Section 23 21 23 - Hydronic Pumps.docx

DOCX document 29 KB Posted

Attached to
Misc. Generator Repairs and Improvements Federal contract opportunity
Solicitation number
36C25621R0179
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This solicitation is for miscellaneous generator repairs and improvements at the Gulf Coast Veterans Health Care System in Pensacola, Florida. The total set-aside contract requires furnishing all labor, tools, materials, equipment, supervision and other requirements to perform work associated with Project 520-22-166. Offerors must be registered and verified as a Service-Disabled Veteran-Owned Small Business. Joint venture agreements must be included with any proposal to be considered. The work includes repairs and improvements to generators at the Gulf Coast Veterans Health Care System located at 790 Veterans Way in Pensacola, Florida. The agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16.

View the file

Other files for this federal contract opportunity

Other files attached to Misc. Generator Repairs and Improvements, newest first.
File Type Posted
S06 36C25621R0179 0001 (JACC650KW).pdf PDF
S06 36C25621R0179 0001 (IMG_1379).jpg JPG image
S06 36C25621R0179 0001 (Site Visit Sign-In Sheet).pdf PDF
S06 36C25621R0179 0001 (IMG_1380).jpg JPG image
S06 36C25621R0179 0001 (230kW 1 of 2).jpg JPG image
S06 36C25621R0179 0001 (JACC350KW).pdf PDF
S06 36C25621R0179 0001 (E-5.01-Layout1).pdf PDF
36C25621R0179.pdf PDF
VAP-MH-205.pdf PDF
Section 28 05 11 - Common Work Results for Electronic Safety-Security.docx DOCX document
Section 22 05 11 - Common Work Results For Plumbing.docx DOCX document
Section 26 24 16 - Panelboards.docx DOCX document
ICRA.pdf PDF
Room Detail Draft VAP-MH-101-2P.pdf PDF
Room 1C151 Draft-MH-101-3.pdf PDF
EXHIBIT D CONTRACTOR EVALUATION FORM CONSTRUCTION SAFETY.docx DOCX document
Room 2A121 Draft VAP-MH-102-1.pdf PDF
EXHIBIT B PAST AND PRESENT PERFORMANCE QUESTIONNAIRE.docx DOCX document
Draft VAP-MH-101-4.pdf PDF
Section 26 05 71 - Electrical System Protective Device Study.DOC DOC document
Section 23 05 93 - Testing Adjusting and Balancing for HVAC.docx DOCX document
VHA Directive 1193 - COVID 2019 Vaccination Program.pdf PDF
VAP-MH-601.pdf PDF
ACC-1 Power Supply Drawing E-6_01.pdf PDF
VAP-MH-401.pdf PDF
Section 26 36 23 - Automatic Transfer Switches.docx DOCX document
Section 23 07 11 - HVAC and Boiler Plant Insulation.docx DOCX document
Section 26 05 13 - Medium Voltage Cables.docx DOCX document
Section 23 05 11 - Common Work Results for HVAC.docx DOCX document
Section 26 05 11 - Requirements for Electrical Installations.docx DOCX document
Section 01 00 00 - General Requirements.docx DOCX document
Section 23 21 13 - Hydronic Piping.docx DOCX document
Room Detail Draft VAP-MH-101-4.pdf PDF
Room 1E113 Draft-MH-101-5.pdf PDF
EXHIBIT F PROPOSAL INQUIRY FORM.docx DOCX document
Draft VAP-MH-401.pdf PDF
ACC-1 Power Panel Location EQDP E-4_01.pdf PDF
36C25621R0179.pdf PDF
VAP-MH-603.pdf PDF
VAP-PL-501.pdf PDF
Section 26 05 26 - Grounding and Bonding for Electrical Systems.docx DOCX document
Section 26 32 13 - Engine Generators.docx DOCX document
Section 23 09 23 - Direct Digital Control System for HVAC.docx DOCX document
Section 22 11 23 - Domestic Water Pumps.docx DOCX document
Section 23 01 00 - General Provisions of HVAC Systems.doc DOC document
Section 22 05 23 - General Duty Valves For Plumbing Piping.docx DOCX document
Draft VAP-GS-121S-6.pdf PDF
Draft VAP-MH-101-2P.pdf PDF
VA CATEX Form- JACC NRM HVAC and Generators.pdf PDF
Section 23 05 41 - Noise and Vibration Control for HVAC Piping-Equipment.docx DOCX document
Show all 50

Misc. Generator Repairs and Improvements has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

02-01-20

SECTION 23 21 23

HYDRONIC PUMPS

SPEC WRITER NOTE:

1. Delete between // // if not applicable to project. Also delete any other item or paragraph not applicable in the Section and renumber the paragraphs.

2. Provide the year of latest edition to each publication listed in Article 1.3 APPLICABLE PUBLICATIONS.

GENERAL

DESCRIPTION

Capacity: Liters per second (L/s) (Gallons per minute (gpm)) of the fluid pumped. Hydronic pumps for Heating, Ventilating and Air Conditioning.

Definitions:

Capacity: Liters per second (L/s) (Gallons per minute (gpm)) of the fluid pumped.

Head: Total dynamic head in kPa (feet) of the fluid pumped.

Flat head-capacity curve: Where the shutoff head is less than 1.16 times the head at the best efficiency point.

A complete listing of common acronyms and abbreviations are included in //Section 23 05 10, COMMON WORK RESULTS FOR BOILER PLANT AND STEAM GENERATION// //Section 23 05 11, COMMON WORK RESULTS FOR HVAC//.

RELATED WORK

Section 01 00 00, GENERAL REQUIREMENTS.

Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Section 01 81 13, SUSTAINABLE CONSTRUCTION REQUIREMENTS.

//Section 01 91 00, GENERAL COMMISSIONING REQUIREMENTS.// //Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS.// //Section 23 05 10, COMMON WORK RESULTS FOR BOILER PLANT AND STEAM GENERATION.// //Section 23 05 11, COMMON WORK RESULTS FOR HVAC.// Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.

Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.

Section 23 05 93, TESTING, ADJUSTING, AND BALANCING FOR HVAC.

//Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.// Section 23 21 13, HYDRONIC PIPING.

Section 26 29 11, MOTOR CONTROLLERS.

SPEC WRITER NOTE:

1. Make material requirements agree with requirements specified in the referenced Applicable Publications. Verify and update the publication list to that which applies to the project, unless the reference applies to all mechanical systems. Publications that apply to all mechanical systems may not be specifically referenced in the body of the specification, but, shall form a part of this specification.

2. Insert the year of approved latest edition of the publications between the brackets and delete the brackets //// if applicable to this project.

APPLICABLE PUBLICATIONS

The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. Where conflicts occur these specifications and the VHA standard will govern.

American Society of Mechanical Engineers (ASME):

B16.1-//2015// Cast Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250 American Society for Testing and Materials (ASTM):

A48/48M-//2003(R2016)//Standard Specification for Gray Iron Castings
B62-//2017//Standard Specification for Composition Bronze or Ounce Metal Castings

SUBMITTALS

Submittals, including number of required copies, shall be submitted in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

Information and material submitted under this section shall be marked “SUBMITTED UNDER SECTION 23 21 23, HYDRONIC PUMPS”, with applicable paragraph identification.

Manufacturer's Literature and Data including: Full item description and optional features and accessories. Include dimensions, weights, materials, applications, standard compliance, model numbers, size, and capacity.

Pumps and accessories.

Motors and drives.

Variable speed motor controllers.

Characteristic Curves: Head-capacity, efficiency-capacity, brake horsepower-capacity, and NPSHR-capacity for each pump and for combined pumps in parallel or series service. Identify pump and show fluid pumped, specific gravity, pump speed and curves plotted from zero flow to maximum for the impeller being furnished and at least the maximum diameter impeller that can be used with the casing.

Complete operating and maintenance manuals including wiring diagrams, technical data sheets, information for ordering replacement parts, and troubleshooting guide:

Include complete list indicating all components of the systems.

Include complete diagrams of the internal wiring for each item of equipment.

Diagrams shall have their terminals identified to facilitate installation, operation and maintenance.

//Completed System Readiness Checklist provided by the Commissioning Agent and completed by the contractor, signed by a qualified technician and dated on the date of completion, in accordance with the requirements of Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.// //Submit training plans and instructor qualifications in accordance with the requirements of Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.//

QUALITY ASSURANCE

Design Criteria:

Pumps design and manufacturer shall conform to Hydraulic Institute Standards.

Pump sizes, capacities, pressures, operating characteristics and efficiency shall be as scheduled.

Head-capacity curves shall slope up to maximum head at shut-off. Curves shall be relatively flat for closed systems. Select pumps near the midrange of the curve, so the design capacity falls to the left of the best efficiency point, to allow a cushion for the usual drift to the right in operation, without approaching the pump curve end point and possible cavitation and unstable operation. Select pumps for open systems so that required net positive suction head (NPSHR) does not exceed the net positive head available (NPSHA).

Pump Driver: Furnish with pump. Size shall be non-overloading at any point on the head-capacity curve, including in a parallel or series pumping installation with one pump in operation.

Provide all pumps with motors, impellers, drive assemblies, bearings, coupling guard and other accessories specified. Statically and dynamically balance all rotating parts.

Furnish each pump and motor with a nameplate giving the manufacturers name, serial number of pump, capacity in gpm and head in feet at design condition, horsepower, voltage, frequency, speed and full load current and motor efficiency.

Test all pumps before shipment. The manufacturer shall certify all pump ratings.

After completion of balancing, provide replacement of impellers or trim impellers to provide specified flow at actual pumping head, as installed.

Allowable Vibration Tolerance for Pump Units: Section 23 05 41, NOISE AND VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT.

AS-BUILT DOCUMENTATION

SPEC WRITER NOTE: Coordinate O&M Manual requirements with Section 01 00 00, GENERAL REQUIREMENTS. O&M manuals shall be submitted for content review as part of the close-out documents.

Submit manufacturer’s literature and data updated to include submittal review comments and any equipment substitutions.

Submit operation and maintenance data updated to include submittal review comments, VA approved substitutions and construction revisions shall be //in electronic version on CD or DVD// inserted into a three ring binder. All aspects of system operation and maintenance procedures, including applicable piping isometrics, wiring diagrams of all circuits, a written description of system design, control logic, and sequence of operation shall be included in the operation and maintenance manual. The operations and maintenance manual shall include troubleshooting techniques and procedures for emergency situations. Notes on all special systems or devices shall be included. A List of recommended spare parts (manufacturer, model number, and quantity) shall be furnished. Information explaining any special knowledge or tools the owner will be required to employ shall be inserted into the As-Built documentation.

SPEC WRITER NOTE: Select and edit one of the bracketed options after the paragraph below to indicate the format in which the contractor must provide record drawing files. Select the hand-marked option only when the designer has been separately contracted to provide the record drawings from the contractor’s mark-ups. Select the BIM option only when a BIM model will be generated, which is typically only performed by the designer on some Design-Bid-Build projects or by the contractor on some Design-Build projects.

The installing contractor shall maintain as-built drawings of each completed phase for verification; and, shall provide the complete set at the time of final systems certification testing. Should the installing contractor engage the testing company to provide as-built or any portion thereof, it shall not be deemed a conflict of interest or breach of the ‘third party testing company’ requirement. Provide record drawings as follows:

//Red-lined, hand-marked drawings are to be provided, with one paper copy and a scanned PDF version of the hand-marked drawings provided on CD or DVD.// //As-built drawings are to be provided, with a copy of them on AutoCAD version // // provided on CD or DVD. The CAD drawings shall use multiple line layers with a separate individual layer for each system.// //As-built drawings are to be provided, with a copy of them in three-dimensional Building Information Modeling (BIM) software version // // provided on CD or DVD.// The as-built drawings shall indicate the location and type of all lockout/tagout points for all energy sources for all equipment and pumps to include breaker location and numbers, valve tag numbers, etc. Coordinate lockout/tagout procedures and practices with local VA requirements.

Certification documentation shall be provided to COR 21 working days prior to submitting the request for final inspection. The documentation shall include all test results, the names of individuals performing work for the testing agency on this project, detailed procedures followed for all tests, and provide documentation/certification that all results of tests were within limits specified. Test results shall contain written sequence of test procedure with written test results annotated at each step along with the expected outcome or setpoint. The results shall include all readings, including but not limited to data on device (make, model and performance characteristics), normal pressures, switch ranges, trip points, amp readings, and calibration data to include equipment serial numbers or individual identifications, etc.

SPARE MATERIALS

Furnish one spare seal and casing gasket for each pump to the //COR// //Project Manager//.

PRODUCTS

CENTRIFUGAL PUMPS, BRONZE FITTED

General:

Provide pumps that will operate continuously without overheating bearings or motors at every condition of operation on the pump curve, or produce noise audible outside the room or space in which installed.

Provide pumps of size, type and capacity as indicated, complete with electric motor and drive assembly, unless otherwise indicated. Design pump casings for the indicated working pressure and factory test at 1-1/2 times the designed pressure.

Provide pumps of the same type, the product of a single manufacturer, with pump parts of the same size and type interchangeable.

General Construction Requirements Balance: Rotating parts, statically and dynamically.

Construction: To permit servicing without breaking piping or motor connections.

Pump Motors: Provide high efficiency motors, inverter duty for variable speed service. Refer to Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT. Motors shall be //open drip proof// //TEFC// and operate at 1750 RPM unless noted otherwise.

Heating pumps shall be suitable for handling water to 107 degrees C (225 degrees F).

Provide coupling guards that meet OSHA requirements.

Pump Connections: Flanged.

Pump shall be factory tested.

Performance: As scheduled on the Contract Drawings.

Variable Speed Pumps:

The pumps shall be the type shown on the drawings and specified herein flex coupled to //an open drip proof// //a TEFC// motor.

Variable Speed Motor Controllers: Refer to Section 26 29 11, MOTOR CONTROLLERS and to //Section 23 05 10, COMMON WORK RESULTS FOR BOILER PLANT AND STEAM GENERATION// //Section 23 05 11, COMMON WORK RESULTS FOR HVAC// Article, VARIABLE SPEED MOTOR CONTROLLERS. Furnish controllers with pumps and motors.

Pump operation and speed control shall be as shown on the drawings.

SPEC WRITER NOTE: For simple systems, integrated VFD pumps may be specified. Coordinate the integrated VFD specifications with electrical Section 26 29 11, MOTOR CONTROLLERS.

//Direct drive pumps with integrated variable frequency drive (VFD) utilizing the design pump curve programmed on board the built-in controller (also known as sensor-less, or self-sensing). Pump to comply with paragraphs in this section. VFD and motor to comply with Section 26 29 11, MOTOR CONTROLLERS and Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.// In-Line Type, Base Mounted End Suction or Double Suction Type:

Casing and Bearing Housing: Close-grained cast iron, ASTM A48/A48M.

Casing Wear Rings: Bronze.

Suction and Discharge: Plain face flange, 861 kPa (125 psig), ASME B16.1.

Casing Vent: Manual brass cock at high point.

Casing Drain and Gauge Taps: 15 mm (1/2 inch) plugged connections minimum size.

Impeller: Bronze, ASTM B62, enclosed type, keyed to shaft.

Shaft: Steel, Type 1045 or stainless steel.

Shaft Seal: Manufacturer's standard mechanical type to suit pressure and temperature and fluid pumped.

Shaft Sleeve: Bronze or stainless steel.

Motor: Furnish with pump. Refer to Section 23 05 12, GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT.

Base Mounted Pumps:

Designed for disassembling for service or repair without disturbing the piping or removing the motor.

Impeller Wear Rings: Bronze.

Shaft Coupling: Non-lubricated steel flexible type or spacer type with coupling guard, bolted to the baseplate.

Bearings (Double-Suction pumps): Regreaseable ball or roller type.

Provide lip seal and slinger outboard of each bearing.

Base: Cast iron or fabricated steel for common mounting to a concrete base.

Provide line sized shut-off valve and suction strainer, maintain manufacturer recommended straight pipe length on pump suction (with blow down valve). Contractor option: Provide suction diffuser as follows:

Body: Cast iron with steel inlet vanes and combination diffuser-strainer-orifice cylinder with 5 mm (3/16 inch) diameter openings for pump protection. Provide taps for strainer blowdown and gauge connections.

Provide adjustable foot support for suction piping.

Strainer free area: Not less than five times the suction piping.

Provide disposable startup strainer.

SPEC WRITER NOTE: Vertical turbine pumps shall be used for condenser water systems where the centrifugal pumps or the piping layouts are such that the required net positive suction head is in excess of what the conventional centrifugal pump can produce. Indicate on pump schedule the number of stages. Provide scaled drawing detail showing the following distances from the sump/basin bottom: to underside of suction strainer, to minimum water surface level, to the underside of baseplate.

VERTICAL TURBINE PUMP

Pump Bowls: Close-grained cast iron, flanged and bolted type, reinforced with four ribs (minimum), which are at least one-half the flange metal thickness. Number of stages as indicated on drawings.

Impellers: Bronze, enclosed type, secured to the shaft with steel tempered keys.

Replaceable Wear Rings: Bronze.

Pump Shaft: Type 416, stainless steel.

Suction Bell: Cast iron, belled to reduce entrance losses.

Suction Strainer: Bronze, basket type, with net open area at least twice the calculated area at the suction bell lip.

Sleeve Bearings: Bronze provided in each bowl and in the suction bell, to be lubricated by the pumped fluid. Suction bell bearing shall be packed permanently with non-soluble grease and fitted with a bronze sand collar.

Discharge Column Pipe: Steel with threaded or flanged connections.

Line-shaft: Type 1045, steel connected through steel threaded couplings. Shaft (and column) sections shall not exceed 3 m (10 feet) in length. Provide the necessary length of column and shaft as required to mount pump with the distances shown.

Replaceable Shaft Sleeves: Stainless steel "shrunkfit" on the line-shaft at each bearing location.

Column Connection Bearings: Fluted rubber supported by non-threaded "spider" type retainers butted between the machined faces of the discharge column. "Spider" shall be made of nickel-iron with a minimum Brinell hardness number of 170.

Surface Discharge Head Assembly: Close-grained cast iron with integral 861 kPa (125 psig) flat face flange, ASME B16.1. Provide two lifting lugs with capacity to support the weight of the entire pump. Provide steel base plate and hardware for securing the discharge head to the base plate.

Stuffing Box: Manufacturer’s standard, two Teflon seal cages, and split type packing gland.

Stuffing Box Bearing Housing: Cast iron, one piece, with bronze sleeve bearings.

Motor: Vertical, hollow shaft type, direct connected. //WPI (Weather Protected Type I)// //WPII (Weather Protected Type II)//.

EXECUTION

INSTALLATION

If an installation is unsatisfactory to the COR, the Contractor shall correct the installation at no additional cost or time to the Government.

Follow manufacturer's written instructions for pump mounting and startup. Access/Service space around pumps shall not be less than minimum space recommended by pumps manufacturer.

Provide drains for bases and seals for base mounted pumps, piped to and discharging into floor drains.

Coordinate location of thermometer and pressure gauges as per Section 23 21 13, HYDRONIC PIPING.

STARTUP AND TESTING

Perform tests as recommended by product manufacturer and listed standards and under actual or simulated operating conditions and prove full compliance with design and specified requirements. Tests of the various items of equipment shall be performed simultaneously with the system of which each item is an integral part.

When any defects are detected, correct defects and repeat test at no additional cost or time to the Government.

//The Commissioning Agent will observe startup and contractor testing of selected equipment. Coordinate the startup and contractor testing schedules with COR and Commissioning Agent. Provide a minimum notice of 10 working days prior to startup and testing.// Verify that the piping system has been flushed, cleaned and filled.

Lubricate pumps before startup.

Prime the pump, vent all air from the casing and verify that the rotation is correct. To avoid damage to mechanical seals, never start or run the pump in dry condition.

Verify that correct size heaters-motor over-load devices are installed for each pump controller unit.

Field modifications to the bearings and or impeller (including trimming) are prohibited. If the pump does not meet the specified vibration tolerance send the pump back to the manufacturer for a replacement pump. All modifications to the pump shall be performed at the factory.

Ensure the disposable strainer is free of debris prior to testing and balancing of the hydronic system.

After several days of operation, replace the disposable startup strainer with a regular strainer in the suction diffuser.

//COMMISSIONING

Provide commissioning documentation in accordance with the requirements of Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.

Components provided under this section of the specification will be tested as part of a larger system.//

DEMONSTRATION AND TRAINING

Provide services of manufacturer’s technical representative for //4// // // hour//s// to instruct each VA personnel responsible in operation and maintenance of the system.

//Submit training plans and instructor qualifications in accordance with the requirements of Section 23 08 00, COMMISSIONING OF HVAC SYSTEMS.// E N D 23 21 23 - 1