S02 - Attachment 12 - EHRM Columbia VAHCS Addendum 001.pdf
PDF 754 KB Posted
- Attached to
- EHRM Infrastructure Upgrades Construction - Columbia, SC VAMC Federal contract opportunity
- Solicitation number
- 36C77623R0096
About this file
This document package includes construction documents and addendum for infrastructure upgrades at the Columbia, South Carolina VA Medical Center. The project involves upgrading the fiber optic and copper cabling backbone between buildings and to the main data center, as well as installing security cameras and access control systems at several buildings. Buildings to receive fiber connections, security cameras, and access control include the main hospital, outpatient clinic, engineering buildings, and community living center. The work requires installing new fiber and copper cabling in conduits and cable trays, as well as mounting network equipment racks, switches, patch panels, UPSes, and PDUs. Media converters will connect security cameras to the fiber network. Access control devices like card readers, locks, and door contacts will integrate with the existing system.
View the file
Other files for this federal contract opportunity
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
703 Main Ave. SW
PO Box 1629 Hickory, NC 28603
Telephone: (828) 315-9962 Website: www.atriaxgroup.com
Atriax, PLLC, 703 Main Ave. SW (28603), PO Box 1629, Hickory, NC 28603, Phone: (828) 315-9962
INTEGRITY ● SERVICE ● EXCELLENCE
Addendum Number 001
To the Construction Documents for: EHRM Infrastructure Upgrades
VA Project Number: 544-20-107
Date: 16 June 2023
General:
The following changes, additions, or deletions shall be made to the following documents as indicated. All conditions not included below shall remain the same.
Item Number:
1. Drawing sheet TG006 - Added T25 to the list of buildings requiring fiber connection back to B100 Data Center. Added note to explain the fiber being used for the cameras is the same fiber being installed for the voice/data backbone between each building and the B100 Data center.
2. Drawing sheet TNBT25.1 - Added camera to monitor the TE. Added note to detail the camera connection requirement back to B100 Data center.
3. Drawing sheet TN430 - Added keynote to detail requirement for monitoring of the TE with door contact that runs back to B20 for connection to existing access control panel.
1" CONDUIT STUBBED INTO TOP OF
DOOR FRAME FOR BALANCED
MAGNETIC SWITCH (BMS)
MIN. 1" CONDUIT TO NEW
ACS/ IDS PANEL WITHIN
TR
6" X 6" SECURITY JUNCTION BOX FOR
SECURITY DOOR INTERFACE MODULE
SURFACE MOUNT JUNCTION BOX ON SECURE
SIDE OF DOOR 6" ABOVE FINISHED CEILING
OR 30" ABOVE DOOR FRAME WHEN NO
CEILING IS AVAILABLE. COORDINATE
LOCATION WITH MECHANICAL EQUIPMENT IN
AREA.
ACS
JUNCTION
BOX
1" CONDUIT TO CARD
READER/ KEYPAD (CR/KP)
JUNCTION BOX
RECESSED DOUBLE GANG
JUNCTION BOX WITH SINGLE
GANG MOUNTING RING FOR
CARD READER/ KEYPAD
(CR/KP) MOUNT AT 48 INCHES
A.F.F. UNLESS OTHERWISE
NOTED
BMS
CR/KP
EL
1" CONDUIT TO ELECTRIC
STRIKE (EL)
REX
1" CONDUIT FOR REX
PLEASE REFER TO
THE ARCHITECURAL
DOOR HARDWARE
SCHEDULE
MIN. 1" CONDUIT WITH CAT
6A CABLING FROM
CAMERA TO EXISTING
SSTV TELECOM ROOM
LOCATION
DOME CAMERA:
MOUNT CAMERA IN A POSITION
TO PREVENT GLARE FROM
OVERHEAD LIGHTING.
SSTV
FINISHED WALL
SURFACE MOUNTED
DEEP SINGLE GANG
JUNCTION BOX
SSTV
CEILING SLAB
C R
/K P
EL
B M
S
CR/KP
EL
BMS
CARD READER/ KEYPAD JUNCTION BOX WITH
MIN. 1" CONDUIT FROM ACS/IDS JUNCTION BOX
LOCATED ABOVE TR DOOR TO NEW PREMISE
CONTROL UNIT LOCATION.
SYMBOL LEGEND:
ELECTRONIC LOCK WITH MIN. 1" CONDUIT
FROM ACS/IDS JUNCTION BOX LOCATED ABOVE
TR DOOR TO NEW PREMISE CONTROL UNIT
LOCATION.
BALANCED MAGNETIC SWITCH W ITH MIN. 1"
CONDUIT FROM ACS/IDS JUNCTION BOX
LOCATED ABOVE TR DOOR TO NEW PREMISE
CONTROL UNIT LOCATION.
DOME STYLE SECURITY CAMERA.
R E
X
REX REQUEST TO EXIT DEVICE WITH MIN. 1"
CONDUIT FROM ACS/IDS JUNCTION BOX
LOCATED ABOVE TR DOOR TO NEW PREMISE
CONTROL UNIT LOCATION.
PCU
PCU PREMISE CONTROL UNIT FOR ACS/IDS SYSTEM
DEVICES. WILL REQUIRE DEDICATED 20A
CIRCUIT PROVIDED BY ELECTRICAL.
NEW TR
CR/KP
EL
BMS
REX
PCU
SW
EXISTING
TCP/IP
NETWORK
EQUIPMENT
RACKSW RACK MOUNTED SW ITCH FOR SECURITY
CPP RACK MOUNTED COPPER PATCH PANEL
CPP
X
NOTE: COORDINATE WITH LOCAL SECURITY CONTRACTOR
CPP
SW
X
VMS
X
EXISTING
TCP/IP
NETWORK
NEW DOME
STYLE CAMERA
CPP
SW
VMS
NEW CAT 6A
CABLING
EXISTING COPPER PATCH PANEL
EXISTING OWNER PROVIDED SSTV
SWITCH
EXISTING OWNER PROVIDED VIDEO
MANAGEMENT SYSTEM
EXISTING TR IN BULDINGS WITH
EXISTING CAMERA SWITCH
SYMBOL LEGENDNEW TR
EQUIPMENT
RACK
CPP
SW
X
VMS
X
EXISTING
TCP/IP
NETWORK
NEW DOME
STYLE CAMERA
NEW CAT 6A
CABLING
DATA CENTER B100 NEW TR IN BUILDINGS WITH NO EXISTING CAMERA
SWITCH (B5, B6, B8, B20, BT25, BT36, B105 AND VARO)
EQUIPMENT
RACK
SM OSP FIBER
10/100/1000 MEDIA
CONVERTER
FPP
10/100/1000 MEDIA
CONVERTER
CAT 6A CABLING
SM OS2 JUMPER
EQUIPMENT
RACK
FPP
SM OS2 JUMPER
FIBER INSTALLED AS PART OF THIS
PROJECT. SEE SHEET TG003
RACK/ ENCLOSURE
RACK MOUNTED UPS
ZONE
PDU
RACKED EQUIPMENT
RACKED EQUIPMENT
RACKED EQUIPMENT
POWER
SUPPLY 1
POWER
SUPPLY 2
LEG A
BUS B
RACK/ ENCLOSURE
RACK MOUNTED UPS
RACKED EQUIPMENT
RACKED EQUIPMENT
RACKED EQUIPMENT
POWER
SUPPLY 1
POWER
SUPPLY 2
LEG B
BUS A
NOTE:
RACKS/ ENCLOSURES WILL HAVE A/B
REDUNDANT L21-30 CIRCUITS FOR THE
PAIR OF NETW ORK RACK/ ENCLOSURES,
WITH A 30A ZONE PDU SERVING THE PAIR
AND A/B REDUNDANT 20A RACK PDU'S TO
DISTRIBUTE THE POWER IN EACH RACK
B SIDE
VERTICAL RACK
MOUNTED PDU
A SIDE
VERTICAL RACK
MOUNTED PDU
RACK/ ENCLOSURE
RACK MOUNTED UPS
RACKED EQUIPMENT
RACKED EQUIPMENT
RACKED EQUIPMENT
POWER
SUPPLY 1
POWER
SUPPLY 2
BUS B
BUS A
FOR TR'S WITH ONE NETW ORK RACK FOR TR'S WITH TWO NETWORK RACKS
NOTE:
RACK/ ENCLOSURE WILL HAVE
A/B REDUNDANT L21-20
CIRCUITS FOR THE NETWORK
RACK/ ENCLOSURE, WITH A/B
REDUNDANT 20A RACK PDU'S
TO DISTRIBUTE THE POWER IN
THE RACK
B SIDE
VERTICAL RACK
MOUNTED PDU
A SIDE
VERTICAL RACK
MOUNTED PDU
KEY
BUS A: COMMERCIAL POWER
BRANCH CIRCUIT
BUS B: GENERATOR POWER BRANCH
CIRCUIT (WHERE AVAILABLE)
LEG A/B: A AND B DISTRIBUTION LEGS
OF THE ZONE PDU
POWER SUPPLY 1/2: REDUNDANT
POWER SUPPLIES IN EACH PIECE OF
IT EQUIPMENT
MIN. 1" CONDUIT TO CABLE
TRAY OR NEAREST TELECOM
ROOM (TR)
4-11/16 INCHES SQUARE
BY 2-1/8 INCHES DEEP
JUNCTION BOX
COMPRESSION TYPE
STEEL CONNECTOR
DOUBLE GANG JUNCTION BOX
REDUCTION RING FOR SINGLE
GANG FACEPLATE
PULL STRING
SINGLE GANG
FACEPLATE
PULL STRING TIED TO
CABLETRAY
NOTE:
THIS DETAIL IS ONLY FOR JUNCTION
BOX ROUGH-IN INFORMATION
SEE TELECOM FLOOR PLAN, OUTLET
TYPE SCHEDULE AND FACEPLATE
DETAILS FOR OUTLET TYPES,
CABLING AND FACEPLATE
INFORMATION
DESIGN OUTLET BOX FOR RECESS
MOUNTING WITH THE FACEPLATE
FLUSH WITH THE WALL SURFACE, AT
THE SAME HEIGHT AS THE
ELECTRICAL OUTLETS
EXISTING
OUTLET
TYPICAL
OFFICE
EXISTING
CONDUIT
WITHIN WALL
CORRIDOR
NEW CABLE
TRAY
EXISTING
TROUGH
EXISTING
OUTLET
TYPICAL
OFFICE
EXISTING
CONDUIT
WITHIN WALL
CORRIDOR
NEW CONDUIT
EXISTING DATA
CABLE THROUGH
CEILING TILE
(THIS CABLE IS
WITHIN SPACE
AND NOT WITHIN
WALL)
EXISTING
OUTLET WITH
NEW CAT 6A
CABLE
TYPICAL
OFFICE
EXISTING
CONDUIT
WITHIN WALL
CORRIDOR
NEW CABLE
TRAY
CEILING CEILING CEILING
EXISTING
TROUGH
RETERMINATE
CABLING AFTER
REMOVING FROM
EXISTING
OUTLET
NEW CAT 6A
CABLING TO
EXISTING
OUTLET
DEMO OF
EXISTING
TROUGH
NEW CONDUIT
CONDUIT
CONNECTOR
STEP 1:
• CONTRACTOR TO IDENTIFY EXISTING
CONDUIT RUN FROM EACH OUTLET
STEP 2:
• REMOVE EXISTING CABLE FROM EXISTING CONDUIT
(BACK TO NEAREST PULL POINT/CABLE TROUGH
• CUT EXISTING CONDUIT ABOVE CEILING
• RE-ROUTE EXISTING CABLE THROUGH FIRE
PROTECTION GROMMET IN CEILING TILE
STEP 3:
• CONNECT EXISTING CONDUIT TO NEW CONDUIT
• INSTALL NEW CABLE THROUGH CONDUIT
• DEMOLISH OLD UNUSED PATHWAY
• REPLACE CEILING TILE
1" CONDUIT STUBBED INTO TOP OF
DOOR FRAME FOR BALANCED
MAGNETIC SWITCH (BMS)
MIN. 1" CONDUIT TO NEW ACS/
IDS PANEL WITHIN TR
6" X 6" SECURITY JUNCTION BOX FOR SECURITY DOOR
INTERFACE MODULE SURFACE MOUNT JUNCTION BOX
ON SECURE SIDE OF DOOR 6" ABOVE FINISHED CEILING
OR 30" ABOVE DOOR FRAME WHEN NO CEILING IS
AVAILABLE. COORDINATE LOCATION WITH MECHANICAL
EQUIPMENT IN AREA.
ACS/IDS
ACCESSIBLE CEILING
BALANCED
MAGNETIC SW ITCH
(BMS) STUB 1"
CONDUIT INTO TOP
OF DOOR FRAME
RECESSED DOUBLE GANG
JUNCTION BOX WITH SINGLE
GANG MOUNTING RING FOR
CARD READER (CR, CR/KP)
MOUNT AT 48 INCHES A.F.F.
UNLESS OTHERWISE NOTED
1" CONDUIT TO CARD
READER (CR, CR/KP)
JUNCTION BOX
BMS BMS
CR/KP
1" CONDUIT TO
ELECTRIC
STRIKE (EL)
REX
1" CONDUIT FOR REX
EL
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
COLUMBIA VAMC, COLUMBIA, SC
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TG006
DETAILS
CJF
CJF JRQ
SCALE: NONE
B1
TYPICAL TR DOOR - BMS, CARD READER/ KEYPAD, ELEC
STRIKE, REX
SCALE: NONE
F3
TYPICAL DOME CAMERA DETAIL
SCALE: NONE
D6
TYPICAL TR SECURITY LAYOUT
SCALE: NONE
B6
TYPICAL SECURITY CAMERA SYSTEM DIAGRAM
SCALE: NONE
F6
ZONE PDU DISTRIBUTION DIAGRAM
SCALE: 12" = 1'-0"
F1
TYPICAL JUNCTION BOX ROUGH-IN DETAIL
SCALE: 12" = 1'-0"
D1
EXISTING OUTLET TRANSITION TO NEW OUTLET
PHASING DETAIL
SCALE: 12" = 1'-0"
B3
DOUBLE DOOR - DUAL HSS-CR
REVISION #1 06/16/2023
789 SF / 73.3 m²
ENGINEERING
SHOP
RCC102R
252 SF / 23.5 m²
ENGINEERING
OFF
RCC101R
TN430
F1
T3
T3
WP
T3
(TYP.)
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
FULLY SPRINKLERED TNBT25.1
BT25 OVERALL PLAN - FIRST
FLOOR
CJF
CJF JRQ
BT25
SCALE: 1/8" = 1'-0"
F1
BT25 OVERALL PLAN - FIRST FLOOR
KEYNOTES
1. PROVIDE (1) 2" CONDUIT FOR OUTSIDE PLANT FIBER ENTRANCE PATHWAY
FROM HANDHOLE TO BUILDING TELECOM ROOM
2. PROVIDE DEDICATED 1" CONDUIT FROM EACH OUTLET BACK BOX TO WALL
MOUNTED TELECOMMUNICATIONS ENCLOSURE FOR HORIZONTAL
CABLING PATHWAY. DO NOT "DAISY CHAIN" OUTLETS BACK BOXES.
3. PROVIDE SSTV CAMERAS WITH CAT 6A TO SM FIBER MEDIA CONVERTERS
FOR SSTV FIBER CONNECTION TO B100 DATA CENTER.
REVISION #1 06/16/2023
252 SF / 23.5 m²
ENGINEERING
OFF
RCC101R
TN430
W C
A B
F4
T3
WP
T3
T3
PW01
WCAB16
FPP48
CPP WM1U
PDU
UPS2U
SM02
D02
PBB
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
FULLY SPRINKLERED TN430
BT25 ENLARGED PLANS AND
ELEVATIONS
CJF
CJF JRQ
BT25
W135 EQUIPMENT SCHEDULE
EQUIP TYPE DESCRIPTION
PBB TELECOM PRIMARY BONDING BUSBAR.
PW01 3/4" THICK, FIRE RATED, 3/4" X 4' X 8' AC GRADE PLYWOOD.
TELECOM OUTLET SCHEDULE - FIRST FLOOR
OUTLET TYPE LOCATION NETWORK_ID DESCRIPTION
IDF/TR ROOM
NAME AND
NUMBER CABLE_U_1
T3 RCC 101R UNCLASSIFIED (3) CAT 6A UTP CABLES FOR UNCLASSIFIED NETWORK RCC 101R 9
WP RCC 101R UNCLASSIFIED (1) CAT 6A UTP CABLES FOR UNCLASSIFIED NETWORK RCC 101R 1
OUTLET TOTAL: 4 10
TR EQUIPMENT RACK SCHEDULE
RACK_ID
EQUIPMENT
DESIGNATION NETWORK DESCRIPTION RACK SPACES
COPPER
PORTS
FIBER
STRANDS
RCC101R WCAB16 UNCLASSIFIED WALL MOUNT CABINET - 16 RU SWING-OUT, W/ FANS, INTERNAL GROUND BUSBAR, HINGED AND LOCKABLE TRANSPARENT FRONT DOOR, SWING-OUT FRONT SECTION WITH VENTED REAR SECTION FIXED TO THE WALL, FULL HT FRONT AND REAL VERT. WIRE MGMT BOTH SIDES, SURGE PROTECTED 6 OUTLET (MIN.) VERTICAL POWER STRIP. CABINET MUST ADHERE TO SEISMIC REQUIREMENTS IN ACCORDANCE WITH ASCE 7-05 CHAPTER 13.
RCC101R FPP48 UNCLASSIFIED FIBER PATCH PANEL - 1U OPTICAL FIBER ENCLOSURE W/ (2) 24 STR ADAPTER PLATES. 1 0 48
RCC101R CPP UNCLASSIFIED CAT 6A ANGLED HIGH DENSITY PATCH PANEL, 48-PORT, 1U, ACCEPTS SHIELDED, UTP, AND FIBER CASSETTES. 1 48 0
RCC101R UPS2U UNCLASSIFIED 120V, 15A, 5-15P, SINGLE PHASE, UNINTERRUPTED POWER SUPPLY - 2U RACK MOUNTED 2
RCC101R WM1U UNCLASSIFIED WIRE MANAGEMENT - 1U HORIZONTAL 1
RCC101R PDU UNCLASSIFIED RACK MOUNT PDU. L5-20 INPUT. NEMA 5-15 OUTPUT. 1 RU 1
RCC101R PDU UNCLASSIFIED RACK MOUNT PDU. L5-20 INPUT. NEMA 5-15 OUTPUT. 1 RU 1
RCC101R WM1U UNCLASSIFIED WIRE MANAGEMENT - 1U HORIZONTAL 1
SCALE: 1/2" = 1'-0"
F1
ENGINEERING OFF RCC101R ENLARGED PLAN
SCALE: 3/4" = 1'-0"
F4
ENGINEERING OFF RCC101R RACK ELEVATION
KEYNOTES
1. PROVIDE (1) 2" CONDUIT FOR OUTSIDE PLANT FIBER ENTRANCE PATHWAY
FROM HANDHOLE TO BUILDING TELECOM ROOM.
2. PROVIDE SEISMIC BRACING FOR WALL MOUNTED CABINET.
3. SEE SCHEDULE ON SHEET TG005 - DETAILS FOR SIZING OF
TELECOMMUNICATIONS BONDING CONDUCTORS.
4. PROVIDE DEDICATED 1" CONDUIT FROM EACH OUTLET BACK BOX TO WALL
MOUNTED TELECOMMUNICATIONS ENCLOSURE FOR HORIZONTAL
CABLING PATHWAY. DO NOT "DAISY CHAIN" OUTLETS BACK BOXES.
5. THE CONTRACTOR SHALL PROVIDE A SURFACE MOUNTED BALANCED
MAGNETIC SWITCH DOOR CONTACT WITHIN THE TELECOM CABINET TO
MONITOR THE POSITION OF THE DOOR. THE DOOR POSITION SWITCH
SHALL BE CABLED TO B20 WITH 18 GAUGE CABLE PER MANUFACTURERS
RECOMMENDATIONS. REFER TO B20 PLANS FOR LOCATION OF EXISTING
ACCESS CONTROL PANEL. COORDINATE WITH VA SECURITY INTEGRATOR
FOR PROGRAMMING.