S02-657A4-21-800-ATTACHMENT 5- MBC Drawings Volume 2_R_06242025.pdf
PDF 7 MB Posted
- Attached to
- Z2DA--657A4-21-800, TF - FCA - Remove and Replace End-of-Life HVAC Infrastructure Building 1
- Solicitation number
- 36C25525R0106
About this file
These architectural and engineering documents are detailed design drawings for a temporary modular building complex (MBC) at the VA Medical Center in Poplar Bluff, Missouri. The 36-page drawing set covers structural, architectural, mechanical, electrical, fire protection, and technology systems for a swing space facility to temporarily relocate various medical departments during building renovations.
The modular building is designed to accommodate laboratory, dental, administrative, and support spaces across four construction phases. Key features include a connecting link to the main hospital, a 2-hour fire-rated wall, fully sprinklered spaces, and systems designed to VA standards. The project involves demolishing existing temporary structures, installing a new modular building with multiple unit types, and providing comprehensive infrastructure including HVAC, electrical, technology, and fire protection systems. The design emphasizes flexibility, with provisions for equipment relocation and phased construction to minimize disruption to hospital operations.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL STRUCTURAL NOTES
DESIGN CRITERIA:
APPLICABLE BUILDING CODE: 2018 IBC (WITH VA AMENDMENTS)
SELECT REFERENCED STANDARDS:
ACI 301-16: CODE OF STANDARD PRACTICE FOR REINFORCED CONCRETE BUILDINGS
ACI 318-14: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
ACI 530-15: BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES
AISC 303-16: CODE OF STANDARD PRACTICE FOR STRUCTURAL STEEL BUILDINGS AND
BRIDGES
AISC 360-16 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
ASCE 7-16: MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES,
INCLUDING SUPPLEMENT NO. 1 AND 2, EXCLUDING CHAPTER 14 AND APPENDIX 11A
AWS D1.1-20: STRUCTURAL STEEL WELDING CODE – STEEL
AWS D1.3-18: STRUCTURAL STEEL WELDING CODE – SHEET STEEL
AWS D1.4-17: STRUCTURAL STEEL WELDING CODE –REINFORCING STEEL
AWS D1.8-21: SEISMIC SUPPLEMENT
VA SEISMIC DESIGN REQUIREMENTS, H-18-8
VA PHYSICAL SECURITY DESIGN MANUAL FOR MISSION CRITICAL FACILITIES, (PSRDM-
MC), OCTOBER 1, 2020, REVISED JUNE 1, 2023
VA STRUCTURAL DESIGN MANUAL FOR HOSPITAL…PROJECTS, FEBRUARY 1, 2014
OTHER SELECT REFERENCED STANDARDS MAY BE INDICATED ELSEWHERE IN THE
CONTRACT DOCUMENTS, AS APPLICABLE.
THE PROVISIONS OF THE REFERENCED BUILDING CODE AND ALL REFERENCED
STANDARDS THEREIN SHALL APPLY TO THIS PROJECT. WHERE THERE IS A CONFLICT
BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC REQUIREMENT, THE SPECIFIC
REQUIREMENT SHALL BE APPLICABLE. TYPICALLY, THE LATEST EDITION OF
CONSTRUCTION STANDARDS SHALL BE UTILIZED, AS APPROVED BY THE AUTHORITY
HAVING JURISDICTION.
STRUCTURAL SYSTEMS HAVE BEEN DESIGNED (OR SHALL BE DESIGNED FOR DELEGATED
DESIGN ITEMS) TO RESIST THE FOLLOWING DESIGN LOADS IN THEIR FINAL, IN-PLACE CONDITION:
ABBREVIATIONS:
“LINK” – CONNECTOR STRUCTURE BETWEEN MAIN HOSPITAL AND MBC, SEPARATED BY A
STRUCTURALLY-INDEPENDENT FIRE WALL;
“MBC” – MODULAR BUILDING COMPLEX (TEMPORARY CONSTRUCTION - DELEGATED
DESIGN);
DEAD LOAD:
WEIGHT OF ALL MATERIALS OF FINAL BUILDING CONSTRUCTION, INCLUDING BUILT-IN
PARTITIONS AND FIXED SERVICE EQUIPMENT.
FLOOR LIVE LOAD*,**:
LINK
CORRIDORS =100 PSF
STAIRWAYS, EXIT WAYS, LOBBIES,
ASSEMBLY AREAS AND
ELEVATOR LOBBIES =100 PSF
TYPICAL SLAB-ON-GRADE IN LINK =100 PSF
MBC:
SEE SHEET SF101 FOR LIVE LOADS FOR DESIGN IN THE MBC.
*PROVISIONS FOR MOVEABLE PARTITIONS HAVE NOT BEEN APPLIED, WHICH IS IN
ACCORDANCE WITH BUILDING CODE, EXCEPT AS INDICATED ABOVE. FIXED PARTITIONS
(E.G., METAL STUDS) ARE CONSIDERED A DEAD LOAD.
**IN ACCORDANCE WITH SECTION 106.1 OF IBC, BUILDING IS EXEMPT FROM POSTING LIVE
LOAD SIGNS, SINCE NOT COMMERCIAL NOR INDUSTRIAL BUILDING.
LIVE LOAD REDUCTIONS HAVE BEEN MADE.
SNOW LOAD:
GROUND SNOW LOAD Pg = 28 PSF (ASCE 7-22, SEE CALCULATIONS; LOAD
FACTOR = 1.0) (IBC 500-YEAR+ MRI)
FLAT ROOF SNOW LOAD* Pf = 20 PSF MINIMUM SNOW LOAD Pm = 20 PSF SNOW EXPOSURE FACTOR Ce = 1.0 (EXPOSURE B, PARTIALLY EXPOSED) SNOW SLOPED ROOF FACTOR Cs = 0.75 SNOW THERMAL FACTOR Ct = 1.0 SNOW IMPORTANCE FACTOR Is = 1.0 (ASCE 7-22)
RISK CATEGORY IV
*PARTIAL, UNBALANCED, AND DRIFT SNOW LOADING SHALL BE APPLIED IN ACCORDANCE
WITH BUILDING CODE AND ASCE 7.
SNOW LOADS ARE NOT REDUCIBLE.
WIND LOAD:
ULTIMATE WIND SPEED Vult = 119 MPH (3-SECOND GUST) ASD WIND SPEED Vasd = 92 MPH (3-SECOND GUST) DRIFT WIND SPEED (25-YEAR MRI) Vdrift = 80 MPH (3-SECOND GUST)
GUST EFFECT FACTOR G = 0.85
WIND EXPOSURE CATEGORY B
RISK CATEGORY IV
INTERNAL PRESSURE COEFFICIENT GCpi = +/- 0.18
SEISMIC LOAD:
MAPPED SPECTRAL RESPONSE COEFFICIENTS
Ss = 1.3 S1 = 0.35
DESIGN SPECTRAL RESPONSE COEFFICIENTS
Sds = 0.77 Sd1 = 0.47
RISK CATEGORY IV
SEISMIC IMPORTANCE FACTOR Ie = 1.5
SEISMIC DESIGN CATEGORY D
SEISMIC SITE CLASS D
BASIC SEISMIC-FORCE-RESISTING SYSTEM:
LINK: STEEL ORDINARY MOMENT FRAMES WITH UNLIMITED HEIGHT DESIGNED IN
ACCORDANCE WITH AISC 360 PER TABLE 15.4-1 (NONBUILDING STRUCTURE
SIMILAR TO BUILDINGS)
MBC: AS DETERMINED BY MBC ENGINEER IN ACCORDANCE WITH CHAPTER 12 OF
ASCE 7-22
RESPONSE MODIFICATION FACTOR:
LINK: R = 1.0
MBC: AS DETERMINED BY MBC ENGINEER IN ACCORDANCE WITH ASCE 7-22
DESIGN BASE SHEAR:
LINK: V = 23 KIPS
MBC: AS DETERMINED BY MBC ENGINEER IN ACCORDANCE WITH ASCE 7-22
SEISMIC RESPONSE COEFFICIENT:
LINK: Cs = 1.16
MBC: AS DETERMINED BY MBC ENGINEER IN ACCORDANCE WITH ASCE 7-22
LONG-PERIOD TRANSITION PERIOD TL = 12 SEC
ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE PROCEDURE
100 PERCENT OF THE SEISMIC FORCES IN ONE DIRECTION PLUS 30 PERCENT OF THE
SEISMIC FORCES IN THE PERPENDICULAR DIRECTION WERE (ARE TO BE) APPLIED
SIMULTANEOUSLY PER SECTION 12.5.3.1.A OF ASCE 7.
ALL NON-STRUCTURAL COMPONENTS REQUIRED FOR CONTINUED OPERATION AND/OR
LIFE-SAFETY SHALL BE SEISMICALLY BRACED (DELEGATED DESIGN) PER CHAPTER 13 OF
ASCE 7 AND THE PROJECT REQUIREMENTS.
ROOF LIVE LOAD:
20 PSF TYPICAL
ROOF LIVE LOAD REDUCTIONS HAVE NOT BEEN MADE.
INTERIOR WALLS:
5 PSF LATERAL LOAD IN ABSENCE OF ANY WIND LOAD EFFECTS
CONSTRUCTION LOADING IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR.
PROVISIONS FOR FUTURE EXPANSION
1. NO PROVISIONS FOR FUTURE EXPANSION HAVE BEEN MADE IN THE STRUCTURAL SYSTEMS.
FIRE-RESISTIVE STRUCTURAL ELEMENTS DEFINITIONS
1. SEE ARCHITECTURAL AND FIRE PROTECTION DRAWINGS FOR REQUIRED FIRE RATINGS AND
ASSOCIATED UL ASSEMBLIES FOR FIRE PROTECTION OF STRUCTURAL ELEMENTS.
2. THE FOLLOWING ELEMENTS ARE DEFINED AS “PRIMARY STRUCTURAL FRAME”:
a. STEEL COLUMNS
b. STEEL POSTS, EXCLUDING THOSE SUPPORTING STAIRS ONLY
c. STEEL HANGERS, EXCLUDING THOSE SUPPORTING STAIRS ONLY
d. STEEL BEAMS AND GIRDERS DIRECTLY ATTACHING TO STEEL COLUMNS
e. STEEL BEAMS AND GIRDERS DIRECTLY ATTACHING TO STEEL POSTS, EXCLUDING THOSE
SUPPORTING STAIRS ONLY
f. STEEL BEAMS AND GIRDERS DIRECTLY SUPPORTING HANGERS, EXCLUDING THOSE
SUPPORTING STAIRS ONLY
GENERAL PROJECT NOTES
1. ALL DIMENSIONS AND CONDITIONS SHOWN ON THE DRAWINGS SHALL BE VERIFIED BY THE
CONTRACTOR PRIOR TO FABRICATION OR CONSTRUCTION.
2. THE RESIDENT ENGINEER SHALL BE NOTIFIED IN WRITING OF ANY EXISTING CONDITIONS
WHICH DIFFER FROM THOSE SHOWN ON THE CONTRACT DOCUMENTS.
3. THE ENGINEER WILL NOT ACCEPT SHOP DRAWINGS WITHOUT FIRST BEING REVIEWED AND
SIGNED BY THE CONTRACTOR. ALL CHANGES SHALL BE FLAGGED AND NOTED AS DEVIATING
FROM THE CONTRACT DOCUMENTS.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF THE NEW AND EXISTING
BUILDINGS DURING THE EXECUTION OF THE CONTRACT.
5. ALL CONSTRUCTION SHALL BE COORDINATED WITH THE OWNER TO MINIMIZE DISRUPTION.
6. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN ADEQUATE SHORING AND BRACING TO
PROTECT THE EXISTING STRUCTURE (INCLUDING AREAWAY RETAINING WALLS) AND UNFINISHED
NEW CONSTRUCTION.
7. AN ENGINEER REGISTERED IN THE STATE OF MISSOURI SHALL PERFORM THE DESIGN OF ALL
SHORING AND TEMPORARY BRACING.
8. ALL NON-STRUCTURAL COMPONENTS REQUIRED FOR CONTINUED OPERATION AND/OR LIFE-
SAFETY SHALL BE SEISMICALLY BRACED (DELEGATED DESIGN) PER CHAPTER 13 OF ASCE 7 AND
THE PROJECT REQUIREMENTS.
9. ALL NON-STRUCTURAL COMPONENTS WEIGHING 31 POUNDS OR MORE SHALL BE BRACED
(DELEGATED DESIGN) PER THE REQUIREMENTS OF THE VA-PHYSICAL SECURITY DESIGN MANUAL
FOR MISSION CRITICAL FACILITIES AND THE PROJECT REQUIREMENTS.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR DESIGN AND PROVISION OF ALL TEMPORARY
GUYS, BRACING, AND OTHER SUPPORTS AS NEEDED TO SAFELY RESIST ALL LOADS TO WHICH
THE STRUCTURE MAY BE SUBJECTED, INCLUDING LOADS FROM ERECTION EQUIPMENT AND
OPERATIONS, AND ALL WIND OR SEISMIC FORCES COMPARABLE IN INTENSITY FOR WHICH THE
STRUCTURES WERE DESIGNED. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ADEQUATE LATERAL SUPPORT FOR THE STRUCTURES DURING CONSTRUCTION UNTIL ALL
STRUCTURAL ELEMENTS HAVE BEEN ERECTED, ACHIEVED DESIGN STRENGTHS, AND
CONNECTED PER CONTRACT DOCUMENTS.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR DESIGN AND PROVISION OF ALL SHORING
REQUIRED FOR TEMPORARY EARTH RETENTION. DESIGN OF SUCH SHORING SHALL BE BASED
ON LATERAL EARTH PRESSURES GIVEN IN THE GEOTECHNICAL REPORT.
12. THE DIAPHRAGM PROVIDED BY THE CONCRETE-FILLED METAL FLOOR DECK IS REQUIRED TO
BRACE THE STEEL COLUMNS OF THE LINK AND IS REQUIRED TO BRACE SAID COLUMNS AND
COMPLETE THE LATERAL LOAD RESISTING SYSTEM OF THE STRUCTURE. THE DIAPHRAGM(S)
PROVIDED FOR THE MBC SHALL BE AS DETERMINED BY THE MBC STRUCTURAL ENGINEER
(DELEGATED DESIGN). THE CONTRACTOR SHALL PROVIDE LATERAL BRACING AS REQUIRED
DURING CONSTRUCTION UNTIL THESE ELEMENTS HAVE BEEN CONSTRUCTED AND THE
CONCRETE (WHERE APPLICABLE) HAS ACHIEVED A STRENGTH OF AT LEAST 75% OF ITS DESIGN
STRENGTH. THE CONTRACTOR IS RESPONSIBLE FOR DESIGN, BRACING, AND SUPPORTING THE
STRUCTURES IF ANY SUBASSEMBLIES ARE PRE-ASSEMBLED THEN ERECTED INTO PLACE.
13. CONTRACTOR SHALL ENSURE NO STRUCTURAL MEMBERS OR ELEMENTS ARE DAMAGED OR
ALTERED UNLESS ALTERATION IS SO INDICATED BY THE STRUCTURAL ENGINEER. ANY SUCH
DAMAGE OR ALTERATION THAT DOES OCCUR SHALL BE BROUGHT TO THE ATTENTION OF THE
RESIDENT ENGINEER AND SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
14. DISCREPANCIES: CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONDITIONS, AND
ELEVATIONS AT JOB SITE AND BRING ANY DISCREPANCIES TO THE ATTENTION OF THE RESIDENT
ENGINEER
15. THE “LINK” IS STRUCTURALLY-INDEPENDENT SEPARATED BY EXPANSION JOINTS FROM THE
EXISTING MAIN HOSPITAL BUILDING AND THE FIRE WALL. SEE DRAWINGS.
16. THE “MBC” SHALL BE STRUCTURALLY INDEPENDENT FROM THE “LINK” STRUCTURE AND THE
FIRE WALL. LOADS MAY APPLIED TO THE NEW MAT FOUNDATION AND ANY CONNECTIONS TO IT
SHALL BE COORDINATED PRIOR TO CASTING CONCRETE FOR MAT FOUNDATION.
17. UTILITIES CONNECTED TO TWO OR MORE INDEPENDENT STRUCTURES SHALL HAVE A
SEISMIC FLEXIBLE COUPLING CAPABLE OF WITHSTANDING MOVEMENT EQUAL TO THE
EXPANSION JOINT SIZE INDICATED ON THE STRUCTURAL DRAWINGS AND STILL REMAIN
OPERATIONAL.
DESIGN ITEMS DELEGATED TO THE CONTRACTOR
1. THE CONTRACTOR IS RESPONSIBLE FOR THE DESIGN OF THE FOLLOWING ITEMS. DESIGNS
SHALL SATISFY THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
A. MODULAR BUILDING COMPLEX (TEMPORARY CONSTRUCTION) - SEE SHEETS SF101 AND
SF102
B. COLD-FORMED STEEL STUD FRAMING AND PRE-FABRICATED COMPONENTS
C. SEISMIC BRACING OF NON-STRUCTURAL COMPONENTS
D. AT/FP BRACING OF NON-STRUCTURAL COMPONENTS
E. METAL STAIRS AND LANDINGS
F. HANDRAILS AND GUARDRAILS
G. RAISED FLOOR SYSTEM
H. ANY SUBASSEMBLIES OF STRUCTURE PRE-ASSEMBLED FOR ERECTION
ALL ITEMS LISTED AS DELEGATED DESIGN ITEMS SHALL BE PERFORMED AND STAMPED BY A
STRUCTURAL ENGINEER LICENSED IN THE STATE OF MISSOURI. SIGNED AND SEALED
ENGINEERING CALCULATIONS SHALL BE SUBMITTED FOR REVIEW AT THE SAME TIME THAT
RELATED SHOP DRAWINGS ARE SUBMITTED FOR REVIEW.
SPECIAL INSPECTIONS:
1. PROVIDE SPECIAL INSPECTIONS AS REQUIRED IN ACCORDANCE WITH THE INTERNATIONAL
BUILDING CODE, THESE CONTRACT DOCUMENTS, AND THE STATEMENT OF SPECIAL
INSPECTIONS FOR THE FOLLOWING: SOILS AND FOUNDATIONS, REINFORCED CONCRETE,
STRUCTURAL MASONRY, STRUCTURAL STEEL, AND METAL DECK. STRUCTURAL OBSERVATIONS
BY THE STRUCTURAL ENGINEER OF RECORD (OR HIS DESIGNATED REPRESENTATIVE) ARE
ALSO REQUIRED. THE STRUCTURAL OBSERVER SHALL BE HIRED BY THE CONTRACTOR AND BE
A REGISTERED CIVIL OR STRUCTURAL ENGINEERING DESIGN PROFESSIONAL REGISTERED IN
THE STATE OF MISSOURI. THE DPIRC FOR THE MBC SHALL PREPARE A SEPARATE STATEMENT
OF SPECIAL INSPECTIONS FOR APPROVAL AND USE FOR THAT CONSTRUCTION.
2. PROVIDE THE SPECIAL INSPECTOR 48 HOURS PRIOR NOTICE FOR THE SPECIAL INSPECTIONS
AND PROVIDE THE STRUCTURAL OBSERVER 14 DAYS’ PRIOR NOTICE FOR STRUCTURAL
OBSERVATIONS.
FOUNDATIONS AND FOOTINGS:
1. FOUNDATIONS ARE DESIGNED FOR A BEARING PRESSURE OF 2,500 PSF FOR CONTINUOUS
FOOTINGS AND 3,000 PSF FOR ISOLATED SPREAD FOOTINGS. BASEMENT WALLS ARE DESIGNED
FOR AN AT-REST, EQUIVALENT FLUID PRESSURE OF 70 PCF. SITE RETAINING WALLS ARE
DESIGNED FOR AN ACTIVE, EQUIVALENT FLUID PRESSURE OF 50 PCF. A PASSIVE, EQUIVALENT FLUID PRESSURE OF 250 PCF WAS USED FOR LATERAL (SLIDING) RESISTANCE. ALL VALUES ARE
AS RECOMMENDED IN THE GEOTECHNICAL ENGINEERING REPORT PREPARED BY SCI
ENGINEERING, INC., SOILS CONSULTANT, DATED JULY 2022, PROJECT #2011-5087.11. ALL
RECOMMENDATIONS CONTAINED IN THE REPORT SHALL BE FOLLOWED UNLESS SPECIFIED
OTHERWISE IN THE CONTRACT DOCUMENTS.
2. IF THE CONTRACTOR DISCOVERS POOR SOIL CONDITIONS UPON EXCAVATION, THE RESIDENT ENGINEER SHALL BE NOTIFIED IN WRITING. FAT CLAYS SHALL BE REMOVED TO A MINIMUM OF 2
FEET BELOW BEARING LEVEL OF THE FOOTINGS AND 3 FEET BENEATH THE BOTTOM OF THE
FLOOR SLABS. THE OVEREXCAVATION SHALL EXTEND LATERALLY AT LEAST 2 FEET BEYOND THE
OUTSIDE EDGE OF THE FOOTINGS AND SLAB-ON-GRADE FOOTPRINTS. THE OVEREXCAVATION
SHALL BE BACKFILLED WITH PROPERLY-COMPACTED, LOW-PLASTIC SOIL OR WITH LEAN
CONCRETE.
3. THE SOILS SPECIAL INSPECTOR SHALL INSPECT THE BEARING SOILS AFTER THE FOOTING
EXCAVATION IS MADE.
4. THE CONTRACTOR SHALL NOTIFY THE SOILS SPECIAL INSPECTOR AT LEAST 48 HOURS PRIOR
TO THE INSPECTION.
5. ALL FOOTINGS SHALL BE PLACED ON EITHER UNDISTURBED PREVIOUSLY COMPACTED
CONTROLLED FILL OR UNDISTURBED NATIVE SOILS AS RECOMMENDED IN THE GEOTECHNICAL
ENGINEERING REPORT. FOOTING EXCAVATIONS THAT HAVE BEEN EXCESSIVELY DISTURBED
SHALL BE OVERDEEPENED TO APPROVED UNDISTURBED SOILS AS DETERMINED BY THE ON-SITE
GEOTECHNICAL ENGINEER. OVEREXCAVATION AND REPLACEMENT WITH STRUCTURAL FILL
SHALL BE PERFORMED WHERE INADEQUATE BEARING MATERIALS ARE PRESENT IN FOOTING
EXCAVATIONS.
6. FOOTINGS SUBJECT TO FROST SHALL HAVE A MINIMUM OF 36 INCHES BETWEEN FINISHED
GRADE AND THE BOTTOM OF FOOTINGS. ELEVATIONS OF BOTTOM OF ALL FOOTINGS HAVE BEEN
ESTIMATED BASED ON AVAILABLE INFORMATION AND SHALL NOT BE CONSTRUED AS WAIVING
ANY OF THE MINIMUM REQUIREMENTS.
7. REMOVE ALL DEBRIS FROM THE EXCAVATION BEFORE THE CONCRETE IS POURED.
8. ALL OVER-EXCAVATION SHALL BE FILLED WITH CONCRETE OR ENGINEERED FILL APPROVED
BY THE SOILS SPECIAL INSPECTOR.
9. ALL FORMS AND ORGANIC DEBRIS SHALL BE REMOVED PRIOR TO BACKFILLING.
10. THE CONTRACTOR SHALL BRING THE BACKFILL UP EQUALLY ON BOTH SIDES OF THE
FOUNDATION WALLS AND BEAMS BELOW GRADE SO AS NOT TO CREATE AN UNBALANCED
LOADING.
11. FOR WALLS RETAINING SOIL ON ONE SIDE, THE CONTRACTOR SHALL NOT BACKFILL THE
WALLS UNTIL THE SUPPORTING FLOOR SLAB IS IN PLACE AND SECURED AND THE CONCRETE
FLOOR SLAB HAS ACHIEVED AT LEAST 75 PERCENT OF ITS DESIGN STRENGTH.
CONCRETE AND REINFORCING STEEL:
1. CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF ACI 301, UNLESS NOTED
OTHERWISE.
2. CONCRETE CLASSES AND USAGES:
A. FOOTINGS AND STRUCTURAL STOOP SLABS:
- MINIMUM COMPRESSIVE STRENGTH; 4500 PSI AT 28 DAYS
- MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO; 0.45
- COARSE AGGREGATE; LIMESTONE, 1” NOMINAL, 30% OF TOTAL AGGREGATE
- SLUMP RANGE BETWEEN 2" AND 4"
- AIR ENTRAINMENT RANGE BETWEEN 4% AND 6%
B. INTERIOR SLABS ON GRADE:
- MINIMUM COMPRESSIVE STRENGTH; 3500 PSI AT 28 DAYS
- MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO; 0.45
- COARSE AGGREGATE; LIMESTONE, 1” NOMINAL, 40% OF TOTAL AGGREGATE
- SLUMP RANGE BETWEEN 2" AND 4"
- NO ENTRAINED AIR
C. CONCRETE FILL OVER METAL DECK (INTERIOR SLABS):
- MINIMUM COMPRESSIVE STRENGTH; 3500 PSI AT 28 DAYS
- MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO; 0.45
- SAND/GRAVEL AGGREGATE
- SLUMP RANGE BETWEEN 2" AND 4"
- NO ENTRAINED AIR
D. FOUNDATION WALLS AND RETAINING WALLS:
- MINIMUM COMPRESSIVE STRENGTH; 4500 PSI AT 28 DAYS
- MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO; 0.45
- COARSE AGGREGATE; LIMESTONE, 3/4” NOMINAL, 30% OF TOTAL
AGGREGATE
- SLUMP RANGE BETWEEN 2” AND 4”
- AIR ENTRAINMENT RANGE BETWEEN 4% AND 6%
3. FLY ASH MAY BE USED UP TO 25%, BY WEIGHT, OF CEMENTITIOUS MATERIAL. FLY ASH SHALL
NOT BE USED IN WALLS, COLUMNS, OR SLABS WITH EXPOSED CONCRETE FINISH.
4. NON-SHRINK GROUT SHALL BE CEMENTITIOUS STRUCTURAL GROUT AND SHALL NOT CONTAIN
METALLIC MATERIAL OR CHLORIDES. MINIMUM COMPRESSIVE STRENGTHS SHALL BE AS
FOLLOWS, 3,000 PSI AT 1 DAY, 5,000 PSI AT 7 DAYS AND 6,000 PSI AT 28 DAYS.
5. SURFACE ACCEPTING EXPANDABLE BENTONITE WATERSTOP SHALL BE SMOOTH AND SHALL
HAVE EITHER A FORMED FINISH OR A FLOAT FINISH. ANY IRREGULARITIES IN THE CONCRETE
SURFACE THAT WILL INTERFERE WITH THE WATERSTOP BEING PLACED IN INTIMATE CONTACT
WITH THE CONCRETE SURFACE SHALL BE GROUND SMOOTH PRIOR TO INSTALLATION.
6. THE CONTRACTOR SHALL VERIFY AND COORDINATE ALL MECHANICAL AND ELECTRICAL
SLEEVES AND ALL UTILITY LOCATIONS PRIOR TO PLACEMENT OF CONCRETE.
7. ALL REINFORCING STEEL SHALL BE ASTM A-615, GRADE 60, EXCEPT REINFORCING TO BE
WELDED SHALL BE ASTM A-706, UNLESS NOTED OTHERWISE. WELDING SHALL USE E80XX
ELECTRODES IN CONFORMANCE WITH AWS D1.4.
8. WELDED STEEL WIRE FABRIC SHALL BE ASTM A-185, PLAIN TYPE AND FINISH, FLAT SHEETS.
9. ALL REINFORCING SHALL BE CONTINUOUS OR SHALL LAP AS SCHEDULED FOR TENSION LAP
SPLICES, UNLESS NOTED OTHERWISE.
10. HEADED DEFORMED BARS SHALL CONFORM TO ASTM A-615, GRADE 60 AND ASTM A970
INCLUDING ANNEX A1 REQUIREMENTS FOR CLASS HA HEAD DIMENSIONS. OBSTRUCTIONS OR
INTERRUPTIONS OF THE BAR DEFORMATIONS, IF ANY, SHALL NOT EXTEND MORE THAN 2 BAR
DIAMETERS FORM THE BEARING FACE OF THE HEAD.
11. PROVIDE CORNER BARS AND LAP CORNER BARS WITH MAIN REINFORCEMENT.
12. ALL INTERIOR CONCRETE SLABS-ON-GRADE SHALL BE 5” THICK AND SHALL BE REINFORCED WITH #4@16” c/c EACH WAY, EXCEPTED WHERE INDICATED TO BE 4" THICK WHICH SHALL BE REINFORCED WITH 6 x 6 - W1.4 x W1.4 WWF, UNLESS NOTED OTHERWISE.
13. ALL INTERIOR CONCRETE SLABS-ON-GRADE SHALL HAVE CONTROL JOINTS ON COLUMN
LINES AND AS NECESSARY TO NOT TO EXCEED 10 FEET O.C. AND SHALL BE EQUALLY-SPACED
BETWEEN COLUMN LINES, UNLESS OTHERWISE INDICATED.
14. FLOOR FINISH TOLERANCES FOR SLABS ON GRADE SHALL BE IN ACCORDANCE WITH ACI 117, STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND
MATERIALS. THE F-NUMBER SYSTEM SHALL BE USED WITH A FLATNESS OF 30 AND A LEVELNESS
OF 20 MEASURED IN ACCORDANCE WITH ASTM E 1155-87, EXCEPT THE LABORATORY AREA OF
THE MBC SHALL ACHIEVE A FLATNESS OF 50 AND A LEVELNESS OF 30.
15. A VAPOR BARRIER SHALL BE USED AT ALL INTERIOR SLABS ON GRADE. THE THICKNESS
SHALL BE AT LEAST 15 MILS.
16. THE PLACEMENT OF THE SLAB ON GRADE VAPOR BARRIER IS DEPENDENT UPON THE
POTENTIAL FOR WETTING THE SUBGRADE. IF THE SLAB AND GRANULAR FILL ARE PLACED UNDER
A WATERTIGHT ROOF, THE VAPOR BARRIER SHALL BE PLACED UNDER THE GRANULAR FILL. IF
THE ROOF IS NOT IN PLACE, THE VAPOR BARRIER SHALL BE PLACED DIRECTLY UNDER THE SLAB-
ON-GRADE.
17. PROVIDE 2 ADDITIONAL #5 REINFORCING BARS AT ALL SIDES OF OPENINGS IN CONCRETE WALLS THAT ARE GREATER THAN 1'- 6" IN ANY DIRECTION. EXTEND THE BARS 2'-O" PAST EDGES
OF THE OPENING (HOOK BARS IF NECESSARY).
18. WHERE THE SPACING OF SLAB REINFORCING IS CALLED OUT AS "ON CENTER (O.C.)", PLACE
THE FIRST BAR 3" FROM THE EDGE OF THE SLAB.
19. ALL REINFORCING STEEL SHALL BE EITHER CONTINUOUS OR DOWELED THROUGH
CONSTRUCTION JOINTS. DOWELS SHALL BE THE SAME SIZE AND SPACING AS SCHEDULED
REINFORCING AND SHALL LAP AS SCHEDULED.
20. CONCRETE PROTECTION FOR REINFORCING SHALL BE AS FOLLOWS UNLESS NOTED
OTHERWISE:
MINIMUM COVER (INCHES)
CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH --------------------------- 3
EXPOSED TO EARTH OR WEATHER
#5 BARS AND SMALLER --------------------------------------------------------------- 1 ½ #6 THROUGH #18 BARS ---------------------------------------------------------------- 2
NOT EXPOSED TO WEATHER OR IN CONTACT WITH EARTH,
SLABS, WALLS AND JOISTS
#11 BARS AND SMALLER ------------------------------------------------ ¾
#14 AND #18 BARS ----------------------------------------------------------- 1 ½
BEAMS, GIRDERS AND COLUMNS (PRINCIPAL REINFORCEMENT,
STIRRUPS OR SPIRALS) ------------------------------------------------------------------------ 1 ½
21. THE CONTRACTOR SHALL SUBMIT CONCRETE REINFORCING STEEL SHOP DRAWINGS TO THE
RESIDENT ENGINEER.
22. PROVIDE ¾-INCH CHAMFER ON ALL EXPOSED CONCRETE CORNERS, EXCEPT WHERE
MASONRY WALLS ARE LAID FLUSH WITH THE WALL, COLUMN, OR BEAM FACE.
23. EXPOSED CONCRETE WALLS TO HAVE VERTICAL CONTROL JOINTS (FILLED WITH JOINT
SEALER) AT 20’-0” O.C. MAX., EXTENDING DOWN TO TOP OF FOUNDATION. DO NOT CUT OR STOP
HORIZONTAL BARS.
24. FORMWORK SHALL BE ADJUSTED BEFORE AND AFTER CONCRETE PLACING OPERATIONS
(PRIOR TO INITIAL SET) TO COMPENSATE FOR FORMWORK DEFLECTION, IN ADDITION TO ANY
CAMBER SPECIFIED ON THE DRAWINGS.
25. LAP GRADE BEAM TOP BARS AT MIDSPAN, BOTTOM BARS AT SUPPORTS, UNLESS DETAILED
OTHERWISE.
26. NON-CONTINUOUS ENDS OF TOP BARS IN BEAMS AND SLABS SHALL TERMINATE WITH A
STANDARD 90-DEGREE OR 180 DEGREE HOOK, UNLESS SPECIFICALLY NOTED OTHERWISE.
CONCRETE AND BRICK MASONRY:
1. CONCRETE MASONRY UNITS SHALL BE STANDARD WEIGHT. HOLLOW UNITS SHALL CONFORM
TO ASTM C 90 AND SOLID UNITS SHALL CONFORM TO ASTM C 55, GRADE N. MASONRY
COMPRESSIVE STRENGTH (f'm) SHALL NOT BE LESS THAN 2000 PSI. NET AREA COMPRESSIVE
STRENGTH OF MASONRY UNITS SHALL BE 2,800 PSI.
2. ALL MORTAR SHALL CONFORM TO ASTM C-270, TYPE S OR M.
3. FULL MORTAR COVERAGE SHALL BE MADE ON THE FACE SHELLS AND ON THE WEBS
SURROUNDING CELLS TO BE GROUTED.
4. GROUT SHALL CONFORM TO ASTM C-476.
5. GROUT FOR FILLING BLOCK CELLS SHALL BE COURSE AGGREGATE GROUT MEETING ASTM
C476, WITH A MINIMUM STRENGTH OF 2,000 PSI AT 28 DAYS AND A SLUMP RANGE BETWEEN 8"
AND 10".
6. GROUT OR MORTAR ADMIXTURES ARE NOT ALLOWED WITHOUT APPROVAL OF THE ENGINEER.
7. THE CONTRACTOR MAY USE EITHER LOW LIFT OR HIGH LIFT GROUTING PROCEDURES IN
ACCORDANCE WITH THE FOLLOWING SPECIFICATIONS (NOTE: IN NO CASE SHALL THE VERTICAL
DROP OF GROUT BE GREATER THAN 5 FEET.):
LOW LIFT GROUTING
WITH GROUTING LIFTS 5 FEET OR LESS IN HEIGHT: THE WALL SHALL STAND A MINIMUM OF 24
HOURS BEFORE GROUTING. THE GROUT POUR SHALL STOP 1" BELOW THE TOP OF THE LAST
COURSE TO ACT AS A SHEAR KEY BETWEEN THIS LIFT AND THE LIFT ABOVE. THE GROUT
SHALL BE VIBRATED WHEN PLACED AND VIBRATED AGAIN A FEW MINUTES LATER TO
REMOVE AIR POCKETS.
HIGH LIFT GROUTING
WITH GROUTING LIFTS GREATER THAN 5 FEET IN HEIGHT: WHERE ACCESS FROM THE TOP IS
POSSIBLE, THE WALL MAY BE LAID FULL HEIGHT OR TO HORIZONTAL BOND BEAMS,
WHICHEVER IS LESS. CLEAN OUT HOLES SHALL BE PROVIDED IN THE BOTTOM COURSE AT
EVERY VERTICAL GROUTED CELL. VERTICAL REINFORCEMENT SHALL BE SECURED AGAINST
DISPLACEMENT WITH GALVANIZED WIRE POSITIONERS AT 8'-0" O.C. MAX.
8. ALL INTERIOR MASONRY WALLS SHALL BE REINFORCED WITH # 5 VERTICAL REINFORCEMENT AT 24 INCHES O.C. IN GROUTED CELLS, UNLESS NOTED OTHERWISE. THE MASONRY FIRE WALL
SHALL BE REINFORCED WITH # 6 VERTICAL REINFORCEMENT AT 8 INCHES O.C. IN GROUTED
CELLS AND ACHIEVE A 3-HOUR RATING. USE (1) # 6 FULL HEIGHT IN EACH OF TWO CELLS
ADJACENT TO OPENINGS AND CORNERS AND ENDS OF WALLS. ALL MASONRY WALLS SHALL
HAVE GALVANIZED HORIZONTAL JOINT REINFORCEMENT AT 16" O.C. VERTICAL SPACING.
REINFORCEMENT SHALL BE TRUSS TYPE WITH 3/16" SIDE RODS AND 3/16" CROSS RODS.
REINFORCEMENT SHALL BE LAPPED AT ALL SPLICE LOCATIONS PER MANUFACTURER
RECOMMENDATIONS. PROVIDE PREFABRICATED CORNER SECTIONS AND 'T' SECTIONS AT
INTERSECTING WALLS UNLESS NOTED OTHERWISE. PROVIDE BOND BEAMS AT 4’-0” MAXIMUM
HEIGHT AND AT TOP OF WALL, REINFORCED WITH (2)-#5 x CONTINUOUS.
9. ALL MASONRY VENEER THAT HAS STRUCTURAL MASONRY BACKUP SHALL HAVE 3 WIRE
LADDER TYPE HORIZONTAL JOINT REINFORCING AT 16" OC.
10. ALL MASONRY VENEER THAT HAS WOOD OR METAL STUD BACKUP SHALL BE ANCHORED
WITH 2 PIECE ADJUSTABLE WIRE TIES. THE TIES SHALL BE SPACED 16" HORIZONTALLY AND 16"
VERTICALLY.
11. ALL REINFORCING STEEL SHALL BE ASTM A-615, GRADE 60, EXCEPT REINFORCING TO BE
WELDED SHALL BE ASTM A-706, UNLESS NOTED OTHERWISE.
12. VERTICAL REINFORCING SHALL BE LAPPED 72 BAR DIAMETERS AT ALL SPLICES. BARS SHALL
EXTEND VERTICALLY THROUGH BOND BEAMS.
13. ALL VERTICAL REINFORCING SHALL HAVE FOUNDATION DOWELS WITH STANDARD 90-
DEGREE OR 180-DEGREE HOOKS AT BOTTOM MATCHING THE SIZE AND SPACING OF THE
VERTICAL REINFORCING UNLESS NOTED OTHERWISE.
14. ALL MASONRY SHALL HAVE OVERLAPPING MASONRY BONDING AT CORNERS AND WALL
INTERSECTIONS. BOND BEAMS SHALL HAVE CORNER BARS TO MATCH BOND BEAM
REINFORCING.
15. VERTICAL CONTROL JOINTS FOR CONCRETE MASONRY UNITS SHALL NOT EXCEED 30 FEET
O.C AND SHALL NOT EXCEED 6'-0" FROM CORNERS. HORIZONTAL JOINT REINFORCING SHALL BE
DISCONTINUOUS AT CONTROL JOINTS.
16. VERTICAL CONTROL JOINTS FOR BRICK MASONRY UNITS SHALL NOT EXCEED 25 FEET O.C.
AND SHALL NOT EXCEED 10'-0" FROM CORNERS.
17. THE CONTRACTOR SHALL SUBMIT STRUCTURAL MASONRY REINFORCING STEEL SHOP
DRAWINGS TO THE RESIDENT ENGINEER.
STRUCTURAL STEEL:
1. STRUCTURAL STEEL SHALL BE DESIGNED, FABRICATED AND ERECTED IN ACCORDANCE WITH
THE AISC 360 AND AISC 303, LATEST EDITIONS.
2. ALL WIDE FLANGES SHALL BE ASTM A992, GRADE 50, UNLESS NOTED OTHERWISE. CHANNELS, ANGLES AND PLATE MATERIAL SHALL BE ASTM A36, EXCEPT WHERE INDICATED TO BE Fy = 50 KSI, SHALL BE ASTM A572, GRADE 50.
3. ALL STRUCTURAL PIPES SHALL BE ASTM A53, GRADE B, FY = 35 KSI.
4. ALL ROUND HOLLOW STRUCTURAL SECTIONS (HSS) SHALL BE ASTM A500, GRADE C, Fy=46 KSI.
5. ALL RECTANGULAR HOLLOW STRUCTURAL SECTIONS (HSS) SHALL BE ASTM A500, GRADE C,
FY = 50 KSI.
6. ALL STRUCTURAL STEEL BOLTS SHALL BE 3/4" DIAMETER ASTM A325N FOR STANDARD
CONNECTIONS AND SHALL BE ASTM A325SC IN BRACED FRAME OR MOMENT FRAME
CONNECTIONS UNLESS NOTED OTHERWISE. ANCHOR RODS SHALL BE 3/4" DIAMETER ASTM
F1554 WITH A HEAD OR NUT AT THE EMBEDDED END AND A ½” MIN. PROJECTION ABOVE THE TOP
NUT, UNLESS NOTED OTHERWISE.
7. ALL WELDING SHALL BE PERFORMED USING E70XX ELECTRODES BY CERTIFIED WELDERS IN
ACCORDANCE WITH AWS D 1.1 AND D1.8, LATEST EDITIONS.
8. STEEL SHALL BE THOROUGHLY CLEANED OF MILL SCALE PRIOR TO APPLICATION OF THE
PRIMER IN ACCORDANCE WITH SSPC SP-2 OR SP-3 FOR CONCEALED STEEL AND SSPC SP-6 FOR
STEEL EXPOSED TO VIEW.
9. SHOP PAINT CONCEALED STRUCTURAL STEEL WITH ONE COAT, 2 MILS OF FABRICATOR'S
STANDARD PRIMER, AND SHOP PAINT STRUCTURAL STEEL EXPOSED TO VIEW WITH TNEMEC 9097 ZINC RICH PRIMER, SERIES 66 EPOXY, AND SERIES 73 SEMI-GLOSS TOP COAT, 2.5 MILS PER
APPLICATION, COLOR BY OWNER. DO NOT PAINT THE CONTACT SURFACES OF SLIP-CRITICAL
BOLTED CONNECTIONS, OF FIELD WELDED CONNECTIONS OR OF STEEL IN CONTACT WITH
CONCRETE.
10.STANDARD AISC CONNECTIONS SHALL BE USED UNLESS SHOWN OTHERWISE. NO
CONNECTION SHALL HAVE LESS THAN TWO BOLTS OR AN EQUIVALENT WELD.
11.BRACING MEMBERS SHALL BE FRAMED TO THE CENTERLINE OF THE BEAMS AND COLUMNS AT
THE CONNECTION UNLESS NOTED OTHERWISE.
12.MEMBERS COMPOSED OF TWO BACK TO BACK ANGLES OR CHANNELS SHALL HAVE STITCH
BOLTS OR WELDS AT 5'-0" O.C. MAXIMUM UNLESS NOTED OTHERWISE.
13.FACES OF STRUCTURAL STEEL MEMBERS THAT ARE IN CONTACT WITH METAL WALL PANELS
SHALL BE FREE OF PROJECTING NUT AND BOLT HEADS.
14.GALVANIZED STEEL SHALL BE SURFACE PREPARED BY CAUSTIC CLEANING, ACID PICKLING, AND FLUXING, AND SHALL BE HOT DIP GALVANIZED ACCORDING TO ASTM A123, "STANDARD
SPECIFICATION FOR ZINC (HOT DIP GALVANIZED) COATINGS ON IRON AND STEEL PRODUCTS".
15.STEEL PLATE THAT IS TO BE BENT AND HOT DIP GALVANIZED SHALL BE DONE SO IN
ACCORDANCE WITH THE PROCEDURES OF ASTM A143-74 "STANDARD PRACTICE FOR
SAFEGAURDING AGAINST EMBRITTLEMENT OF HOT DIP GALVANIZED STRUCTURAL STEEL
PRODUCTS AND PROCEDURE FOR DETECTING EMBRITTLEMENT".
16.WHEN BENDING PLATE, THE FABRICATOR SHALL CONFORM TO AISC MANUAL OF STEEL
CONSTRUCTION REQUIREMENTS FOR THE MINIMUM RADIUS OF COLD BENDING FOR PLATE.
17.BASE PLATE HOLE AND WASHER SIZES FOR ANCHOR RODS SHALL BE PER AISC
RECOMMENDATIONS.
18.BEARING SURFACES OF COLUMNS SHALL BE FINISHED TO PROVIDE FULL BEARING CONTACT
WITH BASE PLATE (AND CAP PLATE AS REQUIRED FOR LOAD TRANSFER. BASE PLATES (AND CAP
PLATES) SHALL BE FINISHED IN ACCORDANCE WITH SECTION M2.8 OF AISC 360.
19.THE FREE END OF ALL CANTILEVERS SHALL USE FULL-DEPTH STIFFENERS EACH SIDE.
20.THE DESIGN WAS (OR SHALL BE) PERFORMED IN ACCORDANCE WITH AISC 360 USING THE
ALLOWABLE STRESS OR LOAD AND RESISTANCE FACTOR DESIGN METHOD.
21.THE CONSTRUCTION TYPE IS FULLY-RESTRAINED.
22.THE CONTRACTOR SHALL SUBMIT STRUCTURAL STEEL SHOP DRAWINGS TO THE RESIDENT
ENGINEER.
STEEL STAIRS AND GRATING:
1. STRUCTURAL STEEL SHALL BE DESIGNED, FABRICATED AND ERECTED IN ACCORDANCE WITH
THE AISC 360 AND AISC 301, LATEST EDITIONS. DESIGN SHALL BE PERFORMED BY A STRUCTURAL
ENGINEER, LICENSED IN THE STATE OF MISSOURI.
2. ALL WIDE FLANGES SHALL BE ASTM A992, GRADE 50, UNLESS NOTED OTHERWISE. CHANNELS, ANGLES AND PLATE MATERIAL SHALL BE ASTM A36.
3. STAIR TREADS SHALL BE 1" BAR GRATING WITH CHECKER PLATE NOSING.
4. PROVIDE SAFETY NOSING AT THE TOP OF ALL STAIRS AND AT OTHER EXPOSED EDGES OF THE
FLOOR.
5. ALL LADDERS AND STAIRS SHALL BE SUPPORTED BY HANGERS AND POSTS ONLY WHERE
INDICATED AND OTHERWISE BOLTED TO FRAMING MEMBERS, OR ANCHORED TO CONCRETE
WITH 5/8" DIAMETER SCREW ANCHORS EMBEDDED 4" INTO THE CONCRETE.
6. ALL METAL GRATING AND GRATING TREADS SHALL COMPLY WITH THE SPECIFICATIONS OF
THE NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS.
7. WELDED STEEL GRATING SHALL HAVE 1" X 3/16" BEARING BARS AT 1 3/16" O.C., AND CROSS
BARS AT 4" O.C. UNLESS NOTED OTHERWISE.
8. ALL GRATING BEARING AND CROSS BARS SHALL BE IN LINE.
9. BAND ALL EXPOSED EDGES OF GRATING, EXCEPT AT SUPPORTS WHERE GRATING ABUTS
CONCRETE, STEEL OR ADJACENT GRATING PANEL. BAND EDGES AT ALL BLOCKOUTS. ALL
REMOVABLE GRATING PANELS SHALL BE BANDED.
10. CHECKERED FLOOR PLATE SHALL BE REGULAR QUALITY CARBON STEEL SAFETY PLATE AND
SHALL BE FASTENED TO SUPPORTING MEMBERS WITH 3/16" FILLET WELDS 2" LONG, 8" O.C.
UNLESS NOTED OTHERWISE.
11. THE CONTRACTOR SHALL SUBMIT STRUCTURAL STEEL STAIR AND GRATING SHOP
DRAWINGS TO THE RESIDENT ENGINEER.
STEEL DECK:
1. STEEL DECK SHALL CONFORM TO THE STEEL DECK SPECIFICATIONS AND LOAD TABLES OF
THE STEEL DECK INSTITUTE (SDI).
2. STEEL DECK AT THE ROOF OF THE LINK SHALL BE 2” DEEP, 20 GAGE, COMPOSITE DECK AND
SHALL HAVE A MINIMUM YIELD STRESS OF 33,000 PSI.
3. STEEL DECK AT THE CEILING OVER THE COLD FORMED METAL FRAMING SHALL BE 9/16”
DEEP, 24 GAGE NON COMPOSITE DECK. FASTEN 9/16” DECK WITH #12 SCREWS AT 35/5 OR 34/4
PATTERN. NO SIDELAP CONNECTIONS ARE REQUIRED.
4. COMPOSITE AND NON-COMPOSITE STEEL DECK SHALL HAVE A MINIMUM YIELD STRENGTH
OF 50,000 PSI. DO NOT INSTALL CONTRACTION JOINTS IN CONCRETE-FILLED METAL DECK.
5. METAL DECKING SHALL BE CONTINUOUS OVER THREE OR MORE SPANS.
6. FASTEN DECK AT THE LINK WITH 5/8" PUDDLE WELDS AT 36/4 PATTERN AND WELDED
WASHERS AS RECOMMENDED BY MANUFACTURER.
7. METAL DECK AT THE LINK SHALL HAVE A MINIMUM OF #10 TEK SCREWS AT 12" O.C. FOR
SIDELAP FASTENERS. SIDELAPS OF COMPOSITE FLOOR DECK WITH SPANS OVER 5 FEET
SHALL HAVE A MINIMUM OF #10 TEK SCREWS AT 36” O.C.
8. METAL DECK SHALL BE GALVANIZED, UNLESS NOTED OTHERWISE. WHERE WELDING HAS
DAMAGED THE DECK COATING, THE COATINGS SHALL BE REPAIRED IN THE FIELD.
9.SUSPENDED CEILINGS, LIGHT FIXTURES, DUCTS, OR OTHER UTILITIES SHALL NOT BE
SUPPORTED BY THE STEEL ROOF DECK.
10. THE CONTRACTOR SHALL COORDINATE WITH THE OTHER DISCIPLINES’ DRAWINGS AND
THE LOCATION OF ALL OPENINGS CUT THROUGH METAL DECK.
11. ALL HOLES IN THE METAL DECK GREATER THAN 6" BUT LESS THAN 13" WIDE SHALL BE
COVERED WITH A 14-GAGE STEEL PLATE EXTENDING 2 FLUTES BEYOND THE OPENING ON ALL
SIDES AND FASTENED WITH #10 TEK SCREWS AT 6” O.C AROUND PERIMETER. OPENINGS
FROM 13” TO 36” SHALL BE FRAMED ON FOUR SIDES WITH L6x4x3/8 (LLV) ANGLES EXTENDING
TO THE ADJACENT SUPPORTING MEMBERS ON EACH SIDE BEYOND THE OPENING.
12. PROVIDE ADDITIONAL ANGLES AND OTHER MISCELLANEOUS STEEL TO SUPPORT DECKING
AT AREAS WHERE DECK IS CUT FROM COLUMNS OR OTHER PENETRATIONS TO PREVENT
WEAKENED AREAS IN DECK.
13. PROVIDE ALL NECESSARY DETAILS INCLUDING RIDGE AND VALLEY PLATES, CLOSURE
PLATES, AND ANY OTHER ACCESSORIES REQUIRED FOR A FINISHED SURFACE FOR ROOF
INSTALLATION.
14. THE CONTRACTOR SHALL SUBMIT STEEL DECK SHOP DRAWINGS TO THE RESIDENT
ENGINEER
COLD-FORMED METAL FRAMING:
1. ALL STUDS, JOISTS, AND CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWINGS
SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF MISSOURI
FOR THE SPACING AND LOADS INDICATED. WORK SHALL MEET THE REQUIREMENTS OF THE
AMERICAN IRON AND STEEL INSTITUTE (AISI), 'DESIGN OF COLD FORMED STEEL STRUCTURAL
MEMBERS', LATEST STANDARDS.
2. ALL COLD-FORMED STEEL MEMBERS SHALL BE FORMED FROM STEEL CONFORMING TO
ASTM A446 AND HAVING A GALVANIZED COATING MEETING THE REQUIREMENTS OF ASTM
A653.
3. WALL STUDS AT WALLS NOTED TO BE X-BRACED (“W.B.”) AND LOAD BEARING WALLS
(NOTED “LBW”) SHALL BE 'C' SHAPED, AT 16" O.C. WITH 1 5/8" FLANGES AND ½" MINIMUM LIPS, 18 GAGE THICK, AND FY = 33 KSI, UNLESS NOTED OTHERWISE. SEE ARCHITECTURAL FOR STUD
DEPTH, EITHER 3 5/8” OR 6”.
4. WALL STUD TRACKS SHALL BE 18 GAGE THICKNESS WITH FY = 33KSI AND THE TRACKS
SHALL MATCH THE WIDTH OF STUD WALL SPECIFIED.
5. WALL STUD BLOCKING SHALL BE 18 GAGE THICK WITH FY = 33KSI AND THE BLOCKING SHALL
MATCH THE WIDTH AND TYPE OF STUD WALL SPECIFIED.
6. CEILING JOISTS AND FRAMING SHALL BE 'C' SHAPED, AT 16” O.C., WITH 1 5/8" FLANGES AND ½" MINIMUM LIPS, AND FY = 33 KSI. SEE FRAMING PLANS FOR JOIST DEPTH AND THICKNESS.
7. CEILING JOIST CLOSURE TRACKS SHALL MATCH THE DEPTH AND THICKNESS OF THE
JOISTS. CLOSURE TRACKS SHALL BE USED AT THE ENDS OF ALL JOISTS.
8. CEILING JOIST BLOCKING SHALL MATCH THE DEPTH AND GAGE OF JOIST SPECIFIED.
9. PROVIDE ALL ACCESSORIES, INCLUDING TRACKS, BLOCKING, LINTELS, CLIP ANGLES, STRAP
BRACING, SHOES, AND FASTENERS TO PROVIDE A COMPLETE METAL FRAMING SYSTEM. ALL
METAL FRAMING COMPONENTS SHALL HAVE A GALVANIZED FINISH COMPLYING WITH ASTM
A525 FOR A MINIMUM G90 COATING (G60 MAY BE USED FOR INTERIOR FRAMING NOT ON
EXTERIOR WALLS OF THE BUILDING).
10. CONNECTIONS FOR COLD-FORMED STEEL MEMBERS SHALL BE STANDARD DETAILS AS
RECOMMENDED BY THE COLD-FORMED STEEL MANUFACTURER UNLESS NOTED OTHERWISE.
11. FASTENING OF COLD-FORMED STEEL MEMBERS SHALL BE WITH SELF-TAPPING SCREWS
OR WELDING. SELF-TAPPING SCREWS SHALL BE NO. 8 UNLESS NOTED OTHERWISE. SELF-
TAPPING SCREWS SHALL HAVE A MINIMUM SPACING OF ¾" AND A MINIMUM EDGE DISTANCE
OF ¾" UNLESS NOTED OTHERWISE. APPROVED SELF-TAPPING SCREWS SHALL BE SHALL BE
MANUFACTURED BY BUILDEX, COMPASS, OR GRABBER. WIRE TYING OF COMPONENTS IS NOT
PERMITTED.
12. FASTENING OF COLD-FORMED STEEL FRAMING TO STRUCTURAL STEEL SHALL BE WITH
MINIMUM #12 TEK SCREWS OR WITH MINIMUM 0.177 INCH SHANK DIAMETER POWDER DRIVEN
FASTENERS UNLESS NOTED OTHERWISE.
13. FASTENING OF COLD-FORMED STEEL RUNNING TRACK TO CONCRETE FOUNDATION/SLAB
SHALL BE WITH TWO ( 2 ) -1/4" x 1 ¼" SCREW ANCHORS AT 32" O.C. FASTENING OF COLD-
FORMED STEEL FRAMING TO OTHER CONCRETE OR GROUTED SOLID MASONRY SHALL BE
WITH MINIMUM 3/16" x 1 ¼" SCREW ANCHOR UNLESS NOTED OTHERWISE. APPROVED
CONCRETE / MASONRY SCREW ANCHORS SHALL BE:
a. TAPCON ANCHOR, BY ITW RAMSET / REDHEAD,
b. TAPCON ANCHOR, BY FASTENAL COMPANY,
c. KWIK-CON II+ FASTENING SYSTEM, BY HILTI,
d. OR AN APPROVED EQUAL.
14. ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO
PERPENDICULAR MEMBERS, OR, WHERE REQUIRED, FOR AN ANGULAR FT TO ABUTTING
MEMBERS. MEMBERS SHALL BE HELD IN PLACE UNTIL PROPERLY FASTENED.
15. COLD-FORMED STEEL STUDS SHALL BE PLACED DIRECTLY BELOW CEILING JOISTS AND
SHALL HAVE FULL BEARING AGAINST TOP AND BOTTOM TRACK WEB. STUDS SHALL BE
SECURELY ATTACHED TO THE FLANGE OR WEB OF BOTH TOP TRACK AND BOTTOM TRACK
UNLESS NOTED OTHERWISE.
16. SPLICES ARE NOT ALLOWED IN STUD MEMBERS.
17. TRACK MEMBER SPLICES SHALL BE FASTENED WITH BUTT-WELDS OR SHALL BE
FASTENED WITH A PIECE OF STUD INSERTED AND CENTERED IN THE TRACK SPLICE WITH
THREE (3) SCREWS IN EACH TRACK FLANGE FOR TWELVE (12) SCREWS TOTAL. THE
CONTRACTOR SHALL PROVIDE TWO STUDS UNDER ALL TRACK SPLICES.
18. THE CONTRACTOR SHALL USE A MINIMUM OF TWO STUDS SUPPORTING HEADERS AND A
MINIMUM OF THREE STUDS AT CORNERS UNLESS NOTED OTHERWISE.
19.
20. INSTALL WALL STUD BRIDGING AFTER STUDS ARE ERECTED AND BEFORE CONSTRUCTION
LOADS ARE APPLIED. BRIDGING SHALL BE ATTACHED IN A MANNER TO PREVENT STUD
ROTATION. UNLESS NOTED OTHERWISE, BRIDGING SHALL BE SPACED AT 4'-0" ON CENTER
MAXIMUM. FOLLOW RECOMMENDATIONS BY COLD-FORMED STUD MANUFACTURER FOR
BRIDGING.
21. INSTALL CEILING JOIST BRIDGING AFTER JOISTS ARE ERECTED AND BEFORE
CONSTRUCTION LOADS ARE APPLIED. BRIDGING SHALL BE ATTACHED IN A MANNER TO
PREVENT JOIST ROTATION. UNLESS NOTED OTHERWISE, BRIDGING SHALL BE INSTALLED AT
MIDSPAN FOR SPANS 16 FEET OR LESS AND INSTALLED AT 8'-0" O.C. FOR SPANS GREATER
THAN 16 FEET. FOLLOW RECOMMENDATIONS BY COLD-FORMED JOIST MANUFACTURER FOR
BRIDGING.
22.THE CONTRACTOR SHALL SUBMIT COLD-FORMED STEEL FRAMING SHOP DRAWINGS TO THE
RESIDENT ENGINEER.
POST-INSTALLED ANCHORAGE:
1. ALL POST-INSTALLED (MECHANICAL AND/OR ADHESIVE) ANCHORS SHALL BE THE TYPE, SIZE
AND EMBEDMENT AS SHOWN ON THE DRAWINGS. WHEN EMBEDMENT IS NOT SHOWN ON THE
DRAWINGS, THE EMBEDMENT SHALL BE THE STANDARD (NOT MINIMUM) EMBEDMENT AS
RECOMMENDED BY THE MANUFACTURER.
2. THE PLACEMENT OF EXPANSION BOLTS IN MASONRY HEAD JOINTS OR 'T' JOINTS SHALL BE
AVOIDED IF POSSIBLE. EXPANSION BOLTS SHALL HAVE A MINIMUM OF 8" OF GROUT AROUND
ALL SIDES OF THE BOLTS.
3. APPROVED EXPANSION ANCHORS SHALL BE:
a. KWIK BOLT 3 EXPANSION ANCHOR BY HILTI,
b. TRUBOLT WEDGE ANCHOR BY ITW RAMSET / REDHEAD,
c. OR AN APPROVED EQUAL.
4. APPROVED ADHESIVE ANCHORS SHALL BE:
a. HY-200 INJECTION ADHESIVE ANCHOR INTO SOLID CONCRETE OR SOLID MASONRY
BLOCK, BY HILTI,
b. HY-70 INJECTION ADHESIVE ANCHOR WITH SCREEN TUBE INTO HOLLOW MASONRY
BLOCK OR SOLID BRICK WITH VOIDS, BY HILTI,
c. EPCON ADHESIVE ANCHOR SYSYEM WITH CERAMIC 6 EPOXY INTO SOLID
CONCRETE OR SOLID MASONRY, BY ITW RAMSET / REDHEAD,
d. EPCON ADHESIVE ANCHOR SYSYEM WITH CERAMIC 6 EPOXY WITH SCREEN TUBES
INTO HOLLOW MASONRY BLOCK OR SOLID BRICK WITH VOIDS, BY ITW RAMSET /
REDHEAD,
e. OR AN APPROVED EQUAL.
DEMOLITION:
1. PRIOR TO REMOVAL OF THE EXISTING SUPPORTING STRUCTURE, ADEQUATELY SHORE THE
EXISTING PORTIONS SO THAT NO MOVEMENT OCCURS. MAINTAIN THE EXISTING LINES AND
ELEVATIONS AFTER PERMANENT SUPPORTS ARE IN PLACE.
2. SHORING FOR THE EXISTING STRUCTURE MUST BE POSITIONED TO ALLOW THE FACILITY
TO OPERATE AND REMAIN OPEN DURING ITS NORMAL HOURS.
3. ANY DEMOLITION OR CONSTRUCTION WHICH RESULTS IN SIGNIFICANT DUST OR NOISE
MUST BE SEPARATED FROM THE REMAINING BUILDING BY AN ADEQUATE DUST FRAMED
PARTITION AND A POLYETHYLENE LINER.
4. PROVIDE TEMPORARY HOOK-UPS TO ALL DISRUPTED UTILITIES DURING DEMOLITION AND
UNTIL THE NEW PERMANENT HOOK-UPS ARE COMPLETED.
BAR
SIZE
OTHER
TOP
BAR
OTHER
TOP
BAR
DEVEL.
LENGTH
SPLICE
#3 1'-5" 1'-10" 1'-10" 2'-4" 0'-9" 1'-0"
#4 1'-10" 2'-5" 2'-5" 3'-1" 0'-11" 1'-3"
#5 2'-4" 3'-0" 3'-0" 3'-11" 1'-2" 1'-7"
#6 2'-9" 3'-7" 3'-7" 4'-8" 1'-5" 1'-11"
#7 4'-0" 5'-3" 5'-3" 6'-9" 1'-8" 2'-3"
#8 4'-7" 6'-0" 6'-0" 7'-9" 1'-10" 2'-6"
#9 5'-2" 6'-9" 6'-9" 8'-9" 2'-1" 2'-10"
#10 5'-10" 7'-7" 7'-7" 9'-10" 2'-4" 3'-3"
#11 6'-6" 8'-5" 8'-5" 10'-11" 2'-7" 3'-7"
DEVELOPMENT
LENGTH CLASS 'B' SPLICE
TENSION COMPRESSION
fy=60000 PSI f'c=3500 PSI
NOTES:
1. IF CONCRETE CLEAR COVER IS LESS THAN 1.0 x db OR CENTER-TO-CENTER SPACING IS LESS THAN 3.0 x db, MULTIPLY LENGTH BY 1.5 (db = BAR DIAMETER)
2. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 1'-0" OF
CONCRETE CAST BELOW THE BARS.
3. FOR LIGHTWEIGHT CONCRETE, MULTIPLY LENGTH BY 1.33.
4. FOR GRADE 75 BARS (IF APPLICABLE), MULTIPLY LENGTH BY 1.25.
5. TABULATED VALUES ARE FOR UNCOATED OR ZINC-COATED
(GALVANIZED) BARS. FOR EPOXY COATED BARS MULITPLY
LENGTH BY 1.5.
BAR
SIZE
OTHER
TOP
BAR
OTHER
TOP
BAR
DEVEL.
LENGTH
SPLICE
#3 1'-2" 1'-6" 1'-6" 1'-11" 0'-8" 1'-0"
#4 1'-6" 2'-0" 2'-0" 2'-6" 0'-9" 1'-3"
#5 1'-11" 2'-5" 2'-5" 3'-2" 1'-0" 1'-7"
#6 2'-3" 2'-9" 2'-9" 3'-10" 1'-2" 1'-11"
#7 3'-3" 4'-3" 4'-3" 5'-6" 1'-4" 2'-3"
#8 3'-9" 4'-11" 4'-11" 6'-4" 1'-6" 2'-6"
#9 4'-3" 5'-6" 5'-6" 7'-2" 1'-9" 2'-10"
#10 4'-9" 6'-2" 6'-2" 8'-0" 1'-11" 3'-3"
#11 5'-4" 6'-10" 6'-10" 8'-11" 2'-2" 3'-7"
DEVELOPMENT
LENGTH
CLASS 'B' SPLICE
TENSION COMPRESSION
fy=60000 PSI f'c=4500 PSI
NOTES:
1. IF CONCRETE CLEAR COVER IS LESS THAN 1.0 x db OR CENTER-TO-CENTER SPACING IS LESS THAN 3.0 x db, MULTIPLY LENGTH BY 1.5 (db = BAR DIAMETER)
2. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 1'-0" OF
CONCRETE CAST BELOW THE BARS.
3. FOR LIGHTWEIGHT CONCRETE, MULTIPLY LENGTH BY 1.33.
4. FOR GRADE 75 BARS (IF APPLICABLE), MULTIPLY LENGTH BY 1.25.
5. TABULATED VALUES ARE FOR UNCOATED OR ZINC-COATED
(GALVANIZED) BARS. FOR EPOXY COATED BARS MULITPLY
LENGTH BY 1.5.
TABLE 033000- 1d - BAR LAP &
DEVELOPMENT LENGTHS
TABLE 033000- 1b - BAR LAP &
DEVELOPMENT LENGTHS
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 1
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
DRS / BAS MGJ
A u to d e s k D o c s /2
-1
A
-2
-3
V A
P o p la r B lu ff
R e m o v e a n d R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B M
B .S tr u c t_
R
V
A P
B
M O
-M e ta lB ld g .r v t
/1
/2
:5
:5
P
M
SG001
STRUCTURAL GENERAL NOTES REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATION, AND
AIR CONDITIONING
657A4-21-800
8/30/24
MODULAR BLDG.
Mark Revisions: Date:
L-A
L-B
L-C
L-1 L-2 L-3
DEMO CONNECTOR LINK
SUPERSTRUCTURE
AND MAT FOOTING, U.N.O.
SAWCUT FOUNDATION
WALLS AND MAT FTG.
FROM STOOP
SD101
E9DEMO
STEEL
COL'S
(E) CANOPY COL. &
FTG. TO REMAIN
DEMO PLAN NOTES:
1. FOR STRUCTURAL GENERAL NOTES, SEE SHEET SG001.
2. HATCHING INDICATES STRUCTRUE TO BE DEMOLISHED.
DEMO MODULAR BLDG & ALL FOUNDATIONS, U.N.O.
L-A
L-B
L-3
DEMO STEEL LINK STRUCTURE
DOWN TO TOP OF SLAB - SAWCUT
OFF ANCHOR BOLTS AND COAT
TOPS W/ EPOXY PAINT
(E) HOSPITAL
ENTRANCE
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 1
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
DRS / BAS MGJ
A u to d e s k D o c s /2
-1
A
-2
-3
V A
P o p la r B lu ff
R e m o v e a n d R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B M
B .S tr u c t_
R
V
A P
B
M O
-M e ta lB ld g .r v t
/1
/2
:5
:4
P
M
SD101
PHASE 4 - DEMO PLAN REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATION, AND
AIR CONDITIONING
657A4-21-800
8/30/24
MODULAR BLDG.
3/16" = 1'-0"F2
PHASE 4 - DEMO PLAN
1/4" = 1'-0"E9
PARTIAL DEMO PLAN
(E) CANOPY COLUMN & FTG.
- SIZE OF (E) FTG. IS NOT KNOWN
CONTRACTOR FIELD VERIFY SIZE
AND DEPTH OF FTG. AND NOTIFY
ENGINEER
4' - 0" 2' - 11 1/2"
2' - 3"
L-A
L-B
L-C
L-1 L-2 L-3
/4
(F .V
/2
6' - 9 1 /4"
(F.V.)
6' - 10"
6"
HSS 5x5x1/2 POST
(B.O.S. EL. = 431'-10")
TYP. 12 PLACES
6"
/4
/2
6"
2'-8" TH. CONC. MAT FTG.
W/ #8 @ 12" O.C., EA. WAY,
TOP & BOT. (B.O.F. EL. = 429'-0")
12" CMU, 2-HR FIRE RATED WALL (B.O.W.
EL. = 431'-8") WALL SHALL TERMINATE AT INT.
SURFACE OF MTL. SIDING & BOT. OF ROOF
DECK OR SHTG. - SEE ARCH.
10" TH. CONC. WALL - TYP
OVER MAT FTG. (T.O.W. EL. = 433'-0")
10" TH. CONC. WALL,
OVER MAT FTG.
(T.O. SLAB
EL. = 433'-0")
1' - 11 1/2"
7' - 10 3/4"
(F.V.)
5' - 9 3/4"
PROVIDE MATCHING HORIZ. DOWELS
IN FOOTING, FNDN. WALL & STOOP SLAB
- DRILL & EPOXY W/ HILTI HY200
(EMBED 6") - TYP.
C6
SF501
B.O.F.
429' - 0"
TYP.
BP-2 BP-2
BP-1
BP-1
BP-1
BP-1
BP-1
BP-1
CONST. JT. W/ BLDG.
PAPER OR 30 LB
FELT IN VERT. PLANE
EXISTING SLAB AND
FNDN UNKNOWN -
CONTRACTOR TO
DETERMINE IN
FIELD AS REQ'D
432' - 0"
T.O.W.
@ DOOR
MODULAR BUILDING COMPLEX (MBC)
(TEMPORARY CONSTRUCTION)
(NORTH OF FIRE WALL)
(DELEGATED DESIGN)
TO FACE OF TEMPORARY
CONSTRUCTION (NO HEAVY
EQUIPMENT WITHIN 7 FEET
OF EXISTING RETAINING WALL)
(E) RETAINING WALL
(RETAINED SIDE) (LOW SIDE)
(A B
O V
E M
A T
E
X P
J T
(E) ENCLOSED
VESTIBULE
(E) ENCLOSED
COLUMN
(E) HOSPITAL BUILDING
15' - 11 1/2" 4' - 7"
4' - 1"
10'-0" MIN.
C1
SF501
B8
SF501
C3
SF501
DEDUCT ALTERNATE -
SEE AG002 &
BUILDING 1
DRAWINGS
FOUNDATION PLAN NOTES:
1. FOR STRUCTURAL GENERAL NOTES, SEE SHEET SG001.
2. INDICATES: 5" SLAB-ON-GRADE, ELEV. = 433'-0" (MATCH EXIST.)
3. INDICATES: STOOP SLAB - 8" MIN. CONC. OVER 6" VOID FORM
4. "F.V." INDICATES FIELD VERIFY DIMENSION PRIOR TO FABRICATION AND ERECTION. ALL
DIMENSIONS OF EXISTING STRUCTURES ARE BASED ONLY ON AVAILABLE DRAWINGS.
6. "CF-1" INDICATES 24x16 CONTINUOUS FTG., SEE
7. "F-X" INDICATES SPREAD FTG'S, SEE
TEMPORARY CONSTRUCTION STRUCTURAL DESIGN CRITERIA
GENERAL NOTES:
1. CONFIGURATION OF TEMPORARY SPACE TO BE DETERMINED BY THE CONTRACTOR.
ILLUSTRATION SHOWN ONLY TO DISTINGUISH BETWEEN CONSTRUCTION WITH DIFFERENT
STRUCTURAL REQUIREMENTS, NOT TO CONVEY ANY INTENDED SIZES OR LOCATIONS (DIAGRAM
NOT TO SCALE).
INDICATES "EXTENDED SPACE"
INDICATES "CONNECTORS / CORRIDORS / RAMPS"
INDICATES "STAIRS AND PLATFORMS"
INDICATES "SPECIALTY SPACE"
2. ALL TEMPORARY CONSTRUCTION IS DELEGATED DESIGN TO THE CONTRACTOR AND ALL
ASSOCIATED STRUCTURES (INCLUDING ANY TEMPORARY TRAILERS, MODULES, ETC.) SHALL BE
DESIGNED BY A STRUCTURAL ENGINEER LICENSED IN THE STATE OF MISSOURI.
3. THE STRUCTURES FOR ALL TEMPORARY SPACES SHALL BE DESIGNED FOR THE LOADS AND
CRITERIA OF THE DEPARTMENT OF VETERANS AFFAIRS "STRUCTURAL DESIGN MANUAL FOR
HOSPITAL...PROJECTS," DATED 1 FEB 2014, UNLESS SPECIFICALLY INDICATED OTHERWISE.
4. ALL TEMPORARY CONSTRUCTION SHALL BE SUPPORTED BY FOUNDATIONS PROTECTED
FROM FROST (36" MIN. BELOW GRADE) TO MINIMIZE DISPLACEMENT DUE TO SEASONAL
VARIATIONS, UNLESS SPECIFICALLY INDICATED OTHERWISE. A CRUSHED ROCK PAD IS TO BE
PROVIDED (SEE CIVIL) AND ALL DEPTH MEASUREMENTS TAKEN FROM THE LOWEST GRADE
WITHIN THE FOOTPRINT OF THE CONTRACTOR'S FOUNDATION SYSTEM.
5. CONSTRUCTION SHALL BE POSITIVELY ATTACHED TO FOUNDATIONS OR GROUND TO
ADEQUATELY RESIST THE DESIGN SEISMIC FORCES FROM THE VA DESIGN STANDARD, UNLESS
SPECIFICALLY INDICATED OTHERWISE.
6. ALL WOOD CONSTRUCTION SHALL BE APPROPRIATELY PROTECTED FROM TERMITES.
7. EACH TEMPORARY STRUCTURE SHALL HAVE A SEISMIC-FORCE-RESISTING-SYSTEM (SFRS)
THAT IS PERMISSIBLE IN SEISMIC DESIGN CATEGORY "D" FOR THE HEIGHT OF THE STRUCTURE
PER ASCE 7.
8. ALL SPACES SHALL BE DESIGNED FOR THE UNIFORM LIVE LOADS INDICATED BELOW IN
ADDITION TO A CONCENTRATED LOAD OF 2000 LB, PLACED UPON ANY SPACE 2.5 FT SQUARE,
WHEREVER THIS LOAD UPON AN OTHERWISE UNLOADED FLOOR WOULD PRODUCE STRESSES
GREATER THAN THOSE CAUSED BY THE UNIFORM LOAD.
9. ALL TEMPORARY SPACES SHALL BE APPROPRIATELY DESIGNED TO SUPPORT THE WEIGHTS
OF THE ACTUAL PROCURRED EQUIPMENT AND RELOCATED EQUIPMENT, INCLUDING ANY
SUPPORT FOR TRANSPORTATION OF THE EQUIPMENT THROUGH THE TEMPORARY SPACES.
EXTENDED SPACES
1. EXTENDED SPACES SHALL BE DESIGNED FOR A LIVE LOAD PER THE LINE ITEMS BELOW
ACCOMODATING ALL LAYOUTS PROPOSED BY THE CONTRACTOR (I.E., MORE THAN THE MINIMUM
MAY BE USED TO ALLOW FOR OTHER CONFIGURATIONS):
A. ADMINISTRATIVE (E.G. OFFICES): 80 PSF + 20 PSF PARTITIONS
B. RESTROOMS: 80 PSF
C. CORRIDORS/HALLWAYS: 100 PSF
D. DENTAL AREAS: 60 PSF + 20 PSF PARTITIONS
E. DENTAL LAB AREAS: 100 PSF
F. LAUNDRY AREAS (NO EQUIPMENT PERMITTED): 150 PSF.
G. MAILROOM AREAS: 125 PSF
H. CLINIC AND SUPPORT SERVICES: 80 PSF + 20 PSF PARTITIONS
I. STORAGE AREAS (LIGHT): 150 PSF
J. JANITORS/HOUSEKEEPING CLOSETS: 100 PSF
K. LABORATORY: 100 PSF
STAIRS AND PLATFORMS:
1. STAIRS AND PLATFORMS SHALL BE DESIGNED FOR A LIVE LOAD OF
100 PSF.
CONNECTORS/CORRIDORS/RAMPS:
1 CONNECTORS, CORRIDORS, AND RAMPS SHALL BE DESIGNED FOR A LIVE LOAD OF 100 PSF.
SPECIALTY SPACES:
1. SPECIALTY SPACES SHALL BE DESIGNED FOR A LIVE LOAD PER THE LINE ITEMS BELOW:
A. LABORATORY: 100 PSF.
B. DENTAL: 60 PSF.
C. DENTAL LAB AREAS: 100 PSF
D. LAUNDRY AREAS (NO EQUIPMENT PERMITTED): 150 PSF
E. MAILROOM AREAS: 125 PSF
F. CLINIC AND SUPPORT SERVICES: 80 PSF + 20 PSF PARTITIONS
G. STORAGE AREAS (LIGHT): 150 PSF
2. SPECIALTY SPACES WHICH ARE TO BE IN PLACE NO LONGER THAN 12 MONTHS MAY BE
SUPPORTED ON THE CRUSHED ROCK PAD WITHOUT A FOUNDATION DOWN TO FROST,
PROVIDED THE CONTRACTOR AND MANUFACTURER DO NOT REQUIRE SUCH SUPPORT.
3. SPECIALTY SPACES WHICH ARE TO BE IN PLACE NO LONGER THAN 12 MONTHS DO NOT
REQUIRE POSITIVE ATTACHMENT TO THE FOUNDATION OR GROUNT BE SUPPORTED.
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 1
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
DRS / BAS MGJ
A u to d e s k D o c s /2
-1
A
-2
-3
V A
P o p la r B lu ff
R e m o v e a n d R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B M
B .S tr u c t_
R
V
A P
B
M O
-M e ta lB ld g .r v t
/1
/2
:5
:5
P
M
SF101
PHASE 1 - FOUNDATION PLAN REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATION, AND
AIR CONDITIONING
657A4-21-800
8/30/24
MODULAR BLDG.
3/16" = 1'-0"F2
PHASE 1 - FOUNDATION PLAN
L-A
L-B
L-C
L-1 L-2 L-3
HSS5x5x1/2
H S
S x x /2
H S
S x x /2
H S
S x x /2
H SS5x
5x 1/
HSS5x5x1/2
HSS5x5x1/2
H S
S x x /2
(T.O.S. EL. = 442'-5 1/2")(T
.O
.S E
L
/2
(T.O.S. EL. = 443'-5")(T.O.S. EL. = 443'-5")
(T .O
.S E
L
T Y
P A
L O
N G
L -1
HSS 5x5x1/2 POST
(T.O.S. EL. AS SHOWN)
TYP. 12 PLACES
12" CMU, 2-HR FIRE RATED WALL (B.O.W.
EL. = 432'-0") WALL SHALL TERMINATE AT INT.
SURFACE OF MTL. SIDING & BOT. OF ROOF
DECK OR SHTG. - SEE ARCH.
E1
SF501
H S
S x x /2
H S
S x x /2
HSS5x5x1/2
(F .V
/4
(F .V
/2
6' - 10 1/2"
(F.V.)
6' - 10"
E .J
3' - 6"
(E) CANOPY COLUMN
(CONSTRUCTION UNKNOWN)
(E) CANOPY COLUMN
(CONSTRUCTION UNKNOWN)
4" E.J.
H S
S 5x5 x1/2H S
S x5 x1 /2
MODULAR BUILDING COMPLEX (MBC)
- SEE SHEET SF101
M
IN
E .J
SF501
B3
FRAMING PLAN NOTES:
1. FOR STRUCTURAL GENERAL NOTES, SEE SHEET SG001.
2. HSS 5x5x3/8 (T.O.S. EL. = 443'-5")
3. INDICATES MOMENT CONNECTION - SEE
4. INDICATES SPAN DIRECTION OF 2"-20 GA. COMPOSITE METAL
DECK WITH 4 1/2" NORMAL WEIGHT CONCRETE (6 1/2" TOTAL) WITH #3 @ 14"
O.C., EA. WAY.
5. COORDINATE WITH OTHER DISCIPLINES AND EQUIPMENT PROCURRED FOR
PENETRATIONS AND OPENINGS. ALL PENETRATIONS SHALL BE SLEEVED.
6. "MBC" INDICATES MODULAR BUILDING COMPLEX (DELEGATED DESIGN)
7. "F.V." INDICATES FIELD VERIFY DIMESION PRIOR TO FABRICATION AND
ERECTION. ALL DIMESIONS OF EXISTING STRUCTURES ARE BASED ON ON
AVAILABLE DRAWINGS.
8. "E.J." INDICATES EXPANSION JOINT AND SHALL BE THE MINIMUM DISTANCE
FROM ALL LOCATION AND SURFACES OF ADJACENT STRUCTURES.
9. INDICATES (DOWNWARD) SLOPING STRUCTURE - SEE ARCH.
INDICATES BEAM SIZE
INDICATES TOP OF STEEL ELEVATION
B1
SF501
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA…