S02 - Attachment 11 - Columbia EHRM Telecom Drawing Set 9 of 9.pdf

PDF 17 MB Posted

Attached to
EHRM Infrastructure Upgrades Construction - Columbia, SC VAMC Federal contract opportunity
Solicitation number
36C77623R0096
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This file is an attachment to a solicitation for the EHRM Infrastructure Upgrades Construction project at the Columbia, South Carolina VA Medical Center. The solicitation number is 36C77623R0096 and is being issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas. The attachment contains drawing set number 9 of 9 with plans related to the telecommunications infrastructure for the project. Offerors will need to review all 9 drawing sets to understand the full scope of upgrades required, which include construction and installation of a new telecommunications system at the medical center to support the Electronic Health Record Modernization initiative. Proposals are due by the date specified on the first page of the solicitation document.

View the file

Other files for this federal contract opportunity

Other files attached to EHRM Infrastructure Upgrades Construction - Columbia, SC VAMC, newest first.
File Type Posted
36C77623R0096 0003 - Extension and RFI Answers - Columbia.pdf PDF
36C77623R0096 0002 - Columbia EHRM - Site Visit Sign-In and Risk Assess.pdf PDF
544 20 107 Columbia EHRM Infrastructure Risk Assessment.pdf PDF
36C77623R0096 0001 - Columbia EHRM - Extend RFI Deadline.pdf PDF
Columbia VA EHRM Site Visit Sign-In Sheet.pdf PDF
S02 - Attachment 1 - Columbia EHRM Statement of Work 21Feb23.pdf PDF
S02 - Attachment 2 - Columbia EHRM Specifications - 21Feb23.pdf PDF
S02 - Attachment 4 - Columbia EHRM Civil Drawing Set 2 of 9.pdf PDF
S02 - Attachment 5 - Columbia EHRM Arch Drawing Set 3 of 9.pdf PDF
S02 - Attachment 7 - Columbia EHRM Arch Drawing Set 5 of 9.pdf PDF
S02 - Attachment 16 - Wage Rates - Richland 1.6.23.pdf PDF
S02 - Attachment 13 - Limitations on Subcontracting - Construction.pdf PDF
S02 - Attachment 8 - Columbia EHRM Fire Drawing Set 6 of 9.pdf PDF
S02 - Solicitation - 36C77623R0096 - RFP - Columbia EHRM.pdf PDF
S02 - Attachment 3 - Columbia EHRM General Drawing Set 1 of 9.pdf PDF
S02 - Attachment 6 - Columbia EHRM Arch Drawing Set 4 of 9.pdf PDF
S02 - Attachment 9 - Columbia EHRM Mechanical Drawing Set 7 of 9.pdf PDF
S02 - Attachment 10 - Columbia EHRM Electrical Drawing Set 8 of 9.pdf PDF
S02 - Attachment 12 - EHRM Columbia VAHCS Addendum 001.pdf PDF
S02 - Attachment 14 - Contractor Safety - Environmental Form.pdf PDF
S02 - Attachment 15 - Site Visit Instructions.pdf PDF
Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CEILING MOUNTED DATA

OUTLET

SYMBOL DESCRIPTION

TELECOM LEGEND

CEILING MOUNTED VOICE

OUTLET

CEILING MOUNTED

VOICE/DATA OUTLET

FLOOR BOX MOUNTED DATA

OUTLET

FLOOR BOX MOUNTED

VOICE OUTLET

FLOOR BOX MOUNTED

TELECOMMUNICATIONS

OUTLET

WALL - FLUSH MOUNTED

DATA OUTLET

WALL - FLUSH MOUNTED

VOICE OUTLET

WALL - FLUSH MOUNTED

TELECOMMUNICATIONS

OUTLET

OVERHEAD OR

UNDERFLOOR CABLE TRAY -

SIZE AS INDICATED ON

DRAWINGS

CABLE TRAY LADDER

RACK - TYPICALLY

MOUNTED 1FT ABOVE

TELECOM RACK/ CABINET

45RU, 7 FOOT HIGH, 30 INCH

DEPTH HIGH DENSITY

RACKING SYSTEM

J JUNCTION BOX

CENTERLINE

EHH

HH

EXISTING HANDHOLE

NEW HANDHOLE

EMH EXISTING MAINTENANCE

HOLE

MH NEW MANHOLE

CONDUIT OR CONDUIT

SLEEVE WITH BUSHINGS. 4

INCH DIAMETER U.O.N.

CONDUIT OR CONDUIT

SLEEVE 'UP' (WHITE)

CONDUIT OR CONDUIT

SLEEVE 'DOW N' (BLACK)

'#' NUMBER IDENTIFIER INDICATES CABLE COUNT AT

OUTLET. SEE TELECOM OUTLET SCHEDULES FOR

OUTLET AND NETWORK DEFINITIONS.

NOTE: COPPER CABLING NUMBERING MUST BE FOR A

SINGLE COPPER CABLE ONLY. WHERE FIBER CABLING

IS INDICATED CABLE COUNT MUST BE FOR A SINGLE 2-

STRAND FIBER CABLE.

EXAMPLE: 4 INDICATES TELECOMMUNICATIONS

OUTLET WITH (4) COPPER CABLES AT

OUTLET.

16RU SWING-OUT WALL

MOUNTED TELECOM

CABINET

WALL - SURFACE MOUNTED

TELECOMMUNICATIONS

OUTLET

SM

SYSTEMS FURNITURE

MOUNTED

TELECOMMUNICATIONS

OUTLET

CR/KP

EL

BMS

CARD READER/ KEYPAD

ELECTRIC STRIKE

BALANCED MAGNETIC

SWITCH

CEILING MOUNTED DOME

STYLE SECURITY CAMERA

REX REQUEST TO EXIT DEVICE

VERTICAL WIRE MANAGER

PCU

PREMISE CONTROL UNIT

FOR ACS/IDS SYSTEM

DEVICES. WILL REQUIRE

DEDICATED 20A CIRCUIT

PROVIDED BY ELECTRICAL.

SEIS

SEISMIC VIBRATION

DETECTION DEVICE

Location

Issue Date

Specialized Engineering Solutions

1300 Baxter Street, Suite 355

Charlotte, NC 28204

544-20-107PROJECT # 544-20-107

EHRM INFRASTRUCTURE UPGRADES

www.atriaxgroup.com

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

COLUMBIA VAMC, COLUMBIA, SC

VA FORM 08 - 6231

A

F ile

P a th

/1

/2

:3

:0

P M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TG001

LEGEND, ABBREVIATIONS

AND GENERAL NOTES

CJF

CJF JRQ

TELECOM ABBREVIATIONS

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NETWORK INTERFACE CARD

NID NETWORK INTERFACE DEVICE

NM NANOMETER

NTS NOT TO SCALE

O

OC ON CENTER

OD OUTSIDE DIAMETER

OEM ORIGINAL EQUIPMENT

MANUFACTURER

OS OPERATING SYSTEM

OSP OUTSIDE PLANT

P

PA PUBLIC ADDRESS

PABX PRIVATE AUTOMATIC BRANCH

EXCHANGE

PB PULL-BOX (SIZED PER BICSI TDMM)

PBB PRIMARY BONDING BACKBONE

PBX PRIVATE BRANCE EXCHANGE

PC PERSONAL COMPUTER

PCN PERSONAL COMMUNICATIONS

NETWORK

PCS PERSONAL COMMUNICATIONS

SYSTEMS

PED PEDESTAL

PIR PASSIVE INFRARED

PM POLE MOUNTED

PNL PANEL

POTS PLAIN OLD TELEPHONE SERVICE

PR PAIRS (NUMBERS OF PAIRS IN

COPPER CABLE)

PROX PROXIMITY

PVC POLYVINYL CHLORIDE

PWR POWER

R

RCDD REGISTERED COMMUNICATIONS

DISTRIBUTION DESIGNER

RCP REFLECTED CEILING PLAN

RECPT RECEPTACLE

RFI RADIO FREQUENCY INTERFACE

RGS RIGID GALVANIZED STEEL

RM ROOM

RMC RIGID METALLIC CONDUIT

S

SBB SECONDARY BONDING BACKBONE

SCTP SCREENED TWISTED PAIR

SMFO SINGLEMODE FIBER OPTIC

SP SERVICE PROVIDER

SPOE SECONDARY POINT OF ENTRY

SSTV SECURITY SURVEILLANCE VIDEO

SYSTEM

STD STANDARD

STP SHEILDED TWISTED PAIR

SW SWITCH

T

TBB TELECOMMUNICATIONS BONDING

BACKBONE

TBD TO BE DETERMINED

TCO TELECOMMUNICATIONS OUTLET

TCP/IP TRANSMISSION CONTROL

PROTOCOL W/ INTERNET

PROTOCOL

TDMM TELECOMMUNICATIONS

DISTRIBUTION METHODS MANUAL

TEL TELEPHONE

TELCO TELEPHONE COMPANY

TELECOM TELECOMMUNICATIONS

TEMP TEMPERATURE

TGB TELECOMMUNICATIONS GROUND

BUS BAR

TIA TELECOMMUNICATIONS INDUSTRY

ASSOCIATION

TR TELECOMMUNICATIONS ROOM

TV TELEVISION

TYP TYPICAL

U

UC UNDER COUNTER

UG UNDERGROUND

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTP UNSHIELDED TWISTED PAIR

V

V VOLT

W

W WATT

WAN WIDE AREA NETWORK

WAP WIRELESS ACCESS POINT

WLAN WIRELESS LOCAL AREA NETWORK

WP WEATHERPROOF

X

X,(X) EXISTING - TO BE DEMOLISHED

TELECOM ABBREVIATIONS

A

AC ABOVE COUNTER

ADA AMERICANS WITH DISABILITIES ACT

AFC ABOVE FINISHED CEILING

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

ALT ALTERNATE

AMP AMPERE

ANSI AMERICAN NATIONAL STANDARDS

INSTITUTE

ARCH ARCHITECT

ATR ALL THREAD ROD

AV AUDIO VISUAL

AWG AMERICAN WIRE GUAGE

B

BATT BATTERY

BDA BI-DIRECTIONAL ANTENNA

BFC BELOW FINISHED CEILING

BFF BELOW FINISHED FLOOR

BFG BELOW FINISHED GRADE

BICSI BUILDING INDUSTRY CONSULTING

SERVICES INTERNATIONAL

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C

C CONDUIT

CAB CABINET

CAT CATEGORY

CATV COMMUNITY ANTENNA TV (CABLE

TV)

CF CONTRACTOR FURNISHED

CFCI CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CFOI CONTRACTOR FURNISHED OWNER

INSTALLED

CL CENTER LINE

CLEC COMPETITIVE LOCAL EXCHANGE

CARRIER

CLG CEILING

CMP COMMUNICATIONS PLENUM CABLE

CMR COMMUNICATIONS RISER CABLE

CO CENTRAL OFFICE

COAX COAXIAL CABLE

CONT CONTINUE

COORD COORDINATE

CT CABLE TRAY

D

DAS DISTRIBUTED ANTENNA SYSTEM

DB DECIBEL

DEMARC DEMARCATION

DEMO DEMOLITION

DIA DIAMETER

DIAG DIAGRAM

DWG DRAWING

E

E, (E) EXISTING

E.G. FOR EXAMPLE

EIA ELECTRONICS INDUSTRY ALLIANCE

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

EMH EXISTING MANHOLE

EMI ELECTROMAGNETIC

INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EP EXPLOSION PROOF

ERRCS EMERGENCY RESPONDER RADIO

COVERAGE SYSTEM

EXIST EXISTING

F

FACP FIRE ALARM CONTROL PANEL

FBO FURNISHED BY OTHERS

FCC FEDERAL COMMUNICATIONS

COMMISION

FO FIBER OPTIC

FR FIRE RATED

FT FOOT/ FEET

G

GB GIGABYTE

GBPS GIGABITS PER SECOND

GC GENERAL CONTRACTOR

GE GROUND EQUALIZER

GND GROUND

GUI GRAPHICAL USER INTERFACE

H

HC HORIZONTAL CROSS-CONNECT

HH HANDHOLE

HVAC HEATING, VENTILATION AND AIR

CONDITIONING

I

IAW IN ACCORDANCE WITH

ID INSIDE DIAMETER

IDF INTERMEDIATE DISTRIBUTION

FRAME

IEC INTERNATIONAL

ELECTROTECHNICAL COMMISION

IEEE INSTITUTE OF ELECTRICAL AND

ELECTRONICS ENGINEERS, INC.

IG ISOLATED GROUND

INT INTERCOM

IP INTERNET PROTOCOL

ISO INTERNATIONAL ORGANIZATION OF

STANDARDS

ISP INTERNET SERVICE PROVIDER

J

J-BOX,JB JUNCTION BOX

K

KM KILOMETER

KVA KILOVOLT AMPERES

KW KILOWATT

L

LAN LOCAL AREA NETWORK

LEC LOCAL EXCHANGE CARRIER

LED LIGHT EMITTING DIODE

LV LOW VOLTAGE

M

M METER

MAG MAGNETIC

MAN METROPOLITAN AREA NETWORK

MAX MAXIMUM

MB MEGABYTE

MBPS MEGABITS PER SECOND

MC MAIN CROSS-CONNECT

MDF MAIN DISTRIBUTION FRAME

MECH MECHANICAL

MFR MANUFACTURER

MH MANHOLE

MI MILE

MIN MINIMUM

MM MILLIMETER

MMFO MULTIMODE FIBER OPTIC

MPOE MAIN POINT OF ENTRY

N

NA NOT ACCEPTABLE

NEC NATIONAL ELECTRICAL CODE -

NFPA 70

TELECOM LEGEND NOTES

A SYMBOLS ORIENTATION DOES NOT IMPLY DEVICE OR

EQUIPMENT ORIENTATION. UNLESS NOTED AS SUCH.

SEE REFLECTED CEILING PLANS FOR ALL CEILING

MOUNTED DEVICE POSITIONS AND ORIENTATIONS

B SYMBOL SIZE DOES NOT IMPLY EQUIPMENT SIZE, UON.

C MOUNTING HEIGHT INDICATED IN LEGEND AND ON THE

DRAWINGS MUST BE THE DISTANCE MEASURED FROM

THE CENTER OF THE DEVICE TO THE FINISHED FLOOR.

D NOT ALL SYMBOLS ARE USED.

E REFER TO TYPICAL DETAILS ON TN500 SERIES

DRAWINGS.

TELECOM GENERAL NOTES

25 THE LOCATIONS AND ELEVATIONS OF TECHNOLOGY DEVICES SHOWN ON THESE DRAWINGS ARE

SCHEMATIC UNLESS ACTUAL DIMENSIONS ARE SHOWN ON THE DRAWINGS. REFER TO THE

ARCHITECTURAL PLANS AND OBTAIN THE APPROVAL OF THE OWNER'S REPRESENTATIVE FOR THE ACTUAL

LOCATIONS AND ELEVATIONS OF ALL DEVICES.

26 COMPLY WITH CURRENT ADA REQUIREMENTS FOR MOUNTING HEIGHTS OF ALL DEVICES AND EQUIPMENT.

27 PROVIDE SUPPORTS AND ANCHORING FOR CONDUIT, CABLE TRAYS, EQUIPMENT, AND OTHER

NON-STRUCTURAL ELEMENTS. SEE TECHNOLOGY SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS

INCLUDING INSTALLATION IN DESIGNATED SEISMIC AREAS.

28 ALL COMMUNICATIONS CONDUIT, CABLE TRAYS, LADDER RACKS AND EQUIPMENT RACKS SHALL BE

BONDED TO BUILDING GROUND SYSTEM PER NEC 250 AND ANSI/TIA-607-C

29 LABEL ALL CLOSETS, RACKS, FRAMES, CABINETS, TERMINATION BLOCKS, CABLES, TERMINATIONS, RACEWAYS, ETC. IN ACCORDANCE WITH ANSI/TIA-606-B AND OWNER'S CRITERIA

30 ALL COMMUNICATIONS RACEWAYS AND PATHWAYS SHALL MINIMIZE UNNECESSARY CABLE LENGTHS AND MAINTAIN INDUSTRY STANDARD LENGTH LIMITATIONS FOR HORIZONTAL CABLE DISTRIBUTION (E.G. CAT.6).

BASIC LINK CABLE LENGTH SHALL NOT EXCEED 295-FT (90M) FOR UTP CABLE, 200-FT (60M) FOR SERIES-6

COAXIAL CABLE.

31 PROVIDE PROTECTIVE BUSHINGS ON ALL COMMUNICATIONS CONDUITS AND WHERE CABLING ROUTES

THROUGH METAL STUDS.

32 PROVIDE LOW-VOLTAGE CABLES IN CONDUITS, CABLE TRAYS, WIREWAYS OR OTHER APPROVED CABLE MANAGEMENT DEVICES OR SYSTEMS. THE CONTRACTOR SHALL NOT INSTALL CABLING SUPPORTED BY CEILING SYSTEMS (CEILING TILE OR GRID, GYPSUM BOARD, LATH & PLASTER), HVAC DUCTS OR PIPES, LIGHTING FIXTURES, ELECTRICAL CONDUITS OR CABLES, PLUMBING/FIRE PROTECTION PIPES, OR ANY

OTHER DEVICES NOT INTENDED FOR THE SUPPORT OF LOW-VOLTAGE CABLING.

33 REUSABLE VELCRO TIES SHALL BE USED TO BUNDLE OR MANAGE CABLES. PLASTIC ZIP TIES SHALL NOT BE

PERMITTED.

34 SIZE AND ORIENTATION OF ALL TELECOM PULL-BOXES SHALL MEET OR EXCEED THE BICSI TDMM

REQUIREMENTS.

35 ALL OUTSIDE CONDUITS SHALL BE INSTALLED WITH NYLON PULL LINES HAVING 1200 LB MINIMUM TENSILE

STRENGTH AND NUMBERED FOOT MARKINGS.

36 THERE SHALL BE A MINIMUM OF ONE TELECOMMUNICATIONS ROOM (TR) PER FLOOR. ADDITIONAL ROOMS SHALL BE PROVIDED WHEN: A. THE FLOOR AREA TO BE SERVED EXCEEDS 1000msq (10,000 sqft); OR B. THE

HORIZONTAL DISTRIBUTION DISTANCE TO THE WORK AREA EXCEEDS 90M (295FT).

37 MINIMUM TR FLOOR SPACE REQUIREMENT SHALL BE 80sqft FOR A SINGLE RACK TR WITH AN ADDITIONAL 20sqft OF SPACE PER ADDTIONAL RACK.

38 ALL GROUND BARS, CONNECTIONS TO BUILDING STEEL AND CONNECTIONS TO PANELBOARDS SHALL BE

SUPPLIED AND INSTALLED BY ELECTRICAL TRADE.

39 EXISTING ELEVATOR COPPER TELEPHONE CIRCUITS TO REMAIN CONNECTED TO EXISTING TR'S.

40 ALL NEW RACKS AND CABINETS ARE TO RECEIVE SEISMIC BRACING EQUIVALENT TO CHATSWORTH PART

NUMBER 10562-001 OR BETTER.

41 OSP CABLING SHALL BE COILED A MINIMUM OF ONE TIME AROUND EACH MH/HH IT PASSES THROUGH.

42 THIS PROJECT REQUIRES THE CONTRACTOR TO INSTALL TWO FULLY REDUNDANT AND GEOGRAPHICALLY DIVERSE FIBER FEEDS (A FEED AND B FEED) TO EACH TELECOM ROOM IN EACH BUILDING. THE SITE INFRASTRUCTURE HAS BEEN DESIGNED SUCH THAT THE A FEED AND THE B FEED FOR ANY INDIVIDUAL TELECOM ROOM SHALL NOT RUN IN THE SAME CONDUIT, OR IN THE SAME DUCTBANK, OR IN THE SAME

MANHOLE/HANDHOLE.

43 THIS PROJECT INCLUDES THE ONE FOR ONE REPLACEMENT OF THE EXISTING HORIZONTAL CATEGORY COPPER CABLING FROM THE TELECOM ROOMS TO THE WORK AREAS. DURING THE DESIGN SITE SURVEY, NOT ALL CABLING WAS VISUALLY ACCESSIBLE DUE TO THE FURNITURE OR SPACES BEING IN USE. THE CONTRACTOR SHALL ASSUME AN ADDITIONAL 15% (ABOVE AND BEYOND WHAT IS CURRENTLY SHOWN ON THE DRAWINGS.) FOR HORIZONTAL CABLING AND HORIZONTAL CABLING CONNECTIONS (FACEPLATES, JACKS, PATCH PANEL PORTS, ETC.) THE CONTRACTOR IS ALSO REQUIRED TO PERFORM THEIR OWN SITE SURVEY SOMETIME AFTER AWARD BUT BEFORE INSTALLATION TO DETERMINE THE FINAL HORIZONTAL CABLING COUNTS FROM EACH TR FOR CABLES THAT ARE BEING REPLACED. BASED ON THE DESIGN SITE

SURVEY THE CONTRACTOR'S SURVEY IS ESTIMATED TO TAKE 4 DAYS OF AFTERHOURS SURVEY

(3PM-11PM) AND SHALL BE COORDINATED WITH THE COR.

44 CABLE TRAYS THAT PASS OVER WALL MOUNTED ELECTRICAL PANELS SHALL HAVE A 6" HORIZONTAL

OFFSET FROM WALL TO ALLOW FOR CONDUIT CLEARANCES.

45 DRAWINGS ARE BASED ON EXISTING BUILDING PLANS AND FIELD INVESTIGATIONS. CONTRACTOR SHALL VISIT THE EXISTING BUILDING AND ACQUAINT THEMSELVES WITH THE EXISTING CONDITIONS.

CONTRACTOR SHALL EXAMINE DRAWINGS TO AVOID CONFLICT.

46 PLYWOOD FOR TR WALLS IS SHOWN ON TELECOM AND DRAWINGS OF OTHER DISCIPLINES. THE PLYWOOD IN EACH DRAWING SET IS THE SAME AND IS NOT MEANT TO BE DUPLICATED BY THE CONTRACTOR.

47 IF CONTRACTOR ENCOUNTERS FIELD CONDITIONS THAT PREVENT INSTALLATION OF SCOPE SHOWN ON THE DRAWINGS, CONTRACTOR SHALL NOTIFY WILEY WILSON AND THE COR FOR ISSUE EXAMINATION AND

RESOLUTION.

48 A AND B BACKBONE CONDUITS ROUTING THROUGH CORRIDORS FROM BUILDING 100 SHALL BE

PHYSICALLY SEPARATED AS MUCH AS POSSIBLE.

49 ALL FLOOR, CEILING OR RATED WALL PENETRATIONS, PERMANENT AND TEMPORARY, SHALL BE FIRESTOPPED AT END OF WORK SHIFT PER SPECIFICATION 07 84 00, FIRESTOPPING. IF FLOOR, CEILING, OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED FOR ADDITIONAL WORK IN THAT AREA, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHALL BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD

THROUGH THE UNSEALED PENETRATION.

50 BLANK SPACE BETWEEN HORIZONTAL CABLE MANAGEMENT PANELS IN TR RACKS INDICATES SPACE

RESERVED FOR GFGI SWITCHES

51 CONTRACTOR TO PROVIDE HORIZONTAL BLANKING PANELS FOR ALL NEW RACKS AND CABINETS. A TOTAL OF (30) 1U BLANKING PANELS SHALL BE PROVIDED FOR EACH RACK. A TOTAL OF (45) 1RU BLANKING

PANELS SHALL BE PROVIDED FOR EACH NEW CABINET.

52 IN AREAS WHERE TELECOM WORK PENETRATES INTERIOR OR EXTERIOR WALLS, CEILING PANELS, GRID SYSTEM, GYPSUM CEILINGS AND/OR BULKHEADS, CONTRACTOR SHALL BE REQUIRED TO PATCH AND

REPAIR PENETRATIONS AS A RESULT OF THE WORK.

TELECOM GENERAL NOTES

1 INTENT OF THE DRAWINGS - THE DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL LOCATION OF

OUTLETS, RACEWAYS, AND EQUIPMENT. THE DRAWINGS DO NOT SHOW ALL NECESSARY OFFSETS, JUNCTION BOXES, CABLE TRAY TRANSITIONS, AND ADJUSTMENTS NECESSITATED BY COORDINATION WITH OTHER TRADES. PROVIDE ALL OFFSETS, RACEWAY COMPONENTS, ACCESSORIES, AND ADJUSTMENTS

NECESSITATED BY COORDINATION WITH OTHER TRADES.

2 COORDINATION WITH OTHER TRADES - EXAMINE AND REVIEW THE CONTRACT DOCUMENTS OF ALL DIVISIONS IN ORDER TO COORDINATE THE INSTALLATION WORK. USE DIMENSIONED ARCHITECTURAL AND

STRUCTURAL CONTRACT DRAWINGS TO VERIFY THE SPACE NECESSARY FOR LOCATING OUTLETS,

RACEWAYS, AND EXACT EQUIPMENT. USE FIELD MEASUREMENTS TO VERIFY DIMENSIONS WHERE AREAS ARE CONGESTED, AND EXACT LOCATION IS CRITICAL TO ASSURE PROPER INSTALLATION. COORDINATION SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO, VERIFYING THE LOCATION AND SIZE OF OPENINGS FOR PENETRATIONS IN FLOORS, WALLS, PARTITIONS, CEILINGS, AND ROOFS WITH THE INSTALLING TRADES;

ALLOCATION OF SPACE WITH OTHER TRADES INSTALLING WORK IN CHASES, SHAFTS, CEILING

INTERSTITIAL SPACES, AND EQUIPMENT SPACES; AND THE PHASING OF INSTALLATION WORK WITH THAT

OF OTHER TRADES.

3 WORKMANSHIP - INSTALL ALL WORK IN A WORKMANLIKE MANNER THAT PROVIDES A FIRST CLASS COMPLETED INSTALLATION. REMOVE, CORRECT AND REPLACE ANY WORK DEEMED UNACCEPTABLE AT

THE DISCRETION OF THE CONTRACTING OFFICER.

4 EQUIPMENT - INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS, THE SPECIFICATIONS, AND APPROVED SHOP DRAWINGS, PROVIDE SERVICE AND OPERATING CLEARANCES AROUND ALL SIDES OF EACH PIECE OF EQUIPMENT IN ACCORDANCE WITH REGULATORY REQUIREMENTS, MANUFACTURER'S PRINTED REQUIREMENTS AND RECOMMENDATIONS.

5 LARGE EQUIPMENT - SOME LARGE EQUIPMENT MAY REQUIRE DISASSEMBLY IN ORDER TO INSTALL IN THE BUILDING. SECURE THE SERVICES OF THE MANUFACTURER FOR REASSEMBLY WHERE NECESSARY TO

MAINTAIN WARRANTIES IN EFFECT.

6 ALL THE SYMBOLS IN THE LEGEND MAY NOT HAVE BEEN USED ON THE PLANS. SYMBOLS NOT LISTED IN

LEGEND ARE IDENTIFIED WHERE THEY OCCUR.

7 ANY PENETRATIONS THAT ARE REQUIRED THRU WALLS, FLOORS, OR CEILINGS SHALL MAINTAIN THE APPLICABLE RATING OF THE SURFACE BEING PENETRATED. (IE. FIRE RATED WALLS BEING PENETRATED REQUIRE CABLE/PATHWAY PENETRATION TO MATCH THE RATING OF THE WALL). THIS ALSO APPLIES TO

ALL TEMPORARY BARRIERS THAT MAY BE INSTALLED TO COMPLY WITH ICRA REQUIREMENTS.

8 PROVIDE PULL CORD HAVING AT LEAST A 90KG TENSILE STRENGTH IN ALL TELECOMMUNICATIONS INDOOR

CONDUITS.

9 UNLESS NOTED OTHERWISE, ALL CONDUITS SHALL BE INSTALLED CONCEALED UNDER FLOOR SLABS, ABOVE THE CEILING AND WITHIN THE FINISHED WALLS. ALL OUTLET BOXES SHALL BE INSTALLED FLUSH MOUNTED WITHIN FINISHED WALLS, CEILINGS OR FLOORS. SURFACE MOUNTED RACEWAY AND OUTLET BOXES SHALL NOT BE PERMITTED ON FINISHED WALLS, CEILINGS OR FLOORS. SURFACE MOUNTED RACEWAY AND OUTLET BOXES SHALL NOT BE PERMITTED ON FINISHED WALLS CEILINGS OR FLOORS.

EMBEDDED CONDUITS IN CAST-IN-PLACE CONCRETE (COLUMNS, BEAMS, FLOORS, WALLS OR ELEVATED

SLABS) ARE PERMITTED. REFER TO ELECTRICAL DETAILS FOR SPECIFIC REQUIREMENTS.

10 ALL TELECOMMUNICATIONS BONDING BACKBONE CONDUCTORS SHALL BE INSULATED, COPPER

CONDUCTOR. INSTALL TBB CONDUCTORS IN CONDUIT TO PROVIDE PROTECTION FROM PHYSICAL DAMAGE.

WHERE TBB CONDUCTORS ARE INSTALLED IN METALLIC CONDUIT, BOND BOTH END WITH A LISTED BONDING BUSHING. TERMINATE TBB AND GE CONDUCTORS ON PBB AND SBBs WITH A LISTED TWO-HOLE

COMPRESSION CONNECTOR.

11 TELECOMMUNICATIONS PULL BOXES SHALL BE IN STRAIGHT SECTIONS OF CONDUIT. DO NOT USE BOXES IN LIEU OF ELBOWS OR BENDS. NOT ALL TELECOMMUNICATIONS PULL BOXES ARE SHOWN. BEYOND THOSE SHOWN PROVIDE BOXES WHEN: 1. RACEWAY SECTION INCLUDES (2) TWO OR MORE 90 DEGREE BENDS OR

EQUIVALENT. 2. LENGTH OF RACEWAY SECTION IS GREATER THAN 30 METERS (100 FEET).

12 PROVIDE METALLIC CONDUIT WITH INSULATED BUSHINGS AT TERMINATIONS.

13 FACTORY ELBOWS OR FIELD BENDS SHALL HAVE AN INTERNAL RADIUS OF NOT LESS THAN (6) TIMES THE DIAMETER OF THE CONDUIT LESS THAN 2". INTERNAL RADIUS SHALL BE (10) TIMES THE DIAMETER FOR CONDUITS GREATER THAN 2". NO HARD 90 DEGREE TURNS PERMITTED IN ANY TELECOM CONDUIT.

14 CONDUITS HAVE BEEN SIZED BASED ON THE NEC, AS WELL AS ANSI/EIA/TIA 569-C. WHERE INSTALLATION VARIES, INCREASE CONDUITS SIZES ACCORDING TO MAXIMUM NUMBER OF CABLES BASED ON ALLOWABLE

FILL TABLE.

15 PROVIDE WARNING OR CAUTION LABELS ON ALL ENCLOSURES THAT USE OR CONTAIN FIBER OPTIC

CABLING.

16 LABEL ALL CABLES WITHIN 4" OF EACH TERMINATION. PROVIDE 12" LONG SERVICE LOOP AT THE WORK AREA END OF EACH HORIZONTAL CABLE. PROVIDE DUST COVERS ON ALL SPARE SYSTEM PATCH PANEL

JACKS.

17 FURNISH ADDITIONAL MATERIALS AS IDENTIFIED HEREIN AND WITHIN PROJECT SPECIFICATIONS.

18 PROVIDE D-RINGS EVERY 12" ALONG CABLE RUNS TO SUPPORT ENTERING AND EXITING WIRING FIELDS.

19 PROVIDE VELCRO CABLE TIES TO ATTACH CABLES TO WIRE MANAGEMENT, D-RINGS AND OTHER SUPPORT

MEANS.

20 PROVIDE TESTING OF ENTIRE STRUCTURED CABLING PLANT PER SPECIFICATIONS.

21 PROVIDE (2) NEW 4" CONDUITS TO BUILDINGS AND BETWEEN HANDHOLES UNLESS OTHERWISE NOTED FOR ALL BACKBONE FIBER CABLING. TYPICAL DEPTH OF CONDUIT DUCTBANK IS TO BE 36 INCHES BELOW GRADE. DUCTBANK SHALL BE CONCRETE ENCASED. REFER TO CIVIL DRAWINGS FOR EXACT DUCTBANK

COORDINATES AND ADDITIONAL DETAILS.

22 WHERE FLOOR BOXES ARE USED CONTRACTOR SHALL PROVIDE PATCH CORDS FOR VOICE AND DATA

THAT ARE OF APPROPRIATE LENGTH TO REACH THE WORKSTATION EQUIPMENT THEY SERVE.

23 DROP COUNT QUANTITIES ARE PROVIDED ON TN400 SERIES DRAWINGS TO ILLUSTRATE CROSS-CONNECT FIELD OR PATCH PANEL SIZING AND ARE NOT TO BE RELIED UPON FOR FINAL OUTLET QUANTITIES.

PROVIDE OUTLETS, JACKS, PATCH PANELS AND OTHER MATERIALS BASED ON QUANTITIES INDICATED ON

FLOOR PLANS AND SPECIFIED WITHIN THE CONTRACT DOCUMENTS

24 PROVIDE JACKETING, SHEATHING, ARMORING AND FILLING COMPOUNDS FOR OUTSIDE PLANT CABLES IN ACCORDANCE WITH THE CONTRACT DOCUMENT SPECIFICATION REQUIREMENTS. PROVIDE OUTSIDE PLANT CABLES SUITABLE FOR USE IN EXTERIOR APPLICATIONS AND IN ACCORDANCE WITH THE CABLES LISTING AND LABELING APPLICATIONS. UNLESS NOTED OTHERWISE, OUTSIDE PLANT APPLICATIONS SHALL BE CONSIDERED TO BE APPLICABLE FOR: CABLING INSTALLED BEYOND THE EXTERIOR WALLS OF A BUILDING, EITHER ABOVE OR BELOW GRADE, AND/OR BETWEEN BUILDING ENTRANCE PROTECTORS.

TELECOM SCOPE OF WORK RESPONSIBILITY MATRIX

DESCRIPTION CFCI GFGI NOTES

ACTIVE CABINET/ RACK MOUNTED NETWORK SWITCHES X

CABINET/ RACK MOUNTED PDU AND UPS (TELECOM ROOMS ONLY) X

COPPER AND FIBER PATCH PANELS AND ASSOCIATED TERMINATIONS X

COPPER PATCH CABLES IN THE TELECOM ROOMS (FROM PATCH PANEL TO SWITCH) X

DEDICATED TELECOMMUNICATIONS GROUNDING AND BONDING SYSTEM X

DEMO OF EXISTING PASSIVE STRUCTURED CABLING SYSTEM (PATHWAYS, CABLE,

TERMINATIONS, PATCH PANELS, OUTLETS, ETC.)

X

EXISTING COPPER PATCH CABLES AT THE WORK AREA OUTLETS (FROM OUTLET TO

WORKSTATION)

TO REMAIN

MODIFICATION OF EXISTING OSP FIBER CONNECTION TO THE BUILDING X

NEW BACKBONE INSIDE PLANT CABLING (FIBER AND COPPER) X

NEW BACKBONE INSIDE PLANT PATHWAYS X

NEW EQUIPMENT CABINETS AND RACKS IN THE TELECOM ROOMS AND MAIN SERVER ROOM X

NEW FIBER PATCH CABLES IN THE TELECOM ROOMS AND MAIN SERVER ROOM X

NEW HORIZONTAL INSIDE PLANT CABLING X

NEW HORIZONTAL INSIDE PLANT PATHWAYS X

TERMINATION AND TESTING OF ALL BACKBONE CABLING X

TERMINATION OF ALL HORIZONTAL CABLING X

TELECOM DEMOLITION NOTES

SECURITY GENERAL NOTES

1 THE SECURITY CONTRACTOR SHALL PROVIDE, INSTALL, DOCUMENT, AND TEST A FULLY INTEGRATED SECURITY SYSTEM FOR THE OWNER. THE INTEGRATED SECURITY SYSTEM SHALL INCLUDE A MICROPROCESSOR-BASED SECURITY

MANAGEMENT/CARD ACCESS/ALARM MONITORING SYSTEM, A CLOSED CIRCUIT TELEVISION SYSTEM, VARIOUS ASSOCIATED CONTROL AND/OR SUPPORT EQUIPMENT, AND ALL REQUIRED CABLING AND WIRING. SECURITY SYSTEM

CONDUCTORS SHALL NOT BE INSTALLED IN THE SAME CONDUIT AS "AC" POWER CONDUCTORS.

2 SECURITY SYSTEM CONDUCTORS SHALL BE PROVIDED BY CONTRACTOR, AS NOTED HEREIN. CONDUITS AND WALLBOXES FOR THE SECURITY SYSTEM WILL BE PROVIDED BY CONTRACTOR.

3 THE SECURITY CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING FINAL SECURITY EQUIPMENT LAYOUT AND ROUTING OF CONDUIT AS SHOWN ON THE PROJECT DRAWINGS. ANY COORDINATION CONFLICTS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE COR, WHO SHALL APPROVE ALL CHANGES PRIOR TO THE INITIATION OF WORK. THE SECURITY CONTRACTOR SHALL SUBMIT CONDUIT AND WIRE LAYOUT DRAWING SHOWING CIRCUIT NUMBERS , WIRING, ACTUATOR POWER SUPPLY(S) WITH BATTERY BACKUP, AND CONDUIT ROUTINGS FOR APPROVAL PRIOR TO THE INITIATION OF WORK.

4 ALL REQUIRED EQUIPMENT AND HARDWARE MAY NOT BE INDICATED ON DRAWINGS, DEPENDING ON THE SPECIFIC MANUFACTURER SUBMITTED FOR APPROVAL. CONTRACTOR SHALL PROVIDE ALL REQUIRED EQUIPMENT AND HARDWARE IN ORDER TO MEET THE INTENT OF DESIGN AND SHALL PROVIDE THE OWNER WITH A COMPLETE AND FULLY OPERATIONAL ELECTRONIC SECURITY SYSTEM. QUESTIONS REGARDING THE INTENT OF DESIGN SHALL BE

PROMPTLY BROUGHT TO THE ATTENTION OF THE COR.

5 CONDUCTORS SHALL NOT BE LESS THAN #18 AWG, UNLESS OTHERWISE INDICATED. EXCEPTIONS INCLUDE MANUFACTURER-PROVIDED LEADS AND INTERNAL EQUIPMENT WIRING.

6 SECURITY SYSTEM SIGNAL CONDUCTORS SHALL NOT, UNDER ANY CIRCUMSTANCE, BE INSTALLED IN THE SAME CONDUIT AS POWER CONDUCTORS.

7 WIRE FILL, CONDUCTORS, AND CONDUIT SHALL BE SIZED BY THE CONTRACTOR, EXCEPT WHERE SIZE IS INDICATED, AND SHALL BE INSTALLED ACCORDING TO THE NATIONAL ELECTRICAL CODE, AS WELL AS ALL STATE AND LOCAL CODES HAVING JURISDICTION. NUMBER OF CONDUCTORS REQUIRED MAY VARY BASED ON THE SPECIFIC MANUFACTURER'S EQUIPMENT SELECTED BY THE CONTRACTOR. MINIMUM CONDUIT SIZE SHALL BE 1/2 INCH.

8 ALL 120 VOLT INPUT POWER FOR POWER SUPPLIES AND OTHER SYSTEM COMPONENTS SHALL BE PROVIDED. THE SECURITY CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF SECURITY SYSTEM POWER REQUIREMENTS.

120 VOLT INPUT POWER FOR ALL ESS SHALL BE DEDICATED.

9 ALL SECURITY WIRING SHALL BE CONSISTENTLY COLOR-CODED AND TAGGED. COORDINATION OF EXACT WIRE CODING AND TAGGING IS MANDATORY. THE SECURITY CONTRACTOR IS DIRECTLY RESPONSIBLE FOR COORDINATING WIRING FROM EQUIPMENT HARDWARE MANUFACTURERS TERMINAL STRIPS TO THE FINAL CONNECTION POINTS OF EQUIPMENT WITHIN SCOPE OF THE PROJECT.

10 THE SECURITY CONTRACTOR SHALL PROVIDE ALL REQUIRED PROGRAMMING, AND SHALL COORDINATE WITH THE OWNER ALL HARDWARE AND SOFTWARE PROGRAMMING FEATURES WHICH DICTATE OR OTHERWISE INFLUENCE USER

OPERATION OR FUNCTIONALITY OF THE ELECTRONIC SECURITY SYSTEM.

11 REQUIREMENTS FOR CONDUCTORS AND CONDUITS SIZES AND QUANTITIES MAY VARY WITH THE SELECTION AND PLACEMENT OF SECURITY EQUIPMENT. CONDUCTORS AND CONDUIT SIZES AND QUANTITIES ARE SUGGESTIVE ONLY AND DO NOT NECESSARILY REPRESENT WHAT WILL OR SHOULD BE INSTALLED. GC SHALL BE RESPONSIBLE FOR PROVIDING ACTUAL CONDUCTOR AND CONDUIT SIZES AND QUANTITIES ON SHOP DRAWING SUBMITTAL. THE SECURITY CONTRACTOR SHALL COORDINATE WITH THE DIVISION 26 SUBCONTRACTOR, ALL CONDUIT SIZES, QUANTITIES, AND LOCATIONS, AS WELL AS ALL POWER SUPPLY AND EQUIPMENT LOCATIONS THAT NEED A CIRCUIT NOT SHOWN ON THE

PLANS.

12 THE SCOPE FOR INTRUSION DETECTION SYSTEM INCLUDES THE DATA CENTER AND ALL NEW TELECOM ROOMS. THE CONTRACTOR SHALL PROVIDE NEW INTRUSION DETECTION DEVICES AS DEPICTED ON THE DRAWINGS. THE CONTRACTOR IS RESPONSIBLE FOR ALL EXPANSION BOARDS, SUB PANELS, INTERCONNECTIONS, POWER SUPPLIES, ETC NECESSARY TO CONNECT THE NEW DEVICES AS SHOWN TO THE EXISTING INTRUSION DETECTION SYSTEM

PANEL.

13 THE SCOPE FOR THE ACCESS CONTROL SYSTEM INCLUDES THE NEW DOORS TO THE DATA CENTER AS WELL AS EVERY DOOR TO THE NEW TELECOM ROOMS THROUGHOUT THE PROJECT. THE CONTRACTOR SHALL PROVIDE THE MOST CURRENT 2-DOOR ACCESS CONTROL SYSTEM CONTROL PANEL THAT TIES INTO THE EXISTING SITE ACCESS CONTROL SYSTEM. THE SITE CURRENTLY UTILIZES THE SOFTWARE HOUSE iSTAR ACCESS CONTROL SYSTEM. THE NEW 2-DOOR CONTROLLERS SHALL PROVIDE A MINIMUM OF 100MBPS CONNECTION TO THE DATA NETWORK. WITHIN EACH NEW TELECOM ROOM AND DATA CENTER THE CONTRACTOR SHALL PROVIDE A CONNECTION FROM THE NEW ACCESS SYSTEM CONTROLLER TO THE GFGI PROVIDED NETWORK SWITCH THAT IS LOCATED IN THE NEW TELECOM RACK.

1. REMOVE CABLING AND ASSOCIATED PATCH PANELS FROM EXISTING

TR'S AFTER NEW INFRASTRUCTURE IS INSTALLED AND

OPERATIONAL.

2. REMOVE ALL ABANDONED TELECOMMUNICATIONS CABLING FROM

EXISTING TR'S. EXISTING FIBER CABLE IS EXEMPT FROM THIS

REQUIREMENT.

3. IN AREAS TO BE RENOVATED FOR NEW TR'S, EXISTING WORK AREA

OUTLETS SHALL BE DEMOLISHED AND REMOVED. CABLING, JACKS

AND FACEPLATES SHALL BE REMOVED BY THE TELECOM

CONTRACTOR. PATHWAYS (CONDUIT, BOXES, ETC.) SHALL BE

REMOVED BY THE ELECTRICAL CONTRACTOR - SEE ELEC PLANS.

4. ALL OTHER EXISTING NON-TELECOM SYSTEMS TO REMAIN IN

EXISTING TR'S IAW TABLE BELOW.

5. REFER TO INSTALLATION/CONSTRUCTION PROCEDURES IN PROJECT

PHASING PLAN IN ARCHITECTURAL SET FOR ADDITIONAL DEMOLITION

DETAILS

DEMO AND REMOVEEXISTING HORIZONTAL COPPER TO W AO'S AND W AP'S

EQUIPMENT OR SUBSYSTEM DEMO OR TO

REMAIN

EXISTING HORIZONTAL COPPER PATCH PANELS TO W AO'S AND WAP'S

TO REMAIN

TO REMAIN

EXISTING TR DEMOLITION

EXISTING RACKS

EXISTING UPS IN REUSED TR'S

EXISTING DOOR SECURITY DEVICES AND CCTV CAMERA

EXISTING UPS

EXISTING BACKBONE FIBER

EXISTING PCU (FOR SECURITY INCLUDING CCTV)

DEMO AND REMOVE

TO REMAIN

DEMO AND REMOVE

EXISTING BACKBONE COPPER TO REMAIN

TO REMAIN

TO REMAIN

VA

N

#4

WATER METER

E

CB

CB

CBCB

B20

B8

B9

B9A

B6

B106

B120

B22

B133

BT36

B100

B100A

B103A

B103

B114

B5

B122

B21

BT25

B105

T1

T2

T7 T4

T71

T70

T69

T68

T67

T64

T65

T66

T63

T62

T61T60

T59

T58

T53

T52

T51

T50

T46

T47

T45

T43

T42

T41

T40

T39

T38

T36

T37 T33

T35

T22

T34 T21

T20

T19

T23

T25

T24

T29T26

T18

T27

T57

T28

T55

T56

VARO

T30

T31 T32

T54

T8T9

T10

T11

T12

T15

T13

T16

T17

T14

HH

HH

HH

MH

MH

MH

EMH

EMH

EMH

HH

HH

HH

HH

HH

HH

HH

HH

HH

HH

HH

HH

HH HH

HH

HH

HH

HH

HH

HH

HH

HH HH

HH

HH

HH

HH

HH

HH

B7

2 2

2 2

19 23

T-28

EHH

MH

MH

T3

HH

T5T6

MH

HH

T44

T48

T49

Location

Issue Date

Specialized Engineering Solutions

1300 Baxter Street, Suite 355

Charlotte, NC 28204

544-20-107PROJECT # 544-20-107

EHRM INFRASTRUCTURE UPGRADES

www.atriaxgroup.com

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

COLUMBIA VAMC, COLUMBIA, SC

VA FORM 08 - 6231

A

F ile

P a th

/1

/2

:3

:0

P M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TG002

OVERALL SITE PLAN

CJF

CJF JRQ

SCALE: 1 : 100

F1

OVERALL SITE PLAN

KEYNOTES

HH

NEW 48 INCH BY 48 INCH

BY 48 INCH HANDHOLE

SITE LEGEND

EHH

EMH

MH

EXISTING MAINTENANCE HOLE

EXISTING HANDHOLE

NEW 12FOOT BY 7FOOT BY 6FOOT

MAINTENANCE HOLE

(6) NEW 4" PVC CONDUIT

GENERAL NOTES

A. TYPICAL DEPTH OF DUCTBANK IS TO BE 36 INCHES BELOW GRADE.

B. PROVIDE (2) NEW 4 INCH CONDUITS FROM NEAREST MH/HH TO

BUILDINGS UNLESS OTHERWISE NOTED.

C. THIS PROJECT REQUIRES THE CONTRACTOR TO INSTALL TW O

FULLY REDUNDANT AND GEOGRAPHICALLY DIVERSE FIBER FEEDS

(A FEED AND B FEED) TO EACH TELECOM ROOM IN EACH BUILDING.

THE SITE INFRASTRUCTURE HAS BEEN DESIGNED SUCH THAT THE

A FEED AND THE B FEED FOR ANY INDIVIDUAL TELECOM ROOM

SHALL NOT RUN IN THE SAME CONDUIT, OR IN THE SAME

DUCTBANK, OR IN THE SAME MANHOLE/HANDHOLE.

D. OSP CABLING SHALL BE COILED A MINIMUM OF ONE TIME AROUND

EACH MH/HH IT PASSES THROUGH.

E. ALL DUCTBANK SHOW N IS TO BE CONCRETE ENCASED.

F. ALL DUCTBANKS SHALL HAVE 100% SPARE CAPACITY AFTER FIBER

CABLE INSTALLATION, I. E. 6-WAY DUCTBANK SHALL HAVE A

MINIMUM OF (3) EMPTY DUCTS, EACH WITH A PULL STRING; 4-W AY

DUCTBANK SHALL HAVE A MINIMUM OF (2) EMPTY DUCTS, EACH

WITH A PULL STRING, AND 2-WAY DUCTBANK SHALL HAVE ONE

(1) EMPTY DUCT WITH A PULL STRING.

B6 - CIRCUIT AT1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T28-T30-T32-T36-T40-T43-T44

TELECOM DUCT SEGMENT PATHWAY DESTINATION

TO

ORIGIN

FROM

B6 - CIRCUIT B T66-T65-T64-T63-T62-T61-T60-T58-T52-T50-T48-T46-T47

B100 LA108 (A)

B100 LA108 (B)

B7 - CIRCUIT A B100 LA108 (A)

B7 - CIRCUIT B B100 LA108 (B)

B8 - CIRCUIT A B100 LA108 (A)

B8 - CIRCUIT B B100 LA108 (B)

B9 - CIRCUIT A B100 LA108 (A)

B9 - CIRCUIT B B100 LA108 (B)

B20 - CIRCUIT AB100 LA108 (A)

B20 - CIRCUIT B B100 LA108 (B)

B21 - CIRCUIT AB100 LA108 (A)

B21 - CIRCUIT B B100 LA108 (B)

B105 - CIRCUIT AB100 LA108 (A)

B105 - CIRCUIT B B100 LA108 (B)

B122 - CIRCUIT AB100 LA108 (A)

B122 - CIRCUIT B B100 LA108 (B)

B133 - CIRCUIT AB100 LA108 (A)

B133 - CIRCUIT B B100 LA108 (B)

BT25 - CIRCUIT AB100 LA108 (A)

BT25 - CIRCUIT B B100 LA108 (B)

BT36 - CIRCUIT AB100 LA108 (A)

BT36 - CIRCUIT B B100 LA108 (B)

VARO - CIRCUIT AB100 LA108 (A)

VARO - CIRCUIT B B100 LA108 (B)

T1-T2-T3-T4

BUILDING OSP CABLE ROUTING

(4) NEW 4" PVC CONDUIT

(2) NEW 4" PVC CONDUIT

EXISTING CONDUIT TO BE REUSED

1. (6) NEW 4 INCH CONCRETE ENCASED DUCTBANK CONDUITS WITH

(3) PACKS OF 3-3" FABRIC MESH INNERDUCTS IN EACH DUCT

CONTAINING NEW FIBER CABLE(S).

2. (4) NEW 4 INCH CONCRETE ENCASED DUCTBANK CONDUITS WITH

(3) PACKS OF 3-3" FABRIC MESH INNERDUCTS IN EACH DUCT

CONTAINING NEW FIBER CABLE(S).

3. (2) NEW 4 INCH CONCRETE ENCASED DUCTBANK CONDUITS WITH

(3) PACKS OF 3-3" FABRIC MESH INNERDUCTS IN EACH DUCT

CONTAINING NEW FIBER CABLE(S).

4. EXISTING CONDUIT PATHWAY TO BE REUSED.

5. CORRIDOR PATHWAY LOCATIONS. CONDUITS TO BE INSTALLED

ABOVE CEILING THROUGH CORRIDORS. REFER TO DRAWING TN608

FOR CONDUIT SIZES AND QUANTITIES FOR EACH CORRIDOR

ROUTE.

T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T28-T30-T32-T36-T40-T43-T45-T48-T49

T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T28-T30-T32-T36-T37

T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T28-T30-T32-T36-T38-T39

T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T20-T22

T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T28-T30-T31

T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T24-T26

T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T23-T27-T57-T54-T53

T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T20-T21

T1-T2-T5-T7-T8-T9-T10-T11-T12-T15-T18-T19

T1-T2-T5-T7-T8-T9-T10-T11-T12-T13-T14

T66-T65-T64-T63-T62-T61-T60-T58-T52-T51

T66-T65-T64-T63-T62-T61-T60-T58-T52-T50-T48-T45-T43-T42

T66-T65-T64-T63-T62-T61-T60-T58-T52-T50-T48-T45-T43-T41

T66-T65-T64-T63-T62-T61-T60-T58-T52-T50-T48-T45-T43-T40-T36-T33-T35

T66-T65-T64-T63-T62-T61-T60-T58-T54-T55-T56

T66-T65-T64-T63-T62-T61-T60-T58-T54-T57-T28-T29

T66-T65-T64-T63-T62-T61-T60-T58-T54-T57-T27-T23-T18-T15-T12-T11-T10-T9-T8-T7-T6

T66-T65-T64-T63-T62-T61-T60-T59

T66-T65-T64-T63-T62-T61-T60-T58-T52-T50-T48-T45-T43-T40-T36-T33-T34

T66-T65-T64-T63-T62-T61-T60-T58-T54-T57-T27-T24-T25

T66-T65-T64-T63-T62-T61-T60-T58-T54-T57-T27-T23-T18-T16-T17

24 SM OS2 CORR - A/B

STRAND

COUNT

SM = SINGLE MODE

MM = MULTIMODE

OS2 = SM FIBER TYPE

OM4 = MM FIBER TYPE

OSP = PATHWAY EXTERNAL TO

BUILDING

CORR = CORRIDOR PATHWAY

INTERNAL TO BUILDING

100A

103A

VARO

BUILDING 100

9A

T36

24 SM OS2 OSP - A

(3) 24 SM OS2 CORR - A

(3) 24 SM OS2 CORR - B

24 SM OS2 OSP - A

24 SM OS2 OSP - A

24 SM OS2 OSP-B

24 SM OS2 OSP - A

24 SM OS2 OSP-B

24 SM OS2 OSP - A

24 SM OS2 OSP-B

(3) 24 SM OS2 CORR - A

(3) 24 SM OS2 CORR - B

24 SM OS2 OSP-B

24 SM OS2 OSP-B

24 SM OS2 OSP

24 SM OS2 OSP-B

24 SM OS2 OSP - A

24 SM OS2 OSP-B

24 SM OS2 OSP - A

24 SM OS2 OSP-B

(3) 24 SM OS2 CORR - A

(3) 24 SM OS2 CORR - B

(2) 24 SM OS2 CORR - A

(2) 24 SM OS2 CORR - B

(1) 24 SM OS2 CORR - A

(1) 24 SM OS2 CORR - B

(4) 24 SM OS2 CORR - A

(4) 24 SM OS2 CORR - B

24 SM OS2 CORR - A

24 SM OS2 CORR - B

24 SM OS2 CORR - A

24 SM OS2 CORR - B

24 SM OS2 OSP - A

24 SM OS2 OSP-B

(2) 24 SM OS2 OSP - A

(2) 24 SM OS2 OSP-B

T25

24 SM OS2 OSP - A

24 SM OS2 OSP-B

24 SM OS2 OSP - A

24 SM OS2 OSP-B

A = PRIMARY BACKBONE CONNECTION

B = REDUNDANT BACKBONE CONNECTION

Location

Issue Date

Specialized Engineering Solutions

1300 Baxter Street, Suite 355

Charlotte, NC 28204

544-20-107PROJECT # 544-20-107

EHRM INFRASTRUCTURE UPGRADES

www.atriaxgroup.com

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

COLUMBIA VAMC, COLUMBIA, SC

VA FORM 08 - 6231

A

F ile

P a th

/1

/2

:3

:0

P M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TG003

SITE OSP CONNECTIVITY

DIAGRAM

CJF

CJF JRQ

SCALE: NONE

F1

SITE OSP CONNECTIVITY DIAGRAM

GENERAL NOTES

A. THIS PROJECT REQUIRES THE CONTRACTOR TO INSTALL TW O

FULLY REDUNDANT AND GEOGRAPHICALLY DIVERSE FIBER FEEDS

(A FEED AND B FEED) TO EACH TELECOM ROOM IN EACH BUILDING.

THE SITE INFRASTRUCTURE HAS BEEN DESIGNED SUCH THAT THE

A FEED AND THE B FEED FOR ANY INDIVIDUAL TELECOM ROOM

SHALL NOT RUN IN THE SAME CONDUIT, OR IN THE SAME

DUCTBANK, OR IN THE SAME MANHOLE/HANDHOLE.

B. THE CONTRACTOR SHALL INSTALL THE FIBER FROM THE DATA

CENTER TO EACH TELECOM ROOM IN EACH BUILDING AS A

HOMERUN. THERE SHALL BE NO INTERMEDIATE CONNECTION

POINTS FOR ANY FIBER RUN BETW EEN THE DATA CENTER AND THE

END DESTINATION. IF THE CONTRACTOR, FOR ANY REASON,

REQUIRES A SPLICE MID-RUN IN THE FIBER, THEY MUST SUBMIT A

WRITTEN REQUEST TO DO SO FOR EACH INSTANCE.

C. THE CONTRACTOR IS REQUIRED TO LABEL THE FIBER PER THE

SPECIFICATIONS. FIBER SHALL BE LABELED ON EACH END AND

WITHIN EACH PULL POINT (MANHOLE/HANDHOLE). SEE NOTE 'D'

BELOW FOR ADDITIONAL DOCUMENTATION REQUIREMENTS.

D. THE CONTRACTOR IS REQUIRED TO LABEL ALL MANHOLES AND

HANDHOLES AS W ELL AS EACH SECTION OF DUCBANK AND EACH

DUCT WITHIN THE DUCTBANK. THE CONTRACTOR SHALL PROVIDE

AN EXCEL FILE TO THE COR AT THE END OF THE PROJECT STATING

FOR EACH FIBER WHAT THE SOURCE IS, W HAT THE DESTINATION

IS, WHAT MANHOLE/HANDHOLES IT RUNS THROUGH BETWEEN

SOURCE AND DESTINATION, AND W HAT DUCT THE CABLE IS

LOCATED IN WITHIN EACH DUCTBANK. THE CONTRACTOR SHALL

ALSO PROVIDE AS-BUILT BUTTERFLY DIAGRAMS TO THE VA WITH

BOTH GRAPHICAL DEPICTIONS AND PHOTOS OF THE AS-BUILT

CONDITION. BUTTERFLY DIAGRAMS ARE NOT REQUIRED TO HAVE

THE CABLES IDENTIFIED BUT SHALL HAVE ALL

MANHOLE/HANDHOLE, DUCTBANK, AND DUCT LABELS.

SLOPESLOPE

S L

O P

E S

L O

P E

OPENING

GROUND ROD

L E

N G

T H

OPENING

MANHOLE

FRAME AND COVER

RATED CONCRETE

COLLAR (AS REQUIRED

TO BRING COVER TO

GRADE LEVEL)

CABLE PULL RING

EARTH

OPENING

PVC SLEEVE FOR

GROUND ROD (TYP)

LONG COPPER CLAD

STEEL GROUND ROD (TYP)

SUMP REINFORCED CONCRETE

SIDE WALL DUCT ENTRANCE

DUCT TERMINATOR (TYP)

CABLE TRAY (TYP)

SLOPESLOPE

WIDTH

H E

IG

H

T

6'-0"

SLOPE

S L

O P

E

SLOPE

S L

O P

E

OPENING

GROUND ROD

L E

N G

T H

WIDTH

4'-0"

1" PVC SLEEVE FOR

GROUND ROD

3/4" x 10' LONG COPPER

CLAD STEEL GROUND ROD

SUMP REINFORCED CONCRETE

DUCT WINDOW

SIDE WALL DUCT ENTRANCE

DUCT TERMINATOR

CABLE PULL RING

CABLE RACK

SLOPESLOPE

OPENING

EARTH

NOTES: HANDHOLE OVERALL DIMENSION MUST BE A MINIMUM 4' X 4' X 4' (WxLxD), FULLY ENCLOSED EXCEPT FOR DRAINAGE AND CONSTRUCTED OF CONCRETE. HANDHOLE COVER MUST BE LABELED "COMMUNICATIONS" AND MUST BE LOCKABLE WITH A GSA

APPROVE PADLOCK.

NOTE:

1. ALL SCHEDULE 40 PVC DUCTS MUST BE ENCASED IN

CONCRETE.

2. ALL DUCTS STUBBED THROUGH MANHOLE / HAND HOLE

WALLS MUST BE TERMINATED AND SEALED VIA DUCT

TERMINATORS.

3. UNUSED DUCTS MUST BE STUBBED OUT AND CAPPED VIA

A SOLVENT WELDED CONDUIT CAP.

4. ORIENTATION OF MANHOLES / HAND HOLES MUST BE

COORDINATED WITH THE DUCTBANK APPROACH.

5. DEPTH OF DUCTBANKS ARE PROVIDED AS A MINIMUM

FOR GENERAL INFORMATION. REFER TO CIVIL PLANS FOR

PROFILES AND ACTUAL DUCT DEPTH.

6. DUCT ARRANGEMENTS IN THESE DETAILS ARE PROVIDED

FOR GENERAL INFORMATION. REFER TO DUCTBANK

SECTIONS FOR ACTUAL QUANTITIES AND

ARRANGEMENTS.

7. MANHOLE / HAND HOLE COVERS MUST BE H-20 RATED.

12"

MAGNETIC WARNING

TAPE (TYPICAL)

3' MINIMUM DEPTH

FINISHED SURFACE OR GRADE

6" SEPARATION

MINIMUM (TYPICAL)

3" SEPARATION

MINIMUM (TYPICAL)

3" SEPARATION

MINIMUM (TYPICAL)

4" SCHEDULE 40

PVC UON (TYPICAL)

BASE AND INTERMEDIATE

SPACERS HORIZONTALLY ALONG

LENGTH OF DUCTBANK.

3" MINIMUM

(TYPICAL ALL SIDES)

3000 PSI CONCRETE

T#

DUCTBANK SECTION KEY

CONDUIT PURPOSE:

T = TELECOM

SP = SPARE

T1 4"

T2 4"

T3 4"

T4 4"

T5 4"

SP

4"

DUCTBANK SECTION CONDUCTOR

IDENTIFICATION. SEE DUCTBANK

SECTION KEY BELOW .

NOTE: THIS DETAIL IS TYPICAL FOR ALL DUCTBANKS. REFER TO DUCTBANK SECTIONS FOR CONDUIT SIZES AND QUANTITIES

4"

CONDUIT TRADE SIZE

CONDUIT NUMBER

#4 HOOP REBAR

(STIRRUPS) 18" ON CENTER

#4 LONGITUDINAL REBAR

(TYPICAL, EACH CORNER)

CRUSHED STONE AS

NEEDED FOR LEVELING

3" SEPARATION

MINIMUM (TYPICAL)

A. LEVEL SURFACE.

DOUBLE SLOPE TO BET NOT LESS THAN 1:300 DOW N TOWARDS MANHOLES

B. AVERAGE GRADE.

SINGLE SLOPE

SINGLE SLOPE TO BE NOT LESS THAN 1:300

C. VERY STEEP GRADE.

SLOPE TO CONFORM TO GRADE.

96" MIN.

METHOD OF GRADING : TRENCHES SHALL BE UNIFORMLY GRADED. INSTALL

CONDUIT RUNS SO THAT ANY W ATER SEEPING INTO THE CONDUIT, AS WELL AS

LATERALS TO POLES, BUILDINGS, EQUIPMENT PADS, AND VAULTS WILL DRAIN

INTO MANHOLES OR HANDHOLES.

DOUBLE SLOPE

96" MIN. INNERDUCT

TRIPLE PACK

INSTALL

NOTE:

INSTALLATION OF

CABLE

INTO INNERDUCT

FABRIC

INNERDUCT

CELLS ARE CONNECTED

WITH A COLOR CODED

STITCH ALONG THE ENTIRE

LENGTH

TAPE IS COLOR

CODED AND

MARKED FOR

FOOTAGE

1. THE CONDUITS IN THE TOP

ROW OF ALL DUCTBANKS

AND SINGLE CONDUIT

DUCTBANKS SHALL CONTAIN

A INNERDUCT TRIPLE PACK.

NOT

ALLOWED

NOT

ALLOWED

NOT

ALLOWED

NOT

ALLOWED

MANHOLE MANHOLE

MANHOLE MANHOLE

STRAIGHT THROUGH SAME CORNER

OPPOSITE CORNERS SAME WALL

Location

Issue Date

Specialized Engineering Solutions

1300 Baxter Street, Suite 355

Charlotte, NC 28204

544-20-107PROJECT # 544-20-107

EHRM INFRASTRUCTURE UPGRADES

www.atriaxgroup.com

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

COLUMBIA VAMC, COLUMBIA, SC

VA FORM 08 - 6231

A

F ile

P a th

/1

/2

:3

:0

P M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TG004

DETAILS

CJF

CJF JRQ

SCALE: NONE

F1

TYPICAL MANHOLE DETAIL

SCALE: NONE

C1

TYPICAL HANDHOLE DETAIL

SCALE: NONE

F8

TYPICAL TELECOM DUCTBANK SECTION DETAIL

SCALE: NONE

C5

DUCTBANK GRADING DETAILS

SCALE: NONE

C7

INNERDUCT DETAIL

SCALE: NONE

F6

MANHOLE CABLE ROUTING

SLOTTED CHANNEL STRUT CONDUIT

SUPPORT MUST BE 1-1/2" X 1-1/2"

DRILLED STEEL OR SIMILAR. ATTACH TO

FLEX TRAY WITH CARRIAGE BOLT AND

FLEX TRAY "SUPPORT WASHER"

CONDUIT MAY BE ATTACHED IN MULTIPLE

FASHIONS ALONG FLEX TRAY ASSEMBLY.

ALL ATTACHMENTS MUST BE

ELECTRICALLY BONDED.

CONDUIT CLAMP BRACKET WITH

INSULATING BUSHING ON CONDUIT

END.

3/8" GALVANIZED

THREADED ROD

SUPPORT

WIRE MESH

STYLE CABLE

TRAY. SIZE AS

NOTED ON

FLOOR PLANS

THREADED ROD

SUPPORT

HOLD DOWN CLAMP,

BOLT AND NUT

6" LONG SLEEVE TO

PREVENT DAMAGE TO

CABLES

LOCKING NUT

NOTES:

REFER TO CABLE TRAY PLANS FOR DIMENSIONS AND

PLACEMENT.

VOICE AND DATA

NETW ORKS

WALL

SLAB ABOVE

WALL MOUNT BRACKET

INSTALL MIN. 6" ABOVE FINISHED CEILING TO

ALLOW FOR CEILING TILE REMOVAL

LABEL FIELD (TYP.)

PROVIDE SINGLE GANG, FOUR

POSITION, MODULAR FACEPLATE

FOR EACH WORK AREA OUTLET

X#

BLANK (TYP.)

MODULAR

RJ-45 JACK

(TYP.) TYPICAL WORK AREA OUTLET

FACEPLATE SYMBOLS

SEE OUTLET SCHEDULES FOR OUTLET

DEFINITIONS

MINIMUM OUTLET

CONFIGURATIONS:

(2) RJ-45 MODULAR JACKS

PROVIDE OTHER COPPER AND FIBER

OPTIC CONFIGURATIONS TO SUPPORT

SPECIAL OR LEGACY

TELECOMMUNICATIONS SYSTEMS

WHEN REQUIRED

REFER TO COMMUNICATIONS OUTLET

TYPE SCHEDULE FOR CABLE AND

OUTLET QUANTITIES AND

CONFIGURATIONS

X# X#

STANDARD CONFIGURATION IS TW O

RJ-45 MODULAR JACKS AND TWO

BLANKS FOR FUTURE APPLICATIONS

WIRE ALL TERMINATIONS TO TIA 568-

C.0, T568A CONFIGURATION

PROVIDE (#) CATEGORY 6A UTP

CABLES FROM OUTLET TO SERVING

TELECOM ROOM (TR)

CONCRETE CEILING OR SLAB

ANCHOR

BOLT (TYP)

3/8" THREADED

STEEL ROD (TYP)

STEEL

CONDUIT (TYP)

NOTES:

1. FOR SUPPORTS THAT SPAN OVER 3'-0" AND

CONTAIN LARGER THAN 2" CONDUIT, PROVIDE

CENTER HANGER ROD SUPPORT.

STRUT CONDUIT

CLAMP (TYP)

1-5/8" X 1-5/8"

GALVANIZED SLOTTED

CHANNEL STRUT

LOCKING NUT

PROVIDE (1) RJ-45 CATEGORY 6A UTP CABLE

FROM OUTLET TO TR. MOUNT AT 48" A.F.F.

UNLESS OTHERW ISE NOTED.

LABEL FIELD

(TYP.)

MODULAR

RJ-45 JACK

X#

TELEPHONE

MOUNTING STUDS

TELEPHONE

MOUNTING STUDS

IDENTIFICATION LABEL (TYP.)

(1) MODULAR

RJ-45 JACK

SURFACE-MOUNTED

"BISCUIT" TYPE OUTLET

GENERAL NOTES:

1. THIS INSTALLATION SHALL ONLY OCCUR IN LOCATIONS WITH

ACCESSIBLE CEILING OR WHERE CEILING DOES NOT EXIST.

2. CABLING SHALL BE ROUTED SUCH THAT IT IS ACCESSIBLE FROM

END TO END.

3. PROVIDE 10' SERVICE LOOP, COILED IN CEILING SPACE.

X# PROVIDE (1) CATEGORY 6A UTP

CABLES FROM CEILING MOUNTED

OUTLET FOR WIRELESS ACCESS

POINT (WAP) TO NEAREST TR.

X#X#

EXTERIOR WALL

FINISHED GRADE

INTERIOR FLOOR LEVEL

CONDUITS ENTERING

BUILDING

PVC TO RGS

COUPLING

PROVIDE ANNULAR JOINT,

PACKED WITH LOOSE MINERAL

FIBER OR GLASS FIBER AND

CAULKED ON BOTH SIDES WITH

WEATHERPROOF SEALANT

DUCTBANK

REFER TO SITE PLAN

FOR SIZING

BUILDING

FOUNDATION WALL

PVC

PVC

RGS

RGS

EXTERIOR WALL

EXTERIOR NEMA 4X

JUNCTION BOX

RGS

RGS

EMT

EMT

FINISHED CEILING

RGS TO EMT

COUPLING

NOTES:

1. FOR MULTIPLE CONDUIT PENETRATIONS,

PACK VOID SPACE W ITH LOOSE MINERAL

FIBER OR GLASS FIBER AND CAULK ON

BOTH SIDES WITH WEATHERPROOF

SEALANT.

2. FOR AREAS WITH FINISHED CEILINGS

INSTALL CONDUITS ABOVE ACCESSIBLE

CEILING.

EXTERIOR WALL

FINISHED GRADE

INTERIOR FLOOR LEVEL

OPENING FOR CONDUITS

THROUGH BASEMENT W ALL

SEAL WITH WATERTIGHT

SEALING MATERIAL

BUILDING

FOUNDATION WALL

CONDUITS ENTERING

BASEMENT AREA OF

BUILDING

PROVIDE ANNULAR JOINT,

PACKED WITH LOOSE MINERAL

FIBER OR GLASS FIBER AND

CAULKED ON BOTH SIDES WITH

WEATHERPROOF SEALANT

EMT

EMT

RGS TO EMT

COUPLING

PVC TO RGS

COUPLING

DUCTBANK

PVC

PVC

RGS

RGS

BUILDING STEEL

SERVICE

EQUIP.

EARTH ELECTRODE SYSTEM (EES)

BUILDING STEEL

PANELBOARD

PRIMARY

BONDING

BUSBAR

(PBB)

PANELBOARD

PANELBOARD

SECONDARY

BONDING

BUSBAR

(SBB)

PANELBOARD

TELECOMMUNICATIONS ROOM (TR)

TELECOMMUNICATIONS ROOM (TR)

TELECOMMUNICATIONS ROOM (TR)

TELECOM BONDING BACKBONE (TBB)

SEE NOTE

NOTE:

THE IMPEDANCE OF THE TBB INCREASES WITH LENGTH THEREBY

REDUCING ITS ABILITY TO EQUALIZE POTENTIALS BETWEEN TR'S.

THE TBB FOR A LARGE SITE OR LONG RUNS MAY BE VERY COSTLY

TO ACHIEVE. AS AN ALTERNATIVE THE SBB IN EACH TR CAN BE

BONDED TO THE ELECTRICAL PANEL BOARD IN THE TR AND TO

STRUCTURAL STEEL W HERE APPLICABLE. INSTALL BONDING

CONDUCTORS IN THE SHORTEST AND MOST DIRECT PATHS

FEASIBLE.

1. PROVIDE 6 AWG RACK BONDING CONDUCTOR

(RBC) FROM EACH RACK BONDING BUSBAR (RBB)

TO THE 6 AWG TELECOMMUNICATIONS EQUIPMENT

BONDING CONDUCTOR (TEBC) USING

IRREVERSIBLE CRIMP CONNECTORS. PROVIDE

TEBC TO THE PBB/SBB. PROVIDE 6 AWG UNIT

BONDING CONDUCTORS (UBC) FROM EACH PIECE

OF INDIVIDUAL EQUIPMENT WITHIN RACK TO RBB

OR RBC. USE TWO-HOLE COMPRESSION LUGS FOR

ALL RACK CONNECTIONS WHERE POSSIBLE BUT

NO MODIFICATION OF THE RACK OR EQUIPMENT IS

ALLOWED.

2. PROVIDE INSULATED GROUND CABLE FROM

GROUND BAR TO BUILDING STRUCTURE.

EXOTHERMICALLY WELD CABLE TO METAL

STRUCTURE. SIZE CABLE IAW TABLE BELOW .

3. PROVIDE INSULATED GROUND CABLE FROM SBB

TO LOCAL PANELBOARD GROUND BAR. SIZE CABLE

IAW TABLE BELOW.

4. PROVIDE INSULATED GROUND CABLE TBB FROM

PBB TO FURTHEST SBB . CABLE SHALL BE

CONTIGUOUS. SIZE CABLE IAW TABLE BELOW.

5. PROVIDE A CRIMP CONNECTOR WITH TWO BOLT

HOLES FOR SECURING THE TBB CABLE TO THE PBB

OR SBB.

6. PROVIDE INSULATED GROUND CABLE FROM THE

PBB TO THE MAIN GROUNDING ELECTRODE

SYSTEM AT THE SWITCHBOARD. SIZE CABLE IAW

TABLE BELOW .

7. CABLE TRAY BONDING CONDUCTOR WITH

IRREVERSIBLE CRIMP CONNECTOR TO PBB/SBB.

KEYNOTES#

TELECOMMUNICATIONS ROOM (TR)

SECONDARY

BONDING

BUSBAR

(SBB)

SECONDARY

BONDING

BUSBAR

(SBB)

14-20 21-26 27-33 34-41 42-52 53-66 67-84

85-105 106-125 126-150 151-175 176-250 251-300

TBB/GE LINEAR LENGTH (FT) TBB/GE SIZE (AWG)

TBB CONDUCTOR SIZE VS LENGTH

1/0 2/0 3/0 4/0

250 KCMIL

300 KCMIL

350 KCMIL

500 KCMIL

600 KCMIL

750 KCMIL

CABLE LADDER

EQUIPMENT RACK

WITH ACTIVE

EQUIP.

RBB

UBC TO

RACK AND

EACH PIECE

OF EQUIP.

TEBC

CABLE LADDER

EQUIPMENT RACK

WITH ACTIVE

EQUIP.

RBB

UBC TO

RACK AND

EACH PIECE

OF EQUIP.

TEBC

CABLE LADDER

EQUIPMENT RACK

WITH ACTIVE

EQUIP.

RBB

UBC TO

RACK AND

EACH PIECE

OF EQUIP.

RBC

TEBC

CABLE LADDER

EQUIPMENT RACK

WITH ACTIVE

EQUIP.

RBB

UBC TO

RACK AND

EACH PIECE

OF EQUIP.

TEBC

RBC

RBC

RBC

Location

Issue Date

Specialized Engineering Solutions

1300 Baxter Street, Suite 355

Charlotte, NC 28204

544-20-107PROJECT # 544-20-107

EHRM INFRASTRUCTURE UPGRADES

www.atriaxgroup.com

Atriax, pllc 102 3rd Avenue, NE PO Box 1629, Hickory, NC 28603 Phone: 828.315.9962 Fax: 828.315.9964

NC Engineering License No.: P-0214 NC Architectural License No.: 51254 07/14/2022

Project Number

Building Number

Drawing Number

Project Title

Checked Drawn

Drawing Title

Approved:

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

Revisions: Date:

Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com

FOR OFFICIAL USE ONLY (FOUO)

FOR OFFICIAL USE ONLY (FOUO)

COLUMBIA VAMC, COLUMBIA, SC

VA FORM 08 - 6231

A

F ile

P a th

/1

/2

:3

:0

P M

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TG005

DETAILS

CJF

CJF JRQ

SCALE: NONE

F6

TYPICAL CONDUIT TO CABLE TRAY CONNECTION DETAIL

SCALE: NONE

C6

TYPICAL W ORK AREA OUTLET (W AO) FACEPLATE DETAIL

SCALE: NONE

D6

TYPICAL TRAPEZE STYLE CONDUIT SUPPORT

SCALE: NONE

C8

TYPICAL W ALL MOUNT PHONE FACEPLATE DETAIL

SCALE: NONE

D8

TYPICAL CEILING MOUNTED OUTLET

SCALE: NONE

C1

TYPICAL TELECOM DUCTBANK EXTERIOR TRANSITION INTO

BUILDING

SCALE: NONE

C3

TYPICAL TELECOM DUCTBANK TRANSITION INTO BASEMENT

SCALE: 12" = 1'-0"

F1

TYPICAL TELECOM GROUNDING AND BONDING

INFRASTRUCTURE DETAIL

1" CONDUIT STUBBED INTO TOP OF

DOOR FRAME FOR BALANCED

MAGNETIC SWITCH (BMS)

MIN. 1" CONDUIT TO NEW

ACS/ IDS PANEL WITHIN

TR

6" X 6" SECURITY JUNCTION BOX FOR

SECURITY DOOR INTERFACE MODULE

SURFACE MOUNT JUNCTION BOX ON SECURE

SIDE OF DOOR 6" ABOVE FINISHED CEILING

OR 30" ABOVE DOOR FRAME WHEN NO

CEILING IS AVAILABLE. COORDINATE

LOCATION WITH MECHANICAL EQUIPMENT IN

AREA.

ACS

JUNCTION

BOX

1" CONDUIT TO CARD

READER/ KEYPAD (CR/KP)

JUNCTION BOX

RECESSED DOUBLE GANG

JUNCTION BOX WITH SINGLE

GANG MOUNTING RING FOR

CARD READER/ KEYPAD

(CR/KP) MOUNT AT 48 INCHES

A.F.F. UNLESS OTHERWISE

NOTED

BMS

CR/KP

EL

1" CONDUIT TO ELECTRIC

STRIKE (EL)

REX

1" CONDUIT FOR REX

PLEASE REFER TO

THE ARCHITECURAL

DOOR HARDWARE

SCHEDULE

MIN. 1" CONDUIT WITH CAT

6A CABLING FROM

CAMERA TO EXISTING

SSTV TELECOM ROOM

LOCATION

DOME CAMERA:

MOUNT CAMERA IN A POSITION

TO PREVENT GLARE FROM

OVERHEAD LIGHTING.

SSTV

FINISHED WALL

SURFACE MOUNTED

DEEP SINGLE GANG

JUNCTION BOX

SSTV

CEILING SLAB

C R

/K P

EL

B M

S

CR/KP

EL

BMS

CARD READER/ KEYPAD JUNCTION BOX WITH

MIN. 1" CONDUIT FROM ACS/IDS JUNCTION BOX

LOCATED ABOVE TR DOOR TO NEW PREMISE

CONTROL UNIT LOCATION.

SYMBOL LEGEND:

ELECTRONIC LOCK WITH MIN. 1" CONDUIT

FROM ACS/IDS JUNCTION BOX LOCATED ABOVE

TR DOOR TO NEW PREMISE CONTROL UNIT

LOCATION.

BALANCED MAGNETIC SWITCH W ITH MIN. 1"

CONDUIT FROM ACS/IDS JUNCTION BOX

LOCATED ABOVE TR DOOR TO NEW PREMISE

CONTROL UNIT LOCATION.

DOME STYLE SECURITY CAMERA.

R E

X

REX REQUEST TO EXIT DEVICE WITH MIN. 1"

CONDUIT FROM ACS/IDS JUNCTION BOX

LOCATED ABOVE TR DOOR TO NEW PREMISE

CONTROL UNIT LOCATION.

PCU

PCU PREMISE CONTROL UNIT FOR ACS/IDS SYSTEM

DEVICES. WILL REQUIRE DEDICATED 20A

CIRCUIT PROVIDED BY ELECTRICAL.

NEW TR

CR/KP

EL

BMS

REX

PCU

SW

EXISTING

TCP/IP

NETWORK

EQUIPMENT

RACKSW RACK MOUNTED SW ITCH FOR SECURITY

CPP RACK MOUNTED COPPER PATCH PANEL

CPP

X

NOTE: COORDINATE WITH LOCAL SECURITY CONTRACTOR

CPP

SW

X

VMS

X

EXISTING

TCP/IP

NETWORK

NEW DOME

STYLE CAMERA

CPP

SW

VMS

NEW CAT 6A

CABLING

EXISTING COPPER PATCH PANEL

EXISTING OWNER PROVIDED SSTV

SWITCH

EXISTING OWNER PROVIDED VIDEO

MANAGEMENT SYSTEM

EXISTING TR IN BULDINGS WITH

EXISTING CAMERA SWITCH

SYMBOL LEGENDNEW TR

EQUIPMENT

RACK

CPP

SW

X

VMS

X

EXISTING

TCP/IP

NETWORK

NEW DOME

STYLE CAMERA

NEW CAT 6A

CABLING

DATA CENTER B100 NEW TR IN BUILDINGS WITH NO EXISTING CAMERA

SWITCH (B5, B6, B8, B20, BT36, B105 AND VARO)

EQUIPMENT

RACK

SM OSP FIBER

10/100/1000 MEDIA

CONVERTER

FPP

10/100/1000 MEDIA

CONVERTER

CAT 6A CABLING

SM OS2 JUMPER

EQUIPMENT

RACK

FPP

SM OS2 JUMPER

RACK/ ENCLOSURE

RACK MOUNTED UPS

ZONE

PDU

RACKED EQUIPMENT

RACKED EQUIPMENT

RACKED EQUIPMENT

POWER

SUPPLY 1

POWER

SUPPLY 2

LEG A

BUS B

RACK/ ENCLOSURE

RACK MOUNTED UPS

RACKED EQUIPMENT

RACKED EQUIPMENT

RACKED EQUIPMENT

POWER

SUPPLY 1

POWER

SUPPLY 2

LEG B

BUS A

NOTE:

RACKS/ ENCLOSURES WILL HAVE A/B

REDUNDANT L21-30 CIRCUITS FOR THE

PAIR OF NETW ORK RACK/ ENCLOSURES,

WITH A 30A ZONE PDU SERVING THE PAIR

AND A/B REDUNDANT 20A RACK PDU'S TO

DISTRIBUTE THE POWER IN EACH RACK

B SIDE

VERTICAL RACK

MOUNTED PDU

A SIDE

VERTICAL RACK

MOUNTED PDU

RACK/ ENCLOSURE

RACK MOUNTED UPS

RACKED EQUIPMENT

RACKED EQUIPMENT

RACKED EQUIPMENT

POWER

SUPPLY 1

POWER

SUPPLY 2

BUS B

BUS A

FOR TR'S WITH ONE NETW ORK RACK FOR TR'S WITH TWO NETWORK RACKS

NOTE:

RACK/ ENCLOSURE WILL HAVE

A/B REDUNDANT L21-20

CIRCUITS FOR THE NETWORK

RACK/ ENCLOSURE, WITH A/B

REDUNDANT 20A RACK PDU'S

TO DISTRIBUTE THE POWER IN

THE RACK

B SIDE

VERTICAL RACK

MOUNTED PDU

A SIDE

VERTICAL RACK

MOUNTED PDU

KEY

BUS A: COMMERCIAL POWER

BRANCH CIRCUIT

BUS B: GENERATOR POWER BRANCH

CIRCUIT (WHERE AVAILABLE)

LEG A/B: A AND B DISTRIBUTION LEGS

OF THE ZONE PDU

POWER SUPPLY 1/2: REDUNDANT

POWER SUPPLIES IN EACH PIECE OF

IT EQUIPMENT

MIN. 1" CONDUIT TO CABLE

TRAY OR NEAREST TELECOM

ROOM (TR)

4-11/16 INCHES…