S02 - 607-19-107 Drawings VOL1.pdf
PDF 15 MB Posted
- Attached to
- Y1DZ--Replace Electrical-Building 19 607-19-107 Federal contract opportunity
- Solicitation number
- 36C25220B0026
About this file
This document provides details on a federal contract opportunity to replace electrical systems in Building 19 at the William S. Middleton Memorial Veterans Hospital in Madison, Wisconsin. The solicitation seeks bids to furnish all labor, materials, equipment and supervision to complete Project 607-19-107, which involves constructing approximately 1,089 square feet of new space adjacent to the main hospital building. The scope of work includes general construction, site work, underground utilities, electrical, structural, mechanical and fire protection systems, as well as all necessary architectural, equipment and distribution systems. Interested vendors must be a verified Service-Disabled Veteran-Owned Small Business. The solicitation will be issued on or around August 19th, 2020, with bids due by September 18th. The project value is estimated between $2-5 million. Upon award, the contractor must complete the work within 425 calendar days of receiving notice to proceed.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S06 - SF 1442 - Revised 10-7-20.pdf | ||
| 36C25220B0026 0005.docx | DOCX document | |
| 36C25220B0026 0004.docx | DOCX document | |
| S06 - Spec Section 23 81 00.pdf | ||
| 36C25220B0026 0003.docx | DOCX document | |
| S06 - SF 1442 - Revised.pdf | ||
| 36C25220B0026 0002.docx | DOCX document | |
| S06 - Electrical Power Dist Sys - Reference Drawing Only.pdf | ||
| S06 - Wage Determination.pdf | ||
| S06 - Pre-Bid Attendance List.pdf | ||
| S06 - ES100 rev 1.pdf | ||
| S06 - SF 1442.pdf | ||
| S06 - Bid Schedule.pdf | ||
| S06 - 19244 VA Hospital Building 18 - Geotech.pdf | ||
| 36C25220B0026 0001.docx | DOCX document | |
| S06 - CE100 Rev 1.pdf | ||
| S02 - 607-19-107 Drawings VOL 2A.pdf | ||
| S02 - 607-19-107 Drawings VOL 2C.pdf | ||
| S02 - Specifications Volume 1.pdf | ||
| 36C25220B0026_1.docx | DOCX document | |
| P07 - Wage Determination.pdf | ||
| S02 - Specifications Volume 2.pdf | ||
| S02 - 607-19-107 Drawings VOL 2B.pdf |
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PARKING RAMP
BLDG #15
'D' WING
C
H
I
L
L
E
R
P
L
A
N
T
BLDG #19
C
W
I
G
A
N
G
B
SWITCHGEAR
LAUNDRY
EMER. GENERATOR
WELL
PUMPHOUSE
MENTAL
HEALTH
CLINIC
ENTRANCE
MAIN
/LOBBY
BLDG #7
BLDG #12
BLDG #1
BLDG #2
BLDG #13
BLDG #3
BLDG #5
B
L
D
ELEC.
ENTRANCE
OLD MAIN
BLDG #22
M
R
I
COMMUNITY LIVING CENTER
HOSPICE
MENTAL HEALTH
EMERGENCY
UNIVERSITY OF
WISCONSIN
HOSPITAL
C
O
N
N
E
C
T
I
O
R
R
I
D
R
BLDG #27
BLDG #17
B
L
BLDG #14
L
SERVICE ENCLOSURE
C
O
N
T
R
A
C
T
R
P
R
K
I N
G
CONNECTING CORRIDOR
BLDG 21
ROOFTOP UNIT
'G' WING
BLDG #1
L
E
X
I
S
T
I
L
L
N
G
B
A
S
E
M
E
N
T
SITE PLAN
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i l e a t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
B
B
C
A
G
Consultants
NFPA CHAPTER 40.1.2.1.2
IBC CHAPTER 3
SPECIAL-PURPOSE INDUSTRIAL OCCUPANCY.
CLASS S-1, MODERATE HAZARD STORAGE
IBC SECTION 716
NFPA 101 TABLE 8.3.3.2.2
IBC CHAPTER 6
NFPA 101 TYPE 2 (222)
For features that are addressed by both the IBC as well as by NFPA 101 the requirements of NFPA 101 shall be used exclusively. Contractor to notify COR and adjust for any differences encountered in material type or construction.
TYPES OF CONSTRUCTION
SECTION 602 CONSTRUCTION CLASSIFICATION CONSTRUCTION TYPE TYPES: l-A OR l-B, ll-A OR ll-B, lll-A OR lll-B, lV, V-A OR V-B TYPE l-B
TABLE 601
FIRE RESISTANCE RATING REQUIREMENTS
FOR BUILDING ELEMENTS
PRIMARY STRUCTURAL FRAME
BEARING WALLS
EXTERIOR
INTERIOR
NON BEARING WALLS AND PARTITIONS
INTERIOR
FLOOR CONSTRUCTION
ROOF CONSTRUCTION
2(a) HOURS
2 HOUR
2(a) HOUR
0 HOUR
2 HOUR
1 (b,c) HOUR
TABLE 602
FIRE RESISTANCE RATING REQUIREMENTS
FOR EXTERIOR WALLS BASED ON FIRE
SEPARATION DISTANCE
FIRE SEPARATION DISTANCE, LESS THAN 5'-0" = 2 HRS
FIRE SEPARATION DISTANCE, GREATER THAN 5'-0" BUT LESS THAN 10'-0" = 1 HRS
FIRE SEPARATION DISTANCE, GREATER THAN 10'-0" BUT LESS THAN 30'-0" = 0 HRS
FIRE SEPARATION DISTANCE, GREATER THAN 30'-0" = 0 HRS
CODE REQUIREMENT NORTH WALL = 0 HOUR
CODE REQUIREMENT SOUTH WALL = 2 HOUR
CODE REQUIREMENT EAST WALL = 0 HOUR
CODE REQUIREMENT WEST WALL = 0 HOUR
NORTH WALL = 0 HOURS, DISTANCE IS GREATER THAN 30'-0", 2 HOURS PROVIDED
SOUTH WALL = 2 HOURS, DISTANCE IS LESS THAN 5'-0", 2 HOURS PROVIDED
EAST WALL = 0 HOUR, DISTANCE IS GREATER THAN 30'-0", 2 HOURS PROVIDED
WEST WALL = 2 HOURS, DISTANCE IS LESS THAN 5'-0", 2 HOURS PROVIDED
FIRE AND SMOKE PROTECTION
TABLE 705.8
EXTERIOR WALLS/
MAX. AREA OF EXTERIOR WALL OPENING
BASED ON FIRE SEPARATION DISTANCE
AND DEGREE OF OPENING PROTECTION
FIRE SEPARATION DISTANCE
UNPROTECTED
PROTECTED
0-3FT 3-5FT 5-10FT 10-15FT 15-20FT 20-25FT 25-30FT GREATER THAN 30'
N.P. N.P. 10% 15% 25% 45% 70% NO LIMIT
N.P. 15% 25% 45% 75% NO LIMIT NO LIMIT NOT REQUIRED
NORTH WALL = NO OPENING PROVIDED EAST WALL = ONE OPENING PROVIDED - FIRE RATED EXIT DOOR
SOUTH WALL = NO OPENINGS PROVIDED WEST WALL = ONE OPENING PROVIDED- FIRE RATED EXIT DOOR LESS THAN 15% OF WALL AREA
2(a) HOURS - 2 HOURS PROVIDED AT COLUMNS THAT SUPPORT THE FLOOR, 1 HOUR AT THE COLUMNS THAT SUPPORT THE ROOF
NOT APPLICABLE
0 HOUR
1 HOUR
CHAPTER 7
NOT APPLICABLE
2 HOUR
CHAPTER / NUMBER
CODE SECTION
USE AND OCCUPANCY CLASSIFICATION
BUILDING CODE REQUIREMENT ACTUAL PROVIDED
SECTION 311 STORAGE GROUPS, MODERATE HAZARD STORAGE UNITS CLASSIFICATION S-1
ISSUE
CHAPTER 5 GENERAL BUILDING HEIGHTS AND AREAS
TABLE 504.4 ALLOWABLE HEIGHT AND AREAS HEIGHT AND STORY LIMITATIONS BASED ON CONSTRUCTION TYPE:
l-B AND OCCUPANCY S-1
MAXIMUM HEIGHT 160'-0" - MAXIMUM NUMBER OF STORIES 11 MAXIMUM HEIGHT 26'-10"
TABLE 506.2 ALLOWABLE HEIGHT AND AREAS AREA LIMITATIONS BASED ON CONSTRUCTION TYPE:
l-B, NON SPRINKLERED AND OCCUPANCY S-1
MAXIMUM FLOOR AREA = 26,000 SF
TOTAL BUILDING AREA 1,050 SF
SECTION 714
SECTION 714
PENETRATIONS
714.3.1 THROUGH PENETRATIONS, 714.3.1.1 FIRE RESISTENCE RATED ASSEMBLIES PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN APPROVED FIRE RESISTANCE-RATED ASSEMBLY PENETRATING ITEMS WILL BE FIRESTOPED PER SECTION 714.3.1.2, THROUGH WALL PENETRATIONS SHALL
COMPLY WITH SECTIONS, 714.3.1.1 AND 714.3.1.2
PENETRATIONS
713.4.1.3 DUCTS AND TRANSFER OPENINGS PENETRATIONS OF HORIZONTAL ASSEMBLIES BY DUCTS AND AIR TRANSFER OPENINGS
SHALL COMPLY WITH SECTION 716.6.3(1)
NOT MORE THAN 2 STORY CONSTRUCTION, THE ANNULAR SPACE AROUND THE PENETRATING DUCT IS PROTECTED BY AN APPROVED NONCOMBUSTIBLE MATERIAL THAT RESISTS THE FREE PASSAGE OF FLAME AND THE PRODUCTS OF COMBUSTION.
OPENING PROTECTIVES 716.5 FIRE DOOR AND FIRE SHUTTER FIRE PROTECTION RATINGS
EXTERIOR WALL ASSEMBLY OF 2 HOURS, DOOR RATING 1 1/2 HOURS RATED DOORS WILL BE PROVIDED PER TABLE 716.5
FIRE PROOFING MATRIX
COLUMNS - SUPPORTING FLOOR / TUBE 2 HR UL X650 INTUMESCENT / 0.164"
BEAMS - SUPPORTING FLOOR / WF 2 HR UL N614 INTUMESCENT / 0.115"
FOR DIAGONAL BRACING BELOW SUPPORTED FLOOR 2 HR UL X649 INTUMESCENT / SEE MANUFACTURES TABLES FOR THICKNESS
FLOOR - CONCRETE ON MTL. DECK 2 HR UL D 902
COLUMNS - SUPPORTING ROOF / WF 1 HR UL X760 GYPSUM WET MIX / 11/16"
BEAMS - SUPPORTING ROOF / WF 1 HR UL S761 GYPSUM WET MIX / 3/8"
ROOF DECK 1 HR UL P723 GYPSUM WET MIX / 7/8"
EXTERIOR WALL ASSEMBLY 2 HR UL U425 N/A
BUILDING COMPONENT/ SHAPE REQUIRED FIRE RATING UL TEST/ASSEMBLY FIRE PROOFING TYPE / REQUIRED THICKNESS
SYMBOL LEGEND
CODE CRITERIA
7A
F
REVIEWING AGENCIES:
APPLICABLE CODES:
EXX
XXXX
X
XXXX
X
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
EXISTING WALL OF "C" WING
BUILDING 1
EXISTING WALL OF "G" WING-
BUILDING 13
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
B
B
C
A
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
B
B
C
A
G
CONSTRUCTION - SITE PLAN
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
WALKWAY CONCRETE
DN
UP
PARKING
AREA
ROOF
LOADING AREA
EXITSTING
SOIL AND GRAVEL
PROPOSED BUILDING
BUILDING 13 ROOF
HOSPITAL "C"
WING
HOSPITAL "B"
WING
EXISTING CONDENSER
RELOCATED EXISTING
CONDENSER
EXISTING LOADING DOCK
ENCLOSURE
EXISTING
UPS ENCLOSURE
NEW UPS
ENCLOSURE
GAS LINES
NEW CONCRETE PAD AS REQUIRED
GRADE LEVEL KEY NOTES
SYMBOL DESCRIPTION
1 EXISTING HANDRAILING - TO BE MAINTAINED, PROTECT DURING CONSTRUCTION
2 EXISTING GAS LINE, VALVES AND CONDUITS TO BE MAINTAINED, PROTECT DURING CONSTRUCTION
A2001
A200
TRANSFORMERS
AREAWAY
BUILDING 21
UPS ENCLOSURE
EXISTING CONCRETE
EXISTING ASPHALT
"C"
WING
NEW
UPS ENCLOSURE
VAULT
MANHOLES
A300
A200
A200 2
A300
3 4
4 5 7
A
B
C
E
STEEL TUBE COLUMN ON CONCRETE CAISONS
TO SUPPORT ELEVATED FLOOR SLAB, TYP.
LINE OF BUILDING ABOVE
BRICK AND CMU INFILL OF WINDOWS IN THESE LOCATIONS
WINDOW INFILL NOTE:
PROVIDE GYPSUM BOARD AT INTERIOR
FEATHER WALL PATCH TO EXISTING ADJACENT WALL FINISH,
PAINT TO MATCH EXISTING WALL FINISH, TYP.
LEADER FROM ABOVE
NEW CONCRETE PAD COORD. SEE
STRUCTURAL DRAWINGS FOR
REQUIREMENTS
EXISTING
CONDENSER
D
RAILING1
RAILING1
RAILING1
9'-0"
LINE OF
BUILDING
ABOVE
'-0
'-0
SOIL AND GRAVEL
4'-6" x 5'-0" CONCRETE PAD, 5" HIGH
TYPICAL
NEW CONCRETE PAD FOR
RELOCATED CONDENSER
2 GAS LINE
9' - 0"
CONTROL JT. TYP.
STEEL TUBE COLUMN SUPPORTED ON
CONCRETE GRADE BEAM
AND CAISSONS
4' - 6"4' - 6"
SEE DETAIL S-503
FOR TYPICAL STAIR
POST SUPPORT
RELOCATED
CONDENSER
17' - 6"
6'
3"
STAIR LANDING ABOVE
1 VIEW LOOKING SOUTHWEST
1/8" = 1'-0"2 SITE PLAN
A101
SITE AND GROUND
FLOOR PLAN
1/4" = 1'-0"3 GRADE LEVEL - PARKING LOT
NOTE: NOT ALL STRUCTURAL COMPONENTS ARE SHOWN FOR CLARITY PUPOSES. COORDINATE DETAILS WITH STRUCTURAL DRAWINGS
GCDS
Location
Issue Date
B B
C
N
KEY PLAN Not to Scale
A
G
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
100% CONSTRUCTION
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
POC: Aslam Husain
607-19-107
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
REPLACE ELECTRICAL BUILDING 18
Project Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
William S. Middleton, Madison, WI
Building Number
Project Director
Revisions: Date: 11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
DN
EXTERIOR WALL OF
BUILING 13
EXTERIOR WALL OF "C" WING
A2001
A200
REMOVABLE RAILING
FOR EQUIPMENT ACCESS
FOR EQUIPMENT LAYOUT SEE ELECTRICAL DRAWINGS
A300
A200
A200 2
A3002
4 5 7
A
B
C
E
D
5'- 4"
9'-0"5'-11"
'-0
'-0
8 1 /2"
OVERALL EXTERIOR
35'-6 3/4"
2'-
5"
+-4'-6 1/2".
A501
STAIR NO.2
STAIR NO.1
A501
A400
1'-3 3/8"
1'- 4 1
/4"
9 1 /2"
1/2" T. GYP.BD. BD. WRAPS COL'S. FULL HT., TYPICAL
1'- 4 1
/4" 1'-
4 1 /4"
7 3 /8"
7 3 /8"
6 1/2" 6 1/2"
10' - 5" 5' - 1"6' - 1" 11' - 5" O
VE
R
AL
L
E X
TE
R
IO
R
/2
A5014
STRUCTURAL BRACING,
TYPCAL, REFER TO
STRUCTURAL DRWG'S.
FOR MOR DETAIL
PROVIDE FULL HT. GYP. BD. AT BRACING
FROM COLUMN TO COLUMN
NOTE:
PROVIDE BLOCKING AND PLYWOOD OR
SHEET METAL BACKING FOR WALL
MOUNTED PANELS. COORDINATE
LOCATIONS WITH ELECTRICAL
EQUIPMENT LAYOUT.
A2001
A200
A300
A200
A200 2
A300
4 5
A
B
C
E
H.P. ROOF H.P. ROOF
SLOPE DOWN @ 1/4" / FOOT SLOPE DOWN @ 1/4" / FOOT
L.P. ROOF
L.P. ROOF
CONTINUOUS GUTTER
LEADER BELOW
D
PREFINISHED FORMED METAL COPING, TYP.
A500
35'-6 3/4"
'-8
1/ 2"
A500
A500
A500
4'
6"
2' - 0"
EXHAUST FAN ON 18"H.
ROOF CURB
1'
5"
SEE MECH. DRWG'S.
3'
0"
CONTINUOUS ROOF WALKWAY PROTECTION
ROOF ACCESS LADDER
1/4" = 1'-0"1 BLDG 18 FLOOR PLAN
1/4" = 1'-0"2 BLDG 18 ROOF STEEL
FLOOR AND ROOF PLANS
A102
NOTE: NOT ALL STRUCTURAL COMPONENTS ARE SHOWN FOR CLARITY PUPOSES. COORDINATE DETAILS WITH STRUCTURAL DRAWINGS
12'-0"
'-0
FINISH SCHEDULE
ITEM TYPE FINISH/COLOR
EXTERIOR WALLS SHERWIN WILLIAMS H&C STAMPED CONCRETE / COLOR
TO MATCH EXISTING BLDG 21
COORD WITH VA
SEE SCHEDULE
1/
2" 8'
-0
/2
5"
1/ 2"
8' -0
/2
5"
12'-6"
'-6
3"
4"
3"
3"
6'-0"
3' -9
/2
DOOR SCHEDULE
NUMBER WIDTH HEIGHT THICKNESS MATERIAL FINISH
DOOR TYPE.
HW-E3 6'-0" 7'-0" 1 3/4" 18 GA. HOLLOW PAINT TO
MATCH
SW7531
CANVAS TAN
FRAME TYPE.
MATERIAL FINISH
16 GA. PAINT TO
MATCH
SW7531
CANVAS TAN
HARDWARE SCHEDULE
INTERIOR WALLS SHERWIN WILLIAMS
ALL SURFACE ENAMEL
N/A
DOOR SHERWIN WILLIAMS
ALL SURFACE ENAMEL
COLOR TO MATCH EXISTING
SW7531 CANVAS TAN
HARDWARE TYPE. REMARKS
1.WALL PAINT SHALL PRODUCE A SMOOTH, NON-ABSORBANT SURFACE PER OBC 1210.2
ITEM MANUFACTURER MODEL MATERIAL QUANTITY REMARKS
CLOSER LCN 1
HANDLER YALE 8822 FL 304 S/S 1 MORTISE
HINGES MCKINNEY 41
2" x 41
2" 32D 3 PER DOOR
DRIP CAP NATIONAL ALUMINUM 1
LOCKET YALE 8822 FL 304 S/S 1
DEADBOLT YALE 8822 FL 304 S/S 1
SWEEP DOMINION 154AV ALT.1247.7.1 1
CORE MEDECO/ASSA 1 PER SPEC
ABLOY 087100
PANEL SIZE WEIGHT
ROOF 10'-6" x 12'-6" 7375 LBS
FLOOR 10'-0" x 12'-0" 6000 LBS
FRONT 12'-0" x 8'- 0 1/2" 2000 LBS
BACK 12'-0" x 8'- 0 1/2" 3625 LBS
RIGHT 9'-6" x 8'- 0 1/2" 2875LBS
LEFT 9'-6" x 8'- 0 1/2" 2875LBS
TOTAL 24750LBS
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
B
B
C
A
G
NEW UPS BUILDING PLANS AND
SECTIONS
B B
C
N
KEY PLAN Not to Scale
A
G
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
100% CONSTRUCTION
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
POC: Aslam Husain
607-19-107
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
REPLACE ELECTRICAL BUILDING 18
Project Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
William S. Middleton, Madison, WI
Building Number
Project Director
Revisions: Date: 11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
BLDG 18 - T. SLAB - EL. 916'-2"
11' - 8"
BLDG 18 ROOF STEEL
25' - 0"
PARKING LOT - EL 904'-0"
-0' - 6"
'-4
A300 ABCE
NEW UPS BUILDING ELCLOSURE
MATCHES ENCLOSURE OF EXISTING
UPS BUILDING
SEE A-103 FOR ADDITIONAL
INFORMATION
EXISTING UPS BUILDING 21
BUILDING 18 SUPPORT
COLUMN BEYOND
STEEL SUPPORT COLUMNS FOR
EXTERIOR STAIR, SEE STRUCTURAL
DETAILS S-503
LEADER FROM GUTTER ABOVE
DISCHARGES ON EXISTING PAVING
INTERIOR OF
BUILDING 13
NOTE: EXISTING WINDOW OPENINGS OPPOSITE
AND WITHIN 10'-0" OF NEW TRANSFORMERS TO BE INFILLED
WITH CMU. AND FACE BRICK. REMOVE EXISTING WINDOWS AND FRAMES
AND SEAL EXPOSED CMU. SECURE SINGLE WYTHE OF FACE BRICK WITH
MASONRY TIES TO CMU BACKUP. PROVIDE FLASHING UNDER FACE BRICK
AND UP FACE OF CMU 6" MIN. PROVIDE WEEPS.
D
EQ
EQ
EQ
6'-2" EQ EQ
1'-10 1/4"1'-10 1/4"
REMOVABLE
RAILING
1'
5/
8"
BASEMENT
-11' - 6"
BLDG 18 - T. SLAB - EL. 916'-2"
11' - 8"
BLDG 18 ROOF STEEL
25' - 0"
PARKING LOT - EL 904'-0"
-0' - 6"
TOP OF COPING
26' - 10"
A300
A B C E
BASEMENT LEVEL
OF "C" WING
CONTINUOUS GUTTER AT WALL
ALUMINUM COMPOSITE WALL PANELS, TYPICAL
PAINTED STEEL RAILING
D
AREA WAY
EQ EQ EQ
30'-8 1/2"
WALL LOUVER SEE MECHANICAL DRAWINGS
ROOF ACCESS LADDER
BUILDING 13
BASEMENT
-11' - 6"
BLDG 18 - T. SLAB - EL. 916'-2"
11' - 8"
BLDG 18 ROOF STEEL
25' - 0"
PARKING LOT - EL 904'-0"
-0' - 6"
TOP OF COPING
26' - 10"
A300
23457
EXTERIOR WALL
OF "C" WING
EXISTING BUILDING 21
SEE WINDOW INFILL NOTE DRAWING 1 THIS SHEET
LAB BUILDING 13
BEYOND
1'-9 3/8" 1'-9 3/8"10'-6 5/8" 10'-7 5/8" 10'-7 5/8"
35'-6 3/4"
1" PANEL JOINT,TYP.
1'-3 3/8" 1'-3 3/8"
SEE STRUCTURAL DETAILS S-105
FOR WALKWAY, RAILING AND
STAIR CONSTRUCTION
EXISTING STAIR
WIDE FLANGE BEAM, SEE
STRUCTURAL DRAWINGS FOR
MORE DETAIL
ROOF ACCESS LADDER
BLDG 18 - T. SLAB - EL. 916'-2"
11' - 8"
BLDG 18 ROOF STEEL
25' - 0"
PARKING LOT - EL 904'-0"
-0' - 6"
TOP OF COPING
26' - 10"
A300
2 3 4 5 7
CONTINUOUS GUTTER AT SOUTH WALL
COPING AT EAST, WEST AND NORTH WALLS
AREAWAY SEE PLANS
EXISTING EXTERIOR WALL
"C" WING
STEEL SUPPORT COLUMNS
6 9
LEADER DISCHARGE ON PAVEMENT
35'-6 3/4"
1'-9 3/8" 1'-9 3/8"
EQ EQ EQ 1" WIDE PANEL JOINT, TYPICAL
A500
SEE STRUCTURAL DETAILS S-503
ALUMINUM COMPOSITE WALL
PANELS, TYPICAL
1/4" = 1'-0"1 EAST ELEVATION
1/4" = 1'-0"2 WEST ELEVATION
1/4" = 1'-0"3 NORTH ELEVATION
1/4" = 1'-0"4 SOUTH ELEVATION
BUILDING ELEVATIONS
A200
B B
C
N
KEY PLAN Not to Scale
A
G
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
100% CONSTRUCTION
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
POC: Aslam Husain
607-19-107
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
REPLACE ELECTRICAL BUILDING 18
Project Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
William S. Middleton, Madison, WI
Building Number
Project Director
Revisions: Date: 11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
BLDG 18 - T. SLAB - EL. 916'-2"
11' - 8"
BLDG 18 ROOF STEEL
25' - 0"
PARKING LOT - EL 904'-0"
-0' - 6"
TOP OF COPING
26' - 10"
'-4
A300
4 5
1'-3 3/8" 16'-6" 16'-6" 1'-3 3/8"
1'
5/
8"
1'
2"
AREA WAY
BLDG 18 - T. SLAB - EL. 916'-2"
11' - 8"
BLDG 18 ROOF STEEL
25' - 0"
PARKING LOT - EL 904'-0"
-0' - 6"
TOP OF COPING
26' - 10"
A300
A B C E
BUILDING 13
EXISTING
UPS BUILDING
A400
TRANSFORMER
D
'-4
1'-4 1/4"
14'-0" 14'-0"
1'-4 1/4"
PREFINISHED METAL COPING BEYOND
ALUMINUM COMPOSITE CLADDING
EXTENDS PAST SLAB EDGE
AND HORIZONTALLY TO
STRUCTURE ON COL. LINE D
ALUMINUM COMPOSITE CLADDING
EXTENDS PAST SLAB EDGE,
WRAPS STRUCTURE AND
RETURNS UP TO METAL DECK
SEE STRUCTURAL DRAWINGS FOR
MORE INFORMATION ON CASSONS AND GRADE BEAM
LEADER FROM GUTTER ABOVE
3/8" = 1'-0"1 SECTION LOOKING NORTH
3/8" = 1'-0"2 SECTION LOOKING EAST
BUILDING SECTIONS
A300
NOTE: NOT ALL STRUCTURAL COMPONENTS ARE SHOWN FOR CLARITY PUPOSES. COORDINATE DETAILS WITH STRUCTURAL DRAWINGS
B B
C
N
KEY PLAN Not to Scale
A
G
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
100% CONSTRUCTION
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
POC: Aslam Husain
607-19-107
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
REPLACE ELECTRICAL BUILDING 18
Project Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
William S. Middleton, Madison, WI
Building Number
Project Director
Revisions: Date: 11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
BLDG 18 - T. SLAB - EL. 916'-2"
11' - 8"
TOP OF COPING
26' - 10"
A
FOR FLOOR FRAMING, SEE STRUCTURAL DRAWINGS
FOR MORE DETAIL
3, 1/2" T. LAYERS OF TYPE X GYPSUM BOARD
PREFINISHED
METAL COPING
INSULATION ON METAL DECK SLOPE 1/4" /
FOOT, MINIMUM THICKNESS 5" AT LOW POINT
OF ROOF
STEEL WALKWAY AND
STAIR AND RAILING ASSEMBLY BEYOND, SEE PLANS FOR
ADDITIONAL INFORMATION
6" METAL STUD
A400
A500
STUD FRAMING AT COLUMNS UP TO DECK
5/8" FIBERGLAS MAT GYPSUM SHEATHING
ALUMINUM COMPOSITE PANEL CLADDING SYSTEM
UL- U425 EXTERIOR WALL ASSEMBLY
VARIES, SEE PLAN
7 3/8"
SPRAY APPLIED FIRE PROOFING
ALUMINUM COMPOSITE PANELS WRAP PREIMETER STRUCTURE
A
1/2" GYPSUM BOARD RETURNS TO EXTERIOR WALL WHERE
BRACING DOES NOT OCCURE
3 5/8" METAL STUD
2 1 /4"
8 1 /8"
9 1/2"
SPRAY APPLIED FIREPROOFING
ALUMINUM COMPOSITE WALL
CLADDING SYSTEM +- 2 1/4"
EXTERIOR STEEL FRAMED WQALL
CONSTRUCTION
WHERE BRACING OCCURES CONTINUE GYPSUM BOARD TO
ADJACENT COLUMN
BLDG 18 - T. SLAB - EL. 916'-2"
11' - 8"
A
ALUMINUM COMPOSITE
MATERIAL
ALUMINUM COMPOSITE
SYSTEM EXTRUSIONS AND
CLIPS
WEATHER BARRIER
WEEP & BAFFLE
WEEP AND BAFFLE,
TYPICAL
OPEN STEEL GRATE FLOOR PANELS AND FRAMES
TYPICAL EXTERIOR WALL ASSEMBLY
BENT STEEL PLATE CLOSURE
W 14, TYPICAL
COMPOSITE ALUMINUM
CLOSURE
1" HORIZONTAL AND VERTICAL
REVEALS, TYPICAL
STUD FACE
7 3/8"
5/8" FIBERGLAS MAT GYPSUM
2 1/4"
INTUMESCENT FIREPROOFING
WALL PANELS AT THIS LOCATION EXTEND UP TO
ADJACENT PANEL WHEN
WALKWAY IS NOT PRESENT
SEE DET1 /S 105 FOR WALKWAY
SUPPORT FRAMING
FOR METAL WALL FRAMING INFORMATION SEE
S 105
ALUMINUM COMPOSITE PANEL EXTENDS TO
STEEL BEAM AT COLUMN LINE D
2'
2"
2"
3/4" = 1'-0" A3001 TYPICAL WALL SECTION
WALL SECTIONS AND
EXTERIOR DETAILS
A400
1 1/2" = 1'-0"2 GYPSUM BOARD AT COLUMN
1 1/2" = 1'-0"3 WALL BASE DETAIL
NOTE: NOT ALL STRUCTURAL COMPONENTS ARE SHOWN FOR CLARITY PUPOSES. COORDINATE DETAILS WITH STRUCTURAL DRAWINGS
B B
C
N
KEY PLAN Not to Scale
A
G
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
100% CONSTRUCTION
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
POC: Aslam Husain
607-19-107
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
REPLACE ELECTRICAL BUILDING 18
Project Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
William S. Middleton, Madison, WI
Building Number
Project Director
Revisions: Date: 11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
E
FLASHING
CONTINUOUS BEAD OF SEALANT
PREFINISHED GUTTER AND DOWNSPOUT BEYOND,
FABRICATE IN COMPLIANCE WITH SMACNA
GUIDELINES, DISCHARGE AT GRADE
ROOF MEMBRANE OVER
RIGID INSULATION
2 X 8 PRESSURE TREATED CONTINUOUS
BLOCKING AND NAILER
METAL ROOF EDGE TERMINATION
CONTINUOUS BEAD OF SEALANT
SEE STRUCTURAL DWGS
METAL PANEL SYSTEM
WATER RESISTENT BARRIER
2 1/4"
7 3/8"TYP. PIPE / FLUE
PENETRATION
LAP SEALANT
WATER CUT-OFF MASTIC
STAINLESS STEEL CLAMP RING
PRE-MOLDED PIPE
SEAL
ROOFING SYSTEM OVER RIGID
INSULATION
PRIMER AND SEAM ADHESIVE BOTH
SURFACES
METAL ROOF DECK - SEE STRUCT
DRAWINGS
TOP OF COPING
26' - 10"
A
REVEAL IN PANEL SYSTEM SEE
ELEVSTIONS FOR MORE
INFORMATION
ROOF MEMBRANE RUNS UP BACK OF PARAPET
AND OVER THE TOP OF PARAPET WALL
POLYISOCYANURATE, END JOINTS
STAGGERED, 5" OVERALL THICKNESS
90 MIL EPDM ROOF MEMBRANE
PREFINISHED METAL COPING
EXTRUSION AND FASTENERS AS
APPROVED BY ALUMINUM
COMPOSITE PANEL MANUFACTURER
5/8" GYPSUM FIBERGLASS SHEATHING5/8" GYPSUM FIBERGLASS
SHEATHING
WATER RESISTENT BARIER
6"
STUD FACE
7 3/8"
1 1/2" = 1'-0"1 ROOF EDGE AT GUTTER
1 1/2" = 1'-0"2 ROOF PENETRATION
1 1/2" = 1'-0"3 PARAPET DETAIL
A500GCDS
EXTERIOR DETAILS - ROOF
B B
C
N
KEY PLAN Not to Scale
A
G
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
100% CONSTRUCTION
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
POC: Aslam Husain
607-19-107
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
REPLACE ELECTRICAL BUILDING 18
Project Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
William S. Middleton, Madison, WI
Building Number
Project Director
Revisions: Date: 11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
DN
C
E D
A501
1'
0"
5/ 8"
1'
0"
A5014
17 TREADS @ 11" / 18 RISERS @ 6 25/32"
15'-7" 11" 1' - 0"
4 T
RE
AD
S
RI
SE
RS
/32
3'- 8"
SLOPED EXTENSION
HORIZONTAL EXTENSION
'-6
3/ 8"
4' - 2"
1'
3/
4"
1' - 2 3/4"
4'
2"
A
1'
0"
T
RE
AD
S
R
IS
ER
S
/16
9'- 2"
1'- 3 3
/4"
10 TREADS @ 11" / 11 RISERS @ 6 15/16"
9' - 2" 11"
HORIZONTAL EXTENSION
HORIZONTAL EXTENSION
SLOPED EXTENSION
3'
1/
2"
3' - 9 1/2"
1' - 8".
STEEL STAIR
PAINTED STEEL STRINGER
1" TYP
EQ
RI
SE
R
HE
IG
HT
SE
E
SE
CT
IO
N
METAL STAIRS-PIPE
RAILS
GUARDRAIL
PIPE
HANDRAIL
METAL STAIRS
PICKETS
PIPE RAILS
BOTTOM RAIL
DASHED LINED
REPRESENTS
PLANE OF TREAD
NOSING
SE
CT
IO
N
MI
N
1 1 /2"
STEEL BAR
GRATE TREADS
1/4
1 1/4"
3'- 6"
1 1/2".1 1/4".
1 5/8"
1'-0"
2'-5 3/8"
1/1/2".
EQ
EQ
EQ
EQ
EQ
EQ
EQ
1'-0"
3'- 0"
TREADS BEYOND
1/
4"
SUPPORT STRUCTURE
SEE S 103
A501
SLEEVES FOR RAILING SUPORTS
4"
1" 1"
POST OF FIXED RAILING
POST OF REMOVABLE RAILING
TOP OF WALKWAY- SEE STRUCTURAL DRAWINGS
FOR MORE DETAIL
1"
PIPE SLEEVE WELDED TO WALKWAY
THRU BOLTED CONNECTIONS
1/2" = 1'-0"1 A 501 STAIR NO. 1 ENLARGED PLAN
1/2" = 1'-0"2 A 501 STAIR NO. 2 ENLARGED PLAN
1 1/2" = 1'-0"3 A501 HANDRAIL SECTION AND ELEVATION DETAIL
1/2" = 1'-0"4 ELEVATION REMOVABLE RAILING
3" = 1'-0"5 DETAIL AT REMOVABLE RAILING
A501GCDS
STAIR DETAILED PLANS
AND DETAILS
B B
C
N
KEY PLAN Not to Scale
A
G
VA FORM 08 - 6231
A
Fi le
P at h 6/
/2
:3
9:
P M
100% CONSTRUCTION
DOCUMENTS
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
POC: Aslam Husain
607-19-107
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
REPLACE ELECTRICAL BUILDING 18
Project Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
William S. Middleton, Madison, WI
Building Number
Project Director
Revisions: Date: 11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
DOOR SCHEDULE
NUMBER WIDTH HEIGHT MATERIAL DOOR AND FRAME FINISH HDWR. RATING COMMENTS
01 72" 84" HOLLOW METAL / STEEL PAINT HW-E2 90 MIN
02 36" 84" HOLLOW METAL / STEEL PAINT HW-E1 90 MIN
DOUBLE RUNNERS SCREWED TOGETHER AT
12" O.C., MATCH STUD GAGE. SCREW TOP RUNNER TO JAMB STUDS
JAMB ANCHORS ABOVE EACH HINGE
REINFORCEMENT AND BELOW TOP HINGE
REINFORCEMENT
DOUBLE STUDS TYPICAL, 20 GAGE MIN.
FLOOR CLIPS WITH FASTENERS AS REQUIRED
ELEVATION
ISOMETRIC VIEW
METAL FRAMING AT DOOR OPENINGS
3 LAYERS, 1/2" TYPE X GYPSUM BOARD
5/8" FIBERGLASS MAT GYPSUM SHEATHING
6" STEEL STUDS
8 1/8"
ALUMINUM COMPOSITE PANEL SYSTEM
WATER RESISTANT BARRIER
2"
1" 1/2"
EDGE OF PANEL ALIGNS WITH REVEAL AND EDGE OF ADJACENT PANEL
F - FLUSH F -DBL FLUSH
DOOR TYPES
TYPE 1 SINGLE TYPE 2 DOUBLE
FRAME TYPES
3 LAYERS, 1/2" TYPE X GYPSUM BOARD
8 1 /8"
ALUMINUM COMPOSITE
PANEL SYSTEM
WATER RESISTANT
BARRIER
2"1/2
2"5/8"
6" STEEL STUD
FRAMING,
DOUBLE STUDS
AT JAMBS
SEALANT ALL AROUND FRAME, TYP.
HOLLOW METAL DOOR AND FRAME
EDGE OF PANEL ALIGNS WITH REVEAL AND EDGE OR PANEL ABOVE DOOR, TYPICAL
1/4" = 1'-0"2 METAL FRAMING AT DOOR OPENINGS
3" = 1'-0"3 A600 DOOR HEAD
3" = 1'-0"5 A600 DOOR JAMB
A600GCDS
DOOR SCHEDULE AND
DETAILS
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
STRUCTURAL- GENERAL NOTES
S000
DETAIL
S000
BREAK LINE
DOUBLE BREAK LINE
ELEVATION REFERENCE
SECTION REFERENCE
U.N.O. - UNLESS NOTED OTHERWISE
T/STEEL - TOP OF STEEL
T/CONCRETE - TOP OF CONCRETE
C/C - CENTER TO CENTER OR CENTER ON CENTER
N.S. - NEAR SIDE
F.S. - FAR SIDE
EXISTING WALL OF "C" WING
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
STRUCTURAL- SITE PLAN
E
W14x 61 FLOOR
BEAM-CONTINUOUS
W14x 61 FLOOR
BEAM-CONT
D
B
W x 6
FL
OO
R
BE
AM
-C
ON
T.
W x 9
FL
OO
R
BE
AM
-C
ON
T.
6" THICK
REINFORCED
CONCRETE SLAB
WITH 1 1/2" - C22
FLOOR DECK#4
REBAR 12" C/C
BOTH WAY- 1 1/2"
FROM TOP
FLOOR
DECK SPAN
L 3 1/2" x 3 1/2" X 3/8" -
T/STEEL EL.
915'-2"
L 3 1/2" x 3 1/2" X 3/8" -
T/STEEL EL.
915'-2"
L 3 1/2" x 3 1/2" X 3/8" -
T/STEEL EL.
915'-2"
W8x 24 PLATFORM
SUPPORT BEAM-2
PLS.
W8x 24 PLATFORM
SUPPORT BEAM
-2 PLS.
W8x 24 PLATFORM
SUPPORT BEAM
W8x 24 PLATFORM
SUPPORT BEAM-4
PLS..
W8x 24 PLATFORM
SUPPORT BEAM- 4
PLS..
TRANSFORMERS
LIFTING
SUPPORT
PLAN - BELOW
C10X15.3 PLATFORM
SUPPORT BEAM-TYP.
BACKED WITH 3/8" X
2" BARING PLATE
W8x 24 PLATFORM
SUPPORT BEAM
C10X15.3 PLATFORM
SUPPORT BEAM-TYP.
BACKED WITH 3/8" X
2" BARING PLATE
W8x 24 PLATFORM
SUPPORT BEAM-2
PLS.
STAIR STRINGER NO
2. SEE 2 /A501
STAIR STRINGER NO
1. SEE 1 /A501
C10X15.3 PLATFORM
SUPPORT BEAM-TYP.
BACKED WITH 3/8" X
2" BARING PLATE
W
EL
DM
EN
T
W x 6
FL
OO
R
BE
AM
-C
ON
T.
W x 6
FL
OO
R
BE
AM
-C
ON
T.
W x 6
FL
OO
R
BE
AM
-C
ON
T.
W x 6
FL
OO
R
BE
AM
-C
ON
T.
W x 9
FL
OO
R
BE
AM
-C
ON
T. W x 6
FL
OO
R
BE
AM
-C
ON
T.
W x 6
FL
OO
R
BE
AM
-C
ON
T.
A
5 9
H.P. ROOF
EL 930'-1"
H.P. ROOF
SL
OP
E
DO
W N
1/
4"
FO
OT
SL
OP
E
DO
W N
1/
4"
FO
OT
W10X22 ROOF
BEAMS
SPACING,TYPICAL
W
X6
RO
OF
BE
AM
-C
ON
T.
W10 x 33 SUPPORT
COLUMN (TYP.)
C
E
W x
R
OO
F
BE
AM
W10X22 ROOF
BEAMS
SPACING,TYPICAL
L.P. ROOF
EL 929'-6"
L4X4X3/8"
ANGLES, TYP
1 1/2" ROOF B24-
DECK
ROOF DECK
SPAN
ROOF DECK
SPAN
ROOF DECK
SPAN
ROOF DECK
SPAN
ROOF DECK
SPAN
ROOF DECK
SPAN
1" C
AM
BE
R
W10 x 33 SUPPORT
COLUMN (TYP.)
W10 x 33 SUPPORT
COLUMN (TYP.)
W10 x 33 SUPPORT
COLUMN (TYP.)
FA
CE
O F
AR
CH
IT
EC
TU
RA
L W
AL
L
PA
NE
L
W x
R
OO
F
BE
AM
W x
R
OO
F
BE
AM
W x
R
OO
F
BE
AM
18 1/2" SQ
OPENING
FOR EF-1
W
X6
RO
OF
BE
AM
-C
ON
T.
W10 x 33 SUPPORT
COLUMN (TYP.)
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
STRUCTURAL- STEEL FLOOR &
ROOF PLANS
2 7 9
T/TRANSFORMER PAD
904'-0"
PARKING LOT
903'-0"
EXISTING EXTERIOR WALL
"C" WING
CONCRETE
ASPHALT
4 FT GRADE BEAM
STAIR - PIT
(BUILDING 1
BASEMENT )
892' - 6"
1500 kVA-
TRANSFORMERS-
SEE ELECTRICAL
10" THICK NEW
REINFORECED
CONCRETE
T/ CONCRETE EL.
903.6667' (HIGH)
Work Point
Work Point
Work PointWork PointWork Point
W14x 61 FLOOR
BEAM
T/TRANSFORMER PAD
903.75'
T/TRANSFORMER PAD
903.5'
W14x 61 FLOOR
BEAM
W14x 90 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
C10 X20 C10 X20 C10 X20 C10 X20
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 90 FLOOR
BEAM
AS NOTED IN THE SOIL REPORT- "BY CGC, INC." FULL
DEPTH CASING SHALL BE USED TO ADVANCE DRILLED
CAISSONS TO THE INTENDED DEPTH (TYP.)- SEE SPEC
31-63-26
W8x 31BRACE
W8x 31BRACE W8x 31BRACE
W8x 31BRACE
2 4 7
EXISTING EXTERIOR WALL
"C" WING
STAIR - PIT
(BUILDING 1
BASEMENT )
892' - 6"
T/SLAB
904'-0"
W14x 61 FLOOR
BEAM
Work Point
PARKING LOT
903'-0"
T/SITE- GRADE
CONCRETE
903.6667'
EXISTING CONCRETE STAIRS
TO BASEMENT "C" WING
CONCRETE ASPHALT
Work Point
Work PointWork PointWork Point
Work Point
W14x 90 FLOOR BEAM W14x 90 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
C10 X20 C10 X20 C10 X20 C10 X20
AS NOTED IN THE SOIL REPORT- "BY CGC, INC." FULL
DEPTH CASING SHALL BE USED TO ADVANCE DRILLED
CAISSONS TO THE INTENDED DEPTH (TYP.)- SEE SPEC
31-63-26
W8x 31BRACE W8x 31BRACE W8x 31BRACE
W8x 31BRACE
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
STRUCTURAL- ELEVATIONS
W10 x 33 SUPPORT
COLUMN
W21X62 ROOF BEAM
BEYOND- CONT.
W10 x 33 SUPPORT
COLUMN
W10 x 33 SUPPORT
COLUMN
W10 x 33 SUPPORT
COLUMN
W10 x 33 SUPPORT
COLUMN
W10 x 33 SUPPORT
COLUMN
Work Point Work Point
Work Point Work Point Work PointWork Point
Work PointWork Point
W21X62 ROOF BEAM
BEYOND- CONT.
2 5 9 259
STEEL WALL PANELS, TYPICAL - SEE
ARCHITECTURAL
W14x 61 FLOOR
BEAM
W14x 90 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 90 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
L3"X3"X3/8"CROSS BRACING
ANGLE
L3"X3"X3/8"CROSS BRACING
ANGLE
3/8" GUSSET PLATE
WITH 3/4"Ø BOLT-3/8" GUSSET PLATE
WITH 3/4"Ø BOLT-
W12 x 26 ROOF
SUPPORT BEAM
W12 x 26 ROOF
SUPPORT BEAM
C
STEEL WALL PANELS, TYPICAL - SEE
ARCHITECTURAL
W10 x 33 SUPPORT
COLUMN
W10 x 33 SUPPORT COLUMN W10 x 33 SUPPORT
COLUMN
W14X30 ROOF
SUPPORT BEAM
-BEYOND
W12 x 26 ROOF
SUPPORT BEAM
W12 x 26 ROOF
SUPPORT BEAM
W10 x 33 SUPPORT
COLUMN
W10 x 33 SUPPORT COLUMNW10 x 33 SUPPORT
COLUMN
W14X30 ROOF
SUPPORT
BEAM-BEYOND
L3"X3"X3/8"CROSS BRACING
ANGLE
Work Point Work Point
Work Point Work Point
Work Point
Work Point Work Point
Work Point
AE
CA E
L3"X3"X3/8"CROSS BRACING
ANGLE
3/8" GUSSET PLATE
WITH 3/4"Ø BOLT-
3/8" GUSSET PLATE
WITH 3/4"Ø BOLT-
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
STRUCTURAL- ELEVATIONS
W12 x 26 ROOF
SUPPORT BEAM
W12 x 26 ROOF
SUPPORT BEAM
5C5
W10 x 33 SUPPORT
COLUMN
W10 x 33 SUPPORT
COLUMN
W14X30 ROOF
SUPPORT BEAM
W21X62 ROOF BEAM-CONT.
CAMBER
W10X22 ROOF
BEAMS-BEYOND
AE
W10 x 33 SUPPORT
COLUMN
W10 x 33
SUPPORT
COLUMN
W21X62 ROOF BEAM
- CONT.
2 5 9
W12 x 26 ROOF
SUPPORT BEAM
W12 x 26 ROOF
SUPPORT BEAM
W14X30 ROOF
SUPPORT BEAM
W14X30 ROOF
SUPPORT BEAM
W24x 104 SUPPORT
BEAM
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
W14x 90 FLOOR
BEAM-CONT.
W24x 104 SUPPORT
BEAM
E
W14x 61 FLOOR
BEAM
HAND CHAIN HOIST
2- 6,600 lbs CAPACITY.
TWO-W8x 24 HOIST BEAM
SUPPORT
W14x 61 FLOOR
BEAM-BEYOND.
HSS, 6 X 6 X 3/8 SPREADER BEAM
T/ TRANSFORMER - RESTING
T/ TRANSFORMER - MAXIMUM LIFT
EL 904' TO 904.5'
T/ GRAD VARIES
T/ NEW CONCRETE- STEP TOWARDS
ASPHALT PARKING
SLIDE OUT WITH USE OF
DOLLIES/ROLLERS OR OTHER
AVAILABLE MEANS
ELECTRICAL CONDUIT
4" THICK ELECTRICAL PAD-
MATCH REQUIREMENTS FOR
SIZES OF EQUIPMENT
6" THICK CONCRETE SLAB
WITH 1 1/2" B22 FLOOR DECK
& #4 REBAR 12" C/C BOTH
WAY- 2" FROM TOP
T/ TRANSFORMER PAD EL VARIES
6" THICK CONCRETE SLAB
WITH 1 1/2" B22 FLOOR DECK
& #4 REBAR 12" C/C BOTH
WAY- 2" FROM TOP
T/ STEEL EL. 914'-6 1/8"
W14x 61 FLOOR
BEAM- TOP OF
FLANGE NOT SHOWN
FOR CLARITY
W14x 90 FLOOR
BEAM
STRUCTURAL SECTIONS
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
TYP.
TYP.
TYP.
TYP.
A
TYP.
TYP.
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
STRUCTURAL- WALL SECTIONS
E
TYP.
TYP.
TYP.
TYP.
TYP.
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
STRUCTURAL- WALL SECTIONS
Work Point
8 1/4 NTS
D
B
T/ STEEL EL. 914'-6 1/8"
(-32k)
W8x 31-BRACE
Work Point
12NTS
8 9/16
D
B
T/ STEEL EL. 914'-6 1/8"
W8x 31-BRACE
(-70k)
Work Point
DB
12NTS
8 9/16
W8x 31-BRACE
(+74k)
(+74k)
W8x 31-BRACE
W14x 90 FLOOR BEAM
Work Point
12 NTS
10 1/4
BB
W8x 31 BRACE
T/ STEEL EL. 914'-6 1/8" T/ STEEL EL. 914'-6 1/8"
T/ STEEL EL. 915'-8"
(-32k)
W8x 31-BRACE
12NTS
10 1/4
12 NTS
10 1/4
Work Point
DB
W8x 31-CROSS
BRACING BEAM
(+74k)
(-32k) (32k)
Work Point
8 1/4 NTS
DB
7 7
W8x 31-BRACE
W8x 31-BRACE
(+74k)
(+64k)
W14x 61 FLOOR
BEAM- RUNNING
NORTH AND SOUTH
W14x 61 FLOOR
BEAM CUT TO SUIT
AND COPED AT EACH
W14 X 61 NORTH
SOUTH FLOOR BEAM
E
D
E
W14x 61 FLOOR
BEAM
W14x 61 FLOOR
BEAM
STRUCTURAL DETAILS
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
C
1/4
NTS
Work Point
NTS
10 3/4
NTS
C
E
E
1/4
NTS
Work Point
10 3/4
NTS
Work Point
NTS
E
C
Work Point
C
Work Point
1/4
NTS
NTS
11 1/4
NTS
C
A
A
Work Point
1/4
NTS
Work Point
11 1/4
NTS
NTS
A
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
STRUCTURAL DETAILS
NTS
E
3 SIDES
E
E
Work Point
W21X62 ROOF BEAM
W21X62 ROOF BEAM
NTS
3/4"Ø A325 BOLTS - TYP. 3 SIDES (TYP.)
T/STEEL 929'-6"
Work Point
9 1/2
NTS
A
3 SIDES
A
A
Work Point
W21X62 ROOF BEAM
9 1/2
NTS
3 SIDES (TYP.) 3/4"Ø A325 BOLTS - TYP.
W21X62 ROOF BEAM
T/STEEL 930'-1"
E
1/4
NTS
3 SIDES (TYP.)
3 SIDES (TYP.)
A
1/4
NTS
A
1/4
NTS
E
1/4
NTS
3 SIDES (TYP.)
C
W21X62 ROOF BEAM
W14X30 ROOF
SUPPORT BEAM
W14X30 ROOF
SUPPORT BEAM
3 SIDES (TYP.)
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
(4)1"Ø HOLES FOR
7/8"Ø ANCHOR
BOLTS.
TYP.
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
MISCELLANEOUS STRUCTURAL
DETAILS
#6 DOWEL BARS #6 DOWEL BARS
1 3/8"Ø RODS
THREADED ON ENDS.
1 3/8"Ø RODS
THREADED ON ENDS.
ROUGHEN
SURFACE
#4 STIRRUPS
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
CAISSONS AND GRADE BEAM
1 3/8"Ø HEAVY HEX
NUT AND WASHER
4 SIDES
ROUGHEN
SURFACE
HILTI RE 500
EPOXY ADHESIVE
OR APPROVED
EQUAL
#6 DOWEL BAR
#3 TIE
#3 CROSS TIE
#6 DOWEL BAR
TYP.
#3 TIES
#3 CROSS TIE
3/4" @ 45°
CHAMFER
18" SQ BASE
PLATE
(4)1 7/16"Ø HOLES
FOR 1 3/8"°
THREADED RODS.
P 3/16" X 1" FULL
LENGTH OF BENT
PLATE
L
FILL GAP BETWEEN WELDS WITH
CAULK PRIOR TO FIRE PROOFING
AND PAINTING
TYP.
TYP.
3/4" @ 45°
CHAMFER
1 3/8"Ø RODS
THREADED ON
ENDS.
(4)1 7/16"Ø HOLES
FOR 1 3/8"Ø
THREADED RODS.
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
CONCRETE PEDESTAL, ANCHORS &
BASE PLATE STRUCTURAL DETAILS
TYP.
A
TYP.
W14 FLOOR BEAMS
W14x 61 FLOOR
BEAM-CONT.
W8x 24 PLATFORM
SUPPORT BEAM-TYP.
W
AL
L
PA
NE
L
L 3 1/2" x
3 1/2" X 3/8" - B/STEEL
EL. 915'-2"
W8x 24 PLATFORM
SUPPORT BEAM-TYP.
13/16"Ø HOLE
FOR 3/4" BOLT
- TYP.
P 3/8"L
W14x 90 FLOOR
L 3 1/2" x
3 1/2" X 3/8" - B/STEEL
EL. 915'-2"
L 3 1/2" x
3 1/2" X 3/8" - B/STEEL
EL. 915'-2"
13/16"Ø HOLE
FOR 3/4" BOLT
- TYP.
P 3/8"L
L 3 1/2" x
3 1/2" X 3/8" - T/STEEL
EL. 915'-2"
W14x 61 FLOOR
BEAM-CONT.
P 3/8"L
TYP.
13/16"Ø HOLE
FOR 3/4" BOLT
- TYP.L 3 1/2" x
3 1/2" X 3/8" - T/STEEL
EL. 915'-2" ANGLES
L 3 1/2" x
3 1/2" X 3/8" - B/STEEL
EL. 915'-2"
13/16"Ø HOLE
FOR 3/4" BOLT
L 3 X 3 X 1/4" DIAGONALLY ACROSS
L 3 X 3 X 1/4"
DIAGONALLY ACROSS
EL - 3 5/8"
TYP.
Project Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F i t h
P
M
100% CONSTRUCTION
DOCUMENTS
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
POC: Aslam Husain
William S. Middleton, Madison, WI
607-19-107 Building Number
Project Director
Revisions: Date:
9245 Calumet Ave. Suite 205, Phone: (219) 836-2120 Fax: (219) 836-1129 Munster, IN 46321
Electrical:
1232 Fourier Drive, Suite 101, Phone: 608.833.7000 Fax: 608.833.6996 Madison, Wisconsin 53717
11.4.19
100% CONSTRUCTION DOCUMENTS 11.4.2019
REPLACE ELECTRICAL BUILDING 18
| Sheets |
| A101 - SITE AND GROUND FLOOR PLAN |
| A102 - FLOOR AND ROOF PLANS |
| A200 - ELEVATIONS |
| A300 - BUILDING SECTIONS |
| A400 - WALL SECTIONS AND EXTERIOR DETAILS |
| A500 - EXTERIOR DETAILS - ROOF |
| A501 - STAIR DETAILED PLANS AND DETAILS |
| A600 - DOOR SCHEDULE AND DETAILS |
| G001 - CODE MATRIX |
| Sheets |
| A101 - SITE AND GROUND FLOOR PLAN |
| A102 - FLOOR AND ROOF PLANS |
| A200 - ELEVATIONS |
| A300 - BUILDING SECTIONS |
| A400 - WALL SECTIONS AND EXTERIOR DETAILS |
| A500 - EXTERIOR DETAILS - ROOF |
| A501 - STAIR DETAILED PLANS AND DETAILS |
| A600 - DOOR SCHEDULE AND DETAILS |
| G001 - CODE MATRIX |
| Sheets |
| A200 - ELEVATIONS |
| A300 - BUILDING SECTIONS |
| Sheets |
| A200 - ELEVATIONS |
| A300 - BUILDING SECTIONS |
| Sheets |
| A101 - SITE AND GROUND FLOOR PLAN |
| A102 - FLOOR AND ROOF PLANS |
| A200 - ELEVATIONS |
| A300 - BUILDING SECTIONS |
| A400 - WALL SECTIONS AND EXTERIOR DETAILS |
| A500 - EXTERIOR DETAILS - ROOF |
| A501 - STAIR DETAILED PLANS AND DETAILS |
| A600 - DOOR SCHEDULE AND DETAILS |
| G001 - CODE MATRIX |
| Sheets |
| A101 - SITE AND GROUND FLOOR PLAN |
| A102 - FLOOR AND ROOF PLANS |
| A200 - ELEVATIONS |
| A300 - BUILDING SECTIONS |
| A400 - WALL SECTIONS AND EXTERIOR DETAILS |
| A500 - EXTERIOR DETAILS - ROOF |
| A501 - STAIR DETAILED PLANS AND DETAILS |
| A600 - DOOR SCHEDULE AND DETAILS |
| G001 - CODE MATRIX |
| Sheets |
| A101 - SITE AND GROUND FLOOR PLAN |
| A102 - FLOOR AND ROOF PLANS |
| A200 - ELEVATIONS |
| A300 - BUILDING SECTIONS |
| A400 - WALL SECTIONS AND EXTERIOR DETAILS |
| A500 - EXTERIOR DETAILS - ROOF |
| A501 - STAIR DETAILED PLANS AND DETAILS |
| A600 - DOOR SCHEDULE AND DETAILS |
| G001 - CODE MATRIX |
| Sheets |
| A101 - SITE AND GROUND FLOOR PLAN |
| A102 - FLOOR AND ROOF PLANS |
| A200 - ELEVATIONS |
| A300 - BUILDING SECTIONS |
| A400 - WALL SECTIONS AND EXTERIOR DETAILS |
| A500 - EXTERIOR DETAILS - ROOF |
| A501 - STAIR DETAILED PLANS AND DETAILS |
| A600 - DOOR SCHEDULE AND DETAILS |
| G001 - CODE MATRIX |
File details come from the government source that posted it. Updated .