This is an amendment to specifications sections 232113 (Hydronic Piping) and 232213 (Steam and Condensate Heating Piping) for the Captain James A. Lovell Federal Health Care Center project, specifically related to chilled water piping from Building B188 to B3.

The amendment requires contractors to replace ASTM A307 general purpose bolts with ASTM A193 high temperature bolts and ASTM A194 high temperature nuts on hot water steam and hydronic systems. The changes originated from a December 2024 VA internal memo to modify PG-18-1 Master Specifications. The amendment makes specific revisions to both specification sections, updating the bolt and nut requirements for flanged connections to use materials rated for high temperature or high pressure service. The amendment is dated January 8, 2025 and applies to VA Contract/Task 36C25219D0022/36C25223N0287 under VA project number 556-23-104.

View the file

Other files

File Type Posted
C01_Contract Award Notice CON 556-23-101 36C25225C0039_1.pdf PDF
S06_Att2 CON-IFB Amendment 0009 RFI Pre-Bid Responses 36C25225B0005 556-23-101_04102025.xlsx XLSX spreadsheet
S06_CON-IFB Amendment 0009 SF30 556-23-101 36C25225B0005_04102025.pdf PDF
S06_Att1 CON-IFB Amendment 0009 SF30 Continuation Page 36C25225B0005_04102025 1.pdf PDF
S06_Att4 CON-IFB Amendment 0009 VAAR 852.219-75 Limitations on Subcontracting 556-23-101 36C25225B0005_04102025.pdf PDF
S06_Att3 CON-IFB Amendment 0009 Executive Order Provision and Clause Changes 36C25225B0005_04102025.pdf PDF
36C25225B0005 Amendment 0008.pdf PDF
S06_CON-IFB Amendment 0007 SF30 556-23-101 36C25225B0005_03262025 1.docx DOCX document
S06_CON-IFB Amendment 0006 SF30 556-23-101 36C25225B0005_03192025.docx DOCX document
S06_Att1 CON-IFB Amendment 0006 RFI Pre-Bid Responses 36C25225B0005 556-23-101_03192025.xlsx XLSX spreadsheet
S06_CON-IFB Amendment 0005 SF30 556-23-101 36C25225B0005_03072025.pdf PDF
S06_Att5 CON-IFB Amendment 0005 Wage Rates SAM IL current as of 02202025.docx DOCX document
S06_Att1 CON-IFB Amendment 0005 RFI Pre-Bid Responses 36C25225B0005 556-23-101_03062025.xlsx XLSX spreadsheet
S06_Att2 CON-IFB Amendment 0005 Sheet MD100 in Response to RFI Question 13_03062025.pdf PDF
S06_Att3 CON-IFB Amendment 0005 SPECS Correction Plus Section 01 00 00 36C25225B0005 556-23-101_01282025.pdf PDF
S06_Att4 CON-IFB Amendment 0005 Rev1 Addendum correcting select drawing text 556-23-101_03052025 (1).docx DOCX document
1S06_CON-IFB Amendment 0004 SF30 556-23-101_36C25225B0005.pdf PDF
36C25225B0005 0003.docx DOCX document
36C25225B0005 0002.docx DOCX document
S04_Site Visit No. 2 Sign-In-Sheet 556-23-101 Renovate CLC Bldg. 134 - 2C_01282025.pdf PDF
36C25225B0005 0001.docx DOCX document
S04_Site Visit Sign-In-Sheet 556-23-101 Renovate CLC Bldg. 134 - 2C_01212025.pdf PDF
S02_Att9 Regulatory Requirements 01 41 00 24JAN22_556-23-101.pdf PDF
S02_Att2 Part 3 of 5 DRAWINGS-Finish Fire 100 Perent 556-23-101 21June2024.pdf PDF
S02_Att1 SPECS COMBINED 36C25225B0005 556-23-101_06212024.pdf PDF
S02_Att8 Quality Requirements 01 40 00 19MAY20_556-23-101.pdf PDF
S02_Att2 Part 2 of 5 DRAWINGS-Electrical 100 Percent 556-23-101 21June2024.pdf PDF
S02_Att6 Safety Requirements 01 35 26 27AUG21_556-23-101.pdf PDF
S02_Att4 VHA Directive Seasonal Flu Shot 1192_01_D_2020-08-10_556-23-101.pdf PDF
S02_Att2 Part 4 of 5 DRAWINGS-General 100 Percent 556-23-101 21June2024.pdf PDF
S02_Att2 Part 1 of 5 DRAWINGS-Architectural 100 Percent 556-23-101 21June2024.pdf PDF
S02_Att2A Addendum Memo to Correct Select Drawing Text_12272024.pdf PDF
S02_Att5 Wage Rates SAM IL current as of 01032025.pdf PDF
36C25225B0005_1.docx DOCX document
S02_Att7 Infection Control Requirements 01 35 33 27AUG21_556-23-101.pdf PDF
S02_Att10 VAAR 852.219-75 Certification 36C25225B0005_556-23-101.pdf PDF
S02_Att3 FHCC Contracted Dispensers 36C25225B0005 556-23-101_12192024.pdf PDF
S02_Att2 Part 5 of 5 Drawings-Plumbing Mechanical 100 Percent 556-23-101 21June2024.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT

Project: Captain James A. Lovell Federal Health Care Center

Chilled Water from B188 to B3

To: Sean Brewner

Re: VA Internal Memo dated December 2024, VA Request

Amendment Number: 01

From: Jonathan Carr, AIA

Date: 01/08/2025

VA | AE Project Number: 556-23-104 | 22018

Contract|Task: 36C25219D0022 | 36C25223N0287

Specification Section: 232113, 232213 Paragraph: See Below Drawing Reference: N/A Detail: N/A

Description: Amendment 01 originates from a December 2024 internal VA memo to modify PG-18-1 Master Specifications. VA Master

Specifications 232113 and 232213 currently allow general purpose ASTM A307 bolts on steam and hot water pipe flanges. VA seeks to update PG-18-1 Master Specifications to use high temperature nuts and bolts for flanged connections on steam and hot water piping systems. Amendment 01 requires Bidders to replace ASTM A307 general purpose bolts with ASTM A193 high temperature bolts and

ASTM A194 high temperature nuts on hot water steam and hydronic systems.

Specification revisions are as follows:

1. Section 232113 Hydronic Piping.

A. Par. 1.3.C:

i. Delete “A307-07…Standard Specification for Carbon Steel Bolts and Studs, 60,000 PSI Tensile Strength.”

ii. Replace the above deletion with “A193/A193M-23…Standard Specification for Alloy-Steel and Stainless Steel

Bolting for High Temperature or High Pressure Service and Other Special Purpose Applications.”

iii. Add “A194/A194M-22…Standard Specification for Carbon Steel, Alloy Steel, and Stainless Steel Nuts for Bolts for High Pressure or High Temperature Service, or Both.”

B. Par. 2.3.A.2.b:

i. Delete “Flange bolting: Carbon steel machine bolts or studs and nuts, ASTM A307, Grade B.”

ii. Replace the above deletion with “Flange Bolting: high strength carbon steel bolts or studs, ASTM A193, Class 2, Grade B7. Nuts shall be ASTM A194/A194M.”

2. Section 232213 Steam and Condensate Heating Piping.

A. Par. 1.3.C:

i. Delete “A307-07…Standard Specification for Carbon Steel Bolts and Studs, 60,000 PSI Tensile Strength.”

ii. Replace the above deletion with “A193/A193M-23…Standard Specification for Alloy-Steel and Stainless Steel

Bolting for High Temperature or High Pressure Service and Other Special Purpose Applications.”

iii. Add “A194/A194M-22…Standard Specification for Carbon Steel, Alloy Steel, and Stainless Steel Nuts for Bolts for High Pressure or High Temperature Service, or Both.”

☐ Attachments: None.

Signed by: Date: 01/08/2025

Copies: ☐ ☐ ☐ ☐ ☐ ☐ ☐ File