This document is a set of architectural demolition and renovation plans for the John J. Pershing Veterans' Administration Medical Center in Poplar Bluff, Missouri. The drawings detail a comprehensive project to remove and replace end-of-life heating, ventilation, and air conditioning (HVAC) infrastructure in Building 1. The plans cover multiple floors (ground, first, second, fourth) and include detailed demolition plans for ceilings, roofs, and mechanical systems across various wings and departments such as dental, medical records, laboratories, and clinical areas.

The drawings provide extensive technical specifications for the demolition process, including removing existing air handling units, ductwork, roofing materials, and ceiling components. A key feature is the option for a "Deduct Alternate" that allows the VA to selectively remove or modify parts of the project scope, such as deleting work in specific wings or removing certain mechanical systems. The plans emphasize maintaining continuous VA operations during construction, with careful coordination required for infrastructure modifications and temporary building arrangements.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FRONT APPROACH, PULL SIDE FRONT APPROACH, PUSH SIDE

NOTE: X=12" MINIMUM IF DOOR HAS

BOTH A CLOSER AND LATCH

HINGE SIDE APPROACHES - SWINGING DOORS

LATCH SIDE APPROACHES - SWINGING DOORS

NOTE:

1. ALL DOORS IN ALCOVES SHALL COMPLY WITH CLEARANCES FOR FRONT APPROACHES.

HINGE APPROACH, PULL SIDE HINGE APPROACH, PUSH SIDE

LATCH APPROACH, PULL SIDE LATCH APPROACH, PUSH SIDE

NOTE: X=36" MINIMUM IF Y=60"; X=42"

MINIMUM IF Y=54".

NOTE: Y=48" MINIMUM IF DOOR HAS

BOTH A LATCH AND CLOSER.

NOTE: Y=54" MINIMUM IF DOOR HAS

CLOSER.

NOTE: Y=48" MINIMUM IF DOOR HAS

CLOSER.

FRONT APPROACHES - SWINGING DOORS

MIN.

18"

M

IN

M

IN

X

54" MIN.

M

IN

.60

X

MIN.

24"

M

IN

M

IN

MIN.

24" X X

Y Y

Y

PULL SIDE PUSH SIDE

POCKET OR HINGE APPROACH - SLIDING BARN DOORS

POCKET OR HINGE APPROACH STOP OR LATCH APPROACH

FRONT AND SIDE APPROACHES - NO DOORS

M

IN

M

IN

24"42

M

IN

22" MIN. 42

M

IN

GENERAL SYMBOLS

A101

SIM

A101

SIM

1i

A101

SIM

D

SCALE:1 View Name 1/8" = 1'-0"

A

NTRUE

NORTH

A

B

EARTH

EARTH GRAVEL

CONCRETE

METALS

BRICK

CMU

TILE

STONE

WOOD

GYPSUM

GLASS

INSULATION

REGULAR

STEEL ALUMINUM

FACE COMMON

CMU

CERAMIC

MARBLE LIMESTONE

FINISH BLOCKING

PLASTER OR GWB

LARGE SCALE SMALL SCALE

BATT OR LOOSE RIGID

SURFACE

ACTUAL SQ. FT.

PROGRAMMED SQ. FT.

ROOM NUMBER

DOOR NUMBER

KEYNOTE

WALL TYPE

REVISION NUMBER

ELEVATION INDICATION

COLUMN GRID

IDENTIFICATION

NORTH ARROW

XXX WINDOW NUMBER

DETAIL TITLE

BUILDING SECTION

WALL SECTION

EXTERIOR/INTERIOR

ELEVATION

INTERIOR MULTI-VIEW

ELEVATION

ELEVATION NUMBER

SHEET ON WHICH

ELEVATION IS DRAWN

ELEVATION NUMBER

SHEET ON WHICH

ELEVATION IS DRAWN

MATERIALS REFERENCE

Room Name

150 PSF / 150 SF

PROPERTY CORNER

PROPERTY LINE

4" UNDERGROUND COMMUNICATION

(NO. INDICATES NO. OF DUCTS)

4" UNDERGROUND DUCT

(NO. INDICATES NO. OF DUCTS)

TELEPHONE LINE OH

UNDERGROUND ELECTRICAL

CONDUIT

OVERHEAD POWER LINE

ELECTRICAL MANHOLE

P/T = POWER & TELEPHONE

W/ STREET LIGHT

W/ DOWN GUY (NO. INDICATES LENGTH, CLASS

GUY & ANCHOR STRENGTH)

POWER POLE (NO. INDICATES LENGTH &

CLASS)

REMOVE OR ABANDON LINE

VALVE

GAS LINE

IRRIGATION WATER MAIN

FIRE WATER LINE

WATER LINE

STORM SEWER

SANITARY SEWER FORCE MAIN

SANITARY SEWER

CURB LINE

STREET CENTER LINE

BUILDING

EXISTING NEW

SITE

EXISTING NEW

S

MH CO

SFM

SS SS

MH

CLAL

Y.D.

F.H.

W

F

IRM

G

4M

P T

P T

P

UG

T

2-T

P

UG

T

2-T

POLE

4M

45-2

45-2

G

IRM

F

Y.D.

F.H.

W

AL

SS SS

MH

SFM

S

MH CO

GRID COORDINATES

SECTION LINE

CONTOURS

SPOT ELEVATIONS

DRAINAGE DITCH OR SWALE

CONCRETE PAVEMENT (SECTION)

BITUMINOUS PAVEMENT (SECTION)

CONTRACTION JOINT FOR PAVEMENT

BORINGS, TEXT

TREES, DECIDUOUS - WITH

DIAMETER

EVERGREEN - WITH HEIGHT

SHRUBS

CHAIN-LINK FENCE

BARBED WIRE FENCE

SECURITY FENCE XX XX

XX

XX XX

XX

12"

10'

HIGH

12" (TO BE REMOVED)

10' (TO BE REMOVED)

HOLE #3

90 X 10W 90 X 10 W (TOP OF WALL)

90 X 10C 90 X 10 C (TOP OF CURB)

90 X 10P 90 X 10 P (TOP OF PAVEMENT)

90 X 10 90 X 10

SEC 24

SEC 25

290 N

90 W

09 20 00.A1

A101

SIM

DETAIL SECTION

AE201

CONTRACTOR SHALL REFER TO THE MODULAR

BUILDING COMPLEX PACKAGE FOR COORDINATION

AND RELOCATION DURING PHASING OF

DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,

ETC. REQUIRED FOR CONTINUED VA OPERATIONS.

MODULAR BUILDING

COMPLEX COORDINATION

JIM

H.

HAGEMAN

A-2205

A

R C H I T E

C

T

S T

A T

E

O F N E B

R A

S K

A

8/30/2024

Project Number

Building Number

Drawing Number

Project Title

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

IMEG Corp.

15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132

CC

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

A u to d e s k D o c s

/2

-1

A -2

-3

V

A P o p la r

B lu ff

R e m o v e a n d

R e p la c e

L a b A

H U a n d A

H U

/6

A

-2

-3

.B

.A rc h R

-1

-R e p l L a b A

H U

A

H U

.r v t

/9

/2

:0

:0

P M

AG001

ARCHITECTURAL ABBREVIATIONS

& LEGENDS

REMOVE AND REPLACE END OF

LIFE HEATING, VENTILATION, AND

AIR CONDITIONING

JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL

CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO

63901-3318

657A4-21-800

8/30/2024 GG KRK

1/4" = 1'-0"1

GUIDE FOR CLEARANCES AT DOORS

ABBREVIATIONS

A

A/C AIR CONDITIONING

AB ANCHOR BOLT / AIR BLENDER

ABS ACRYLONITRILE-BUTADIENE-STYRENE

AC ALTERNATING CURRENT / AIR COMPRESSOR

ACP ASBESTOS CEMENT PIPE

ACU AIR CONDITIONING UNIT

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ADJ ADJACENT / ADJUSTABLE

ADR ACCESS DOOR

AFF ABOVE FINISH FLOOR

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

APPROX APPROXIMATELY

APT APARTMENT

ARCH ARCHITECT(URAL)

ASPH ASPHALT

AT ACOUSTICAL PANEL CEILING

ATB AIR TERMINAL BOX

ATD AIR TRANSFER DUCT

ATU AIR TERMINAL UNIT

AUX AUXILIARY

AVG AVERAGE

AWC ACOUSTICAL WALLCOVERING

AZ AZIMUTH

B

BB BALLED AND BURLAPPED

BD BOARD

BDD BACK DRAFT DAMPER

BE BOTTOM ELEVATION

BL BUILDING LINE

BLDG BUILDING

BLKG BLOCKING

BM BENCH MARK / BEAM

BR BARE ROOT

BRG BEARING

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

C/C CENTER TO CENTER

CAB CABINET

CB CIRCUIT BREAKER / CATCH BASIN

CC COOLING UNIT

CE COVER ELEVATION

CEM CEMENT

CFM CUBIC FEET PER MINUTE

CFS CONCRETE FLOOR SEALER

CG CORNER GUARD

CH CHILLER

CI CURB INLET / CAST IRON

CIP CAST IRON PIPE

CJ CONTROL JOINT OR CONTRACTION JOINT

CKT CIRCUIT

CL CENTER LINE

CLG CEILING

CLO CLOSET

CLR CLEAR

CM CENTIMETER

CMH CUBIC METER PER HOUR

CMP CORRUGATED METAL PIPE

CMT CERAMIC MOSAIC TILE

CMU CONCRETE MASONRY UNIT

CO CLEANOUT / CARBON MONOXIDE

CO2 CARBON DIOXIDE

COL COLUMN

COMB COMBINATION / COMBINE

COMP COMPRESSIBLE

CONC CONCRETE

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUOUS / CONTINUATION

CONTR CONTRACTOR

CORR CORRIDOR

CP CEMENT PIPE

CPT CARPET

CSF CUBIC FEET PER SECOND

CT CERAMIC TILE / COOLING TOWER

CTR CENTER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CUYD CUBIC YARD

CW COLD WATER

D

D DRAIN / DIFFUSER

DA DENTAL AIR

DBL DOUBLE

DEPR DEPRESSED

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIFF DIFFUSER

DIP DUCTILE IRON PIPE

DISC DISCONNECT

DISP DISPENSER

DIST DISTRIBUTION

DK DECK

DL DEAD LOAD

DN DOWN

DO DITTO

DPR DAMPER

DR DOOR

DS DOWNSPOUT

DV DENTAL VACUUM

DWG DRAWING

DWL DOWEL

DWP DOMESTIC WATER PUMP

E

E EPOXY

EA EACH / EXHAUST AIR

EF EACH FACE / EXHAUST FAN

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC(AL)

ELEV ELEVATOR

EMBED EMBEDMENT

EMD ESTIMATED MAXIMUM DEMAND

EMT ELECTRICAL METAL TUBING

EQ EQUAL

EQUIP EQUIPMENT

ET EXPANSION TANK

EVAC MEDICAL GAS EVACUATION

EW EACH WAY

EWC ELECTRICAL WATER COOLER

EWH ELECTRICAL WATER HEATER

EXH EXHAUST

EXIST EXISTING

EXP EXPOSED

EXPN EXPANSION

EXT EXTERIOR

F

F FIRE MAIN

FA FIRE ALARM

FCU FAN COIL UNIT

FD FLOOR DRAIN / FIRE DAMPER

FD / SD COMBINATION FIRE AND SMOKE DAMPER

FDC FIRE DEPARTMENT CONNECTION

FDN FOUNDATION

FDR FEEDER

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FH FIRE HYDRANT

FHC FIRE HOSE CABINET

FIN FINISH

FIX FIXTURE

FL FLOOR

FM FORCE MAIN / FACTORY MUTUAL

FP FIREPROOFING / FIRE PUMP

FPM FEET PER MINUTE

FR FIRE RATED

FRP FIBERGLASS REINFORCED PLASTIC

FS FLOW SWITCH

FT FEET

FTG FOOTING

FVC FIRE VALVE CABINET

G

G GAS / GRILLE

GA GAGE

GALV GALVANIZED

GB GRAB BAR

GBD GRAVITY BACKDRAFT DAMPER

GEN GENERATOR

GFRC GLASS FIBER REINFORCED CONCRETE

GI GALVANIZED IRON

GL GLASS

GLB GLASS BLOCK

GP GLAZED PAINT

GPM GALLONS PER MINUTE

GR GRADE

GRV GRAVITY ROOF VENTILATOR

GWB GYPSUM WALLBOARD

GYP GYPSUM

H

HB HOSE BIBB

HC HEATING COIL

HDNR HARDENER

HDW HARDWARE

HDWD HARDWOOD

HK1E HOOK ONE END

HK2E HOOK TWO ENDS

HM HOLLOW METAL

HORIZ HORIZONTAL

HP HORSEPOWER

HPT HIGH POINT

HR HOUR

HS HIGH STRENGTH

HT HEIGHT

HTG HEATING

HTR HEATER

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

HW HOT WATER

HWC HOT WATER CIRCULATING

HZ HERTZ

I

IA INSTRUMENT AIR

IC INTERCOM

ICB INTEGRAL COVE BASE

ID INSIDE DIAMETER

IE INVERT ELEVATION

IF INSIDE FACE

IN INCH

INSUL INSULATION

INT INTERIOR

J

JAN JANITOR

JB JUNCTION BOX

JP JOCKEY PUMP

JST JOIST

JT JOINT

K

KC MIL THOUSAND CIRCULAR MILS

KCJ KEYED CONSTRUCTION JOINT

KIT KITCHEN

KPA KILOPASCALS

KS KITCHEN SINK

KV KILOVOLT

KVA KILOVOLT AMPERE

KW KILOWATTS

L

L LITER

LA LABORATORY AIR

LAB LABORATORY

LAM LAMINATE

LAV LAVATORY

LBS POUNDS

LF LINEAR FEET

LIN LINEAR

LL LIVE LOAD

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LMU LIGHTWEIGHT MASONRY UNITS

LONG LONGITUDINAL

LPM LITERS PER MINUTE

LT LIGHT

LT WT LIGHT WEIGHT

LTG LIGHTING

LV LABORATORY VACUUM

LVL LEVEL

LVT LUXURY VINYL TILE

M

M METER

M2 SQUARE METER

M3 CUBIC METER

MA MEDICAL AIR

MAINT MAINTENANCE

MAR MARBLE

MAS MASONRY

MAT MATERIAL / ENTRY CARPET

MAX MAXIMUM

MBH 1000 BTUH

MDO MEDIUM DENSITY OVERLAY

MECH MECHANICAL

MET METAL

MFR MANUFACTURER

MG MOTOR GENERATOR / MEDICAL GAS

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MM MILLIMETER

MO MASONRY OPENING

MTD MOUNTED

MTG MOUNTING

MULL MULLION

MV MEDICAL VACUUM

N

N NITROGEN

N2O NITROUS OXIDE

NEC NATIONAL ELECTRICAL CODE

NFPA NATIONAL FIRE PROTECTION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

O/S OFFSET

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

OC ON CENTER

OD OUTSIDE DIAMETER

OF OUTSIDE FACE

OPNG OPENING

OPP OPPOSITE

OX OXYGEN

OZ OUNCE

P

P PAINT / PUMP / PENDANT

PA PASCAL

PART PARTITION

PAVT PAVEMENT

PC POINT OF CURVATURE

PCF POUNDS PER CUBIC FOOT

PED PEDESTAL

PERP PERPENDICULAR

PHC PREHEAT COIL

PHVAC PLUMBING, HEATING, VENTILATING AND AIR

CONDITIONING

PI POINT OF INTERSECTION

PIV POST INDICATOR VALVE

PKG PARKING

PL PLASTIC LAMINATE / PROPERTY LINE / PLATE

PLAS PLASTER

PLBG PLUMBING

PLF POUNDS PER LINEAR FOOT

PLYWD PLYWOOD

PNL PANEL

PR PAIR

PROJ PROJECTION

PRV PRESSURE REGULATING VALVE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT POINT OF TANGENCY / PORCELAIN TILE

PTVC POINT OF VERTICAL CURVATURE

PVC POLYVINYL CHLORIDE

PVI POINT OF VERTICAL INTERSECTION

PVT POINT OF VERTICAL TANGENCY

Q

QT QUARRY TILE

R

R RADIUS / REGISTER

RA RETURN AIR

RB RESILIENT BASE

RCP REINFORCED CONCRETE PIPE

RD ROOF DRAIN

REF REFERENCE

REFL REFLECTED

REG REGISTER

REINF REINFORCED

REQD REQUIRED

REV REVERSE / REVISION

RF RETURN FAN

RGS RIGID GALVANIZED STEEL

RH ROOF HOOD / RELATIVE HUMIDITY / REHEAT

RHC REHEAT COIL

RM ROOM

RO ROUGH OPENING

ROW RIGHT OF WAY

RT RESILIENT TILE

RWC RIGID WALLCOVERING

S

S STAIR / STAIN / SURFACE / SANITARY

SA SUPPLY AIR / SOUND ATTENUATOR

SAN SANITARY

SCH SCHEDULE

SD SMOKE DAMPER / SUB DRAIN

SECT SECTION

SF SUPPLY FAN

SHT SHEET

SIM SIMILAR

SOG SLAB-ON-GRADE

SP SUMP PUMP

SPEC SPECIFICATIONS

SPF SPRAY POLYURETHANE FOAM

SQ SQUARE

SS SERVICE SINK / STORM SEWER

SSO STORM SEWER OVERFLOW

SSTL STAINLESS STEEL

ST STAIR TREAD

STA STATION

STD STANDARD

STE STANDARD TAPERED END

STIFF STIFFENER

STIR STIRRUP

STL STEEL

STOR STORAGE

STR STRUCTURAL

SUSP SUSPENDED

SW SWITCH

SWGR SWITCHGEAR

SYM SYMMETRICAL

T

T TREAD

T&B TOP AND BOTTOM

T&G TONGUE AND GROOVE

TC TOP OF CURB

TE TOP ELEVATION

TEL TELEPHONE

TEMP TEMPERATURE

TER TERRAZZO

TLT TOILET

TOPO TOPOGRAPHY

TOS TOP OF STEEL

TOW TOP OF WALL

TP TOP OF PAVEMENT

TRANS TRANSVERSE

TYP TYPICAL

U

UC UNDERCUT

UG UNDERGROUND

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

UR URINAL

UV UNIT VENTILATOR

V

V VOLT

VAV VARIABLE AIR VOLUME

VB VINYL BASE

VC VERTICAL CURVE

VCP VITRIFIED CLAY PIPE

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VFD VARIABLE FREQUENCY DRIVE

VTR VENT THROUGH ROOF

VWC VINYL WALL COVERING

W

W WATT / WATER

W/ WITH

W/O WITHOUT

WAGD WASTE ANESTHESIA GAS DISPOSAL

WC WATER CLOSET

WD WOOD

WDW WINDOW

WH WATER HEATER / WALL HYDRANT

WP WEATHERPROOF

WPFG WATERPROOFING

WS WATER STOP

WT WEIGHT

WWF WELDED WIRE FABRIC

X

XFMR TRANSFORMER

Y

YD YARD

YH YARD HYDRANT

Mark Revisions: Date:

ARCHITECTURAL GENERAL NOTES

1. THE CONTRACTOR SHALL INSPECT THE SITE,

STUDY EXISTING CONDITIONS, REVIEW

DRAWINGS AND SPECIFICATIONS.

CONTRACTOR SHALL ADJUST FOR ACTUAL

FIELD CONDITIONS AT NO ADDITIONAL

EXPENSE TO THE OWNER.

2. CONTRACTOR SHALL TAKE ALL

MEASUREMENTS FOR THE WORK AND BE

RESPONSIBLE FOR SAME. COORDINATE THE

WORK AND SHOP DRAWINGS WITH ALL

OTHER TRADES AFFECTED AND MAKE ANY

NECESSARY OFFSETS TO CONCEAL PIPING

AND DUCTWORK AND TO CLEAR EQUIPMENT,

STRUCTURAL MEMBERS AND OTHER

OBSTRUCTIONS.

3. ALL UTILITIES AND SERVICES SHALL BE KEPT

IN CONTINUOUS OPERATION UNLESS

WRITTEN PERMISSION IS OTHERWISE

GRANTED BY THE OWNER.

A. MINOR SHUTDOWNS OF LESS THAN

48 HOURS REQUIRE 7 TO 14 DAYS’

NOTICE;

B. MAJOR SHUTDOWNS OF MORE THAN

48 HOURS REQUIRE 14 DAYS’ NOTICE.

C. CONTRACTOR MUST CONTACT VA'S

COR PRIOR TO ANY SHUTDOWNS.

4. TEMPORARY ALTERATIONS AND

CONNECTIONS REQUIRED BY THIS

CONTRACT SHALL BE MADE SO THAT ALL

BUILDING SERVICES ARE MAINTAINED

WITH MINIMUM INTERRUPTION. SCHEDULE

ALL ELECTRICAL/MECHANICAL OUTAGES

14 DAYS IN ADVANCE WITH THE OWNER.

5. PROTECT ALL WORK, MATERIALS AND

EQUIPMENT. CAP OR PLUG TEMPORARY

OPENINGS. DELIVER ALL WORK TO THE

OWNER CLEAN AND IN GOOD CONDITION.

6. WHEN DEMOLITION IS COMPLETE, NOTIFY

ARCHITECT AND OWNER FOR A SCHEDULED

MEETING TO REVIEW EXISTING CONDITIONS

AND ANY CONCERNS REGARDING NEW

WORK.

7. CUTTING AND PATCHING OF EXISTING

WALLS, FLOORS OR CEILINGS REQUIRED BY

NEW WORK SHALL BE INCLUDED AS WORK

PROVIDED UNDER THIS CONTRACT.

8. CUTTING SHALL BE DONE WITH CARE SO AS

NOT TO DAMAGE EXISTING EQUIPMENT,

CONNECTIONS, CONTROLS, ETC.

9. DAMAGE CAUSED BY SUCH CUTTING SHALL

BE REPLACED OR REPAIRED TO ORIGINAL

CONDITION BY CONTRACTOR AT NO COST TO

THE OWNER, UNLESS UNFORESEEN EXISTING

CONDITIONS ARE DISCOVERED AND OWNER

IS NOTIFIED.

10. ALL OCCUPIED WORK AREAS, BUILDING

CORRIDORS AND EXTERIOR AREAS SHALL BE

KEPT CLEAR OF DEBRIS.

11. ALL MATERIALS AND EQUIPMENT SHALL BE

NEW, OF THE BEST QUALITY AND FREE

FROM DEFECTS.

12. MANUFACTURER AND MODEL NUMBERS

SPECIFIED ESTABLISH THE TYPE AND

QUALITY REQUIRED, UNLESS OTHERWISE

NOTED.

13. ALL WORK SHALL COMPLY WITH

APPLICABLE REGULATIONS, CODES AND

ORDINANCES.

14. THE CONTRACTOR SHALL PERFORM ALL

TESTS AS SPECIFIED OR AS NECESSARY TO

DEMONSTRATE A COMPLETE AND

SATISFACTORY INSTALLATION.

15. ALL EXPOSED PENETRATIONS MADE

THROUGH EXISTING ROOFS, FLOORS, AND

WALLS SHALL BE PATCHED WITH LIKE

MATERIALS TO MATCH THE SURROUNDING

AREAS, AND FILLED AS CLOSE AS POSSIBLE

TO THE NEW PIPING OR DUCTWORK.

A. ALL EXPOSED PENETRATIONS MADE

THROUGH EXISTING ROOFS ARE TO

BE COORDINATED WITH THE ROOFING

WARRANTY CONTRACTOR.

B. ALL PENETRATIONS THROUGH RATED

WALLS SHALL BE PATCHED TO

MAINTAIN RATING.

16. THE CONTRACTOR SHALL BE RESPONSIBLE

FOR REPAIRING AND REPLACING ANY

DAMAGE TO EXISTING MATERIALS

RESULTING FROM WORK UNDER THIS

CONTRACT AND SHALL RESTORE SUCH TO

IT'S ORIGINAL CONDITION WITH NEW

MATERIALS TO MATCH EXISTING.

16. INSTALL THE SPECIFIED FIRE STOPPING

(SLEEVES, WRAP, CONDUIT, ETC.) AT RATED

CONSTRUCTION:

A. FIRE STOP ALL PENETRATIONS

WHERE NEW DEVICES/LINES,

RELOCATING EXISTING

DEVICES/LINES, PENETRATING

FLOORS, CEILINGS AND OTHER RATED

BARRIERS.

B. FIRE STOP ALL NEWLY CREATED

PENETRATIONS WHERE EXISTING

DEVICES/LINES PENETRATE FLOORS,

CEILINGS AND OTHER RATED

BARRIERS. USE FIRE APPROVED

CAULKING AND FIRE STOPS (SEE

SPECIFICATIONS).

17. ALL METAL STUD AND GYPSUM WALLBOARD

PARTITIONS ARE DIMENSIONED TO THE

OUTSIDE FACE OF WALL AND TO THE

COLUMN GRD UNLESS OTHERWISE NOTED.

18. ALL GYPSUM BOARD SHALL BE TYPE ’X' FIRE

CODE GYPSUM BOARD MOLD AND MOISTURE

RESISTANT AT WALLS AND CEILINGS.

19. PROVIDE WOOD BLOCKING OR 16 GA.

SHEET METAL BACKING PLATES IN ALL

WALLS TO RECEIVE WALL HUNG

ACCESSORIES, SUCH AS EQUIPMENT,

GRAB BARS, MILLWORK, COAT HOOKS,

AND DOOR STOPS, ETC. IF WOOD

BLOCKING IS USED, PROVIDE AS FIRE-

RESISTANT.

20. ALL ITEMS AND DEVICES, SUCH AS COVER

PLATES, SWITCH PLATES, CONVENIENCE

OUTLETS, DOOR STOPS, AND OTHER FINISH

HARDWARE, ETC. SHALL BE REMOVED AND

REINSTALLED AS PART OF THE REFINISHING

OF EXISTING WALLS INDICATED TO REMAIN.

21. THE CONTRACTOR SHALL WORK WITH THE

CONDITIONS AS THEY EXIST AT THE SITE.

ALL ABOVE CEILING CONDITIONS SHALL BE

REVIEWED AND MODIFICATIONS

IDENTIFIED, COORDINATED, AND

INCORPORATED INTO THE SHOP DRAWING

PROCESS. COORDINATE ALL ABOVE

CEILING WORK TO ENSURE A COMPLETE

AND OPERATIONAL SYSTEM AT NO

ADDITIONAL COST TO THE OWNER.

COORDINATION SHALL INCLUDE, BUT NOT

BE LIMITED TO THE FOLLOWING:

A. THE OWNER'S EQUIPMENT

REQUIREMENTS.

B. THE CEILING SUPPORT SYSTEM.

C. THE MECHANICAL DUCTWORK

SYSTEM.

D. THE LIGHTING FIXTURES.

E. ELECTRICAL WIRING AND CONDUIT

SYSTEMS.

F. THE PLUMBING AND PIPING

SYSTEMS.

G. THE COMMUNICATIONS

SYSTEMS.

22. ALL NEW STUD WALLS AND GYPSUM BOARD

SHALL EXTEND TO STRUCTURE UNLESS

NOTED OTHERWISE.

23. WHEN ALTERING THE BUILDING, IF

STRUCTURAL INTEGRITY APPEARS TO BE

IN QUESTION CONTRACTOR SHALL NOTIFY

OWNER AND ARCHITECT IMMEDIATELY.

24. ALL NEW CONSTRUCTION IS INDICATED BOLD

OR FULL TONE UNLESS NOTED OTHERWISE.

25. WHEN WALL PARTITIONS OF DIFFERENT

FIRE RATING INTERSECT, THE HIGHEST

RATED PARTITION TAKES PRECEDENT.

MAINTAIN RATING BEHIND RECESSED

AREAS IN WALLS.

26. ALL CORRIDOR WALLS ARE REQUIRED TO BE

SMOKE TIGHT, WHETHER THEY ARE FIRE

RATED OR NOT. REPAIR AND EXTEND AT

LEAST THE CORRIDOR SIDE OF NON-RATED

CORRIDOR WALLS TO STRUCTURE, UNLESS

NOTED OTHERWISE, SEE WALL TYPES LISTED

IN DRAWINGS.

27. COORDINATE CONSTRUCTION

REQUIREMENTS WITH MECHANICAL AND

ELECTRICAL DRAWINGS.

28. REVIEW AREAS OF WORK WITH COR FOR

INFECTION CONTROL REQUIREMENTS.

AREAS REQUIRING CLASS I/CLASS II

INFECTION CONTROL WILL REQUIRE

APPROVAL BY THE COR PRIOR TO

BEGINNING WORK. AREAS REQUIRING

CLASS III/CLASS IV INFECTION CONTROL

REQUIRE PERMITS FROM THE VA. SEE

DIVISION 1 SPECIFICATION "SAFETY

REQUIREMENTS-INFECTION CONTROL” FOR

DETAILED INFORMATION.

29. CONTRACTOR SHALL OBSERVE WORK

RESTRICTIONS NOTED IN PHASING

REQUIREMENTS, ON DRAWINGS AND IN THE

SPECIFICATIONS FOR AREAS THAT ARE A

PART OF OR ADJACENT TO

ADMINISTRATIVE, DIETARY, SUPPORT, IN-

PATIENT, OUT-PATIENT AND CLINICAL

AREAS.

30. IF WALLS ARE NOT DAMAGED, THEY CAN BE

CLEANED AFTER DEMO OF CEILINGS AND

HVAC.

31. MISC. EXISTING ACCESSORIES (VA

RESPONSIBLE FOR THESE ITEMS).

1. DASHED BOLD LINES INDICATE EXTEND OF

DEMOLITION INCLUDING THE FOLLOWING:

A. INTERIOR PARTITIONS (REMOVED TO

STRUCTURE)

B. CEILINGS, INCLUDING CEILING

SUSPENSION SYSTEM, MISC. STEEL

SUPPORTS FOR SUSPENDED

EQUIPMENT, SUSPENDED

EQUIPMENT, LIGHT FIXTURES,

DIFFUSERS AND GRILLES ETC.

C. FLOOR FINISHES (TO CONCRETE)

INCLUDING CARPET, RVT, SHEET

VINYL, CERAMIC TILE, QUARRY TILE,

BRICK PAVERS, ETC.

D. DOORS AND FRAMES UNLESS NOTED

OTHERWISE IN DOOR SCHEDULE

E. WINDOW GLAZING AND FRAMES

UNLESS NOTED OTHERWISE

F. BRICK AND BACK-UP WALL SYSTEM

G. CABINETWORK, SHELVING, BASES

H. TOILET PARTITIONS AND

ACCESSORIES

I. TACK BOARDS, MARKER BOARDS,

PEGBOARDS, DISPLAY BOARDS

J. EQUIPMENT ITEMS

K. PLUMBING FIXTURES

2. CONTRACTOR SHALL FIELD VERIFY ALL

EXISTING CONDITIONS.

3. ALL LIGHT OR HALFTONE LINES INDICATE

EXISTING TO REMAIN.

4. SEE SPECIFICATIONS SECTIONS FOR

CUTTING AND PATCHING, INCLUDING

DEMOLITION 02 41 00.

5. SEE ROOM FINISH SCHEDULE, MECHANICAL

PLANS AND ELECTRICAL PLANS FOR

EXTENTS OF NEW CEILING CONSTRUCTION

OR CEILING PATCHING IN EXISTING AREAS.

6. SEE ROOM FINISH SCHEDULE FOR EXTENT

OF NEW FLOORING MATERIAL IN EXISTING

AREAS.

7. SEE ROOM FINISH SCHEDULE FOR EXTENT

OF NEW WALL COVERING MATERIAL IN

EXISTING AREAS. WHERE NEW FINISHES

ARE REQUIRED, REMOVE EXISTING WALL

FINISHES, (TEXTURED PLASTIC COATING,

VINYL WALL COVERING, PANELING, BASE,

ETC.).

8. CONTRACTOR TO VERIFY ALL WALL

CONSTRUCTION & FINISHES NOTED FOR

REMOVAL. TAKE INTO ACCOUNT ANY

DISCREPANCY AND MAKE PROPER

ADJUSTMENT TO ACCOMPLISH REQUIRED

CONSTRUCTION & FINISHES. IF

STRUCTURAL INTEGRITY IS VIOLATED,

CONTACT ARCHITECT.

9. COORDINATE PHASING WITH OWNER.

10. COORDINATE REMOVAL OF FURNITURE AND

EXISTING EQUIPMENT WITH OWNER.

11. REFER TO EQUIPMENT SCHEDULE ON SHEET

QH601 FOR NEW LOCATIONS OF EXISTING

EQUIPMENT, ETC.

12. SAW CUT EDGES OF EXISTING FLOOR SLAB

FOR REMOVAL AND INSTALLATION OF

UTILITIES. REFER TO MECHANICAL AND

ELECTRICAL DRAWINGS.

13. REMOVE FURRING OR GWB ONLY WHERE

REQUIRED TO COMPLETE CONSTRUCTION.

14. PATCH AND MATCH WALLS AS REQUIRED TO

COMPLETE AND MATCH EXISTING

CONDITIONS, UNLESS AN ALTERNATIVE

MATERIAL AND FINISH IS INDICATED.

15. REMOVE CEILINGS ONLY AS REQUIRED FOR

NEW CONSTRUCTION. REINSTALL, REPLACE

OR PATCH AS REQUIRED.

DEMOLITION GENERAL

NOTES

1. ALL CONTRACTORS ARE RESPONSIBLE FOR

REVIEWING ENTIRE SET OF DOCUMENTS TO

DETERMINE THEIR FULL SCOPE OF WORK.

CONTRACTOR SHALL NOT BE ALLOWED

EXTRA COSTS DUE TO FAILURE TO REVIEW

ENTIRE SET OF DOCUMENTS.

2. COVER AND PROTECT ALL VA EQUIPMENT

AND FURNITURE SO THAT THE FUNCTION

AND APPEARANCE IS NOT AFFECTED BY

CONSTRUCTION, THE CONTRACTOR, THEIR

EQUIPMENT, MATERIALS, OR ANY

INVOLVED ACTIONS.

3. A 1 HR MINIMUM FIRE-RATED SEPARATION

IS REQUIRED BETWEEN ALL OCCUPIED

SPACE AND CONSTRUCTION AREAS. THIS

PROTECTION INCLUDES ANY EXISTING

PENETRATIONS AND OPENINGS.

4. SEE BID SET FOR MODULAR BUILDING

COMPLEX AS PART OF BID PACKAGE.

IMPORTANT

CONTRACTOR NOTES

1. ALL STRUCTURAL STEEL AT BUILDING 1

SHALL RECEIVE SPRAY APPLIED

FIREPROOFING TO ACHIEVE A 2-HOUR

RATING.

2. MAINTAIN FIRE RATED CONSTRUCTION AT

WALL PENETRATIONS, (CONSTRUCTION TO

CONFORM TO MANUFACTURER'S FIRE

RATED / TEST ASSEMBLIES.

3. FIRE CAULK ALL SLEEVES AND

PENETRATIONS AT FIRE WALLS /

PARTITIONS AND FLOORS. CONFORM WITH

THE TESTED / SUBMITTED FIRE RATED

ASSEMBLY. USE RED FIRE CAULK AND

LABEL WALL WITH U.L. DESIGN NUMBER.

FIRE RATED WALLS SHOWN ON PLAN.

4. PATCH AND REPAIR ALL EXISTING

FIREPROOFING ON EXISTING STRUCTURAL

MEMBERS, INCLUDING THAT WHICH IS

UNCOVERED NEEDING REPAIR AND THAT

WHICH IS DISTURBED DURING

CONSTRUCTION.

FIREPROOFING GENERAL

NOTES

IF THE CONTRACTOR ENCOUNTERS MATERIAL

THAT COULD BE HAZARDOUS, THE CONTRACTOR

SHALL STOP WORK AND NOTIFY THE

GOVERNMENT IMMEDIATELY FOR DIRECTION.

HAZARDOUS MATERIALS

1. REFER TO ARCHITECTURAL DEMO PLANS

FOR APPROXIMATE EXTENTS OF

DEMOLITION WORK IN PROJECT AREA.

COORDINATE WITH VA COR.

2. REFER TO ROOM FINISH SCHEDULE AND

SPECIFICATIONS FOR INFORMATION ON

FINISHES.

3. REFER TO MEP DRAWINGS FOR

INFORMATION PERTAINING TO

MECHANICAL, ELECTRICAL, AND PLUMBING

WORK. ALL NOTES REGARDING THE

REMOVAL, INSTALL, LOCATION AND/OR

INFORMATION OF MEP ITEMS ARE GIVEN

FOR REFERENCE AND CLARITY ONLY.

4. REFER TO FIRE PROTECTION DRAWINGS

FOR RELATED FIRE PROTECTION

REMODELING.

5. PATCH EXISTING OPENINGS AS NEEDED

AND PREP SURFACE FOR NEW FINISH.

6. PATCH EXISTING WALL W/ FINISHES TO

MATCH EXISTING WHERE DAMAGED BY

DEMOLITION.

7. COORDINATE ALL REINSTALLATION OF VA

ITEMS & ACCESSORIES WITH COR.

8. CONSTRUCTION WASTE IS TO BE REMOVED

TO DUMPSTER. THE COR WILL APPROVE OF

DUMPSTER LOCATIONS.

9. INFILL ALL LOCATIONS WHERE MASONRY

WALLS HAVE BEEN REMOVED.

10. CONTRACTOR TO VERIFY LOCATION OF

EXISTING MEP AND RELATED ITEMS PRIOR

TO START OF RENOVATION

WORK.COORDINATE ALL EXISTING AND

NEW WORK.

11. MECHANICAL AND ELECTRICAL WORK TO

FIT WITHIN WALLS AND CHASES SHOWN;

WHERE EXISTING OR NEW MECHANICAL

AND ELECTRICAL WORK FALLS OUTSIDE OF

THE PROVIDED WALLS AND CHASES, THE

CONTRACTOR SHALL NOTIFY THE COR FOR

REVISIONS TO THE LAYOUT OF WALLS OR

CHASE AT NO ADDITIONAL COST TO THE

OWNER.

12. DEMO WORK AND NEW WORK INDICATE

APPROXIMATE AREA TO BE REMOVED.

CONTRACTOR TO FIELD VERIFY ACTUAL

AREA TO BE REMOVED. CONTRACTOR TO

COORDINATE WORK AREA WITH ALL

TRADES FOR FULL SCOPE OF WORK.

CONTRACTOR IS RESPONSIBLE FOR WORK

AS NECESSARY, FIELD VERIFY.

13. MAINTAIN ALL EXISTING FIRE RATINGS.

FIELD VERIFY.

14. ANY CONTRACTOR DISTURBED FINISHES

MUST BE RESTORED TO MATCH THE

EXISTING FINISH. COORDINATE WITH VA TO

MATCH EXISTING FINISHES.

15. COVER AND PROTECT ALL VA EQUIPMENT

AND FURNITURE SO THAT THE FUNCTION

AND APPEARANCE IS NOT AFFECTED BY

CONSTRUCTION, THE CONTRACTOR, THEIR

EQUIPMENT AND MATERIALS, OR ANY

INVOLVED ACTIONS.

16. A 1 HR MINIMUM FIRE-RATED SEPARATION

IS REQUIRED BETWEEN ALL OCCUPIED

SPACE AND CONSTRUCTION AREAS. THIS

PROTECTION INCLUDES ANY EXISTING

PENETRATIONS AND OPENINGS.

17. PATCH FLOOR SLABS AT PENETRATIONS

AND OPENINGS RESULTING FROM

REMOVAL OF PIPING AS NECESSARY TO

MAINTAIN EXISTING FIRE SEPARATION AND

FINISH AT PIPING AND EQUIPMENT

REMOVAL LOCATIONS PATCH TO MATCH

ADJACENT EXISTING FLOOR.

18. PATCH PARTITION WALLS AT NEW

PENETRATIONS RESULTING FROM

INSTALLATION OF NEW CONDUIT, MECH.,

PLUMBING, OR ELECT. SYSTEM. SEAL

AGAINST NEW PIPING TO MATCH EXISTING

WALL CONDITION. MATCH EXISTING WALL

CONDITION (FINISH, PAINT COLOR, WALL

MOUNTED EQUIPMENT AND ACCESSORIES,

ETC.) TYP. WALL CONDITION: GWB OR

PLASTER. SEE MEP DRAWINGS FOR FULL

EXTENT OF WORK. REMOVE REPLACE,

PATCH AND REPAIR WALL TO THE EXTENT

NECESSARY TO COMPLETE WORK AND

MEET THE REQUIRED STANDARDS FOR VA

CONSTRUCTION. COORDINATE REMOVAL

AND REINSTALLATION OF WALL MOUNTED

EQUIPMENT, ETC. FIELD VERIFY. MAINTAIN

EXISTING FIRE RATINGS. VERIFY EXISTING

CONDITIONS WITH COR DURING PRE-

CONSTRUCTION WALK THRU, ADDITIONAL

COSTS WILL NOT BE ALLOWED.

RENOVATION GENERAL NOTES

19. HATCH PARTITION WALLS AND FILL/PATCH

OPENINGS RESULTING FROM REMOVAL OF

PIPING. MATCH EXISTING WALL CONDITION

(FINISH, PAINT COLOR, WALL MOUNTED

EQUIPMENT, AND ACCESSORIES, ETC.) TYP.

WALL CONDITION: GWB OR PLASTER. SEE

MEP DRAWINGS FOR FULL EXTENT OF

WORK. REMOVE, REPLACE, PATCH, AND

REPAIR WALL TO THE EXTENT NECESSARY

TO COMPLETE WORK AND MEET THE

REQUIRED STANDARDS FOR VA

CONTSTRUCTION. COORDINATE REMOVAL

AND REINSTALLATION OF WALL MOUNTED

EQUIPMENT, ETC. FIELD VERIFY. MAINTAIN

EXISTING FIRE RATINGS. VERIFY EXISTING

CONDITIONS WITH COR DURING PRE-

CONSTRUCTION WALK THRU, ADDITIONAL

COSTS WILL NOT BE ALLOWED.

20. CONTRACTOR SHALL PROVIDE ALL

NECESSARY TEMPORARY SUPPORTS AS

REQUIRED FOR CEILING MOUNTED

EQUIPMENT DURING DEMOLITION AND

REBUILD OPERATIONS.

21. REMOVE TEMPORARY CONSTRUCTION

PARTITIONS AFTER COMPLETION OF WORK.

PATCH/PAINT TO MATCH EXISTING/NEW

FINISHES.

22. MEP ELEMENTS SHOWN IN

ARCHITECTURAL PLANS ARE FOR

REFERENCE ONLY. REFER TO MEP

DRAWINGS FOR INFORMATION PERTAINING

TO MEP ELEMENTS.

23. DISRUPTIVE ACTIVITIES IN OCCUPIED

SPACES TO BE LIMITED AS DIRECTED BY

COR. COORDINATE WELL IN ADVANCE WITH

COR PRIOR TO BEGINNING WORK.

SEE SECTION 01 00 00 - GENERAL REQUIREMENTS

FOR FULL DESCRIPTION OF DEDUCT ALTERNATE.

REFER TO SHEET AG002- ARCHITECTURAL

GENERAL NOTES FOR LISTING OF DEDUCT

ALTERNATE. SEE DRAWINGS FOR ADDITIONAL

NOTES AND DIRECTIONS RELATED TO DEDUCT

ALTERNATE.

DEDUCT ALTERNATE

DEDUCT ALTERNATE LIST

DEDUCT ALTERNATE – INCLUDES THE FOLLOWING:

A. DELETE NEW AHU-9 AND ALL RELATED

AND/OR CONNECTED SYSTEMS (DUCTWORK,

PIPING, STRUCTURAL PLATFORM,

REROOFING, CEILING REPLACEMENT,

TEMPERATURE CONTROL, ELECTRICAL,

DEMOLITION, ETC.)

B. DELETE NEW DENTAL AHU AND ALL RELATED

AND/OR CONNECTED SYSTEMS (DUCTWORK,

PIPING, STRUCTURAL PLATFORM,

REROOFING, CEILING REPLACEMENT,

TEMPERATURE CONTROL, ELECTRICAL,

DEMOLITION, ETC.)

C. DELETE ALL ARCHITECTURAL & INTERIOR

DESIGN WORK (DEMOLITION, AND NEW) ON

GROUND FLOOR, AREAS AW & E

D. DELETE ALL ARCHITECTURAL & INTERIOR

DESIGN WORK (DEMOLITION, AND NEW) ON

FIRST FLOOR, AREAS AW, E & F (EXCEPT FOR

WORK RELATED TO DEDICATED AHU SERVING

MAIL ROOM 1A-173)

E. DELETE ALL FIRE PROTECTION WORK

(DEMOLITION, AND NEW) ON GROUND FLOOR,

AREAS AW & E

F. DELETE ALL FIRE PROTECTION WORK

(DEMOLITION, AND NEW) ON FIRST FLOOR,

AREAS AW, E & F

G. DELETE ALL PLUMBING WORK (DEMOLITION,

AND NEW) ON GROUND FLOOR, AREAS AW & E

H. DELETE ALL PLUMBING WORK (DEMOLITION,

AND NEW) ON FIRST FLOOR, AREAS AW, E & F

I. DELETE ALL MECHANICAL PIPING WORK

(DEMOLITION, AND NEW) ON GROUND FLOOR,

AREAS AW & E

J. DELETE ALL MECHANICAL PIPING

(DEMOLITION, AND NEW) ON FIRST FLOOR,

AREAS AW, E & F (EXCEPT FOR WORK

RELATED TO DEDICATED AHU SERVING MAIL

ROOM 1A-173)

K. DELETE ALL MECHANICAL VENTILATION WORK

(DEMOLITION, AND NEW) ON GROUND FLOOR,

AREAS AW & E

L. DELETE ALL MECHANICAL VENTILATION

(DEMOLITION, AND NEW) ON FIRST FLOOR,

AREAS AW, E & F (EXCEPT FOR WORK

RELATED TO DEDICATED AHU SERVING MAIL

ROOM 1A-173)

M. DELETE ALL WORK RELATED TO THE NEW

TEMPORARY AHU, SHOWN ON FIRST FLOOR

VENTILATION WEST OF BUILDING 1

N. DELETE ALL ELECTRICAL LIGHTING & POWER

WORK (DEMOLITION, AND NEW) ON GROUND

FLOOR, AREAS AW & E

O. DELETE ALL ELECTRICAL LIGHTING & POWER

WORK (DEMOLITION, AND NEW) ON FIRST

FLOOR, AREAS AW, E & F (EXCEPT FOR WORK

RELATED TO DEDICATED AHU SERVING MAIL

ROOM 1A-173)

P. DELETE ALL TEMPORARY MODULAR

BUILDINGS AND/OR TRAILERS SHOWN FOR

PHASES 2, 3, & 4. ONLY PHASE 1 TEMPORARY

BUILDINGS AND CONNECTING LINK REMAINS

CONTRACTOR SHALL REFER TO THE MODULAR

BUILDING COMPLEX PACKAGE FOR COORDINATION

AND RELOCATION DURING PHASING OF

DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,

ETC. REQUIRED FOR CONTINUED VA OPERATIONS.

MODULAR BUILDING

COMPLEX COORDINATION

JIM

H.

HAGEMAN

A-2205

A

R C H I T E

C

T

S T

A T

E

O F N E B

R A

S K

A

8/30/2024

Project Number

Building Number

Drawing Number

Project Title

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

IMEG Corp.

15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132

CC

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

A u to d e s k D o c s

/2

-1

A -2

-3

V

A P o p la r

B lu ff

R e m o v e a n d

R e p la c e

L a b A

H U a n d A

H U

/6

A

-2

-3

.B

.A rc h R

-1

-R e p l L a b A

H U

A

H U

.r v t

/9

/2

:0

:0

P M

AG002

ARCHITECTURAL GENERAL

NOTES

REMOVE AND REPLACE END OF

LIFE HEATING, VENTILATION, AND

AIR CONDITIONING

JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL

CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO

63901-3318

657A4-21-800

8/30/2024 JHH ALESIA

AD104

D1

A-200

F6

MEDICAL

RECORDS

1A-101

RELEASE OF

INFORMATION

1A-102

PATIENT REP QM

1A-103

BUSINESS

1A-104

BUSINESS

1A-105

BREAK ROOM

1A-106

MY HEALTHE-VET

OFFICE

1A-107

EXAM

ROOM/DOCTOR

OFFICE

1A-108

DENTAL WAITING

ROOM

1E-110

CLERK'S OFFICE

1E-111

BREAK ROOM

1E-112

DENTAL

HYGEINE

1E-113

ORAL SURGERY

1E-114

OFFICE

1E-116

DENTAL

LABORATORY

1E-129

DENTAL

TREATMENT

1E-130

DENTAL IMAGING

1E-131

DENTAL IMAGING

1E-132

PATIENT

EDUCATION

1A-144

SOILED

LINEN/CLOSET

1F-147

RESTROOM, F

1F-149

MEDICATION

ROOM

1F-150

BUSINESS

OFFICE

1F-151

BUSINESS

OFFICE

1F-152

EXAM

1F-154

OEF/OIF CASE

MANAGER

1F-155

CHECK-IN/WAITING

1F-156

EXAM

1F-157

EXAM

1F-159

STAFF WORK

ROOM

1F-160

STERILE

1F-161

C&P CHECK IN

1F-163

WAITING ROOM

1F-166

EXAM

1F-167

OFFICE OF

PATIENT

ADVOCATE

1A-171

VETERANS

EXPERIENCE

OFFICE

1A-172

MAIL ROOM

1A-173

DENTAL

TREATMENT

1E-130A

A B B.1 W X Y AA CC BB DD FF L M

1.1

14.1

EXAM

1F-153

RESTROOM

1F-162RESTROOM, F

1F-158

CAREGIVER

SUPPORT/RN

ASSESSOR

1F-165

HOLDING AREA

1A-170

RESTROOM, M

1F-169

HAC CLOSET

1F-168

ADMISSIONS

1A-142

CLOSET

1E-115

ELECTRICAL

CLOSET

1E-110B

COMPRESSOR

1E-109

CORRIDOR E

1E-C01

HOOD

STAIR E

1E-S01

D21

REMOVE DUCT AND PATCH

REMOVE HOOD AND PATCH

REMOVE HOOD AND PATCH

REMOVE HOOD AND PATCH

REMOVE DUCT AND PATCH

REMOVE HOOD AND PATCH

REMOVE DUCT AND PATCH

REMOVE HOOD AND

PATCH

CONTRACTOR SHALL REFER TO THE MODULAR

BUILDING COMPLEX PACKAGE FOR COORDINATION

AND RELOCATION DURING PHASING OF

DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,

ETC. REQUIRED FOR CONTINUED VA OPERATIONS.

MODULAR BUILDING

COMPLEX COORDINATION

SEE GENERAL NOTES ON SHEET AG002.

GENERAL

DEMOLITION NOTESSEE PROJECT MANUAL SECTION 01 00 00-GENERAL

CONDITIONS, SHEET AG002 & TEMPORARY

MODULAR BUILDING COMPLEX DRAWINGS FOR

DESCRIPTION OF DEDUCT ALTERNATE.

DEDUCT ALTERNATE

JIM

H.

HAGEMAN

A-2205

A

R C H I T E

C

T

S T

A T

E

O F N E B

R A

S K

A

8/30/2024

PLAN

NORTH

TRUE

NORTH

Project Number

Building Number

Drawing Number

Project Title

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

IMEG Corp.

15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132

CC

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

KEY PLAN

E

F

D

B

TT

Aw Ac Ae

C

A u to d e s k D o c s

/2

-1

A -2

-3

V

A P o p la r

B lu ff

R e m o v e a n d

R e p la c e

L a b A

H U a n d A

H U

/6

A

-2

-3

.B

.A rc h R

-1

-R e p l L a b A

H U

A

H U

.r v t

/9

/2

:0

:4

P M

AD101

FIRST FLOOR - DEMOLITION PLAN REMOVE AND REPLACE END OF

LIFE HEATING, VENTILATION, AND

AIR CONDITIONING

JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL

CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO

63901-3318

657A4-21-800

8/30/2024 GG TF

1/16" = 1'-0"1

FIRST FLOOR - DEMOLITION PLAN

1" = 1'-0"A5

LOOKING WEST

1" = 1'-0"C7

HOOD END

1" = 1'-0"C5

DUCT CONNECTED TO HOOD

1" = 1'-0"D7

AREA BELOW HOOD

1" = 1'-0"D5

DUCK CONNECTED TO HOOD

KEYNOTE LEGEND

KEY KEYNOTE

D21 DENTAL HOOD REMOVAL IN DENTAL LAB

1E-129.

DEDUCT ALTERNATE - SEE AG002 &

TEMPORARY MODULAR BUILDING

COMPLEX DRAWINGS

N O P

Q

R S T U V

HEMATOLOGY

2C-048

CHEMISTRY

2C-046

CORRIDOR C

2C-C01

ANCILLARY

OFFICE

2C-051

SPECIMEN &

REAGENT

STORAGE

2C-045

BREAK ROOM

2C-044

RESTROOM, M/F

2C-043

CLOSET

2C-042A

LAB

INFORMATION

OFFICE

2C-042

REAGENT /

SUPPLIES ROOM

2C-054

HOUSEKEEPING

CLOSET

2C-052

HOUSEKEEPING

CLOSET

2C-053

RESTROOM, M/F

2C-055A

LAB COAT

CLOSET

2C-054A

LAB

SUPERVISOR

OFFICE

2C-041

PHLEBOTOMY

2A-055

WAITING ROOM

RADIOLOGY/LAB

2A-057

WAITING ROOM

RAIOLOGY/LAB

2A-058

CULTURE ROOM

2A-038

MICROBIOLOGY

2A-037B

BLOOD BANK /

HISTOLOGY

2A-037A

LAB SUPPLY

ROOM

2A-037

RECORDS/SUPPLY

STORAGE

2A-036

DEMO CASEWORK

DEMO CASEWORK

DEMO CASEWORK

CORRIDOR A3

2A-C01

REMOVE EXIST

FLOOR TILE/MASTIC -

SEE HAZ-MAT

DRAWINGS

REMOVE EXIST

FLOOR TILE/MASTIC -

SEE HAZ-MAT

DRAWINGS

A-901 F8

ELECTRICAL

CLOSET

2A-035

EQUIPMENT

2B-034

X-RAY IMAGING

ROOM

2B-033

STORAGE

2B-010

RESTROOM, F

2B-011

CT CONTROL

ROOM

2A-007

RESTROOM, M

2A-009

LINEN CHUTE/HK

CLOSET

2A-008

EXISTING HAND SINK TO REMAIN

EXISTING BASE CABINET /

COUNTERTOP / SINK TO REMAIN

CONTRACTOR SHALL REFER TO THE MODULAR

BUILDING COMPLEX PACKAGE FOR COORDINATION

AND RELOCATION DURING PHASING OF

DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,

ETC. REQUIRED FOR CONTINUED VA OPERATIONS.

MODULAR BUILDING

COMPLEX COORDINATION

SEE GENERAL NOTES ON SHEET AG002.

GENERAL

DEMOLITION NOTESSEE PROJECT MANUAL SECTION 01 00 00-GENERAL

CONDITIONS, SHEET AG002 & TEMPORARY

MODULAR BUILDING COMPLEX DRAWINGS FOR

DESCRIPTION OF DEDUCT ALTERNATE.

DEDUCT ALTERNATE

JIM

H.

HAGEMAN

A-2205

A

R C H I T E

C

T

S T

A T

E

O F N E B

R A

S K

A

8/30/2024

PLAN

NORTH

TRUE

NORTH

Project Number

Building Number

Drawing Number

Project Title

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

IMEG Corp.

15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132

CC

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

E

D

C

B

KEY PLAN

F

Aw Ac Ae

A u to d e s k D o c s

/2

-1

A -2

-3

V

A P o p la r

B lu ff

R e m o v e a n d

R e p la c e

L a b A

H U a n d A

H U

/6

A

-2

-3

.B

.A rc h R

-1

-R e p l L a b A

H U

A

H U

.r v t

/9

/2

:0

:5

P M

AD102

SECOND FLOOR - DEMOLITION

PLAN

REMOVE AND REPLACE END OF

LIFE HEATING, VENTILATION, AND

AIR CONDITIONING

JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL

CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO

63901-3318

657A4-21-800

8/30/2024 GG KRK

1/8" = 1'-0"1

SECOND FLOOR - DEMOLITION PLAN

DEDUCT ALTERNATE - SEE AG002 &

TEMPORARY MODULAR BUILDING

A-200

D1

D1

A-301

REMOVE EXISTING WINDOW,

WINDOW SILL AND MASONRY WALL

BELOW WINDOW SILL. WALL

DEMOLITION EXTENDS BELOW

FLOOR LEVEL TO CREATE SPACE

FOR NEW CAST CONCRETE DOOR SILL

EXISTING MASONRY SUPPORT LINTEL REMAINS

IN PLACE ABOVE EXISTING WINDOW OPENING.

SEE STRUCTURAL DEMO NOTES AND DETAIL

P

Q

R S T U V

SALVAGE/CLEAN EXISTING BRICK REMOVED

FROM OPENING FOR USE IN NEW OPENING

PHYSICAL

THERAPY

4C-038A

SOCIAL WORKER

(CARE-GIVER

SPPT.

COORD./PALLIATIVE

CARE)

4C-038B

MINIMUM DATA

SET CARE PLAN

COORDINATOR

OFFICE

4C-038

PATIENT ROOM

[2]

4C-038C

PATIENT ROOM

[2]

4C-037

CORRIDOR C

4C-C01RESTROOM, M/F

4C-040

RESTROOM, M/F

4C-037A

LINEN CLOSET

4A-042

ELECTRICAL

CLOSET

4A-041

STAIRWELL 4

4A-S01

MEDICATION

ROOM

4A-045

BREAK ROOM

4A-044

CORRIDOR A

4A-C02

LIVING ROOM

4A-034

CONTRACTOR SHALL REFER TO THE MODULAR

BUILDING COMPLEX PACKAGE FOR COORDINATION

AND RELOCATION DURING PHASING OF

DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,

ETC. REQUIRED FOR CONTINUED VA OPERATIONS.

MODULAR BUILDING

COMPLEX COORDINATION

SEE GENERAL NOTES ON SHEET AG002.

GENERAL

DEMOLITION NOTESSEE PROJECT MANUAL SECTION 01 00 00-GENERAL

CONDITIONS, SHEET AG002 & TEMPORARY

MODULAR BUILDING COMPLEX DRAWINGS FOR

DESCRIPTION OF DEDUCT ALTERNATE.

DEDUCT ALTERNATE

JIM

H.

HAGEMAN

A-2205

A

R C H I T E

C

T

S T

A T

E

O F N E B

R A

S K

A

8/30/2024

PLAN

NORTH

TRUE

NORTH

Project Number

Building Number

Drawing Number

Project Title

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

IMEG Corp.

15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132

CC

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

E

F

D

C

B

KEY PLAN

Aw Ac Ae

A u to d e s k D o c s

/2

-1

A -2

-3

V

A P o p la r

B lu ff

R e m o v e a n d

R e p la c e

L a b A

H U a n d A

H U

/6

A

-2

-3

.B

.A rc h R

-1

-R e p l L a b A

H U

A

H U

.r v t

/9

/2

:0

:5

P M

AD103

FOURTH FLOOR - DEMOLITION

PLAN

REMOVE AND REPLACE END OF

LIFE HEATING, VENTILATION, AND

AIR CONDITIONING

JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL

CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO

63901-3318

657A4-21-800

8/30/2024 GG KRK

1/4" = 1'-0"1

FOURTH FLOOR DEMO PLAN

DOOR TO REMAIN

REMOVE/REUSE PARAPET CAP AS

REQUIRED TO REPLACE ROOF

MEMBRANE AND FLASHING

METAL LOUVER SCREEN

TO REMAIN

NOTE:

CHANGE OF ELEVATION

APPROX 18" HIGHER

THAN SOUTH ROOF

REMOVE AND RETAIN FOR

REUSE - EXISTING FALL

PROTECTION AS

REQUIRED. REMOVE AND

REUSE PARAPET STONE CAP

ASSEMBLIES, ROOF

MEMBRANE, FLASHING,

INSULATION, AND SHEATHING

TO STRUCTURAL DECK

BELOW-TYPICAL ALL HATCHED

AREAS THIS PLAN

REMOVE EXISTING AIR

HANDLER AND PERIMETER

SUPORT CURB STRUCTURE-

CLEAR ROOF PENETRATIONS

(VERIFY NUMBER) FOR INFILL

WORK

EGRESS ROUTE RAILING COLUMN

SUPORT BLOCKS (8 VERIFY) AT

DECK LEVEL TO REMAIM

EXISTING METAL

LOUVER SUPPORT

SYSTEM TO REMAIN -

(8) VERIFY NUMBER

OF SUPORTS ALONG ENTIRE PERIMITER OF

SUPPORTING CURB REMOVE

WOOD NAILER, COUNTER

FLASHING, CURB FLASHING

BOND BEAM TOP COURSE

AD104

E5

A B B.1 W X Y AA CC

1.1

DENTAL

LABORATORY

1E-129

CORRIDOR E

1E-C01

OFFICE

1E-116

EXISTING EXHAUST

FAN/CURB TO REMOVE &

REPLACE W/ NEW

CURB/FAN - SEE MECH

1-EF11

EF-2E

INFILL ABANDONED

ROOF FAN OPENING -

SEE MECH

RD

RD

RD

RD

RD

RD

SLOPE

1/4" / FT

SLOPE

1/4" / FT

SLOPE

1/4" / FT

SLOPE

1/4" / FT

SLOPE

1/4" / FT

+3"

+3"

+3"

AHU-9E

BOILER ROOM ROOF

EXISTING CHAIN LINK FENCE

AD104B9

AD104

C9

VTR

AD104

D9

AD104

F5

AD104

F7

AD104

E9

SCREEN WALL BRACE

SUPPORT BASE - REMOVE AND

REPLACE TPO MEMBRANE (TYP)

SCREEN SUPPORT COLUMN

BASE - REMOVE AND

REPLACE TPO MEMBRANE

(TYP)

VTR

SLOPE

1/4" / FT

A-501

B4

T.O. CONC DECK @ RIDGE = 432.83' (FV)

T.O. WOOD DECK @ RIDGE = 434.75' (FV)

B.O. WOOD ROOF JOIST +1'-3" ABOVE

ROOF DECK

T.O. CONC DECK @ RIDGE = 432.83'

T.O. WOOD DECK @ RIDGE = 434.5' +

SLOPED CRICKET = 434.9' (FV)

DOOR TO REMAIN

EXISTING AHU AND SUPPORT CURBING TO

BE REMOVED- VERIFY ROOF PENETRATIONS

FOR REPAIR BY INFILL

EXISTING CHILLER AND SUPORT CURBING

TO BE REMOVED- VERIFY ROOF

PENETRATIONS FOR REPAIR BY INFILL

REMOVE PARAPET CAP ASSEMBLIES,

ROOF MEMBRANE, FLASHING,

INSULATION, AND SHEATHING TO

STRUCTURAL DECK BELOW - TYPICAL ALL

HATCHED AREAS

REMOVE EXIST. STL. STAIRS,

LANDING, AND GUARDRAILS

REMOVE AND RETAIN FOR

USE - EXISTING FALL

PROTECTION AS REQUIRED.

CUT OUT BACK SIDE OF MASNORY

PARAPET, PARAPET CAP, & ROOFING IN

ROUGHLY 18"X14" AREA DOWN TO ROOF

SLAB FOR INSTALLATION OF 8 STEEL

TUBE COLUMNS, THEN REPLACE

MASONRY SURROUNDINGS COLUMNS.

COORDINATE LOCATION WITH NEW

CONSTRUCTION.

PORTIONS OF ROOF WILL NEED TO BE DEMO'D FOR

NEW MECHANICAL DUCT WORK. REFER TO MEP

DRAWINGS FOR LOCATION.

P Q R S T U V

STORAGE

3C-041C

CORRIDOR C

NORTH

3C-01A

HOSPITALIST

3C-041B

AD104 A5

AD104 B5

AD104

A6

AD104

B6

AD104

A7

RDRD

AD104

B7

SLOPE

1/4" FT

S

LO

P E

1/ 4"

F T

SL

O

PE

1/

4" F

T

SLOPE

1/4" FT

S

LO

P E

SLOPE

REMOVE FOR REUSE, ALUM.

LOUVER SCREEN WALL &

RESPECTIVE TRIM PIECES,

AND STEEL TUBE SUPPORT

SYSTEM TO BELOW ROOF.

FF L M

CORRIDOR A3

2A-C01

PRIMARY CARE

PROGRAM

SUPPORT

ASSISTANT

OFFICE

2A-131

ASSOCIATE

CHIEF OF STAFF,

PRIMARY CARE

OFFICE

2A-132

CT COOLING

SYSTEM

2A-002A

HOT LAB

2A-001

NUCLEAR

MEDICINE

IMAGING ROOM

2A-002

PROGRAM

DIRECTOR,

MENTAL HEALTH

OFFICE

2A-130

A-402

A-402 E1

F1

REMOVE EXISTING CURB AND

FLASHING IN ITS ENTIRETY

REMOVE EXISTING CANT

EXISTING ROOF STRUCTURE

REMOVE EXISTING BOND

BEAM TOP COURSE

EXISTING ROOF INSULATION

TO REMAIN

EXISTING MASONRY TO

REMAIN

DEMOLISH EXISTING DUCTWORK

AS NEEDED FOR NEW

CONSTRUCTION WORK

REMOVE EXISTING RIGID

INSULATION

REMOVE EXISTING AHU - REFER TO

MECHANICAL

REMOVE EXISTING TPO & INSULATION

VARIES

SEE GENERAL NOTES ON SHEET AG002.

GENERAL

DEMOLITION NOTESSEE PROJECT MANUAL SECTION 01 00 00-GENERAL

CONDITIONS, SHEET AG002 & TEMPORARY

MODULAR BUILDING COMPLEX DRAWINGS FOR

DESCRIPTION OF DEDUCT ALTERNATE.

DEDUCT ALTERNATE

REMOVE / REPLACE TPO MEMBRANE

TEAR OFF TPO & INSULATION TO WOOD

DECK AND REPLACE WITH NEW

TEAR OFF TPO & INSULATION TO WOOD

DECK AND REPLACE WITH NEW

REMOVE AND REPLACE ROOF DRAIN

TEAR OFF TPO & INSULATION TO WOOD

DECK AND REPLACE WITH NEW

REMOVE AND REPLACE ROOF DRAIN

TEAR OFF TPO & INSULATION TO

WOOD DECK AND REPLACE WITH

NEW

REMOVE / REPLACE ROOF DRAIN

REMOVE AHU & CURB / INFILL

REMOVE / REPLACE FLASHING FOR VTR -

SEE MECH FOR VTR WORK

REMOVE / REPLACE ROOF DRAIN

REMOVE AND REPLACE TPO MEMBRANE

(TYP)

REMOVE AND REPLACE TPO MEMBRANE

(TYP)

TEAR OFF TPO & INSULATION TO

WOOD DECK AND REPLACE WITH

NEW

EXISTING EXHAUST FAN/CURB TO

REMOVE & REPLACE W/ NEW

CURB/FAN

REMOVE AND REPLACE ROOF DRAIN

REMOVE / REPLACE FLASHING FOR

VTR - SEE MECH FOR VTR WORK

REMOVE AND INFILL

TEAR OFF TPO & INSULATION TO WOOD

DECK AND REPLACE WITH NEW

REMOVE - SEE MECH FOR VTR WORK

REMOVE AND REPLACE ROOF DRAIN

REMOVE AND REPLACE TPO MEMBRANE

REMOVE EXISTING EQUIPMENT -

SEE MECHANICAL SHEETS

EXISTING SCUPPER

REMOVE EXISTING EQUIPMENT -

SEE MECHANICAL SHEETS

REMOVE EXISTING EQUIPMENT -

SEE MECHANICAL SHEETS

RELOCATE EXISTING SPLIT

SYSTEM AND ALL PIPING,

BRACKETS, CONTROLS,WIRING,

ACCESSORIES, ETC AS

REQUIRED TO COORDINATE

WITH NEW DUCT LAYOUT -

SEE MECHANICAL SHEETS

REMOVE EXISTING

EQUIPMENT - SEE

MECHANICAL SHEETS

TEAR OFF TPO & INSULATION

AND REPLACE WITH NEW,

TYP.

REMOVE EXISTING

EQUIPMENT - SEE

MECHANICAL SHEETS

REMOVE STEPS AND

RAILING - DOOR TO REMAIN

JIM

H.

HAGEMAN

A-2205

A

R C H I T E

C

T

S T

A T

E

O F N E B

R A

S K

A

8/30/2024

PLAN

NORTH

TRUE

NORTH

Project Number

Building Number

Drawing Number

Project Title

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

IMEG Corp.

15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132

CC

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

KEY PLAN

E

F

D

B

Aw Ac Ae

C

A u to d e s k D o c s

/2

-1

A -2

-3

V

A P o p la r

B lu ff

R e m o v e a n d

R e p la c e

L a b A

H U a n d A

H U

/6

A

-2

-3

.B

.A rc h R

-1

-R e p l L a b A

H U

A

H U

.r v t

/9

/2

:0

:5

P M

AD104

ROOF DEMOLITION PLANS REMOVE AND REPLACE END OF

LIFE HEATING, VENTILATION, AND

AIR CONDITIONING

JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL

CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO

63901-3318

657A4-21-800

8/30/2024 GG KRK

1/8" = 1'-0"D1

FIRST FLOOR - ENLARGED ROOF DEMO PLAN - AREA 'E' - LAUNDRY

1/8" = 1'-0"C5

THIRD FLOOR - ENLARGED ROOF DEMO PLAN - AREA 'C' - LAB AHU

1/8" = 1'-0"F1

SECOND FLOOR - ENLARGED MAIN ENTRY ROOF DEMO PLAN - AREA

'A-CENTER' - MAIL RTU

1" = 1'-0"E5

DEMOLITION SECTION - ROOFTOP AHU CURB

DEDUCT ALTERNATE - SEE AG002 &

TEMPORARY MODULAR BUILDING

COMPLEX DRAWINGS

DEDUCT ALTERNATE - SEE AG002 &

TEMPORARY MODULAR BUILDING

COMPLEX DRAWINGS

1 1/2" = 1'-0"B9

EXISTING LAUNDRY ROOF

1 1/2" = 1'-0"C9

EXISTING LAUNDRY ROOF

1 1/2" = 1'-0"D9

EXISTING LAUNDRY ROOF

1 1/2" = 1'-0"F5

EXISTING LAUNDRY ROOF

1 1/2" = 1'-0"F7

EXISTING LAUNDRY ROOF

1 1/2" = 1'-0"E9

EXISTING LAUNDRY ROOF

NOT TO SCALE

NOT TO SCALE

NOT TO SCALE

NOT TO SCALENOT TO SCALENOT TO SCALE

1 1/2" = 1'-0"A5

EXISTING 3RD FL C ROOF

1 1/2" = 1'-0"B5

EXISTING 3RD FL C ROOF

1 1/2" = 1'-0"A6

EXISTING 3RD FL C ROOF

1 1/2" = 1'-0"B6

EXISTING 3RD FL C ROOF

1 1/2" = 1'-0"A7

EXISTING 3RD FL C ROOF

1 1/2" = 1'-0"B7

EXISTING 3RD FL C ROOF

NOT TO SCALE

NOT TO SCALE

NOT TO SCALE

NOT TO SCALE

NOT TO SCALE

NOT TO SCALE

NOT TO SCALENOT TO SCALE

ACD110

F1

ACD110

F4

RESTROOM/

SHOWER, M

GA-055

LOCKER RM., M

GA-056

STORAGE

GE-068

MORGUE

GA-072

EMS

GA-073

REST ROOM

GA-075

RESTROOM/

SHOWER, F

GA-079

CREDIT UNION

GA-080

REMOVE GWB SOFIT ABOVE AT

ACD110

B4

A B B.1 W X Y AA CC BB DD FF L M

N O P Q R S T U V

1.1

14.1

ELECTRICAL

ROOM

GA-081

OFFICE

GA-082

OFFICE

GE-063

OFFICE

GE-062

LAUNDRY

GE-070

VESTIBULE

GE-069

SOILED LINEN

GE-067

LAUNDRY

GE-066

STAFF

RESTROOM

GE-065

OFFICE

GE-068A

CORRIDOR

GE-C01

ROOM

GE-064

CORRIDOR

GA-C01

SUPPLY

GA-059

CLOSET

GA-058

RESTROOM, F

GA-079A

STORAGE

GA-076

SLOPED CORRIDOR CEILING - REMOVE AND RELACE

EXIST GWB/MTL STUD BULKHEAD TO REMAIN -

MODIFY AS REQ'D FOR REMOVAL OF EXISTING

DUCTS AND INSTALLATION OF NEW DUCTWORK

LOCKER RM., F

GA-077

OFFICE

GA-077A

OPEN TO

STRUCTURE

CORRIDOR

GE-C01

343 SF

STORAGE

GC-011A

STAIRWELL C

GC-S01

MECH. ROOM

GC-011

EYE CLINIC

GC-10C

EYE CLINIC

GC-10B

EYE CLINIC

GC-10A

EYE GLASS

SALES

GC-010

ELEC. CLOSET

GC-09B

CORRIDOR

GC-C01

ELEV

GC-E05

EXAM ROOM

GC-014

EXAM ROOM

GC-14A

PROCEDURE

GC-015

PROCEDURE

GC-15A

EXAM

GC-016

EYE CLINIC

GC-16A

CHECK-IN

GA-017

CHECK-IN

GA-17C

RESTROOM M/F

GA-17A

STAIRWELL 4

GA-S01

ENTRANCE

GA-09A

PHARMACY

WAITING ROOM

GA-07A

RECONCILLIATION

GA-07Q

MECH. RM

GA-07

PHYSICAL

THERAPY

GA-18

EXAM 2

GA-18A

WAITING RM

GA-17B

ELEC. CLOSET

GA-07TPROSTHETICS

GA-03

CHUTE

GA-05

PIPE CHASE

GA-01C

STORAGE

GA-07M

STAIRWELL 5

GA-S02

CALL CENTER

GB-07J

PURCHASER'S

OFFICE

GB-07K

BREAKROOM

GB-07N

RESTROOM

GB-07R

HVAC RM

GB-07S

NARCOTICS RM

GB-07G

CHEMO HD RM

GB-07F

IV ROOM

GB-07E

CLOSET

GB-07P

IV HOOD ROOM

GB-07L

IV TECHNICIAN

GB-07D

DIRECTOR'S

OFFICE

GB-07C

SECRETARY

GB-07O

STOCK AREA

GB-07I

DISPENSING

GB-07H

CORRIDOR

GB-C01

DISPENSING

GB-07B

EXAM 1

GA-02

STORAGE

GA-1A

PIPE CHASE

GA-01B

TELECOMMUNICATIONS

GD-22

TELECOM

SWITCH

GA-052

ELEC. CLOSET

GD-01D

SUPERVISOR

OFFICE

GD-47

RESTROOM, M

GD-46

CLOSET

GD-47A

COUMADIN

STORAGE

GD-28

COUMADIN

CLOSET

GD-29

ELEC. STORAGE

GD-27

STAIRWELL 6

GD-S03

COUMADIN

CLINIC

GD-30

CONFERENCE

ROOM

GD-45A

CORRIDOR

GD-CC

STORAGE

GD-32

BIOMED SHOP

GD-34

BIOMED

GD-35

MECH. ROOM

GD-45

ELEC. CLOSET

GD-GD

ELEC. SHOP

GD-36

BACKUP

STORAGE

GD-37

MECH. ROOM

GD-38

UNION OFFICE

GD-44

AC SHOP

GD-44A

STAIRWELL 7

GD-S01

EQUIP. STORAGE

GD-42

TRASH CART

GD-39

STAIRWELL 3

GA-S03

CONTRACTOR SHALL REFER TO THE MODULAR

BUILDING COMPLEX PACKAGE FOR COORDINATION

AND RELOCATION DURING PHASING OF

DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,

ETC. REQUIRED FOR CONTINUED VA OPERATIONS.

MODULAR BUILDING

COMPLEX COORDINATION

SEE GENERAL NOTES ON SHEET AG002.

GENERAL DEMOLITION

AND RENOVATION NOTESSEE PROJECT MANUAL SECTION 01 00 00-GENERAL

CONDITIONS, SHEET AG002 & TEMPORARY

MODULAR BUILDING COMPLEX DRAWINGS FOR

DESCRIPTION OF DEDUCT ALTERNATE.

DEDUCT ALTERNATE

DEMO WOOD CEILING

EXISTING GYPSUM WALL BOARD CEILING

EXISTING SUSPENDED ACOUSTICAL REMAIN

DEMO SUSPENDED ACOUSTICAL

EXISTING SUPPLY AIR GRILLE - SEE MECHANICAL

EXISTING RETURN AIR GRILLE - SEE MECHANICAL

EXISTING RECESSED 2X2 LIGHT FIXTURE - SEE ELECTRICAL

EXISTING RECESSED 2X4 LIGHT FIXTURE - SEE ELECTRICAL

EXISTING CAN LIGHT

EXISTING EXIT LIGHT

EXISTING WIRELESS ACCESS POINT

EXISTING SPEAKER

EXISTING SMOKE DETECTOR

EXISTING OCCUPANCY SENSOR

EXISTING VIDEO SURVEILLANCE CAMERA

REFLECTED CEILING LEGEND

WOOD CEILING

GYPSUM WALL BOARD CEILING

SUSPENDED ACOUSTICAL CEILING

SUPPLY AIR GRILLE - SEE MECHANICAL

RETURN AIR GRILLE TO - SEE MECHANICAL

RECESSED 2X2 LIGHT FIXTURE - SEE ELECTRICAL

RECESSED 2X4 LIGHT FIXTURE - SEE ELECTRICAL

CAN LIGHT

EXIT LIGHT

WIRELESS ACCESS POINT

SPEAKER

SMOKE DETECTOR

OCCUPANCY SENSOR

VIDEO SURVEILLANCE CAMERA

S

S SD

OS OS

OS

WAP

WAP

CCTV

CCTV

JIM

H.

HAGEMAN

A-2205

A

R C H I T E

C

T

S T

A T

E

O F N E B

R A

S K

A

8/30/2024

PLAN

NORTH

TRUE

NORTH

Project Number

Building Number

Drawing Number

Project Title

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMP

321 4 5 6 7 8 9 10

E

ARCHITECT/ENGINEER OF RECORD

Alesia Architecture P.C.

3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941

Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698

AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001

IMEG Corp.

15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132

CC

o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t

Aw

F

D

Ac Ae

B

KEY PLAN

C

A u to d e s k D o c s

/2

-1

A -2

-3

V

A P o p la r

B lu ff

R e m o v e a n d

R e p la c e

L a b A

H U a n d A

H U

/6

A

-2

-3

.B

.A rc h R

-1

-R e p l L a b A

H U

A

H U

.r v t

/9

/2

:0

:2

P M

ACD100

GROUND FLOOR - CEILING DEMO

PLAN

REMOVE AND REPLACE END OF

LIFE HEATING, VENTILATION, AND

AIR CONDITIONING

JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL

CENTER 1500 N. WESTWOOD BLVD.

This is the start of the file's text. The full file is on GovTribe.