S02-657A4-21-800-ATTACHMENT 5- Building 1 Drawings Volume 2_R_06242025.pdf
PDF 18 MB Posted
- Attached to
- Z2DA--657A4-21-800, TF - FCA - Remove and Replace End-of-Life HVAC Infrastructure Building 1
- Solicitation number
- 36C25525R0106
About this file
This document is a set of architectural demolition and renovation plans for the John J. Pershing Veterans' Administration Medical Center in Poplar Bluff, Missouri. The drawings detail a comprehensive project to remove and replace end-of-life heating, ventilation, and air conditioning (HVAC) infrastructure in Building 1. The plans cover multiple floors (ground, first, second, fourth) and include detailed demolition plans for ceilings, roofs, and mechanical systems across various wings and departments such as dental, medical records, laboratories, and clinical areas.
The drawings provide extensive technical specifications for the demolition process, including removing existing air handling units, ductwork, roofing materials, and ceiling components. A key feature is the option for a "Deduct Alternate" that allows the VA to selectively remove or modify parts of the project scope, such as deleting work in specific wings or removing certain mechanical systems. The plans emphasize maintaining continuous VA operations during construction, with careful coordination required for infrastructure modifications and temporary building arrangements.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FRONT APPROACH, PULL SIDE FRONT APPROACH, PUSH SIDE
NOTE: X=12" MINIMUM IF DOOR HAS
BOTH A CLOSER AND LATCH
HINGE SIDE APPROACHES - SWINGING DOORS
LATCH SIDE APPROACHES - SWINGING DOORS
NOTE:
1. ALL DOORS IN ALCOVES SHALL COMPLY WITH CLEARANCES FOR FRONT APPROACHES.
HINGE APPROACH, PULL SIDE HINGE APPROACH, PUSH SIDE
LATCH APPROACH, PULL SIDE LATCH APPROACH, PUSH SIDE
NOTE: X=36" MINIMUM IF Y=60"; X=42"
MINIMUM IF Y=54".
NOTE: Y=48" MINIMUM IF DOOR HAS
BOTH A LATCH AND CLOSER.
NOTE: Y=54" MINIMUM IF DOOR HAS
CLOSER.
NOTE: Y=48" MINIMUM IF DOOR HAS
CLOSER.
FRONT APPROACHES - SWINGING DOORS
MIN.
18"
M
IN
M
IN
X
54" MIN.
M
IN
.60
X
MIN.
24"
M
IN
M
IN
MIN.
24" X X
Y Y
Y
PULL SIDE PUSH SIDE
POCKET OR HINGE APPROACH - SLIDING BARN DOORS
POCKET OR HINGE APPROACH STOP OR LATCH APPROACH
FRONT AND SIDE APPROACHES - NO DOORS
M
IN
M
IN
24"42
M
IN
22" MIN. 42
M
IN
GENERAL SYMBOLS
A101
SIM
A101
SIM
1i
A101
SIM
D
SCALE:1 View Name 1/8" = 1'-0"
A
NTRUE
NORTH
A
B
EARTH
EARTH GRAVEL
CONCRETE
METALS
BRICK
CMU
TILE
STONE
WOOD
GYPSUM
GLASS
INSULATION
REGULAR
STEEL ALUMINUM
FACE COMMON
CMU
CERAMIC
MARBLE LIMESTONE
FINISH BLOCKING
PLASTER OR GWB
LARGE SCALE SMALL SCALE
BATT OR LOOSE RIGID
SURFACE
ACTUAL SQ. FT.
PROGRAMMED SQ. FT.
ROOM NUMBER
DOOR NUMBER
KEYNOTE
WALL TYPE
REVISION NUMBER
ELEVATION INDICATION
COLUMN GRID
IDENTIFICATION
NORTH ARROW
XXX WINDOW NUMBER
DETAIL TITLE
BUILDING SECTION
WALL SECTION
EXTERIOR/INTERIOR
ELEVATION
INTERIOR MULTI-VIEW
ELEVATION
ELEVATION NUMBER
SHEET ON WHICH
ELEVATION IS DRAWN
ELEVATION NUMBER
SHEET ON WHICH
ELEVATION IS DRAWN
MATERIALS REFERENCE
Room Name
150 PSF / 150 SF
PROPERTY CORNER
PROPERTY LINE
4" UNDERGROUND COMMUNICATION
(NO. INDICATES NO. OF DUCTS)
4" UNDERGROUND DUCT
(NO. INDICATES NO. OF DUCTS)
TELEPHONE LINE OH
UNDERGROUND ELECTRICAL
CONDUIT
OVERHEAD POWER LINE
ELECTRICAL MANHOLE
P/T = POWER & TELEPHONE
W/ STREET LIGHT
W/ DOWN GUY (NO. INDICATES LENGTH, CLASS
GUY & ANCHOR STRENGTH)
POWER POLE (NO. INDICATES LENGTH &
CLASS)
REMOVE OR ABANDON LINE
VALVE
GAS LINE
IRRIGATION WATER MAIN
FIRE WATER LINE
WATER LINE
STORM SEWER
SANITARY SEWER FORCE MAIN
SANITARY SEWER
CURB LINE
STREET CENTER LINE
BUILDING
EXISTING NEW
SITE
EXISTING NEW
S
MH CO
SFM
SS SS
MH
CLAL
Y.D.
F.H.
W
F
IRM
G
4M
P T
P T
P
UG
T
2-T
P
UG
T
2-T
POLE
4M
45-2
45-2
G
IRM
F
Y.D.
F.H.
W
AL
SS SS
MH
SFM
S
MH CO
GRID COORDINATES
SECTION LINE
CONTOURS
SPOT ELEVATIONS
DRAINAGE DITCH OR SWALE
CONCRETE PAVEMENT (SECTION)
BITUMINOUS PAVEMENT (SECTION)
CONTRACTION JOINT FOR PAVEMENT
BORINGS, TEXT
TREES, DECIDUOUS - WITH
DIAMETER
EVERGREEN - WITH HEIGHT
SHRUBS
CHAIN-LINK FENCE
BARBED WIRE FENCE
SECURITY FENCE XX XX
XX
XX XX
XX
12"
10'
HIGH
12" (TO BE REMOVED)
10' (TO BE REMOVED)
HOLE #3
90 X 10W 90 X 10 W (TOP OF WALL)
90 X 10C 90 X 10 C (TOP OF CURB)
90 X 10P 90 X 10 P (TOP OF PAVEMENT)
90 X 10 90 X 10
SEC 24
SEC 25
290 N
90 W
09 20 00.A1
A101
SIM
DETAIL SECTION
AE201
CONTRACTOR SHALL REFER TO THE MODULAR
BUILDING COMPLEX PACKAGE FOR COORDINATION
AND RELOCATION DURING PHASING OF
DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,
ETC. REQUIRED FOR CONTINUED VA OPERATIONS.
MODULAR BUILDING
COMPLEX COORDINATION
JIM
H.
HAGEMAN
A-2205
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
8/30/2024
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
CC
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
A u to d e s k D o c s
/2
-1
A -2
-3
V
A P o p la r
B lu ff
R e m o v e a n d
R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.A rc h R
-1
-R e p l L a b A
H U
A
H U
.r v t
/9
/2
:0
:0
P M
AG001
ARCHITECTURAL ABBREVIATIONS
& LEGENDS
REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATION, AND
AIR CONDITIONING
JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL
CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO
63901-3318
657A4-21-800
8/30/2024 GG KRK
1/4" = 1'-0"1
GUIDE FOR CLEARANCES AT DOORS
ABBREVIATIONS
A
A/C AIR CONDITIONING
AB ANCHOR BOLT / AIR BLENDER
ABS ACRYLONITRILE-BUTADIENE-STYRENE
AC ALTERNATING CURRENT / AIR COMPRESSOR
ACP ASBESTOS CEMENT PIPE
ACU AIR CONDITIONING UNIT
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJACENT / ADJUSTABLE
ADR ACCESS DOOR
AFF ABOVE FINISH FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
APPROX APPROXIMATELY
APT APARTMENT
ARCH ARCHITECT(URAL)
ASPH ASPHALT
AT ACOUSTICAL PANEL CEILING
ATB AIR TERMINAL BOX
ATD AIR TRANSFER DUCT
ATU AIR TERMINAL UNIT
AUX AUXILIARY
AVG AVERAGE
AWC ACOUSTICAL WALLCOVERING
AZ AZIMUTH
B
BB BALLED AND BURLAPPED
BD BOARD
BDD BACK DRAFT DAMPER
BE BOTTOM ELEVATION
BL BUILDING LINE
BLDG BUILDING
BLKG BLOCKING
BM BENCH MARK / BEAM
BR BARE ROOT
BRG BEARING
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C
C/C CENTER TO CENTER
CAB CABINET
CB CIRCUIT BREAKER / CATCH BASIN
CC COOLING UNIT
CE COVER ELEVATION
CEM CEMENT
CFM CUBIC FEET PER MINUTE
CFS CONCRETE FLOOR SEALER
CG CORNER GUARD
CH CHILLER
CI CURB INLET / CAST IRON
CIP CAST IRON PIPE
CJ CONTROL JOINT OR CONTRACTION JOINT
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CLO CLOSET
CLR CLEAR
CM CENTIMETER
CMH CUBIC METER PER HOUR
CMP CORRUGATED METAL PIPE
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CO CLEANOUT / CARBON MONOXIDE
CO2 CARBON DIOXIDE
COL COLUMN
COMB COMBINATION / COMBINE
COMP COMPRESSIBLE
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS / CONTINUATION
CONTR CONTRACTOR
CORR CORRIDOR
CP CEMENT PIPE
CPT CARPET
CSF CUBIC FEET PER SECOND
CT CERAMIC TILE / COOLING TOWER
CTR CENTER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CUYD CUBIC YARD
CW COLD WATER
D
D DRAIN / DIFFUSER
DA DENTAL AIR
DBL DOUBLE
DEPR DEPRESSED
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIFF DIFFUSER
DIP DUCTILE IRON PIPE
DISC DISCONNECT
DISP DISPENSER
DIST DISTRIBUTION
DK DECK
DL DEAD LOAD
DN DOWN
DO DITTO
DPR DAMPER
DR DOOR
DS DOWNSPOUT
DV DENTAL VACUUM
DWG DRAWING
DWL DOWEL
DWP DOMESTIC WATER PUMP
E
E EPOXY
EA EACH / EXHAUST AIR
EF EACH FACE / EXHAUST FAN
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMBED EMBEDMENT
EMD ESTIMATED MAXIMUM DEMAND
EMT ELECTRICAL METAL TUBING
EQ EQUAL
EQUIP EQUIPMENT
ET EXPANSION TANK
EVAC MEDICAL GAS EVACUATION
EW EACH WAY
EWC ELECTRICAL WATER COOLER
EWH ELECTRICAL WATER HEATER
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED
EXPN EXPANSION
EXT EXTERIOR
F
F FIRE MAIN
FA FIRE ALARM
FCU FAN COIL UNIT
FD FLOOR DRAIN / FIRE DAMPER
FD / SD COMBINATION FIRE AND SMOKE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FDR FEEDER
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIN FINISH
FIX FIXTURE
FL FLOOR
FM FORCE MAIN / FACTORY MUTUAL
FP FIREPROOFING / FIRE PUMP
FPM FEET PER MINUTE
FR FIRE RATED
FRP FIBERGLASS REINFORCED PLASTIC
FS FLOW SWITCH
FT FEET
FTG FOOTING
FVC FIRE VALVE CABINET
G
G GAS / GRILLE
GA GAGE
GALV GALVANIZED
GB GRAB BAR
GBD GRAVITY BACKDRAFT DAMPER
GEN GENERATOR
GFRC GLASS FIBER REINFORCED CONCRETE
GI GALVANIZED IRON
GL GLASS
GLB GLASS BLOCK
GP GLAZED PAINT
GPM GALLONS PER MINUTE
GR GRADE
GRV GRAVITY ROOF VENTILATOR
GWB GYPSUM WALLBOARD
GYP GYPSUM
H
HB HOSE BIBB
HC HEATING COIL
HDNR HARDENER
HDW HARDWARE
HDWD HARDWOOD
HK1E HOOK ONE END
HK2E HOOK TWO ENDS
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSEPOWER
HPT HIGH POINT
HR HOUR
HS HIGH STRENGTH
HT HEIGHT
HTG HEATING
HTR HEATER
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HW HOT WATER
HWC HOT WATER CIRCULATING
HZ HERTZ
I
IA INSTRUMENT AIR
IC INTERCOM
ICB INTEGRAL COVE BASE
ID INSIDE DIAMETER
IE INVERT ELEVATION
IF INSIDE FACE
IN INCH
INSUL INSULATION
INT INTERIOR
J
JAN JANITOR
JB JUNCTION BOX
JP JOCKEY PUMP
JST JOIST
JT JOINT
K
KC MIL THOUSAND CIRCULAR MILS
KCJ KEYED CONSTRUCTION JOINT
KIT KITCHEN
KPA KILOPASCALS
KS KITCHEN SINK
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATTS
L
L LITER
LA LABORATORY AIR
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LBS POUNDS
LF LINEAR FEET
LIN LINEAR
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LMU LIGHTWEIGHT MASONRY UNITS
LONG LONGITUDINAL
LPM LITERS PER MINUTE
LT LIGHT
LT WT LIGHT WEIGHT
LTG LIGHTING
LV LABORATORY VACUUM
LVL LEVEL
LVT LUXURY VINYL TILE
M
M METER
M2 SQUARE METER
M3 CUBIC METER
MA MEDICAL AIR
MAINT MAINTENANCE
MAR MARBLE
MAS MASONRY
MAT MATERIAL / ENTRY CARPET
MAX MAXIMUM
MBH 1000 BTUH
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MET METAL
MFR MANUFACTURER
MG MOTOR GENERATOR / MEDICAL GAS
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MM MILLIMETER
MO MASONRY OPENING
MTD MOUNTED
MTG MOUNTING
MULL MULLION
MV MEDICAL VACUUM
N
N NITROGEN
N2O NITROUS OXIDE
NEC NATIONAL ELECTRICAL CODE
NFPA NATIONAL FIRE PROTECTION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
O
O/S OFFSET
OA OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
OX OXYGEN
OZ OUNCE
P
P PAINT / PUMP / PENDANT
PA PASCAL
PART PARTITION
PAVT PAVEMENT
PC POINT OF CURVATURE
PCF POUNDS PER CUBIC FOOT
PED PEDESTAL
PERP PERPENDICULAR
PHC PREHEAT COIL
PHVAC PLUMBING, HEATING, VENTILATING AND AIR
CONDITIONING
PI POINT OF INTERSECTION
PIV POST INDICATOR VALVE
PKG PARKING
PL PLASTIC LAMINATE / PROPERTY LINE / PLATE
PLAS PLASTER
PLBG PLUMBING
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PNL PANEL
PR PAIR
PROJ PROJECTION
PRV PRESSURE REGULATING VALVE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT OF TANGENCY / PORCELAIN TILE
PTVC POINT OF VERTICAL CURVATURE
PVC POLYVINYL CHLORIDE
PVI POINT OF VERTICAL INTERSECTION
PVT POINT OF VERTICAL TANGENCY
Q
QT QUARRY TILE
R
R RADIUS / REGISTER
RA RETURN AIR
RB RESILIENT BASE
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
REF REFERENCE
REFL REFLECTED
REG REGISTER
REINF REINFORCED
REQD REQUIRED
REV REVERSE / REVISION
RF RETURN FAN
RGS RIGID GALVANIZED STEEL
RH ROOF HOOD / RELATIVE HUMIDITY / REHEAT
RHC REHEAT COIL
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RT RESILIENT TILE
RWC RIGID WALLCOVERING
S
S STAIR / STAIN / SURFACE / SANITARY
SA SUPPLY AIR / SOUND ATTENUATOR
SAN SANITARY
SCH SCHEDULE
SD SMOKE DAMPER / SUB DRAIN
SECT SECTION
SF SUPPLY FAN
SHT SHEET
SIM SIMILAR
SOG SLAB-ON-GRADE
SP SUMP PUMP
SPEC SPECIFICATIONS
SPF SPRAY POLYURETHANE FOAM
SQ SQUARE
SS SERVICE SINK / STORM SEWER
SSO STORM SEWER OVERFLOW
SSTL STAINLESS STEEL
ST STAIR TREAD
STA STATION
STD STANDARD
STE STANDARD TAPERED END
STIFF STIFFENER
STIR STIRRUP
STL STEEL
STOR STORAGE
STR STRUCTURAL
SUSP SUSPENDED
SW SWITCH
SWGR SWITCHGEAR
SYM SYMMETRICAL
T
T TREAD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TC TOP OF CURB
TE TOP ELEVATION
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TLT TOILET
TOPO TOPOGRAPHY
TOS TOP OF STEEL
TOW TOP OF WALL
TP TOP OF PAVEMENT
TRANS TRANSVERSE
TYP TYPICAL
U
UC UNDERCUT
UG UNDERGROUND
UH UNIT HEATER
UNO UNLESS NOTED OTHERWISE
UR URINAL
UV UNIT VENTILATOR
V
V VOLT
VAV VARIABLE AIR VOLUME
VB VINYL BASE
VC VERTICAL CURVE
VCP VITRIFIED CLAY PIPE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W
W WATT / WATER
W/ WITH
W/O WITHOUT
WAGD WASTE ANESTHESIA GAS DISPOSAL
WC WATER CLOSET
WD WOOD
WDW WINDOW
WH WATER HEATER / WALL HYDRANT
WP WEATHERPROOF
WPFG WATERPROOFING
WS WATER STOP
WT WEIGHT
WWF WELDED WIRE FABRIC
X
XFMR TRANSFORMER
Y
YD YARD
YH YARD HYDRANT
Mark Revisions: Date:
ARCHITECTURAL GENERAL NOTES
1. THE CONTRACTOR SHALL INSPECT THE SITE,
STUDY EXISTING CONDITIONS, REVIEW
DRAWINGS AND SPECIFICATIONS.
CONTRACTOR SHALL ADJUST FOR ACTUAL
FIELD CONDITIONS AT NO ADDITIONAL
EXPENSE TO THE OWNER.
2. CONTRACTOR SHALL TAKE ALL
MEASUREMENTS FOR THE WORK AND BE
RESPONSIBLE FOR SAME. COORDINATE THE
WORK AND SHOP DRAWINGS WITH ALL
OTHER TRADES AFFECTED AND MAKE ANY
NECESSARY OFFSETS TO CONCEAL PIPING
AND DUCTWORK AND TO CLEAR EQUIPMENT,
STRUCTURAL MEMBERS AND OTHER
OBSTRUCTIONS.
3. ALL UTILITIES AND SERVICES SHALL BE KEPT
IN CONTINUOUS OPERATION UNLESS
WRITTEN PERMISSION IS OTHERWISE
GRANTED BY THE OWNER.
A. MINOR SHUTDOWNS OF LESS THAN
48 HOURS REQUIRE 7 TO 14 DAYS’
NOTICE;
B. MAJOR SHUTDOWNS OF MORE THAN
48 HOURS REQUIRE 14 DAYS’ NOTICE.
C. CONTRACTOR MUST CONTACT VA'S
COR PRIOR TO ANY SHUTDOWNS.
4. TEMPORARY ALTERATIONS AND
CONNECTIONS REQUIRED BY THIS
CONTRACT SHALL BE MADE SO THAT ALL
BUILDING SERVICES ARE MAINTAINED
WITH MINIMUM INTERRUPTION. SCHEDULE
ALL ELECTRICAL/MECHANICAL OUTAGES
14 DAYS IN ADVANCE WITH THE OWNER.
5. PROTECT ALL WORK, MATERIALS AND
EQUIPMENT. CAP OR PLUG TEMPORARY
OPENINGS. DELIVER ALL WORK TO THE
OWNER CLEAN AND IN GOOD CONDITION.
6. WHEN DEMOLITION IS COMPLETE, NOTIFY
ARCHITECT AND OWNER FOR A SCHEDULED
MEETING TO REVIEW EXISTING CONDITIONS
AND ANY CONCERNS REGARDING NEW
WORK.
7. CUTTING AND PATCHING OF EXISTING
WALLS, FLOORS OR CEILINGS REQUIRED BY
NEW WORK SHALL BE INCLUDED AS WORK
PROVIDED UNDER THIS CONTRACT.
8. CUTTING SHALL BE DONE WITH CARE SO AS
NOT TO DAMAGE EXISTING EQUIPMENT,
CONNECTIONS, CONTROLS, ETC.
9. DAMAGE CAUSED BY SUCH CUTTING SHALL
BE REPLACED OR REPAIRED TO ORIGINAL
CONDITION BY CONTRACTOR AT NO COST TO
THE OWNER, UNLESS UNFORESEEN EXISTING
CONDITIONS ARE DISCOVERED AND OWNER
IS NOTIFIED.
10. ALL OCCUPIED WORK AREAS, BUILDING
CORRIDORS AND EXTERIOR AREAS SHALL BE
KEPT CLEAR OF DEBRIS.
11. ALL MATERIALS AND EQUIPMENT SHALL BE
NEW, OF THE BEST QUALITY AND FREE
FROM DEFECTS.
12. MANUFACTURER AND MODEL NUMBERS
SPECIFIED ESTABLISH THE TYPE AND
QUALITY REQUIRED, UNLESS OTHERWISE
NOTED.
13. ALL WORK SHALL COMPLY WITH
APPLICABLE REGULATIONS, CODES AND
ORDINANCES.
14. THE CONTRACTOR SHALL PERFORM ALL
TESTS AS SPECIFIED OR AS NECESSARY TO
DEMONSTRATE A COMPLETE AND
SATISFACTORY INSTALLATION.
15. ALL EXPOSED PENETRATIONS MADE
THROUGH EXISTING ROOFS, FLOORS, AND
WALLS SHALL BE PATCHED WITH LIKE
MATERIALS TO MATCH THE SURROUNDING
AREAS, AND FILLED AS CLOSE AS POSSIBLE
TO THE NEW PIPING OR DUCTWORK.
A. ALL EXPOSED PENETRATIONS MADE
THROUGH EXISTING ROOFS ARE TO
BE COORDINATED WITH THE ROOFING
WARRANTY CONTRACTOR.
B. ALL PENETRATIONS THROUGH RATED
WALLS SHALL BE PATCHED TO
MAINTAIN RATING.
16. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR REPAIRING AND REPLACING ANY
DAMAGE TO EXISTING MATERIALS
RESULTING FROM WORK UNDER THIS
CONTRACT AND SHALL RESTORE SUCH TO
IT'S ORIGINAL CONDITION WITH NEW
MATERIALS TO MATCH EXISTING.
16. INSTALL THE SPECIFIED FIRE STOPPING
(SLEEVES, WRAP, CONDUIT, ETC.) AT RATED
CONSTRUCTION:
A. FIRE STOP ALL PENETRATIONS
WHERE NEW DEVICES/LINES,
RELOCATING EXISTING
DEVICES/LINES, PENETRATING
FLOORS, CEILINGS AND OTHER RATED
BARRIERS.
B. FIRE STOP ALL NEWLY CREATED
PENETRATIONS WHERE EXISTING
DEVICES/LINES PENETRATE FLOORS,
CEILINGS AND OTHER RATED
BARRIERS. USE FIRE APPROVED
CAULKING AND FIRE STOPS (SEE
SPECIFICATIONS).
17. ALL METAL STUD AND GYPSUM WALLBOARD
PARTITIONS ARE DIMENSIONED TO THE
OUTSIDE FACE OF WALL AND TO THE
COLUMN GRD UNLESS OTHERWISE NOTED.
18. ALL GYPSUM BOARD SHALL BE TYPE ’X' FIRE
CODE GYPSUM BOARD MOLD AND MOISTURE
RESISTANT AT WALLS AND CEILINGS.
19. PROVIDE WOOD BLOCKING OR 16 GA.
SHEET METAL BACKING PLATES IN ALL
WALLS TO RECEIVE WALL HUNG
ACCESSORIES, SUCH AS EQUIPMENT,
GRAB BARS, MILLWORK, COAT HOOKS,
AND DOOR STOPS, ETC. IF WOOD
BLOCKING IS USED, PROVIDE AS FIRE-
RESISTANT.
20. ALL ITEMS AND DEVICES, SUCH AS COVER
PLATES, SWITCH PLATES, CONVENIENCE
OUTLETS, DOOR STOPS, AND OTHER FINISH
HARDWARE, ETC. SHALL BE REMOVED AND
REINSTALLED AS PART OF THE REFINISHING
OF EXISTING WALLS INDICATED TO REMAIN.
21. THE CONTRACTOR SHALL WORK WITH THE
CONDITIONS AS THEY EXIST AT THE SITE.
ALL ABOVE CEILING CONDITIONS SHALL BE
REVIEWED AND MODIFICATIONS
IDENTIFIED, COORDINATED, AND
INCORPORATED INTO THE SHOP DRAWING
PROCESS. COORDINATE ALL ABOVE
CEILING WORK TO ENSURE A COMPLETE
AND OPERATIONAL SYSTEM AT NO
ADDITIONAL COST TO THE OWNER.
COORDINATION SHALL INCLUDE, BUT NOT
BE LIMITED TO THE FOLLOWING:
A. THE OWNER'S EQUIPMENT
REQUIREMENTS.
B. THE CEILING SUPPORT SYSTEM.
C. THE MECHANICAL DUCTWORK
SYSTEM.
D. THE LIGHTING FIXTURES.
E. ELECTRICAL WIRING AND CONDUIT
SYSTEMS.
F. THE PLUMBING AND PIPING
SYSTEMS.
G. THE COMMUNICATIONS
SYSTEMS.
22. ALL NEW STUD WALLS AND GYPSUM BOARD
SHALL EXTEND TO STRUCTURE UNLESS
NOTED OTHERWISE.
23. WHEN ALTERING THE BUILDING, IF
STRUCTURAL INTEGRITY APPEARS TO BE
IN QUESTION CONTRACTOR SHALL NOTIFY
OWNER AND ARCHITECT IMMEDIATELY.
24. ALL NEW CONSTRUCTION IS INDICATED BOLD
OR FULL TONE UNLESS NOTED OTHERWISE.
25. WHEN WALL PARTITIONS OF DIFFERENT
FIRE RATING INTERSECT, THE HIGHEST
RATED PARTITION TAKES PRECEDENT.
MAINTAIN RATING BEHIND RECESSED
AREAS IN WALLS.
26. ALL CORRIDOR WALLS ARE REQUIRED TO BE
SMOKE TIGHT, WHETHER THEY ARE FIRE
RATED OR NOT. REPAIR AND EXTEND AT
LEAST THE CORRIDOR SIDE OF NON-RATED
CORRIDOR WALLS TO STRUCTURE, UNLESS
NOTED OTHERWISE, SEE WALL TYPES LISTED
IN DRAWINGS.
27. COORDINATE CONSTRUCTION
REQUIREMENTS WITH MECHANICAL AND
ELECTRICAL DRAWINGS.
28. REVIEW AREAS OF WORK WITH COR FOR
INFECTION CONTROL REQUIREMENTS.
AREAS REQUIRING CLASS I/CLASS II
INFECTION CONTROL WILL REQUIRE
APPROVAL BY THE COR PRIOR TO
BEGINNING WORK. AREAS REQUIRING
CLASS III/CLASS IV INFECTION CONTROL
REQUIRE PERMITS FROM THE VA. SEE
DIVISION 1 SPECIFICATION "SAFETY
REQUIREMENTS-INFECTION CONTROL” FOR
DETAILED INFORMATION.
29. CONTRACTOR SHALL OBSERVE WORK
RESTRICTIONS NOTED IN PHASING
REQUIREMENTS, ON DRAWINGS AND IN THE
SPECIFICATIONS FOR AREAS THAT ARE A
PART OF OR ADJACENT TO
ADMINISTRATIVE, DIETARY, SUPPORT, IN-
PATIENT, OUT-PATIENT AND CLINICAL
AREAS.
30. IF WALLS ARE NOT DAMAGED, THEY CAN BE
CLEANED AFTER DEMO OF CEILINGS AND
HVAC.
31. MISC. EXISTING ACCESSORIES (VA
RESPONSIBLE FOR THESE ITEMS).
1. DASHED BOLD LINES INDICATE EXTEND OF
DEMOLITION INCLUDING THE FOLLOWING:
A. INTERIOR PARTITIONS (REMOVED TO
STRUCTURE)
B. CEILINGS, INCLUDING CEILING
SUSPENSION SYSTEM, MISC. STEEL
SUPPORTS FOR SUSPENDED
EQUIPMENT, SUSPENDED
EQUIPMENT, LIGHT FIXTURES,
DIFFUSERS AND GRILLES ETC.
C. FLOOR FINISHES (TO CONCRETE)
INCLUDING CARPET, RVT, SHEET
VINYL, CERAMIC TILE, QUARRY TILE,
BRICK PAVERS, ETC.
D. DOORS AND FRAMES UNLESS NOTED
OTHERWISE IN DOOR SCHEDULE
E. WINDOW GLAZING AND FRAMES
UNLESS NOTED OTHERWISE
F. BRICK AND BACK-UP WALL SYSTEM
G. CABINETWORK, SHELVING, BASES
H. TOILET PARTITIONS AND
ACCESSORIES
I. TACK BOARDS, MARKER BOARDS,
PEGBOARDS, DISPLAY BOARDS
J. EQUIPMENT ITEMS
K. PLUMBING FIXTURES
2. CONTRACTOR SHALL FIELD VERIFY ALL
EXISTING CONDITIONS.
3. ALL LIGHT OR HALFTONE LINES INDICATE
EXISTING TO REMAIN.
4. SEE SPECIFICATIONS SECTIONS FOR
CUTTING AND PATCHING, INCLUDING
DEMOLITION 02 41 00.
5. SEE ROOM FINISH SCHEDULE, MECHANICAL
PLANS AND ELECTRICAL PLANS FOR
EXTENTS OF NEW CEILING CONSTRUCTION
OR CEILING PATCHING IN EXISTING AREAS.
6. SEE ROOM FINISH SCHEDULE FOR EXTENT
OF NEW FLOORING MATERIAL IN EXISTING
AREAS.
7. SEE ROOM FINISH SCHEDULE FOR EXTENT
OF NEW WALL COVERING MATERIAL IN
EXISTING AREAS. WHERE NEW FINISHES
ARE REQUIRED, REMOVE EXISTING WALL
FINISHES, (TEXTURED PLASTIC COATING,
VINYL WALL COVERING, PANELING, BASE,
ETC.).
8. CONTRACTOR TO VERIFY ALL WALL
CONSTRUCTION & FINISHES NOTED FOR
REMOVAL. TAKE INTO ACCOUNT ANY
DISCREPANCY AND MAKE PROPER
ADJUSTMENT TO ACCOMPLISH REQUIRED
CONSTRUCTION & FINISHES. IF
STRUCTURAL INTEGRITY IS VIOLATED,
CONTACT ARCHITECT.
9. COORDINATE PHASING WITH OWNER.
10. COORDINATE REMOVAL OF FURNITURE AND
EXISTING EQUIPMENT WITH OWNER.
11. REFER TO EQUIPMENT SCHEDULE ON SHEET
QH601 FOR NEW LOCATIONS OF EXISTING
EQUIPMENT, ETC.
12. SAW CUT EDGES OF EXISTING FLOOR SLAB
FOR REMOVAL AND INSTALLATION OF
UTILITIES. REFER TO MECHANICAL AND
ELECTRICAL DRAWINGS.
13. REMOVE FURRING OR GWB ONLY WHERE
REQUIRED TO COMPLETE CONSTRUCTION.
14. PATCH AND MATCH WALLS AS REQUIRED TO
COMPLETE AND MATCH EXISTING
CONDITIONS, UNLESS AN ALTERNATIVE
MATERIAL AND FINISH IS INDICATED.
15. REMOVE CEILINGS ONLY AS REQUIRED FOR
NEW CONSTRUCTION. REINSTALL, REPLACE
OR PATCH AS REQUIRED.
DEMOLITION GENERAL
NOTES
1. ALL CONTRACTORS ARE RESPONSIBLE FOR
REVIEWING ENTIRE SET OF DOCUMENTS TO
DETERMINE THEIR FULL SCOPE OF WORK.
CONTRACTOR SHALL NOT BE ALLOWED
EXTRA COSTS DUE TO FAILURE TO REVIEW
ENTIRE SET OF DOCUMENTS.
2. COVER AND PROTECT ALL VA EQUIPMENT
AND FURNITURE SO THAT THE FUNCTION
AND APPEARANCE IS NOT AFFECTED BY
CONSTRUCTION, THE CONTRACTOR, THEIR
EQUIPMENT, MATERIALS, OR ANY
INVOLVED ACTIONS.
3. A 1 HR MINIMUM FIRE-RATED SEPARATION
IS REQUIRED BETWEEN ALL OCCUPIED
SPACE AND CONSTRUCTION AREAS. THIS
PROTECTION INCLUDES ANY EXISTING
PENETRATIONS AND OPENINGS.
4. SEE BID SET FOR MODULAR BUILDING
COMPLEX AS PART OF BID PACKAGE.
IMPORTANT
CONTRACTOR NOTES
1. ALL STRUCTURAL STEEL AT BUILDING 1
SHALL RECEIVE SPRAY APPLIED
FIREPROOFING TO ACHIEVE A 2-HOUR
RATING.
2. MAINTAIN FIRE RATED CONSTRUCTION AT
WALL PENETRATIONS, (CONSTRUCTION TO
CONFORM TO MANUFACTURER'S FIRE
RATED / TEST ASSEMBLIES.
3. FIRE CAULK ALL SLEEVES AND
PENETRATIONS AT FIRE WALLS /
PARTITIONS AND FLOORS. CONFORM WITH
THE TESTED / SUBMITTED FIRE RATED
ASSEMBLY. USE RED FIRE CAULK AND
LABEL WALL WITH U.L. DESIGN NUMBER.
FIRE RATED WALLS SHOWN ON PLAN.
4. PATCH AND REPAIR ALL EXISTING
FIREPROOFING ON EXISTING STRUCTURAL
MEMBERS, INCLUDING THAT WHICH IS
UNCOVERED NEEDING REPAIR AND THAT
WHICH IS DISTURBED DURING
CONSTRUCTION.
FIREPROOFING GENERAL
NOTES
IF THE CONTRACTOR ENCOUNTERS MATERIAL
THAT COULD BE HAZARDOUS, THE CONTRACTOR
SHALL STOP WORK AND NOTIFY THE
GOVERNMENT IMMEDIATELY FOR DIRECTION.
HAZARDOUS MATERIALS
1. REFER TO ARCHITECTURAL DEMO PLANS
FOR APPROXIMATE EXTENTS OF
DEMOLITION WORK IN PROJECT AREA.
COORDINATE WITH VA COR.
2. REFER TO ROOM FINISH SCHEDULE AND
SPECIFICATIONS FOR INFORMATION ON
FINISHES.
3. REFER TO MEP DRAWINGS FOR
INFORMATION PERTAINING TO
MECHANICAL, ELECTRICAL, AND PLUMBING
WORK. ALL NOTES REGARDING THE
REMOVAL, INSTALL, LOCATION AND/OR
INFORMATION OF MEP ITEMS ARE GIVEN
FOR REFERENCE AND CLARITY ONLY.
4. REFER TO FIRE PROTECTION DRAWINGS
FOR RELATED FIRE PROTECTION
REMODELING.
5. PATCH EXISTING OPENINGS AS NEEDED
AND PREP SURFACE FOR NEW FINISH.
6. PATCH EXISTING WALL W/ FINISHES TO
MATCH EXISTING WHERE DAMAGED BY
DEMOLITION.
7. COORDINATE ALL REINSTALLATION OF VA
ITEMS & ACCESSORIES WITH COR.
8. CONSTRUCTION WASTE IS TO BE REMOVED
TO DUMPSTER. THE COR WILL APPROVE OF
DUMPSTER LOCATIONS.
9. INFILL ALL LOCATIONS WHERE MASONRY
WALLS HAVE BEEN REMOVED.
10. CONTRACTOR TO VERIFY LOCATION OF
EXISTING MEP AND RELATED ITEMS PRIOR
TO START OF RENOVATION
WORK.COORDINATE ALL EXISTING AND
NEW WORK.
11. MECHANICAL AND ELECTRICAL WORK TO
FIT WITHIN WALLS AND CHASES SHOWN;
WHERE EXISTING OR NEW MECHANICAL
AND ELECTRICAL WORK FALLS OUTSIDE OF
THE PROVIDED WALLS AND CHASES, THE
CONTRACTOR SHALL NOTIFY THE COR FOR
REVISIONS TO THE LAYOUT OF WALLS OR
CHASE AT NO ADDITIONAL COST TO THE
OWNER.
12. DEMO WORK AND NEW WORK INDICATE
APPROXIMATE AREA TO BE REMOVED.
CONTRACTOR TO FIELD VERIFY ACTUAL
AREA TO BE REMOVED. CONTRACTOR TO
COORDINATE WORK AREA WITH ALL
TRADES FOR FULL SCOPE OF WORK.
CONTRACTOR IS RESPONSIBLE FOR WORK
AS NECESSARY, FIELD VERIFY.
13. MAINTAIN ALL EXISTING FIRE RATINGS.
FIELD VERIFY.
14. ANY CONTRACTOR DISTURBED FINISHES
MUST BE RESTORED TO MATCH THE
EXISTING FINISH. COORDINATE WITH VA TO
MATCH EXISTING FINISHES.
15. COVER AND PROTECT ALL VA EQUIPMENT
AND FURNITURE SO THAT THE FUNCTION
AND APPEARANCE IS NOT AFFECTED BY
CONSTRUCTION, THE CONTRACTOR, THEIR
EQUIPMENT AND MATERIALS, OR ANY
INVOLVED ACTIONS.
16. A 1 HR MINIMUM FIRE-RATED SEPARATION
IS REQUIRED BETWEEN ALL OCCUPIED
SPACE AND CONSTRUCTION AREAS. THIS
PROTECTION INCLUDES ANY EXISTING
PENETRATIONS AND OPENINGS.
17. PATCH FLOOR SLABS AT PENETRATIONS
AND OPENINGS RESULTING FROM
REMOVAL OF PIPING AS NECESSARY TO
MAINTAIN EXISTING FIRE SEPARATION AND
FINISH AT PIPING AND EQUIPMENT
REMOVAL LOCATIONS PATCH TO MATCH
ADJACENT EXISTING FLOOR.
18. PATCH PARTITION WALLS AT NEW
PENETRATIONS RESULTING FROM
INSTALLATION OF NEW CONDUIT, MECH.,
PLUMBING, OR ELECT. SYSTEM. SEAL
AGAINST NEW PIPING TO MATCH EXISTING
WALL CONDITION. MATCH EXISTING WALL
CONDITION (FINISH, PAINT COLOR, WALL
MOUNTED EQUIPMENT AND ACCESSORIES,
ETC.) TYP. WALL CONDITION: GWB OR
PLASTER. SEE MEP DRAWINGS FOR FULL
EXTENT OF WORK. REMOVE REPLACE,
PATCH AND REPAIR WALL TO THE EXTENT
NECESSARY TO COMPLETE WORK AND
MEET THE REQUIRED STANDARDS FOR VA
CONSTRUCTION. COORDINATE REMOVAL
AND REINSTALLATION OF WALL MOUNTED
EQUIPMENT, ETC. FIELD VERIFY. MAINTAIN
EXISTING FIRE RATINGS. VERIFY EXISTING
CONDITIONS WITH COR DURING PRE-
CONSTRUCTION WALK THRU, ADDITIONAL
COSTS WILL NOT BE ALLOWED.
RENOVATION GENERAL NOTES
19. HATCH PARTITION WALLS AND FILL/PATCH
OPENINGS RESULTING FROM REMOVAL OF
PIPING. MATCH EXISTING WALL CONDITION
(FINISH, PAINT COLOR, WALL MOUNTED
EQUIPMENT, AND ACCESSORIES, ETC.) TYP.
WALL CONDITION: GWB OR PLASTER. SEE
MEP DRAWINGS FOR FULL EXTENT OF
WORK. REMOVE, REPLACE, PATCH, AND
REPAIR WALL TO THE EXTENT NECESSARY
TO COMPLETE WORK AND MEET THE
REQUIRED STANDARDS FOR VA
CONTSTRUCTION. COORDINATE REMOVAL
AND REINSTALLATION OF WALL MOUNTED
EQUIPMENT, ETC. FIELD VERIFY. MAINTAIN
EXISTING FIRE RATINGS. VERIFY EXISTING
CONDITIONS WITH COR DURING PRE-
CONSTRUCTION WALK THRU, ADDITIONAL
COSTS WILL NOT BE ALLOWED.
20. CONTRACTOR SHALL PROVIDE ALL
NECESSARY TEMPORARY SUPPORTS AS
REQUIRED FOR CEILING MOUNTED
EQUIPMENT DURING DEMOLITION AND
REBUILD OPERATIONS.
21. REMOVE TEMPORARY CONSTRUCTION
PARTITIONS AFTER COMPLETION OF WORK.
PATCH/PAINT TO MATCH EXISTING/NEW
FINISHES.
22. MEP ELEMENTS SHOWN IN
ARCHITECTURAL PLANS ARE FOR
REFERENCE ONLY. REFER TO MEP
DRAWINGS FOR INFORMATION PERTAINING
TO MEP ELEMENTS.
23. DISRUPTIVE ACTIVITIES IN OCCUPIED
SPACES TO BE LIMITED AS DIRECTED BY
COR. COORDINATE WELL IN ADVANCE WITH
COR PRIOR TO BEGINNING WORK.
SEE SECTION 01 00 00 - GENERAL REQUIREMENTS
FOR FULL DESCRIPTION OF DEDUCT ALTERNATE.
REFER TO SHEET AG002- ARCHITECTURAL
GENERAL NOTES FOR LISTING OF DEDUCT
ALTERNATE. SEE DRAWINGS FOR ADDITIONAL
NOTES AND DIRECTIONS RELATED TO DEDUCT
ALTERNATE.
DEDUCT ALTERNATE
DEDUCT ALTERNATE LIST
DEDUCT ALTERNATE – INCLUDES THE FOLLOWING:
A. DELETE NEW AHU-9 AND ALL RELATED
AND/OR CONNECTED SYSTEMS (DUCTWORK,
PIPING, STRUCTURAL PLATFORM,
REROOFING, CEILING REPLACEMENT,
TEMPERATURE CONTROL, ELECTRICAL,
DEMOLITION, ETC.)
B. DELETE NEW DENTAL AHU AND ALL RELATED
AND/OR CONNECTED SYSTEMS (DUCTWORK,
PIPING, STRUCTURAL PLATFORM,
REROOFING, CEILING REPLACEMENT,
TEMPERATURE CONTROL, ELECTRICAL,
DEMOLITION, ETC.)
C. DELETE ALL ARCHITECTURAL & INTERIOR
DESIGN WORK (DEMOLITION, AND NEW) ON
GROUND FLOOR, AREAS AW & E
D. DELETE ALL ARCHITECTURAL & INTERIOR
DESIGN WORK (DEMOLITION, AND NEW) ON
FIRST FLOOR, AREAS AW, E & F (EXCEPT FOR
WORK RELATED TO DEDICATED AHU SERVING
MAIL ROOM 1A-173)
E. DELETE ALL FIRE PROTECTION WORK
(DEMOLITION, AND NEW) ON GROUND FLOOR,
AREAS AW & E
F. DELETE ALL FIRE PROTECTION WORK
(DEMOLITION, AND NEW) ON FIRST FLOOR,
AREAS AW, E & F
G. DELETE ALL PLUMBING WORK (DEMOLITION,
AND NEW) ON GROUND FLOOR, AREAS AW & E
H. DELETE ALL PLUMBING WORK (DEMOLITION,
AND NEW) ON FIRST FLOOR, AREAS AW, E & F
I. DELETE ALL MECHANICAL PIPING WORK
(DEMOLITION, AND NEW) ON GROUND FLOOR,
AREAS AW & E
J. DELETE ALL MECHANICAL PIPING
(DEMOLITION, AND NEW) ON FIRST FLOOR,
AREAS AW, E & F (EXCEPT FOR WORK
RELATED TO DEDICATED AHU SERVING MAIL
ROOM 1A-173)
K. DELETE ALL MECHANICAL VENTILATION WORK
(DEMOLITION, AND NEW) ON GROUND FLOOR,
AREAS AW & E
L. DELETE ALL MECHANICAL VENTILATION
(DEMOLITION, AND NEW) ON FIRST FLOOR,
AREAS AW, E & F (EXCEPT FOR WORK
RELATED TO DEDICATED AHU SERVING MAIL
ROOM 1A-173)
M. DELETE ALL WORK RELATED TO THE NEW
TEMPORARY AHU, SHOWN ON FIRST FLOOR
VENTILATION WEST OF BUILDING 1
N. DELETE ALL ELECTRICAL LIGHTING & POWER
WORK (DEMOLITION, AND NEW) ON GROUND
FLOOR, AREAS AW & E
O. DELETE ALL ELECTRICAL LIGHTING & POWER
WORK (DEMOLITION, AND NEW) ON FIRST
FLOOR, AREAS AW, E & F (EXCEPT FOR WORK
RELATED TO DEDICATED AHU SERVING MAIL
ROOM 1A-173)
P. DELETE ALL TEMPORARY MODULAR
BUILDINGS AND/OR TRAILERS SHOWN FOR
PHASES 2, 3, & 4. ONLY PHASE 1 TEMPORARY
BUILDINGS AND CONNECTING LINK REMAINS
CONTRACTOR SHALL REFER TO THE MODULAR
BUILDING COMPLEX PACKAGE FOR COORDINATION
AND RELOCATION DURING PHASING OF
DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,
ETC. REQUIRED FOR CONTINUED VA OPERATIONS.
MODULAR BUILDING
COMPLEX COORDINATION
JIM
H.
HAGEMAN
A-2205
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
8/30/2024
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
CC
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
A u to d e s k D o c s
/2
-1
A -2
-3
V
A P o p la r
B lu ff
R e m o v e a n d
R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.A rc h R
-1
-R e p l L a b A
H U
A
H U
.r v t
/9
/2
:0
:0
P M
AG002
ARCHITECTURAL GENERAL
NOTES
REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATION, AND
AIR CONDITIONING
JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL
CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO
63901-3318
657A4-21-800
8/30/2024 JHH ALESIA
AD104
D1
A-200
F6
MEDICAL
RECORDS
1A-101
RELEASE OF
INFORMATION
1A-102
PATIENT REP QM
1A-103
BUSINESS
1A-104
BUSINESS
1A-105
BREAK ROOM
1A-106
MY HEALTHE-VET
OFFICE
1A-107
EXAM
ROOM/DOCTOR
OFFICE
1A-108
DENTAL WAITING
ROOM
1E-110
CLERK'S OFFICE
1E-111
BREAK ROOM
1E-112
DENTAL
HYGEINE
1E-113
ORAL SURGERY
1E-114
OFFICE
1E-116
DENTAL
LABORATORY
1E-129
DENTAL
TREATMENT
1E-130
DENTAL IMAGING
1E-131
DENTAL IMAGING
1E-132
PATIENT
EDUCATION
1A-144
SOILED
LINEN/CLOSET
1F-147
RESTROOM, F
1F-149
MEDICATION
ROOM
1F-150
BUSINESS
OFFICE
1F-151
BUSINESS
OFFICE
1F-152
EXAM
1F-154
OEF/OIF CASE
MANAGER
1F-155
CHECK-IN/WAITING
1F-156
EXAM
1F-157
EXAM
1F-159
STAFF WORK
ROOM
1F-160
STERILE
1F-161
C&P CHECK IN
1F-163
WAITING ROOM
1F-166
EXAM
1F-167
OFFICE OF
PATIENT
ADVOCATE
1A-171
VETERANS
EXPERIENCE
OFFICE
1A-172
MAIL ROOM
1A-173
DENTAL
TREATMENT
1E-130A
A B B.1 W X Y AA CC BB DD FF L M
1.1
14.1
EXAM
1F-153
RESTROOM
1F-162RESTROOM, F
1F-158
CAREGIVER
SUPPORT/RN
ASSESSOR
1F-165
HOLDING AREA
1A-170
RESTROOM, M
1F-169
HAC CLOSET
1F-168
ADMISSIONS
1A-142
CLOSET
1E-115
ELECTRICAL
CLOSET
1E-110B
COMPRESSOR
1E-109
CORRIDOR E
1E-C01
HOOD
STAIR E
1E-S01
D21
REMOVE DUCT AND PATCH
REMOVE HOOD AND PATCH
REMOVE HOOD AND PATCH
REMOVE HOOD AND PATCH
REMOVE DUCT AND PATCH
REMOVE HOOD AND PATCH
REMOVE DUCT AND PATCH
REMOVE HOOD AND
PATCH
CONTRACTOR SHALL REFER TO THE MODULAR
BUILDING COMPLEX PACKAGE FOR COORDINATION
AND RELOCATION DURING PHASING OF
DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,
ETC. REQUIRED FOR CONTINUED VA OPERATIONS.
MODULAR BUILDING
COMPLEX COORDINATION
SEE GENERAL NOTES ON SHEET AG002.
GENERAL
DEMOLITION NOTESSEE PROJECT MANUAL SECTION 01 00 00-GENERAL
CONDITIONS, SHEET AG002 & TEMPORARY
MODULAR BUILDING COMPLEX DRAWINGS FOR
DESCRIPTION OF DEDUCT ALTERNATE.
DEDUCT ALTERNATE
JIM
H.
HAGEMAN
A-2205
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
8/30/2024
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
CC
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
KEY PLAN
E
F
D
B
TT
Aw Ac Ae
C
A u to d e s k D o c s
/2
-1
A -2
-3
V
A P o p la r
B lu ff
R e m o v e a n d
R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.A rc h R
-1
-R e p l L a b A
H U
A
H U
.r v t
/9
/2
:0
:4
P M
AD101
FIRST FLOOR - DEMOLITION PLAN REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATION, AND
AIR CONDITIONING
JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL
CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO
63901-3318
657A4-21-800
8/30/2024 GG TF
1/16" = 1'-0"1
FIRST FLOOR - DEMOLITION PLAN
1" = 1'-0"A5
LOOKING WEST
1" = 1'-0"C7
HOOD END
1" = 1'-0"C5
DUCT CONNECTED TO HOOD
1" = 1'-0"D7
AREA BELOW HOOD
1" = 1'-0"D5
DUCK CONNECTED TO HOOD
KEYNOTE LEGEND
KEY KEYNOTE
D21 DENTAL HOOD REMOVAL IN DENTAL LAB
1E-129.
DEDUCT ALTERNATE - SEE AG002 &
TEMPORARY MODULAR BUILDING
COMPLEX DRAWINGS
N O P
Q
R S T U V
HEMATOLOGY
2C-048
CHEMISTRY
2C-046
CORRIDOR C
2C-C01
ANCILLARY
OFFICE
2C-051
SPECIMEN &
REAGENT
STORAGE
2C-045
BREAK ROOM
2C-044
RESTROOM, M/F
2C-043
CLOSET
2C-042A
LAB
INFORMATION
OFFICE
2C-042
REAGENT /
SUPPLIES ROOM
2C-054
HOUSEKEEPING
CLOSET
2C-052
HOUSEKEEPING
CLOSET
2C-053
RESTROOM, M/F
2C-055A
LAB COAT
CLOSET
2C-054A
LAB
SUPERVISOR
OFFICE
2C-041
PHLEBOTOMY
2A-055
WAITING ROOM
RADIOLOGY/LAB
2A-057
WAITING ROOM
RAIOLOGY/LAB
2A-058
CULTURE ROOM
2A-038
MICROBIOLOGY
2A-037B
BLOOD BANK /
HISTOLOGY
2A-037A
LAB SUPPLY
ROOM
2A-037
RECORDS/SUPPLY
STORAGE
2A-036
DEMO CASEWORK
DEMO CASEWORK
DEMO CASEWORK
CORRIDOR A3
2A-C01
REMOVE EXIST
FLOOR TILE/MASTIC -
SEE HAZ-MAT
DRAWINGS
REMOVE EXIST
FLOOR TILE/MASTIC -
SEE HAZ-MAT
DRAWINGS
A-901 F8
ELECTRICAL
CLOSET
2A-035
EQUIPMENT
2B-034
X-RAY IMAGING
ROOM
2B-033
STORAGE
2B-010
RESTROOM, F
2B-011
CT CONTROL
ROOM
2A-007
RESTROOM, M
2A-009
LINEN CHUTE/HK
CLOSET
2A-008
EXISTING HAND SINK TO REMAIN
EXISTING BASE CABINET /
COUNTERTOP / SINK TO REMAIN
CONTRACTOR SHALL REFER TO THE MODULAR
BUILDING COMPLEX PACKAGE FOR COORDINATION
AND RELOCATION DURING PHASING OF
DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,
ETC. REQUIRED FOR CONTINUED VA OPERATIONS.
MODULAR BUILDING
COMPLEX COORDINATION
SEE GENERAL NOTES ON SHEET AG002.
GENERAL
DEMOLITION NOTESSEE PROJECT MANUAL SECTION 01 00 00-GENERAL
CONDITIONS, SHEET AG002 & TEMPORARY
MODULAR BUILDING COMPLEX DRAWINGS FOR
DESCRIPTION OF DEDUCT ALTERNATE.
DEDUCT ALTERNATE
JIM
H.
HAGEMAN
A-2205
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
8/30/2024
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
CC
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
E
D
C
B
KEY PLAN
F
Aw Ac Ae
A u to d e s k D o c s
/2
-1
A -2
-3
V
A P o p la r
B lu ff
R e m o v e a n d
R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.A rc h R
-1
-R e p l L a b A
H U
A
H U
.r v t
/9
/2
:0
:5
P M
AD102
SECOND FLOOR - DEMOLITION
PLAN
REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATION, AND
AIR CONDITIONING
JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL
CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO
63901-3318
657A4-21-800
8/30/2024 GG KRK
1/8" = 1'-0"1
SECOND FLOOR - DEMOLITION PLAN
DEDUCT ALTERNATE - SEE AG002 &
TEMPORARY MODULAR BUILDING
A-200
D1
D1
A-301
REMOVE EXISTING WINDOW,
WINDOW SILL AND MASONRY WALL
BELOW WINDOW SILL. WALL
DEMOLITION EXTENDS BELOW
FLOOR LEVEL TO CREATE SPACE
FOR NEW CAST CONCRETE DOOR SILL
EXISTING MASONRY SUPPORT LINTEL REMAINS
IN PLACE ABOVE EXISTING WINDOW OPENING.
SEE STRUCTURAL DEMO NOTES AND DETAIL
P
Q
R S T U V
SALVAGE/CLEAN EXISTING BRICK REMOVED
FROM OPENING FOR USE IN NEW OPENING
PHYSICAL
THERAPY
4C-038A
SOCIAL WORKER
(CARE-GIVER
SPPT.
COORD./PALLIATIVE
CARE)
4C-038B
MINIMUM DATA
SET CARE PLAN
COORDINATOR
OFFICE
4C-038
PATIENT ROOM
[2]
4C-038C
PATIENT ROOM
[2]
4C-037
CORRIDOR C
4C-C01RESTROOM, M/F
4C-040
RESTROOM, M/F
4C-037A
LINEN CLOSET
4A-042
ELECTRICAL
CLOSET
4A-041
STAIRWELL 4
4A-S01
MEDICATION
ROOM
4A-045
BREAK ROOM
4A-044
CORRIDOR A
4A-C02
LIVING ROOM
4A-034
CONTRACTOR SHALL REFER TO THE MODULAR
BUILDING COMPLEX PACKAGE FOR COORDINATION
AND RELOCATION DURING PHASING OF
DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,
ETC. REQUIRED FOR CONTINUED VA OPERATIONS.
MODULAR BUILDING
COMPLEX COORDINATION
SEE GENERAL NOTES ON SHEET AG002.
GENERAL
DEMOLITION NOTESSEE PROJECT MANUAL SECTION 01 00 00-GENERAL
CONDITIONS, SHEET AG002 & TEMPORARY
MODULAR BUILDING COMPLEX DRAWINGS FOR
DESCRIPTION OF DEDUCT ALTERNATE.
DEDUCT ALTERNATE
JIM
H.
HAGEMAN
A-2205
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
8/30/2024
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
CC
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
E
F
D
C
B
KEY PLAN
Aw Ac Ae
A u to d e s k D o c s
/2
-1
A -2
-3
V
A P o p la r
B lu ff
R e m o v e a n d
R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.A rc h R
-1
-R e p l L a b A
H U
A
H U
.r v t
/9
/2
:0
:5
P M
AD103
FOURTH FLOOR - DEMOLITION
PLAN
REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATION, AND
AIR CONDITIONING
JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL
CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO
63901-3318
657A4-21-800
8/30/2024 GG KRK
1/4" = 1'-0"1
FOURTH FLOOR DEMO PLAN
DOOR TO REMAIN
REMOVE/REUSE PARAPET CAP AS
REQUIRED TO REPLACE ROOF
MEMBRANE AND FLASHING
METAL LOUVER SCREEN
TO REMAIN
NOTE:
CHANGE OF ELEVATION
APPROX 18" HIGHER
THAN SOUTH ROOF
REMOVE AND RETAIN FOR
REUSE - EXISTING FALL
PROTECTION AS
REQUIRED. REMOVE AND
REUSE PARAPET STONE CAP
ASSEMBLIES, ROOF
MEMBRANE, FLASHING,
INSULATION, AND SHEATHING
TO STRUCTURAL DECK
BELOW-TYPICAL ALL HATCHED
AREAS THIS PLAN
REMOVE EXISTING AIR
HANDLER AND PERIMETER
SUPORT CURB STRUCTURE-
CLEAR ROOF PENETRATIONS
(VERIFY NUMBER) FOR INFILL
WORK
EGRESS ROUTE RAILING COLUMN
SUPORT BLOCKS (8 VERIFY) AT
DECK LEVEL TO REMAIM
EXISTING METAL
LOUVER SUPPORT
SYSTEM TO REMAIN -
(8) VERIFY NUMBER
OF SUPORTS ALONG ENTIRE PERIMITER OF
SUPPORTING CURB REMOVE
WOOD NAILER, COUNTER
FLASHING, CURB FLASHING
BOND BEAM TOP COURSE
AD104
E5
A B B.1 W X Y AA CC
1.1
DENTAL
LABORATORY
1E-129
CORRIDOR E
1E-C01
OFFICE
1E-116
EXISTING EXHAUST
FAN/CURB TO REMOVE &
REPLACE W/ NEW
CURB/FAN - SEE MECH
1-EF11
EF-2E
INFILL ABANDONED
ROOF FAN OPENING -
SEE MECH
RD
RD
RD
RD
RD
RD
SLOPE
1/4" / FT
SLOPE
1/4" / FT
SLOPE
1/4" / FT
SLOPE
1/4" / FT
SLOPE
1/4" / FT
+3"
+3"
+3"
AHU-9E
BOILER ROOM ROOF
EXISTING CHAIN LINK FENCE
AD104B9
AD104
C9
VTR
AD104
D9
AD104
F5
AD104
F7
AD104
E9
SCREEN WALL BRACE
SUPPORT BASE - REMOVE AND
REPLACE TPO MEMBRANE (TYP)
SCREEN SUPPORT COLUMN
BASE - REMOVE AND
REPLACE TPO MEMBRANE
(TYP)
VTR
SLOPE
1/4" / FT
A-501
B4
T.O. CONC DECK @ RIDGE = 432.83' (FV)
T.O. WOOD DECK @ RIDGE = 434.75' (FV)
B.O. WOOD ROOF JOIST +1'-3" ABOVE
ROOF DECK
T.O. CONC DECK @ RIDGE = 432.83'
T.O. WOOD DECK @ RIDGE = 434.5' +
SLOPED CRICKET = 434.9' (FV)
DOOR TO REMAIN
EXISTING AHU AND SUPPORT CURBING TO
BE REMOVED- VERIFY ROOF PENETRATIONS
FOR REPAIR BY INFILL
EXISTING CHILLER AND SUPORT CURBING
TO BE REMOVED- VERIFY ROOF
PENETRATIONS FOR REPAIR BY INFILL
REMOVE PARAPET CAP ASSEMBLIES,
ROOF MEMBRANE, FLASHING,
INSULATION, AND SHEATHING TO
STRUCTURAL DECK BELOW - TYPICAL ALL
HATCHED AREAS
REMOVE EXIST. STL. STAIRS,
LANDING, AND GUARDRAILS
REMOVE AND RETAIN FOR
USE - EXISTING FALL
PROTECTION AS REQUIRED.
CUT OUT BACK SIDE OF MASNORY
PARAPET, PARAPET CAP, & ROOFING IN
ROUGHLY 18"X14" AREA DOWN TO ROOF
SLAB FOR INSTALLATION OF 8 STEEL
TUBE COLUMNS, THEN REPLACE
MASONRY SURROUNDINGS COLUMNS.
COORDINATE LOCATION WITH NEW
CONSTRUCTION.
PORTIONS OF ROOF WILL NEED TO BE DEMO'D FOR
NEW MECHANICAL DUCT WORK. REFER TO MEP
DRAWINGS FOR LOCATION.
P Q R S T U V
STORAGE
3C-041C
CORRIDOR C
NORTH
3C-01A
HOSPITALIST
3C-041B
AD104 A5
AD104 B5
AD104
A6
AD104
B6
AD104
A7
RDRD
AD104
B7
SLOPE
1/4" FT
S
LO
P E
1/ 4"
F T
SL
O
PE
1/
4" F
T
SLOPE
1/4" FT
S
LO
P E
SLOPE
REMOVE FOR REUSE, ALUM.
LOUVER SCREEN WALL &
RESPECTIVE TRIM PIECES,
AND STEEL TUBE SUPPORT
SYSTEM TO BELOW ROOF.
FF L M
CORRIDOR A3
2A-C01
PRIMARY CARE
PROGRAM
SUPPORT
ASSISTANT
OFFICE
2A-131
ASSOCIATE
CHIEF OF STAFF,
PRIMARY CARE
OFFICE
2A-132
CT COOLING
SYSTEM
2A-002A
HOT LAB
2A-001
NUCLEAR
MEDICINE
IMAGING ROOM
2A-002
PROGRAM
DIRECTOR,
MENTAL HEALTH
OFFICE
2A-130
A-402
A-402 E1
F1
REMOVE EXISTING CURB AND
FLASHING IN ITS ENTIRETY
REMOVE EXISTING CANT
EXISTING ROOF STRUCTURE
REMOVE EXISTING BOND
BEAM TOP COURSE
EXISTING ROOF INSULATION
TO REMAIN
EXISTING MASONRY TO
REMAIN
DEMOLISH EXISTING DUCTWORK
AS NEEDED FOR NEW
CONSTRUCTION WORK
REMOVE EXISTING RIGID
INSULATION
REMOVE EXISTING AHU - REFER TO
MECHANICAL
REMOVE EXISTING TPO & INSULATION
VARIES
SEE GENERAL NOTES ON SHEET AG002.
GENERAL
DEMOLITION NOTESSEE PROJECT MANUAL SECTION 01 00 00-GENERAL
CONDITIONS, SHEET AG002 & TEMPORARY
MODULAR BUILDING COMPLEX DRAWINGS FOR
DESCRIPTION OF DEDUCT ALTERNATE.
DEDUCT ALTERNATE
REMOVE / REPLACE TPO MEMBRANE
TEAR OFF TPO & INSULATION TO WOOD
DECK AND REPLACE WITH NEW
TEAR OFF TPO & INSULATION TO WOOD
DECK AND REPLACE WITH NEW
REMOVE AND REPLACE ROOF DRAIN
TEAR OFF TPO & INSULATION TO WOOD
DECK AND REPLACE WITH NEW
REMOVE AND REPLACE ROOF DRAIN
TEAR OFF TPO & INSULATION TO
WOOD DECK AND REPLACE WITH
NEW
REMOVE / REPLACE ROOF DRAIN
REMOVE AHU & CURB / INFILL
REMOVE / REPLACE FLASHING FOR VTR -
SEE MECH FOR VTR WORK
REMOVE / REPLACE ROOF DRAIN
REMOVE AND REPLACE TPO MEMBRANE
(TYP)
REMOVE AND REPLACE TPO MEMBRANE
(TYP)
TEAR OFF TPO & INSULATION TO
WOOD DECK AND REPLACE WITH
NEW
EXISTING EXHAUST FAN/CURB TO
REMOVE & REPLACE W/ NEW
CURB/FAN
REMOVE AND REPLACE ROOF DRAIN
REMOVE / REPLACE FLASHING FOR
VTR - SEE MECH FOR VTR WORK
REMOVE AND INFILL
TEAR OFF TPO & INSULATION TO WOOD
DECK AND REPLACE WITH NEW
REMOVE - SEE MECH FOR VTR WORK
REMOVE AND REPLACE ROOF DRAIN
REMOVE AND REPLACE TPO MEMBRANE
REMOVE EXISTING EQUIPMENT -
SEE MECHANICAL SHEETS
EXISTING SCUPPER
REMOVE EXISTING EQUIPMENT -
SEE MECHANICAL SHEETS
REMOVE EXISTING EQUIPMENT -
SEE MECHANICAL SHEETS
RELOCATE EXISTING SPLIT
SYSTEM AND ALL PIPING,
BRACKETS, CONTROLS,WIRING,
ACCESSORIES, ETC AS
REQUIRED TO COORDINATE
WITH NEW DUCT LAYOUT -
SEE MECHANICAL SHEETS
REMOVE EXISTING
EQUIPMENT - SEE
MECHANICAL SHEETS
TEAR OFF TPO & INSULATION
AND REPLACE WITH NEW,
TYP.
REMOVE EXISTING
EQUIPMENT - SEE
MECHANICAL SHEETS
REMOVE STEPS AND
RAILING - DOOR TO REMAIN
JIM
H.
HAGEMAN
A-2205
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
8/30/2024
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORD
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
CC
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
KEY PLAN
E
F
D
B
Aw Ac Ae
C
A u to d e s k D o c s
/2
-1
A -2
-3
V
A P o p la r
B lu ff
R e m o v e a n d
R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.A rc h R
-1
-R e p l L a b A
H U
A
H U
.r v t
/9
/2
:0
:5
P M
AD104
ROOF DEMOLITION PLANS REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATION, AND
AIR CONDITIONING
JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL
CENTER 1500 N. WESTWOOD BLVD. POPLAR BLUFF, MO
63901-3318
657A4-21-800
8/30/2024 GG KRK
1/8" = 1'-0"D1
FIRST FLOOR - ENLARGED ROOF DEMO PLAN - AREA 'E' - LAUNDRY
1/8" = 1'-0"C5
THIRD FLOOR - ENLARGED ROOF DEMO PLAN - AREA 'C' - LAB AHU
1/8" = 1'-0"F1
SECOND FLOOR - ENLARGED MAIN ENTRY ROOF DEMO PLAN - AREA
'A-CENTER' - MAIL RTU
1" = 1'-0"E5
DEMOLITION SECTION - ROOFTOP AHU CURB
DEDUCT ALTERNATE - SEE AG002 &
TEMPORARY MODULAR BUILDING
COMPLEX DRAWINGS
DEDUCT ALTERNATE - SEE AG002 &
TEMPORARY MODULAR BUILDING
COMPLEX DRAWINGS
1 1/2" = 1'-0"B9
EXISTING LAUNDRY ROOF
1 1/2" = 1'-0"C9
EXISTING LAUNDRY ROOF
1 1/2" = 1'-0"D9
EXISTING LAUNDRY ROOF
1 1/2" = 1'-0"F5
EXISTING LAUNDRY ROOF
1 1/2" = 1'-0"F7
EXISTING LAUNDRY ROOF
1 1/2" = 1'-0"E9
EXISTING LAUNDRY ROOF
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALENOT TO SCALENOT TO SCALE
1 1/2" = 1'-0"A5
EXISTING 3RD FL C ROOF
1 1/2" = 1'-0"B5
EXISTING 3RD FL C ROOF
1 1/2" = 1'-0"A6
EXISTING 3RD FL C ROOF
1 1/2" = 1'-0"B6
EXISTING 3RD FL C ROOF
1 1/2" = 1'-0"A7
EXISTING 3RD FL C ROOF
1 1/2" = 1'-0"B7
EXISTING 3RD FL C ROOF
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALENOT TO SCALE
ACD110
F1
ACD110
F4
RESTROOM/
SHOWER, M
GA-055
LOCKER RM., M
GA-056
STORAGE
GE-068
MORGUE
GA-072
EMS
GA-073
REST ROOM
GA-075
RESTROOM/
SHOWER, F
GA-079
CREDIT UNION
GA-080
REMOVE GWB SOFIT ABOVE AT
ACD110
B4
A B B.1 W X Y AA CC BB DD FF L M
N O P Q R S T U V
1.1
14.1
ELECTRICAL
ROOM
GA-081
OFFICE
GA-082
OFFICE
GE-063
OFFICE
GE-062
LAUNDRY
GE-070
VESTIBULE
GE-069
SOILED LINEN
GE-067
LAUNDRY
GE-066
STAFF
RESTROOM
GE-065
OFFICE
GE-068A
CORRIDOR
GE-C01
ROOM
GE-064
CORRIDOR
GA-C01
SUPPLY
GA-059
CLOSET
GA-058
RESTROOM, F
GA-079A
STORAGE
GA-076
SLOPED CORRIDOR CEILING - REMOVE AND RELACE
EXIST GWB/MTL STUD BULKHEAD TO REMAIN -
MODIFY AS REQ'D FOR REMOVAL OF EXISTING
DUCTS AND INSTALLATION OF NEW DUCTWORK
LOCKER RM., F
GA-077
OFFICE
GA-077A
OPEN TO
STRUCTURE
CORRIDOR
GE-C01
343 SF
STORAGE
GC-011A
STAIRWELL C
GC-S01
MECH. ROOM
GC-011
EYE CLINIC
GC-10C
EYE CLINIC
GC-10B
EYE CLINIC
GC-10A
EYE GLASS
SALES
GC-010
ELEC. CLOSET
GC-09B
CORRIDOR
GC-C01
ELEV
GC-E05
EXAM ROOM
GC-014
EXAM ROOM
GC-14A
PROCEDURE
GC-015
PROCEDURE
GC-15A
EXAM
GC-016
EYE CLINIC
GC-16A
CHECK-IN
GA-017
CHECK-IN
GA-17C
RESTROOM M/F
GA-17A
STAIRWELL 4
GA-S01
ENTRANCE
GA-09A
PHARMACY
WAITING ROOM
GA-07A
RECONCILLIATION
GA-07Q
MECH. RM
GA-07
PHYSICAL
THERAPY
GA-18
EXAM 2
GA-18A
WAITING RM
GA-17B
ELEC. CLOSET
GA-07TPROSTHETICS
GA-03
CHUTE
GA-05
PIPE CHASE
GA-01C
STORAGE
GA-07M
STAIRWELL 5
GA-S02
CALL CENTER
GB-07J
PURCHASER'S
OFFICE
GB-07K
BREAKROOM
GB-07N
RESTROOM
GB-07R
HVAC RM
GB-07S
NARCOTICS RM
GB-07G
CHEMO HD RM
GB-07F
IV ROOM
GB-07E
CLOSET
GB-07P
IV HOOD ROOM
GB-07L
IV TECHNICIAN
GB-07D
DIRECTOR'S
OFFICE
GB-07C
SECRETARY
GB-07O
STOCK AREA
GB-07I
DISPENSING
GB-07H
CORRIDOR
GB-C01
DISPENSING
GB-07B
EXAM 1
GA-02
STORAGE
GA-1A
PIPE CHASE
GA-01B
TELECOMMUNICATIONS
GD-22
TELECOM
SWITCH
GA-052
ELEC. CLOSET
GD-01D
SUPERVISOR
OFFICE
GD-47
RESTROOM, M
GD-46
CLOSET
GD-47A
COUMADIN
STORAGE
GD-28
COUMADIN
CLOSET
GD-29
ELEC. STORAGE
GD-27
STAIRWELL 6
GD-S03
COUMADIN
CLINIC
GD-30
CONFERENCE
ROOM
GD-45A
CORRIDOR
GD-CC
STORAGE
GD-32
BIOMED SHOP
GD-34
BIOMED
GD-35
MECH. ROOM
GD-45
ELEC. CLOSET
GD-GD
ELEC. SHOP
GD-36
BACKUP
STORAGE
GD-37
MECH. ROOM
GD-38
UNION OFFICE
GD-44
AC SHOP
GD-44A
STAIRWELL 7
GD-S01
EQUIP. STORAGE
GD-42
TRASH CART
GD-39
STAIRWELL 3
GA-S03
CONTRACTOR SHALL REFER TO THE MODULAR
BUILDING COMPLEX PACKAGE FOR COORDINATION
AND RELOCATION DURING PHASING OF
DEPARTMENTS, EQUIPMENT, INFRASTRUCTURE,
ETC. REQUIRED FOR CONTINUED VA OPERATIONS.
MODULAR BUILDING
COMPLEX COORDINATION
SEE GENERAL NOTES ON SHEET AG002.
GENERAL DEMOLITION
AND RENOVATION NOTESSEE PROJECT MANUAL SECTION 01 00 00-GENERAL
CONDITIONS, SHEET AG002 & TEMPORARY
MODULAR BUILDING COMPLEX DRAWINGS FOR
DESCRIPTION OF DEDUCT ALTERNATE.
DEDUCT ALTERNATE
DEMO WOOD CEILING
EXISTING GYPSUM WALL BOARD CEILING
EXISTING SUSPENDED ACOUSTICAL REMAIN
DEMO SUSPENDED ACOUSTICAL
EXISTING SUPPLY AIR GRILLE - SEE MECHANICAL
EXISTING RETURN AIR GRILLE - SEE MECHANICAL
EXISTING RECESSED 2X2 LIGHT FIXTURE - SEE ELECTRICAL
EXISTING RECESSED 2X4 LIGHT FIXTURE - SEE ELECTRICAL
EXISTING CAN LIGHT
EXISTING EXIT LIGHT
EXISTING WIRELESS ACCESS POINT
EXISTING SPEAKER
EXISTING SMOKE DETECTOR
EXISTING OCCUPANCY SENSOR
EXISTING VIDEO SURVEILLANCE CAMERA
REFLECTED CEILING LEGEND
WOOD CEILING
GYPSUM WALL BOARD CEILING
SUSPENDED ACOUSTICAL CEILING
SUPPLY AIR GRILLE - SEE MECHANICAL
RETURN AIR GRILLE TO - SEE MECHANICAL
RECESSED 2X2 LIGHT FIXTURE - SEE ELECTRICAL
RECESSED 2X4 LIGHT FIXTURE - SEE ELECTRICAL
CAN LIGHT
EXIT LIGHT
WIRELESS ACCESS POINT
SPEAKER
SMOKE DETECTOR
OCCUPANCY SENSOR
VIDEO SURVEILLANCE CAMERA
S
S SD
OS OS
OS
WAP
WAP
CCTV
CCTV
JIM
H.
HAGEMAN
A-2205
A
R C H I T E
C
T
S T
A T
E
O F N E B
R A
S K
A
8/30/2024
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
E
ARCHITECT/ENGINEER OF RECORD
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
CC
o n e e ig h th i n c h o n e f o o t th re e i n c h e s o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
Aw
F
D
Ac Ae
B
KEY PLAN
C
A u to d e s k D o c s
/2
-1
A -2
-3
V
A P o p la r
B lu ff
R e m o v e a n d
R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.A rc h R
-1
-R e p l L a b A
H U
A
H U
.r v t
/9
/2
:0
:2
P M
ACD100
GROUND FLOOR - CEILING DEMO
PLAN
REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATION, AND
AIR CONDITIONING
JOHN J. PERSHING VETERANS' ADMINISTRATION MEDICAL
CENTER 1500 N. WESTWOOD BLVD.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .