This file is an attachment to a solicitation for the EHRM Infrastructure Upgrades Construction project at the Columbia, South Carolina VA Medical Center. The solicitation number is 36C77623R0096 and is being issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The attachment contains drawing set number 9 of 9 with plans related to the telecommunications infrastructure for the project. Offerors will need to review all 9 drawing sets to understand the full scope of upgrades required, which include construction and installation of a new telecommunications system at the medical center to support the Electronic Health Record Modernization initiative. Proposals are due by the date specified on the first page of the solicitation document.
View the file
Other files for this federal contract opportunity
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CEILING MOUNTED DATA
OUTLET
SYMBOL DESCRIPTION
TELECOM LEGEND
CEILING MOUNTED VOICE
OUTLET
CEILING MOUNTED
VOICE/DATA OUTLET
FLOOR BOX MOUNTED DATA
OUTLET
FLOOR BOX MOUNTED
VOICE OUTLET
FLOOR BOX MOUNTED
TELECOMMUNICATIONS
OUTLET
WALL - FLUSH MOUNTED
DATA OUTLET
WALL - FLUSH MOUNTED
VOICE OUTLET
WALL - FLUSH MOUNTED
TELECOMMUNICATIONS
OUTLET
OVERHEAD OR
UNDERFLOOR CABLE TRAY -
SIZE AS INDICATED ON
DRAWINGS
CABLE TRAY LADDER
RACK - TYPICALLY
MOUNTED 1FT ABOVE
TELECOM RACK/ CABINET
45RU, 7 FOOT HIGH, 30 INCH
DEPTH HIGH DENSITY
RACKING SYSTEM
J JUNCTION BOX
CENTERLINE
EHH
HH
EXISTING HANDHOLE
NEW HANDHOLE
EMH EXISTING MAINTENANCE
HOLE
MH NEW MANHOLE
CONDUIT OR CONDUIT
SLEEVE WITH BUSHINGS. 4
INCH DIAMETER U.O.N.
CONDUIT OR CONDUIT
SLEEVE 'UP' (WHITE)
CONDUIT OR CONDUIT
SLEEVE 'DOW N' (BLACK)
'#' NUMBER IDENTIFIER INDICATES CABLE COUNT AT
OUTLET. SEE TELECOM OUTLET SCHEDULES FOR
OUTLET AND NETWORK DEFINITIONS.
NOTE: COPPER CABLING NUMBERING MUST BE FOR A
SINGLE COPPER CABLE ONLY. WHERE FIBER CABLING
IS INDICATED CABLE COUNT MUST BE FOR A SINGLE 2-
STRAND FIBER CABLE.
EXAMPLE: 4 INDICATES TELECOMMUNICATIONS
OUTLET WITH (4) COPPER CABLES AT
OUTLET.
16RU SWING-OUT WALL
MOUNTED TELECOM
CABINET
WALL - SURFACE MOUNTED
TELECOMMUNICATIONS
OUTLET
SM
SYSTEMS FURNITURE
MOUNTED
TELECOMMUNICATIONS
OUTLET
CR/KP
EL
BMS
CARD READER/ KEYPAD
ELECTRIC STRIKE
BALANCED MAGNETIC
SWITCH
CEILING MOUNTED DOME
STYLE SECURITY CAMERA
REX REQUEST TO EXIT DEVICE
VERTICAL WIRE MANAGER
PCU
PREMISE CONTROL UNIT
FOR ACS/IDS SYSTEM
DEVICES. WILL REQUIRE
DEDICATED 20A CIRCUIT
PROVIDED BY ELECTRICAL.
SEIS
SEISMIC VIBRATION
DETECTION DEVICE
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
COLUMBIA VAMC, COLUMBIA, SC
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TG001
LEGEND, ABBREVIATIONS
AND GENERAL NOTES
CJF
CJF JRQ
TELECOM ABBREVIATIONS
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NETWORK INTERFACE CARD
NID NETWORK INTERFACE DEVICE
NM NANOMETER
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OEM ORIGINAL EQUIPMENT
MANUFACTURER
OS OPERATING SYSTEM
OSP OUTSIDE PLANT
P
PA PUBLIC ADDRESS
PABX PRIVATE AUTOMATIC BRANCH
EXCHANGE
PB PULL-BOX (SIZED PER BICSI TDMM)
PBB PRIMARY BONDING BACKBONE
PBX PRIVATE BRANCE EXCHANGE
PC PERSONAL COMPUTER
PCN PERSONAL COMMUNICATIONS
NETWORK
PCS PERSONAL COMMUNICATIONS
SYSTEMS
PED PEDESTAL
PIR PASSIVE INFRARED
PM POLE MOUNTED
PNL PANEL
POTS PLAIN OLD TELEPHONE SERVICE
PR PAIRS (NUMBERS OF PAIRS IN
COPPER CABLE)
PROX PROXIMITY
PVC POLYVINYL CHLORIDE
PWR POWER
R
RCDD REGISTERED COMMUNICATIONS
DISTRIBUTION DESIGNER
RCP REFLECTED CEILING PLAN
RECPT RECEPTACLE
RFI RADIO FREQUENCY INTERFACE
RGS RIGID GALVANIZED STEEL
RM ROOM
RMC RIGID METALLIC CONDUIT
S
SBB SECONDARY BONDING BACKBONE
SCTP SCREENED TWISTED PAIR
SMFO SINGLEMODE FIBER OPTIC
SP SERVICE PROVIDER
SPOE SECONDARY POINT OF ENTRY
SSTV SECURITY SURVEILLANCE VIDEO
SYSTEM
STD STANDARD
STP SHEILDED TWISTED PAIR
SW SWITCH
T
TBB TELECOMMUNICATIONS BONDING
BACKBONE
TBD TO BE DETERMINED
TCO TELECOMMUNICATIONS OUTLET
TCP/IP TRANSMISSION CONTROL
PROTOCOL W/ INTERNET
PROTOCOL
TDMM TELECOMMUNICATIONS
DISTRIBUTION METHODS MANUAL
TEL TELEPHONE
TELCO TELEPHONE COMPANY
TELECOM TELECOMMUNICATIONS
TEMP TEMPERATURE
TGB TELECOMMUNICATIONS GROUND
BUS BAR
TIA TELECOMMUNICATIONS INDUSTRY
ASSOCIATION
TR TELECOMMUNICATIONS ROOM
TV TELEVISION
TYP TYPICAL
U
UC UNDER COUNTER
UG UNDERGROUND
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
V
V VOLT
W
W WATT
WAN WIDE AREA NETWORK
WAP WIRELESS ACCESS POINT
WLAN WIRELESS LOCAL AREA NETWORK
WP WEATHERPROOF
X
X,(X) EXISTING - TO BE DEMOLISHED
TELECOM ABBREVIATIONS
A
AC ABOVE COUNTER
ADA AMERICANS WITH DISABILITIES ACT
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ALT ALTERNATE
AMP AMPERE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
ARCH ARCHITECT
ATR ALL THREAD ROD
AV AUDIO VISUAL
AWG AMERICAN WIRE GUAGE
B
BATT BATTERY
BDA BI-DIRECTIONAL ANTENNA
BFC BELOW FINISHED CEILING
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
BICSI BUILDING INDUSTRY CONSULTING
SERVICES INTERNATIONAL
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C
C CONDUIT
CAB CABINET
CAT CATEGORY
CATV COMMUNITY ANTENNA TV (CABLE
TV)
CF CONTRACTOR FURNISHED
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CFOI CONTRACTOR FURNISHED OWNER
INSTALLED
CL CENTER LINE
CLEC COMPETITIVE LOCAL EXCHANGE
CARRIER
CLG CEILING
CMP COMMUNICATIONS PLENUM CABLE
CMR COMMUNICATIONS RISER CABLE
CO CENTRAL OFFICE
COAX COAXIAL CABLE
CONT CONTINUE
COORD COORDINATE
CT CABLE TRAY
D
DAS DISTRIBUTED ANTENNA SYSTEM
DB DECIBEL
DEMARC DEMARCATION
DEMO DEMOLITION
DIA DIAMETER
DIAG DIAGRAM
DWG DRAWING
E
E, (E) EXISTING
E.G. FOR EXAMPLE
EIA ELECTRONICS INDUSTRY ALLIANCE
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EMH EXISTING MANHOLE
EMI ELECTROMAGNETIC
INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EP EXPLOSION PROOF
ERRCS EMERGENCY RESPONDER RADIO
COVERAGE SYSTEM
EXIST EXISTING
F
FACP FIRE ALARM CONTROL PANEL
FBO FURNISHED BY OTHERS
FCC FEDERAL COMMUNICATIONS
COMMISION
FO FIBER OPTIC
FR FIRE RATED
FT FOOT/ FEET
G
GB GIGABYTE
GBPS GIGABITS PER SECOND
GC GENERAL CONTRACTOR
GE GROUND EQUALIZER
GND GROUND
GUI GRAPHICAL USER INTERFACE
H
HC HORIZONTAL CROSS-CONNECT
HH HANDHOLE
HVAC HEATING, VENTILATION AND AIR
CONDITIONING
I
IAW IN ACCORDANCE WITH
ID INSIDE DIAMETER
IDF INTERMEDIATE DISTRIBUTION
FRAME
IEC INTERNATIONAL
ELECTROTECHNICAL COMMISION
IEEE INSTITUTE OF ELECTRICAL AND
ELECTRONICS ENGINEERS, INC.
IG ISOLATED GROUND
INT INTERCOM
IP INTERNET PROTOCOL
ISO INTERNATIONAL ORGANIZATION OF
STANDARDS
ISP INTERNET SERVICE PROVIDER
J
J-BOX,JB JUNCTION BOX
K
KM KILOMETER
KVA KILOVOLT AMPERES
KW KILOWATT
L
LAN LOCAL AREA NETWORK
LEC LOCAL EXCHANGE CARRIER
LED LIGHT EMITTING DIODE
LV LOW VOLTAGE
M
M METER
MAG MAGNETIC
MAN METROPOLITAN AREA NETWORK
MAX MAXIMUM
MB MEGABYTE
MBPS MEGABITS PER SECOND
MC MAIN CROSS-CONNECT
MDF MAIN DISTRIBUTION FRAME
MECH MECHANICAL
MFR MANUFACTURER
MH MANHOLE
MI MILE
MIN MINIMUM
MM MILLIMETER
MMFO MULTIMODE FIBER OPTIC
MPOE MAIN POINT OF ENTRY
N
NA NOT ACCEPTABLE
NEC NATIONAL ELECTRICAL CODE -
NFPA 70
TELECOM LEGEND NOTES
A SYMBOLS ORIENTATION DOES NOT IMPLY DEVICE OR
EQUIPMENT ORIENTATION. UNLESS NOTED AS SUCH.
SEE REFLECTED CEILING PLANS FOR ALL CEILING
MOUNTED DEVICE POSITIONS AND ORIENTATIONS
B SYMBOL SIZE DOES NOT IMPLY EQUIPMENT SIZE, UON.
C MOUNTING HEIGHT INDICATED IN LEGEND AND ON THE
DRAWINGS MUST BE THE DISTANCE MEASURED FROM
THE CENTER OF THE DEVICE TO THE FINISHED FLOOR.
D NOT ALL SYMBOLS ARE USED.
E REFER TO TYPICAL DETAILS ON TN500 SERIES
DRAWINGS.
TELECOM GENERAL NOTES
25 THE LOCATIONS AND ELEVATIONS OF TECHNOLOGY DEVICES SHOWN ON THESE DRAWINGS ARE
SCHEMATIC UNLESS ACTUAL DIMENSIONS ARE SHOWN ON THE DRAWINGS. REFER TO THE
ARCHITECTURAL PLANS AND OBTAIN THE APPROVAL OF THE OWNER'S REPRESENTATIVE FOR THE ACTUAL
LOCATIONS AND ELEVATIONS OF ALL DEVICES.
26 COMPLY WITH CURRENT ADA REQUIREMENTS FOR MOUNTING HEIGHTS OF ALL DEVICES AND EQUIPMENT.
27 PROVIDE SUPPORTS AND ANCHORING FOR CONDUIT, CABLE TRAYS, EQUIPMENT, AND OTHER
NON-STRUCTURAL ELEMENTS. SEE TECHNOLOGY SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS
INCLUDING INSTALLATION IN DESIGNATED SEISMIC AREAS.
28 ALL COMMUNICATIONS CONDUIT, CABLE TRAYS, LADDER RACKS AND EQUIPMENT RACKS SHALL BE
BONDED TO BUILDING GROUND SYSTEM PER NEC 250 AND ANSI/TIA-607-C
29 LABEL ALL CLOSETS, RACKS, FRAMES, CABINETS, TERMINATION BLOCKS, CABLES, TERMINATIONS, RACEWAYS, ETC. IN ACCORDANCE WITH ANSI/TIA-606-B AND OWNER'S CRITERIA
30 ALL COMMUNICATIONS RACEWAYS AND PATHWAYS SHALL MINIMIZE UNNECESSARY CABLE LENGTHS AND MAINTAIN INDUSTRY STANDARD LENGTH LIMITATIONS FOR HORIZONTAL CABLE DISTRIBUTION (E.G. CAT.6).
BASIC LINK CABLE LENGTH SHALL NOT EXCEED 295-FT (90M) FOR UTP CABLE, 200-FT (60M) FOR SERIES-6
COAXIAL CABLE.
31 PROVIDE PROTECTIVE BUSHINGS ON ALL COMMUNICATIONS CONDUITS AND WHERE CABLING ROUTES
THROUGH METAL STUDS.
32 PROVIDE LOW-VOLTAGE CABLES IN CONDUITS, CABLE TRAYS, WIREWAYS OR OTHER APPROVED CABLE MANAGEMENT DEVICES OR SYSTEMS. THE CONTRACTOR SHALL NOT INSTALL CABLING SUPPORTED BY CEILING SYSTEMS (CEILING TILE OR GRID, GYPSUM BOARD, LATH & PLASTER), HVAC DUCTS OR PIPES, LIGHTING FIXTURES, ELECTRICAL CONDUITS OR CABLES, PLUMBING/FIRE PROTECTION PIPES, OR ANY
OTHER DEVICES NOT INTENDED FOR THE SUPPORT OF LOW-VOLTAGE CABLING.
33 REUSABLE VELCRO TIES SHALL BE USED TO BUNDLE OR MANAGE CABLES. PLASTIC ZIP TIES SHALL NOT BE
PERMITTED.
34 SIZE AND ORIENTATION OF ALL TELECOM PULL-BOXES SHALL MEET OR EXCEED THE BICSI TDMM
REQUIREMENTS.
35 ALL OUTSIDE CONDUITS SHALL BE INSTALLED WITH NYLON PULL LINES HAVING 1200 LB MINIMUM TENSILE
STRENGTH AND NUMBERED FOOT MARKINGS.
36 THERE SHALL BE A MINIMUM OF ONE TELECOMMUNICATIONS ROOM (TR) PER FLOOR. ADDITIONAL ROOMS SHALL BE PROVIDED WHEN: A. THE FLOOR AREA TO BE SERVED EXCEEDS 1000msq (10,000 sqft); OR B. THE
HORIZONTAL DISTRIBUTION DISTANCE TO THE WORK AREA EXCEEDS 90M (295FT).
37 MINIMUM TR FLOOR SPACE REQUIREMENT SHALL BE 80sqft FOR A SINGLE RACK TR WITH AN ADDITIONAL 20sqft OF SPACE PER ADDTIONAL RACK.
38 ALL GROUND BARS, CONNECTIONS TO BUILDING STEEL AND CONNECTIONS TO PANELBOARDS SHALL BE
SUPPLIED AND INSTALLED BY ELECTRICAL TRADE.
39 EXISTING ELEVATOR COPPER TELEPHONE CIRCUITS TO REMAIN CONNECTED TO EXISTING TR'S.
40 ALL NEW RACKS AND CABINETS ARE TO RECEIVE SEISMIC BRACING EQUIVALENT TO CHATSWORTH PART
NUMBER 10562-001 OR BETTER.
41 OSP CABLING SHALL BE COILED A MINIMUM OF ONE TIME AROUND EACH MH/HH IT PASSES THROUGH.
42 THIS PROJECT REQUIRES THE CONTRACTOR TO INSTALL TWO FULLY REDUNDANT AND GEOGRAPHICALLY DIVERSE FIBER FEEDS (A FEED AND B FEED) TO EACH TELECOM ROOM IN EACH BUILDING. THE SITE INFRASTRUCTURE HAS BEEN DESIGNED SUCH THAT THE A FEED AND THE B FEED FOR ANY INDIVIDUAL TELECOM ROOM SHALL NOT RUN IN THE SAME CONDUIT, OR IN THE SAME DUCTBANK, OR IN THE SAME
MANHOLE/HANDHOLE.
43 THIS PROJECT INCLUDES THE ONE FOR ONE REPLACEMENT OF THE EXISTING HORIZONTAL CATEGORY COPPER CABLING FROM THE TELECOM ROOMS TO THE WORK AREAS. DURING THE DESIGN SITE SURVEY, NOT ALL CABLING WAS VISUALLY ACCESSIBLE DUE TO THE FURNITURE OR SPACES BEING IN USE. THE CONTRACTOR SHALL ASSUME AN ADDITIONAL 15% (ABOVE AND BEYOND WHAT IS CURRENTLY SHOWN ON THE DRAWINGS.) FOR HORIZONTAL CABLING AND HORIZONTAL CABLING CONNECTIONS (FACEPLATES, JACKS, PATCH PANEL PORTS, ETC.) THE CONTRACTOR IS ALSO REQUIRED TO PERFORM THEIR OWN SITE SURVEY SOMETIME AFTER AWARD BUT BEFORE INSTALLATION TO DETERMINE THE FINAL HORIZONTAL CABLING COUNTS FROM EACH TR FOR CABLES THAT ARE BEING REPLACED. BASED ON THE DESIGN SITE
SURVEY THE CONTRACTOR'S SURVEY IS ESTIMATED TO TAKE 4 DAYS OF AFTERHOURS SURVEY
(3PM-11PM) AND SHALL BE COORDINATED WITH THE COR.
44 CABLE TRAYS THAT PASS OVER WALL MOUNTED ELECTRICAL PANELS SHALL HAVE A 6" HORIZONTAL
OFFSET FROM WALL TO ALLOW FOR CONDUIT CLEARANCES.
45 DRAWINGS ARE BASED ON EXISTING BUILDING PLANS AND FIELD INVESTIGATIONS. CONTRACTOR SHALL VISIT THE EXISTING BUILDING AND ACQUAINT THEMSELVES WITH THE EXISTING CONDITIONS.
CONTRACTOR SHALL EXAMINE DRAWINGS TO AVOID CONFLICT.
46 PLYWOOD FOR TR WALLS IS SHOWN ON TELECOM AND DRAWINGS OF OTHER DISCIPLINES. THE PLYWOOD IN EACH DRAWING SET IS THE SAME AND IS NOT MEANT TO BE DUPLICATED BY THE CONTRACTOR.
47 IF CONTRACTOR ENCOUNTERS FIELD CONDITIONS THAT PREVENT INSTALLATION OF SCOPE SHOWN ON THE DRAWINGS, CONTRACTOR SHALL NOTIFY WILEY WILSON AND THE COR FOR ISSUE EXAMINATION AND
RESOLUTION.
48 A AND B BACKBONE CONDUITS ROUTING THROUGH CORRIDORS FROM BUILDING 100 SHALL BE
PHYSICALLY SEPARATED AS MUCH AS POSSIBLE.
49 ALL FLOOR, CEILING OR RATED WALL PENETRATIONS, PERMANENT AND TEMPORARY, SHALL BE FIRESTOPPED AT END OF WORK SHIFT PER SPECIFICATION 07 84 00, FIRESTOPPING. IF FLOOR, CEILING, OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED FOR ADDITIONAL WORK IN THAT AREA, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHALL BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD
THROUGH THE UNSEALED PENETRATION.
50 BLANK SPACE BETWEEN HORIZONTAL CABLE MANAGEMENT PANELS IN TR RACKS INDICATES SPACE
RESERVED FOR GFGI SWITCHES
51 CONTRACTOR TO PROVIDE HORIZONTAL BLANKING PANELS FOR ALL NEW RACKS AND CABINETS. A TOTAL OF (30) 1U BLANKING PANELS SHALL BE PROVIDED FOR EACH RACK. A TOTAL OF (45) 1RU BLANKING
PANELS SHALL BE PROVIDED FOR EACH NEW CABINET.
52 IN AREAS WHERE TELECOM WORK PENETRATES INTERIOR OR EXTERIOR WALLS, CEILING PANELS, GRID SYSTEM, GYPSUM CEILINGS AND/OR BULKHEADS, CONTRACTOR SHALL BE REQUIRED TO PATCH AND
REPAIR PENETRATIONS AS A RESULT OF THE WORK.
TELECOM GENERAL NOTES
1 INTENT OF THE DRAWINGS - THE DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL LOCATION OF
OUTLETS, RACEWAYS, AND EQUIPMENT. THE DRAWINGS DO NOT SHOW ALL NECESSARY OFFSETS, JUNCTION BOXES, CABLE TRAY TRANSITIONS, AND ADJUSTMENTS NECESSITATED BY COORDINATION WITH OTHER TRADES. PROVIDE ALL OFFSETS, RACEWAY COMPONENTS, ACCESSORIES, AND ADJUSTMENTS
NECESSITATED BY COORDINATION WITH OTHER TRADES.
2 COORDINATION WITH OTHER TRADES - EXAMINE AND REVIEW THE CONTRACT DOCUMENTS OF ALL DIVISIONS IN ORDER TO COORDINATE THE INSTALLATION WORK. USE DIMENSIONED ARCHITECTURAL AND
STRUCTURAL CONTRACT DRAWINGS TO VERIFY THE SPACE NECESSARY FOR LOCATING OUTLETS,
RACEWAYS, AND EXACT EQUIPMENT. USE FIELD MEASUREMENTS TO VERIFY DIMENSIONS WHERE AREAS ARE CONGESTED, AND EXACT LOCATION IS CRITICAL TO ASSURE PROPER INSTALLATION. COORDINATION SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO, VERIFYING THE LOCATION AND SIZE OF OPENINGS FOR PENETRATIONS IN FLOORS, WALLS, PARTITIONS, CEILINGS, AND ROOFS WITH THE INSTALLING TRADES;
ALLOCATION OF SPACE WITH OTHER TRADES INSTALLING WORK IN CHASES, SHAFTS, CEILING
INTERSTITIAL SPACES, AND EQUIPMENT SPACES; AND THE PHASING OF INSTALLATION WORK WITH THAT
OF OTHER TRADES.
3 WORKMANSHIP - INSTALL ALL WORK IN A WORKMANLIKE MANNER THAT PROVIDES A FIRST CLASS COMPLETED INSTALLATION. REMOVE, CORRECT AND REPLACE ANY WORK DEEMED UNACCEPTABLE AT
THE DISCRETION OF THE CONTRACTING OFFICER.
4 EQUIPMENT - INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS, THE SPECIFICATIONS, AND APPROVED SHOP DRAWINGS, PROVIDE SERVICE AND OPERATING CLEARANCES AROUND ALL SIDES OF EACH PIECE OF EQUIPMENT IN ACCORDANCE WITH REGULATORY REQUIREMENTS, MANUFACTURER'S PRINTED REQUIREMENTS AND RECOMMENDATIONS.
5 LARGE EQUIPMENT - SOME LARGE EQUIPMENT MAY REQUIRE DISASSEMBLY IN ORDER TO INSTALL IN THE BUILDING. SECURE THE SERVICES OF THE MANUFACTURER FOR REASSEMBLY WHERE NECESSARY TO
MAINTAIN WARRANTIES IN EFFECT.
6 ALL THE SYMBOLS IN THE LEGEND MAY NOT HAVE BEEN USED ON THE PLANS. SYMBOLS NOT LISTED IN
LEGEND ARE IDENTIFIED WHERE THEY OCCUR.
7 ANY PENETRATIONS THAT ARE REQUIRED THRU WALLS, FLOORS, OR CEILINGS SHALL MAINTAIN THE APPLICABLE RATING OF THE SURFACE BEING PENETRATED. (IE. FIRE RATED WALLS BEING PENETRATED REQUIRE CABLE/PATHWAY PENETRATION TO MATCH THE RATING OF THE WALL). THIS ALSO APPLIES TO
ALL TEMPORARY BARRIERS THAT MAY BE INSTALLED TO COMPLY WITH ICRA REQUIREMENTS.
8 PROVIDE PULL CORD HAVING AT LEAST A 90KG TENSILE STRENGTH IN ALL TELECOMMUNICATIONS INDOOR
CONDUITS.
9 UNLESS NOTED OTHERWISE, ALL CONDUITS SHALL BE INSTALLED CONCEALED UNDER FLOOR SLABS, ABOVE THE CEILING AND WITHIN THE FINISHED WALLS. ALL OUTLET BOXES SHALL BE INSTALLED FLUSH MOUNTED WITHIN FINISHED WALLS, CEILINGS OR FLOORS. SURFACE MOUNTED RACEWAY AND OUTLET BOXES SHALL NOT BE PERMITTED ON FINISHED WALLS, CEILINGS OR FLOORS. SURFACE MOUNTED RACEWAY AND OUTLET BOXES SHALL NOT BE PERMITTED ON FINISHED WALLS CEILINGS OR FLOORS.
EMBEDDED CONDUITS IN CAST-IN-PLACE CONCRETE (COLUMNS, BEAMS, FLOORS, WALLS OR ELEVATED
SLABS) ARE PERMITTED. REFER TO ELECTRICAL DETAILS FOR SPECIFIC REQUIREMENTS.
10 ALL TELECOMMUNICATIONS BONDING BACKBONE CONDUCTORS SHALL BE INSULATED, COPPER
CONDUCTOR. INSTALL TBB CONDUCTORS IN CONDUIT TO PROVIDE PROTECTION FROM PHYSICAL DAMAGE.
WHERE TBB CONDUCTORS ARE INSTALLED IN METALLIC CONDUIT, BOND BOTH END WITH A LISTED BONDING BUSHING. TERMINATE TBB AND GE CONDUCTORS ON PBB AND SBBs WITH A LISTED TWO-HOLE
COMPRESSION CONNECTOR.
11 TELECOMMUNICATIONS PULL BOXES SHALL BE IN STRAIGHT SECTIONS OF CONDUIT. DO NOT USE BOXES IN LIEU OF ELBOWS OR BENDS. NOT ALL TELECOMMUNICATIONS PULL BOXES ARE SHOWN. BEYOND THOSE SHOWN PROVIDE BOXES WHEN: 1. RACEWAY SECTION INCLUDES (2) TWO OR MORE 90 DEGREE BENDS OR
EQUIVALENT. 2. LENGTH OF RACEWAY SECTION IS GREATER THAN 30 METERS (100 FEET).
12 PROVIDE METALLIC CONDUIT WITH INSULATED BUSHINGS AT TERMINATIONS.
13 FACTORY ELBOWS OR FIELD BENDS SHALL HAVE AN INTERNAL RADIUS OF NOT LESS THAN (6) TIMES THE DIAMETER OF THE CONDUIT LESS THAN 2". INTERNAL RADIUS SHALL BE (10) TIMES THE DIAMETER FOR CONDUITS GREATER THAN 2". NO HARD 90 DEGREE TURNS PERMITTED IN ANY TELECOM CONDUIT.
14 CONDUITS HAVE BEEN SIZED BASED ON THE NEC, AS WELL AS ANSI/EIA/TIA 569-C. WHERE INSTALLATION VARIES, INCREASE CONDUITS SIZES ACCORDING TO MAXIMUM NUMBER OF CABLES BASED ON ALLOWABLE
FILL TABLE.
15 PROVIDE WARNING OR CAUTION LABELS ON ALL ENCLOSURES THAT USE OR CONTAIN FIBER OPTIC
CABLING.
16 LABEL ALL CABLES WITHIN 4" OF EACH TERMINATION. PROVIDE 12" LONG SERVICE LOOP AT THE WORK AREA END OF EACH HORIZONTAL CABLE. PROVIDE DUST COVERS ON ALL SPARE SYSTEM PATCH PANEL
JACKS.
17 FURNISH ADDITIONAL MATERIALS AS IDENTIFIED HEREIN AND WITHIN PROJECT SPECIFICATIONS.
18 PROVIDE D-RINGS EVERY 12" ALONG CABLE RUNS TO SUPPORT ENTERING AND EXITING WIRING FIELDS.
19 PROVIDE VELCRO CABLE TIES TO ATTACH CABLES TO WIRE MANAGEMENT, D-RINGS AND OTHER SUPPORT
MEANS.
20 PROVIDE TESTING OF ENTIRE STRUCTURED CABLING PLANT PER SPECIFICATIONS.
21 PROVIDE (2) NEW 4" CONDUITS TO BUILDINGS AND BETWEEN HANDHOLES UNLESS OTHERWISE NOTED FOR ALL BACKBONE FIBER CABLING. TYPICAL DEPTH OF CONDUIT DUCTBANK IS TO BE 36 INCHES BELOW GRADE. DUCTBANK SHALL BE CONCRETE ENCASED. REFER TO CIVIL DRAWINGS FOR EXACT DUCTBANK
COORDINATES AND ADDITIONAL DETAILS.
22 WHERE FLOOR BOXES ARE USED CONTRACTOR SHALL PROVIDE PATCH CORDS FOR VOICE AND DATA
THAT ARE OF APPROPRIATE LENGTH TO REACH THE WORKSTATION EQUIPMENT THEY SERVE.
23 DROP COUNT QUANTITIES ARE PROVIDED ON TN400 SERIES DRAWINGS TO ILLUSTRATE CROSS-CONNECT FIELD OR PATCH PANEL SIZING AND ARE NOT TO BE RELIED UPON FOR FINAL OUTLET QUANTITIES.
PROVIDE OUTLETS, JACKS, PATCH PANELS AND OTHER MATERIALS BASED ON QUANTITIES INDICATED ON
FLOOR PLANS AND SPECIFIED WITHIN THE CONTRACT DOCUMENTS
24 PROVIDE JACKETING, SHEATHING, ARMORING AND FILLING COMPOUNDS FOR OUTSIDE PLANT CABLES IN ACCORDANCE WITH THE CONTRACT DOCUMENT SPECIFICATION REQUIREMENTS. PROVIDE OUTSIDE PLANT CABLES SUITABLE FOR USE IN EXTERIOR APPLICATIONS AND IN ACCORDANCE WITH THE CABLES LISTING AND LABELING APPLICATIONS. UNLESS NOTED OTHERWISE, OUTSIDE PLANT APPLICATIONS SHALL BE CONSIDERED TO BE APPLICABLE FOR: CABLING INSTALLED BEYOND THE EXTERIOR WALLS OF A BUILDING, EITHER ABOVE OR BELOW GRADE, AND/OR BETWEEN BUILDING ENTRANCE PROTECTORS.
TELECOM SCOPE OF WORK RESPONSIBILITY MATRIX
DESCRIPTION CFCI GFGI NOTES
ACTIVE CABINET/ RACK MOUNTED NETWORK SWITCHES X
CABINET/ RACK MOUNTED PDU AND UPS (TELECOM ROOMS ONLY) X
COPPER AND FIBER PATCH PANELS AND ASSOCIATED TERMINATIONS X
COPPER PATCH CABLES IN THE TELECOM ROOMS (FROM PATCH PANEL TO SWITCH) X
DEDICATED TELECOMMUNICATIONS GROUNDING AND BONDING SYSTEM X
DEMO OF EXISTING PASSIVE STRUCTURED CABLING SYSTEM (PATHWAYS, CABLE,
TERMINATIONS, PATCH PANELS, OUTLETS, ETC.)
X
EXISTING COPPER PATCH CABLES AT THE WORK AREA OUTLETS (FROM OUTLET TO
WORKSTATION)
TO REMAIN
MODIFICATION OF EXISTING OSP FIBER CONNECTION TO THE BUILDING X
NEW BACKBONE INSIDE PLANT CABLING (FIBER AND COPPER) X
NEW BACKBONE INSIDE PLANT PATHWAYS X
NEW EQUIPMENT CABINETS AND RACKS IN THE TELECOM ROOMS AND MAIN SERVER ROOM X
NEW FIBER PATCH CABLES IN THE TELECOM ROOMS AND MAIN SERVER ROOM X
NEW HORIZONTAL INSIDE PLANT CABLING X
NEW HORIZONTAL INSIDE PLANT PATHWAYS X
TERMINATION AND TESTING OF ALL BACKBONE CABLING X
TERMINATION OF ALL HORIZONTAL CABLING X
TELECOM DEMOLITION NOTES
SECURITY GENERAL NOTES
1 THE SECURITY CONTRACTOR SHALL PROVIDE, INSTALL, DOCUMENT, AND TEST A FULLY INTEGRATED SECURITY SYSTEM FOR THE OWNER. THE INTEGRATED SECURITY SYSTEM SHALL INCLUDE A MICROPROCESSOR-BASED SECURITY
MANAGEMENT/CARD ACCESS/ALARM MONITORING SYSTEM, A CLOSED CIRCUIT TELEVISION SYSTEM, VARIOUS ASSOCIATED CONTROL AND/OR SUPPORT EQUIPMENT, AND ALL REQUIRED CABLING AND WIRING. SECURITY SYSTEM
CONDUCTORS SHALL NOT BE INSTALLED IN THE SAME CONDUIT AS "AC" POWER CONDUCTORS.
2 SECURITY SYSTEM CONDUCTORS SHALL BE PROVIDED BY CONTRACTOR, AS NOTED HEREIN. CONDUITS AND WALLBOXES FOR THE SECURITY SYSTEM WILL BE PROVIDED BY CONTRACTOR.
3 THE SECURITY CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING FINAL SECURITY EQUIPMENT LAYOUT AND ROUTING OF CONDUIT AS SHOWN ON THE PROJECT DRAWINGS. ANY COORDINATION CONFLICTS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE COR, WHO SHALL APPROVE ALL CHANGES PRIOR TO THE INITIATION OF WORK. THE SECURITY CONTRACTOR SHALL SUBMIT CONDUIT AND WIRE LAYOUT DRAWING SHOWING CIRCUIT NUMBERS , WIRING, ACTUATOR POWER SUPPLY(S) WITH BATTERY BACKUP, AND CONDUIT ROUTINGS FOR APPROVAL PRIOR TO THE INITIATION OF WORK.
4 ALL REQUIRED EQUIPMENT AND HARDWARE MAY NOT BE INDICATED ON DRAWINGS, DEPENDING ON THE SPECIFIC MANUFACTURER SUBMITTED FOR APPROVAL. CONTRACTOR SHALL PROVIDE ALL REQUIRED EQUIPMENT AND HARDWARE IN ORDER TO MEET THE INTENT OF DESIGN AND SHALL PROVIDE THE OWNER WITH A COMPLETE AND FULLY OPERATIONAL ELECTRONIC SECURITY SYSTEM. QUESTIONS REGARDING THE INTENT OF DESIGN SHALL BE
PROMPTLY BROUGHT TO THE ATTENTION OF THE COR.
5 CONDUCTORS SHALL NOT BE LESS THAN #18 AWG, UNLESS OTHERWISE INDICATED. EXCEPTIONS INCLUDE MANUFACTURER-PROVIDED LEADS AND INTERNAL EQUIPMENT WIRING.
6 SECURITY SYSTEM SIGNAL CONDUCTORS SHALL NOT, UNDER ANY CIRCUMSTANCE, BE INSTALLED IN THE SAME CONDUIT AS POWER CONDUCTORS.
7 WIRE FILL, CONDUCTORS, AND CONDUIT SHALL BE SIZED BY THE CONTRACTOR, EXCEPT WHERE SIZE IS INDICATED, AND SHALL BE INSTALLED ACCORDING TO THE NATIONAL ELECTRICAL CODE, AS WELL AS ALL STATE AND LOCAL CODES HAVING JURISDICTION. NUMBER OF CONDUCTORS REQUIRED MAY VARY BASED ON THE SPECIFIC MANUFACTURER'S EQUIPMENT SELECTED BY THE CONTRACTOR. MINIMUM CONDUIT SIZE SHALL BE 1/2 INCH.
8 ALL 120 VOLT INPUT POWER FOR POWER SUPPLIES AND OTHER SYSTEM COMPONENTS SHALL BE PROVIDED. THE SECURITY CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF SECURITY SYSTEM POWER REQUIREMENTS.
120 VOLT INPUT POWER FOR ALL ESS SHALL BE DEDICATED.
9 ALL SECURITY WIRING SHALL BE CONSISTENTLY COLOR-CODED AND TAGGED. COORDINATION OF EXACT WIRE CODING AND TAGGING IS MANDATORY. THE SECURITY CONTRACTOR IS DIRECTLY RESPONSIBLE FOR COORDINATING WIRING FROM EQUIPMENT HARDWARE MANUFACTURERS TERMINAL STRIPS TO THE FINAL CONNECTION POINTS OF EQUIPMENT WITHIN SCOPE OF THE PROJECT.
10 THE SECURITY CONTRACTOR SHALL PROVIDE ALL REQUIRED PROGRAMMING, AND SHALL COORDINATE WITH THE OWNER ALL HARDWARE AND SOFTWARE PROGRAMMING FEATURES WHICH DICTATE OR OTHERWISE INFLUENCE USER
OPERATION OR FUNCTIONALITY OF THE ELECTRONIC SECURITY SYSTEM.
11 REQUIREMENTS FOR CONDUCTORS AND CONDUITS SIZES AND QUANTITIES MAY VARY WITH THE SELECTION AND PLACEMENT OF SECURITY EQUIPMENT. CONDUCTORS AND CONDUIT SIZES AND QUANTITIES ARE SUGGESTIVE ONLY AND DO NOT NECESSARILY REPRESENT WHAT WILL OR SHOULD BE INSTALLED. GC SHALL BE RESPONSIBLE FOR PROVIDING ACTUAL CONDUCTOR AND CONDUIT SIZES AND QUANTITIES ON SHOP DRAWING SUBMITTAL. THE SECURITY CONTRACTOR SHALL COORDINATE WITH THE DIVISION 26 SUBCONTRACTOR, ALL CONDUIT SIZES, QUANTITIES, AND LOCATIONS, AS WELL AS ALL POWER SUPPLY AND EQUIPMENT LOCATIONS THAT NEED A CIRCUIT NOT SHOWN ON THE
PLANS.
12 THE SCOPE FOR INTRUSION DETECTION SYSTEM INCLUDES THE DATA CENTER AND ALL NEW TELECOM ROOMS. THE CONTRACTOR SHALL PROVIDE NEW INTRUSION DETECTION DEVICES AS DEPICTED ON THE DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR ALL EXPANSION BOARDS, SUB PANELS, INTERCONNECTIONS, POWER SUPPLIES, ETC NECESSARY TO CONNECT THE NEW DEVICES AS SHOWN TO THE EXISTING INTRUSION DETECTION SYSTEM
PANEL.
13 THE SCOPE FOR THE ACCESS CONTROL SYSTEM INCLUDES THE NEW DOORS TO THE DATA CENTER AS WELL AS EVERY DOOR TO THE NEW TELECOM ROOMS THROUGHOUT THE PROJECT. THE CONTRACTOR SHALL PROVIDE THE MOST CURRENT 2-DOOR ACCESS CONTROL SYSTEM CONTROL PANEL THAT TIES INTO THE EXISTING SITE ACCESS CONTROL SYSTEM. THE SITE CURRENTLY UTILIZES THE SOFTWARE HOUSE iSTAR ACCESS CONTROL SYSTEM. THE NEW 2-DOOR CONTROLLERS SHALL PROVIDE A MINIMUM OF 100MBPS CONNECTION TO THE DATA NETWORK. WITHIN EACH NEW TELECOM ROOM AND DATA CENTER THE CONTRACTOR SHALL PROVIDE A CONNECTION FROM THE NEW ACCESS SYSTEM CONTROLLER TO THE GFGI PROVIDED NETWORK SWITCH THAT IS LOCATED IN THE NEW TELECOM RACK.
1. REMOVE CABLING AND ASSOCIATED PATCH PANELS FROM EXISTING
TR'S AFTER NEW INFRASTRUCTURE IS INSTALLED AND
OPERATIONAL.
2. REMOVE ALL ABANDONED TELECOMMUNICATIONS CABLING FROM
EXISTING TR'S. EXISTING FIBER CABLE IS EXEMPT FROM THIS
REQUIREMENT.
3. IN AREAS TO BE RENOVATED FOR NEW TR'S, EXISTING WORK AREA
OUTLETS SHALL BE DEMOLISHED AND REMOVED. CABLING, JACKS
AND FACEPLATES SHALL BE REMOVED BY THE TELECOM
CONTRACTOR. PATHWAYS (CONDUIT, BOXES, ETC.) SHALL BE
REMOVED BY THE ELECTRICAL CONTRACTOR - SEE ELEC PLANS.
4. ALL OTHER EXISTING NON-TELECOM SYSTEMS TO REMAIN IN
EXISTING TR'S IAW TABLE BELOW.
5. REFER TO INSTALLATION/CONSTRUCTION PROCEDURES IN PROJECT
PHASING PLAN IN ARCHITECTURAL SET FOR ADDITIONAL DEMOLITION
DETAILS
DEMO AND REMOVEEXISTING HORIZONTAL COPPER TO W AO'S AND W AP'S
EQUIPMENT OR SUBSYSTEM DEMO OR TO
REMAIN
EXISTING HORIZONTAL COPPER PATCH PANELS TO W AO'S AND WAP'S
TO REMAIN
TO REMAIN
EXISTING TR DEMOLITION
EXISTING RACKS
EXISTING UPS IN REUSED TR'S
EXISTING DOOR SECURITY DEVICES AND CCTV CAMERA
EXISTING UPS
EXISTING BACKBONE FIBER
EXISTING PCU (FOR SECURITY INCLUDING CCTV)
DEMO AND REMOVE
TO REMAIN
DEMO AND REMOVE
EXISTING BACKBONE COPPER TO REMAIN
TO REMAIN
TO REMAIN
VA
N
#4
WATER METER
E
CB
CB
CBCB
B20
B8
B9
B9A
B6
B106
B120
B22
B133
BT36
B100
B100A
B103A
B103
B114
B5
B122
B21
BT25
B105
T1
T2
T7 T4
T71
T70
T69
T68
T67
T64
T65
T66
T63
T62
T61T60
T59
T58
T53
T52
T51
T50
T46
T47
T45
T43
T42
T41
T40
T39
T38
T36
T37 T33
T35
T22
T34 T21
T20
T19
T23
T25
T24
T29T26
T18
T27
T57
T28
T55
T56
VARO
T30
T31 T32
T54
T8T9
T10
T11
T12
T15
T13
T16
T17
T14
HH
HH
HH
MH
MH
MH
EMH
EMH
EMH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH HH
HH
HH
HH
HH
HH
HH
HH
HH HH
HH
HH
HH
HH
HH
HH
B7
2 2
2 2
19 23
T-28
EHH
MH
MH
T3
HH
T5T6
MH
HH
T44
T48
T49
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
COLUMBIA VAMC, COLUMBIA, SC
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TG002
OVERALL SITE PLAN
CJF
CJF JRQ
SCALE: 1 : 100
F1
OVERALL SITE PLAN
KEYNOTES
HH
NEW 48 INCH BY 48 INCH
BY 48 INCH HANDHOLE
SITE LEGEND
EHH
EMH
MH
EXISTING MAINTENANCE HOLE
EXISTING HANDHOLE
NEW 12FOOT BY 7FOOT BY 6FOOT
MAINTENANCE HOLE
(6) NEW 4" PVC CONDUIT
GENERAL NOTES
A. TYPICAL DEPTH OF DUCTBANK IS TO BE 36 INCHES BELOW GRADE.
B. PROVIDE (2) NEW 4 INCH CONDUITS FROM NEAREST MH/HH TO
BUILDINGS UNLESS OTHERWISE NOTED.
C. THIS PROJECT REQUIRES THE CONTRACTOR TO INSTALL TW O
FULLY REDUNDANT AND GEOGRAPHICALLY DIVERSE FIBER FEEDS
(A FEED AND B FEED) TO EACH TELECOM ROOM IN EACH BUILDING.
THE SITE INFRASTRUCTURE HAS BEEN DESIGNED SUCH THAT THE
A FEED AND THE B FEED FOR ANY INDIVIDUAL TELECOM ROOM
SHALL NOT RUN IN THE SAME CONDUIT, OR IN THE SAME
DUCTBANK, OR IN THE SAME MANHOLE/HANDHOLE.
D. OSP CABLING SHALL BE COILED A MINIMUM OF ONE TIME AROUND
EACH MH/HH IT PASSES THROUGH.
E. ALL DUCTBANK SHOW N IS TO BE CONCRETE ENCASED.
F. ALL DUCTBANKS SHALL HAVE 100% SPARE CAPACITY AFTER FIBER
CABLE INSTALLATION, I. E. 6-WAY DUCTBANK SHALL HAVE A
MINIMUM OF (3) EMPTY DUCTS, EACH WITH A PULL STRING; 4-W AY
DUCTBANK SHALL HAVE A MINIMUM OF (2) EMPTY DUCTS, EACH
WITH A PULL STRING, AND 2-WAY DUCTBANK SHALL HAVE ONE
(1) EMPTY DUCT WITH A PULL STRING.
B6 - CIRCUIT AT1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T28-T30-T32-T36-T40-T43-T44
TELECOM DUCT SEGMENT PATHWAY DESTINATION
TO
ORIGIN
FROM
B6 - CIRCUIT B T66-T65-T64-T63-T62-T61-T60-T58-T52-T50-T48-T46-T47
B100 LA108 (A)
B100 LA108 (B)
B7 - CIRCUIT A B100 LA108 (A)
B7 - CIRCUIT B B100 LA108 (B)
B8 - CIRCUIT A B100 LA108 (A)
B8 - CIRCUIT B B100 LA108 (B)
B9 - CIRCUIT A B100 LA108 (A)
B9 - CIRCUIT B B100 LA108 (B)
B20 - CIRCUIT AB100 LA108 (A)
B20 - CIRCUIT B B100 LA108 (B)
B21 - CIRCUIT AB100 LA108 (A)
B21 - CIRCUIT B B100 LA108 (B)
B105 - CIRCUIT AB100 LA108 (A)
B105 - CIRCUIT B B100 LA108 (B)
B122 - CIRCUIT AB100 LA108 (A)
B122 - CIRCUIT B B100 LA108 (B)
B133 - CIRCUIT AB100 LA108 (A)
B133 - CIRCUIT B B100 LA108 (B)
BT25 - CIRCUIT AB100 LA108 (A)
BT25 - CIRCUIT B B100 LA108 (B)
BT36 - CIRCUIT AB100 LA108 (A)
BT36 - CIRCUIT B B100 LA108 (B)
VARO - CIRCUIT AB100 LA108 (A)
VARO - CIRCUIT B B100 LA108 (B)
T1-T2-T3-T4
BUILDING OSP CABLE ROUTING
(4) NEW 4" PVC CONDUIT
(2) NEW 4" PVC CONDUIT
EXISTING CONDUIT TO BE REUSED
1. (6) NEW 4 INCH CONCRETE ENCASED DUCTBANK CONDUITS WITH
(3) PACKS OF 3-3" FABRIC MESH INNERDUCTS IN EACH DUCT
CONTAINING NEW FIBER CABLE(S).
2. (4) NEW 4 INCH CONCRETE ENCASED DUCTBANK CONDUITS WITH
(3) PACKS OF 3-3" FABRIC MESH INNERDUCTS IN EACH DUCT
CONTAINING NEW FIBER CABLE(S).
3. (2) NEW 4 INCH CONCRETE ENCASED DUCTBANK CONDUITS WITH
(3) PACKS OF 3-3" FABRIC MESH INNERDUCTS IN EACH DUCT
CONTAINING NEW FIBER CABLE(S).
4. EXISTING CONDUIT PATHWAY TO BE REUSED.
5. CORRIDOR PATHWAY LOCATIONS. CONDUITS TO BE INSTALLED
ABOVE CEILING THROUGH CORRIDORS. REFER TO DRAWING TN608
FOR CONDUIT SIZES AND QUANTITIES FOR EACH CORRIDOR
ROUTE.
T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T28-T30-T32-T36-T40-T43-T45-T48-T49
T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T28-T30-T32-T36-T37
T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T28-T30-T32-T36-T38-T39
T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T20-T22
T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T28-T30-T31
T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T24-T26
T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T57-T54-T53
T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T20-T21
T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T19
T1-T2-T5-T7-T8-T9-T10-T11-T12-T13-T14
T66-T65-T64-T63-T62-T61-T60-T58-T52-T51
T66-T65-T64-T63-T62-T61-T60-T58-T52-T50-T48-T45-T43-T42
T66-T65-T64-T63-T62-T61-T60-T58-T52-T50-T48-T45-T43-T41
T66-T65-T64-T63-T62-T61-T60-T58-T52-T50-T48-T45-T43-T40-T36-T33-T35
T66-T65-T64-T63-T62-T61-T60-T58-T54-T55-T56
T66-T65-T64-T63-T62-T61-T60-T58-T54-T57-T28-T29
T66-T65-T64-T63-T62-T61-T60-T58-T54-T57-T27-T23-T18-T15-T12-T11-T10-T9-T8-T7-T6
T66-T65-T64-T63-T62-T61-T60-T59
T66-T65-T64-T63-T62-T61-T60-T58-T52-T50-T48-T45-T43-T40-T36-T33-T34
T66-T65-T64-T63-T62-T61-T60-T58-T54-T57-T27-T24-T25
T66-T65-T64-T63-T62-T61-T60-T58-T54-T57-T27-T23-T18-T16-T17
24 SM OS2 CORR - A/B
STRAND
COUNT
SM = SINGLE MODE
MM = MULTIMODE
OS2 = SM FIBER TYPE
OM4 = MM FIBER TYPE
OSP = PATHWAY EXTERNAL TO
BUILDING
CORR = CORRIDOR PATHWAY
INTERNAL TO BUILDING
100A
103A
VARO
BUILDING 100
9A
T36
24 SM OS2 OSP - A
(3) 24 SM OS2 CORR - A
(3) 24 SM OS2 CORR - B
24 SM OS2 OSP - A
24 SM OS2 OSP - A
24 SM OS2 OSP-B
24 SM OS2 OSP - A
24 SM OS2 OSP-B
24 SM OS2 OSP - A
24 SM OS2 OSP-B
(3) 24 SM OS2 CORR - A
(3) 24 SM OS2 CORR - B
24 SM OS2 OSP-B
24 SM OS2 OSP-B
24 SM OS2 OSP
24 SM OS2 OSP-B
24 SM OS2 OSP - A
24 SM OS2 OSP-B
24 SM OS2 OSP - A
24 SM OS2 OSP-B
(3) 24 SM OS2 CORR - A
(3) 24 SM OS2 CORR - B
(2) 24 SM OS2 CORR - A
(2) 24 SM OS2 CORR - B
(1) 24 SM OS2 CORR - A
(1) 24 SM OS2 CORR - B
(4) 24 SM OS2 CORR - A
(4) 24 SM OS2 CORR - B
24 SM OS2 CORR - A
24 SM OS2 CORR - B
24 SM OS2 CORR - A
24 SM OS2 CORR - B
24 SM OS2 OSP - A
24 SM OS2 OSP-B
(2) 24 SM OS2 OSP - A
(2) 24 SM OS2 OSP-B
T25
24 SM OS2 OSP - A
24 SM OS2 OSP-B
24 SM OS2 OSP - A
24 SM OS2 OSP-B
A = PRIMARY BACKBONE CONNECTION
B = REDUNDANT BACKBONE CONNECTION
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
COLUMBIA VAMC, COLUMBIA, SC
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TG003
SITE OSP CONNECTIVITY
DIAGRAM
CJF
CJF JRQ
SCALE: NONE
F1
SITE OSP CONNECTIVITY DIAGRAM
GENERAL NOTES
A. THIS PROJECT REQUIRES THE CONTRACTOR TO INSTALL TW O
FULLY REDUNDANT AND GEOGRAPHICALLY DIVERSE FIBER FEEDS
(A FEED AND B FEED) TO EACH TELECOM ROOM IN EACH BUILDING.
THE SITE INFRASTRUCTURE HAS BEEN DESIGNED SUCH THAT THE
A FEED AND THE B FEED FOR ANY INDIVIDUAL TELECOM ROOM
SHALL NOT RUN IN THE SAME CONDUIT, OR IN THE SAME
DUCTBANK, OR IN THE SAME MANHOLE/HANDHOLE.
B. THE CONTRACTOR SHALL INSTALL THE FIBER FROM THE DATA
CENTER TO EACH TELECOM ROOM IN EACH BUILDING AS A
HOMERUN. THERE SHALL BE NO INTERMEDIATE CONNECTION
POINTS FOR ANY FIBER RUN BETW EEN THE DATA CENTER AND THE
END DESTINATION. IF THE CONTRACTOR, FOR ANY REASON,
REQUIRES A SPLICE MID-RUN IN THE FIBER, THEY MUST SUBMIT A
WRITTEN REQUEST TO DO SO FOR EACH INSTANCE.
C. THE CONTRACTOR IS REQUIRED TO LABEL THE FIBER PER THE
SPECIFICATIONS. FIBER SHALL BE LABELED ON EACH END AND
WITHIN EACH PULL POINT (MANHOLE/HANDHOLE). SEE NOTE 'D'
BELOW FOR ADDITIONAL DOCUMENTATION REQUIREMENTS.
D. THE CONTRACTOR IS REQUIRED TO LABEL ALL MANHOLES AND
HANDHOLES AS W ELL AS EACH SECTION OF DUCBANK AND EACH
DUCT WITHIN THE DUCTBANK. THE CONTRACTOR SHALL PROVIDE
AN EXCEL FILE TO THE COR AT THE END OF THE PROJECT STATING
FOR EACH FIBER WHAT THE SOURCE IS, W HAT THE DESTINATION
IS, WHAT MANHOLE/HANDHOLES IT RUNS THROUGH BETWEEN
SOURCE AND DESTINATION, AND W HAT DUCT THE CABLE IS
LOCATED IN WITHIN EACH DUCTBANK. THE CONTRACTOR SHALL
ALSO PROVIDE AS-BUILT BUTTERFLY DIAGRAMS TO THE VA WITH
BOTH GRAPHICAL DEPICTIONS AND PHOTOS OF THE AS-BUILT
CONDITION. BUTTERFLY DIAGRAMS ARE NOT REQUIRED TO HAVE
THE CABLES IDENTIFIED BUT SHALL HAVE ALL
MANHOLE/HANDHOLE, DUCTBANK, AND DUCT LABELS.
SLOPESLOPE
S L
O P
E S
L O
P E
OPENING
GROUND ROD
L E
N G
T H
OPENING
MANHOLE
FRAME AND COVER
RATED CONCRETE
COLLAR (AS REQUIRED
TO BRING COVER TO
GRADE LEVEL)
CABLE PULL RING
EARTH
OPENING
PVC SLEEVE FOR
GROUND ROD (TYP)
LONG COPPER CLAD
STEEL GROUND ROD (TYP)
SUMP REINFORCED CONCRETE
SIDE WALL DUCT ENTRANCE
DUCT TERMINATOR (TYP)
CABLE TRAY (TYP)
SLOPESLOPE
WIDTH
H E
IG
H
T
6'-0"
SLOPE
S L
O P
E
SLOPE
S L
O P
E
OPENING
GROUND ROD
L E
N G
T H
WIDTH
4'-0"
1" PVC SLEEVE FOR
GROUND ROD
3/4" x 10' LONG COPPER
CLAD STEEL GROUND ROD
SUMP REINFORCED CONCRETE
DUCT WINDOW
SIDE WALL DUCT ENTRANCE
DUCT TERMINATOR
CABLE PULL RING
CABLE RACK
SLOPESLOPE
OPENING
EARTH
NOTES: HANDHOLE OVERALL DIMENSION MUST BE A MINIMUM 4' X 4' X 4' (WxLxD), FULLY ENCLOSED EXCEPT FOR DRAINAGE AND CONSTRUCTED OF CONCRETE. HANDHOLE COVER MUST BE LABELED "COMMUNICATIONS" AND MUST BE LOCKABLE WITH A GSA
APPROVE PADLOCK.
NOTE:
1. ALL SCHEDULE 40 PVC DUCTS MUST BE ENCASED IN
CONCRETE.
2. ALL DUCTS STUBBED THROUGH MANHOLE / HAND HOLE
WALLS MUST BE TERMINATED AND SEALED VIA DUCT
TERMINATORS.
3. UNUSED DUCTS MUST BE STUBBED OUT AND CAPPED VIA
A SOLVENT WELDED CONDUIT CAP.
4. ORIENTATION OF MANHOLES / HAND HOLES MUST BE
COORDINATED WITH THE DUCTBANK APPROACH.
5. DEPTH OF DUCTBANKS ARE PROVIDED AS A MINIMUM
FOR GENERAL INFORMATION. REFER TO CIVIL PLANS FOR
PROFILES AND ACTUAL DUCT DEPTH.
6. DUCT ARRANGEMENTS IN THESE DETAILS ARE PROVIDED
FOR GENERAL INFORMATION. REFER TO DUCTBANK
SECTIONS FOR ACTUAL QUANTITIES AND
ARRANGEMENTS.
7. MANHOLE / HAND HOLE COVERS MUST BE H-20 RATED.
12"
MAGNETIC WARNING
TAPE (TYPICAL)
3' MINIMUM DEPTH
FINISHED SURFACE OR GRADE
6" SEPARATION
MINIMUM (TYPICAL)
3" SEPARATION
MINIMUM (TYPICAL)
3" SEPARATION
MINIMUM (TYPICAL)
4" SCHEDULE 40
PVC UON (TYPICAL)
BASE AND INTERMEDIATE
SPACERS HORIZONTALLY ALONG
LENGTH OF DUCTBANK.
3" MINIMUM
(TYPICAL ALL SIDES)
3000 PSI CONCRETE
T#
DUCTBANK SECTION KEY
CONDUIT PURPOSE:
T = TELECOM
SP = SPARE
T1 4"
T2 4"
T3 4"
T4 4"
T5 4"
SP
4"
DUCTBANK SECTION CONDUCTOR
IDENTIFICATION. SEE DUCTBANK
SECTION KEY BELOW .
NOTE: THIS DETAIL IS TYPICAL FOR ALL DUCTBANKS. REFER TO DUCTBANK SECTIONS FOR CONDUIT SIZES AND QUANTITIES
4"
CONDUIT TRADE SIZE
CONDUIT NUMBER
#4 HOOP REBAR
(STIRRUPS) 18" ON CENTER
#4 LONGITUDINAL REBAR
(TYPICAL, EACH CORNER)
CRUSHED STONE AS
NEEDED FOR LEVELING
3" SEPARATION
MINIMUM (TYPICAL)
A. LEVEL SURFACE.
DOUBLE SLOPE TO BET NOT LESS THAN 1:300 DOW N TOWARDS MANHOLES
B. AVERAGE GRADE.
SINGLE SLOPE
SINGLE SLOPE TO BE NOT LESS THAN 1:300
C. VERY STEEP GRADE.
SLOPE TO CONFORM TO GRADE.
96" MIN.
METHOD OF GRADING : TRENCHES SHALL BE UNIFORMLY GRADED. INSTALL
CONDUIT RUNS SO THAT ANY W ATER SEEPING INTO THE CONDUIT, AS WELL AS
LATERALS TO POLES, BUILDINGS, EQUIPMENT PADS, AND VAULTS WILL DRAIN
INTO MANHOLES OR HANDHOLES.
DOUBLE SLOPE
96" MIN. INNERDUCT
TRIPLE PACK
INSTALL
NOTE:
INSTALLATION OF
CABLE
INTO INNERDUCT
FABRIC
INNERDUCT
CELLS ARE CONNECTED
WITH A COLOR CODED
STITCH ALONG THE ENTIRE
LENGTH
TAPE IS COLOR
CODED AND
MARKED FOR
FOOTAGE
1. THE CONDUITS IN THE TOP
ROW OF ALL DUCTBANKS
AND SINGLE CONDUIT
DUCTBANKS SHALL CONTAIN
A INNERDUCT TRIPLE PACK.
NOT
ALLOWED
NOT
ALLOWED
NOT
ALLOWED
NOT
ALLOWED
MANHOLE MANHOLE
MANHOLE MANHOLE
STRAIGHT THROUGH SAME CORNER
OPPOSITE CORNERS SAME WALL
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
COLUMBIA VAMC, COLUMBIA, SC
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TG004
DETAILS
CJF
CJF JRQ
SCALE: NONE
F1
TYPICAL MANHOLE DETAIL
SCALE: NONE
C1
TYPICAL HANDHOLE DETAIL
SCALE: NONE
F8
TYPICAL TELECOM DUCTBANK SECTION DETAIL
SCALE: NONE
C5
DUCTBANK GRADING DETAILS
SCALE: NONE
C7
INNERDUCT DETAIL
SCALE: NONE
F6
MANHOLE CABLE ROUTING
SLOTTED CHANNEL STRUT CONDUIT
SUPPORT MUST BE 1-1/2" X 1-1/2"
DRILLED STEEL OR SIMILAR. ATTACH TO
FLEX TRAY WITH CARRIAGE BOLT AND
FLEX TRAY "SUPPORT WASHER"
CONDUIT MAY BE ATTACHED IN MULTIPLE
FASHIONS ALONG FLEX TRAY ASSEMBLY.
ALL ATTACHMENTS MUST BE
ELECTRICALLY BONDED.
CONDUIT CLAMP BRACKET WITH
INSULATING BUSHING ON CONDUIT
END.
3/8" GALVANIZED
THREADED ROD
SUPPORT
WIRE MESH
STYLE CABLE
TRAY. SIZE AS
NOTED ON
FLOOR PLANS
THREADED ROD
SUPPORT
HOLD DOWN CLAMP,
BOLT AND NUT
6" LONG SLEEVE TO
PREVENT DAMAGE TO
CABLES
LOCKING NUT
NOTES:
REFER TO CABLE TRAY PLANS FOR DIMENSIONS AND
PLACEMENT.
VOICE AND DATA
NETW ORKS
WALL
SLAB ABOVE
WALL MOUNT BRACKET
INSTALL MIN. 6" ABOVE FINISHED CEILING TO
ALLOW FOR CEILING TILE REMOVAL
LABEL FIELD (TYP.)
PROVIDE SINGLE GANG, FOUR
POSITION, MODULAR FACEPLATE
FOR EACH WORK AREA OUTLET
X#
BLANK (TYP.)
MODULAR
RJ-45 JACK
(TYP.) TYPICAL WORK AREA OUTLET
FACEPLATE SYMBOLS
SEE OUTLET SCHEDULES FOR OUTLET
DEFINITIONS
MINIMUM OUTLET
CONFIGURATIONS:
(2) RJ-45 MODULAR JACKS
PROVIDE OTHER COPPER AND FIBER
OPTIC CONFIGURATIONS TO SUPPORT
SPECIAL OR LEGACY
TELECOMMUNICATIONS SYSTEMS
WHEN REQUIRED
REFER TO COMMUNICATIONS OUTLET
TYPE SCHEDULE FOR CABLE AND
OUTLET QUANTITIES AND
CONFIGURATIONS
X# X#
STANDARD CONFIGURATION IS TW O
RJ-45 MODULAR JACKS AND TWO
BLANKS FOR FUTURE APPLICATIONS
WIRE ALL TERMINATIONS TO TIA 568-
C.0, T568A CONFIGURATION
PROVIDE (#) CATEGORY 6A UTP
CABLES FROM OUTLET TO SERVING
TELECOM ROOM (TR)
CONCRETE CEILING OR SLAB
ANCHOR
BOLT (TYP)
3/8" THREADED
STEEL ROD (TYP)
STEEL
CONDUIT (TYP)
NOTES:
1. FOR SUPPORTS THAT SPAN OVER 3'-0" AND
CONTAIN LARGER THAN 2" CONDUIT, PROVIDE
CENTER HANGER ROD SUPPORT.
STRUT CONDUIT
CLAMP (TYP)
1-5/8" X 1-5/8"
GALVANIZED SLOTTED
CHANNEL STRUT
LOCKING NUT
PROVIDE (1) RJ-45 CATEGORY 6A UTP CABLE
FROM OUTLET TO TR. MOUNT AT 48" A.F.F.
UNLESS OTHERW ISE NOTED.
LABEL FIELD
(TYP.)
MODULAR
RJ-45 JACK
X#
TELEPHONE
MOUNTING STUDS
TELEPHONE
MOUNTING STUDS
IDENTIFICATION LABEL (TYP.)
(1) MODULAR
RJ-45 JACK
SURFACE-MOUNTED
"BISCUIT" TYPE OUTLET
GENERAL NOTES:
1. THIS INSTALLATION SHALL ONLY OCCUR IN LOCATIONS WITH
ACCESSIBLE CEILING OR WHERE CEILING DOES NOT EXIST.
2. CABLING SHALL BE ROUTED SUCH THAT IT IS ACCESSIBLE FROM
END TO END.
3. PROVIDE 10' SERVICE LOOP, COILED IN CEILING SPACE.
X# PROVIDE (1) CATEGORY 6A UTP
CABLES FROM CEILING MOUNTED
OUTLET FOR WIRELESS ACCESS
POINT (WAP) TO NEAREST TR.
X#X#
EXTERIOR WALL
FINISHED GRADE
INTERIOR FLOOR LEVEL
CONDUITS ENTERING
BUILDING
PVC TO RGS
COUPLING
PROVIDE ANNULAR JOINT,
PACKED WITH LOOSE MINERAL
FIBER OR GLASS FIBER AND
CAULKED ON BOTH SIDES WITH
WEATHERPROOF SEALANT
DUCTBANK
REFER TO SITE PLAN
FOR SIZING
BUILDING
FOUNDATION WALL
PVC
PVC
RGS
RGS
EXTERIOR WALL
EXTERIOR NEMA 4X
JUNCTION BOX
RGS
RGS
EMT
EMT
FINISHED CEILING
RGS TO EMT
COUPLING
NOTES:
1. FOR MULTIPLE CONDUIT PENETRATIONS,
PACK VOID SPACE W ITH LOOSE MINERAL
FIBER OR GLASS FIBER AND CAULK ON
BOTH SIDES WITH WEATHERPROOF
SEALANT.
2. FOR AREAS WITH FINISHED CEILINGS
INSTALL CONDUITS ABOVE ACCESSIBLE
CEILING.
EXTERIOR WALL
FINISHED GRADE
INTERIOR FLOOR LEVEL
OPENING FOR CONDUITS
THROUGH BASEMENT W ALL
SEAL WITH WATERTIGHT
SEALING MATERIAL
BUILDING
FOUNDATION WALL
CONDUITS ENTERING
BASEMENT AREA OF
BUILDING
PROVIDE ANNULAR JOINT,
PACKED WITH LOOSE MINERAL
FIBER OR GLASS FIBER AND
CAULKED ON BOTH SIDES WITH
WEATHERPROOF SEALANT
EMT
EMT
RGS TO EMT
COUPLING
PVC TO RGS
COUPLING
DUCTBANK
PVC
PVC
RGS
RGS
BUILDING STEEL
SERVICE
EQUIP.
EARTH ELECTRODE SYSTEM (EES)
BUILDING STEEL
PANELBOARD
PRIMARY
BONDING
BUSBAR
(PBB)
PANELBOARD
PANELBOARD
SECONDARY
BONDING
BUSBAR
(SBB)
PANELBOARD
TELECOMMUNICATIONS ROOM (TR)
TELECOMMUNICATIONS ROOM (TR)
TELECOMMUNICATIONS ROOM (TR)
TELECOM BONDING BACKBONE (TBB)
SEE NOTE
NOTE:
THE IMPEDANCE OF THE TBB INCREASES WITH LENGTH THEREBY
REDUCING ITS ABILITY TO EQUALIZE POTENTIALS BETWEEN TR'S.
THE TBB FOR A LARGE SITE OR LONG RUNS MAY BE VERY COSTLY
TO ACHIEVE. AS AN ALTERNATIVE THE SBB IN EACH TR CAN BE
BONDED TO THE ELECTRICAL PANEL BOARD IN THE TR AND TO
STRUCTURAL STEEL W HERE APPLICABLE. INSTALL BONDING
CONDUCTORS IN THE SHORTEST AND MOST DIRECT PATHS
FEASIBLE.
1. PROVIDE 6 AWG RACK BONDING CONDUCTOR
(RBC) FROM EACH RACK BONDING BUSBAR (RBB)
TO THE 6 AWG TELECOMMUNICATIONS EQUIPMENT
BONDING CONDUCTOR (TEBC) USING
IRREVERSIBLE CRIMP CONNECTORS. PROVIDE
TEBC TO THE PBB/SBB. PROVIDE 6 AWG UNIT
BONDING CONDUCTORS (UBC) FROM EACH PIECE
OF INDIVIDUAL EQUIPMENT WITHIN RACK TO RBB
OR RBC. USE TWO-HOLE COMPRESSION LUGS FOR
ALL RACK CONNECTIONS WHERE POSSIBLE BUT
NO MODIFICATION OF THE RACK OR EQUIPMENT IS
ALLOWED.
2. PROVIDE INSULATED GROUND CABLE FROM
GROUND BAR TO BUILDING STRUCTURE.
EXOTHERMICALLY WELD CABLE TO METAL
STRUCTURE. SIZE CABLE IAW TABLE BELOW .
3. PROVIDE INSULATED GROUND CABLE FROM SBB
TO LOCAL PANELBOARD GROUND BAR. SIZE CABLE
IAW TABLE BELOW.
4. PROVIDE INSULATED GROUND CABLE TBB FROM
PBB TO FURTHEST SBB . CABLE SHALL BE
CONTIGUOUS. SIZE CABLE IAW TABLE BELOW.
5. PROVIDE A CRIMP CONNECTOR WITH TWO BOLT
HOLES FOR SECURING THE TBB CABLE TO THE PBB
OR SBB.
6. PROVIDE INSULATED GROUND CABLE FROM THE
PBB TO THE MAIN GROUNDING ELECTRODE
SYSTEM AT THE SWITCHBOARD. SIZE CABLE IAW
TABLE BELOW .
7. CABLE TRAY BONDING CONDUCTOR WITH
IRREVERSIBLE CRIMP CONNECTOR TO PBB/SBB.
KEYNOTES#
TELECOMMUNICATIONS ROOM (TR)
SECONDARY
BONDING
BUSBAR
(SBB)
SECONDARY
BONDING
BUSBAR
(SBB)
14-20 21-26 27-33 34-41 42-52 53-66 67-84
85-105 106-125 126-150 151-175 176-250 251-300
TBB/GE LINEAR LENGTH (FT) TBB/GE SIZE (AWG)
TBB CONDUCTOR SIZE VS LENGTH
1/0 2/0 3/0 4/0
250 KCMIL
300 KCMIL
350 KCMIL
500 KCMIL
600 KCMIL
750 KCMIL
CABLE LADDER
EQUIPMENT RACK
WITH ACTIVE
EQUIP.
RBB
UBC TO
RACK AND
EACH PIECE
OF EQUIP.
TEBC
CABLE LADDER
EQUIPMENT RACK
WITH ACTIVE
EQUIP.
RBB
UBC TO
RACK AND
EACH PIECE
OF EQUIP.
TEBC
CABLE LADDER
EQUIPMENT RACK
WITH ACTIVE
EQUIP.
RBB
UBC TO
RACK AND
EACH PIECE
OF EQUIP.
RBC
TEBC
CABLE LADDER
EQUIPMENT RACK
WITH ACTIVE
EQUIP.
RBB
UBC TO
RACK AND
EACH PIECE
OF EQUIP.
TEBC
RBC
RBC
RBC
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
Charlotte, NC 28204
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964
NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
COLUMBIA VAMC, COLUMBIA, SC
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TG005
DETAILS
CJF
CJF JRQ
SCALE: NONE
F6
TYPICAL CONDUIT TO CABLE TRAY CONNECTION DETAIL
SCALE: NONE
C6
TYPICAL W ORK AREA OUTLET (W AO) FACEPLATE DETAIL
SCALE: NONE
D6
TYPICAL TRAPEZE STYLE CONDUIT SUPPORT
SCALE: NONE
C8
TYPICAL W ALL MOUNT PHONE FACEPLATE DETAIL
SCALE: NONE
D8
TYPICAL CEILING MOUNTED OUTLET
SCALE: NONE
C1
TYPICAL TELECOM DUCTBANK EXTERIOR TRANSITION INTO
BUILDING
SCALE: NONE
C3
TYPICAL TELECOM DUCTBANK TRANSITION INTO BASEMENT
SCALE: 12" = 1'-0"
F1
TYPICAL TELECOM GROUNDING AND BONDING
INFRASTRUCTURE DETAIL
1" CONDUIT STUBBED INTO TOP OF
DOOR FRAME FOR BALANCED
MAGNETIC SWITCH (BMS)
MIN. 1" CONDUIT TO NEW
ACS/ IDS PANEL WITHIN
TR
6" X 6" SECURITY JUNCTION BOX FOR
SECURITY DOOR INTERFACE MODULE
SURFACE MOUNT JUNCTION BOX ON SECURE
SIDE OF DOOR 6" ABOVE FINISHED CEILING
OR 30" ABOVE DOOR FRAME WHEN NO
CEILING IS AVAILABLE. COORDINATE
LOCATION WITH MECHANICAL EQUIPMENT IN
AREA.
ACS
JUNCTION
BOX
1" CONDUIT TO CARD
READER/ KEYPAD (CR/KP)
JUNCTION BOX
RECESSED DOUBLE GANG
JUNCTION BOX WITH SINGLE
GANG MOUNTING RING FOR
CARD READER/ KEYPAD
(CR/KP) MOUNT AT 48 INCHES
A.F.F. UNLESS OTHERWISE
NOTED
BMS
CR/KP
EL
1" CONDUIT TO ELECTRIC
STRIKE (EL)
REX
1" CONDUIT FOR REX
PLEASE REFER TO
THE ARCHITECURAL
DOOR HARDWARE
SCHEDULE
MIN. 1" CONDUIT WITH CAT
6A CABLING FROM
CAMERA TO EXISTING
SSTV TELECOM ROOM
LOCATION
DOME CAMERA:
MOUNT CAMERA IN A POSITION
TO PREVENT GLARE FROM
OVERHEAD LIGHTING.
SSTV
FINISHED WALL
SURFACE MOUNTED
DEEP SINGLE GANG
JUNCTION BOX
SSTV
CEILING SLAB
C R
/K P
EL
B M
S
CR/KP
EL
BMS
CARD READER/ KEYPAD JUNCTION BOX WITH
MIN. 1" CONDUIT FROM ACS/IDS JUNCTION BOX
LOCATED ABOVE TR DOOR TO NEW PREMISE
CONTROL UNIT LOCATION.
SYMBOL LEGEND:
ELECTRONIC LOCK WITH MIN. 1" CONDUIT
FROM ACS/IDS JUNCTION BOX LOCATED ABOVE
TR DOOR TO NEW PREMISE CONTROL UNIT
LOCATION.
BALANCED MAGNETIC SWITCH W ITH MIN. 1"
CONDUIT FROM ACS/IDS JUNCTION BOX
LOCATED ABOVE TR DOOR TO NEW PREMISE
CONTROL UNIT LOCATION.
DOME STYLE SECURITY CAMERA.
R E
X
REX REQUEST TO EXIT DEVICE WITH MIN. 1"
CONDUIT FROM ACS/IDS JUNCTION BOX
LOCATED ABOVE TR DOOR TO NEW PREMISE
CONTROL UNIT LOCATION.
PCU
PCU PREMISE CONTROL UNIT FOR ACS/IDS SYSTEM
DEVICES. WILL REQUIRE DEDICATED 20A
CIRCUIT PROVIDED BY ELECTRICAL.
NEW TR
CR/KP
EL
BMS
REX
PCU
SW
EXISTING
TCP/IP
NETWORK
EQUIPMENT
RACKSW RACK MOUNTED SW ITCH FOR SECURITY
CPP RACK MOUNTED COPPER PATCH PANEL
CPP
X
NOTE: COORDINATE WITH LOCAL SECURITY CONTRACTOR
CPP
SW
X
VMS
X
EXISTING
TCP/IP
NETWORK
NEW DOME
STYLE CAMERA
CPP
SW
VMS
NEW CAT 6A
CABLING
EXISTING COPPER PATCH PANEL
EXISTING OWNER PROVIDED SSTV
SWITCH
EXISTING OWNER PROVIDED VIDEO
MANAGEMENT SYSTEM
EXISTING TR IN BULDINGS WITH
EXISTING CAMERA SWITCH
SYMBOL LEGENDNEW TR
EQUIPMENT
RACK
CPP
SW
X
VMS
X
EXISTING
TCP/IP
NETWORK
NEW DOME
STYLE CAMERA
NEW CAT 6A
CABLING
DATA CENTER B100 NEW TR IN BUILDINGS WITH NO EXISTING CAMERA
SWITCH (B5, B6, B8, B20, BT36, B105 AND VARO)
EQUIPMENT
RACK
SM OSP FIBER
10/100/1000 MEDIA
CONVERTER
FPP
10/100/1000 MEDIA
CONVERTER
CAT 6A CABLING
SM OS2 JUMPER
EQUIPMENT
RACK
FPP
SM OS2 JUMPER
RACK/ ENCLOSURE
RACK MOUNTED UPS
ZONE
PDU
RACKED EQUIPMENT
RACKED EQUIPMENT
RACKED EQUIPMENT
POWER
SUPPLY 1
POWER
SUPPLY 2
LEG A
BUS B
RACK/ ENCLOSURE
RACK MOUNTED UPS
RACKED EQUIPMENT
RACKED EQUIPMENT
RACKED EQUIPMENT
POWER
SUPPLY 1
POWER
SUPPLY 2
LEG B
BUS A
NOTE:
RACKS/ ENCLOSURES WILL HAVE A/B
REDUNDANT L21-30 CIRCUITS FOR THE
PAIR OF NETW ORK RACK/ ENCLOSURES,
WITH A 30A ZONE PDU SERVING THE PAIR
AND A/B REDUNDANT 20A RACK PDU'S TO
DISTRIBUTE THE POWER IN EACH RACK
B SIDE
VERTICAL RACK
MOUNTED PDU
A SIDE
VERTICAL RACK
MOUNTED PDU
RACK/ ENCLOSURE
RACK MOUNTED UPS
RACKED EQUIPMENT
RACKED EQUIPMENT
RACKED EQUIPMENT
POWER
SUPPLY 1
POWER
SUPPLY 2
BUS B
BUS A
FOR TR'S WITH ONE NETW ORK RACK FOR TR'S WITH TWO NETWORK RACKS
NOTE:
RACK/ ENCLOSURE WILL HAVE
A/B REDUNDANT L21-20
CIRCUITS FOR THE NETWORK
RACK/ ENCLOSURE, WITH A/B
REDUNDANT 20A RACK PDU'S
TO DISTRIBUTE THE POWER IN
THE RACK
B SIDE
VERTICAL RACK
MOUNTED PDU
A SIDE
VERTICAL RACK
MOUNTED PDU
KEY
BUS A: COMMERCIAL POWER
BRANCH CIRCUIT
BUS B: GENERATOR POWER BRANCH
CIRCUIT (WHERE AVAILABLE)
LEG A/B: A AND B DISTRIBUTION LEGS
OF THE ZONE PDU
POWER SUPPLY 1/2: REDUNDANT
POWER SUPPLIES IN EACH PIECE OF
IT EQUIPMENT
MIN. 1" CONDUIT TO CABLE
TRAY OR NEAREST TELECOM
ROOM (TR)
4-11/16 INCHES…