Section E- Issued for Construction Plan Set and Technical Specifications (1).pdf
PDF 2 MB Posted
- Solicitation number
- BPM007689
- Issued by
- Gila County, Arizona
About this file
This is a construction plan set and technical specifications document issued by MRT Design, LLC for the U.S. Army Depot at Camp Navajo in Arizona, specifically for roof removal and installation work on Buildings 239 and 241. The project is identified as IFB NG-25-003 and is being managed by Arizona DEMA (Department of Emergency Management). The specifications document was drawn and certified by registered architect Akram Nasr Rosheidat and dated April 10, 2026. A non-mandatory pre-bid conference and site visit is scheduled for September 2, 2026 at 10:00 AM Arizona Time at Camp Navajo, Building 16, located at 1 Hughes Avenue, Bellemont, AZ 86015. All prospective bidders are required to complete form BPM007689 ATT 1 19B and submit it to Douglas Taylor at douglas.taylor@azdema.gov prior to the site visit to gain facility access. Additionally, bidders must review BPM007689 ATT 2 1141 Camp Navajo-Specific Contract Provisions before the site walk, and DEMA personnel will review these provisions at the start of the meeting. Bidders must sign in electronically before August 27, 2026 at 5:00 PM Arizona Time.
The specifications document provides the architectural and technical framework for the roof project, including details on materials, dimensions, and construction standards. Valid identification must be presented at Camp Navajo's security gate, and visitors should notify security that they are attending the pre-construction meeting and job walk for re-roofing of Buildings 239 and 241. The document includes standardized abbreviations and nomenclature for construction elements such as anchor bolts, aggregate base course, air conditioning systems, and acoustical materials. No specific pricing information, set asides, contract terms, or funding sources are detailed in the technical specifications document itself.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DA
TE
IS
SU
ED
PROJECT NUMBER
US
A
RM
Y
DE
PO
T
- C
AM
P
NA
VA
JO
W
AR
EH
OU
SE
R
OO
F
BU
IL
DI
NG
S
26004
NO
DE
SC
RI
PT
IO
N
DA
TE
340 EAST PALM LANE
SUITE 304
PHOENIX, ARIZONA 85004
P: 602.667.9098
WWW.MRTDESIGNLLC.COM
THIS DRAWING IS AN INSTRUMENT OF SERVICE AND THE
PROPERTY OF MRT DESIGN, LLC AND SHALL REMAIN THEIR
PROPERTY. THE USE OF THIS DRAWING SHALL BE
RESTRICTED TO THE SITE FOR WHICH IT WAS PREPARED,
AND PUBLICATION THEREOF IS EXPRESSLY LIMITED TO
SUCH. REUSE, REPRODUCTION, OR PUBLICATION BY ANY
METHOD, IN WHOLE OR IN PART, IS PROHIBITED WITHOUT
THE WRITTEN PART, IS PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF MRT DESIGN, LLC.
PR
OJ
EC
T
NA
M
E
A
DD
RE
SS
SHEET
DR
AW
N
BY
CH
EC
KE
D
BY
SH
EE
T
NA
M E:
SEAL
RE
VI
SI
ON
S
CA
M
P
NA
VA
JO
BE
LL
EM
ON
T, A
RI
ZO
NA
mrt design llc
PL
OT
TE
D
BY
O N
4/1 4/2
6 1
0:1 6 A
M A
T O:
\26
4 C
NI
O
RO
OF
P
RO
JE
CT
\D
RA
W
IN
GS
\26
4 C
NI
O
RO
OF
P
RO
JE
CT
_G
1-
SP
EC
S.
DW
G
O
N
E
T A
C I
F
I
T
R
E
C d e n g i
S e t a
D
AKRAM NASR
ROSHEIDAT
R E
G
I
S
T
E
R
E
D
A
R
C
H
I
T
E
C
T
04.10.2026
AP
RI
L
, 2
ZC
AN
R vicinity map1 SCALE: NONEbellemont, arizona N
EXTG.
NEW
+4'-6" +5'-10"
EL.= +8'-8"
TOP/WALL
13'-4"
6'-0" 7-4"
+8"
@ AT
AB ANCHOR BOLT
ABC AGGREGATE BASE COURSE
A/C AIR CONDITIONING
AC ACOUSTIC
ACT ACOUSTICAL CEILING TILE
ACP ASPHALTIC CONCRETE PAVING
AD AREA DRAIN
ADJ ADJACENT
AFF ABOVE FINISH FLOOR
AGG AGGREGATE
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
<, L ANGLE
AP ACCESS PANEL
APPROX APPROXIMATE
ASB ASBESTOS
ASPH ASPHALT
ASSY ASSEMBLY
BB BOND BEAM
BD BOARD
BIT BITUMINOUS
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BENCHMARK
B/ BOTTOM OF
BRG BEARING
BUR BUILT UP ROOF
C, [ CHANNEL
CAB CABINET
CB CATCH BASIN
CCTV CLOSED CIRCUIT TELEVISION
C/C CENTER-TO-CENTER
CG CORNER GUARD
CI CAST IRON
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEAR(ANCE)
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
COORD COORDINATE
CONC CONCRETE
CONTR CONTRACTOR
CONST CONSTRUCTION
CONT CONTINUOUS OR CONTINUE
CORR CORRIDOR
CP CONCRETE PIPE
CPT CARPET
CNTR COUNTER
CF CUBIC FOOT
CW COLD WATER
CFM CUBIC FEET PER MINUTE
DBL DOUBLE
DEMO DEMOLISH, DEMOLITION
DF DRINKING FOUNTAIN
DIA, Ø DIAMETER
DIM DIMENSION
DISP DISPENSER
DL DEAD LOAD
DN DOWN
DS DOWN SPOUT
DTL DETAIL
DWG DRAWING
DWR DRAWER
COLUMN LINE MARKER
STRUCTURAL GRID CENTERLINE DESIGNATION
PHOTOGRAPH OR ELEVATION MARKER
DIRECTS VIEW OF INTERIOR AND EXTERIOR
ELEVATIONS OR PHOTOGRAPH LOCATION
DATUM OR LEVEL LINE MARKER
INDICATES ELEVATION LINE ON ELEVATION OR
SECTION DRAWING
POINT ELEVATION
MARKER INDICATES ELEVATION TO PROJECT ZERO ON
FRAMING, DRAINAGE, OR CEILING PLANS
ROOF PITCH MARKER
INDICATES ROOF PITCH PROPORTION ON ELEVATION
SCOPE OF WORK/SEPARATION LINE
OUTLINE OF INCLUSIVE WORK AREA OR CONSTRUCTION
PHASE OR FIRE SEPARATION
CUTLINE/MATCH LINE
CUTAWAY SECTION OF DRAWING & POINT OF
ALIGNMENT FOR DIVIDED DRAWINGS OF SAME SCALE
WALL TYPE MARKER
WALL OR PARTITION TYPE REFERENCE; SEE PARTITION
DETAILS FOR MORE INFORMATION
WINDOW MARKER
WINDOW, OPENING, OR GLAZING TYPE REFERENCE;
SEE WINDOW ELEVATIONS FOR MORE INFORMATION
KEYNOTE MARKERS
DRAWING NOTE REFERENCE;
SEE KEYNOTE LEGEND (THREE-DIGIT SPECIFICATION
DIVISION AND THREE-DIGIT NOTE NUMBER)
ACCESSORY/EQUIPMENT MARKER
TOILET ACCESSORY, FIXTURE, OR SPECIAL EQUIPMENT
REFERENCE; SEE ACCESSORY SCHEDULE FOR MORE
INFORMATION
DRAWING REVISION MARKER
PRECEDES LINE REVISION DATES AND INDICATES
REVISED OR NEW ELEMENTS
EXISTING CONSTRUCTION TO BE DEMOLISHED
ALL DASHED ELEMENTS EXISTING TO BE DEMOLISHED
AND REMOVED
EXISTING CONSTRUCTION TO REMAIN
ALL SHADED ELEMENTS EXISTING AND NOT TO BE
DISTURBED IN THIS SCOPE OF WORK (FOR ADDITIONS
AND TENANT IMPROVEMENTS)
NEW CONSTRUCTION
ALL SOLID-LINED ELEMENTS TO BE INCLUDED IN THIS
SCOPE OF WORK
DIMENSION LINE
ALL DIMENSIONS ALIGNED TO FACE OF GYPSUM BOARD,
MASONRY, OR ROUGH CONSTRUCTION, UNLESS NOTED
OTHERWISE
A
DOOR MARKER
DOOR TYPE DESIGNATION, REFERENCES
ROOM NUMBER THAT DOOR SERVES; SEE
DOOR SCHEDULE FOR MORE INFORMATION
drawing title 1 SCALE: 1/8"=1'-0"plan N
TITLE BAR
INDICATES DRAWING REFERENCE NO., DESCRIPTION,
SCALE, & TRUE NORTH ARROW (WHERE APPLICABLE)
PROJECT NORTH MARKER
INDICATES DEVIATION FROM TRUE
MAGNETIC NORTH ON SITE PLANS WHERE
PROJECT NORTH IS MODIFIED
N
NO WORK THIS AREA
DOT PATTERN IN EXCLUDED WORK AREA
EA EACH
EIFS EXTERIOR INSULATION & FINISH SYSTEM
ELEC ELECTRIC(AL)
EMERG EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER(ING)
EQ EQUAL
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXTG EXISTING
EXTR EXTERIOR
EXP EXPANSION
EJ EXPANSION JOINT
E/ EDGE OF
FRET FIRE RETARDANT (TREATED)
FRAT FIRE RATED
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FD FLOOR DRAIN
FDN FOUNDATION
FF FINISH FLOOR
FHC FIRE HOSE CABINET
FLUOR FLUORESCENT
FO, F/ FACE OF
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FT, ' FOOT
FTG FOOTING
FX FIRE EXTINGUISHER
FXC FIRE EXTINGUISHER CABINET
GA GAGE, GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACT(OR)
GCB GYPSUM CEILING BOARD
GP GYPSUM PLASTER
GWB GYPSUM WALL BOARD
GYP GYPSUM
HI HIGH
HB HOSE BIBB
HC HOLLOW CORE
HD HEAVY DUTY
HDWR HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
HR HOUR
HT HEIGHT
HVAC HEATING, VENTILATION &
AIR CONDITIONING
HW HOT WATER
ICC INTERNATIONAL CODE COUNCIL
ID INSIDE DIAMETER
INV INVERT ELEVATION
IN INCH
INFO INFORMATION
INSUL INSULATION
INTR INTERIOR
INTER INTERMEDIATE
JAN JANITOR (CLOSET)
JST JOIST
JT JOINT
KD KNOCK DOWN
KO KNOCK OUT
KP KICK PLATE
LLV LONG LEG VERTICAL
L LONG
LL LIVE LOAD
LAM LAMINATE
LAV LAVATORY
LF LINEAR FEET
LH LEFT HAND
LP LOW POINT
LVR LOUVER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MECH MECHANICAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODULAR
MR MOISTURE RESISTANT
MTG MOUNTING
MTL METAL
NIC NOT-IN-CONTRACT
NRC NOISE REDUCTION COEFFICIENT
NTS NOT-TO-SCALE
OA OVERALL
OC ON CENTER(S)
OD OUTSIDE DIAMETER
OFCI OWNER-FURNISHED,
CONTRACTOR-INSTALLED
O/S OUTSIDE
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
PAR PARALLEL
PART PARTITION
PBD PARTICLE BOARD
PBX TELEPHONE SWITCHBOARD
PC PRECAST CONCRETE
PCF POUNDS-PER-CUBIC-FOOT
PERF PERFORATE(D)
PERIM PERIMETER
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLF POUNDS PER LINEAR FOOT
PR PAIR
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PTD PAPER TOWEL DISPENSER
PWD PLYWOOD
QT QUARRY TILE
QTY QUANTITY
R RISERS
RAD RADIUS
RA RETURN AIR
RD ROOF DRAIN
REF REFERENCE
REFR REFRIGERATOR
REINF REINFORCING
REQ'D REQUIRED
RES RESILIENT
REV REVISION(S), REVISED
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
SLV SHORT LEG VERTICAL
STN STAIN
SC SOLID CORE
SCH SCHEDULE
SD STORM DRAIN
SEC SECTION, SPECIFICATION
SF SQUARE FEET
SGT STRUCTURAL GLAZED TILE
SHT SHEET
SHR SHOWER
SIM SIMILAR
SMS SHEET METAL SCREW
SND SANITARY NAPKIN DISPOSAL
SPL SPECIAL
SQ SQUARE
SS SERVICE SINK
SST STAINLESS STEEL
ST STEEL
STAG STAGGERED
STC SOUND TRANSMISSION COEFFICIENT
STD STANDARD
STRUC STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
SW SWITCH
SYM SYMMETRY(ICAL)
T TREADS
T&G TONGUE & GROOVE
TB TACKBOARD
TC TOP OF CURB
TEL TELEPHONE
TEMP TEMPORARY
TERR TERRAZZO
THK THICK(NESS)
THRES THRESHOLD
TMP TOP OF MASONRY PARAPET
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOP TOP OF PARAPET
TOS TOP OF STEEL
TOW TOP OF WALL
TPD TOILET PAPER DISPENSER
TYP TYPICAL
UNF UNFINISHED
UNO UNLESS NOTED OTHERWISE
VB VAPOR BARRIER
VCT VINYL COMPOSITION TILE
VENT VENTILATION
VERT VERTICAL
VIF VERIFY IN FIELD
VNR VENEER
VT VINYL TILE
VWC VINYL WALL COVERING
W WIDE
w/ WITH
WC WATER CLOSET
WD WOOD
WDW WINDOW
WG WIRE GLASS
WH WALL HUNG
WM WIRE MESH
w/o WITHOUT
WP WATERPROOFING
WR WATER REPELLENT
WSCT WAINSCOT
WT WEIGHT
W/W WALL-TO-WALL
WWF WELDED WIRE FABRIC
XFMR TRANSFORMER
YD YARD
symbols
PHONE:
EMAIL:
CONTACT:
client representative
STATE OF ARIZONA
DEPT OF EMERGENCY & MILITARY AFFAIRS
CAMP NAVAJO, BELLEMONT, ARIZONA 86015
DOUG TAYLOR, OES MANAGER OOD/FE
928.230.3362
DOUGLAS.TAYLOR@AZDEMA.GOV
010.001
US ARMY DEPOT - CAMP NAVAJO
WAREHOUSE ROOF
BUILDINGS 239 & 241
CAMP NAVAJO, BELLEMONT, ARIZONA 86015
A
A
A
X
AX
INTERIOR ELEVATION MARKER
DIRECTS VIEW OF EACH INTERIOR ELEVATION
DESIGNATION (ELEVATIONS A, B, C, & D)
X
AX
A
B
C
D
X
AX
DETAIL MARKER AND BUBBLE
EXTENT OF, OR CUT LINE THROUGH DETAIL OR
ENLARGED PLAN
X
AX BUILDING SECTION MARKER
CUT LINE THROUGH BUILDING SECTION
X
AX WALL SECTION MARKER
CUT LINE THROUGH SECTION IN DIRECTION OF ARROW
ROOM MARKER
ROOM NAME AND NUMBER REFERENCE; SEE ROOM
FINISH SCHEDULE FOR MORE INFORMATION
OFFICE
CPTEXST
PT1
FINISH MARKER
FINISH NOTE REFERENCE; SEE FINISH LEGEND
FLOOR FINISH MARKER
INDICATES FLOORING TYPE
abbreviations code summary sheet index
SHEET NO. SHEET DESCRIPTION REV
A0.0 COVER SHEET
GENERAL
mrt design llc
340 east palm lane, suite 304 phoenix, arizona 85004 p: 602.667.9098 f: 602.331.3558 www.mrtdesignllc.com mrt project number 26004
SUMMARY: THIS PROJECT WILL REPLACE THE ROOFING AT BUILDINGS 239 & 241. THE EXISTING ROOF IS TO BE REMOVED;
NEW FASCIA AND SOFFITS ARE REQUIRED.
APPLICABLE CODES: 2018 INTERNATIONAL BUILDING CODE
2018 INTERNATIONAL MECHANICAL CODE
2018 INTERNATIONAL PLUMBING CODE
2017 NFPA 70 / NATIONAL ELECTRICAL CODE
2018 INTERNATIONAL FUEL GAS CODE
ICC A117.1-2017 ACCESSIBLE AND USABLE BUILDINGS FACILITIES
BUILDING AREA: 202,538 G.S.F.
OCCUPANCY: S2 (LOW HAZARD STORAGE) - NO CHANGE
CONSTUCTION TYPE: II-B NON-COMBUSTIBLE, MASONRY WALLS, STEEL-FRAMED ROOF
SHEET NO. SHEET DESCRIPTION REV
A1.0 OVERALL FLOOR & ROOF PLAN
A5.0 ROOF DETAILS
A5.1 ROOF DETAILS
A7.0 ARCHITECTURAL SPECIFICATIONS
A7.1 ARCHITECTURAL SPECIFICATIONS
ARCHITECTURAL
E. BELLEMONT RD.
I-40
PROJECT LOCATION
G1
SH
EE
T
IN
DE
X, S
YM
BO
LS
AB
BR
EV
IA
TI
ON
S
C
OD
E
SU
M
M
AR
Y
BUILDING 239
BUILDING 241
O
N
E
T A
C I
F
I
T
R
E
C d e n g i
S e t a
D
AKRAM NASR
ROSHEIDAT
R E
G
I
S
T
E
R
C
H
I
T
E
C
T
O
N
E
T A
C I
F
I
T
R
E
C d e n g i
S e t a
D
AKRAM NASR
ROSHEIDAT
R E
G
I
S
T
E
R
C
H
I
T
E
C
T
04.10.2026
04.10.2026 https://app.procore.com/2960976/project/drawing_areas/2637610/drawing_log/391855043 https://app.procore.com/2960976/project/drawing_areas/2637610/drawing_log/391855041 https://app.procore.com/2960976/project/drawing_areas/2637610/drawing_log/391855040 https://app.procore.com/2960976/project/drawing_areas/2637610/drawing_log/391855038 https://app.procore.com/2960976/project/drawing_areas/2637610/drawing_log/391855039 202012 Approved PCS
119'-3 3/8"
B.O. EXIST ROOF PLANK (RIDGE)
116'-6"
T.O. EXIST WALL (EAVE)
100'-0"
EXIST FIN. FLR.
DA
TE
IS
SU
ED
PROJECT NUMBER
US
A
RM
Y
DE
PO
T
- C
AM
P
NA
VA
JO
W
AR
EH
OU
SE
R
OO
F
BU
IL
DI
NG
S
26004
NO
DE
SC
RI
PT
IO
N
DA
TE
340 EAST PALM LANE
SUITE 304
PHOENIX, ARIZONA 85004
P: 602.667.9098
WWW.MRTDESIGNLLC.COM
THIS DRAWING IS AN INSTRUMENT OF SERVICE AND THE
PROPERTY OF MRT DESIGN, LLC AND SHALL REMAIN THEIR
PROPERTY. THE USE OF THIS DRAWING SHALL BE
RESTRICTED TO THE SITE FOR WHICH IT WAS PREPARED,
AND PUBLICATION THEREOF IS EXPRESSLY LIMITED TO
SUCH. REUSE, REPRODUCTION, OR PUBLICATION BY ANY
METHOD, IN WHOLE OR IN PART, IS PROHIBITED WITHOUT
THE WRITTEN PART, IS PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF MRT DESIGN, LLC.
PR
OJ
EC
T
NA
M
E
A
DD
RE
SS
SHEET
DR
AW
N
BY
CH
EC
KE
D
BY
SH
EE
T
NA
M E:
SEAL
RE
VI
SI
ON
S
CA
M
P
NA
VA
JO
BE
LL
EM
ON
T, A
RI
ZO
NA
mrt design llc
PL
OT
TE
D
BY
O N
4/1 4/2
6 1
0:1 4 A
M A
T O:
\26
4 C
NI
O
RO
OF
P
RO
JE
CT
\D
RA
W
IN
GS
\26
4 C
NI
O
RO
OF
P
RO
JE
CT
_G
SA
1 C -B
AY
R
EN
OV
AT
IO
N_ X-
PL
AN
N
EW
-2
0.D W
G
O
N
E
T A
C I
F
I
T
R
E
C d e n g i
S e t a
D
AKRAM NASR
ROSHEIDAT
R E
G
I
S
T
E
R
C
H
I
T
E
C
T
04.10.2026
AP
RI
L
, 2
ZC
AN
R
KEY NOTES
1. EXISTING STEEL COLUMN
2. EXISTING OVERHEAD ROLL-UP DOOR.
3. EXISTING SPRINKLER ENCLOSURE.
4. EXISTING PILASTER.
5. EXISTING ROOFING TO BE REMOVED AND REPLACED.
6. EXISTING STANDING SEAM METAL ROOF TO REMAIN
7. EXISTING MASONRY WALL/EXPANSION JOINT.
8. EXISTING ROOF OVERHAND (SEE DETAIL 1/A5.1)
9. EXISTING WALL BELOW.
10. NEW SINGLE-PLY ROOFIND MEMBRANE ON COVER BOARD
11. NEW CURB WITH 8" HIGH PREFABRICATED CRICKET AT ROOF VENTILATORS, TYP.
12. ROOF STEP-UP +/-8" @ EXPANSION JOINT
13. REMOVE
14. REMOVE WOOD NAILER AND DRIP EDGE AT
EAVES (SEE DETAIL 1/A5.1)
15. FLEXIBLE WALKWAY
16. UNIT PRICE 1 TO REPLACE ONE 2'-8"x5'0"
SECTION OF GYPSUM PANEL WITH NEW
METAL DECK/INSULATION BOARD SIMILAR
TO DETAIL 2/A5.1
17. UNIT PRICE 2 REMOVE ONE 2'-8"x5'-0"
SECTION OF GYPSUM PANEL AND REPLACE
WITH NEW 1 1/2" METAL DECK/INSULATION
ASSEMBLY AS SHOWN IN DETAIL 2/A5.1.
GUTTER TABLE
BLDG# NUMBER OF GUTTERS WITH DOWNSPOUTS
239 8 (6 FRONT, 2 REAR)
240 5 (5 FRONT)
241 6 (6 FRONT)
EAVE OVERHANG WITH METAL DECKING
BLDG# PERCENTAGE OF EXISTING METAL DECKING
239 49%
240 35%
241 61%
ADDITIVE ALTERNATE 1 ADDITIVE ALTERNATE 2BASE BID
A1.0
OV
ER
AL
L
FL
OO
R
R
OO
F
PL
AN
FLOOR PLAN1 SCALE: 1 / 32 " = 1' - 0"
ROOF PLAN2 SCALE: 1 / 32 " = 1' - 0"
EAST & WEST (SIM. OPP.) ELEVATION3 SCALE: 1 / 32 " = 1' - 0"
NORTH & SOUTH ELEVATION (SIM. OPP.)4 SCALE: 1 / 32 " = 1' - 0"
https://app.procore.com/2960976/project/drawing_areas/2637610/drawing_log/391855040 https://app.procore.com/2960976/project/drawing_areas/2637610/drawing_log/391855040 https://app.procore.com/2960976/project/drawing_areas/2637610/drawing_log/391855040 https://app.procore.com/2960976/project/drawing_areas/2637610/drawing_log/391855040
1 / 2 " EXTERIOR GYPSUM
ROOF SHEATHING COVER
BOARD, SPATTER ADHERED
TO EXPOSED GYPSUM DECK
EXISTING WIRE MESH
REINFORCED GYPSUM
STRUCTURAL DECK
60 MIL THERMOPLASTIC
MEMBRANE WITH FLEECE
BACK, FULLY ADHERED
EXISTING BULB T FRAME AT 32" O.C.
EXISTING 1 / 2 " GYPSUM
BOARD FORM
EXISTING WIRE MESH
REINFORCED GYPSUM
STRUCTURAL DECK
REMOVE 4 PILES BUILT
UP ROOFING AND AGGREGATE
TOPPING
EXISTING BULB T FRAME AT 32" O.C.
EXISTING STEEL BAR JOISTS
@ 5'0" O.C. (BEYOND)
EXISTING 1 / 2 " GYPSUM
FORM BOARD
PROPOSED
DEMOLITION
NEW EXPANSION JOINT ASSEMBLY
(BEYOND) TERMINATE AT FACE
OF EXISTING CMU WALL
PREFINISHED 22 GA FLASHING
CONT. 20 GA. G.I CLEAT
CLOSE END OF EXPANSION JOINT
ASSEMBLY WITH 1 / 2 " SHEATHING
TO EDGE OF EXISTING WALL
EXPANSION JOINT. WRAP SINGLE PLY
FLASHING AROUND CORNER TO EDGE
OF WALL EXP. JOINT
60 MIL FLEECE
BACK SINGLE PLY
ROOF MEMBRANE
EXISTING ROOF INFILL
EXISTING METAL DECK
NEW 1 / 2 " PREFINISHED
SOFFIT PANELS, SCREW
TO EXISTING TRUSS TOP
CHORD FLANGE
TOP CHORD OF EXISTING
ROOF STEEL JOIST
EXISTING CMU WALL
EXISTING BUILDING
EXPANSION JOINTS
CONTINUOUS 20 GA. G.I CLEAT
PREFINISHED 22 GA, FLASHING
EDGE SEALANT
PREFINISHED
SOFFIT TRIM
END SPACER
NEW 1 /2 " PREFINISHED
SOFFT PANELS AND TRIM,
SCREW TO EXISTING TOP
CHORD OF EXISTING TRUSS
EDGE SEALANT
NEW WOOD NAILER
EXISTING EDGE ANGLE
FULLY ADHERED FLEECE BACK
SINGLE PLY ROOF MEMBRANE
(BASE BID)
1 / 2 " COVER BOARD (BASE BID)
SPATTER FOAM ADHESIVE BETWEEN
COVER BOARD AND SURFACE FILL
MATERIAL (BASE BID)
ROOF FILLER ON METAL DECK
NEW 1 - 1 / 2 " METAL
DECK AT EAVE
PREFINISHED 22 GA.
DRIP EDGE
(BASE BID)
CONT. 20 GA. G.I
CLEAT (BASE BID)
CONTINUOUS ROOF
ANGLE (BASE BID)
BOLTS THROUGH WEB SPACE
OF TOP CHORD (BASE BID)
NEW 1 / 2 " PREFINISHED
SOFFIT PANELS AND TRIM,
SCREW TO EXISTING TRUSS
TOP CHORD (BASE BID)
TOP CHORD OF EXISTING
ROOF STEEL JOIST
NEW CONT. 1 / 4 " SPACER,
FIELD VERIFY (BASE BID)
NEW 1 - 1 / 2 " X 2 " HEMMED
PREFINISHED 24 GA. TRIM
(BASE BID)
EXISTING 12 " CMU WALL
1 1 / 2 " METAL 'B' DECK SCREWED
TO TOP CHORD AT JOIST BEYOND
(UNIT PRICE 2)
SEALANT WITH BACKER
ROD (UNIT PRICE 2)
MOLDED FOAM RUBBER
CLOSURE STRIP
(UNIT PRICE 2)
NOTE: TOP OF WALL CONDITION IS UNKNOWN. ADVISE ARCHITECT IF ACTUAL CONDITION VARIES
EXISTING 2 - 1 /2 "
BULB T PANEL
SUPPORT
EXISTING WWF REINFORCED
POURED GYPSUM DECK
ASSEMBLY
1 " POLYISOCYNURATE INSULATION
BOARD ATTACHED PER MANUFACTURER
(UNIT PRICE 2)
SPATTER FOAM ADHESIVE BETWEEN
COVER BOARD AND INSULATION
PANELS (BASE BID)
1 / 2 " COVER BOARD (BASE BID)
SEAM SEALANT
2 - 3 / 4 " X 4 " (FIELD VERIFY)
WOOD NAILER BOLTED TO
TOP CHORD (BASE BID)
EDGE SEALANT
(BASE BID)
FULLY ADHERED FLEECE BACK
SINGLE PLY ROOF MEMBRANE
(BASE BID)
REMOVE ENTIRE EXISTING REINFORCED 32 " x 60 " x 2 "
GYPSUM PANEL ASSEMBLY FROM EAVE WHEN ANY
PORTION HAS LOST ITS STRUCTURAL INTEGRITY
(UNIT PRICE 2)
REMOVE 1 / 2 " FIBER BOARD
SOFFIT (BASE BID)
REMOVE DRIP EDGE
AND CLEATS
(BASE BID)
REMOVE 2 1 / 2x4
WOOD NAILER
(BASE BID)
EXISTING EDGE ANGLE
REMOVE BUR ROOFING SYSTEM
AND GRAVEL BALLAST (BASE BID)
EXISTING BULB T PANEL SUPPORT
EXISTING 2 " WWF REINFORCED
POURED GYPSUM DECK ASSEMBLY
EXISTING GYPSUM
FORM BOARD
EXISTING 16" STEEL JOIST
PROPOSED
2' - 8" (FIELD VERIFY)
NEW 1 - 1 / 2 " x 2 " HEMMED
PREFINISHED 24 GA. TRIM
NEW CONT. 1 / 4 " SPACERS
(FIELD VERIFY)
NEW 1 / 2 " PREFINISHED
SOFFIT PANELS WITH END
TRIM SCREW TO EXISTING
FLANGE OF BULB TEE
PREFINISHED
SOFFIT TRIM
NEW 2 3 / 4 " x 4 "
NAILER (VERIFY)
NEW CONT.
20 GA. G.I.
CLEAT
PREFINISHED 22 GA
FLASHING WITH
GRAVEL STOP
EDGE SEALANT
EXPANSION ANCHOR
OR NAIL AND PLUG
EXISTING EDGE ANGLE
FULLY ADHERED 60 MIL
FLEECE BACK SINGLE PLY
ROOF MEMBRANE
1/ 2 " COVER BOARD
SEAM SEALANT
ADHESIVE BETWEEN
COVER BOARD AND
EXISTING ROOF PANELS
EXISTING 'BULB' T
PANEL SUPPORTS
BEYOND
NOTE: PROVIDE TAPERED
RIGID INSULATION CRICKET AT
HIGH END OF ROOF CURB
(8"H x 12"D x WIDTH OF CURB)
REINSTALL VENTILATOR
ON NEW INSULATED
METAL CURB
FLEXIBLE JOINT
FILLER
FLEXIBLE FLASHING
FULLY ADHERED WITH
BONDING ADHESIVE
( 2 ) NEW 2X (CUT FROM 2X10)
60 MIL FLEECE
BACK MEMBRANE
FULLY ADHERED
ADHERE COVER BOARD
TO GYPSUM PANELS WITH
LOW RISE FOAM ADHESIVE
IN SPATTER PATTERN
SEAM SEALANT
2 1 / 2 " GYPSUM
DECK ASSEMBLY
EXISTING 2x3
CURB BOLTED
THROUGH DECK
TOP CHORD STEEL JOIST
EXISTING L FRAME
NEW L BRACKET
SIMPSON Z MAX
18 GUAGE 2 PER SIDE
FIELD VERIFY
4' - 0" x 4' - 0" +/-
EXISTING STEEL WF
BEAM (BEYOND)
EXISTING BAR JOIST
FULLY ADHERED 60 MIL FLEECE
BACK SINGLE PLY ROOF MEMBRANE
ADHERE COVER BOARD TO GYPSUM
PANELS WITH LOW RISE FOAM
ADHESIVE IN SPATTER PATTERN
1 / 2 " DENS DECK
REMOVE EXISTING DRIP, CLEATS, WOOD,
FILLER AND EXPANSION FLASHING
LOWER FLASHING MEMBRANE ADHERED AND
NAILED TO SUBSTRATE
TOP FLASHING MEMBRANE ADHERED TO
LOWER MEMBRANE AND EXTENDED 4"
OVER FULLY ADHERED ROOF MEMBRANE
2" X 8" NAILED TO 2" X 2"
2" X 2" SET IN ADHESIVE
SEAM SEALANT
SINGLE PLY FLASHING
MEMBRANE
EXISTING 2" GYPSUM
OVER 1 / 2 " GYPSUM
BOARD
EXISTING 12" CMU WALL
EXISTING GYPSUM DECK
EXISTING 2" GYPSUM
OVER 1 / 2 " GYPSUM
BOARD 32" X 60" PANELS
EXISTING EDGE ANGLE
SEAM SEALANT
FULLY ADHERED 60 MIL FLEECE
BACK SINGLE PLY ROOF MEMBRANE
1 / 2 " DENS DECK - PROVIDE
1 / 8 " GAP BETWEEN PANELS
ADHERE COVER BOARD TO GYPSUM PANELS
WITH LOW RISE FOAM ADHESIVE IN SPATTER
PATTERN
1 1 / 2 " EXISTING EXP. JT.
COMPRESSIBLE 1 - 1 / 2 " DIAMETER
CLOSED CELL FOAM RUBBER TUBE
4"4"
6"2 12 "
DA
TE
IS
SU
ED
PROJECT NUMBER
US
A
RM
Y
DE
PO
T
- C
AM
P
NA
VA
JO
W
AR
EH
OU
SE
R
OO
F
BU
IL
DI
NG
S
26004
NO
DE
SC
RI
PT
IO
N
DA
TE
340 EAST PALM LANE
SUITE 304
PHOENIX, ARIZONA 85004
P: 602.667.9098
WWW.MRTDESIGNLLC.COM
THIS DRAWING IS AN INSTRUMENT OF SERVICE AND THE
PROPERTY OF MRT DESIGN, LLC AND SHALL REMAIN THEIR
PROPERTY. THE USE OF THIS DRAWING SHALL BE
RESTRICTED TO THE SITE FOR WHICH IT WAS PREPARED,
AND PUBLICATION THEREOF IS EXPRESSLY LIMITED TO
SUCH. REUSE, REPRODUCTION, OR PUBLICATION BY ANY
METHOD, IN WHOLE OR IN PART, IS PROHIBITED WITHOUT
THE WRITTEN PART, IS PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF MRT DESIGN, LLC.
PR
OJ
EC
T
NA
M
E
A
DD
RE
SS
SHEET
DR
AW
N
BY
CH
EC
KE
D
BY
SH
EE
T
NA
M E:
SEAL
RE
VI
SI
ON
S
CA
M
P
NA
VA
JO
BE
LL
EM
ON
T, A
RI
ZO
NA
mrt design llc
PL
OT
TE
D
BY
O N
4/1 4/2
6 1
1:0 8 A
M A
T O:
\26
4 C
NI
O
RO
OF
P
RO
JE
CT
\D
RA
W
IN
GS
\26
4 C
NI
O
RO
OF
P
RO
JE
CT
_G
SA
1 C -B
AY
R
EN
OV
AT
IO
N_ X-
PL
AN
N
EW
-2
0.D W
G
O
N
E
T A
C I
F
I
T
R
E
C d e n g i
S e t a
D
AKRAM NASR
ROSHEIDAT
R E
G
I
S
T
E
R
C
H
I
T
E
C
T
04.10.2026
AP
RI
L
, 2
ZC
AN
R
A5.0
RO
OF
D
ET
AI
LS
EXPANSION JOINT @ BAYS1 SCALE: 3 " = 1' - 0"
EAVE OVERHANG STRUCTURAL REPAIR (UNIT PRICE 2)4 SCALE: 3 " = 1' - 0"
FASCIA @ LOW ROOF AT EXPANSION JT.5 SCALE: 3 " = 1' - 0"
TYPICAL ROOFING SYSTEM REPLACEMENT6 SCALE: 3 " = 1' - 0"
VENTILATOR CURB EXTENSION2 SCALE: 3 " = 1' - 0"
ROOF EDGE AT RAKE3 SCALE: 3 " = 1' - 0"
EXISTING WWF REINFORCED
POURED GYPSUM DECK
ASSEMBLY
EXISTING BULB TEE GYPSUM
PANEL SUPPORT FRAME
TOP CHORD OF EXISTING
ROOF STEEL JOISTS
@ 5' - 0" O.C.
REMOVE ENTIRE 32" X 60"
GYPSUM PANEL ASSEMBLY
WHEN ANY PORTION HAS LOST
ITS STRUCTURAL INTEGRITY
1 1 / 2 " METAL B DECK
SCREWED TO TOP CHORD
AT JOIST BEYOND
SPATTER FOAM ADHESIVE
BETWEEN COVER BOARD AND
INSULATION PANELS
1 / 2 " EXTERIOR GYPSUM COVER BOARD
FULLY ADHERED FLEECE-BACK SINGLE PLY
ROOF MEMBRANE
1 RIGID POLYISOCYANURATE ROOF INSULATION
ANCHORED TO METAL DECK PER MANUFACTURER
REMOVE EXISTING WOOD NAILER,
INSTALL 2 - 3 / 4 " X 4" (FIELD VERIFY)
WOOD NAILER BOLTED TO TOP CHORD
EDGE SEALANT
REMOVE EXISTING DRIP EDGE AND
CLEATS, PROVIDE NEW PREFINISHED
22 GA, DRIP/FASCIA
CONTINUOUS 20 GA. G.I CLEAT
CONTINUOUS ROOF
ANGLE TO REMAIN
REPLACE BOLTS THROUGH WEB SPACE
OF TOP CHORD
NEW 1 / 2 " PREFINISHED SOFFIT
PANELS, WITH END TRIM ATTACH TO
EXISTING TRUSS TOP CHORD
REMOVE EXISTING FIBER
BOARD SOFFIT PANELS
TOP CHORD OF EXISTING
ROOF STEEL JOISTS
@ 5' - 0" O.C.
NEW CONT. 1 / 4 " SPACER
(FIELD VERIFY)
NEW 1 - 1 / 2 " X 2"
PREFINSIHED TRIM,
ANCHOR TO MASONRY
EXISTING 12" CMU WALL
NOTE: THIS DETAIL IS TYPICAL. SOME SECTIONS MAY HAVE THE
ORIGINAL REINFORCED GYPSUM DECKING INSTEAD OF THE
METAL DECKING ILLUSTRATED
EXISTING WWF REINFORCED
POURED GYPSUM DECK
ASSEMBLY
EXISTING BULB TEE GYPSUM
PANEL SUPPORT FRAME
EXISTING METAL DECK ASSEMBLY, FIELD
VERIFY EXISTING FILLER ABOVE
SPATTER FOAM ADHESIVE BETWEEN COVER
BOARD AND INSULATION PANELS (BASE BID)
1 / 2 " EXTERIOR GYPSUM COVER BOARD
FULLY ADHERED FLEECE BACK SINGLE
PLY ROOF MEMBRANE
SEAM SEALANT
DA
TE
IS
SU
ED
PROJECT NUMBER
US
A
RM
Y
DE
PO
T
- C
AM
P
NA
VA
JO
W
AR
EH
OU
SE
R
OO
F
BU
IL
DI
NG
S
26004
NO
DE
SC
RI
PT
IO
N
DA
TE
340 EAST PALM LANE
SUITE 304
PHOENIX, ARIZONA 85004
P: 602.667.9098
WWW.MRTDESIGNLLC.COM
THIS DRAWING IS AN INSTRUMENT OF SERVICE AND THE
PROPERTY OF MRT DESIGN, LLC AND SHALL REMAIN THEIR
PROPERTY. THE USE OF THIS DRAWING SHALL BE
RESTRICTED TO THE SITE FOR WHICH IT WAS PREPARED,
AND PUBLICATION THEREOF IS EXPRESSLY LIMITED TO
SUCH. REUSE, REPRODUCTION, OR PUBLICATION BY ANY
METHOD, IN WHOLE OR IN PART, IS PROHIBITED WITHOUT
THE WRITTEN PART, IS PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF MRT DESIGN, LLC.
PR
OJ
EC
T
NA
M
E
A
DD
RE
SS
SHEET
DR
AW
N
BY
CH
EC
KE
D
BY
SH
EE
T
NA
M E:
SEAL
RE
VI
SI
ON
S
CA
M
P
NA
VA
JO
BE
LL
EM
ON
T, A
RI
ZO
NA
mrt design llc
PL
OT
TE
D
BY
O N
4/1 4/2
6 1
1:0 8 A
M A
T O:
\26
4 C
NI
O
RO
OF
P
RO
JE
CT
\D
RA
W
IN
GS
\26
4 C
NI
O
RO
OF
P
RO
JE
CT
_G
SA
1 C -B
AY
R
EN
OV
AT
IO
N_ X-
PL
AN
N
EW
-2
0.D W
G
O
N
E
T A
C I
F
I
T
R
E
C d e n g i
S e t a
D
AKRAM NASR
ROSHEIDAT
R E
G
I
S
T
E
R
C
H
I
T
E
C
T
04.10.2026
AP
RI
L
, 2
ZC
AN
R
A5.1
RO
OF
D
ET
AI
LS
INTERIOR ROOF PANEL REPLACEMENT (UNIT PRICE 1)2 SCALE: 3 " = 1' - 0"
TYPICAL BASE BID EDGE @ EAVE1 SCALE: 3 " = 1' - 0"
IS
SU
ED
PROJECT NUMBER
US
A
RM
Y
DE
PO
T
- C
AM
P
NA
VA
JO
W
AR
EH
OU
SE
R
OO
F
BU
IL
DI
NG
S
26004
NO
DE
SC
RI
PT
IO
N
DA
TE
340 EAST PALM LANE
SUITE 304
PHOENIX, ARIZONA 85004
P: 602.667.9098
WWW.MRTDESIGNLLC.COM
THIS DRAWING IS AN INSTRUMENT OF SERVICE AND THE
PROPERTY OF MRT DESIGN, LLC AND SHALL REMAIN THEIR
PROPERTY. THE USE OF THIS DRAWING SHALL BE
RESTRICTED TO THE SITE FOR WHICH IT WAS PREPARED,
AND PUBLICATION THEREOF IS EXPRESSLY LIMITED TO
SUCH. REUSE, REPRODUCTION, OR PUBLICATION BY ANY
METHOD, IN WHOLE OR IN PART, IS PROHIBITED WITHOUT
THE WRITTEN PART, IS PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF MRT DESIGN, LLC.
PR
OJ
EC
T
NA
M
E
A
DD
RE
SS
SHEET
DR
AW
N
BY
CH
EC
KE
D
BY
SH
EE
T
NA
M E:
SEAL
RE
VI
SI
ON
S
CA
M
P
NA
VA
JO
BE
LL
EM
ON
T, A
RI
ZO
NA
mrt design llc
PL
OT
TE
D
BY
O N
4/1 4/2
6 1
0:1 7 A
M A
T O:
\26
4 C
NI
O
RO
OF
P
RO
JE
CT
\D
RA
W
IN
GS
\26
4 C
NI
O
RO
OF
P
RO
JE
CT
_G
1-
SP
EC
S.
DW
G
O
N
E
T A
C I
F
I
T
R
E
C d e n g i
S e t a
D
AKRAM NASR
ROSHEIDAT
R E
G
I
S
T
E
R
C
H
I
T
E
C
T
04.10.2026
AP
RI
L
, 2
ZC
AN
R
SECTION 070150.19 PREPARATION FOR RE-ROOFING
PART 1 GENERAL
1.1 RELATED DOCUMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND
DIVISION 01 SPECIFICATION SECTIONS, APPLY TO THIS SECTION.
1.2 SUMMARY
A. SECTION INCLUDES:
1. ROOF TEAR-OFF.
2. PARTIAL ROOF TEAR-OFF.
3. TEMPORARY ROOFING MEMBRANE.
4. ROOF RE-COVER PREPARATION.
5. REMOVAL OF BASE FLASHINGS
1.3 MATERIALS OWNERSHIP
A. EXCEPT FOR ITEMS OR MATERIALS INDICATED TO BE REUSED, REINSTALLED, OR OTHERWISE INDICATED TO REMAIN
OWNER'S PROPERTY, DEMOLISHED MATERIALS SHALL BECOME CONTRACTOR'S PROPERTY AND SHALL BE REMOVED
FROM PROJECT SITE.
1.4 DEFINITIONS
A. ROOFING TERMINOLOGY: REFER TO ASTM D 1079 AND GLOSSARY IN NRCA'S "THE NRCA ROOFING AND WATERPROOFING
MANUAL" FOR DEFINITION OF TERMS RELATED TO ROOFING WORK IN THIS SECTION.
B. EXISTING MEMBRANE ROOFING SYSTEM: FOUR PLIES OF EXISTING BUILT-UP ASPHALT ROOFING MEMBRANES OVER
REINFORCED 1½'- 2” PLUS/MINUS THICK GYPCRETE ON ½” GYPSUM BOARD.
C. ROOF RE-COVER PREPARATION: EXISTING ROOFING MEMBRANE THAT IS TO REMAIN AND BE PREPARED FOR REUSE.
D. ROOF TEAR-OFF: REMOVAL OF EXISTING MEMBRANE ROOFING SYSTEM FROM DECK.
E. PARTIAL ROOF TEAR-OFF: REMOVAL OF A PORTION OF EXISTING MEMBRANE ROOFING SYSTEM FROM DECK OR REMOVAL
OF SELECTED COMPONENTS AND ACCESSORIES FROM EXISTING MEMBRANE ROOFING SYSTEM.
F. REMOVE: DETACH ITEMS FROM EXISTING CONSTRUCTION AND LEGALLY DISPOSE OF THEM OFF-SITE UNLESS INDICATED
TO BE REMOVED AND REINSTALLED.
G. EXISTING TO REMAIN: EXISTING ITEMS OF CONSTRUCTION THAT ARE NOT INDICATED
1.5 ACTION SUBMITTALS
A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED.
1.6 INFORMATIONAL SUBMITTALS
A. PHOTOGRAPHS OR VIDEOTAPE: SHOW EXISTING CONDITIONS OF ADJOINING CONSTRUCTION AND SITE IMPROVEMENTS, INCLUDING EXTERIOR AND INTERIOR FINISH SURFACES, THAT MIGHT BE MISCONSTRUED AS HAVING BEEN DAMAGED BY
REROOFING OPERATIONS. SUBMIT BEFORE WORK BEGINS.
B. LANDFILL RECORDS: INDICATE RECEIPT AND ACCEPTANCE OF HAZARDOUS WASTES, SUCH AS ASBESTOS-CONTAINING
MATERIAL, BY A LANDFILL FACILITY LICENSED TO ACCEPT HAZARDOUS WASTES.
1.7 QUALITY ASSURANCE
A. REROOFING CONFERENCE: CONDUCT CONFERENCE AT PROJECT SITE.
1. MEET WITH OWNER; ARCHITECT; ROOFING SYSTEM MANUFACTURER'S REPRESENTATIVE; ROOFING INSTALLER
INCLUDING PROJECT MANAGER, SUPERINTENDENT, AND FOREMAN.
2. REVIEW METHODS AND PROCEDURES RELATED TO ROOFING SYSTEM TEAR-OFF AND REPLACEMENT INCLUDING, BUT
NOT LIMITED TO, THE FOLLOWING:
a. REROOFING PREPARATION, INCLUDING MEMBRANE ROOFING SYSTEM MANUFACTURER'S WRITTEN
INSTRUCTIONS.
b. TEMPORARY PROTECTION REQUIREMENTS FOR EXISTING STANDING SEAM ROOFING SYSTEM THAT IS TO
REMAIN DURING AND AFTER INSTALLATION.
c. CONSTRUCTION SCHEDULE AND AVAILABILITY OF MATERIALS, INSTALLER'S PERSONNEL, EQUIPMENT, AND
FACILITIES NEEDED TO MAKE PROGRESS AND AVOID DELAYS.
d. EXISTING DECK REMOVAL PROCEDURES AND OWNER NOTIFICATIONS.
e. CONDITION AND ACCEPTANCE OF EXISTING ROOF DECK AND BASE FLASHING SUBSTRATE FOR REUSE.
f. STRUCTURAL LOADING LIMITATIONS OF DECK DURING REROOFING.
g. BASE FLASHINGS, SPECIAL ROOFING DETAILS, DRAINAGE, PENETRATIONS, EQUIPMENT CURBS, AND
CONDITION OF OTHER CONSTRUCTION THAT WILL AFFECT REROOFING.
h. SHUTDOWN OF FIRE-SUPPRESSION, -PROTECTION, AND -ALARM AND -DETECTION SYSTEMS.
i. ASBESTOS REMOVAL AND DISCOVERY OF ASBESTOS-CONTAINING MATERIALS.
j. GOVERNING REGULATIONS AND REQUIREMENTS FOR INSURANCE AND CERTIFICATES IF APPLICABLE.
k. EXISTING CONDITIONS THAT MAY REQUIRE NOTIFICATION OF ARCHITECT BEFORE PROCEEDING.
1.8 PROJECT CONDITIONS
A. A. OWNER WILL OCCUPY PORTIONS OF BUILDING IMMEDIATELY BELOW REROOFING AREA. CONDUCT REROOFING SO
OWNER'S
OPERATIONS WILL NOT BE DISRUPTED. PROVIDE OWNER WITH NOT LESS THAN 1 WEEK NOTICE OF ACTIVITIES THAT MAY AFFECT
OWNER'S OPERATIONS.
1. COORDINATE WORK ACTIVITIES DAILY WITH OWNER SO OWNER CAN PLACE PROTECTIVE DUST OR WATER LEAKAGE COVERS OVER SENSITIVE EQUIPMENT OR FURNISHINGS, SHUT DOWN HVAC AND FIRE-ALARM OR -DETECTION
EQUIPMENT IF NEEDED, AND EVACUATE OCCUPANTS FROM BELOW THE WORK AREA.
2. BEFORE WORKING OVER STRUCTURALLY IMPAIRED AREAS OF DECK, NOTIFY OWNER TO EVACUATE OCCUPANTS FROM BELOW THE AFFECTED AREA. VERIFY THAT OCCUPANTS BELOW THE WORK AREA HAVE BEEN EVACUATED
BEFORE PROCEEDING WITH WORK OVER THE IMPAIRED DECK AREA.
B. PROTECT BUILDING TO BE REROOFED, ADJACENT BUILDINGS, WALKWAYS, SITE IMPROVEMENTS, EXTERIOR PLANTINGS, AND LANDSCAPING FROM DAMAGE OR SOILING FROM REROOFING OPERATIONS.
C. MAINTAIN ACCESS TO EXISTING WALKWAYS, CORRIDORS, AND OTHER ADJACENT OCCUPIED OR USED FACILITIES.
D. CONDITIONS EXISTING AT TIME OF INSPECTION FOR BIDDING WILL BE MAINTAINED BY OWNER AS FAR AS PRACTICAL.
E. LIMIT CONSTRUCTION LOADS ON ROOF.
F. WEATHER LIMITATIONS: PROCEED WITH REROOFING PREPARATION ONLY WHEN EXISTING AND FORECASTED WEATHER
CONDITIONS PERMIT WORK TO PROCEED WITHOUT WATER ENTERING EXISTING ROOFING SYSTEM OR BUILDING.
G. HAZARDOUS MATERIALS: IT IS NOT EXPECTED THAT HAZARDOUS MATERIALS SUCH AS ASBESTOS-CONTAINING MATERIALS
WILL BE ENCOUNTERED IN THE WORK.
1. IF MATERIALS SUSPECTED OF CONTAINING HAZARDOUS MATERIALS ARE ENCOUNTERED, DO NOT DISTURB;
IMMEDIATELY NOTIFY ARCHITECT AND OWNER. HAZARDOUS MATERIALS WILL BE REMOVED BY OWNER UNDER A
SEPARATE CONTRACT.
H. CONTRACTOR IS TO COORDINATE THIS WORK AROUND OTHERS AT THIS BUILDING. A PAINTING CONTRACTOR WILL BE
PAINTING THE BUILDING AND ROOF VENTILATORS.
PART 2 PRODUCTS
2.1 INFILL MATERIALS
A. USE INFILL MATERIALS MATCHING EXISTING MEMBRANE ROOFING SYSTEM MATERIALS UNLESS OTHERWISE INDICATED.
2.2 RECOVER BOARDS
A. RECOVER BOARD: REFER TO ROOFING SPECIFICATION FOR REQUIREMENTS.
PART 3 EXECUTION
3.1 PREPARATION
A. COVER EXHAUST LOUVERS BEFORE PROCEEDING WITH REROOFING WORK THAT COULD AFFECT INDOOR AIR QUALITY OR
ACTIVATE SMOKE DETECTORS IN THE DUCTWORK.
B. DURING REMOVAL OPERATIONS, HAVE SUFFICIENT AND SUITABLE MATERIALS ON-SITE TO FACILITATE RAPID
INSTALLATION OF TEMPORARY PROTECTION IN THE EVENT OF UNEXPECTED RAIN.
C. VERIFY THAT ROOFTOP UTILITIES AND SERVICE PIPING HAVE BEEN SHUT OFF BEFORE BEGINNING THE WORK.
3.2 ROOF TEAR-OFF
A. GENERAL: NOTIFY OWNER EACH DAY OF EXTENT OF ROOF TEAR-OFF PROPOSED FOR THAT DAY AND OBTAIN
AUTHORIZATION TO PROCEED.
B. REMOVE LOOSE AGGREGATE FROM AGGREGATE-SURFACED BUILT-UP BITUMINOUS ROOFING USING A POWER BROOM.
C. ROOF TEAR-OFF: REMOVE EXISTING FOUR PLY ROOFING MEMBRANES AND OTHER MEMBRANE ROOFING SYSTEM
COMPONENTS DOWN TO THE GYPCRETE DECK.
1. REMOVE EXCESS ASPHALT FROM EXISTING INCIDENTAL STEEL DECKING USED TO REPAIR PREVIOUS PATCHES.
3.3 DECK PREPARATION
A. INSPECT DECK AFTER TEAR-OFF OF MEMBRANE ROOFING SYSTEM.
B. VERIFY THAT GYPCRETE SUBSTRATE IS VISIBLY DRY AND FREE OF MOISTURE. TEST FOR CAPILLARY MOISTURE BY
PLASTIC SHEET METHOD ACCORDING TO ASTM D 4263 OR BY POURING 1 PINT (0.5 L) OF HOT ROOFING ASPHALT ON DECK AT START OF EACH DAY'S WORK AND AT START OF EACH ROOF AREA OR PLANE. DO NOT PROCEED WITH ROOFING WORK IF MOISTURE CONDENSES UNDER THE PLASTIC SHEET OR IF ASPHALT TEST SAMPLE FOAMS OR CAN BE EASILY AND
CLEANLY STRIPPED AFTER COOLING.
C. IF BROKEN OR LOOSE FASTENERS THAT SECURE DECK PANELS TO ONE ANOTHER OR TO STRUCTURE ARE OBSERVED OR IF DECK APPEARS OR FEELS INADEQUATELY ATTACHED, IMMEDIATELY NOTIFY ARCHITECT. DO NOT PROCEED WITH
INSTALLATION UNTIL DIRECTED BY ARCHITECT.
D. IF DECK SURFACE IS NOT SUITABLE FOR RECEIVING NEW ROOFING OR IF STRUCTURAL INTEGRITY OF DECK IS SUSPECT, IMMEDIATELY NOTIFY ARCHITECT. DO NOT PROCEED WITH INSTALLATION UNTIL DIRECTED BY ARCHITECT.
E. PROVIDE ADDITIONAL DECK SECUREMENT AS INDICATED ON DRAWINGS.
F. REPLACE DECK WHERE NEEDED AND AUTHORIZED BY THE ARCHITECT, PER DETAIL AS INDICATED ON DRAWINGS. NOTE
THAT THIS WORK IS PRICED ON A PER UNIT REPLACED BASIS.
3.4 ROOF RE-COVER PREPARATION
A. REMOVE BLISTERS, RIDGES, BUCKLES, AND OTHER SUBSTRATE IRREGULARITIES FROM EXISTING ROOFING MEMBRANE
THAT INHIBIT NEW RECOVER BOARDS FROM CONFORMING TO SUBSTRATE.
1. REMOVE LOOSE AGGREGATE FROM AGGREGATE-SURFACED BUILT-UP BITUMINOUS ROOFING WITH A POWER
BROOM.
2. BROOM CLEAN EXISTING SUBSTRATE.
3. COORDINATE WITH OWNER'S INSPECTOR TO SCHEDULE TIMES FOR INSPECTIONS BEFORE PROCEEDING WITH
INSTALLATION OF RECOVER BOARDS.
4. VERIFY THAT EXISTING SUBSTRATE IS DRY BEFORE PROCEEDING WITH INSTALLATION OF RECOVER BOARDS. SPOT
CHECK SUBSTRATES WITH AN ELECTRICAL CAPACITANCE MOISTURE-DETECTION METER.
3.5 EXISTING BASE FLASHINGS
A. REMOVE EXISTING BASE FLASHINGS AROUND PARAPETS, CURBS, WALLS, AND PENETRATIONS.
1. CLEAN SUBSTRATES OF CONTAMINANTS SUCH AS ASPHALT, SHEET MATERIALS, DIRT, AND DEBRIS.
B. DO NOT DAMAGE METAL COUNTERFLASHINGS THAT ARE TO REMAIN. REPLACE METAL COUNTERFLASHINGS DAMAGED
DURING REMOVAL WITH COUNTERFLASHINGS OF SAME METAL, WEIGHT OR THICKNESS, AND FINISH. RETAIN FIRST
PARAGRAPH BELOW IF REUSING EXISTING PARAPET SHEATHING.
3.6 DISPOSAL
A. COLLECT DEMOLISHED MATERIALS AND PLACE IN CONTAINERS. PROMPTLY DISPOSE OF DEMOLISHED MATERIALS. DO NOT
ALLOW DEMOLISHED MATERIALS TO ACCUMULATE ON-SITE.
B. TRANSPORT AND LEGALLY DISPOSE OF DEMOLISHED MATERIALS OFF OWNER'S PROPERTY.
SECTION 075419 POLY-VINYL CHLORIDE ROOFING
PART 1GENERAL
1.1 RELATED DOCUMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY CONDITIONS AND
DIVISION 01 SPECIFICATION SECTIONS, APPLY TO THIS SECTION.
1.2 SUMMARY
A. SECTION INCLUDES:
1. ADHERED PVC MEMBRANE ROOFING SYSTEM, WITH FLEECE BACK.
B. RELATED SECTIONS:
1. DIVISION 07 SECTION "PREPARATION FOR RE-ROOFING.”
2. DIVISION 07 SECTION "SHEET METAL FLASHING AND TRIM" FOR METAL ROOF PENETRATION FLASHINGS, FLASHINGS, AND COUNTER FLASHINGS.
3. DIVISION 07 SECTION "JOINT SEALANTS" FOR JOINT SEALANTS, JOINT FILLERS, AND JOINT PREPARATION.
1.3 DEFINITIONS
A. ROOFING TERMINOLOGY: SEE ASTM D 1079 AND GLOSSARY IN NRCA'S "THE NRCA ROOFING AND WATERPROOFING
MANUAL" FOR DEFINITION OF TERMS RELATED TO ROOFING WORK IN THIS SECTION.
1.4 PERFORMANCE REQUIREMENTS
WIND UPLIFT RESISTANCE: PERFORMANCE TESTING SHALL BE IN ACCORDANCE WITH ANSI/FM 4474, FM 4450, FM 4470, UL
580 OR UL 1897.
FIRE CLASSIFICATION: PERFORMANCE TESTING SHALL BE IN ACCORDANCE WITH UL 790, ASTM E108, FM 4450 OR FM 4470. MEET REQUIREMENTS OF UL CLASS A OR FM CLASS A. PERFORMANCE TESTING SHALL BE IN ACCORDANCE WITH UL 1256, FM 4450 OR FM 4470 TO MEET THE SPECIFIED REQUIREMENTS FOR INTERIOR FLAME SPREAD AND FUEL
CONTRIBUTION. MEETS REQUIREMENTS OF UL 1256, OR FM CLASS1.
ROOF SLOPE: FINISHED ROOF SLOPE FOR PVC SURFACES SHALL BE ¼ INCH PER FOOT (2 PERCENT) MINIMUM FOR ROOF
DRAINAGE.
IMPACT RESISTANCE: PERFORMANCE TESTING FOR IMPACT RESISTANCE SHALL BE IN ACCORDANCE WITH FM 4450, FM 4470 OR ASTM D4272 TO MEET THE SPECIFIED IMPACT RESISTANCE REQUIREMENTS. MEETS REQUIREMENTS FOR FM-SH
(SEVERE HAIL)
A. GENERAL PERFORMANCE: INSTALLED MEMBRANE ROOFING AND BASE FLASHINGS SHALL WITHSTAND SPECIFIED UPLIFT PRESSURES, THERMALLY INDUCED MOVEMENT, AND EXPOSURE TO WEATHER WITHOUT FAILURE DUE TO DEFECTIVE MANUFACTURE, FABRICATION, INSTALLATION, OR OTHER DEFECTS IN CONSTRUCTION. MEMBRANE ROOFING AND BASE
FLASHINGS SHALL REMAIN WATERTIGHT.
B. MATERIAL COMPATIBILITY: PROVIDE ROOFING MATERIALS THAT ARE COMPATIBLE WITH ONE ANOTHER UNDER CONDITIONS OF SERVICE AND APPLICATION REQUIRED, AS DEMONSTRATED BY MEMBRANE ROOFING MANUFACTURER
BASED ON TESTING AND FIELD EXPERIENCE.
C. ENERGY PERFORMANCE: PROVIDE ROOFING SYSTEM THAT IS LISTED ON THE DOE'S ENERGY STAR "ROOF PRODUCTS
QUALIFIED PRODUCT LIST" FOR LOW-SLOPE ROOF PRODUCTS.
1.5 ACTION SUBMITTALS
A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED.
B. LEED SUBMITTALS:
1. PRODUCT DATA FOR CREDIT SS 7.2: FOR ROOF MATERIALS, INDICATING THAT ROOF MATERIALS COMPLY WITH SOLAR
REFLECTANCE INDEX REQUIREMENT.
2. PRODUCT DATA FOR CREDIT IEQ 4.1: FOR ADHESIVES AND SEALANTS USED INSIDE THE WEATHERPROOFING SYSTEM, DOCUMENTATION INCLUDING PRINTED STATEMENT OF VOC CONTENT.
3. LABORATORY TEST REPORTS FOR CREDIT IEQ 4: FOR ADHESIVES AND SEALANTS USED INSIDE THE WEATHERPROOFING SYSTEM, DOCUMENTATION INDICATING THAT THEY COMPLY WITH THE TESTING AND PRODUCT REQUIREMENTS OF THE CALIFORNIA DEPARTMENT OF HEALTH SERVICES' "STANDARD PRACTICE FOR THE TESTING OF VOLATILE ORGANIC EMISSIONS FROM VARIOUS SOURCES USING SMALL-SCALE ENVIRONMENTAL CHAMBERS."
4.
1.6 INFORMATIONAL SUBMITTALS
A. QUALIFICATION DATA: FOR QUALIFIED INSTALLER AND MANUFACTURER.
B. MANUFACTURER CERTIFICATES: SIGNED BY ROOFING MANUFACTURER CERTIFYING THAT ROOFING SYSTEM COMPLIES
WITH REQUIREMENTS SPECIFIED IN "PERFORMANCE REQUIREMENTS" ARTICLE.
C. PRODUCT TEST REPORTS: BASED ON EVALUATION OF COMPREHENSIVE TESTS PERFORMED BY MANUFACTURER AND
WITNESSED BY A QUALIFIED TESTING AGENCY, FOR COMPONENTS OF MEMBRANE ROOFING SYSTEM.
D. FIELD TEST REPORTS:
1. ADHESIVE PULLOUT TEST RESULTS AND MANUFACTURER'S REVISED REQUIREMENTS FOR RIBBON ADHESIVE
PATTERNS.
E. WARRANTIES: SAMPLE OF SPECIAL WARRANTIES.
1.7 CLOSEOUT SUBMITTALS
A. MAINTENANCE DATA: FOR ROOFING SYSTEM TO INCLUDE IN MAINTENANCE MANUALS.
1.8 QUALITY ASSURANCE
A. MANUFACTURER QUALIFICATIONS: A QUALIFIED MANUFACTURER THAT IS FM APPROVALS APPROVED FOR MEMBRANE
ROOFING SYSTEM IDENTICAL TO THAT USED FOR THIS PROJECT.
B. INSTALLER QUALIFICATIONS: A QUALIFIED FIRM THAT IS APPROVED, AUTHORIZED, OR LICENSED BY MEMBRANE ROOFING
SYSTEM MANUFACTURER TO INSTALL MANUFACTURER'S PRODUCT AND THAT IS ELIGIBLE TO RECEIVE MANUFACTURER'S
SPECIAL WARRANTY.
C. SOURCE LIMITATIONS: OBTAIN COMPONENTS INCLUDING PRODUCTS FOR MEMBRANE ROOFING SYSTEM FROM SAME
MANUFACTURER AS MEMBRANE ROOFING.
D. PREINSTALLATION ROOFING CONFERENCE: CONDUCT CONFERENCE AT PROJECT SITE.
1. MEET WITH OWNER, ARCHITECT, ROOFING INSTALLER, AND ROOFING SYSTEM MANUFACTURER'S REPRESENTATIVE.
2. REVIEW METHODS AND PROCEDURES RELATED TO ROOFING INSTALLATION, INCLUDING MANUFACTURER'S WRITTEN
INSTRUCTIONS.
3. REVIEW AND FINALIZE CONSTRUCTION SCHEDULE AND VERIFY AVAILABILITY OF MATERIALS, INSTALLER'S
PERSONNEL, EQUIPMENT, AND FACILITIES NEEDED TO MAKE PROGRESS AND AVOID DELAYS.
4. EXAMINE DECK SUBSTRATE CONDITIONS AND FINISHES FOR COMPLIANCE WITH REQUIREMENTS, INCLUDING
FLATNESS AND FASTENING.
5. REVIEW STRUCTURAL LOADING LIMITATIONS OF ROOF DECK DURING AND AFTER ROOFING.
6. REVIEW BASE FLASHINGS, SPECIAL ROOFING DETAILS, ROOF DRAINAGE, ROOF PENETRATIONS, EQUIPMENT CURBS, AND CONDITION OF OTHER CONSTRUCTION THAT WILL AFFECT ROOFING SYSTEM.
7. REVIEW GOVERNING REGULATIONS AND REQUIREMENTS FOR INSURANCE AND CERTIFICATES IF APPLICABLE.
8. REVIEW TEMPORARY PROTECTION REQUIREMENTS FOR ROOFING SYSTEM DURING AND AFTER INSTALLATION.
9. REVIEW ROOF OBSERVATION AND REPAIR PROCEDURES AFTER ROOFING INSTALLATION.
1.9 DELIVERY, STORAGE, AND HANDLING
A. DELIVER ROOFING MATERIALS TO PROJECT SITE IN ORIGINAL CONTAINERS WITH SEALS UNBROKEN AND LABELED WITH
MANUFACTURER'S NAME, PRODUCT BRAND NAME AND TYPE, DATE OF MANUFACTURE, APPROVAL OR LISTING AGENCY
MARKINGS, AND DIRECTIONS FOR STORING AND MIXING WITH OTHER COMPONENTS.
B. STORE LIQUID MATERIALS IN THEIR ORIGINAL UNDAMAGED CONTAINERS IN A CLEAN, DRY, PROTECTED LOCATION AND WITHIN THE TEMPERATURE RANGE REQUIRED BY ROOFING SYSTEM MANUFACTURER. PROTECT STORED LIQUID MATERIAL
FROM DIRECT SUNLIGHT.
1. DISCARD AND LEGALLY DISPOSE OF LIQUID MATERIAL THAT CANNOT BE APPLIED WITHIN ITS STATED SHELF LIFE.
C. HANDLE AND STORE ROOFING MATERIALS AND PLACE EQUIPMENT IN A MANNER TO AVOID PERMANENT DEFLECTION OF
DECK.
1.10 PROJECT CONDITIONS
A. WEATHER LIMITATIONS: PROCEED WITH INSTALLATION ONLY WHEN EXISTING AND FORECASTED WEATHER CONDITIONS
PERMIT ROOFING SYSTEM TO BE INSTALLED ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS AND WARRANTY
REQUIREMENTS.
1.11 WARRANTY
A. SPECIAL WARRANTY: MANUFACTURER'S STANDARD OR CUSTOMIZED FORM, WITHOUT MONETARY LIMITATION, IN WHICH
MANUFACTURER AGREES TO REPAIR OR REPLACE COMPONENTS OF MEMBRANE ROOFING SYSTEM THAT FAIL IN
MATERIALS OR WORKMANSHIP WITHIN SPECIFIED WARRANTY PERIOD.
1. SPECIAL WARRANTY INCLUDES MEMBRANE ROOFING, BASE FLASHINGS, COVER BOARDS, ROOFING ACCESSORIES, AND OTHER COMPONENTS OF MEMBRANE ROOFING SYSTEM.
2. WARRANTY PERIOD: 20 YEARS FROM DATE OF SUBSTANTIAL COMPLETION.
3. PROVIDE 1 ½” HAIL RIDER.
B. SPECIAL PROJECT WARRANTY: SUBMIT ROOFING INSTALLER'S WARRANTY, ON WARRANTY FORM AT END OF THIS SECTION, SIGNED BY INSTALLER, COVERING THE WORK OF THIS SECTION, INCLUDING ALL COMPONENTS OF MEMBRANE ROOFING SYSTEM SUCH AS MEMBRANE ROOFING, BASE FLASHING, ROOF INSULATION, FASTENERS, COVER BOARDS, AND
WALKWAY PRODUCTS, FOR THE FOLLOWING WARRANTY PERIOD:
1. WARRANTY PERIOD: FIVE YEARS FROM DATE OF SUBSTANTIAL COMPLETION.
PART 2 PRODUCTS
2.1 THERMOPLASTIC MEMBRANE ROOFING
A. PVC SHEET: ASTM D 4434/D 4434M, TYPE III, GRADE I, NON WICKING POLYESTER SCRIM REINFORCED, FLEECE BACKED.
1. THICKNESS: 60 MILS MINIMUM (30 MILS OVER SCRIM) & 55 MIL FLEECE.
2. EXPOSED FACE COLOR: GRAY.
2.2 AUXILIARY MEMBRANE ROOFING MATERIALS
A. GENERAL: AUXILIARY MATERIALS RECOMMENDED BY ROOFING SYSTEM MANUFACTURER FOR INTENDED USE AND
COMPATIBLE WITH OTHER ROOFING COMPONENTS.
1. ADHESIVES AND SEALANTS: COMPLY WITH VOC LIMITS OF AUTHORITIES HAVING JURISDICTION
B. SHEET/BASE FLASHING: MANUFACTURER PRE-APPROVED NON-FLEECE/FELT BACKED POLYESTER PVC MEMBRANE OF THE
SAME TYPE, THICKNESS, AND COLOR AS THE FIELD MEMBRANE.
C. PREFABRICATED CORNER FLASHING:
1. COLOR: GRAY
D. FLASHING BONDING ADHESIVE: SOLVENT BASED.
E. LOW-RISE, URETHANE, FIELD MEMBRANE ADHESIVE: ROOF SYSTEM MANUFACTURER'S STANDARD SPRAY-APPLIED, LOW-RISE, TWO-COMPONENT URETHANE ADHESIVE FORMULATED FOR COMPATIBILITY AND USE WITH FABRIC-BACKED
MEMBRANE ROOFING.
F. VINYL-COATED METAL: VINYL-COATED METAL WITH A FACTORY-APPLIED PVC MEMBRANE.
1. TO BE USED TO CUSTOM FABRICATE METAL DETAILS SUCH AS:
a. METAL DRIP EDGE FLASHINGS
b. THROUGH WALL SCUPPERS
c. OTHER DETAIL FLASHINGS THAT REQUIRE VINYL-COATED METAL
G. METAL TERMINATION BARS: MANUFACTURER'S STANDARD, PREDRILLED STAINLESS STEEL OR ALUMINUM BARS, APPROXIMATELY 1 BY 1/8 INCH (25 BY 3 MM) THICK; WITH ANCHORS.
H. FASTENERS: FACTORY-COATED STEEL FASTENERS AND METAL OR PLASTIC PLATES COMPLYING WITH CORROSION-RESISTANCE PROVISIONS IN FM APPROVALS 4470, DESIGNED FOR FASTENING ROOFING COMPONENTS TO
SUBSTRATE, AND ACCEPTABLE TO ROOFING SYSTEM MANUFACTURER.
I. MISCELLANEOUS ACCESSORIES: PROVIDE POURABLE SEALERS, PREFORMED CONE AND VENT SHEET FLASHINGS, PREFORMED INSIDE AND OUTSIDE CORNER SHEET FLASHINGS, T-JOINT COVERS, LAP SEALANTS, TERMINATION REGLETS, AND OTHER ACCESSORIES.
2.3 SUBSTRATE BOARDS
A. SUBSTRATE BOARD: ASTM C 1177/C 1177M, GLASS-MAT, WATER-RESISTANT GYPSUM SUBSTRATE OR ASTM C 1278/C 1278M, FIBER-REINFORCED GYPSUM BOARD.
2. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY THE FOLLOWING:
a. AS RECOMMENDED AND PROVIDED ROOF SYSTEM MANUFACTURER
3. THICKNESS: 1/2 INCH (13 MM).
4. SURFACE FINISH: FACTORY PRIMED
B. SUBSTRATE BOARD ADHESIVE: MANUFACTURER'S RECOMMENDED ADHESIVE FORMULATED TO ATTACH ROOF INSULATION, SUBSTRATE BOARD, OR COVERBOARD TO SUBSTRATE OR TO ANOTHER INSULATION LAYER AS FOLLOWS:
1. LOW-RISE, MODIFIED ASPHALTIC, ASBESTOS-FREE, COLD-APPLIED ADHESIVE.
b. BASIS-OF-DESIGN URETHANE ADHESIVE PRODUCT: SOPREMA, INC.; DUOTACK 365.
2.4 WALKWAYS
A. FLEXIBLE WALKWAYS: FACTORY-FORMED, NONPOROUS, HEAVY-DUTY, SLIP-RESISTING, SURFACE-TEXTURED WALKWAY
PADS OR ROLLS, APPROXIMATELY 3/16 INCH (5 MM) THICK AND ACCEPTABLE TO ROOFING SYSTEM MANUFACTURER.
1. PADS SIZE: APPROXIMATELY 36 BY 60 INCHES (914 BY 1524 MM).
2. ROLL SIZE: APPROXIMATELY 36 INCHES BY 50 FEET
3. COLOR: CONTRASTING WITH ROOF MEMBRANE.
PART 3 EXECUTION
3.1 EXAMINATION
A. EXAMINE SUBSTRATES, AREAS, AND CONDITIONS, WITH INSTALLER PRESENT, FOR COMPLIANCE WITH THE FOLLOWING
REQUIREMENTS AND OTHER CONDITIONS AFFECTING PERFORMANCE OF ROOFING SYSTEM:
1. VERIFY THAT ROOF OPENINGS AND PENETRATIONS ARE IN PLACE AND CURBS ARE SET AND BRACED AND THAT
ROOF DRAIN BODIES ARE SECURELY CLAMPED IN PLACE.
2. VERIFY THAT WOOD BLOCKING, CURBS, AND NAILERS ARE SECURELY ANCHORED TO ROOF DECK AT PENETRATIONS
AND TERMINATIONS AND THAT NAILERS MATCH THICKNESSES OF INSULATION.
3. VERIFY THAT SURFACE PLANE FLATNESS AND FASTENING OF STEEL ROOF DECK COMPLIES WITH REQUIREMENTS IN
DIVISION 05 SECTION "STEEL DECKING."
4. VERIFY THAT GYPCRETE SUBSTRATE IS VISIBLY DRY AND FREE OF MOISTURE. TEST FOR CAPILLARY MOISTURE BY
PLASTIC SHEET METHOD ACCORDING TO ASTM D 4263.
5. VERIFY THAT GYPCRETE CURING COMPOUNDS THAT WILL IMPAIR ADHESION OF ROOFING COMPONENTS TO ROOF
DECK HAVE BEEN REMOVED.
B. PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED.
3.2 PREPARATION
A. CLEAN SUBSTRATE OF DUST, DEBRIS, MOISTURE, AND OTHER SUBSTANCES DETRIMENTAL TO ROOFING SYSTEM
INSTALLATION ACCORDING TO ROOFING SYSTEM MANUFACTURER'S WRITTEN INSTRUCTIONS.
1. REMOVE SHARP PROJECTIONS.
B. PREVENT MATERIALS FROM ENTERING AND CLOGGING ROOF DRAINS AND CONDUCTORS AND FROM SPILLING OR MIGRATING ONTO SURFACES OF OTHER CONSTRUCTION. REMOVE ROOF-DRAIN PLUGS WHEN NO WORK IS TAKING PLACE
OR WHEN RAIN IS FORECAST.
C. PERFORM FASTENER OR ADHESIVE PULLOUT TESTS ACCORDING TO ROOF SYSTEM MANUFACTURER'S WRITTEN
INSTRUCTIONS.
1. SUBMIT TEST RESULT WITHIN 24 HOURS OF PERFORMING TESTS.
a. INCLUDE MANUFACTURER'S REQUIREMENTS FOR ANY REVISION TO PREVIOUSLY SUBMITTED FASTENER
PATTERNS REQUIRED TO ACHIEVE SPECIFIED WIND UPLIFT REQUIREMENTS.
3.3 ROOFING INSTALLATION, GENERAL
A. INSTALL ROOFING SYSTEM ACCORDING TO ROOFING SYSTEM MANUFACTURER'S WRITTEN INSTRUCTIONS.
B. COMPLETE TERMINATIONS AND BASE FLASHINGS AND PROVIDE TEMPORARY SEALS TO PREVENT WATER FROM ENTERING
COMPLETED SECTIONS OF ROOFING SYSTEM AT END OF WORKDAY OR WHEN RAIN IS FORECAST. REMOVE AND DISCARD
TEMPORARY SEALS BEFORE BEGINNING WORK ON ADJOINING ROOFING.
C. INSTALL ROOF MEMBRANE AND AUXILIARY MATERIALS TO TIE IN TO EXISTING ROOFING TO MAINTAIN WEATHERTIGHTNESS
OF TRANSITION.
3.4 SUBSTRATE BOARD INSTALLATION
A. INSTALL SUBSTRATE BOARD OVER GYPSUM DECK WITH LONG JOINTS IN CONTINUOUS STRAIGHT LINES, WITH END JOINTS
STAGGERED NOT LESS THAN 24 INCHES (610 MM) IN ADJACENT ROWS.
1. TIGHTLY BUTT SUBSTRATE BOARDS TOGETHER.
2. CUT SUBSTRATE BOARD TO FIT TIGHT AROUND PENETRATIONS AND PROJECTIONS, AND TO FIT TIGHT TO
INTERSECTING SLOPING ROOF DECKS.
3. ADHERE SUBSTRATE BOARDS TO GYPSUM DECK ACCORDING TO ROOF SYSTEMS MANUFACTURERS GUIDELINES.
a. LOW RISE FOAM BEAD PATTERN: ADHESIVE TO BE APPLIED PER MANUFACTURERS BEAD ADHESIVE ATTACHMENT PATTERN AS SUBMITTED AS PART OF THE “ACTION SUBMITTALS” (1.5) AND “INFORMATIONAL
SUBMITALLS”
b. (1.6) AND APPROVED BY ARCHITECT.
3.5 ADHERED ROOFING INSTALLATION
A. ADHERE ROOF MEMBRANE OVER AREA TO RECEIVE ROOFING ACCORDING TO ROOFING SYSTEM MANUFACTURER'S
WRITTEN INSTRUCTIONS.
B. UNROLL ROOF MEMBRANE AND ALLOW TO RELAX BEFORE INSTALLING.
C. START INSTALLATION OF ROOFING IN PRESENCE OF ROOFING SYSTEM MANUFACTURER'S TECHNICAL PERSONNEL.
D. ACCURATELY ALIGN ROOF MEMBRANE, AND MAINTAIN UNIFORM SIDE AND END LAPS OF MINIMUM DIMENSIONS REQUIRED
BY MANUFACTURER. STAGGER END LAPS.
E. FABRIC-BACKED ROOF MEMBRANE ADHESIVE: APPLY LOW-RISE FOAM TO SUBSTRATE AT RATE REQUIRED BY
MANUFACTURER, AND INSTALL FABRIC-BACKED ROOF MEMBRANE.
1. FLEECE-BACKED MEMBRANE IS TO BE APPLIED IN A SPATTER PATTERN.
2. NOTE: RIBBON OR BEAD APPLICATION IS NOT ACCEPTABLE FOR THIS PROJECT.
F. IN ADDITION TO ADHERING, MECHANICALLY FASTEN ROOF MEMBRANE SECURELY AT TERMINATIONS, PENETRATIONS, AND
PERIMETER OF ROOFING.
G. APPLY ROOF MEMBRANE WITH SIDE LAPS SHINGLED WITH SLOPE OF ROOF DECK WHERE POSSIBLE.
H. SEAMS: CLEAN SEAM AREAS, OVERLAP ROOFING, AND HOT-AIR WELD SIDE AND END LAPS OF ROOF MEMBRANE AND
SHEET FLASHINGS TO ENSURE A WATERTIGHT SEAM INSTALLATION.
1. TEST LAP EDGES WITH PROBE TO VERIFY SEAM WELD CONTINUITY. APPLY LAP SEALANT TO SEAL CUT EDGES OF
ROOF MEMBRANE AND SHEET FLASHINGS.
2. VERIFY FIELD STRENGTH OF SEAMS A MINIMUM OF TWICE DAILY, AND REPAIR SEAM SAMPLE AREAS.
3. REPAIR TEARS, VOIDS, AND LAPPED SEAMS IN ROOF MEMBRANE THAT DO NOT COMPLY WITH REQUIREMENTS.
I. SPREAD SEALANT BED OVER DECK-DRAIN FLANGE AT ROOF DRAINS, AND SECURELY SEAL ROOF MEMBRANE IN PLACE
WITH CLAMPING
J. RING.
3.6 BASE FLASHING INSTALLATION
A. INSTALL SHEET FLASHINGS AND PREFORMED FLASHING ACCESSORIES, AND ADHERE TO SUBSTRATES ACCORDING TO
ROOFING SYSTEM MANUFACTURER'S WRITTEN INSTRUCTIONS.
B. APPLY BONDING ADHESIVE AT REQUIRED RATE. DO NOT APPLY TO SEAM AREA OF FLASHING.
C. FLASH PENETRATIONS AND FIELD-FORMED INSIDE AND OUTSIDE CORNERS WITH REINFORCED SHEET FLASHING.
D. CLEAN SEAM AREAS, OVERLAP, AND FIRMLY ROLL SHEET FLASHINGS INTO THE ADHESIVE. HOT-AIR WELD SIDE AND END
LAPS TO ENSURE A WATERTIGHT SEAM INSTALLATION.
E. TERMINATE AND SEAL TOP OF SHEET FLASHINGS AND MECHANICALLY ANCHOR TO SUBSTRATE THROUGH TERMINATION
BARS.
3.7 WALKWAY INSTALLATION
A. FLEXIBLE WALKWAYS: INSTALL WALKWAY PRODUCTS ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS.
1. INSTALL FLEXIBLE WALKWAYS AT THE FOLLOWING LOCATIONS:
a. LOCATIONS INDICATED ON DRAWINGS.
b. AS REQUIRED BY ROOF MEMBRANE MANUFACTURER'S WARRANTY REQUIREMENTS.
2. PROVIDE 6-INCH (76-MM) CLEARANCE BETWEEN ADJOINING PADS.
3. HEAT WELD TO SUBSTRATE OR ADHERE WALKWAY PRODUCTS TO SUBSTRATE WITH COMPATIBLE ADHESIVE
ACCORDING TO ROOFING SYSTEM MANUFACTURER'S WRITTEN INSTRUCTIONS.
3.8 FIELD QUALITY CONTROL
A. OWNER'S REPRESENTATIVE WILL OBSERVE CONSTRUCTION PROGRESS, AT A MINIMUM AFTER ROOF TEAR OFF, AFTER
COVERBOARD INSTALLATION, AND DURING MEMBRANE INSTALLATION
B. FINAL ROOF INSPECTION: ARRANGE FOR ROOFING SYSTEM MANUFACTURER'S TECHNICAL PERSONNEL TO INSPECT
ROOFING INSTALLATION ON COMPLETION.
C. REPAIR OR REMOVE AND REPLACE COMPONENTS OF MEMBRANE ROOFING SYSTEM WHERE INSPECTIONS INDICATE THAT
THEY DO NOT COMPLY WITH SPECIFIED REQUIREMENTS.
D. ADDITIONAL INSPECTIONS, AT CONTRACTOR'S EXPENSE, WILL BE PERFORMED TO DETERMINE COMPLIANCE OF REPLACED
OR ADDITIONAL WORK WITH SPECIFIED REQUIREMENTS.
3.9 PROTECTING AND CLEANING
A. PROTECT MEMBRANE ROOFING SYSTEM FROM DAMAGE AND WEAR DURING REMAINDER OF CONSTRUCTION PERIOD.
WHEN REMAINING CONSTRUCTION WILL NOT AFFECT OR ENDANGER ROOFING, INSPECT ROOFING FOR DETERIORATION AND DAMAGE, DESCRIBING ITS NATURE AND EXTENT IN A WRITTEN REPORT, WITH COPIES TO ARCHITECT AND OWNER.
B. CORRECT DEFICIENCIES IN OR REMOVE MEMBRANE ROOFING SYSTEM THAT DOES NOT COMPLY WITH REQUIREMENTS;
REPAIR SUBSTRATES; AND REPAIR OR REINSTALL MEMBRANE ROOFING SYSTEM TO A CONDITION FREE OF DAMAGE AND DETERIORATION AT TIME OF SUBSTANTIAL COMPLETION AND ACCORDING TO WARRANTY REQUIREMENTS.
C. CLEAN OVERSPRAY AND SPILLAGE FROM ADJACENT CONSTRUCTION USING CLEANING AGENTS AND PROCEDURES
RECOMMENDED BY MANUFACTURER OF AFFECTED CONSTRUCTION.
3.10 ROOFING INSTALLER'S WARRANTY
A. WHEREAS <INSERT NAME> OF <INSERT ADDRESS>, HEREIN CALLED THE "ROOFING INSTALLER," HAS PERFORMED
ROOFING AND ASSOCIATED WORK ("WORK") ON THE FOLLOWING PROJECT:
1. OWNER: <INSERT NAME OF OWNER>.
2. ADDRESS: <INSERT ADDRESS>.
3. BUILDING NAME/TYPE: <INSERT INFORMATION>.
4. ADDRESS: <INSERT ADDRESS>.
5. AREA OF WORK: <INSERT INFORMATION>.
6. ACCEPTANCE DATE: <INSERT DATE>.
7. WARRANTY PERIOD: <INSERT TIME>.
8. EXPIRATION DATE: <INSERT DATE>.
B. AND WHEREAS ROOFING INSTALLER HAS CONTRACTED (EITHER DIRECTLY WITH OWNER OR INDIRECTLY AS A SUBCONTRACTOR) TO WARRANT SAID WORK AGAINST LEAKS AND FAULTY OR DEFECTIVE MATERIALS AND WORKMANSHIP
FOR DESIGNATED WARRANTY PERIOD,
C. NOW THEREFORE ROOFING INSTALLER HEREBY WARRANTS, SUBJECT TO TERMS AND CONDITIONS HEREIN SET FORTH, THAT DURING WARRANTY PERIOD HE WILL, AT HIS OWN COST AND EXPENSE, MAKE OR CAUSE TO BE MADE SUCH REPAIRS TO OR REPLACEMENTS OF SAID WORK AS ARE NECESSARY TO CORRECT FAULTY AND DEFECTIVE WORK AND AS ARE
NECESSARY TO MAINTAIN SAID WORK IN A WATERTIGHT CONDITION.
D. THIS WARRANTY IS MADE SUBJECT TO THE FOLLOWING TERMS AND CONDITIONS:
1. SPECIFICALLY EXCLUDED FROM THIS WARRANTY ARE DAMAGES TO WORK AND OTHER PARTS OF THE BUILDING, AND
TO BUILDING CONTENTS, CAUSED BY:
a. LIGHTNING;
b. PEAK GUST WIND SPEED EXCEEDING 115 MPH;
c. FIRE;
d. FAILURE OF ROOFING SYSTEM SUBSTRATE, INCLUDING CRACKING, SETTLEMENT, EXCESSIVE DEFLECTION, DETERIORATION, AND DECOMPOSITION;
e. FAULTY CONSTRUCTION OF PARAPET WALLS, COPINGS, CHIMNEYS, SKYLIGHTS, VENTS, EQUIPMENT
SUPPORTS, AND OTHER EDGE CONDITIONS AND PENETRATIONS OF THE WORK;
f. VAPOR CONDENSATION ON BOTTOM OF ROOFING; AND
g. ACTIVITY ON ROOFING BY OTHERS, INCLUDING CONSTRUCTION CONTRACTORS, MAINTENANCE PERSONNEL, OTHER…
This is the start of the file's text. The full file is on GovTribe.