This file is an electrical drawing set attachment related to the EHRM Infrastructure Upgrades Construction solicitation number 36C77623R0096 issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The solicitation seeks construction services for infrastructure upgrades at the Columbia, South Carolina VA Medical Center and involves electrical work. The attachment contains electrical drawings for the project, including site plans, schematics and diagrams to support bidding on the opportunity. Offerors should review the drawings along with the solicitation documents to understand the full scope of requirements for the infrastructure upgrade construction project at the medical center.
View the file
Other files for this federal contract opportunity
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A. BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 75' SHALL UTILIZE #10 AWG CONDUCTORS.
RECEPTACLE BRANCH CIRCUITS WITH A TOTAL LENGTH LONGER THAN 150' SHALL UTILIZE #8 AWG
CONDUCTORS.
B. FOR ALL CONDUIT AND OTHER ITEMS PENETRATING A FIRE RATED WALL, PROVIDE UL LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM THAT IS SPECIFIC TO THE WALL CONSTRUCTION ASSEMBLY AND COMPLIANT WITH ASTM E814. INSTALL SYSTEM IN STRICT COMPLIANCE WITH THE FIRE STOPPING MANUFACTURER’S U.L. APPROVED DETAIL. WHERE EXISTING WALLS ARE BEING UPGRADED TO FIRE RATED WALLS OR THE FIRE RATING IS BEING MODIFIED, PROVIDE U.L. LISTED THROUGH PENETRATION FIRE STOPPING SYSTEM FOR ALL NEW AND EXISTING PENETRATIONS. REFER TO THE ARCHITECTURAL LIFE
SAFETY PLANS FOR LOCATIONS OF FIRE RATED WALLS.
C. NEW ROOF MOUNTED EQUIPMENT SHALL BE BONDED TO EXISTING BUILDING LIGHTNING PROTECTION SYSTEM IF ONE EXISTS. PROVIDE AIR TERMINALS ON TOP OF EQUIPMENT AND BOND TO EXISTING SYSTEM PER NFPA 780 AND UL 96A REQUIREMENTS. PROVIDE UL INSPECTION AND/OR LPI SYSTEM INSPECTION AS REQUIRED TO OBTAIN UL MASTER LABEL RECERTIFICATION, UL MASTER LABEL AND/OR LPI SYSTEM
CERTIFICATE.
D. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO ADDITIONAL
COST TO THE OWNER.
E. NEW WIRING DEVICES AND ASSOCIATED COVERPLATES SHALL MATCH EXISTING FINISH OF SIMILAR
INSTALLED DEVICES.
F. THE SELECTED EQUIPMENT AIC RATINGS ARE BASED ON THE IMPEDANCES FOR CONDUCTORS AND TRANSFORMERS USED IN THE CALCULATIONS. IF DIFFERENT EQUIPMENT OR DIFFERENT CONFIGURATIONS
ARE SELECTED FOR INSTALLATION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATELY RATED EQUIPMENT THAT MEETS APPLICABLE SELECTIVE COORDINATION GOALS AND
PROVIDES SIMILAR INCIDENT ENERGY RISK OF ARC FLASH HAZARDS.
G. PROVIDE AN INSULATED CONTINUOUS COPPER CONDUCTOR, NOT SMALLER THAN #10, TO BOND ALL
NORMAL AND ESSENTIAL ELECTRICAL SYSTEM PANELBOARDS TOGETHER THAT SERVE THE SAME
INDIVIDUAL PATIENT VICINITY AS DEFINED IN NEC 517.14.
H. ALL CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, INCLUDING LIGHTING AND WALL RECEPTACLES, SHALL BE MECHANICALLY PROTECTED PER NEC 517.31(C)(3). NON-FLEXIBLE RACEWAY SHALL BE USED FOR CRITICAL AND LIFE SAFETY BRANCH CIRCUITS, EXCEPT THAT THE FINAL CONNECTION TO VIBRATING EQUIPMENT OR LIGHT FIXTURES IF THE TOTAL LENGTH OF FLEXIBLE RACEWAY IS 6' OR LESS ACROSS THE
ENTIRE CIRCUIT LENGTH.
I. PROVIDE ADDITIONAL SUPPORTS AS REQUIRED TO INDEPENDENTLY SUPPORT ALL EXISTING TO REMAIN
CABLING.
J. IN AREAS WHERE WORK PENETRATES INTERIOR OR EXTERIOR WALLS, CEILING PANELS, GRID SYSTEMS, GYPSUM CEILINGS AND/OR BULKHEADS, CONTRACTOR SHALL BE REQUIRED TO PATCH AND REPAIR
PENETRATIONS AS A RESULT OF THE WORK.
(GENERAL NOTES SHALL APPLY TO ALL SHEETS)
ELECTRICAL GENERAL NOTES:
ELECTRICAL ABBREVIATIONS
ABBREVIATION DESCRIPTION
REFER TO OTHER SCHEDULES AND NOTES FOR ADDITIONAL ABBREVIATIONS.
MOUNTING HEIGHT TO CENTERLINE (ABOVE FINISHED FLOOR)
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ALUMINUM
AMPERE TRIP
CEILING
CIRCUIT BREAKER
COLOR TEMP CONTROL
COPPER
DATA (WHEN APPLIED TO COMMUNICATIONS OUTLET)
DEMO (WHEN APPLIED TO EXISTING/DEMO ITEMS)
EXISTING
ELECTRICALLY OPERATED
ENERGY REDUCING MAINTENANCE SWITCH
FUSE
FULL LOAD AMPS
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT ALARM
GROUND FAULT PROTECTION
HORSEPOWER
KILOAMPERE INTERRUPTING CAPACITY
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MINIMUM
MAIN LUGS ONLY
MANUALLY OPERATED
NORMALLY CLOSED
NON-FUSED
NOT IN CONTRACT
NORMALLY OPEN
POLES
PARTIAL
RELOCATE
SHORT CIRCUIT CURRENT RATING
SURGE PROTECTIVE DEVICE
SHUNT TRIP
TYPICAL
UNLESS NOTED OTHERWISE
VOICE
WALL PHONE
WIRE
WEATHER RESISTANT
TRANSFORMER
ZONE SELECTIVE INTERLOCKING
A
AF
AFF
AL
AT
C
CB
CCT
CU
D
D
E
EO
ERMS
F
FLA
G, GFCI
GFA
GFP
HP
KAIC
KVA
KW
MAX
MCA
MCB
MIN
MLO
MO
NC
NF
NIC
NO
P
PART
R
SCCR
SPD
ST
TYP
UNO
V
W
W
WR
XFMR
ZSI
REMARKS: (LIGHTING FIXTURE SCHEDULE) APPLIES TO NEW AND EXISTING RELOCATED FIXTURES.
1. EXIT SIGNS - REFER TO ELECTRICAL PLANS FOR DIRECTION INDICATORS AND MOUNTING TYPE.
2. WALL MOUNTING - COORDINATE EXACT LOCATION WITH ARCHITECT AND ARCHITECTURAL DETAILS. COORDINATE FRAMING
AND BOX SUPPORTS PRIOR TO ROUGH-IN FOR EXACT PLACEMENT OF BOX TO ACHIEVE CENTERING AND ALIGNMENT WITH
FINAL ARCHITECTURAL FINISHES.
3. COVE - COORDINATE EXACT QUANTITIES WITH ARCHITECTURAL DETAILS TO PROVIDE CONTINUOUS ILLUMINATION FOR ENTIRE
LENGTH OF COVE.
4. PENDANT/SUSPENSION MOUNTING - COORDINATE EXACT LOCATION, MOUNTING ELEVATION, AND REQUIRED
PENDANT/SUSPENSION LENGTH WITH ARCHITECT AND ARCHITECTURAL DETAILS.
5. IN ROOMS WHERE CEILING HEIGHT IS LESS THAT 10-FT, FIXTURES SHALL BE SURFACE MOUNTED ON CEILING INSTEAD OF
PENDANT MOUNTED.
GENERAL NOTES: (LIGHTING FIXTURE SCHEDULE)
A. CATALOG NUMBER VERIFICATION - CONTRACTOR SHALL VERIFY LIGHTING FIXTURE INSTALLATION REQUIREMENTS
AND CATALOG NUMBER PRIOR TO ORDERING.
B. SUBSTITUTIONS - WHERE INDICATED WITH 'N' (NO), NO SUBSTITUTIONS WILL BE ACCEPTED. WHERE INDICATED WITH
'P' (PRIOR APPROVAL), SUBSTITUTIONS MUST BE APPROVED PRIOR TO BID WITH ACCEPTANCE ISSUED BY ADDENDUM.
WHERE INDICATED WITH 'Y' (YES), THE FOLLOWING MANUFACTURER'S ARE CONSIDERED ACCEPTABLE EQUIVALENT MANUFACTURER'S, PROVIDED THE EQUIVALENT FIXTURE IS OF THE SAME QUALITY, EFFICIENCY, PERFORMANCE AND
CHARACTERISTICS AS THAT SCHEDULED:
1. ACUITY BRANDS
2. EATON/COOPER BRANDS
3. HUBBELL
4. WILLIAMS
5. PHILLIPS/SIGNIFY BRANDS
C. DOWNLIGHT - PROVIDE DOWNLIGHT REFLECTOR FINISH/COLOR AS SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE.
SELECT CEILING TRIM FINISH/COLOR TO COORDINATE WITH CEILING TYPE. "WHITE" TRIM FOR DOWNLIGHTS MOUNTED IN WHITE ACOUSTICAL TILE CEILINGS. "CLEAR" (TO MATCH REFLECTOR FINISH/COLOR) FOR DOWNLIGHTS MOUNTED
IN PAINTED GYPSUM BOARD CEILINGS.
D. COVE – DRAWINGS PROVIDE GENERAL ILLUSTRATION OF COVE LAYOUT. COORDINATE EXACT UNIT LENGTHS AND QUANTITIES WITH ARCHITECTURAL DETAILS TO PROVIDE CONTINUOUS ILLUMINATION FOR ENTIRE LENGTH OF COVE.
LED COVE LIGHTING FIXTURES SHALL BE INSTALLED END-TO-END (NO GAP BETWEEN FIXTURES) WITH A MAXIMUM 6” GAP AT COVE ENDS AND CORNERS. SELECT UNIT LENGTHS AND QUANTITIES TO ACHIEVE THE ABOVE REQUIRED
PERFORMANCE (SHORTER UNIT LENGTHS IN GREATER QUANTITIES MAY BE REQUIRED).
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
FULLY SPRINKLERED
COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc
102 3rd Avenue, NE
PO Box 1629, Hickory, NC 28603
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
NC Architectural License No.: 51254
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Project Director
Revisions: Date:
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
07/14/2022
20375.007 E-000
ELECTRICAL SYMBOLS AND
ABBREVIATIONS 100
CGH CJF07/14/2022
100% CONSTRUCTION
DOCUMENTS
ELECTRICAL FIXTURE
SYMBOLS
PLAN SYMBOL NAME
RECEPTACLE - DOUBLE DUPLEX
- CONV
RECEPTACLE - DUPLEX - CONV
RECEPTACLE - DUPLEX - CONV -
GFCI
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - CONV
RECEPTACLE - DUPLEX -
EMERGENCY (RED) - KNOWN
LOAD
ELECTRICAL FIXTURE SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
JUNCTION BOX - CEILING GENERAL:
PROVIDE JUNCTION BOX AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH JUNCTION BOX TYPE. REFER TO FLOOR PLANS FOR JUNCTION BOX DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE ACCESSIBLE CEILING WHERE NOT INSTALLED IN ACCESSIBLE CEILING. WHERE SHOWN ADJACENT TO CEILING RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 8” BETWEEN BACK BOXES. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS WITHIN CONDUIT TO SOURCE. REFER TO FLOOR PLANS FOR BRANCH
CIRCUIT DESIGNATION.
TYPE 'LIGHT', CEILING PROCEDURE LIGHT:
PROVIDE 20A 120V BRANCH CIRCUIT TO OWNER FURNISHED CEILING PROCEDURE LIGHT AT APPROXIMATE
LOCATION INDICATED. COORDINATE FINAL CONNECTION WITH FINAL EQUIPMENT SELECTION.
TYPE 'SHADE', MOTORIZED SHADE:
PROVIDE 20A 120V BRANCH CIRCUIT TO JUNCTION BOX, MOUNTED IN ACCESSIBLE LOCATION ABOVE CEILING WITHIN 5'0" OF MOTORIZED SHADE MOTOR LOCATION. PROVIDE CONNECTION TO MANUFACTURER FURNISHED JUNCTION BOX LEADS AND MOTOR LEADS. PROVIDE ONE (1) 1" CONDUIT FROM MOTOR LOCATION TO ACCESSIBLE CEILING LOCATION FOR LOW VOLTAGE CONNECTION TO MOTORIZED SHADE CONTROLLER AND ANY APPLICABLE SPLITTERS. MOUNT SPLITTERS IN LOCATION PER MANUFACTURER REQUIREMENTS. COORDINATE WITH FINAL
EQUIPMENT SELECTION.
TYPE 'EWC-1', ELECTRIC WATER COOLER, REMOTE CHILLER:
PROVIDE 20A 120V BRANCH CIRCUIT TO REMOTE CHILLER, MOUNTED ABOVE FINISHED CEILING. PROVIDE WITH
TOGGLE SWITCH DISCONNECTING MEANS. COORDINATE WITH FINAL EQUIPMENT SELECTION.
JUNCTION BOX - WALL GENERAL:
PROVIDE JUNCTION BOX AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH JUNCTION BOX TYPE. REFER TO PLANS FOR JUNCTION BOX DESIGNATION. PROVIDE ONE (1) 4" SQUARE, 2-1/8" DEEP JUNCTION BOX WITH SINGLE GANG TRIM RING AND BLANK WALL PLATE WITH ONE (1) 1” CONDUIT TO ABOVE FINISHED CEILING WHERE NOT INDICATED OTHERWISE. WHERE SHOWN ADJACENT TO RECEPTACLES ON FLOOR PLANS, PROVIDE MAXIMUM 12” BETWEEN BACK BOXES. WHERE SHOWN AS PART OF BRANCH CIRCUIT, PROVIDE CONDUCTORS
WITHIN CONDUIT TO SOURCE INDICATED ON FLOOR PLANS.
TYPE 'EWC-1', ELECTRIC WATER COOLER:
PROVIDE [DUPLEX RECEPTACLE] [JUNCTION BOX] AT APPROXIMATE LOCATION INDICATED. MOUNT AT [CONFIRM HEIGHT]" AFF. COORDINATE EXACT MOUNTING LOCATION WITH ADA REQUIREMENTS, FINAL PLUMBING FIXTURE SELECTION, AND PLUMBING CONTRACTOR INSTALLATION LOCATION TO CONCEAL BEHIND EQUIPMENT PANEL.
TYPE ‘FF’, MODULAR FURNITURE FEED POWER CONNECTION:
PROVIDE JUNCTION BOX WITH WALL PLATE AND FLEXIBLE CONDUIT CONNECTION FOR POWER TO MODULAR FURNITURE AT APPROXIMATE LOCATION INDICATED. CIRCUIT MODULAR FURNITURE TO 20A 120V BRANCH CIRCUITS IN ASSOCIATED BRANCH PANEL. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS. COORDINATE CONDUIT SIZE REQUIRED WITH QUANTITY OF BRANCH CIRCUIT. ISOLATE BRANCH CIRCUIT CONDUCTORS FROM OTHER BRANCHES. POWER CONNECTION SHALL BE TERMINATED TO MODULAR FURNITURE PER MANUFACTURER REQUIREMENTS. PROVIDE ALL NECESSARY ACCESSORIES FOR CONNECTION TO MODULAR FURNITURE FEED WHIP.
COORDINATE REQUIREMENTS WITH MODULAR FURNITURE MANUFACTURER. PROVIDE VOICE/DATA FURNITURE FEED ADJACENT TO POWER FURNITURE FEED PER PLANS. PROVIDE MAXIMUM 12” BETWEEN BACK BOXES.
COORDINATE EXACT MOUNTING LOCATION WITH ARCHITECT AND MODULAR FURNITURE FINAL LOCATION.
TYPE ‘H’, HORIZONTAL:
PROVIDE JUNCTION BOX DESCRIBED ABOVE, MOUNTED HORIZONTALLY TO ACCOMMODATE BUILDING
CONSTRAINTS.
TYPE 'LIGHT', CEILING PROCEDURE LIGHT WALL-MOUNTED CONTROLLER:
PROVIDE ROUGH-IN FOR CEILING PROCEDURE LIGHT WALL-MOUNTED CONTROLLER, FURNISHED BY PROCEDURE LIGHT MANUFACTURER. MOUNT BACK BOX AT 48" AFF. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL
EQUIPMENT SELECTION.
TYPE 'SHADE', MOTORIZED SHADE WALL-MOUNTED CONTROLLER:
PROVIDE ROUGH-IN FOR WALL-MOUNTED SHADE CONTROLLER, FURNISHED BY CONTROLLER MANUFACTURER.
MOUNT BACK BOX AT 48" AFF. COORDINATE ROUGH-IN REQUIREMENTS WITH FINAL EQUIPMENT SELECTION.
TYPE 'TUBE', PNEUMATIC TUBE STATION:
PROVIDE DUPLEX RECEPTACLE AT APPROXIMATE LOCATION INDICATED, CIRCUITED TO CRITICAL BRANCH CIRCUIT INDICATED ON FLOOR PLANS. COORDINATE MOUNTING HEIGHT AND FINAL CONNECTION REQUIREMENTS WITH FINAL EQUIPMENT SELECTION. PROVIDE NETWORK DATA CONNECTION, MOUNTED ADJACENT TO DUPLEX RECEPTACLE. [PNEUMATIC TUBE SYSTEM INFORMATION IS PRELIMINARY AT THIS TIME. PROVIDE ADDITIONAL 20A 120V HARD-WIRED CRITICAL BRANCH CIRCUIT FOR PNEUMATIC TUBE SYSTEM TRANSFER STATION FOR EACH TUBE STATION LOCATION. PROVIDE 20A, 120V TOGGLE SWITCH DISCONNECT SWITCH AT EACH TRANSFER STATION LOCATION. PROVIDE ONE (1) XXA, XXXV BRANCH CIRCUIT TO SERVE PNEUMATIC TUBE BLOWER FOR ENTIRE SYSTEM. PROVIDE XXA, XXXV NON-FUSED DISCONNECT SWITCH AT BLOWER LOCATION. PROVIDE 3-#XX, #XX GND IN X/X"C. EXACT BRANCH CIRCUITS, SOURCE, AND LOCATIONS ARE TO BE DETERMINED WITH FINAL EQUIPMENT
SELECTION.]
TYPE ‘USB’, POWER USB ONLY DEVICE:
PROVIDE [PASS & SEYMOUR CATALOG # TM8USB4**CC6] [HUBBELL CATALOG # USB4**] FOUR (4) PORT USB TYPE A CHARGING DEVICE OR PRIOR APPROVED EQUIVALENT AT THIS LOCATION. DEVICE SHALL MATCH COLOR OF OTHER WIRING DEVICES PER SPECIFICATION. PROVIDE 4" SQUARE BACK BOX WITH SINGLE GANG TRIM RING AND 3/4" CONDUIT TO SOURCE. COORDINATE BACK BOX DEPTH WITH FINAL DEVICE SELECTION. SUBMIT SHOP DRAWINGS FOR APPROVAL. REFER TO MANUFACTURER INSTALLATION INSTRUCTIONS FOR ADDITIONAL DETAILS.
TYPE 'DISH', DISHWASHER:
PROVIDE 20A 120V ELECTRICAL CONNECTION FOR DISHWASHER AT APPROXIMATE LOCATION INDICATED, MOUNTED WITHIN ADJACENT CABINET. ELECTRICAL CONNECTION SHALL NOT BE ROUGHED-IN BEHIND DISHWASER LOCATION.
PROVIDE 20A, 1 POLE GFCI PROTECTED CIRCUIT BREAKER. COORDINATE MOUNTING LOCATION AND FINAL
CONNECTION REQUIREMENTS WITH MANUFACTURER AND FINAL EQUIPMENT SELECTION.
RECEPTACLE - NEMA OUTLET -
CEILING MOUNTED
PROVIDE ONE (1) 4" SQUARE, 2 1/8" DEEP JUNCTION BOX WITH 1 GANG TRIM RING. PROVIDE CONDUIT TO ELECTRICAL SOURCE SIZED AS INDICATED BELOW. REFER TO FLOOR PLANS FOR ELECTRICAL SOURCE AND NEMA
DESIGNATION. PROVIDE DEVICE, FEEDER, AND CIRCUIT BREAKER AS LISTED BELOW:
NEMA L21-20: 4#12, #12 GND IN 3/4" CONDUIT; 20A, 3 POLE CIRCUIT BREAKER
NEMA L21-30: 4#10, #10 GND IN 3/4" CONDUIT; 30A, 3 POLE CIRCUIT BREAKER
FOR TR ROOMS WITH NO CABLE TRAY DIRECTLY ABOVE RACKS, PROVIDE A DROP CORD WITH KELLUMS GRIP AND RECEPTACLE NOTED FOR RACK POWER. FOR TR ROOMS WITH CABLE TRAY DIRECTLY ABOVE RACKS, MOUNT
RECEPTACLE DIRECTLY TO CABLE TRAY.
SURFACE RACEWAY - POWER GENERAL:
PROVIDE SURFACE RACEWAY AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH SURFACE RACEWAY TYPE. REFER TO PLANS FOR RACEWAY DESIGNATION. PROVIDE GFCI TYPE RECEPTACLES WHERE LOCATED WITHIN 6'-0" OF SINK EDGE. PROVIDE RACEWAY LENGTH PER PLANS. MOUNT 5" ABOVE BACKSPLASH WHERE INDICATED ABOVE COUNTERTOP. MOUNT AT 48" AFF AT ALL OTHER LOCATIONS, UNLESS OTHERWISE INDICATED. PROVIDE MINIMUM ONE (1) [20A 120V BRANCH CIRCUIT FOR EACH 10'-0" OF RACEWAY][15A 120V BRANCH CIRCUIT FOR EACH 8'-0" OF RACEWAY] REFER TO PLAN SHEETS FOR CIRCUIT DESIGNATIONS. COORDINATE REQUIREMENTS WITH RACEWAY MANUFACTURER. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION, INCLUDING BUT NOT LIMITED TO: END CAPS, COUPLINGS, AND SUPPORTS. CONCEAL ALL CONDUITS IN ADJACENT WALL. COORDINATE EXACT MOUNTING HEIGHT AND LOCATION WITH ARCHITECTURAL ELEVATIONS. [WHERE RACEWAYS ARE LOCATED ON PRE-CAST CONCRETE WALLS, ROUTE CONDUITS IN ASSOCIATED VERTICAL UTILITY COLUMN PROVIDED WITH THE LABORATORY FURNITURE. WHERE NOTED WITH 'OSC', MOUNT RACEWAY ON OVERHEAD SERVICE CARRIER. OVERHEAD SERVICE CARRIER IS PROVIDED AS LABORATORY EQUIPMENT. PROVIDE SURFACE MOUNTED CONDUIT SECURED TO OVERHEAD SERVICE CARRIER FOR VERIFICATION ROUTING TO
CEILING.]
TYPE 'SR#', 20A STEEL RACEWAY:
PROVIDE WIREMOLD SERIES 2400 PLUGMOLD SINGLE CHANNEL STEEL SURFACE RACEWAY. PROVIDE WITH IVORY FINISH. PROVIDE WITH SIMPLEX RECEPTACLES LOCATED 0'-6" ON CENTER. PROVIDE 3'-0", 5'-0", AND 6'-0" SECTIONS
COUPLED TOGETHER TO MATCH OVERALL LENGTHS INDICATED ON PLANS.
TYPE 'SR#', 15A STEEL RACEWAY:
PROVIDE WIREMOLD SERIES 2000 (OR PRIOR APPROVED EQUIVALENT) PLUGMOLD SINGLE CHANNEL STEEL SURFACE RACEWAY. PROVIDE WITH [BLACK][IVORY][GRAY][WHITE][STAINLESS STEEL] FINISH. PROVIDE WITH SIMPLEX RECEPTACLES LOCATED 0'-6" ON CENTER. PROVIDE 3', 5', AND 6' SECTIONS COUPLED TOGETHER TO
MATCH OVERALL LENGHTS INDICATED ON PLANS.
TYPE 'SR#', 15A ALUMINUM RACEWAY:
PROVIDE WIREMOLD SERIES AL2000 (OR PRIOR APPROVED EQUIVALENT) PLUGMOLD SINGLE CHANNEL ALUMINUM SURFACE RACEWAY. PROVIDE WITH ANODIZED FINISH. PROVIDE WITH SIMPLEX RECEPTACLES LOCATED 0'-6" ON CENTER. PROVIDE 4', 5', AND 6' SECTIONS COUPLED TOGETHER TO MATCH OVERALL LENGHTS INDICATED ON
PLANS.
LIGHTING DEVICE SYMBOLS
PLAN SYMBOL NAME
LIGHT SWITCH
OCCUPANCY SENSOR - CEILING
SWITCH - VACANCY SENSOR
ELECTRICAL MISC SYMBOLS
PLAN SYMBOL NAME
BRANCH CIRCUIT CONCEALED IN
CEILING OR WALL
BRANCH CIRCUIT CONCEALED IN
FLOOR OR BELOW GRADE
CABLE TRAY
CLEARANCE SPACE
CONDUIT BREAK
CONDUIT DOWN
CONDUIT STUB-OUT
CONDUIT UP
HOMERUN TO PANEL
G = GFCI CIRCUIT
(PART) = PARTIAL CIRCUIT
SWITCHED RECEPTACLE
LIGHTING FIXTURE
SYMBOLS
PLAN SYMBOL NAME
AREA POLE LIGHT
CEILING FAN
DOWNLIGHT FIXTURE
EMERGENCY HATCH
EMERGENCY LIGHTING - WALL
EXIT SIGN - CEILING
CHEVRONS AS SHOWN
INDUSTRIAL STRIP LIGHT
TROFFER - RECESSED
TROFFER - SURFACE MOUNT
ELECTRICAL EQUIPMENT
SYMBOLS
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
ENCLOSED CIRCUIT BREAKER -
SURFACE
ENCLOSED DISCONNECT
SWITCH - NON-FUSED
PANELBOARD - SURFACE
SWITCHBOARD
TRANSFORMER - DRY TYPE
UPS CABINET
ONE LINE SYMBOL
PLAN SYMBOL NAME
AUTOMATIC TRANSFER SWITCH
CONTINUATION
DISCONNECT SWITCH
GROUND BAR
GROUNDING ELECTRODE
PANEL BOARD
SWITCHBOARD
SWITCHBOARD/SWITCHGEAR
SWITCHBOARD/SWITCHGEAR -
DOUBLE TUB
TRANSFORMER
UPS PANEL
COMMUNICATION SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
MUSIC SPEAKER - CEILING PROVIDE PUBLIC ADDRESS & DISTRIBUTED MUSIC COMBINATION CEILING SPEAKER, FLUSH MOUNTED AT APPROXIMATE LOCATION INDICATED ON FLOOR PLANS, CENTERED WITHIN CEILING TILE. [PROVIDE SPEAKER WITH INTEGRAL VOLUME CONTROL.] PROVIDE ONE (1) 1" CONDUIT TO NEAREST ACCESSIBLE CEILING SPACE WHEN MOUNTED WITHIN AN INACCESSIBLE CEILING. PROVIDE CABLING FROM ASSOCIATED [ELECTRICAL] [COMMUNICATIONS] ROOM PUBLIC ADDRESS AMPLIFIER. PROVIDE PUBLIC ADDRESS CABLES, CONDUCTORS, BACK CAN, TILE BRIDGES, POWER AMPLIFIERS, AND SPEAKERS PER SPECIFICATION SECTION 275116. PUBLIC ADDRESS SYSTEM SHALL BE PROVIDED WITH PRIORITY OVERRIDE PAGING TO MUTE MUSIC FOR PUBLIC ADDRESS PAGES REGARDLESS OF AREA VOLUME CONTROLS. PROVIDE ALL ACCESSORIES FOR A COMPLETE INSTALLATION. REFER
TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
LIGHTING FIXTURE SCHEDULE
MARK DESCRIPTION SUBS MANUFACTURER CATALOG # (NOTE A)
LAMP /
NOMINAL
LUMENS CCT
MINIMUM
CRI VOLTAGE
INPUT
WATTS MOUNTING REMARKS
I4 4-FT INDUSTRIAL STRIP. MOUNT AT 10'-0" A.F.F.
UNLESS NOTED OTHERWISE.
Y LITHONIA CLX-L48-4000LM-HEF-RDL-MVOLT-GX10-4
0K-80CRI-WH
4000 LM LED 4000K 80 120 V 25 CEILING SUSPENDED 4,5
I4E SAME AS I4, PROVIDE WITH EMERGENCY
BATTERY. MOUNT AT 10'-0" A.F.F. UNLESS NOTED
OTHERWISE.
Y LITHONIA CLX-L48-4000LM-HEF-RDL-MVOLT-GX10-4
0K-80CRI-WH-PS1050
4000 LM LED 4000K 80 120 V 25 CEILING SUSPENDED 4,5
SECURITY SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
CREDENTIAL CARD READER GENERAL:
PROVIDE PROXIMITY CARD READER [AS DESCRIBED IN THESE GENERAL NOTES AND NOTES BELOW FOR EACH CARD READER TYPE] AT APPROXIMATE LOCATION INDICATED. [REFER TO FLOOR PLANS FOR CARD READER DESIGNATION.] PROVIDE ROUGH-IN PER ACCESS CONTROL ROUGH-IN DETAIL. WHERE SHOWN MOUNTED ON DOOR/WINDOW SYSTEM MULLION, PROVIDE MULLION MOUNT CARD READER SURFACE MOUNTED ON MULLION.
CABLING SHALL BE ROUTED RECESSED WITHIN MULLION TO ACCESSIBLE CEILING SPACE. COORDINATE INSTALLATION WITH MULLION MANUFACTURER. CARD READERS SHALL BE RATED FOR CONTINUOUS OPERATION IN THEIR INSTALLED PROJECT CONDITIONS AS REQUIRED IN SPECIFICATION SECTION 281300. SUBMIT SHOP DRAWINGS FOR APPROVAL. COORDINATE EXACT LOCATION OF CARD READER WITH ARCHITECT, ARCHITECTURAL INTERIOR ELEVATIONS, AND OTHER DOOR COMPONENTS INCLUDING BUT NOT LIMITED TO PUSH PLATE ACTUATORS, REQUEST TO EXIT PUSH BUTTONS, INTERCOM STATIONS, NURSE CALL CANCEL STATIONS, INTRUSION DETECTION KEYPADS, WANDER PREVENTION KEYPADS, AND INFANT PROTECTION KEYPADS. REFER TO ACCESS
CONTROL SYMBOL LEGEND DESCRIPTION FOR CABLING AND ADDITIONAL REQUIREMENTS.
TYPE ‘KEYPAD’, COMBINATION KEYPAD PROXIMITY CARD READER:
PROVIDE COMBINATION KEYPAD PROXIMITY CARD READER PER SPECIFICATION.
DOORBELL PUSHBUTTON PROVIDE NUTONE MODEL [PB7LSN, SATIN NICKEL FINISH] [PB7LWH, WHITE FINISH] SURFACE MOUNT DOORBELL PUSHBUTTON AT APPROXIMATE LOCATION INDICATED ON PLANS. PROVIDE 4" SQUARE BACK BOX MOUNTED AT 48" AFF WITH SINGLE GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR CABLING. PROVIDE CABLING PER DOORBELL CHIME SYMBOL LEGEND DESCRIPTION. COORDINATE TRIM RING SIZE WITH MANUFACTURER. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM INCLUDING BUT NOT LIMITED TO INSTALLATION, CONFIGURATION, DEVICES, AND CABLING. SUBMIT SHOP DRAWINGS FOR APPROVAL.
COORDINATE EXACT LOCATION OF CHIME WITH ARCHITECT AND ARCHITECTURAL INTERIOR ELEVATIONS.
INTERCOM - AUDIO GENERAL:
PROVIDE AUDIO INTERCOM SYSTEM COMPONENTS AS DESCRIBED IN THESE GENERAL NOTES AND THE NOTES BELOW FOR EACH DEVICE TYPE AT LOCATIONS INDICATED. REFER TO FLOOR PLANS FOR DEVICE DESIGNATION.
PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM. CABLING SHALL BE ROUTED IN CONDUIT CONCEALED WITHIN WALLS AND SUPPORTED EXPOSED ABOVE ACCESSIBLE CEILINGS UTILIZING CABLE TRAY OR J-HOOKS EVERY 10' ON CENTER MINIMUM IN CORRIDOR. SUBMIT SHOP DRAWINGS FOR APPROVAL. INTEGRATE DOOR RELEASE WITH DOOR HARDWARE. REFER TO ACCESS CONTROL AND ARCHITECTURAL DOOR HARDWARE
SPECIFICATIONS FOR COORDINATION OF FEATURES, DEVICES, AND CONNECTIONS REQUIRED.
TYPE 'MS', AUDIO MASTER STATION:
PROVIDE AIPHONE MODEL LEM-3 (OR PRIOR APPROVED EQUIVALENT) WALL-MOUNTED AT LOCATION INDICATED.
PROVIDE 4" SQUARE BACK BOX MOUNTED [5" ABOVE BACKSPLASH AT DESK LOCATION INDICATED] [AT 48" AFF] WITH SINGLE GANG TRIM RING. PROVIDE ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR AUDIO CABLING AND ONE (1) 1" CONDUIT TO POWER SUPPLY LOCATION. [POWER SUPPLY SHALL PLUG INTO DUPLEX RECEPTACLE BELOW DESK. PROVIDE 4" SQUARE BACK BOX MOUNTED AT 18" AFF.] [POWER SUPPLY SHALL PLUG INTO RECEPTACLE, MOUNTED WITHIN UL 2043 LISTED ENCLOSURE ABOVE FINISHED CEILING IN ACCESSIBLE LOCATION. PROVIDE NIGEL B DESIGN MODEL NB-PLWB ENCLOSURE (OR PRIOR APPROVED EQUIVALENT).
ENCLOSURE SHALL INCLUDE NEMA 5-20 RECEPTACLE, MOUNTED WITHIN ENCLOSURE. SERVE FROM 20A 120V BRANCH CIRCUIT INDICATED ON FLOORPLANS. INSTALL PER MANUFACTURER REQUIREMENTS.] PROVIDE WITH
AIPHONE MODEL SKK-620 POWER SUPPLY.
TYPE 'WS', AUDIO WALL STATION:
PROVIDE AIPHONE MODEL [LE-DA FLUSH MOUNT] [LE-D SURFACE MOUNT] AUDIO INTERCOM (OR PRIOR APPROVED EQUIVALENT) WALL MOUNTED AT LOCATION INDICATED. PROVIDE 4" SQUARE BACK BOX MOUNTED AT 48" AFF WITH [TWO] [SINGLE] GANG TRIM RING AND ONE (1) 1" CONDUIT TO ABOVE NEAREST ACCESSIBLE CEILING FOR AUDIO CABLING. PROVIDE 18 AWG, PLENUM RATED, TWISTED PAIR CONDUCTOR FROM MASTER STATION TO WALL STATION.
ELECTRICAL EQUIPMENT SYMBOL LEGEND
PLAN SYMBOL NAME DESCRIPTION
BUS DUCT
DIRECT DIGITAL CONTROL
SYSTEM CONTROL PANEL
CIRCUIT CONTROL PANEL TO 20A 120V BRANCH CIRCUIT IN LOCAL [EQUIPMENT] [NORMAL] BRANCH PANEL OF THE ASSOCIATED CONSTRUCTION PHASE. REFER TO FLOOR PLANS FOR BRANCH CIRCUIT DESIGNATIONS.
COORDINATE CONNECTION REQUIREMENTS WITH FINAL EQUIPMENT SELECTION AND PROVIDED NEMA 5-20 RECEPTACLE OR HARD-WIRED CONNECTION TO CABINET AS REQUIRED. PROVIDE ONE (1) NETWORK DATA CABLE
FROM ASSOCIATED COMMUNICATIONS DISTRIBUTION ROOM.
INDICATES
CONNECTED TO
GENERATOR
Revisions: Date:
5L1A
E-005.1
E
TR
109B
E-005.1
SSCU-209
SSCU-303 SSCU-109B
LOGISTICS MAIL RM
AND PRINTING
TENANT SPACE
MAIL RM AND
PRINTING
LOGISTICS MAIL RM
AND PRINTING
109A
TENANT SPACE
RCC108R
TENANT SPACE
COMM CLO
RCC110R
COMMON CORR
RCC102R
TENANT SPACE
MAIL RM AND
PRINTING
VERTICAL SPACE
STAIR
RCC111R
TENANT SPACE
MAIL RM AND
PRINTING
TENANT SPACE
MAIL RM AND
PRINTING
TENANT SPACE
MAIL RM AND
PRINTING
COMMON CORR
RCC105R
TENANT SPACE USC
RCC107R
EDUCATION STOR
LOGISTICS
RCC106R
TENANT SPACE UCS
FITNESS CENTER
TENANT SPACE UCS
FITNESS CENTER
TENANT SPACE UCS
FITNESS CENTER
TENANT SPACE UCS
FITNESS CENTER
TENANT SPACE
MECH SPACE
104C
TENANT SPACE TLT
RCC104R
TENANT SPACE UCS
FITNESS CENTER
COMMON MECH RM
VERTICAL SPACE
CHASE
RCC102C
VERTICAL SPACE
CHASE
RCC101C
COMMON CORR
RCC101R
VERTICAL SPACE
ELEV
RCC109R
VERTICAL SPACE
ELEV
RCC104C
TENANT SPACE UCS
FITNESS CENTER
VERTICAL SPACE
CHASE
RCC103C
VERTICAL SPACE
STAIR
RCC112R
5TR-109B-A 5TR-109B-B
I4E I4E
SSAH-109B
5TR-109B-B-7
5TR-109B-A-6
5TR-109B-B-6
L21-20 L21-20
5TR-109B-B-1,3,5
5TR-109B-A-1,3,5
TR
109B
R
LOGISTICS
109A
3 4
5TR-109B-B-8
PCU
OV
LOGISTICS
109A
D
D
D
D
R
D
1 6
REMARKS: (EQUIPMENT CONNECTION SCHEDULE)
1.CONTROLS BETWEEN INDOOR AND OUTDOOR UNITS - INCLUDE CONTROL WIRING IN CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT PER MANUFACTURER'S REQUIREMENTS.
2."CONTROL TYPE" - PROVIDE CONTROL AND CONNECTIONS: "INT" = CONTROLS ARE MANUFACTURED INTEGRAL TO THE EQUIPMENT (SELF-CONTAINED).
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
FULLY SPRINKLERED
COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc
102 3rd Avenue, NE
PO Box 1629, Hickory, NC 28603
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
NC Architectural License No.: 51254
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Project Director
Revisions: Date:
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
07/14/2022
20375.007 E-005.1
B5 PARTIAL PLAN - LEVEL 1 -
ELECTRICAL 5
CGH CJF07/14/2022
100% CONSTRUCTION
DOCUMENTS
PLAN
NORTH
SCALE: 1/8" = 1'-0"
LEVEL 1 FLOOR PLAN - ELECTRICAL
SCALE: 1/2" = 1'-0"
ENLARGED NEW PLAN - ROOM TR 109B - BUILDING 5
EQUIPMENT CONNECTION SCHEDULE
MARK DESCRIPTION ROOM NAME ROOM # HP KW FLA MCA MOCP VOLTS PHASE POLES
LOAD
[VA]
CONTROL
TYPE
DISCONNECT
BY
DISCONNECT
TYPE FEEDER PANEL
CIRCUIT
NUMBER SCCR GEN REMARKS
SSAH-109B SPLIT SYSTEM INDOOR UNIT TR 109B 0 0 0 0 0 208 1 2 0 INT CABLE PROVIDED BY MANUFACTURER 5TR-109B-B 2,4 0 No 2
SSAH-209 SPLIT SYSTEM INDOOR UNIT TR 209 0 0 0 0 0 208 1 2 0 INT CABLE PROVIDED BY MANUFACTURER 5TR-209-B 2,4 0 No 2
SSAH-303 SPLIT SYSTEM INDOOR UNIT TR 303 0 0 0 0 0 208 1 2 0 INT CABLE PROVIDED BY MANUFACTURER 5TR-303-B 2,4 0 No 2
SSCU-109B SPLIT SYSTEM CONDENSING UNIT OUTDOORS 0 0 0 19 30 208 1 2 3950 INT EC 30A FUSED 2-#10 CU, #10 CU GND - 3/4"C. 5TR-109B-B 2,4 0 No 1
SSCU-209 SPLIT SYSTEM CONDENSING UNIT OUTDOORS 0 0 0 19 30 208 1 2 3950 INT EC 30A FUSED 2-#10 CU, #10 CU GND - 3/4"C. 5TR-209-B 2,4 0 No 1
SSCU-303 SPLIT SYSTEM CONDENSING UNIT OUTDOORS 0 0 0 19 30 208 1 2 3950 INT EC 30A FUSED 2-#10 CU, #10 CU GND - 3/4"C. 5TR-303-B 2,4 0 No 1
B. BUS B PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
66 A
SPARE CAPACITY:
66 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 15198 A
MEQ-C 3950 VA 125.00% 4938 VA DEMAND CURRENT: 34 A
REC 540 VA 100.00% 540 VA DEMAND LOAD: 12159 VA
PWR-C 5295 VA 125.00% 6619 VA CONNECTED CURRENT: 27 A
LTG 50 VA 125.00% 63 VA CONNECTED LOAD: 9835 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 35 A 32 A 18 A
TOTAL LOAD: 3990 VA 3640 VA 2205 VA
23 24
21 22
19 20
17 18
15 16
13 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 TR ROOM LIGHTING 20 A 1 50 VA 300 VA 1 20 A PCU 8
5 1665 VA 540 VA 1 20 A TR ROOM RECEPTACLE 6
3 1665 VA 1975 VA 4
PDU 20 A 3
1665 VA 1975 VA
2 30 A SSCU-109B
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 5L1A PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: BUILDING 5, ROOM 109B VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 5TR-109B-B
B. BUS A PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
81 A
SPARE CAPACITY:
81 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 8480 A
DEMAND CURRENT: 19 A
DEMAND LOAD: 6784 VA
REC 540 VA 100.00% 540 VA CONNECTED CURRENT: 15 A
PWR-C 4995 VA 125.00% 6244 VA CONNECTED LOAD: 5535 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 14 A 14 A 18 A
TOTAL LOAD: 1665 VA 1665 VA 2205 VA
23 24
21 22
19 20
17 18
15 16
13 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 8
5 1665 VA 540 VA 1 20 A TR ROOM RECEPTACLE 6
3 1665 VA 0 VA 4
UPS 20 A 3
1665 VA 0 VA
2 40 A -- SPARE
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 5L1A PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: BUILDING 5, ROOM 109B VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 5TR-109B-A
SCALE: 1/2" = 1'-0"
ENLARGED DEMO PLAN - ROOM 109A - BUILDING 5
SHEET NOTES:
1. REMOVE ALL EXISTING ELECTRICAL DEVICES AND WIRING BACK TO SOURCE. MAINTAIN
CIRCUITING TO EXISTING DEVICES REMAINING OUTSIDE AREA. REMOVE TELEDATA
CONDUIT AND BOXES IN AREA OF RENOVATION. TELECOM CONTRACTOR WILL REMOVE ALL
WIRING, JACKS, AND COVERPLATES. VISIT SITE TO DETERMINE FULL EXTENT OF
DEMOLITION.
2. REFER TO EQUIPMENT CONNECTION SCHEDULE.
3. PROVIDE RECEPTACLE FOR BUS B. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
4. PROVIDE RECEPTACLE FOR BUS A. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
5. CONNECT TO EXISTING RECEPTACLE CIRCUITING IN AREA.
6. RELOCATE EXISTING 2X4 TO NEW 109A AND PROVIDE NEW WALL SWITCH AT NEW DOOR.
GENERAL NOTES:
A. REFER TO TELECOM, HVAC, AND FIRE PROTECTION DRAWINGS. COORDINATE LOCATION
ON NEW LIGHTING FIXTURES, NEW ELECTRICAL PANELS, AND NEW CABLE TRAY MOUNTED
RECEPTACLES WITH OTHER DISCIPLINES.
5L2A E
E-005.2
3TR
5L2B E
E-005.2
EDUCATION
KITCHEN
VERTICAL SPACE
STAIR
RCC202R
VERTICAL SPACE
ELEV
RCC203R
EDUCATION LOBBY
EDUCATION STAGE
RCC204R
VERTICAL SPACE
CHASE
RCC204R
EDUCATION STOR
VERTICAL SPACE
CHASE
RCC201C
EDUCATION MAIN
HALL
COMMON CORR
RCC201R
VERTICAL SPACE
STAIR
RCC206R
VERTICAL SPACE
STAIR
RCC205R
EDUCATION LOBBY
EDUCATION GREEN
RM
EDUCATION STOR
ENGINEERING
EDUCATION
WOMENS BATH
EDUCATION MENS
BATH
5TR-209-A 5TR-209-B
SSAH-209
I4E
I4E
5TR-209-B-7
NEMA L21-20
NEMA L21-20
5TR-209-B-1,3,5
5TR-209-A-1,3,5
TR
5TR-209-A-6
5TR-209-B-8
PCU
OV
5TR-209-B-6
D
D
D
E
E
E
D
EDUCATION
KITCHEN
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
FULLY SPRINKLERED
COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc
102 3rd Avenue, NE
PO Box 1629, Hickory, NC 28603
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
NC Architectural License No.: 51254
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Project Director
Revisions: Date:
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
07/14/2022
20375.007 E-005.2
B5 PARTIAL PLAN - LEVEL 2 -
ELECTRICAL 5
CGH CJF07/14/2022
100% CONSTRUCTION
DOCUMENTS
PLAN
NORTH
SCALE: 1/8" = 1'-0"
LEVEL 2 FLOOR PLAN - ELECTRICAL
SCALE: 1/2" = 1'-0"
ENLARGED NEW PLAN - ROOM TR 209 - BUILDING 5
B. BUS A PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
81 A
SPARE CAPACITY:
81 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 8480 A
DEMAND CURRENT: 19 A
DEMAND LOAD: 6784 VA
REC 540 VA 100.00% 540 VA CONNECTED CURRENT: 15 A
PWR-C 4995 VA 125.00% 6244 VA CONNECTED LOAD: 5535 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 14 A 14 A 18 A
TOTAL LOAD: 1665 VA 1665 VA 2205 VA
23 24
21 22
19 20
17 18
15 16
13 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 8
5 1665 VA 540 VA 1 20 A TR ROOM RECEPTACLE 6
3 1665 VA 0 VA 4
UPS 20 A 3
1665 VA 0 VA
2 40 A -- SPARE
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 5L2B PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: BUILDING 5, ROOM 209 VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 5TR-209-A
B. BUS B PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
66 A
SPARE CAPACITY:
65 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 15423 A
MEQ-C 3950 VA 125.00% 4938 VA DEMAND CURRENT: 34 A
REC 720 VA 100.00% 720 VA DEMAND LOAD: 12339 VA
PWR-C 5295 VA 125.00% 6619 VA CONNECTED CURRENT: 28 A
LTG 50 VA 125.00% 63 VA CONNECTED LOAD: 10015 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 35 A 32 A 20 A
TOTAL LOAD: 3990 VA 3640 VA 2385 VA
23 24
21 22
19 20
17 18
15 16
13 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 TR ROOM LIGHTING 20 A 1 50 VA 300 VA 1 20 A PCU 8
5 1665 VA 720 VA 1 20 A TR ROOM RECEPTACLE 6
3 1665 VA 1975 VA 4
PDU 20 A 3
1665 VA 1975 VA
2 30 A SSCU-209
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 5L2B PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: BUILDING 5, ROOM 209 VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 5TR-209-B
SCALE: 1/2" = 1'-0"
ENLARGED DEMO PLAN - ROOM 209 - BUILDING 5
SHEET NOTES:
1. REMOVE ALL EXISTING ELECTRICAL DEVICES AND WIRING BACK TO SOURCE. MAINTAIN
CIRCUITING TO EXISTING DEVICES REMAINING OUTSIDE AREA. REMOVE TELEDATA
CONDUIT AND BOXES IN AREA OF RENOVATION. TELECOM CONTRACTOR WILL REMOVE
ALL WIRING, JACKS, AND COVERPLATES. VISIT SITE TO DETERMINE FULL EXTENT OF
DEMOLITION.
2. MAINTAIN CIRCUITING TO WALL SWITCH, LIGHTING FIXTURE, AND RECEPTACLE(S) IN
EXISTING 209 SPACE REMAINING.
3. REFER TO EQUIPMENT CONNECTION SCHEDULE.
4. PROVIDE RECEPTACLE FOR BUS B. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
5. PROVIDE RECEPTACLE FOR BUS A. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
GENERAL NOTES:
A. REFER TO TELECOM, HVAC, AND FIRE PROTECTION DRAWINGS. COORDINATE
LOCATION ON NEW LIGHTING FIXTURES, NEW ELECTRICAL PANELS, AND NEW CABLE
TRAY MOUNTED RECEPTACLES WITH OTHER DISCIPLINES.
5L1A 5TR-109B-A 5TR-109B-B
5L2B 5TR-209-A 5TR-209-B
5L3B 5TR-303-B
INSTALL TWO NEW 100/3
CIRCUIT BREAKERS IN
EXISTING PANEL TO
SERVE NEW PANELS.
INSTALL TWO NEW 100/3
CIRCUIT BREAKERS IN
EXISTING PANEL TO
SERVE NEW PANELS.
INSTALL TWO NEW 100/3
CIRCUIT BREAKERS IN
EXISTING PANEL TO
SERVE NEW PANELS.
5TR-303-A
10N 10N
10N 10N
10N 10N
E
E
E
5L3A
5LDP
E
E
TR
E-005.3
5L3B E
E-005.3
OPEN TO BELOW
EDUCATION
BALCONY
309MED MEDIA
PROJECTOR RM
VERT SPACE STAIR
RCC302R
MED MEDIA
PROJECTOR RM
300A
COMMON CORR
RCC301R
TENANT SPACE I G
TENANT SPACE I G
TENANT SPACE I G
TENANT SPACE I G
301A
TENANT SPACE I G
TENANT SPACE I G
TENANT SPACE I G
TENANT SPACE I G
VERTICAL SPACE
CHASE
RCC302C
VERTICAL SPACE
CHASE
RCC301C
OPEN TO BELOW
EDUCATION STOR
EDUCATION STOR
EDUCATION STOR
EDUCATION STOR
EDUCATION STOR
EDUCATION STOR
EDUCATION STOR
312B
EDUCATION STOR
312A
EDUCATION STOR
310A
VERT SPACE STAIR
RCC303R
SSAH-303
I4E
I4E
5TR-303-A
5TR-303-B
5TR-303-B-7
L21-20
L21-20
5TR-303-A-1,3,5
5TR-303-B-1,3,5
TR
5TR-303-B-6
5TR-303-A-6
PCU
5TR-303-B-8
OV
D
D
D
D
D
TENANT SPACE
STOR
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
FULLY SPRINKLERED
COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc
102 3rd Avenue, NE
PO Box 1629, Hickory, NC 28603
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
NC Architectural License No.: 51254
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Project Director
Revisions: Date:
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
07/14/2022
20375.007 E-005.3
B5 PARTIAL PLAN - LEVEL 3 -
ELECTRICAL 5
CGH CJF07/14/2022
100% CONSTRUCTION
DOCUMENTS
SCALE: NONE
ELECTRICAL ONE-LINE - BUILDING 5
PLAN
NORTH
SCALE: 1/8" = 1'-0"
LEVEL 3 FLOOR PLAN - ELECTRICAL
SCALE: 1/2" = 1'-0"
ENLARGED NEW PLAN - ROOM TR 303 - BUILDING 5
B. BUS B PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
66 A
SPARE CAPACITY:
66 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 15198 A
MEQ-C 3950 VA 125.00% 4938 VA DEMAND CURRENT: 34 A
REC 540 VA 100.00% 540 VA DEMAND LOAD: 12159 VA
PWR-C 5295 VA 125.00% 6619 VA CONNECTED CURRENT: 27 A
LTG 50 VA 125.00% 63 VA CONNECTED LOAD: 9835 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 35 A 32 A 18 A
TOTAL LOAD: 3990 VA 3640 VA 2205 VA
23 24
21 22
19 20
17 18
15 16
13 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 TR ROOM LIGHTING 20 A 1 50 VA 300 VA 1 20 A PCU 8
5 1665 VA 540 VA 1 20 A TR ROOM RECEPTACLE 6
3 1665 VA 1975 VA 4
PDU 20 A 3
1665 VA 1975 VA
2 30 A SSCU-303
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 5L3B PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: BUILDING 5, ROOM 303 VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 5TR-303-B
B. BUS A PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
81 A
SPARE CAPACITY:
80 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 8705 A
DEMAND CURRENT: 19 A
DEMAND LOAD: 6964 VA
REC 720 VA 100.00% 720 VA CONNECTED CURRENT: 16 A
PWR-C 4995 VA 125.00% 6244 VA CONNECTED LOAD: 5715 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 14 A 14 A 20 A
TOTAL LOAD: 1665 VA 1665 VA 2385 VA
23 24
21 22
19 20
17 18
15 16
13 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 8
5 1665 VA 720 VA 1 20 A TR ROOM RECEPTACLE 6
3 1665 VA 0 VA 4
UPS 20 A 3
1665 VA 0 VA
2 40 A -- SPARE
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 5L3B PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: BUILDING 5, ROOM 303 VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 5TR-303-A
SCALE: 1/2" = 1'-0"
ENLARGED DEMO PLAN - ROOM 303 - BUILDING 5
SHEET NOTES:
1. REMOVE ALL EXISTING ELECTRICAL DEVICES AND WIRING BACK TO SOURCE. MAINTAIN
CIRCUITING TO EXISTING DEVICES REMAINING OUTSIDE AREA. REMOVE TELEDATA CONDUIT
AND BOXES IN AREA OF RENOVATION. TELECOM CONTRACTOR WILL REMOVE ALL WIRING,
JACKS, AND COVERPLATES. VISIT SITE TO DETERMINE FULL EXTENT OF DEMOLITION.
2. REFER TO EQUIPMENT CONNECTION SCHEDULE.
3. PROVIDE RECEPTACLE FOR BUS B. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
4. PROVIDE RECEPTACLE FOR BUS A. MOUNT RECEPTACLE TO CABLE TRAY ABOVE RACK.
FEEDER SCHEDULE - COPPER
FEEDER NOMINAL SIZE WIRE AND CONDUIT
10N 100 A 4-#1 CU, #8 CU GND - 2" C.
GENERAL NOTES:
A. REFER TO TELECOM, HVAC, AND FIRE PROTECTION DRAWINGS. COORDINATE LOCATION
ON NEW LIGHTING FIXTURES, NEW ELECTRICAL PANELS, AND NEW CABLE TRAY MOUNTED
T-6TR-101
10N 10N
6TR-101
6TR-110A-A 6TR-110A-B
NEW 240/3 TO 120/208/3 TRANSFORMER,
75-KVA.
NEW 120/208/3, 225-AMP MLO PANEL
WITH TWO 100/3 CIRCUIT BREAKERS
TO SERVICE NEW PANELS.
6PDP1
REUSE EXISTING 250/3 SPARE
BREAKER IN EXISTING PANEL TO
SERVE NEW TRANSFORMER.
NEW ENCLOSED CIRCUIT BREAKER, 208/3,
250-AMPS LOCATED WITHIN 10-FT OF NEW
TRANSFORMER.
75T
75T
75T
6LDP1
6MDP
E
TR
110A
E-006.1
EXISTING SWITCHBOARD 6MDP.
6TR-101
NEW 240/3 TO 120/208/3 TRANSFORMER.
SSCU-110A
E
6PDP1
E
E-006.1
ELECTRIC MECH
ROOM
HUMAN RESRC SVC
CHIEF OFFICE
RCC104R
HUMAN RESRC SVC
PIV
COMMON TLT
COMMON TLT
COMMON TLT
104A
COMMON HALL - 1
ENGINEERING ELEC
CLOS
118A
HUMAN RESRC SVC
OFF
108A
HUMAN RESRC SVC
OFF
HUMAN RESRC SVC
OFF
HUMAN RESRC SVC
OFF
HUMAN RESRC SVC
HUMAN RESRC SVC
HUMAN RESRC SVC
TENANT SPACE HAC
COMMON TLT
COMMON TEL
COMMON ELEC
COMMON HALL - 3
COMMON VEST
HUMAN RESRC SVC
HUMAN RESRC SVC
PIV
RCC102R
HUMAN RESRC SVC
OFF
COMMON VEST
PRIMARY CARE OFF
ON-SITE LAUNDRY
LAUNDRY UNIT
HUMAN RESRC TLT
RCC106R
HUMAN RESRC SVC
STOR
RCC101R
PRIMARY CARE
EMPLOYEE HEALTH
ENGINEERING
MECHANICAL AREA
HUMAN RESRC SVC
BRK RM
RCC105R
RCC107R
RCC108R
VERTICAL SPACE
CHASE
RCC101C PRIMARY CARE
EMPLOYEE HEALTH
RCC103R
PRIMARY CARE OFF
COMMON HALL - 2
TR
110A
I4E
I4E
6TR-110A-A
6TR-110A-B
SSAH-110A
6TR-110A-B-7
6TR-110A-B-6
L21-20
L21-20
6TR-110A-B-1,3,5
6TR-110A-A-1,3,5
6TR-110A-A-6
6TR-110A-B-8
OV
PCU
LIMIT OF DEMOLITION
D ON-SITE LAUNDRY
LAUNDRY UNIT
Location
Issue Date
Specialized Engineering Solutions
1300 Baxter Street, Suite 355
FULLY SPRINKLERED
COLUMBIA VA HEALTH CARE SYSTEM, COLUMBIA, SC
544-20-107PROJECT # 544-20-107
EHRM INFRASTRUCTURE UPGRADES
www.atriaxgroup.com
Atriax, pllc
102 3rd Avenue, NE
PO Box 1629, Hickory, NC 28603
Phone: 828.315.9962
Fax: 828.315.9964
NC Engineering License No.: P-0214
NC Architectural License No.: 51254
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Project Director
Revisions: Date:
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
Wiley|Wilson 127 Nationwide Drive Lynchburg, VA 24502 Phone: 434.947.1901 www.wileywilson.com
VA FORM 08 - 6231
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
07/14/2022
20375.007 E-006.1
B6 PARTIAL PLAN - LEVEL 1 -
ELECTRICAL 6
CGH JTD07/14/2022
100% CONSTRUCTION
DOCUMENTS
SCALE: NONE
ELECTRICAL ONE-LINE - BUILDING 6
PLAN
NORTH
SCALE: 1/8" = 1'-0"
LEVEL 1 FLOOR PLAN - ELECTRICAL
SCALE: 1/2" = 1'-0"
ENLARGED NEW PLAN - ROOM TR 110A - BUILDING 6
EQUIPMENT CONNECTION SCHEDULE
MARK DESCRIPTION ROOM NAME ROOM # HP KW FLA MCA MOCP VOLTS PHASE POLES
LOAD
[VA]
CONTROL
TYPE
DISCONNECT
BY
DISCONNECT
TYPE FEEDER PANEL
CIRCUIT
NUMBER SCCR GEN REMARKS
SSAH-110A SPLIT SYSTEM INDOOR UNIT TR 110A 0 0 0 0 0 208 1 2 0 CABLE PROVIDED BY MANUFACTURER 6TR-110A-B 2,4 0 No 2
SSCU-110A SPLIT SYSTEM CONDENSING UNIT OUTDOORS 0 0 0 19 30 208 1 2 1960 EC 30A FUSED 3/4",2#10,1#10G 6TR-110A-B 2,4 0 No 1
B. BUS A PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
81 A
SPARE CAPACITY:
81 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 8480 A
DEMAND CURRENT: 19 A
DEMAND LOAD: 6784 VA
REC 540 VA 100.00% 540 VA CONNECTED CURRENT: 15 A
PWR-C 4995 VA 125.00% 6244 VA CONNECTED LOAD: 5535 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 14 A 14 A 18 A
TOTAL LOAD: 1665 VA 1665 VA 2205 VA
23 24
21 22
19 20
17 18
15 16
13 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 8
5 1665 VA 540 VA 1 20 A TR ROOM RECEPTACLE 6
3 1665 VA 0 VA 4
UPS 20 A 3
1665 VA 0 VA
2 20 A -- SPARE
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 6TR-101 PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: BUILDING 6, ROOM 110A VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 6TR-110A-A
B. BUS B PANEL.
C. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
73 A
SPARE CAPACITY:
72 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 100 A
CONSIDER 125% DEMAND: 12314 A
MEQ-C 1960 VA 125.00% 2450 VA DEMAND CURRENT: 27 A
REC 720 VA 100.00% 720 VA DEMAND LOAD: 9851 VA
PWR-C 5295 VA 125.00% 6619 VA CONNECTED CURRENT: 22 A
LTG 50 VA 125.00% 63 VA CONNECTED LOAD: 8025 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 25 A 22 A 20 A
TOTAL LOAD: 2995 VA 2645 VA 2385 VA
23 24
21 22
19 20
17 18
15 16
13 14
11 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 12
9 SPARE -- 20 A 1 0 VA 0 VA 1 20 A -- SPARE 10
7 TR ROOM LIGHTING 20 A 1 50 VA 300 VA 1 20 A PCU 8
5 1665 VA 720 VA 1 20 A TR ROOM RECEPTACLE 6
3 1665 VA 980 VA 4
PDU 20 A 3
1665 VA 980 VA
2 30 A SSCU-110A
CKT CIRCUIT DESCRIPTION OPT RATING POLES A B C POLES RATING OPT CIRCUIT DESCRIPTION CKT
NEMA ENCLOSURE: 1
MOUNTING: SURFACE AVAILABLE SCC (kA): 10 PANEL POLES: 24
SERVICE RATED: No INTEGRAL SPD: No SECTIONS: 1
BRANCH: NORMAL WIRES: 4 MCB OPTIONS:
SUPPLY FROM: 6TR-101 PHASES: 3 MCB/MLO RATING: 100 A
LOCATION: BUILDING 6, ROOM 110A VOLTS: 208/120 WYE MAINS TYPE: MLO
PANEL: 6TR-110A-B
FEEDER SCHEDULE - COPPER
FEEDER NOMINAL SIZE WIRE AND CONDUIT
10N 100 A 4-#1 CU, #8 CU GND - 2" C.
75T 250 A 4-300 KCMIL CU, #2 CU GND - 3"C.
SCALE: 1/4" = 1'-0"
ENLARGED DEMO PLAN - ROOM 110 - BUILDING 6
REMARKS: (EQUIPMENT CONNECTION SCHEDULE)
1.CONTROLS BETWEEN INDOOR AND OUTDOOR UNITS - INCLUDE CONTROL WIRING IN CONDUIT BETWEEN INDOOR AND OUTDOOR UNIT PER MANUFACTURER'S REQUIREMENTS.
2."CONTROL TYPE" - PROVIDE CONTROL AND CONNECTIONS: "INT" = CONTROLS ARE MANUFACTURED INTEGRAL TO THE EQUIPMENT (SELF-CONTAINED).
B. WHERE NEW PANELS ARE SHOWN AT TELECOM PLYWOOD LOCATIONS, MOUNT PANELS TO PLYWOOD.
A. PANEL AIC (INTERRUPTING) RATING SHALL BE MINIMUM 120% OF THE AVAILABLE SCC (SHORT CIRCUIT CURRENT).
GENERAL REMARKS:
CIRCUIT BREAKER OPTIONS SUFFIX: 'S' OR 'ST' - PROVIDE SHUNT TRIP CIRCUIT BREAKER / 'G' OR 'GFCI' - PROVIDE GFCI CIRCUIT BREAKER / 'GFP' - PROVIDE GFP CIRCUIT BREAKER / 'ERMS' - ENERGY REDUCING MAINTENANCE SWITCH / 'ZSI' - ZONE SELECTIVE INTERLOCKING / 'L' - PROVIDE CIRCUIT BREAKER WITH LOCKING PROVISIONS / 'R'
- PROVIDE CIRCUIT BREAKER WITH RED MARKING
OPTIONS:
179 A
SPARE CAPACITY:
79 %
FEEDER AVAILABLE:
EQUIPMENT AMPS: 225 A
CONSIDER 125% DEMAND: 20794 A
MEQ-C 1960 VA 125.00% 2450 VA DEMAND CURRENT: 46 A
REC 1260 VA 100.00% 1260 VA DEMAND LOAD: 16635 VA
PWR-C 10290 VA 125.00% 12863 VA CONNECTED CURRENT: 38 A
LTG 50 VA 125.00% 63 VA CONNECTED LOAD: 13560 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
TOTAL AMPS: 39 A 36 A 39 A
TOTAL LOAD: 4660 VA 4310 VA 4590 VA
23 24
21 22