This file is an attachment to a solicitation for the EHRM Infrastructure Upgrades Construction project at the Columbia, South Carolina VA Medical Center. The solicitation number is 36C77623R0096 and was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The attachment contains mechanical drawing set number 7 of 9 and is 17MB in size. Offerors would use the drawings to understand the scope of upgrades required for mechanical systems at the medical center campus. The solicitation seeks construction services to modernize existing infrastructure and support future expansion of healthcare services for veterans. Responses are due on an unspecified date.
View the file
Other files for this federal contract opportunity
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONTRACTOR REQUIREMENTS FOR THE
DEMOLITION OF, OR ADDITION TO, ANY PORTION
OF AIR, PLUMBING OR HYDRONIC SYSTEMS.
COVER SHEET NOTES:
THE FOLLOWING SHALL APPLY TO ALL MECHANICAL SYSTEMS AFFECTED BY CONSTRUCTION ACTIVITIES. SYSTEMS INCLUDED BUT ARE NOT LIMITED TO HVAC, EXHAUST, EQUIPMENT, DUCTWORK, DUCTWORK ACCESSORIES, HYDRONICS, COILS, FILTERS, PLUMBING, TEMPERATURE CONTROLS, LIFE
SAFETY CONTROLS AND PRESSURIZATION CONTROLS.
1. AIR QUALITY, QUANTITY AND PRESSURE RELATIONSHIPS SHALL COMPLY WITH THE LATEST, ANSI/ASHRAE/ASHE STANDARD 170
REQUIREMENTS.
2. COMPLY WITH THE FACILITY'S INFECTIOUS CONTROL RISK ASSESSMENT (ICRA) REQUIREMENTS.
3. MAINTAIN EXISTING AIR QUALITY REQUIREMENTS, AIR PRESSURIZATION AND OTHER UTILITY REQUIREMENTS FOR OCCUPIED AREAS
DURING ANY RENOVATION OR CONSTRUCTION.
4. DETERMINE AND VERIFY THE AREAS SERVED BY THE AFFECTED SYSTEMS.
5. TAKE AIR AND OR/ WATER BALANCE READINGS OF THE SYSTEMS BEING AFFECTED.
6. IF THERE ARE SPACES BEING SERVED OUTSIDE OF THE DEMOLITION OR ADDITION AREA, THE FOLLOWING PROCEDURES MUST BE TAKEN:
a. TAKE AIR AND/OR WATER BALANCE READINGS AS NEEDED TO QUANTIFY THE AIR AND/OR WATER FLOWS DELIVERED TO THE
SYSTEMS OUTSIDE THE AFFECTED AREA.
b. DURING DEMOLITION, TAKE ALL NECESSARY MEASURES TO MAINTAIN THE CORRECT AIR AND/OR WATER FLOWS TO THE SYSTEMS
THAT ARE REMAINING.
c. AFTER THE COMPLETION OF DEMOLITION, VERIFY THAT AIR AND/OR WATER FLOWS ARE CORRECT.
d. AFTER COMPLETING ANY ADDITIONS TO THE SYSTEM, VERIFY THAT AIR AND/OR WATER FLOWS ARE CORRECT.
7. THE CONTRACTOR IS TO PROVIDE TEMPORARY AIR/AND OR WATER SYSTEMS AS NEEDED TO MAINTAIN PROPER TEMPERATURE AND
PRESSURE RELATIONSHIPS OF SPACES REQUIRED TO BE OCCUPIED DURING CONSTRUCTION.
8. ALL TEMPORARY AIR SUPPLY SYSTEMS MUST UTILIZE FINAL FILTERS THAT ARE A MINIMUM OF 90% EFFICIENT (MERV 14). FINAL FILTERS
MUST BE DOWNSTREAM OF ALL AIR SUPPLY COMPONENTS.
ABBREVIATION
GENERAL ABBREVIATIONS
DESCRIPTION ABBREVIATION DESCRIPTION
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
AD ACCESS DOOR/PANEL
AFF ABOVE FINISHED FLOOR
AMB AMBIENT
DIA DIAMETER
DN DOWN
E EXISTING
EC ELECTRICAL CONTRACTOR
EFF EFFICIENCY
GC GENERAL CONTRACTOR
FPM FEET PER MINUTE
FPS FEET PER SECOND
L LENGTH
LF LINEAR FEET
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MFR MANUFACTURER
MIN MINIMUM
NIC NOT IN CONTRACT
NTS NOT TO SCALE
PC PLUMBING CONTRACTOR
PSIG POUNDS PER SQUARE INCH GAUGE
RPM REVOLUTIONS PER MINUTE
SHT SHEET
TOB TOP OF BEAM
GPM GALLONS PER MINUTE
TOS TOP OF STEEL
BOB BOTTOM OF BEAM
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
UNION
Y STRAINER WITH BLOWDOWN
ELBOW UP
ELBOW DOWN
TEE UP
PIPING
- SOLID LINE INDICATES SYSTEM SUPPLY
-- DASHED LINE INDICATES SYSTEM RETURN
NUMBER INDICATES NOMINAL DIAMETER IN INCHES,
LETTER(S) INDICATES SYSTEM.
REFER TO ABBREVIATIONS FOR SYSTEM TYPE.
GENERAL MECHANICAL SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
# SHEET NOTE
DENOTES SPECIFIC REQUIREMENT FOR THE SHEET ON WHICH THE NOTE APPEARS
AND IS USED TO DESCRIBE WORK THAT IS TOO LENGTHY TO PLACE ON PLAN.
DIAMETER
DENOTES CONNECTION OF NEW WORK TO
EXISTING SYSTEM
PROTECT EXISTING SYSTEM FROM ENTRANCE OF FOREIGN DEBRIS DURING WORK.
ARROW INDICATES DOWNWARD PIPE SLOPE
#/# INDICATES SLOPE IN INCHES PER FOOT
WHERE PIPING IS NOT MARKED, REFER TO SPECIFICATIONS FOR REQUIREMENTS
ARROW INDICATES DIRECTION OF FLOW IN PIPING
ISOLATION VALVE REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
CHECK VALVE
ARROW INDICATES DIRECTION OF NORMAL FLOW
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
PIPE IN SLEEVE REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
CIRCUIT SETTER, AUTOFLOW, ETC.
REFER TO SPECIFICATIONS FOR TYPE BASED ON SIZE AND SYSTEM
PRESSURE GAUGE
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIESTHERMOMETER - HORIZONTAL PIPE
TEE DOWN
TEE HORIZONTAL
PIPE REDUCER
INDICATES POINT WHERE PIPING CHANGES FROM ONE SIZE TO ANOTHER.
SMALL POINT OF ARROW INDICATES SMALLER SIZE SIDE OF TRANSITION.
REQUIRED SERVICE CLEARANCE FOR EQUIPMENT
CONTINUATION
FIRST SYMBOL APPLIES TO ROUND DUCT AND PIPING.
SECOND SYMBOL APPLIES TO RECTANGULAR AND OVAL DUCT.
PLUMBING SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
AIR VENT
AUTOMATIC FLOW CONTROL VALVE
# INDICATES FLOW TO BE BALANCED IN GPM
BACKFLOW PREVENTER
CALIBRATED BALANCING VALVE
VALVE - THROTTLING SERVICE
VALVE - SHUTOFF SERVICE
P/T PORT
PIPE CAP
PIPE CONTINUATION
PRESSURE GAUGE STEAM REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
PRESSURE REDUCING VALVE
PUMP
RELIEF VALVE
S SENSOR
SUCTION DIFFUSER
THERMOMETER - VERTICAL PIPE REFER TO SPECIFICATIONS FOR TYPE AND ACCESSORIES
VACUUM BREAKER
Y STRAINER
STEAM TRAP
CC CONTROLS CONTRACTOR
PIPING
- SINGLE DASH INDICATES DOMESTIC COLD WATER
- DOUBLE DASH INDICATES DOMESTIC HOT WATER
- TRIPLE DASH INDICATES HOT WATER
CIRCULATING
- SOLID INDICATES SANITARY ABOVE FLOOR
- CONTINUOUS DASHED INDICATES VENT
- LONG DASHED LINES INDICATE SANITARY BELOW
FLOOR
NUMBER INDICATES NOMINAL DIAMETER IN INCHES,
LETTER(S) INDICATES SYSTEM.
REFER TO ABBREVIATIONS FOR SYSTEM TYPE.
C.O.
C.O.
ROOF DRAIN
TAG INDICATES DRAIN SIZE IN INCHES AND AREA
OF ROOF DRAINED IN SQUARE FEET
REFER TO PLUMBING FIXTURE SCHEDULE FOR TYPE.
#"RD
# SF
WALL DISCHARGE (DOWNSPOUT NOZZLE)
TAG INDICATES DRAIN SIZE IN INCHES AND AREA
OF ROOF DRAINED IN SQUARE FEET
REFER TO PLUMBING FIXTURE SCHEDULE FOR TYPE.
#"DSN
# SF
FD-# FLOOR DRAIN REFER TO PLUMBING FIXTURE SCHEDULE FOR TYPE.
CLEANOUT
CIRCLE INDICATES UP TO FLOOR OR WALL CLEANOUT.
LINE INDICATES END OF PIPE CLEANOUT LOCATED ABOVE A CEILING.
DOUBLE GRADE CLEANOUT REFER TO DETAILS FOR ADDITIONAL REQUIREMENTS.
ABBREVIATION
PLUMBING ABBREVIATIONS
DESCRIPTION
CHEMICAL VENTCV
CHEMICAL WASTECW
BOTTLE/GLASS FILLERBF
ABBREVIATION DESCRIPTION
DOMESTIC HOT WATERDHW
DOMESTIC HOT WATER CIRCULATIONDHWC
LAVATORYL
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
BACK FLOW PREVENTERBFP
BATH TUBBT
COMPRESSED AIR (NON-MEDICAL)CA
PROPANELPG
LEAVING WATER TEMPERATURELWT
BTU (1000'S)MBH
CONDENSATE DRAINCD
CLEANOUTCO
CONDENSATE PUMPCP
MOP SINKMS
NORMALLY CLOSEDNC
NORMALLY OPENNO
CLINICAL SINKCS
DOMESTIC COLD WATERDCW
DRINKING FOUNTAINDF
NON-POTABLE WATERNPW
POST INDICATOR VALVEPIV
PRESSURE REDUCING VALVEPRVDOUBLE GRADE CLEANOUTDGCO
DEIONIZED WATERDI
DEIONIZED WATER CIRCULATINGDIC
ROOF DRAINRD
REVERSE OSMOSIS WATERRO
DEIONIZED HOT WATERDIH
RPZ
S
REDUCED PRESSURE ZONE (BACK FLOW PREVENTER)
SINK
DEIONIZED HOT WATER CIRCULATINGDIHC
DISTILLED WATERDIS
DISTILLED WATER CIRCULATINGDISC
SANITARY SEWERSAN
DOMESTIC SOFT COLD WATERSCW
DOMESTIC SOFT HOT WATERSHW
DIALYSIS WATER RETURNDR
DIALYSIS WATER SUPPLYDS
DRAIN TILEDT
DOMESTIC SOFT HOT WATER CIRCULATINGSHWC
SEWAGE EJECTORSE
SHOWERSH
EMERGENCY EYE WASHEEW
EMERGENCY SHOWERES
EMERGENCY SHOWER AND EYE WASH COMBOESEW
STORM OVERFLOWSO
SUMP PUMPSP
SERVICE SINKSS
EXPANSION TANKET
ELECTRIC WATER COOLEREWC
ENTERING WATER TEMPERATUREEWT
STORM SEWERST
TEMPERATURETEMP
URINALUR
FILTERF
FLOOR CLEANOUTFCO
FLOOR DRAINFD
VENTV
VENT THROUGH ROOFVTR
FLOOR SINKFS
WB
WC
WALL BOX
WATER CLOSET
NATURAL GASG
WALL CLEANOUTWCO
GRADE CLEANOUTGCO
HUB DRAINHD
WATER HEATERWH
WATER SOFTENERWS
HORSEPOWERHP
WPD
YCO
WATER PRESSURE DROP
YARD CLEANOUTGREASE VENTGV
HOSE BIBHB
GREASE WASTEGW
DOWN SPOUT NOZZLEDSN
RECTANGULAR DUCTWORK
W = DIMENSION IN VIEW (INCHES)
H = DIMENSION PERPENDICULAR TO VIEW (INCHES)
ROUND DUCTWORK
D = DUCT DIAMETER
TURNING VANES
FLEXIBLE PIPING
WxH
D"Ø
HVAC SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
W/H
FLAT OVAL DUCTWORK
W = DIMENSION IN VIEW (INCHES)
H = DIMENSION PERPENDICULAR TO VIEW (INCHES)
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
REFER TO DUCT CONSTRUCTION SCHEDULE AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
DUCT CROSS SECTION - SUPPLY
DUCT CROSS SECTION - RETURN
DUCT CROSS SECTION - EXHAUST
CROSS SECTION INDICATES DUCT EXTENDING PERPENDICULAR TO THE PAGE. IN
PLAN VIEW THIS INDICATES A DUCT RISE OR DROP TO ANOTHER LEVEL. SOLID
INTERIOR LINE INDICATES EXTENSION UP. DASHED INTERIOR LINE INDICATES
EXTENSION DOWN.
MANUAL BALANCE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE MANUAL BALANCE DAMPERS IN AN
ACCESSIBLE LOCATION AND AS CLOSE TO THE MAIN DUCT AS POSSIBLE.
CONTROL DAMPER
FIRE/SMOKE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
DIFFUSER
REFER TO SPECIFICATIONS FOR TYPE.
FLEXIBLE DUCT
REFER TO SPECIFICATIONS FOR TYPE. REFER TO DETAILS FOR INSTALLATION
REQUIREMENTS. MAXIMUM LENGTH SHALL BE 48 INCHES UNLESS NOTED OTHERWISE
ON THE PLANS OR IN THE SPECIFICATIONS.
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - NO COIL
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - HOT WATER COIL
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - ELECTRIC COIL
VB-#
### CFM
VAV BOX TAG
# = REFERENCE NUMBER IN SCHEDULE
### = AIRFLOW IN CFM
REFER TO VARIABLE VOLUME BOX SCHEDULE FOR TYPES AND SIZING. AIRFLOW
LISTED IS NOMINAL DESIGN CFM AND GPM. FINAL VALUES ARE TO BE DETERMINED BY
TESTING AND BALANCING CONTRACTOR AND PROGRAMMED BY CONTROLS
CONTRACTOR.
VB-#
#.# GPM
VAV BOX TAG
# = REFERENCE NUMBER IN SCHEDULE
#.# = WATER FLOW RATE IN GPM
REFER TO SCHEDULE, DETAILS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION
AND INSTALLATION REQUIREMENTS.
VARIABLE AIR VOLUME BOX - DUAL DUCT
D#
DIFFUSER TAG
D = TYPE # = TYPE NUMBER
### = AIRFLOW IN CFM
REFER TO DIFFUSER SCHEDULE FOR TYPE DESCRIPTIONS AND SIZING. BALANCE TO
AIRFLOW LISTED. WHEN TYPE IS NOT GIVEN AND ONLY CFM IS DESIGNATED, PROVIDE
D1 FOR SUPPLY OR G1 FOR RETURN/EXHAUST.
FLOW ARROW ARROW INDICATES DIRECTION OF AIRFLOW FROM DIFFUSERS WITH ADJUSTABLE
THROWS.
DIFFUSER BLANK OFF SHADED AREA INDICATES QUADRANT OF DIFFUSER TO BE PROVIDED WITH BLANK OFF
PANEL.
RETURN GRILLE
EXHAUST GRILLE
WALL REGISTER / GRILLE
DUCT MOUNTED REGISTER / GRILLE
LINEAR SLOT
REFER TO VARIABLE VOLUME BOX SCHEDULE FOR TYPES AND SIZING. AIRFLOW
LISTED IS NOMINAL DESIGN CFM AND GPM. FINAL VALUES ARE TO BE DETERMINED BY
TESTING AND BALANCING CONTRACTOR AND PROGRAMMED BY CONTROLS
CONTRACTOR.
SMOKE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
ABBREVIATION
HVAC ABBREVIATIONS
DESCRIPTION
AIR BLENDERAB
AIR CONDITIONING UNIT (SPLIT SYSTEM INDOOR UNIT)AC
AIR HANDLING UNITAHU
NOT ALL ABBREVIATIONS APPLY TO THIS SET OF DOCUMENTS
BOILER FEED UNITBFU
BOILERBLR
CONSTANT AIR VOLUME BOXCAV
COOLING COILCC
CONDENSATE DRAINCD
CUBIC FEET PER MINUTECFM
CHILLERCH
CONDENSATE PUMPCP
CONDENSER WATER RETURNCR
CONDENSER WATER SUPPLYCS
COOLING TOWERCT
CONDENSING UNITCU
CABINET UNIT HEATERCUH
CHILLED WATER RETURNCWR
CHILLED WATER SUPPLYCWS
DIFFUSERD
DUAL DUCTDD
DIRECT EXPANSIONDX
EXHAUST AIREA
ENTERING AIR TEMPERATUREEAT
EXHAUST FANEF
EFFICIENCYEFF
ENERGY RECOVERY COILERC
ENERGY RECOVERY WHEELERW
EXPANSION TANKET
ENTERING WATER TEMPERATUREEWT
FILTER BANK (CONSISTING OF ONE OR MORE FILTERS)FB
FAN COIL UNITFCU
FLOW MEASURING STATIONFMS
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
FUEL OIL VENTFOV
FIRE DAMPERFRD
FIRE SMOKE DAMPERFSD
FINNED TUBE RADIATORFTR
GRILLEG
GLYCOL CHILLED WATER RETURNGCWR
GLYCOL CHILLED WATER SUPPLYGCWS
GRAVITY EXHAUSTGE
GLYCOL HEATING HOT WATER RETURNGHWR
GLYCOL HEATING HOT WATER SUPPLYGHWS
GRAVITY INTAKEGI
HEATING COILHC
PRESSURE/TEMPERATURE TEST PORT
TEMPERATURE CONTROL SYMBOLS
SYMBOL DESCRIPTION ADDITIONAL REMARKS
WALL MOUNTED CONTROL DEVICE
# INDICATES TYPE
REFER TO MOUNTING HEIGHTS DETAIL FOR MOUNTING ELEVATION.
T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON MONOXIDE, ETC.)
OCCUPANCY SENSOR
REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION. WHEN SENSOR IS
NOT SHOWN ON ELECTRICAL DRAWINGS IT SHALL BE PROVIDED AND INSTALLED BY
THE TEMPERATURE CONTROLS CONTRACTOR.
DUCT, PIPE, OR CEILING MOUNTED CONTROL
SENSOR
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
T = THERMOSTAT H = HUMIDISTAT S = SENSOR (CARBON DIOXIDE, ETC.)
CONTROL VALVE (3-WAY)
CONTROL VALVE (2-WAY)
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
F/S FLOW MEASURING STATION REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
FIRE DAMPER
REFER TO SPECIFICATIONS FOR TYPE. LOCATE DAMPERS IN AN ACCESSIBLE
LOCATION AND PROVIDE ACCESS DOORS/PANELS IN DUCT AND CEILING/WALL.
CD
FD
SD
FS
DAMPER SHALL BE SAME SIZE AS DUCT UNLESS NOTED OTHERWISE. REFER TO
SEQUENCES, SCHEMATICS AND SPECIFICATIONS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.
REFER TO SPECIFICATIONS FOR TYPE. REFER TO SEQUENCES AND SCHEMATICS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
FLOW SWITCHF
ABBREVIATION DESCRIPTION
HORSEPOWERHP
HIGH PRESSURE STEAM CONDENSATEHPC
HIGH PRESSURE STEAM SUPPLY (86 PSIG AND ABOVE)HPS
HEAT RECOVERY CHILLERHRC
HUMIDIFIERHUM
HEATING HOT WATER RETURNHWR
HEATING HOT WATER SUPPLYHWS
LOW PRESSURE STEAM CONDENSATELPC
LOW PRESSURE STEAM SUPPLY (0-12 PSIG)LPS
LOUVERLV
LEAVING WATER TEMPERATURELWT
BTU (1000'S)MBH
MANUAL DAMPERMD
MOTOR OPERATED DAMPERMOD
MEDIUM PRESSURE STEAM CONDENSATEMPC
MEDIUM PRESSURE STEAM SUPPLY (13-85 PSIG)MPS
NORMALLY CLOSED, NOISE CRITERIANC
NORMALLY OPEN, NUMBERNO
OUTDOOR AIROA
PUMPP
PUMPED CONDENSATEPC
PRESSURE REDUCING VALVEPRV
PUMPED STEAM CONDENSATEPSC
REGISTERR
RETURN AIRRA
RELIEF AIRREA
REFRIGERANT DX LIQUIDREFL
REFRIGERANT DX SUCTION GASREFS
RETURN FANRF
RELATIVE HUMIDITYRH
ROOF TOP UNITRTU
SUPPLY AIRSA
SMOKE DAMPERSD
SUPPLY FANSF
STATIC PRESSURESP
STEAMSTM
TEMPERATURETEMP
TRANSFERTR
UNIT HEATERUH
VARIABLE AIR VOLUME BOXVAV
VENT THROUGH ROOFVTR
WET BULB TEMPERATUREWB
WATER COLUMNWC
WATER PRESSURE DROPWPD
WATER SOURCE HEAT PUMP RETURNWSHPR
WATER SOURCE HEAT PUMP SUPPLYWSHPS
NOT ALL SYMBOLS APPLY TO THIS SET OF DOCUMENTS
NOT ALL SYMBOLS APPLY TO THIS SET OF DOCUMENTS
NOT ALL SYMBOLS APPLY TO THIS SET OF DOCUMENTSNOT ALL SYMBOLS APPLY TO THIS SET OF DOCUMENTS
ALL EQUIPMENT OF THE
SAME TYPE SHALL BE
MANUFACTURED BY THE
SAME MANUFACTURER.
MECHANICAL GENERAL NOTES:
A. THESE NOTES APPLY TO ALL SHEETS CONTAINING HVAC, PIPING, PLUMBING, MEDICAL GAS, AND TEMPERATURE CONTROLS WORK. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. WHERE A DISCREPANCY EXISTS BETWEEN THESE PLANS AND THE PROJECT SPECIFICATIONS, THE SPECIFICATION REQUIREMENTS SHALL TAKE PRECEDENCE OVER THE DRAWINGS.
B. VERIFY THE EXISTING CONDITIONS AT THE PROJECT SITE BEFORE SUBMITTING COST PROPOSAL. BE ADVISED THAT LOCATIONS SHOWN ARE APPROXIMATE. AN ATTEMPT HAS BEEN MADE TO SHOW ALL PIPING, FIXTURES, DUCTWORK, AND OUTLETS. CONTRACTOR SHALL VISIT THE SITE TO VERIFY COMPONENTS, LOCATIONS AND SIZES SHOWN OR NOT SHOWN. ALL COMPONENTS NEED TO BE REMOVED IN THE DEMOLITION AREA UNLESS NOTED ON THE DRAWINGS. IF DEVIATION BETWEEN EXISTING CONDITIONS AND NEW WORK IS FOUND, CONTRACTOR SHALL NOTIFY
ENGINEER.
C. IT IS MANDATORY THAT THE EXISTING BUILDING REMAIN IN CONTINUOUS AND NON-INTERRUPTED OPERATION DURING THE CONSTRUCTION OF THE ADDITIONS AND REMODELING/ALTERATION OF THE EXISTING BUILDING. SERVICES TO THE EXISTING BUILDING SHALL BE KEPT ON CONTINUOUS OPERATION EXCEPT DURING SCHEDULED SHUTDOWNS FOR EXTENSION OR MODIFICATION. PLAN TO COMPLETE SHUTDOWNS DURING OFF HOURS TO MINIMIZE IMPACT TO THE OWNER. COORDINATE SHUTDOWNS WITH THE OWNER A MINIMUM OF 14 DAYS PRIOR TO WORK. PROVIDE TEMPORARY SERVICES WHERE NECESSARY TO ACCOMPLISH ANY SHUTDOWN. THIS INCLUDES BUT IS NOT LIMITED TO STAFFING AND EQUIPMENT FOR FIRE WATCHES, PROVISIONS FOR BOTTLED WATER, AND TEMPORARY HEATING OR COOLING EQUIPMENT.
TEMPORARY MEASURES SHALL NOT BE REMOVED UNTIL THE PERMANENT SYSTEMS ARE OPERATIONAL AND HAVE PASSED ALL REQUIRED
TESTING.
D. REFER TO THE SPECIFICATIONS AND ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. DURING EACH PHASE THE CONTRACTOR SHALL COMPLETE ALL WORK LOCATED WITHIN THE BOUNDARY OF THAT PHASE. ANY WORK AND THAT MUST BE COMPLETED IN THE AREA AFTER THAT AREA HAS BEEN TURNED OVER TO THE OWNER SHALL BE IDENTIFIED AT THE BEGINNING OF THE PHASE FOR EVALUATION AND ACCEPTANCE OF
THE OWNER.
E. CONTRACTOR SHALL BE RESPONSIBLE FOR THEIR OWN DEMOLITION, REMOVAL, CAPPING, STORING, ABANDONING, DISCONNECTING, RELOCATING AND RECONNECTION OF EXISTING EQUIPMENT AND MATERIAL. ALL CUTTING, PATCHING, REPAIRING, REPLACEMENT AND
REFINISHING SHALL MATCH THE EXISTING CONSTRUCTION AS NEARLY AS POSSIBLE.
F. EXCEPT WHERE OTHERWISE SHOWN OR NOTED ON THE DRAWINGS AS "TO BE RETAINED, RELOCATED", ALL EXISTING EQUIPMENT AND MATERIAL IN AREAS TO BE REMODELED/ALTERED SHALL BE REMOVED WHERE THEY INTERFERE WITH PROPOSED NEW CONSTRUCTION AND/OR
WITH PROPOSED USAGE OF SPACE BY OWNER AS FOLLOWS:
a. REMOVE ANY PIPING PROTRUDING ABOVE FINISHED FLOOR OR THROUGH WALL AND CAP WITHIN 3 PIPE DIAMETERS OF NEAREST ACTIVE
MAIN WITH MATERIAL TO MATCH EXISTING.
b. REMOVE ALL FIXTURES, CARRIERS, SUPPLY AND WASTE AND VENT PIPING, STEAM, HEATING HOT WATER, HVAC SUPPLY, RETURN AND EXHAUST AS NOTED. CAP WITHIN 3 PIPE DIAMETERS OF NEAREST ACTIVE MAIN. SUPPLY AND RETURN MAINS ON PIPING SYSTEMS
CONVEYING WATER OR GASES SHALL BE VALVED AND CAPPED
c. IN REMODELED/ALTERED AREAS, ANY PIPING OR DUCTWORK PASSING THROUGH THE REMODELED AREAS TO SERVE (OR BEING SERVED FROM EXISTING ADJACENT, REMOTE, OR SURROUNDING AREAS THAT ARE TO REMAIN) SHALL BE RETAINED AND KEPT OPERATIONAL AND SHALL BE REROUTED IN ALL CASES WHERE THEY INTERFERE WITH ANY NEW WORK OR USAGE TO BE ACCOMPLISHED IN THE
REMODELED AREA.
d. REMOVE UNUSED OR ABANDONED HANGERS AND PATCH ABANDONED PENETRATIONS TO MATCH EXISTING.
e. PENETRATIONS THROUGH EXISTING WALLS AND FLOORS FORMERLY OCCUPIED BY REMOVED PIPING OR DUCTWORK SHALL BE PATCHED
TO MATCH EXISTING CONSTRUCTION.
f. RE-SUPPORT ANY PIPING AND DUCTWORK THAT WAS SUPPORTED FROM BUILDING ELEMENTS REMOVED AS PART OF THE WORK.
g. MAINTAIN CONTROL WIRING OR PNEUMATIC TUBING REQUIRED FOR THE CONTINUED PROPER OPERATION OF THE BUILDING
AUTOMATION SYSTEM.
G. ALL EXISTING EQUIPMENT BEING REMOVED WILL BE HANDED OVER TO OWNER FOR FIRST RIGHT OF SALVAGE. IF OWNER REFUSES SALVAGE
ITEMS, REMOVING CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL.
H. CONTRACTOR SHALL REFER TO THE DRAWINGS OF ALL TRADES TO FAMILIARIZE THEMSELVES WITH EXTENT OF WORK INCLUDING BUT NOT
LIMITED TO WHERE NEW PARTITIONING IS BEING INSTALLED, WHERE EXISTING PARTITIONING IS BEING REMOVED, WHERE CEILINGS ARE BEING
REMOVED AND/OR REPLACED, ETC.
I. THESE DRAWINGS ARE NECESSARILY DIAGRAMMATIC IN NATURE. NOT ALL FITTINGS, OFFSETS, VENTS OR DRAINS ARE SHOWN. THE CONTRACTOR SHALL INCLUDE ALL FITTINGS, OFFSETS, VENTS, DRAINS, AND DEVICES REQUIRED TO PROVIDE A COMPLETE AND FUNCTIONING
SYSTEM.
J. PERFORM AIR AND FLUID BALANCE PRE-TEST ON ALL DISTRIBUTION EQUIPMENT AND ALL AIR OUTLETS IN THE AREA PRIOR TO COMMENCING
WORK. SUBMIT PRE-TEST INFORMATION TO OWNER/ENGINEER.
K. PROVIDE ACCESS DOORS IN DUCTWORK AND/OR ARCHITECTURAL ELEMENTS WHERE REQUIRED TO ACCESS ALL EQUIPMENT REQUIRING MAINTENANCE AND ADJUSTMENT. THIS EQUIPMENT INCLUDES BUT IS NOT LIMITED TO SENSORS, DAMPERS, ACTUATORS, CONTROL DEVICES, VALVES, ETC. ACCESS DOORS SHALL BE SIZED TO PROVIDE APPROPRIATE ACCESS BASED ON HEIGHT OF ACCESS REQUIRED AND ACTIVITY.
INSTALL SUCH THAT ACCESS DOOR IS FULLY OPERABLE WITHOUT THE REMOVAL OF ARCHITECTURAL ELEMENTS SUCH AS CEILING RUNNERS, SUPPORTS, ETC. INSTALL IN A LOCATION SUCH THAT STEPPING OR LEANING OVER PERMANENT EQUIPMENT OR FURNITURE IS NOT REQUIRED.
WHERE ACCESS DOORS ARE REQUIRED IN ARCHITECTURAL ELEMENTS THAT PROVIDE A FIRE AND/OR SMOKE RATING, ACCESS DOOR SHALL
MAINTAIN THE REQUIRED RATING.
L. SEAL ALL WALL PENETRATIONS (DUCTWORK, PIPING, CONTROLS, CONDUITS, ETC.) WITH NON-COMBUSTIBLE MATERIAL. SEAL PENETRATIONS INTO ROOMS THAT REQUIRE PRESSURE CONTROL OR SOUND ISOLATION. WITH NON-COMBUSTIBLE MATERIAL AND CAULK.
M. PIPING AND DUCTWORK SHALL NOT BE ROUTED OVER ELECTRICAL AND TELECOM ROOMS. WHERE ROUTING OVER SUCH ROOMS IS UNAVOIDABLE, CONTRACTOR SHALL COORDINATE WITH OWNER, DESIGN TEAM, AHJ, AND OTHER TRADES REGARDING LOCATION OF PANELS AND UTILITY ROUTING AND SHALL PROVIDE DRIP PANS UNDER ALL UTILITIES WITH MOISTURE SENSORS OR DRAIN PIPING AS REQUIRED BY THE
SPECIFICATIONS.
N. REMOVAL AND REINSTALLATION OF CEILINGS REQUIRED FOR THE COMPLETION OF WORK IS THE RESPONSIBILITY OF THE CONTRACTOR.
CONTRACTOR SHALL REPAIR OR REPLACE ALL DAMAGED CEILING COMPONENTS TO MATCH EXISTING. WHERE AN IDENTICAL MATCH IS NO LONGER AVAILABLE, CONTRACTOR SHALL PROVIDE A SIMILAR REPLACEMENT UPON APPROVAL FROM THE OWNER.
O. FLEXIBLE DUCTWORK SHALL HAVE A MAXIMUM LENGTH OF 48" REGARDLESS OF LENGTH SHOWN ON DRAWINGS. FLEX DUCT INSTALLATION SHALL BE AT TERMINAL ENDS ONLY. CONNECTIONS AT VAV BOX INLETS SHALL BE SOLID HARD DUCT. THE DUCTWORK AT ANY FIRE AND/OR FIRE
SMOKE DAMPER SHALL BE HARD DUCT.
P. LOCATE PIPING AND DUCTWORK IN EXTERIOR BUILDING WALLS ON THE WARM SIDE OF THE BUILDING AND VAPOR BARRIER. COORDINATE INSTALLATION OF BUILDING INSULATION TO RUN CONTINUOUS BETWEEN PIPING AND BUILDING WALL.
Q. SUPPORT ALL DUCTWORK, PIPING AND EQUIPMENT FROM BUILDING STRUCTURE MEMBERS. ROUTE DUCT MAINS TIGHT TO STRUCTURE UNLESS NOTED OTHERWISE. HOLD PIPING TIGHT TO BOTTOM OF STRUCTURAL MEMBERS OR RUN THROUGH JOIST WEBS IF POSSIBLE. DO NOT USE WIRE OR PERFORATED METAL TO SUPPORT PIPING. DO NOT SUPPORT PIPING FROM OTHER PIPING, DUCTWORK, AND/OR ELECTRICAL CONDUITS. SUPPORT FROM BOTTOM CHORD OF BAR JOISTS ONLY AT PANEL POINTS. ALL COMPONENTS REQUIRING MAINTENANCE SHALL BE SUPPORTED IN SUCH A MANNER AS TO BE READILY ACCESSIBLE WITHOUT REMOVAL OF THE CEILING SYSTEM AND TO ALLOW FOR REMOVAL
FROM THE SYSTEM WHEN SUCH REMOVAL IS REQUIRED FOR MAINTENANCE.
R. PROVIDE CONSTRUCTION FILTERS ON AIR MOVING EQUIPMENT SERVING THE CONSTRUCTION AREA AS WELL AS ALL RETURN/EXHAUST DUCT PENETRATIONS COMING FROM THE CONSTRUCTION AREA. AT THE COMPLETION OF WORK, REMOVE ALL TEMPORARY AND CONSTRUCTION
FILTERS AND PROVIDE NEW FILTERS FOR ALL AIR MOVING EQUIPMENT.
S. PROTECT ALL DUCTWORK AND PIPING DURING CONSTRUCTION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. AT A MINIMUM, DUCTWORK AND PIPING ENDS SHALL BE COVERED AND SEALED TO PREVENT THE COLLECTION OF DUST AND DEBRIS. CLEAN ALL INTERIOR SURFACES PRIOR TO INSTALLATION AND PROTECT ONCE INSTALLED. MEDICAL GAS PIPING SHALL BE PROTECTED IN ACCORDANCE WITH NFPA
99 REQUIREMENTS.
T. AT THE COMPLETION OF WORK, CLEAN ALL STRAINERS PROVIDED AS A PART OF THE WORK AS WELL AS PRIMARY SYSTEM STRAINERS LOCATED AT PUMPS WHERE SYSTEMS WERE EXTENDED. ON EXISTING EQUIPMENT, COORDINATE WORK WITH OWNER.
U. PROVIDE INTERMEDIATE TESTING AND BALANCING AT THE COMPLETION OF EACH PHASE AND AS REQUIRED TO MAINTAIN PROPER OPERATION OF SYSTEMS SERVING AREAS OF THE FACILITY IN USE INCLUDING BUT NOT LIMITED TO OCCUPIED AREAS, STORAGE AREAS, AND OTHER AREAS
DEEMED CRITICAL BY THE OWNER OR AHJ.
V. UNLESS NOTED OTHERWISE, DETAILS SHOWN WITHIN THESE DOCUMENTS ARE APPLICABLE FOR ALL PIPING, EQUIPMENT AND DUCTWORK
INSTALLATIONS WHETHER OR NOT SPECIFICALLY NOTED.
W. REFER TO SCHEDULES FOR SIZES OF FINAL RUNOUTS TO EQUIPMENT, FIXTURES, DIFFUSERS, GRILLES, AND TERMINAL DEVICES. FINAL RUNOUT SIZES LISTED SHALL BE USED TO WITHIN 10 EQUIVALENT DIAMETERS OF FINAL CONNECTION POINT. FINAL PIPING CONNECTION TO EQUIPMENT SHALL MATCH EQUIPMENT CONNECTION SIZE, PROVIDE TRANSITIONS AS REQUIRED. REFER TO DETAILS, DIAGRAMS AND SCHEMATICS FOR
ADDITIONAL FINAL CONNECTION REQUIREMENTS.
X. FOR DUCTWORK PENETRATING A ONE HOUR FIRE RATED WALL WHERE A FIRE DAMPER IS NOT SHOWN, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. THE SYSTEM SHALL BE FIRE TESTED PER ASTM E119 AND COMPLY WITH EXCEPTION 1 OF 2018 IBC PART 717.5.2. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER'S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO A ONE HOUR FIRE RATED WALL, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS.
REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS. ALL DUCTWORK PENETRATIONS SHALL BE INSPECTED BY AN APPROVED THIRD PARTY INSPECTION AGENCY IN ACCORDANCE WITH ASTM E2174. THE INSPECTION AGENCY SHALL BE PROCURED BY THE CONTRACTOR. DOCUMENTATION OF APPROVED INSPECTION SHALL BE INCLUDED WITH PROJECT CLOSEOUT
DOCUMENTATION.
Y. FIRE ALARM CONTRACTOR SHALL PROVIDE A DUCT SMOKE DETECTOR FOR EACH SMOKE OR FIRE/SMOKE DAMPER AS REQUIRED BY CODE.
MECHANICAL CONTRACTOR SHALL COORDINATE THE LOCATION OF EACH DUCT SMOKE DETECTOR AND SHALL INSTALL THEM IN THE DUCT.
Z. FOR ALL PIPING, CONDUIT, AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER'S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
AA. IN AREAS WHERE MECHANICAL OR PLUMBING WORK PENETRATES INTERIOR OR EXTERIOR WALLS, CEILING PANELS, GRID SYSTEMS, GYPSUM CEILINGS AND/OR BULKHEADS, CONTRACTOR SHALL BE REQUIRED TO PATCH AND REPAIR PENETRATIONS AS A RESULT OF THE WORK.
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
FULLY SPRINKLERED
COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc
102 3rd Avenue, NE
PO Box 1629, Hickory, NC 28603
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
NC Architectural License No.: 51254
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Project Director
Revisions: Date:
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
20375.007 07/14/2022
M000
MECHANICAL SYMBOLS AND
ABBREVIATIONS VARIOUS
07/14/2022
100% CONSTRUCTION
DOCUMENTS
Revisions: Date:
CONDENSING UNIT
FAN GUARD
REFRIGERANT
GAUGE
CONNECTION
REFRIGERANT
SUCTION LINE
REFRIGERANT LIQUID LINE,
FILTER-DRYER AND SIGHT GLASS
INSTALLED PER MANUFACTURER
SPECIFICATIONS
CONDUIT - POWER
AND CONTROL
CONDENSER
COIL
18" HIGH,
MINIMUM 4'
LONG
EQUIPMENT
RAILS
ROOF CAP AND CURB
NOTE: ELECTRICAL CONTRACTOR SHALL GROUND ROOF MOUNTED CONDENSING
UNIT TO LIGHTNING PROTECTION SYSTEM ON BUILDINGS WITH EXISTING LIGHTNING
PROTECTION SYSTEM.
CONDENSING UNIT
FAN GUARD
REFRIGERANT GAUGE
CONNECTION
REFRIGERANT
SUCTION LINE
REFRIGERANT LIQUID LINE, FILTER-
DRYER AND SIGHT GLASS INSTALLED
PER MANUFACTURER SPECIFICATIONS CONDUIT - POWER AND
CONTROL
6" THICK CONCRETE PAD -
EXTEND 6" BEYOND UNIT
ALL AROUND
THERMOSTAT/
HUMIDISTAT
60"
A. COORDINATE ELEVATION OF DEVICES WITH ALL ADJACENT DEVICES INCLUDING THOSE WITH OTHER TRADES. ALL DEVICES WHICH HAVE ADA AND NON-ADA HEIGHTS LISTED SHALL BE MOUNTED TO COMPLY WITH ADA EXCEPT WHERE NOTED ON THE PLANS AS NON-ADA.
B. GROUP DEVICES IN AN ORGANIZED AND UNIFORM MANNER.
C. REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL REQUIREMENTS. WHERE THESE REQUIREMENTS DIFFER FROM THE ARCHITECTURAL PLANS, THE ARCHITECTURAL PLANS SHALL TAKE PRECEDENCE.
D. ALL DEVICES SHALL BE COORDINATED SO AS NOT TO INTERRUPT A BACK SPLASH OR MATERIAL TRANSITIONS. REFER TO ARCHITECTURAL ELEVATION TO CONFIRM DEVICE IS NOT LOCATED WITHIN TRANSITION AREA.
E. PROVIDE BACKING IN WALLS WHERE WALL MOUNTED DEVICES OR EQUIPMENT ARE INSTALLED. REFER TO ARCHITECTURAL SPECIFICATIONS.
SPLIT SYSTEM DX CONTROLS:
• CONSISTS OF WALL/CEILING MOUNTED BLOWER EVAPORATOR UNIT, ROOF/GRADE MOUNTED CONDENSING UNIT, WALL MOUNTED
CONDITIONING SYSTEMS: THERMOSTAT AND HUMIDISTAT PROVIDED BY TEMPERATURE CONTROLS CONTRACTOR, AND MANUFACTURER
SUPPLIED TEMPERATURE CONTROLLER.
• CYCLE CONDENSING UNIT AND INDOOR UNIT IN UNISON TO MAINTAIN A SPACE TEMPERATURE SETPOINT OF 75°F (ADJUSTABLE). MONITOR ROOM TEMPERATURE, ROOM RELATIVE HUMIDITY, EQUIPMENT STATUS AND CONDENSATE ALARM OUTPUTS FROM EQUIPMENT SUPPLIED CONTROLS THROUGH DDC. SEND ALARM TO THE OPERATOR INTERFACE IF THE SPACE TEMPERATURE EXCEEDS 90°F (ADJUSTABLE) OR SPACE THE SPACE RELATIVE HUMIDITY IS BELOW 8% RH (ADJUSTABLE) OR ABOVE 80% RH (ADJUSTABLE). INTEGRATE ALL MONITORED
PARAMETERS INTO EXISTING SIEMENS BAS.
• SPLIT SYSTEM SHALL BE INTERLOCKED WITH CONDENSATE PUMP FOR PUMP FAILURE AND, UPON PUMP FAILURE, AN ALARM SHALL BE
SENT THROUGH DDC SYSTEM.
COMPUTER ROOM AIR CONDITIONER (CRAC) UNIT CONTROLS:
• CONSISTS OF FLOOR MOUNTED BLOWER EVAPORATOR UNITS WITH LOCAL MONITORING PANEL, GRADE MOUNTED CONDENSING UNIT, MANUFACTURER CONDITIONING SYSTEMS, AND SUPPLIED TEMPERATURE CONTROLLER.
• ALL THREE CRAC UNITS SHALL BE INTERLOCKED WITH EMERGENCY POWER OFF SWITCHES. ALL THREE CRAC UNITS SHALL BE
INTERLOCKED WITH CLEAN AGENT SYSTEM TO SHUT DOWN CRAC UNIT SYSTEM UPON ACTIVATION OF CLEAN AGENT SYSTEM.
• INDOOR EVAPORATOR LOCAL MONITORING PANEL SHALL ACCESS THE FOLLOWING:
1. AUTOMATIC RESTART WITH PROGRAMMABLE DELAY
2. SENSOR CALIBRATION
3. SEQUENTIAL LOAD ACTIVATION
4. CURRENT TEMPERATURE SET POINT AND LOCATION OF SET POINT
5. CURRENT SUPPLY AND RETURN TEMPERATURE AND HUMIDITY
6. UNIT DIAGNOSTICS
7. ALARM HISTORY
8. RUNTIME LOG
9. AUDIBLE/VISUAL ALARM
• CYCLE CONDENSING UNIT AND INDOOR UNIT IN UNISON TO MAINTAIN A SPACE TEMPERATURE SETPOINT OF 75°F (ADJUSTABLE) AND RELATIVE HUMIDITY SETPOINT OF 30-60% RH (ADJUSTABLE). MONITOR SUPPLY AND RETURN TEMPERATURE AND HUMIDITY FOR EACH UNIT, ROOM TEMPERATURE, HUMIDITY, EQUIPMENT STATUS AND CONDENSATE ALARM OUTPUTS FROM EQUIPMENT SUPPLIED CONTROLS THROUGH DDC. SEND ALARM TO THE OPERATOR INTERFACE IF THE SPACE TEMPERATURE EXCEEDS 90°F (ADJUSTABLE) OR SPACE RELATIVE HUMIDITY IS BELOW 20% RH (ADJUSTABLE) OR ABOVE 50% RH (ADJUSTABLE). INTEGRATE ALL MONITORED PARAMETERS INTO
EXISTING SIEMENS BAS.
• NORMAL OPERATION MODE:
1. ALL THREE CRAC UNITS OPERATING AT PART LOAD TO PROVIDE 21,000 CFM OR 7,000 CFM EACH.
• MAINTENANCE/REPAIR OPERATIONS MODE (ONE UNIT DOWN):
1. TWO CRAC UNITS OPERATING AT 9,000 CFM EACH TO PROVIDE 18,000 CFM.
• ALL UNITS SHALL BE CAPABLE OF BEING ISOLATED FOR MAINTENANCE PURPOSES WHILE NOT IMPACTING DATA CENTER COOLING
CAPACITY.
1. UNIT OPERATION SHALL BE INTERLOCKED WITH AN ISOLATION DAMPER LOCATED IN THE RETURN DUCT SERVING EACH UNIT TO
PREVENT RETURN AIR FROM CIRCULATING THROUGH A CRAC UNIT WHILE DOWN FOR MAINTENANCE.
• PROVIDE TEMPERATURE AND HUMIDITY SENSORS IN THE FOLLOWING LOCATIONS FOR IT EQUIPMENT CABINETS.
1. MINIMUM TWO SENSORS PER MONITORED CABINET.
2. SENSORS SHALL BE LOCATED IN CABINETS AT THE ENDS OF CONTIGUOUS ROWS, AND IN EVERY THIRD CABINET IN THE MIDDLE OF A
CONTIGUOUS ROW.
3. TEMPERATURE SENSORS SHALL BE PROVIDED IN THE FRONT MIDDLE AND REAR TOP OF MONITORED CABINETS
A. FRONT MIDDLE SENSOR: CENTERED HORIZONTALLY, INSIDE THE FRONT DOOR, 4 FT +/- 6 INCHES FROM THE FINISHED FLOOR
SURFACE.
B. REAR TOP SENSOR: CENTERED HORIZONTALLY, INSIDE THE REAR DOOR NO MORE THAN 1 FT FROM THE TOP OF THE CABINET.
4. HUMIDITY SENSORS SHALL BE PROVIDED IN THE FRONT MIDDLE OF MONITORED CABINETS.
A. FRONT MIDDLE SENSOR: CENTERED HORIZONTALLY, INSIDE THE FRONT DOOR, 4 FT +/- 6 INCHES FROM THE FINISHED FLOOR
SURFACE.
• CYCLE CONDENSING UNITS AND INDOOR UNITS IN UNISON TO MAINTAIN A SPACE TEMPERATURE SETPOINT OF 75°F (ADJUSTABLE) AND RELATIVE HUMIDITY SETPOINT OF 30% - 60% (ADJUSTABLE). MONITOR ROOM TEMPERATURE, EQUIPMENT STATUS AND CONDENSATE ALARM OUTPUTS FROM EQUIPMENT SUPPLIED CONTROLS THROUGH EXISTING SIEMENS BAS. SEND ALARM TO THE OPERATOR INTERFACE IF THE SPACE TEMPERATURE EXCEEDS 90°F (ADJUSTABLE) OR SPACE RELATIVE HUMIDITY IS BELOW 20% (ADJUSTABLE) OR ABOVE 70%
(ADUSTABLE).
DRIP PAN LEAK DETECTION:
• CONSISTS OF POINT LEAK DETECTION, ZONE LEAK DETECTION PANELS, LINEAR DETECTION SYSTEM, WIRE-FREE SENSORS, AND DCIM
INTEGRATION.
• LIQUID WATER DETECTION SHALL ALARM TO BAS UPON DETECTION OF MOISTURE. MONITORING OF LIQUID WATER DETECTION SHALL BE
CONTINUAL REAL-TIME MONITORING. INTEGRATE ALL MONITORED PARAMETERS INTO EXISTING SIEMENS BAS.
STREET L
4" PVC
AP SEALANT
WATERSTOP
STAINLESS STEEL CLAMP
PRE-FABRICATED
PIPE BOOT
#14x5" FASTENERS
EXISTING MEMBRANE
METAL DECK
ROOF INSULATION
NOTES:
1. MECHANICAL CONTRACTOR SHALL LOCATE AND CUT 4" DIAMETER HOLE, GENERAL CONTRACTOR
SHALL FURNISH AND INSTALL GOOSE NECK ASSEMBLY. CONNECTIONS ARE TO REMAIN LOOSE SO
LINES CAN BE INSTALLED AND MECHANICAL CONTRACTOR SHALL REASSEMBLE GOOSE NECK.
2. INSTALL PIPE BOOT PER MANUFACTURE'S INSTRUCTIONS.
8" MIN.
INSECT SCREEN
FIRESTOPPING
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
FULLY SPRINKLERED
COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc
102 3rd Avenue, NE
PO Box 1629, Hickory, NC 28603
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
NC Architectural License No.: 51254
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Project Director
Revisions: Date:
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
20375.007 07/14/2022
M001
MECHANICAL DETAILS AND
CONTROLS VARIOUS
07/14/2022
100% CONSTRUCTION
DOCUMENTS
NO SCALE
AIR-COOLED CONDENSING UNIT - ROOF MOUNTED
NO SCALE
AIR-COOLED CONDENSING UNIT - SLAB MOUNTED AT GRADE
NO SCALE
MECHANICAL EQUIPMENT MOUNTING HEIGHTS
NO SCALE
MISCELLANEOUS CONTROLS
NO SCALE
GOOSE NECK PENETRATION DETAIL
A
A
System No. W-L-7028 F Ratings - 1 and 2 hr (See Item 1)
T Rating - 3/4"
Section A-A
Section A-A
A
A
System No. W-L-7026 F Ratings - 1 and 2 hr (See Item 1)
T Rating - 0Hr L Rating At Ambient - Less Than 1 CFM/sq ft L Rating AT 400 F - Less Than 1 CFM/sq ft
A
A
System No. W-L-7025 F Ratings - 1 and 2 hr (See Item 1)
T Rating - 1/2Hr L Rating At Ambient - Less Than 1 CFM/sq ft L Rating AT 400 F - Less Than 1 CFM/sq ft
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory and shallinclude the following construction features:
A. Studs - Wall framing shall consist of min 3-1/2 in. (89 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. Additional steel studs shall be used to completely frame the opening.
B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U400 or V400 Series Design in the UL Fire Resistance
Directory. Max area of opening is 73.7 sq ft (6.85 m2) with a max dimension of 104 in. (2.64 m).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
2. Steel Duct - Max 100 in. by 100 in. (2.54 by 2.54 m) No. 26 gauge (or heavier) galv steel duct to be installed either concentrically or eccentrically within the firestop system. The space between the steel duct and periphery of opening shall be min 0 in. ( 0 mm, point contact) to max 2 in. (51 mm). Steel duct to be rigidly supported on both sides of the wall assembly.
3. Firestop System - The firestop system shall consist of the following:
A. Packing Material - (Optional, Not Shown) - Polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fitted into annular space. Packing material to be recessed from both surfaces of wall as required to accommodate the required thickness of fill material.
B. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. Min 1/4 in. (6 mm) diam bead of fill material shall be applied at the point contact location between the steel duct and the gypsum board. For 2 hr Rated walls when LC150 or LE600 Sealant is used, fill material thickness installed to full depth of gypsum board layers on each side of wall assembly.
SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, SpecSeal LCI Sealant, SpecSeal LC150
Sealant or SpecSeal LE 600 Sealant.
C. Steel Retaining Angles - Min No. 16 gauge (0.059 in. or 15 mm) galv steel angles sized to lap steel duct a min of 2 in. (51mm) and to lap wall surfaces a min of 1 in. (25 mm). Angles attached to steel duct on both sides of wall with min No. 10 by 1/2 in. (13 mm) long steel sheet metal screws located a max of 1 in. (25 mm) from each end of steel duct and spaced a max of 6 in. (152 mm) OC.
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as
Canada), respectively.
Section A-A
A
A
Section A-A
System No. W-L-5014 F Ratings - 1 and 2 hr (See Item 1)
T Rating - 1 Hr L Rating At Ambient - Less Than 1 CFM/sq ft L Rating AT 400 F - Less Than 1 CFM/sq ft
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102
mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-5/8 in. (92 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.2 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 18 in. (457mm).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly inwhich it is installed.
Metallic Sleeve - (Optional, Not Shown) - Cylindrical sleeve fabricated from min 0.016 in. (0.41 mm) to max 0.105 in. (2.7 mm) thick sheet steel. Length of steel sleeve to be equal to the thickness of wall. Longitudinal seam of sleeve welded or overlapped min 1 in.
(25 mm). The ends of the steel sleeve shall be flush or recessed max 1/4 in. (6 mm) from wall surfaces.
2. Through Penetrants - One metallic pipe or tubing to be installed either concentrically or eccentrically within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe - Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 12 in. (305 mm) diam (or smaller) cast or ductile iron pipe.
C. Copper Tubing - Nom 4 in. (102 mm) diam (or smaller) Type M (or heavier) copper tube.
D. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.
3. Pipe Coverings* - One of the following types of pipe coverings shall be used:
A. Pipe and Equipment Covering Materials* - Max 2 in. (51 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space between insulated penetrating item and the edge of the through opening shall be min 0 in.
(point contact) to max 1-1/4 in. (32 mm).
See Pipe and Equipment Covering-Materials* - (BRGU) category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.
B. Pipe Covering Materials* - Max 2 in. (51 mm) thick unfaced mineral fiber pipe insulation sized to the outside diam of pipe or tube. Pipe insulation secured with min 18 SWG steel wire spaced max 12 in. (305 mm) OC. The annular space between insulated penetrating item and the edge of the through opening shall be min 0 in. (point contact) to max 1-1/4 in. (32 mm).
IIG MINWOOL L L C - High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT or High
Temperature Pipe Insulation Thermaloc.
C. Sheathing Material* - Used in conjunction with Item 3B. Foil-scrim-kraft or all service jacket material shall be wrapped around the outer circumference of the pipe insulation (Item 3B) with the kraft side exposed. Longitudinal joints and transverse joints sealed with metal fasteners or butt tape.
See Sheathing Materials (BVDV) category in the Building Materials Directory for names of manufacturers. Any sheathing material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.
4. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall. At point contact location between insulated through penetrant and gypsum board, a min 3/8 in. (10 mm) bead of fill material shall be applied to the insulated through penetrant/gypsum board interface on both sides of the wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification
(such as Canada), respectively.
Section A-A
A
A
System No. W-L-1251 F Ratings - 1 and 2 hr (See Item 1)
T Rating - 0 Hr
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud shaft wall assembly shall be constructed of the materials and in the manner specified in the individual U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Steel Studs - "C-H" or "C-T" shaped studs, min 2-1/2 in. (64 mm) wide by 1-1/2 in. (38 mm) deep, fabricated from min No. 25 gauge (0.6 mm thick) galv steel, spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max diam of circular cutout in gypsum liner panel is 10 in. (254 mm).
C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of circular cutout in gypsum board is 10 in. (254 mm).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
2. Metallic Sleeve - Cylindrical sleeve fabricated from min No. 30 gauge (0.3 mm thick) galv sheet steel and having a min 2 in. (51 mm) lap along the longitudinal seam. Length of the sleeve to be equal to the thickness of the wall. Sleeve installed by coiling the sheet steel to a diam smaller than the through opening, inserting the coil through the opening and releasing the coil to let it uncoil against the circular cutouts in the gypsum board layers. The ends of the steel sleeve shall be flush with each surface of the wall.
3. Through Penetrant - - One metallic pipe, tube or conduit installed concentrically or eccentrically within the firestop system. The annular space between the pipe, tube or conduit and the periphery of the sleeved opening to be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe, tube or conduit to be rigidly supported on both sides of wall assembly. One of the following types and sizes of pipe, tube or conduit may be used:
A. Steel Pipe - Nom 8 in. (203 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.
B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 4 in. (102 mm) diam (or smaller) rigid steel conduit, steel electrical metallic tubing (EMT) or flexible steel conduit.
D. Copper Pipe or Tube - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe or Type L (or heavier) copper tube.
4. Firestop System - The firestop system consists of the following items:
A. Packing Material - Min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into sleeved opening as a permanent form.
Packing material to extend throughout thickness of wall except for a 1 in. (25 mm) deep recess on the finished side of wall to accommodate the fill material.
B. Fill Void or Cavity Materials* - Sealant or Putty - Min 1 in. (25 mm) thickness of fill material applied with in sleeve, flush with finished surface of wall. At the point contact location, a min 3/8 in. (10 mm) diam bead of fill material shall be applied at the penetrant/sleeve interface.
SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, or SpecSeal Putty
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as
Canada), respectively.
Section A-A
A
A
System No. W-L-1168 F Ratings - 1 and 2 hr (See Item 1)
T Rating - 1/4, 3/4 and 1 Hr (see Items 2 and 4)
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U400, V400 or W400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing shall consist of min 3-5/8 in. (92 mm) wide steel studs spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners , as specified in the individual U400, V400 or W400
Series design. Max height of opening is 6 in. (152 mm). Max width of opening is 36 in. (914 mm).
The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrants - Multiple pipes or conduits installed in single layer array within the firestop system. The annular space between the pipes and conduits and the edges of the opening shall be min 0 in. (point contact) to max 3 in. (76 mm). The separation between pipes and conduits to be min 1/4 in. (6 mm) to max 3 in. (76 mm). Pipes and conduits to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipe or conduit may be used:
A. Steel Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.
B. Conduit - Nom 4 in. (102 mm) diam (or smaller) rigid steel conduit or steel electrical metallic tubing (EMT).
When diam of pipe or conduit is greater than 2 in. (51 mm), T, FT and FTH Ratings are 1/4 hr. Otherwise, T, FT and FTH Ratings are 3/4 hr or 1 hr as detailed in Item 4.
3. Forming Material - (Optional, Not Shown) - Foam backer rod, mineral wool batt insulation or glass fiber insulation packed into opening and recessed min 5/8 in. (16 mm) from each surface of the wall to accommodate fill material.
4. Fill Void or Cavity Materials* - Sealant - Min 5/8 in. (16 mm) thickness of fill material installed to completely fill annular space between pipes, conduits and gypsum wallboard flush with each surface of wall. Min 1/4 in. (6 mm) diam bead of fill material applied to the pipe/wall interface at the point contact locations on both sides of the wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal LC150 Sealant, SpecSeal Series SSS Sealant or SpecSeal LCI Sealant. When SpecSeal
LC150 Sealant is used with max 2 in. (51 mm) diam pipe or conduit, T, FT and FTH Ratings are 3/4 hr. Otherwise, when SpecSeal
LCI or SpecSeal Series SSS Sealant is used with max 2 in. (51 mm) diam pipe or conduit, T, FT and FTH Ratings are 1 hr.
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as
Canada), respectively.
A
A
System No. W-L-1049 F Ratings - 1 and 2 hr (See Item 1) T Rating - 0Hr
L Rating At Ambient - Less Than 1 CFM/sq ft L Rating AT 400 F - Less Than 1 CFM/sq ft
Section A-A
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-5/8 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. When steel studs are used and the diam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between the vertical studs and screw-attached to the steel studs at each end. The framed opening in the wall shall be
4 to 6 in. (102 to 152 mm) wider and 4 to 6 in. (102 to 152 mm) higher than the diam of the penetrating item such that, when the penetrating item is installed in the opening, a 2 to 3 in. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides.
B. Gypsum Board* - 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance
Directory. Max diam of opening is 26 in. (660 mm) for steel stud walls. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls.
The hourly F and FH Ratings of the firestop system are…