S02 - Attachment 12 - EHRM Columbia VAHCS Addendum 001.pdf

PDF 754 KB Posted

Attached to
EHRM Infrastructure Upgrades Construction - Columbia, SC VAMC Federal contract opportunity
Solicitation number
36C77623R0096
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document package includes construction documents and addendum for infrastructure upgrades at the Columbia, South Carolina VA Medical Center. The project involves upgrading the fiber optic and copper cabling backbone between buildings and to the main data center, as well as installing security cameras and access control systems at several buildings. Buildings to receive fiber connections, security cameras, and access control include the main hospital, outpatient clinic, engineering buildings, and community living center. The work requires installing new fiber and copper cabling in conduits and cable trays, as well as mounting network equipment racks, switches, patch panels, UPSes, and PDUs. Media converters will connect security cameras to the fiber network. Access control devices like card readers, locks, and door contacts will integrate with the existing system.

View the file

Other files for this federal contract opportunity

Other files attached to EHRM Infrastructure Upgrades Construction - Columbia, SC VAMC, newest first.
File Type Posted
36C77623R0096 0003 - Extension and RFI Answers - Columbia.pdf PDF
36C77623R0096 0002 - Columbia EHRM - Site Visit Sign-In and Risk Assess.pdf PDF
544 20 107 Columbia EHRM Infrastructure Risk Assessment.pdf PDF
36C77623R0096 0001 - Columbia EHRM - Extend RFI Deadline.pdf PDF
Columbia VA EHRM Site Visit Sign-In Sheet.pdf PDF
S02 - Attachment 13 - Limitations on Subcontracting - Construction.pdf PDF
S02 - Attachment 8 - Columbia EHRM Fire Drawing Set 6 of 9.pdf PDF
S02 - Attachment 1 - Columbia EHRM Statement of Work 21Feb23.pdf PDF
S02 - Attachment 2 - Columbia EHRM Specifications - 21Feb23.pdf PDF
S02 - Attachment 4 - Columbia EHRM Civil Drawing Set 2 of 9.pdf PDF
S02 - Attachment 5 - Columbia EHRM Arch Drawing Set 3 of 9.pdf PDF
S02 - Attachment 7 - Columbia EHRM Arch Drawing Set 5 of 9.pdf PDF
S02 - Attachment 16 - Wage Rates - Richland 1.6.23.pdf PDF
S02 - Solicitation - 36C77623R0096 - RFP - Columbia EHRM.pdf PDF
S02 - Attachment 3 - Columbia EHRM General Drawing Set 1 of 9.pdf PDF
S02 - Attachment 6 - Columbia EHRM Arch Drawing Set 4 of 9.pdf PDF
S02 - Attachment 9 - Columbia EHRM Mechanical Drawing Set 7 of 9.pdf PDF
S02 - Attachment 10 - Columbia EHRM Electrical Drawing Set 8 of 9.pdf PDF
S02 - Attachment 14 - Contractor Safety - Environmental Form.pdf PDF
S02 - Attachment 11 - Columbia EHRM Telecom Drawing Set 9 of 9.pdf PDF
S02 - Attachment 15 - Site Visit Instructions.pdf PDF
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

703 Main Ave. SW

PO Box 1629 Hickory, NC 28603

Telephone: (828) 315-9962 Website: www.atriaxgroup.com

Atriax, PLLC, 703 Main Ave. SW (28603), PO Box 1629, Hickory, NC 28603, Phone: (828) 315-9962

INTEGRITY ● SERVICE ● EXCELLENCE

Addendum Number 001

To the Construction Documents for: EHRM Infrastructure Upgrades

VA Project Number: 544-20-107

Date: 16 June 2023

General:

The following changes, additions, or deletions shall be made to the following documents as indicated. All conditions not included below shall remain the same.

Item Number:

1. Drawing sheet TG006 - Added T25 to the list of buildings requiring fiber connection back to B100 Data Center. Added note to explain the fiber being used for the cameras is the same fiber being installed for the voice/data backbone between each building and the B100 Data center.

2. Drawing sheet TNBT25.1 - Added camera to monitor the TE. Added note to detail the camera connection requirement back to B100 Data center.

3. Drawing sheet TN430 - Added keynote to detail requirement for monitoring of the TE with door contact that runs back to B20 for connection to existing access control panel.

1" CONDUIT STUBBED INTO TOP OF

DOOR FRAME FOR BALANCED

MAGNETIC SWITCH (BMS)

MIN. 1" CONDUIT TO NEW

ACS/ IDS PANEL WITHIN

TR

6" X 6" SECURITY JUNCTION BOX FOR

SECURITY DOOR INTERFACE MODULE

SURFACE MOUNT JUNCTION BOX ON SECURE

SIDE OF DOOR 6" ABOVE FINISHED CEILING

OR 30" ABOVE DOOR FRAME WHEN NO

CEILING IS AVAILABLE. COORDINATE

LOCATION WITH MECHANICAL EQUIPMENT IN

AREA.

ACS

JUNCTION

BOX

1" CONDUIT TO CARD

READER/ KEYPAD (CR/KP)

JUNCTION BOX

RECESSED DOUBLE GANG

JUNCTION BOX WITH SINGLE

GANG MOUNTING RING FOR

CARD READER/ KEYPAD

(CR/KP) MOUNT AT 48 INCHES

A.F.F. UNLESS OTHERWISE

NOTED

BMS

CR/KP

EL

1" CONDUIT TO ELECTRIC

STRIKE (EL)

REX

1" CONDUIT FOR REX

PLEASE REFER TO

THE ARCHITECURAL

DOOR HARDWARE

SCHEDULE

MIN. 1" CONDUIT WITH CAT

6A CABLING FROM

CAMERA TO EXISTING

SSTV TELECOM ROOM

LOCATION

DOME CAMERA:

MOUNT CAMERA IN A POSITION

TO PREVENT GLARE FROM

OVERHEAD LIGHTING.

SSTV

FINISHED WALL

SURFACE MOUNTED

DEEP SINGLE GANG

JUNCTION BOX

SSTV

CEILING SLAB

C R

/K P

EL

B M

S

CR/KP

EL

BMS

CARD READER/ KEYPAD JUNCTION BOX WITH

MIN. 1" CONDUIT FROM ACS/IDS JUNCTION BOX

LOCATED ABOVE TR DOOR TO NEW PREMISE

CONTROL UNIT LOCATION.

SYMBOL LEGEND:

ELECTRONIC LOCK WITH MIN. 1" CONDUIT

FROM ACS/IDS JUNCTION BOX LOCATED ABOVE

TR DOOR TO NEW PREMISE CONTROL UNIT

LOCATION.

BALANCED MAGNETIC SWITCH W ITH MIN. 1"

CONDUIT FROM ACS/IDS JUNCTION BOX

LOCATED ABOVE TR DOOR TO NEW PREMISE

CONTROL UNIT LOCATION.

DOME STYLE SECURITY CAMERA.

R E

X

REX REQUEST TO EXIT DEVICE WITH MIN. 1"

CONDUIT FROM ACS/IDS JUNCTION BOX

LOCATED ABOVE TR DOOR TO NEW PREMISE

CONTROL UNIT LOCATION.

PCU

PCU PREMISE CONTROL UNIT FOR ACS/IDS SYSTEM

DEVICES. WILL REQUIRE DEDICATED 20A

CIRCUIT PROVIDED BY ELECTRICAL.

NEW TR

CR/KP

EL

BMS

REX

PCU

SW

EXISTING

TCP/IP

NETWORK

EQUIPMENT

RACKSW RACK MOUNTED SW ITCH FOR SECURITY

CPP RACK MOUNTED COPPER PATCH PANEL

CPP

X

NOTE: COORDINATE WITH LOCAL SECURITY CONTRACTOR

CPP

SW

X

VMS

X

EXISTING

TCP/IP

NETWORK

NEW DOME

STYLE CAMERA

CPP

SW

VMS

NEW CAT 6A

CABLING

EXISTING COPPER PATCH PANEL

EXISTING OWNER PROVIDED SSTV

SWITCH

EXISTING OWNER PROVIDED VIDEO

MANAGEMENT SYSTEM

EXISTING TR IN BULDINGS WITH

EXISTING CAMERA SWITCH

SYMBOL LEGENDNEW TR

EQUIPMENT

RACK

CPP

SW

X

VMS

X

EXISTING

TCP/IP

NETWORK

NEW DOME

STYLE CAMERA

NEW CAT 6A

CABLING

DATA CENTER B100 NEW TR IN BUILDINGS WITH NO EXISTING CAMERA

SWITCH (B5, B6, B8, B20, BT25, BT36, B105 AND VARO)

EQUIPMENT

RACK

SM OSP FIBER

10/100/1000 MEDIA

CONVERTER

FPP

10/100/1000 MEDIA

CONVERTER

CAT 6A CABLING

SM OS2 JUMPER

EQUIPMENT

RACK

FPP

SM OS2 JUMPER

FIBER INSTALLED AS PART OF THIS

PROJECT. SEE SHEET TG003

RACK/ ENCLOSURE

RACK MOUNTED UPS

ZONE

PDU

RACKED EQUIPMENT

RACKED EQUIPMENT

RACKED EQUIPMENT

POWER

SUPPLY 1

POWER

SUPPLY 2

LEG A

BUS B

RACK/ ENCLOSURE

RACK MOUNTED UPS

RACKED EQUIPMENT

RACKED EQUIPMENT

RACKED EQUIPMENT

POWER

SUPPLY 1

POWER

SUPPLY 2

LEG B

BUS A

NOTE:

RACKS/ ENCLOSURES WILL HAVE A/B

REDUNDANT L21-30 CIRCUITS FOR THE

PAIR OF NETW ORK RACK/ ENCLOSURES,

WITH A 30A ZONE PDU SERVING THE PAIR

AND A/B REDUNDANT 20A RACK PDU'S TO

DISTRIBUTE THE POWER IN EACH RACK

B SIDE

VERTICAL RACK

MOUNTED PDU

A SIDE

VERTICAL RACK

MOUNTED PDU

RACK/ ENCLOSURE

RACK MOUNTED UPS

RACKED EQUIPMENT

RACKED EQUIPMENT

RACKED EQUIPMENT

POWER

SUPPLY 1

POWER

SUPPLY 2

BUS B

BUS A

FOR TR'S WITH ONE NETW ORK RACK FOR TR'S WITH TWO NETWORK RACKS

NOTE:

RACK/ ENCLOSURE WILL HAVE

A/B REDUNDANT L21-20

CIRCUITS FOR THE NETWORK

RACK/ ENCLOSURE, WITH A/B

REDUNDANT 20A RACK PDU'S

TO DISTRIBUTE THE POWER IN

THE RACK

B SIDE

VERTICAL RACK

MOUNTED PDU

A SIDE

VERTICAL RACK

MOUNTED PDU

KEY

BUS A: COMMERCIAL POWER

BRANCH CIRCUIT

BUS B: GENERATOR POWER BRANCH

CIRCUIT (WHERE AVAILABLE)

LEG A/B: A AND B DISTRIBUTION LEGS

OF THE ZONE PDU

POWER SUPPLY 1/2: REDUNDANT

POWER SUPPLIES IN EACH PIECE OF

IT EQUIPMENT

MIN. 1" CONDUIT TO CABLE

TRAY OR NEAREST TELECOM

ROOM (TR)

4-11/16 INCHES SQUARE

BY 2-1/8 INCHES DEEP

JUNCTION BOX

COMPRESSION TYPE

STEEL CONNECTOR

DOUBLE GANG JUNCTION BOX

REDUCTION RING FOR SINGLE

GANG FACEPLATE

PULL STRING

SINGLE GANG

FACEPLATE

PULL STRING TIED TO

CABLETRAY

NOTE:

THIS DETAIL IS ONLY FOR JUNCTION

BOX ROUGH-IN INFORMATION

SEE TELECOM FLOOR PLAN, OUTLET

TYPE SCHEDULE AND FACEPLATE

DETAILS FOR OUTLET TYPES,

CABLING AND FACEPLATE

INFORMATION

DESIGN OUTLET BOX FOR RECESS

MOUNTING WITH THE FACEPLATE

FLUSH WITH THE WALL SURFACE, AT

THE SAME HEIGHT AS THE

ELECTRICAL OUTLETS

EXISTING

OUTLET

TYPICAL

OFFICE

EXISTING

CONDUIT

WITHIN WALL

CORRIDOR

NEW CABLE

TRAY

EXISTING

TROUGH

EXISTING

OUTLET

TYPICAL

OFFICE

EXISTING

CONDUIT

WITHIN WALL

CORRIDOR

NEW CONDUIT

EXISTING DATA

CABLE THROUGH

CEILING TILE

(THIS CABLE IS

WITHIN SPACE

AND NOT WITHIN

WALL)

EXISTING

OUTLET WITH

NEW CAT 6A

CABLE

TYPICAL

OFFICE

EXISTING

CONDUIT

WITHIN WALL

CORRIDOR

NEW CABLE

TRAY

CEILING CEILING CEILING

EXISTING

TROUGH

RETERMINATE

CABLING AFTER

REMOVING FROM

EXISTING

OUTLET

NEW CAT 6A

CABLING TO

EXISTING

OUTLET

DEMO OF

EXISTING

TROUGH

NEW CONDUIT

CONDUIT

CONNECTOR

STEP 1:

• CONTRACTOR TO IDENTIFY EXISTING

CONDUIT RUN FROM EACH OUTLET

STEP 2:

• REMOVE EXISTING CABLE FROM EXISTING CONDUIT

(BACK TO NEAREST PULL POINT/CABLE TROUGH

• CUT EXISTING CONDUIT ABOVE CEILING

• RE-ROUTE EXISTING CABLE THROUGH FIRE

PROTECTION GROMMET IN CEILING TILE

STEP 3:

• CONNECT EXISTING CONDUIT TO NEW CONDUIT

• INSTALL NEW CABLE THROUGH CONDUIT

• DEMOLISH OLD UNUSED PATHWAY

• REPLACE CEILING TILE

1" CONDUIT STUBBED INTO TOP OF

DOOR FRAME FOR BALANCED

MAGNETIC SWITCH (BMS)

MIN. 1" CONDUIT TO NEW ACS/

IDS PANEL WITHIN TR

6" X 6" SECURITY JUNCTION BOX FOR SECURITY DOOR

INTERFACE MODULE SURFACE MOUNT JUNCTION BOX

ON SECURE SIDE OF DOOR 6" ABOVE FINISHED CEILING

OR 30" ABOVE DOOR FRAME WHEN NO CEILING IS

AVAILABLE. COORDINATE LOCATION WITH MECHANICAL

EQUIPMENT IN AREA.

ACS/IDS

ACCESSIBLE CEILING

BALANCED

MAGNETIC SW ITCH

(BMS) STUB 1"

CONDUIT INTO TOP

OF DOOR FRAME

RECESSED DOUBLE GANG

JUNCTION BOX WITH SINGLE

GANG MOUNTING RING FOR

CARD READER (CR, CR/KP)

MOUNT AT 48 INCHES A.F.F.

UNLESS OTHERWISE NOTED

1" CONDUIT TO CARD

READER (CR, CR/KP)

JUNCTION BOX

BMS BMS

CR/KP

1" CONDUIT TO

ELECTRIC

STRIKE (EL)

REX

1" CONDUIT FOR REX

EL

Location

Issue Date

Specialized Engineering Solutions

1300 Baxter Street, Suite 355

Charlotte, NC 28204

544-20-107PROJECT # 544-20-107

EHRM INFRASTRUCTURE UPGRADES

www.atriaxgroup.com

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

COLUMBIA VAMC, COLUMBIA, SC

VA FORM 08 - 6231

A

F ile

P a th

/1

/2

:3

:0

P M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TG006

DETAILS

CJF

CJF JRQ

SCALE: NONE

B1

TYPICAL TR DOOR - BMS, CARD READER/ KEYPAD, ELEC

STRIKE, REX

SCALE: NONE

F3

TYPICAL DOME CAMERA DETAIL

SCALE: NONE

D6

TYPICAL TR SECURITY LAYOUT

SCALE: NONE

B6

TYPICAL SECURITY CAMERA SYSTEM DIAGRAM

SCALE: NONE

F6

ZONE PDU DISTRIBUTION DIAGRAM

SCALE: 12" = 1'-0"

F1

TYPICAL JUNCTION BOX ROUGH-IN DETAIL

SCALE: 12" = 1'-0"

D1

EXISTING OUTLET TRANSITION TO NEW OUTLET

PHASING DETAIL

SCALE: 12" = 1'-0"

B3

DOUBLE DOOR - DUAL HSS-CR

REVISION #1 06/16/2023

789 SF / 73.3 m²

ENGINEERING

SHOP

RCC102R

252 SF / 23.5 m²

ENGINEERING

OFF

RCC101R

TN430

F1

T3

T3

WP

T3

(TYP.)

Location

Issue Date

Specialized Engineering Solutions

1300 Baxter Street, Suite 355

Charlotte, NC 28204

544-20-107PROJECT # 544-20-107

EHRM INFRASTRUCTURE UPGRADES

www.atriaxgroup.com

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC

VA FORM 08 - 6231

A

F ile

P a th

/1

/2

:3

:0

P M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

FULLY SPRINKLERED TNBT25.1

BT25 OVERALL PLAN - FIRST

FLOOR

CJF

CJF JRQ

BT25

SCALE: 1/8" = 1'-0"

F1

BT25 OVERALL PLAN - FIRST FLOOR

KEYNOTES

1. PROVIDE (1) 2" CONDUIT FOR OUTSIDE PLANT FIBER ENTRANCE PATHWAY

FROM HANDHOLE TO BUILDING TELECOM ROOM

2. PROVIDE DEDICATED 1" CONDUIT FROM EACH OUTLET BACK BOX TO WALL

MOUNTED TELECOMMUNICATIONS ENCLOSURE FOR HORIZONTAL

CABLING PATHWAY. DO NOT "DAISY CHAIN" OUTLETS BACK BOXES.

3. PROVIDE SSTV CAMERAS WITH CAT 6A TO SM FIBER MEDIA CONVERTERS

FOR SSTV FIBER CONNECTION TO B100 DATA CENTER.

REVISION #1 06/16/2023

252 SF / 23.5 m²

ENGINEERING

OFF

RCC101R

TN430

W C

A B

F4

T3

WP

T3

T3

PW01

WCAB16

FPP48

CPP WM1U

PDU

UPS2U

SM02

D02

PBB

Location

Issue Date

Specialized Engineering Solutions

1300 Baxter Street, Suite 355

Charlotte, NC 28204

544-20-107PROJECT # 544-20-107

EHRM INFRASTRUCTURE UPGRADES

www.atriaxgroup.com

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC

VA FORM 08 - 6231

A

F ile

P a th

/1

/2

:3

:0

P M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

FULLY SPRINKLERED TN430

BT25 ENLARGED PLANS AND

ELEVATIONS

CJF

CJF JRQ

BT25

W135 EQUIPMENT SCHEDULE

EQUIP TYPE DESCRIPTION

PBB TELECOM PRIMARY BONDING BUSBAR.

PW01 3/4" THICK, FIRE RATED, 3/4" X 4' X 8' AC GRADE PLYWOOD.

TELECOM OUTLET SCHEDULE - FIRST FLOOR

OUTLET TYPE LOCATION NETWORK_ID DESCRIPTION

IDF/TR ROOM

NAME AND

NUMBER CABLE_U_1

T3 RCC 101R UNCLASSIFIED (3) CAT 6A UTP CABLES FOR UNCLASSIFIED NETWORK RCC 101R 9

WP RCC 101R UNCLASSIFIED (1) CAT 6A UTP CABLES FOR UNCLASSIFIED NETWORK RCC 101R 1

OUTLET TOTAL: 4 10

TR EQUIPMENT RACK SCHEDULE

RACK_ID

EQUIPMENT

DESIGNATION NETWORK DESCRIPTION RACK SPACES

COPPER

PORTS

FIBER

STRANDS

RCC101R WCAB16 UNCLASSIFIED WALL MOUNT CABINET - 16 RU SWING-OUT, W/ FANS, INTERNAL GROUND BUSBAR, HINGED AND LOCKABLE TRANSPARENT FRONT DOOR, SWING-OUT FRONT SECTION WITH VENTED REAR SECTION FIXED TO THE WALL, FULL HT FRONT AND REAL VERT. WIRE MGMT BOTH SIDES, SURGE PROTECTED 6 OUTLET (MIN.) VERTICAL POWER STRIP. CABINET MUST ADHERE TO SEISMIC REQUIREMENTS IN ACCORDANCE WITH ASCE 7-05 CHAPTER 13.

RCC101R FPP48 UNCLASSIFIED FIBER PATCH PANEL - 1U OPTICAL FIBER ENCLOSURE W/ (2) 24 STR ADAPTER PLATES. 1 0 48

RCC101R CPP UNCLASSIFIED CAT 6A ANGLED HIGH DENSITY PATCH PANEL, 48-PORT, 1U, ACCEPTS SHIELDED, UTP, AND FIBER CASSETTES. 1 48 0

RCC101R UPS2U UNCLASSIFIED 120V, 15A, 5-15P, SINGLE PHASE, UNINTERRUPTED POWER SUPPLY - 2U RACK MOUNTED 2

RCC101R WM1U UNCLASSIFIED WIRE MANAGEMENT - 1U HORIZONTAL 1

RCC101R PDU UNCLASSIFIED RACK MOUNT PDU. L5-20 INPUT. NEMA 5-15 OUTPUT. 1 RU 1

RCC101R PDU UNCLASSIFIED RACK MOUNT PDU. L5-20 INPUT. NEMA 5-15 OUTPUT. 1 RU 1

RCC101R WM1U UNCLASSIFIED WIRE MANAGEMENT - 1U HORIZONTAL 1

SCALE: 1/2" = 1'-0"

F1

ENGINEERING OFF RCC101R ENLARGED PLAN

SCALE: 3/4" = 1'-0"

F4

ENGINEERING OFF RCC101R RACK ELEVATION

KEYNOTES

1. PROVIDE (1) 2" CONDUIT FOR OUTSIDE PLANT FIBER ENTRANCE PATHWAY

FROM HANDHOLE TO BUILDING TELECOM ROOM.

2. PROVIDE SEISMIC BRACING FOR WALL MOUNTED CABINET.

3. SEE SCHEDULE ON SHEET TG005 - DETAILS FOR SIZING OF

TELECOMMUNICATIONS BONDING CONDUCTORS.

4. PROVIDE DEDICATED 1" CONDUIT FROM EACH OUTLET BACK BOX TO WALL

MOUNTED TELECOMMUNICATIONS ENCLOSURE FOR HORIZONTAL

CABLING PATHWAY. DO NOT "DAISY CHAIN" OUTLETS BACK BOXES.

5. THE CONTRACTOR SHALL PROVIDE A SURFACE MOUNTED BALANCED

MAGNETIC SWITCH DOOR CONTACT WITHIN THE TELECOM CABINET TO

MONITOR THE POSITION OF THE DOOR. THE DOOR POSITION SWITCH

SHALL BE CABLED TO B20 WITH 18 GAUGE CABLE PER MANUFACTURERS

RECOMMENDATIONS. REFER TO B20 PLANS FOR LOCATION OF EXISTING

ACCESS CONTROL PANEL. COORDINATE WITH VA SECURITY INTEGRATOR

FOR PROGRAMMING.

REVISION #1 06/16/2023

Cover Sheet Addendum 001
TG006
TNBT25.1