALLY SPACED 14
GAUGE, TIE-DOWN
STRAPS BY MIAMI TECH
INC., PART #CUTD-1(OR
EQUAL) WITH 1-1/2" PIN
WITH WASHER TO
COMPRESSOR UNIT.
(TYPICAL)
3/16" DIA X 1-1/2"
TAPCON ANCHOR
(TYPICAL)
REFRIGERANT PIPING.
MINIMUM 12" ON ANY SIDE OTHER THEN
SERVICE AND CONTROL BOX SIDE
CLEVIS HANGER FOR INSULATED PIPE
5/8 " ROD ,STEEL, GALVANIZED OR
ELECTRO-PLATED (THREADED ROD NOT
ALLOWDED)
NEW INSULATION PROTECTION SHIELD,
STANDARD CLEVIS PIPE HANGER,
GALVANIZED OR ELECTRO-PLATED FED.
NOT TO SCALE
RETAINING
CLIP
C-CLAMP
HANGER ROD (TYP.)
M501
TYPE B-3 SUBMISSION
MECHANICAL DETAILS
JW
MK
ML
D W
G
N
A M
E
C
U
S E
R S
E
M M
A
P P
D A
T A
L O
C A
L P
R O
J E
C T
W I S
E W
O R
K D
I R
M
O T
T U
S E
P
W D
M S
N
C A
N G
M
S A
B
M
D
V
E
D
A T
E
E
M M
O
T
D
A T
E
PITCH PAD TO
DRAIN SURFACE
WATER AND PROVIDE
BROOM FINISH
4,500 PSI
AIR-ENTRAINED
CONCRETE
3/4" CHAMFER
CORNERS
12" THICK 3/4" CLEAN STONE
BASE MATERIAL
ON COMPACTED SUBGRADE
6"
M
I N
ROOF
SEE ARCH. DWGS
CONCENTRIC PIPE
THIMBLE
VENT TERMINAL/COMBUSTION AIR INLET DETAIL
NOTE:
1. SEE ARCHITECTURAL DWGS FOR ROOF PENETRATION DETAILS AND ROOF FLASHING DETAILS.
2. VENT PIPE SHALL BE WIND RESTRAINED. SEE SPECIFICATION 230548.
SEE ARCH. DWGS
FOR DETAILS
RAIN CAP
5" Ø
NOT TO SCALE
NOTES:
1. CLEARANCE SHOWN ON DETAIL IS FROM BASIS OF DESIGN
EQUIPMENT'S MANUFACTURER'S RECOMMENDATIONS.
2. ENTIRE ASSEMBLY SHALL BE WIND RATED WITH
SIGNED/SEALED CALCULATIONS BY A NC LICENSED P.E.,
INCLUDING THE EQUIPMENT, MOUNTING CURB, ATTACHMENTS,
INSTALLATION, ETC. SEE SPECIFICATION 230548 VIBRATION
AND WIND CONTROLS FOR ADDITIONAL REQUIREMENTS.
PLUMBING SYMBOLS
NG
CHECK VALVES
CONNECTION TO EXISTING SYSTEM
FLOOR DRAIN
TEMPERATURE & PRESSURE RELIEF VALVE
PIPE REDUCER
PIPE UNION
SHOWER HEAD
ROOF DRAIN/AREA DRAIN
NATURAL GAS PIPING
DOMESTIC HOT WATER PIPING
TRAP
VENT PIPING
DOMESTIC COLD WATER
STORM DRAIN PIPING
DIRECTION OF FLOW
ST
GV
GAS VENT PIPING
SANITARY PIPING
S
PLUMBING ABBREVIATIONS
AFF
A.D.
AV
AW
CO
CODP
CFH
CW
DN.
DWG.
EES
EXIST (E)
FAI
FD
FT
G
GAL
GPH
HP
HW
HWR
IE
LAV
L
N.I.C.
P/
RD
RM
PRV
S/SAN
SS
MS
TYP
UR
V
VTR
WC
WCO
ABOVE FINISHED FLOOR
ACCESS DOOR
ACID VENT
ACID WASTE
CLEANOUT
CLEANOUT DECK PLATE
CUBIC FEET PER HOUR
DOMESTIC COLD WATER
DOWN
DRAWING
EMERGENCY EYEWASH + SHOWER
EXISTING
FRESH AIR INLET
FLOOR DRAIN
FOOT/FEET
GAS
GALLONS
GALLONS PER HOUR
HORSEPOWER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
INVERT ELEVATION
LAVATORY
LEADER
NOT IN CONTRACT
PER
ROOF DRAIN
ROOM
PRESSURE REDUCING VALVE
SANITARY
SERVICE SINK
MOP SINK
TYPICAL
URINAL
VENT
VENT THROUGH ROOF
WATER CLOSET
WALL CLEANOUT
LIMITS OF VENDOR
LIMITS OF WORK
WATER HAMMER ARRESTER
WATER HEATER
WHA
WH
PIPE UP
PIPE DOWN
GAS COCK (GAS VALVE)
GATE VALVE OR BALL VALVE
ELEVATIONEL
C.L.
L
C CENTER LINE
EM EW
EMERGENCY EYE WASH
FINISH
FIXTURE UNITS
FLOOR
FIN.
F.U.
FL.
GPF GALLONS PER FLUSH
GPM GALLONS PER MINUTE
HB HOSE BIBB
KS KITCHEN SINK
RT RUNNING TRAP
SL SLEEVE
SH SHOWER
W WASTE
SH DR SHOWER DRAIN
HOT WATER RETURN PIPING
IW INDIRECT WASTE
POINT OF DISCONNECTION
XXX = SHEET NUMBER ON WHICH DETAIL IS LOCATED
A = DETAIL NUMBER
IDENTIFICATION TARGET:
A
XX X
PIPE RISE
PIPE CAP
CLEANOUT DECK PLATE
CLEANOUT
HOSE BIBB
D
DETECTOR (CARBON MONOXIDE
AND COMBUSTIBLE GAS)
1. THE CONTRACTOR SHALL OBTAIN ANY AND ALL PERMITS
REQUIRED FOR THE PERFORMANCE OF WORK AND PAY ALL
FEES IN CONNECTION THEREWITH.
2. CONTRACTOR SHALL CHECK AND VERIFY THE EXACT
LOCATION OF ALL PIPE PENETRATIONS, PIPE ELEVATIONS,
AREA DRAINS, ETC.
3. PROVIDE SHUT OFF VALVES AND UNIONS/FLANGES AT BASE
OF ALL RISERS, MAINS, ALL BRANCHES AND ALL
FIXTURE/EQUIPMENT CONNECTIONS IN ORDER TO ISOLATE
FOR MAINTENANCE PURPOSES.
4. PROVIDE ACCESS DOORS FOR VALVES, AND ANY OTHER
EQUIPMENT AND ACCESSORIES THAT MAY REQUIRE ACCESS
FOR MAINTENANCE OR OPERATION WHICH ARE LOCATED
BEHIND WALLS AND PARTITIONS OR CONCEALED IN HUNG
CEILINGS. COORDINATE INSTALLATION WITH GENERAL
CONTRACTOR.
5. THE CONTRACTOR SHALL COORDINATE PLUMBING WORK
WITH ALL OTHER TRADES AND VERIFY DIMENSION AND
CONDITIONS AT THE SITE PRIOR TO BEGINNING WORK. NO
ADDITIONAL COSTS WILL BE ACCEPTED IF ATTRIBUTED TO
FAILURE TO COORDINATE OR VERIFY.
6. ALL PLUMBING LINES SHOWN ARE DIAGRAMMATIC AND NOT
INTENDED TO SHOW EXACT LOCATIONS. THE CONTRACTOR
SHALL INSTALL PIPING SYSTEM TO MINIMIZE LENGTH OF
RUNS AND AVOID INTERFERENCES.
7. ALL PIPING BELOW GRADE SHALL BE INSTALLED TO CLEAR
FOOTINGS AND SHALL NOT BE INSTALLED WITHIN OR BELOW
THE TRIANGULAR BEARING PLANE OF ALL FOOTINGS.
8. INSTALL PIPING AS STRAIGHT AND DIRECT AS POSSIBLE
FORMING RIGHT ANGLE OR PARALLEL LINES WITH BUILDING
WALLS, NEATLY SPACED, RISERS PLUMB AND TRUE, AND
AVOID INTERFERENCE WITH OTHER CONSTRUCTION.
9. ALL PIPE SLEEVES SHALL BE COORDINATED WITH
STRUCTURAL ENGINEER FOR SIZE, LOCATION AND
ELEVATION.
GENERAL PLUMBING NOTES
TD TRENCH DRAIN
RPZ REDUCED PRESSURE ZONE (BACKFLOW PREVENTER)
NFWH NON-FREEZE WALL HYDRANT
DCDA DOUBLE CHECK DETECTOR ASSEMBLY
M
PLUG VALVE
NG METER
NG REGULATOR
TW TEMPERED WATER
NG NATURAL GAS
GAS FIRED WATER HEATER SCHEDULE
TAG NO.
LOCATION TYPE
PIPE SCHEDULE
SYSTEM LOCATION MATERIAL TYPE STANDARD JOINTS
TYPE L
FITTINGS
DOMESTIC WATER
ABOVE GROUND
COPPER
ASTM B88 SOLDERED WROUGHT
COPPER
TYPE K
DOMESTIC WATER
BURIED
COPPER ASTM B88 COMPRESSION
WROUGHT
COPPER
HUB+SPIGOT
SANITARY/VENT
ASTM A 74 RUBBER GASKET
CAST IRON
NO-HUB
SANITARY/VENT
ABOVE GROUND
CAST IRON ASTM A 888
CISPI 301
HUBLESS
COUPLINGS
CAST IRON
BLACK
GAS PIPING
2 1/2" AND SMALLER
ABOVE GROUND
STEEL ASTM A106 SCH. 40 THREADED
THREADED
MALLEABLE IRON
ANS B16.3 &
CLASS 150
BURIED
CAST IRON
WH-1
MECHANICAL
ROOM
FIXTURE SCHEDULE
TAG FIXTURE TYPE WASTE VENT HOT WATER
COLD WATER
DESCRIPTION
LAV
LAVATORY
1-1/2" 1-1/2" 1/2" 1/2"
WC
WATER CLOSET
4" 2" - 1"
PS
PANTRY SINK
SH
SHOWER
1-1/2"
1-1/2" 1-1/2" 1/2" 1/2"
2" 1/2"
9-199
1/2"
TANKLESS
CONDENSING
GAS
(CFH)
NOTES
UNDER COUNTER,
LEVER OPER. FAUCET
FLOOR MOUNTED,
BOTTOM OUTLET, LEVER
OPERATED FLUSH VALVE
UNDER COUNTER,
STAINLESS STEEL 18X16,
LEVER OPER. FAUCET
COMMERCIAL SHOWER KIT WITH
PRESSURE BALANCE SHOWER VALVE,
VALVE TRIM, 3 FUNCTION HAND SHOWER,
IN-LINE VACUUM BREAKER, METAL HOSE,
WALL SUPPLY, 36" SLIDE BAR, AND A
PRECAST TERRAZZO FLOOR RECEPTOR
TRAP PRIMER SCHEDULE
TAG
LOCATION
NOTES
POWER
TP-1
MECHANICAL
ROOM
1, 2 1/2"
OUTLET
(IN)
EQUIPMENT SERVED
FLOOR DRAINS
8.8 HOLDING
12.1 IN RUSH
120/1/60
VA V/PH/HZ
1/2"
INLET
(IN)
NOTES: 1. INCLUDE DISTRIBUTION UNIT, DU SERIES. 2. 16 GAUGE STEEL ACCESS DOOR
EMERGENCY EYEWASH +
SHOWER SCHEDULE
TAG NO.
LOCATION TYPE ELECTRICAL
EES-1
FROST PROOF WITH
HEAT TRACE FOR
NON-HAZARDOUS AREA
120V/ 1PH
0.7AMP/ 80W
M&I
MAGAZINE
NOTES: 1. SIGNAL LIGHT - AMBER, NEMA 4X
ELECTRIC WATER HEATER SCHEDULE
TAG NO.
LOCATION TYPE
WH-2
M&I
MAGAZINE
36TANKLESS
RATING
(KW)
VOLTS/PH
208/3
CURRENT
(AMPS)
TEMP RISE
(@ 20 GPM)
NOTES
100 1-412 °F
NOTES: 1. FREEZE PROTECTION RATING 2. BRACKETS FOR WALL MOUNTING
3. SIREN AND BEACON 4. EMERGENCY STOP
1, 2, 3
NOTES:
1. SET TEMPERATURE CONTROL SET POINT TO 115°F TO PREVENT SCALDING
2. INCLUDE NEUTRALIZER KIT
3. INCLUDE CONCENTRIC VENT KIT
HEAT TRACING
5-10.5
GAS
PRESSURE
(INCH WC)
NOTES
4.4 GPM
FLOW RATE
AT 90°F
TEMP RISE
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C p a n s i o n
SHEET OF 53
P001
TYPE B-3 SUBMISSION
PLUMBING
NOTES, SYMBOLS,
ABBREVIATIONS &
SCHEDULES
CPK
DS
MLP
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G S
T I D
M S
N
C A
N G
M
S A
B
P
D
V
E
D
A T
E
S
T I
O
T
D
A T
E
P
R
Z
M
WC
LAV
SH
PANTRY
SINK
3/4" HW
1" CW
4" VTR
2" V DN
1/2" HW
1-1/2" SAN DN,
1-1/2" VENT UP
1/2" CW
1/2" HW
1-1/2" SAN DN,
1-1/2" VENT UP
1/2" CW
1" CW
2" V DN
1/2" CW/HW
2" SAN
DN
1-1/2" V
DN
4" FD
3/4" NG DN
TO AHU-1
AHU-1
SEE HVAC DWGS
1-1/4" NG
2" RPZ (STACKED
BELOW DCDA)
1/2" CW
3" FD
1-1/2" V
DN
TP-1
3/4" NG
VALVE FOR FUTURE USE
FOR REFRIGERATOR
WATER HEATER (WH-1)
SEE NOTE 1
1" NG DN
TO WH-1
1/2" CW/HW
2" CW DN
4" SAN DN
1-1/2" VENT
2"
1-1/2"
CLEANOUT
1-1/2" NG DN
GAS METER
1/2" HW
1" CW
BATHROOM
UNISEX
AREA
BREAK
101A
ELEC.ROOM
MECH./COMM./
NORTH
ADMINISTRATION
BUILDING
4" SAN UP
TO WC
2" SAN UP
TO SH
1-1/2" SAN
UP TO LAV
1-1/2" SAN
UP TO PS
4" SAN UP TO FD
4" SAN, SEE
DWG C103 FOR
CONTINUATION
2" CW UP
1-1/2" NG, SEE
DWG C103 FOR
CONTINUATION
2" V UP
2" V UP
1-1/2" V
UP
2" CW. SEE DWG C103
FOR CONTINUATION
3" UP
TO FD
4" SAN
2" UP TO
CLEANOUT
3" SAN
2" SAN
2" SAN
BATHROOM
UNISEX
AREA
BREAK
101A
ELEC.ROOM
MECH./COMM./
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C p a n s i o n
SHEET OF 53
SCALE: 1/2" = 1'-0"
PLUMBING FLOOR PLAN - ADMINISTRATION BUILDING
P101
TYPE B-3 SUBMISSION
PLUMBING
ADMINISTRATION BUILDING
UNDERSLAB PLAN &
FLOOR PLAN
CPK
DS
MLP
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G S
T I D
M S
N
C A
N G
M
S A
B
P
D
V
E
D
A T
E
S
T I
O
T
D
A T
E
P
M
NTS
KEY PLAN
10 2 4
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
PLUMBING UNDERSLAB FLOOR PLAN - ADMINISTRATION BUILDING
NOTES:
1. WATER HEATER FLUE PROVIDED BY
MECHANICAL. SEE DWG M101.
NORTH
M&I
MAGAZINE
ALUM. WORK BENCH
96" X 30" (N.I.C.)
T W
TW
T W
EMERGENCY EYEWASH & SHOWER (EES-1)
WATER HEATER (WH-2)
1-1/4" CW. SEE DWG C103
FOR CONTINUATION
HAMMER
ARRESTOR
(SIZE B)
1-1/4" TW (SEE NOTE 1)
M&I
MAGAZINE
INSPECTION
AND
MAINTENANCE
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C p a n s i o n
SHEET OF 53
P102
TYPE B-3 SUBMISSION
PLUMBING
M&I MAGAZINE
UNDERSLAB PLAN &
FLOOR PLAN
CPK
DS
MLP
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G S
T I D
M S
N
C A
N G
M
S A
B
P
D
V
E
D
A T
E
S
T I
O
T
D
A T
E
P
M
NTS
KEY PLAN
10 2 4
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
PLUMBING FLOOR PLAN - M&I MAGAZINE
NOTES:
1. PROVIDE HEAT TRACING, PIPING INSULATION
AND STAINLESS STEEL INSULATION JACKETING
ON OUTDOOR PIPING ABOVE THE FROST LINE.
WALL OR PARTITION
ESCUTCHEON PLATE
ON BOTH SIDES TO
COMPLETELY COVER
OPENING
PACK SPACE BETWEEN PIPE
INSULATION & SLEEVE WITH
MINERAL WOOL OR EQUIVALENT
NON-COMBUSTIBLE MATERIAL 25
[1/2"] CLEARANCE
PIPE
INSULATION WHERE SPECIFIED
SHEET METAL SLEEVE MINIMUM
GAUGE NO. 14
5/8 " ROD ,STEEL, GALVANIZED OR
ELECTRO-PLATED (THREADED ROD NOT
ALLOWDED)
NEW INSULATION PROTECTION SHIELD,
FED. SPEC. WW-H-171E TYPE 41 AND
MSS SP-69 TYPE 40
STANDARD CLEVIS PIPE HANGER,
GALVANIZED OR ELECTRO-PLATED FED.
SPEC. WW-H-171E, TYPE I, OR MSS SP-69,
TYPE I
2" (MIN)
CONCRETE
SLAB
PIPE SLEEVE WITH
WATER STOP
PIPE
INTERLOCKING
SYNTHETIC RUBBER
LINK-TYPE SEAL
SLEEVE CLOSURE
PIPE
SUPPORT
(TYP)
BLDG. WALL
TO DOMESTIC
SYSTEM
DOMESTIC WATER
SERVICE
RPZ BACKFLOW
PREVENTER
SLEEVE
CLOSURE
M I
M A
X
FD WITH
FUNNEL
NTS
SLEEVE CLOSURE THROUGH CONCRETE SLAB
NTS
CEILING HUNG CLEVIS HANGER FOR INSULATED PIPE
NTS
PIPE PENETRATION THRU INTERIOR WALL
NTS
BACKFLOW PREVENTER (DOMESTIC WATER) DETAIL
SUPPORT FROM STRUCTURE
DRAIN W/
AIR GAP
FITTING
CONTROL PANEL
SIGN
FLOW SWITCH
1-1/4" TW
FLASHING LIGHT
JUNCTION BOX
NTS
EMERGENCY EYEWASH SHOWER DETAIL
WALL
FLOOR MOUNTED
WATER CLOSET
FINISHED FLOOR
LEVER OPERATED
FLUSH VALVE
WALL FINISH
CONNECT TO
VENT HEADER
NTS
FLOOR MOUNTED WATER CLOSET DETAIL
WASTE HEADER
FINISHED FLOOR
WALL FINISH
LAV
WATER SUPPLY
SAN DN
VENT UP
NTS
LAVATORY DETAIL
THERMOMETER
DOMESTIC HOT WATER
DOMESTIC COLD WATER
TO FD CONDENSATE
NEUTRALIZER
GAS
NTS
WATER HEATER DETAIL
NTS
TYPICAL DETAIL FOR GAS PIPE CONNECTION TO EQUIPMENT
NATURAL GAS
SUPPLY
GAS VALVE
TO EQUIPMENT
TYPICAL
CONNECTION TO
EQUIPMENT INSIDE
BUILDING
DRIP LEG
M
UNION (TYP)
TO EQUIPMENT
UNION (TYP)
GAS VALVE
DRIP LEG
GAS
SUPPLY
M
PRESSURE
GAUGE (TYP.)
COMBUSTION AIR SUPPLY
EXHAUST VENT
EMERGENCY
SHOWER VALVE
NTS
OUTDOOR WATER HEATER DETAIL
HAMMER
ARRESTOR
(REQUIRED)
1-1/4" DIELECTRIC UNION
BALL VALVE
1-1/4" DIA
Y-STRAINER 40 MESH
DRAIN
1-1/4" DIA
10 FT
MAX
NOTES:
1. PROVIDE HEAT TRACE ON PIPING
SUBJECT TO FREEZING
HEAT TRACE. SEE NOTE 1 (TYP.)
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C p a n s i o n
SHEET OF 53
P501
TYPE B-3 SUBMISSION
PLUMBING
DETAILS
CPK
DS
MLP
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G S
T I D
M S
N
C A
N G
M
S A
B
P
D
V
E
D
A T
E
S
T I
O
T
D
A T
E
P
FIRST FLOOR
DOMESTIC WATER RISER DIAGRAM
MECH ROOM
2" RPZA
RPZ
2" WATER SERVICE.
SEE CIVIL DRAWINGS
FOR CONTINUATION
WH-1
1" CW
3/4" CW
LAV
UNISEX
RESTROOM 103
PS
SH
WC
FIRST FLOOR
SANITARY RISER DIAGRAM
4" SAN. SEE CIVIL
DRAWINGS FOR
CONTINUATION
1/2" HW/CW
1/2" HW/CW
BREAK AREA
101A
1" CW
MECH ROOM
LAV
UNISEX
RESTROOM 103
PS
SH
WC
BREAK AREA
101A
4" VTR
FIRST
FLOOR
NATURAL GAS RISER DIAGRAM
MECH ROOM
GAS METER
(259 CFH, 11" WC)
M
1-1/2" NG. SEE CIVIL
DRAWING C103 FOR
CONTINUATION
WH-1
(199 CFH,
5-10.5" WC)
AHU-1
(60 CFH,
5-14" WC)
3" FD
TP-1
1-1/4" NG
3/4" NG
1/2" TRAP
PRIMER (TYP.)
CAPPED FOR FUTURE USE
(REFRIGERATOR)
3/4" HW
1/2" HW/CW
1-1/2"
2"
4"
2"
2"
4" FD
1/2" CW
1/2" TO FD'S
1" NG
1/2" HW/CW
THERMOMETER
DIRT LEG
(TYP.)
FIRST FLOOR
DOMESTIC WATER RISER DIAGRAM -
M&I MAGAZINE
MAINTENANCE
AND
INSPECTION
WH-2
1-1/4" CW. SEE CIVIL
DWG C103 FOR
CONTINUATION
HAMMER ARRESTOR
(SIZE B)
EES-1
1-1/4" TW
HEAT TRACE.
SEE NOTE 1 (TYP.)
NOTES:
1. PROVIDE HEAT TRACE ON
PIPING SUBJECT TO FREEZING
RPZA
(STACKED BELOW DCDA)
SEE FP DRAWINGS
CO
3"
1" CW
1/2" HW
1/2" CW
APPLIANCE
REGULATOR
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C p a n s i o n
SHEET OF 53
P601
TYPE B-3 SUBMISSION
PLUMBING
RISER DIAGRAMS
CPK
DS
MLP
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G S
T I D
M S
N
C A
N G
M
S A
B
P
D
V
E
D
A T
E
S
T I
O
T
D
A T
E
A
UPRIGHT SPRINKLER
SIDEWALL SPRINKLER
OS&Y VALVE W/ TAMPER SWITCH
W/
TYP
SP
WITH
TYPICAL
SPRINKLER
POUNDS PER SQUARE INCH
MATIONAL PIPE THREADNPT
GPM GALLONS PER MINUTE
FEETFT
PIPE CAP
MINIMUMMIN
FDC
GPM
DN
DWG.
DOWN
PIPE DOWN
PIPE UP
CHECK VALVE
FIRE DEPT. CONNECTION
GALLONS PER MINUTE
DRAWINGS
SLEEVESL.
CONTIN. CONTINUATION
ABD AUTOMATIC BALL DRIP
PSI
VALVE, GENERAL
TAMPER SWITCH
FLOW SWITCH
SYMBOLS AND LEGEND
CONCEALED SPRINKLER
TS TAMPER SWITCH
6.
5.
4.
GENERAL NOTES
2.
3.
1.
WORK SHALL BE COMPLETE IN ALL RESPECTS, INCLUDING CONNECTION TO
EXISTING SPRINKLER SYSTEM, ALL NEW SPRINKLER WORK PER THE PLANS, AND
ALL REQUIRED ACCESSORIES, DRAINS AND TEST CONNECTIONS.
WORK SHALL INCLUDE ALL LABOR AND MATERIAL FOR A WET TYPE AUTOMATIC
SPRINKLER SYSTEM WITHIN THE BUILDING WHERE INDICATED ON PLANS.
PROVIDE ALL REQUIRED SPRINKLER HEADS, PIPING, HANGERS, SUPPORTS, AND
DRAINS.
PROVIDE "AS-BUILT" DRAWINGS.
THE WORK IS TO BE PERFORMED IN STRICT COMPLIANCE WITH NFPA 13 (2013
EDITION), ALL CODES AND OTHER NFPA REGULATIONS GOVERNING WORK OF
THIS NATURE.
ALL EQUIPMENT AND MATERIALS SHALL BE AS SPECIFIED OR "APPROVED
EQUAL" BY THE ENGINEER OR ARCHITECT.
SPRINKLER SYSTEM NOTES
1. THE SPRINKLER SYSTEM SHALL BE HYDRAULICALLY DESIGNED AND SHALL CONFORM WITH UFC 3-600-01 AND NFPA 13:
A. THE INSTALLATION COMPONENTS, SPACING, LOCATION, POSITION & TYPE OF SYSTEMS SHALL CONFORM
TO CHAPTERS 4 AND 5.
B. THE OCCUPANCY OF THE AREAS TO BE SPRINKLERED IN ACCORDANCE WITH SECTION 2-1 AND AS
SPECIFIED ON THE PLANS.
C. PIPING SPECIFICATIONS, SYSTEM TEST PIPES, PROTECTION AGAINST CORROSION, FITTINGS, VALVES, HANGERS, GUARDS AND SHIELDS SHALL BE IN ACCORDANCE WITH CHAPTER 3.
D. STOCK OF EXTRA SPRINKLERS SHALL BE FURNISHED AS PER SECTION 3-2.9 (REQUIRED FOR EACH
TEMPERATURE RATING).
E. SPACING, LOCATION AND POSITION OF SPRINKLERS SHALL BE IN ACCORDANCE WITH CHAPTER 5.
F. ALL BLIND SPACES EXCEEDING SIX INCHES IN WIDTH OR DEPTH WHICH CONTAIN COMBUSTIBLE MATERIAL
SHALL BE SPRINKLERED.
G. MINIMUM CLEARANCE OF SPRINKLER DEFLECTOR TO CEILING SHALL BE AS PER SECTION 5-5.4.
H DISTANCE OF SPRINKLER FROM HEAT SOURCE SHALL BE IN ACCORDANCE WITH TABLE 5-3.1.4.2..
I. DRAINAGE SHALL CONFORM TO SECTION 5-14.2.
J. ALL VALVES SHALL BE IDENTIFIED AS REQUIRED BY PARAGRAPH 3-8.
K. DRAIN VALVES AND TEST VALVES SHALL BE APPROVED TYPE AS PER SECTION 3-8.2.
L. HANGERS SHALL BE OF A TYPE APPROVED FOR USE WITH THE PIPE OR TYPE INVOLVED. SPRINKLER PIPING
SHOULD BE SUPPORTED BY ROUND WROUGHT IRON U-TYPE OR APPROVED ADJUSTABLE HANGERS.
M. SPRINKLERS SHALL BE AN APPROVED TYPE AS PER SECTION 5-4.
N. TEMPERATURE RATING SHALL COMPLY WITH SECTION 5-3.1.4.
THE CONTRACTOR IS RESPONSIBLE FOR ALL WORK, MATERIALS, AND LABOR
REQUIRED TO SATISFY A COMPLETE WORKING SYSTEM WHETHER SPECIFIED
OR IMPLIED.
7.
THE DRAWINGS INCLUDED AS PART OF THIS SET OF CONSTRUCTION
DOCUMENTS ARE DEFINED AS PRELIMINARY SPRINKLER PLANS AS SPECIFIED IN
NFPA 13. FINAL WORKING DRAWINGS SHALL BE PREPARED BY THE SPRINKLER
CONTRACTOR AND REVIEWED BY THE ENGINEER.
8.
DO NOT SCALE THIS DRAWING FOR EXACT DIMENSIONS. VERIFY ALL FIGURES,
CONDITIONS, AND DIMENSIONS AT THE JOB SITE.
9.
THE SPRINKLER PLANS ARE INTENDED TO BE DIAGRAMTIC. THEY ARE NOT
INTENDED TO SHOW EVERY ITEM IN ITS EXACT LOCATION.
10.
DESIGN AND INSTALLATION SHALL CONFORM TO NFPA 13 AND UFC 3-600-01.
11.
HANGER INSTALLATION AND SPACING SHALL BE IN ACCORDANCE WITH NFPA 13
12.
PROVIDE HIGH TEMPERATURE SPRINKLERS NEAR BOILERS, HEATERS, ETC. IN
ACCORDANCE WITH NFPA 13
13.
COORDINATE NEW SPRINKLER HEAD ELEVATIONS WITH FINISHED CEILING
HEIGHT.
14.
OBTAIN ALL APPROVALS BEFORE STARTING INSTALLATION.
15.
ARRANGEMENTS OF SPRINKLER HEADS IS DIAGRAMMATIC AND ACTUAL
ARRANGEMENTS SHALL BE AS REQUIRED BY FIELD CONDITIONS.
16.
INSTALL ALL SPRINKLERS IN CENTER OF TILES AND PROVIDE NECESSARY
ELBOWS, TEES AND NIPPLES TO ACCOMMODATE SAME.
17.
18.
19.
CONTRACTOR SHALL COORDINATE SPRINKLER PIPING AND HEAD LOCATIONS WITH
DUCTWORK AND LIGHTING FIXTURES.
20.
21.
ALL SPRINKLER LINES SHALL AVOID INTERFERENCE WITH LIGHTING FIXTURES,
DUCTS AND PIPING.
22.
PROVIDE EXPOSED PIPES WITH APPROVED TYPE, SINGLE PIECE, CAST BRASS
OR CAST IRON ESCUTCHEONS, CHROME PLATED, FIRMLY HELD IN PLACE.
PROVIDE PENDANT SPRINKLER HEADS WITH SPECIAL TYPE CHROME PLATED
ESCUTCHEONS, FIRMLY HELD IN PLACE.
TEST ENTIRE SYSTEM PIPING HYDROSTATICALLY FOR TWO HOURS AT 200 P.S.I.
OR AT 50 P.S.I. ABOVE MAXIMUM WORKING PRESSURE (WHICHEVER IS
GREATER) AND IN ACCORDANCE WITH ALL REQUIREMENTS OF THE
REFERENCED CODES.
ALARM CHECK VALVE
SPRINKLER PIPE
SPRK
TS
FS FLOW SWITCH
FCA FLOOR CONTROL ASSEMBLY
HYDRANT FLOW TEST
DATE 11/27/2018
BY VSC Fire & Security Inc.
LOCATION Building 74 - Hydrants 25, 27
STATIC PRESSURE 80 PSI
RESIDUAL PRESSURE 75 PSI
FLOWRATE 735 GPM
DESIGN CRITERIA
BUILDING M&I MAGAZINE ADMINISTRATION BUILDING
SPRINKLER SYSTEM WET PIPE WET PIPE
CLASSIFICATION EXTRA HAZARD LIGHT HAZARD
DENSITY 0.3 GPM/ SQ FT 0.1 GPM/ SQ FT
APPLICATION AREA 2,500 SQ FT 1,500 SQ FT
SPRINKLER K-FACTOR 11.2 5.6
HOSE DEMAND AT SOURCE 500 GPM 250 GPM
EXP EXPLOSION PROOF
SPRINKLER SCHEDULE
SYMBOL MAXTYPE
RESPONSE FINISH SIZE
(IN)
TEMPERATURE
RATING
K FACTOR MIN
(F)
COVERAGE
(FT)
PRESSURE
CONCEALED
10X13
15X15
STANDARD ORDINARY 7
STANDARD ORDINARY 7
1/2" 5.6
1/2" 5.6
UPRIGHT
(STORAGE/
MECH RM)
CHROME
WHITE
COVER
RECESSED PENDENT SPRINKLER
NOTES
LOCATION
ADMINISTRATION
BUILDING
ADMINISTRATION
BUILDING
M&I MAGAZINE
BUILDING
NOTES: 1. INCLUDE MODEL FP RECESSED ESCUTCHEON
STANDARD 1653/4" 11.2BRONZE
RECESSED
PENDENT
10X13 7
(PSI)
HYDRAULIC FLOW ANALYSIS - M&I MAGAZINE BUILDINGHYDRAULIC FLOW ANALYSIS - ADMINISTRATION BUILDING
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C
M p a n s i o n
SHEET OF 53
FP001
TYPE B-3 SUBMISSION
FIRE PROTECTION
NOTES, SYMBOLS,
ABBREVIATIONS &
SCHEDULES
CPK
DS
MLP
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G S
T I D
M S
N
C A
N G
M
S A
B
F
P D
V
E
D
A T
E
S
T I
O
T
D
A T
E
P
REF
(NIC)
BATHROOM
UNISEX
AREA
CONFERENCE
ELEC.ROOM
MECH./COMM./
OFFICE
MASQ
OFFICE
SHOPCHIEF
2-1/2"
1"
1-1/2"
1"1"
2-1/2" 2-1/2" 2"
1"
1"
1"
1"
1"
1"
1-1/2"
FDC
1"
2-1/2"
4"
6" FIRE SERVICE.
SEE DWG C103 FOR
CONTINUATION
2-1/2" DCDA
NORTH
ADMINISTRATION
BUILDING
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C
M p a n s i o n
SHEET OF 53
SCALE: 1/2" = 1'-0"
FIRE PROTECTION FLOOR PLAN - ADMINISTRATION BUILDING
FP101
TYPE B-3 SUBMISSION
FIRE PROTECTION
ADMINISTRATION BUILDING
FLOOR PLAN
CPK
DS
MLP
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G S
T I D
M S
N
C A
N G
M
S A
B
F
P D
V
E
D
A T
E
S
T I
O
T
D
A T
E
P
M
NTS
KEY PLAN
10 2 4
SCALE: 1/2" = 1'-0"
NORTH
M&I
MAGAZINE
PIR PIR
RECESSED PENDENT
SPRINKLER
FIRE DEPARTMENT
CONNECTION W/
AUTOMATIC BALL DRIP
1"
1"
1-1/2" 1"
1"
2"
4"
RISER CHECK VALVE IN
VERTICAL RISER
2-1/2" DCDA
2-1/2" FIRE SERVICE.
SEE DWG C103 FOR
CONTINUATION
2" TO SPRINKLER SYSTEM.
INSPECTION
AND
MAINTENANCE
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C p a n s i o n
SHEET OF 53
FP102
TYPE B-3 SUBMISSION
FIRE PROTECTION
M&I MAGAZINE
FLOOR PLAN
CPK
DS
MLP
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G S
T I D
M S
N
C A
N G
M
S A
B
F
P D
V
E
D
A T
E
S
T I
O
T
D
A T
E
P
M
NTS
KEY PLAN
10 2 4
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
FIRE PROTECTION FLOOR PLAN - M&I MAGAZINE
CLG. ESCUTCHEON
CONCEALED TYPE
SPRINKLER HEAD
CEILING
3'-0"±
VARIES
V A
R I E
S
SPRINKLER
BRANCH
1" TURN
DOWN
PIPING &
FITTINGS
1"x 1/2"
REDUCER
NTS
DETAIL
NTS
PIPE PENETRATION (PER UL NO. C-AJ-1291)
THREADED ROD SIZE DETERMINED
BY SUPPORTED WEIGHT. SEE
SPECIFICATION 211313 FOR
SPACING AND SIZE
NTS
PIPE SUPPORT DETAIL
SWIVEL RING
PIPE
STANDARD CLEVIS
PIPE HANGER
ATTACH TO STRUCTURE
A
SECTION A-A
A
FLOOR OR WALL
ASSEMBLY
PIPE (STEEL, IRON
OR COPPER)
UL RATED
INTUMESCENT
FIRESTOP SEALANT
UL RATED
INTUMESCENT
FIRESTOP SEALANT
M&I MAGAZINE
BUILDING
SPRINKLER RISER DIAGRAM -
M&I MAGAZINE BUILDING
TSTS
TS
2" RISER
CHECK VALVE
2-1/2"
TAMPER SWITCH
TYP. (SEE NOTE 1)
2" TO SPRINKLER SYSTEM
NORMALLY CLOSED
2-1/2" GATE VALVE
(BACKFLOW PREVENTER
TEST VALVE)
GRADE
2-1/2" X 2-1/2" X 4" FDC
W/ AUTOMATIC BALL DRIP
4"
FS
EXP
EXPEXP
EXP
NOTES:
1. ALARM DEVICES IN M&I MAGAZINE
BUILDING SHALL BE RATED
EXPLOSION PROOF
UPRIGHT SPRINKLER
ROOF
SPRK PIPE
NTS
UPRIGHT SPRINKLER
FIRE RATED WALL OR PARTITION
ESCUTCHEON PLATE
ON BOTH SIDES TO
COMPLETELY COVER
OPENING
PACK SPACE BETWEEN PIPE
INSULATION & SLEEVE WITH
MINERAL WOOL OR EQUIVALENT
NON-COMBUSTIBLE MATERIAL
1/2" CLEARANCE
PIPE
INSULATION WHERE SPECIFIED
SHEET METAL SLEEVE MINIMUM
GAUGE NO. 14
NTS
PIPE PENETRATION THRU INTERIOR WALL
MECHANICAL
ROOM 102
SPRINKLER RISER DIAGRAM -
ADMINISTRATION BUILDING
TSTS
TS
2-1/2" RISER
CHECK VALVE
2-1/2" TO SPRINKLER SYSTEM
2-1/2" TO SPRINKLER SYSTEM
NORMALLY CLOSED
2-1/2" GATE VALVE
(BACKFLOW PREVENTER
TEST VALVE)
GRADE
2-1/2" X 2-1/2" X 4" FDC
W/ AUTOMATIC BALL DRIP
EXTERIOR WALL
4"
UNISEX
RESTROOM 103
ROOM 101
MASQ OFFICE 104
SHOP CHIEF
OFFICE 105
FS
2-1/2"
FLOW SWITCH
(SEE NOTE 1)
2-1/2" DCDA
6" FIRE SERVICE.
SEE CIVIL DRAWINGS
FOR CONTINUATION
6" TO 2-1/2"
REDUCER
2-1/2" DCDA
2-1/2" FIRE SERVICE.
SEE CIVIL DWG C103
FOR CONTINUATION
2" TO SPRINKLER SYSTEM
PRESSURE
GAUGE (TYP.)
PRESSURE
GAUGE (TYP.)
PIPE
SUPPORT
(TYP)
BLDG. WALL
TO FIRE
SYSTEM
FIRE PROTECTION
SERVICE
DOUBLE CHECK
DETECTOR ASSEMBLY
SLEEVE
CLOSURE
NTS
BACKFLOW PREVENTER (FIRE SERVICE) DETAIL
PRESSURE
GAUGE (TYP.)
TS TS
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C p a n s i o n
SHEET OF 53
FP501
TYPE B-3 SUBMISSION
FIRE PROTECTION
DETAILS
CPK
DS
MLP
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G S
T I D
M S
N
C A
N G
M
S A
B
F
P D
V
E
D
A T
E
S
T I
O
T
D
A T
E
P
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C
M p a n s i o n
SHEET OF 53
GENERAL NOTES
1. COORDINATE ALL WORK SHOWN ON DRAWINGS WITH OTHER TRADES TO ASSURE THAT ALL SYSTEMS ARE
COMPLETE AND OPERATIONAL. COORDINATE ALL EQUIPMENT LOCATIONS AND CONDUIT RUNS SUPPLIED
AND/OR INSTALLED UNDER THIS SECTION TO AVOID CONFLICTS OR OBSTRUCTIONS TO OTHER TRADES.
PROVIDE ALL NECESSARY PULL BOXES, VERTICAL SUPPORT BOXES, AND CONDUIT OFFSETS REQUIRED TO
ACCOMPLISH THE ABOVE NOTED COORDINATION, WHETHER OR NOT INDICATED ON PLANS. ALL VERTICAL
SUPPORT BOXES, PULL BOXES, ETC. SHALL BE INSTALLED WHERE REQUIRED TO FACILITATE PULLS AND AT
CODE REQUIRED INTERVALS, AT A MINIMUM.
2. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, NATIONAL
SAFETY CODE, NFPA, OSHA REGULATIONS AND ALL OTHER EXISTING CODES AND REGULATIONS OF
AUTHORITIES WHICH HAVE JURISDICTION.
3. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT EVERY DETAIL OR CONDUIT IS SHOWN.
EXISTING CONDITIONS AND DIMENSIONS SHALL BE VERIFIED IN THE FIELD BEFORE COMMENCING ANY
FABRICATION, ORDERING ANY MATERIAL, OR PERFORMING ANY WORK. ANY DEPARTURE FROM CONCEPT
SHOWN ON THE CONTRACT DRAWINGS SHALL BE SUBMITTED TO THE AUTHORITY HAVING JURISDICTION FOR
APPROVAL. ALL ELECTRICAL EQUIPMENT SHOWN ON THE DRAWINGS AND/OR REQUIRED FOR THE FULL
INTEGRITY OF THE CONTRACT SHALL BE FURNISHED, INSTALLED AND CONNECTED BY THE CONTRACTOR, EXCEPT WHERE EQUIPMENT SHOWN IS IDENTIFIED AS "EXISTING" OR OTHERWISE NOTED ON THE DRAWINGS.
4. UNLESS OTHERWISE NOTED, EQUIPMENT TO BE FURNISHED AND INSTALLED UNDER THIS CONTRACT IS
SHOWN IN HEAVY LINES. EXISTING EQUIPMENT TO REMAIN IS SHOWN IN LIGHT AND/OR DASHED LINES.
5. UNLESS OTHERWISE NOTED, EQUIPMENT AND MATERIALS TO BE FURNISHED AND INSTALLED SHALL BE UL
LISTING AND LABELING WHERE SUCH STANDARD HAD BEEN ESTABLISHED FOR THAT TYPE OF
EQUIPMENT/MATERIAL.
6. UNLESS SPECIFICALLY APPROVED, NO WIRES SHALL BE PULLED IN UNTIL THE CONDUIT SYSTEM IS
COMPLETED. NO GREASE OR OIL SHALL BE USED TO FACILITATE THE PULLING OF WIRES; ONLY APPROVED
PULLING COMPOUND SHALL BE USED.
7. FURNISH AND INSTALL TAGS FOR EQUIPMENT, CONDUITS, AND CABLES THAT ARE INSTALLED UNDER THIS
CONTRACT. TAG IDENTIFICATIONS SHALL BE IN ACCORDANCE WITH CONTRACT DRAWINGS.
8. NO ELECTRICAL CONNECTIONS SHALL BE MADE TO, OR WORK PERFORMED ON, ENERGIZED EQUIPMENT.
9. SCHEDULE ALL DISCONNECTION AND INTERRUPTIONS OF ELECTRICAL SERVICE, COMMUNICATIONS AND
SUPERVISORY SYSTEMS ACCORDING TO THE CONSTRUCTION STAGING PLAN SUBMITTED BY THE
CONTRACTOR AND APPROVED BY THE AUTHORITY HAVING JURISDICTION. ALL INTERRUPTIONS SHALL BE
KEPT TO A MINIMUM, THE SCHEDULE SHALL BE SUBMITTED A MINIMUM OF TWO (2) WEEKS BEFORE ANY
ANTICIPATED INTERRUPTION.
10. FINAL CONNECTIONS TO EQUIPMENT SHALL BE MADE ACCORDING TO VENDOR APPROVED SHOP DRAWINGS.
11. PERFORM CUTTING, DRILLING, AND CORE BORINGS TO PROVIDE PENETRATIONS THROUGH WALLS OR
FLOORS FOR ELECTRICAL INSTALLATION WORK, CORE DRILL DIAMETER SHALL NOT BE MORE THAN 25%
LARGER THAN THE CONDUIT'S OUTSIDE DIAMETER. ALL CONDUITS PENETRATING WALLS AND FLOORS SHALL
BE INSTALLED IN A GALVANIZED STEEL SLEEVE WITH FLOOR SUPPORTS. AFTER CONDUIT INSTALLATION, ALL
PENETRATIONS SHALL BE SEALED.
12. SYSTEM CIRCUITS, AND EQUIPMENT SHALL BE GROUNDED IN ACCORDANCE WITH ARTICLE 250 OF THE
NATIONAL ELECTRICAL CODE.
13. CONDUITS SHALL CONTAIN AN INSULATED GROUND WIRE BONDED TO ENCLOSURES AND SIZED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE NEC, IF SIZE IS NOT SHOWN ON THE CONTRACT DRAWINGS.
14. THE EXPOSED NONCURRENT-CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT AND RACEWAYS SHALL
BE GROUNDED. THE CONTRACTOR SHALL ENSURE CONTINUITY OF THE GROUNDING CIRCUIT THROUGH THIS
GROUNDING CONDUCTOR FROM THE SUPPLYING PANEL BOARD GROUNDING BUS TO THE LOAD GROUND
TERMINAL.
15. FURNISH AND INSTALL CONDUIT FITTINGS, CONNECTORS, CLAMPS, HARDWARE, HANGERS, AND SUPPORTS
AS NECESSARY FOR A COMPLETE INSTALLATION.
16. UNUSED OPENING IN CONDUITS, BOXES, DISCONNECT SWITCHES, CABINETS, AND PANEL BOARDS SHALL BE
CLOSED.
17. UPDATE AND PROVIDE NEW PANELBOARD DIRECTORIES TO REFLECT THE CIRCUITING IN EXISTING OR NEW
PANELBOARDS AFFECTED BY THIS ALTERATION.
18. MAINTAIN EXISTING CIRCUIT CONTINUITY OF EXISTING ITEMS WHICH REMAIN BUT ARE AFFECTED BY THIS
ALTERATION. RECONNECT ALL ALTERED OR REROUTED WORK SO THAT DISTURBED INSTALLATION WILL
AGAIN FUNCTION PROPERLY.
19. UPON COMPLETION OF ALL ELECTRICAL WORK, ADJUST AND TEST ELECTRICAL EQUIPMENT, ALL CIRCUITS, SWITCHES, DISCONNECTS AND ANY OTHER ELECTRICAL ITEMS INSTALLED. ANY DEFECTIVE ITEMS SHALL BE
IMMEDIATELY REPAIRED OR REPLACED WITH NEW AND THAT PORTION OF THE SYSTEM SHALL BE
RE-TESTED. ALL SUCH REMEDIAL WORK SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE AUTHORITY
HAVING JURISDICTION.
20. TEMPORARY POWER FROM EXISTING PANELS FOR LIGHTS, DRILLS, WELDING EQUIPMENT, ETC., SHALL BE
LABELED ON THE PANEL AND PRE-APPROVED PRIOR TO INSTALLATION.
21. ALL CONDUCTORS SHALL BE COPPER WITH THNN/THWN INSULATIONS, UNLESS OTHERWISE NOTED.
22. ALL EXISTING EQUIPMENT IS SHOWN FOR INFORMATION AND REFERENCE ONLY. CONTRACTOR TO VERIFY
ALL EXISTING EQUIPMENT IN THE FIELD.
23. ALL COVER PLATES INSTALLED UNDER THESE CONTRACT DRAWINGS SHALL BE STAINLESS STEEL.
24. 'AUTOMATIC ACCESS CONTROL SYSTEM IS NOT IN THE CONTRACT AND SHALL BE BY OTHERS.
25. CONTRACTOR SHALL FURNISH AND INSTALL CONDUITS FOR ACCESS CONTROL AND ALARM SYSTEMS
UNLESS NOTED OTHERWISE.
E001
TYPE B-3 SUBMISSION
ELECTRICAL NOTES, SYMBOLS,
AND ABBREVIATIONS
EJC
EJC
IB
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G C
O N
D
M S
N
C A
N G
M
S A
B
R
E
D
V
E
D
A T
E
C
O N
O
T
D
A T
E
P
M
ABBREVIATIONS
A, AMP AMPERE
ABBR ABBREVIATIONS
AC ALTERNATING CURRENT
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AIC AVAILABLE INTERRUPTING CAPACITY
AT AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BKR, B BREAKER
C, CDT CONDUIT
CKT BKR CIRCUIT BREAKER
CKT(S) CIRCUIT(S)
C.O CENTRAL OFFICE
CU COPPER
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
ELEC ELECTRIC, ELECTRICAL
EMT ELECTRO-METTALIC TUBING
EM, EMERG EMERGENCY
EQUIP EQUIPMENT
EN EXISTING IN NEW LOCATION
EP EXPLOSION PROOF
EPO EMERGENCY POWER OFF
ER EXISTING TO RELOCATE
E, EXIST EXISTING
FC FAN COIL
FIXT FIXTURE
FL FLOOR
G, GND, GRD GROUND
GFI GROUND FAULT CIRCUIT INTERRUPT
HP HORSEPOWER
IDS INTRUSION DETECTION SYSTEM
J.BOX, J.B. JUNCTION BOX
KVA KILOVOLT AMPERE
KW KILOWATT
KWH KILOWATT HOURS
KWM KILOWATT HOUR METER
LTG LIGHTING
LTS LIGHTS
MCB MAIN CIRCUIT BREAKER
MVOLT MULTI-VOLT
N, NEUT NEUTRAL
NEC NATIONAL ELECTRIC CODE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
No. NUMBER
NL NIGHT LIGHT
P POLE
OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
PNL PANEL
Ø, PH, PHASE
PWR POWER
RECPT RECEPTACLE
REF REFERENCE
RM ROOM
RR EXISTING PANEL TO BE REPLACED WITH NEW
SPD SURGE PROTECTION DEVICE
SPEC SPECIFICATION
SW SWITCH
TBR TO BE RELOCATED
TYP TYPICAL
U.O.N UNLESS NOTED OTHERWISE
V VOLT
VA VOLT-AMPS
W WATT
W WIRE(S)
WP WEATHER PROOF
XFMR TRANSFORMER
RPB/2
EXISTING
NEW INSTALLATION
INDICATES DEMOLITION
CONDUIT TURNED UP
CONDUIT TURNED DOWN
CONDUIT END (CAPPED)
FLEXIBLE CONDUIT OR CABLE
HOMERUN, AS DESIGNATED ON DRAWING
GROUND
PANEL
JUNCTION BOX
DUPLEX RECEPTACLE, 20A, 125V
· 'GFI' INDICATES GROUND FAULT INTERRUPT
RECEPTACLE, GFI TYPE NEMA 5-20R
SINGLE POLE TOGGLE SWITCH, 20A, 120 VAC - 42" AFF, UON
"M" INDICATES MOTOR OPERATED SWITCH
DRAWING KEY PLAN NOTE SYMBOL
PLAN REFERENCE
SYMBOLS
J
LIGHTING FIXTURE, AS INDICATED ON LIGHTING SCHEDULE
A FIXTURE TYPE
a SWITCH/OCCUPANCY SENSOR
1 CIRCUIT NUMBER
EMERGENCY LIGHTING FIXTURE
DRAWING DEMOLITION PLAN NOTE SYMBOL1
FIRE ALARM PULL STATION
OS OCCUPANCY SENSOR WITH MANUAL OVERRIDE
E-XXX
X
WALL MOUNTED FIRE ALARM STROBE
WALL MOUNTED FIRE ALARM HORN/STROBE
M
GROUNDING GRID OR COUNTERPOISE SYSTEM CONDUCTOR
DISCONNECT SWITCH
INDUCTION MOTOR
GROUND ROD
XXAT
XXAF
LOW VOLTAGE CIRCUIT BREAKER
· 'XXAT' INDICATES TRIP RATING
· 'XXAF' INDICATES FRAM RATING
SWITCH
· 'XX' INDICATES AMPERE RATING
· 'Y' INDICATES NUMBER OF POLES
EXOTHERMIC CADWELD CONNECTION
TWO WINDING TRANSFORMER, PHASES AS DETERMINED BY OCPD
· 'Z' INDICATES % IMPEDANCE ANSI STANDARD IF NOT SPECIFIED
· 'WW' INDICATES STRUCTURE DESIGNATION
· 'XX' INDICATES POWER RATING
· 'YY' INDICATES PRIMARY VOLTAGE
· 'QQ' INDICATES SECONDARY VOLTAGE WINDINGS AS
INDICATED
· ' ' INDICATES DELTA CONNECTION
· ' 'INDICATES WYE CONNECTION WITH GROUNDED NEUTRAL
ELECTRICAL SERVICE
EARTH GROUND
AIR TERMINAL
MOTOR STARTER
- 'X' INDICATED NEMA RATINGx
UNDERGROUND ELECTRICAL DUCTBANK
UNDERGROUND DUCTBANK
XX kW
YY V
X:Y
Z
X:Y
(Z)
XFMR
XX kVA
YY-ZZV
R%
'XX'
ONE LINE DIAGRAM
UTILITY METER
GENERATOR
· 'XX' DESIGNATES POWER RATING
· 'YY' DESIGNATES VOLTAGE
CURRENT TRANSFORMER
· 'X:Y' INDICATES RATIO
· 'Z' INDICATES QUANTITY (1 PER PHASE
UNLESS OTHERWISE INDICATED)
POTENTIAL TRANSFORMER (PT).
· 'X:Y' INDICATES RATIO
· 'Z' INDICATES QUANTITY (1 PER PHASE
UNLESS OTHERWISE INDICATED)
SURGE PROTECTION DEVICE
LIGHTNING ARRESTOR
EARTH GROUND
XXA/Y
Y
DISTRIBUTION SWITCH
XXA/Y
Y
N
WTS
XXA
Y
TRANSFER SWITCH
· 'W' INDICATES
A: AUTOMATIC
M: MANUAL
· 'XX' INDICATES RATING IN AMPS
· 'Y' INDICATES NUMBER OF POLES
XXA
Z
FUSE
· 'XX' INDICATES TRIP RATING IN AMPS
· 'Z' INDICATES CLASSIFICATION (IF
SPECIFIED)
XXAT
YYAF
MEDIUM/HIGH VOLTAGE CIRCUIT BREAKER
· 'XXAT' INDICATES TRIP RATING
· 'XXAF' INDICATES FRAM RATING
COMMUNICATIONS AND VOICE OUTLET WITH TWO RJ-45
JACKS AND A FOUR PORT FACEPLATE (TWO BLANK)
FLOOR POWER/COMMUNICATIONS BOX WITH FOUR
(4) RECEPTACLES AND FOUR (4) DATA OUTLETS
FL
S
H
SMOKE DETECTOR
HEAT DETECTOR
F
F
F
MASS NOTIFICATION SPEAKER
WALL MOUNTED GROUND BAR
DIMMER SWITCHD
WALL MOUNTED CARD READERCR
POWER SUPPLY FOR CARD READERPS
WALL MOUNTED TELEPHONE WITH COMMUNICATIONS DROPT
EMERGENCY POWER OFF BUTTON,
PUSH TO CLOSE, PULL TO OPEN
RELAY COIL CONTACT,
VOLTAGE AS INDICATED
C
UNDERGROUND COMMUNICATIONS DUCTBANK
M
SECURITY (NIC) - BY OTHERS
BALANCED MAGNETIC SWITCH
INFRARED SENSOR
DURESS BUTTON KEY RESET
MAGNETIC DOOR LOCK
KEYPAD
BMS
PIR
DB
ML
KP
REQUEST TO EXITREX
MOTORIZED DAMPERM
EU/CU
UNDERGROUND ELECTRICAL AND COMMUNICATIONS DUCTBANK
TS
FS
FIRE ALARM TAMPER SWITCH
FIRE ALARM FLOW SWITCH
ICV
E
E
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
U
T
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
E
E
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
S
S
S
S
S
S
S
S
S
S
S
S
S S
S S
S S
S S
S S
S
S
S
S
S
S
S
S
S
S
S
S
37.5KVA TRANSFORMER
15KV SECTIONALIZER
"SC-D"
MEDIUM VOLTAGE CABLE FROM
15KV SECTIONALIZER TO 37.5KVA
TRANSFORMER
200A DISCONNECT
SWITCH AND
METER ASSEMBLY
FEEDER CABLE FROM 37.5KVA
TRANSFORMER TO 200A
DISCONNECT SWITCH
CONDUIT AND WIRING FOR SITE
LIGHTING TO REMAIN (TYP.)
PANELBOARD "DP" TO REMAIN
BOLLARD (TYP.)
SITE LIGHTING FIXTURE
TO REMAIN
BUILDING 71 AND 73,
MAGAZINEE STORAGE
UNITS TO BE DEMOLISHED
BUILDING 74 M&I UNIT TO
BE DEMOLISHED
FEEDERS FROM
PANELBOARD "DP"
TO BUILDINGS 71
AND 73 MAGAZINE
STORAGE UNITS
TELEPHONE LINE, SECURITY
WIRES, AND FIRE ALARM
WIRES FOR BUILDINGS 71 AND
73 MAGAZINE STORAGE UNITS
SCALE: 1" = 30'
60300
SCALE: 1" = 30'
DEMOLITION SITE PLAN
ED101
TYPE B-3 SUBMISSION
ELECTRICAL DEMOLITION PLAN
EJC
EJC
IB
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G C
O N
D
M S
N
C A
N G
M
S A
B
R
E
D D
V
E
D
A T
E
C
O N
O
T
D
A T
E
P
M
GENERAL NOTES:
1. REFER TO DRAWING E001 FOR NOTES, ABBREVIATIONS, AND LEGEND.
2. DEMOLITION, REMOVALS, AND UNDERGROUND CONDUITS TO REMAIN
SHALL BE CAPPED AND FILLED. SITE RESTORATION REQUIREMENTS
SHALL BE COORDINATED WITH CIVIL DRAWINGS.
DEMOLITION NOTES:
DISCONNECT AND REMOVE MEDIUM VOLTAGE CABLE FROM 15KV
SECTIONALIZER "SC-D" TO 37.5KVA TRANSFORMER. PRESERVE AND
CLEAN CONDUIT MADE AVAILABLE FROM CABLE REMOVAL.
DISCONNECT AND REMOVE 37.5KVA TRANSFORMER INCLUDING ALL
STRUCTURAL SUPPORTS AND PADS SERVING THE STORAGE AREA
ELECTRICAL LOADS.
DISCONNECT AND REMOVE FEEDER CABLE AND CONDUIT FROM
37.5KVA TRANSFORMER TO 200A DISCONNECT SWITCH AND METER
ASSEMBLY.
DISCONNECT AND REMOVE METER ASSEMBLY AFTER FEEDER CABLE
DISCONNECTION.
DISCONNECT AND REMOVE 200A DISCONNECT SWITCH SERVING
PANELBOARD "DP."
DEMOLISH BOLLARDS SURROUNDING PANELBOARD "DP," 200A
DISCONNECT SWITCH, AND METER ASSEMBLY.
DISCONNECT AND REMOVE EXTERIOR LIGHT FIXTURES FOR
BUILDINGS 71 AND 73 MAGAZINE STORAGE UNITS.
DISCONNECT AND REMOVE FEEDER CABLES AND ASSOCIATED
CONDUIT FOR BUILDING 71, 73, AND 74 FROM PANELBOARD "DP."
DISCONNECT AND REMOVE TELEPHONE LINE, SECURITY WIRES, AND
FIRE ALARM WIRES FOR BUILDINGS 71, 73, AND 74. ABANDON
CONDUIT IN PLACER. REFER TO CIVIL DRAWINGS FOR ADDITIONAL
INFORMATION.
CONTRACTOR SHALL MAINTAIN POWER TO BUILDINGS 71, 73, AND 74
UNTIL COMPLETION OF STAGE 2 LISTED ON SHEET CD101, ALL
MUNITIONS ARE REMOVED FROM THE SITE, AND THE MSA IS
DECOMMISSIONED.
D
SHEET NUMBER:
ISSUE DATE:
SHEET TITLE:
PROJECT NUMBER:
PROJECT INFORMATION:
REVISION HISTORY:
April 5, 2021
398570
DATEDESCRIPTION
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT MANAGER:
DMR
P r o j e c t
N o
F
J R
P
C h a r l o t s e
C
D I A
N
C
N o r r o l i n a
A i r
N a t i o n a l
G u a r d
C
B
A
D
C
B
A
54321
1 W oo d A ve S ou th
Ise lin
, N J 0
-4
3.3
.34
| m ott ma c.c om
M
IN
UT
EM
AN
W
AY
CH
AR
LO
TT
E, N
C
C
C o n v e r s i o n
C
M p a n s i o n
SHEET OF 53
T
T
S
D
S
S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S S
S
S
U
T
S S
S S
S S
S S
S S
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W W
W W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
S
S
S
S
SS
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
S
S
S
S
S S
S S
S
S
S
S
S
S
W
W
W W
EU/C
U
E U
C
U
E U
C
U
E
U
C
U
E U
C
U
ADMIN BUILDING
EXISTING 15KV
SECTIONALIZER
REFER TO DRAWING E101 FOR
ADMIN BUILDING ELECTRICAL PLANS
SEE ENLARGED PLAN ON THIS
DRAWING FOR POWER AND
COMMUNICATIONS DISTRIBUTIONS
FOR BUILDINGS
2-4"
UTILIZE EXISTING
2" CONDUIT
EXISTING COMMUNICATIONS
MANHOLE
HHC-4
R-011 R-012
2-4"
R-013 R-014
EXISTING COMMUNICATIONS
DUCTBANK TO BUILDING 72
(APPROX. 1100')
E U
C
U
E U
C
U
HHE-3
HHC-3
ICV
U
T
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S S
S S
S S
S S
S S
S S
S
S
S
S
S
S
S S
S S
W
W
W
WW
W
W
W
R-001
R-002
R-004
R-005
E U
/C U
E U
/C U
E U
/C U
E U
C
U
STORAGE BUILDING
225KVA UTILITY
TRANSFORMER
EXISTING
PANELBOARD "DP"
HHE-2
M&I BUILDING
BOLLARDS
(TYP)
MAIN DISTRIBUTION
PANELBOARD "MDP"
REFER TO SITE PLAN FOR
CONDUIT CONTINUATION
HHC-2
R-016
HHC-1
R-029
R-038
R-039
R-033
HHE-1
R-017
6-4"
R-007
R-008
R-009
R-010 R-034
12-4"
R-041
R-042
R-003 R-006 R-040 R-043
HHC-5
HHE-4
R-044
R-045
R-047
R-048
R-050
R-051
12-4"
R-053
R-054
R-046 R-049 R-052 R-055
REFER TO DRAWING E102
FOR M&I BUILDING
ELECTRICAL PLANS
E U
C
U
E U
C
U
E U
C
U
E U
C
U
E U
C
U E
U C
U E
U C
U E
U C
U E
U C
U
REFER TO DRAWING E102
FOR STORAGE BUILDING
ELECTRICAL PLANS
SCALE: 1" = 30'
60300
SCALE: 1" = 30'
SITE PLAN
ES101
TYPE B-3 SUBMISSION
ELECTRICAL SITE PLAN
EJC
EJC
IB
D W
G
N
A M
E
C
P
W W
O R
K I N
G H
M M
F
E D
F
U E
L I N
G C
O N
D
M S
N
C A
N G
M
S A
B
R
E
S D
V
E
D
A T
E
C
O N
O
T
D
A T
E
P
M
SCALE: 1" = 10'
ENLARGED ELECTRICAL SITE PLAN
SCALE: 1" = 10'
20100
GENERAL NOTES:
1. REFER TO DRAWING E001 FOR NOTES, ABBREVIATIONS, AND LEGEND.
DEMOLITION NOTES:
FURNISH AND INSTALL…