This document provides details on a federal solicitation for drydock repairs to the NOAA Ship RONALD H. BROWN. The solicitation number is 1305M222QNMAN0008 and was issued by the Department of Commerce National Oceanic and Atmospheric Administration. Interested parties are invited to submit quotes for drydock repairs including work on the ship's bow thruster and control systems. The response deadline is not specified but the repairs are intended to take place during fiscal year 2022. The document includes a technical file on the bow thruster and control systems to inform repair work to those areas of the vessel.
View the file
Other files
Show 40 more
Latest 50 of 81 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SECTION THREE PAGE 1
OPERATING AND
MAINTENANCE
INSTRUCTIONS
I
SECTION THREE
STEERING GEAR STARTER
AND CONTROL BOX,
WHEELHOUSE CONTROL
PANEL
HALTER MARINE INC, MOSS POINT SHIPYARD, MOSS POINT, MS
"AGOR" CLASS OCEANOGRAPHIC RESEARCH VESSELS
NUMBER NAME HULL NO. ELLIOTT UNIT SERIAL OPERA TOR
CONTRACT NO.
'AGOR24' 'ROGER REVELLE' M 250 CG12666 G653W SCRIPPS I.O.
'AGOR 25' 'ATLANTIS'
'AGOR NOAA' 'RESEARCHER'
PP 991C 88
LITHO IN USA
FR\772
M251 CG14734 G656W WOODSHOLE 0 .1.
M 252 CG14735 G657W N.O.A.A
r r
SECTION THREE PAGE 2
SECTION THREE - INDEX OF CONTENTS
STEERING GEAR STARTER AND CONTROL BOX,
WHEELHOUSE CONTROL PANEL
C 1 GENERAL TECHNICAL SPECIFICATION
C2 INSTALLATION OF EQUIPMENT
C3 SPECIFICATION OF COMPONENTS WITHIN STEERING GEAR STARTER AND
CONTROL BOX, WITH BASIC FAULT FINDING INSTRUCTION
C4 OPERATIONAL NOTES
C5
FR\772
PP991C88
LITHO IN USA
(i) Control Station Selection
(ii) Alarms
(iii) Thrust Direction Control
(iv) Thrust Magnitude Control
(v) Start Sequence At Bridge Control Panel
(vi) Thruster Ready For Service
(vii) Take Over On Service
(viii) Zero Thrust (Continuous Rotation) Facility
(ix) Stop Sequence At Bridge Control Panel
(x) Emergency Stop Sequence At Control Panels
(xi) Alignment Check
(xii) Heater On
(xiii) Control Power On
(xiv) Bridge Control Station Fault Location
SPARE PARTS IDENTIFICATION
SECTION THREE PAGE 3
SECTION THREE- INDEX OF CONTENTS (Contd.)
STEERING GEAR STARTER AND CONTROL BOX,
WHEELHOUSE CONTROL PANEL
C6 CIRCUIT DRAWINGS AND PANEL GENERAL ARRANGEMENT DRAWINGS:
FR\772
PP 991 C 88
LITHO IN USA
CABLE BLOCK DIAGRAM DRG. NO. HED 5766 ElOO
INTERCONNECTION DIAGRAM FOR CABLES DRG. NO. 5766 ElOl TO DRG NO.
HED 5766 EllO, HED 5766 El26 TO DRG NO. HED 5766 El33 (E128 DELETED)
WIRING DIAGRAM FOR STEERING MOTOR STARTER PANEL DRG. NO. HED
5766 Elll TO DRG. NO. HED 5766 El25
GENERAL ARRANGEMENT OF STEERING MOTOR STARTER AND CONTROL
PANEL DRG. NO. HED 5766 M201
GENERAL ARRANGEMENT FOR BRIDGE CONTROL STATION DRG. NO. HED
5766 M202
WIRING DIAGRAM FOR THRUST DIRECTION INDICATOR 4A0101353
THRUST DIRECTION INDICATOR 4A0101751
STORK KWANT CONTROL UNIT 'RSCU' 4A0102062
APPENDIX "A" ROCHESTER INSTRUMENTS ET7204(W)R
INSTRUCTION MANUAL
APPENDIX "B" ALLEN-BRADLEY SLC 500 CONTROLLER
INSTRUCTION MANUAL
APPENDIX "C" NEMIC-LAMBDA POWER SUPPLY UNIT
INSTRUCTION MANUAL
APPENDIX "D" FAIL-SAFE MGM-600 INSULATION MONITOR
DATA SHEET
SECTION THREE PAGE 4
Cl GENERAL TECHNICAL SPECIFICATION
FR\772
PP 991C 88
LITHO IN USA
The complete starting, control and alarm functions for the thruster, including the lubricating oil system, thruster alignment and thruster steering gear are provided from the steering gear starter and control box, mounted adjacent to the thruster and the main thruster drive motor controller.
This starter and control box (see drawing HED 5766 M201), with front opening lockable door, is complete with the following major components:
1) Steering motor start contactors - CLOCKWISE and COUNTERCLOCKWISE.
2) Lubricating oil pump start contactor.
3) Steering motor cooling fan motor start contactor.
4) 24 V DC power supply unit.
5) Steering motor thermistor trip amplifier.
6) Thruster rotor shaft bearing temperature thermocouple trip amplifier.
7) Steering gear motor insulation resistance monitor.
8) Multifunction control and alarm programmable controller.
9) Thrust direction indicator, independently driven from dedicated steering gear transmitter.
1 0) Thrust magnitude indicator, driven from mam drive motor speed generator/transmitter.
11) Controller for steering motor and control box anti-condensation heaters.
12) Supply fuses for all electrical supplies.
This starter and control box, with its door mounted indicators and pushbuttons, can act as LOCAL control for the thruster and its main drive motor. In addition, the starter and control box provides signals to and accepts signals from the Bridge Control panel and from the ships joystick system and future dynamic positioning system. For thruster magnitude and direction, from the Bridge Control panel, these signals are provided from a Sterk Kwant, type RSCU 360° control head fitted to the panel.
SECTION THREE PAGE 5
C2 INSTALLATION OF EQUIPMENT
FR\772
PP991C88
LITHO IN USA
Examine equipment for any damage that may have been sustained during delivery.
Immediately prior to commissioning of starter and control box and control panel, examine closely all terminal rails to ensure that all connections and cables are correct and are in accordance with wiring diagrams HED 5766 ElOO to E123 .
DO NOT ATTEMPT TO PUT POWER ONTO STARTER AND CONTROL BOX
OR STEERING GEAR MOTOR UNTIL ALL NATIONAL AND LOCAL
REGULATIONS REGARDING CONNECTION, INSULATION TESTING AND
GROUNDING OF ELECTRICAL EQUIPMENT HAVE BEEN COMPLIED WITH.
Before applying mains voltage to steering gear starter and control box, ensure that control box isolator switch 'I' is in OFF position.
SECTION THREE PAGE 6
C3 SPECIFICATION OF COMPONENTS WITHIN STEERING GEAR STARTER
AND CONTROL BOX, WITH BASIC FAULT FINDING INSTRUCTION
FR\772
PP 991C 88
LITHO IN USA
1) Steering Motor Start Contactor (2Oft)
2)
Items 14K5 And 14K6 Drg. HED 5766 E111 Line 13-21
MANUFACTURER
RATING
COIL
DESIGNATION
Telemecanique
3 pole 63A
24 VDC
LP 1-D6511 BD (Contactor) LA9-D4002 (Mechanical Interlock) LA9-D6569 (Reversing Power Connections) LA9-D701 (Power Terminal Shroud) LA 1-D22 (2 N/0 + 2 N/C Contact Block) LA4-DA20 (R.C. Suppressor)
Lubricating Oil Pump Start Contactor (1 Oft) Item 14K8 Drg. HED 5766 Elll Line 31
MANUFACTURER
RATING
COIL
DESIGNATION
Telemecanique
3 pole 9A
24 VDC
LP1-D091 OBD
(Contactor) LP4-DA20 (R.C. Suppressor)
3) Steering Motor Cooling Fan Start Contactor (1 Oft) Item 14K7 Drg. HED 5766 Ell1 Line 26
MANUFACTURER
RATING
COIL
DESIGNATION
T elemecanique
3 pole 9A
24 VDC
LP1-D0910BD
(Contactor) LP4-DA2U (R.C. Suppressor)
I
FR\772
PP 991 C 88
LITHO IN USA
SECTION THREE PAGE 7
NOTE:
CONTACTORCONTACTS
For 1), 2) and 3) above, contacts should be examined and cleaned periodically and renewed when contact faces have become badly worn or pitted.
FAULT LOCATION
For 1) above, if steering motor does not rotate in either direction, check following:
a) Examine fuses Fl , F2 and F3 .
b) Emergency stop pushbutton has been pressed at any location and requires resetting.
c) PLC unit is failing to provide output signal and shows an error fault.
Consult PLC manual in this section for fault finding.
For 1) above, if steering motor rotates in one direction only, check following:
a) Examine relevant coil of either contactor 13K5 or 13K6 for "open circuit".
For 2) above, iflubrication oil pump motor fails to start, check following:
a) Examine fuses F7, F8 and F9.
b) Lubricating pump motor has burnt out. Check motor windings insulation resistance.
c) PLC unit is failing to provide output signal and shows an error fault.
Consult PLC manual in this section for fault finding.
d) Examine coil 14K8 of this contactor for "open circuit" .
FR\772
PP 991C 88
LITHO IN USA
SECTION THREE PAGE 8
For 3) above, if steering motor cooling fan motor fails to start, check following:
a) Examine fuses F4, FS and F6.
b) Lubricating pump motor has burnt out. Check motor windings insulation resistance.
c) PLC unit is failing to provide output signal and shows an error fault.
Consult PLC manual in this section for fault finding .
d) Examine coil 14K7 ofthis contactor for "open circuit" .
4) Power Supply Unit ( 1 Oft) Drg. HED 5766 Ell2 Line 4
This unit provides smooth rectified supply to all 24 V DC functions within the steering gear starter and control box. Input power supply is from mcommg 480/3/60 mains voltage, via fitted open type supply transformer unit.
MANUFACTURER Coutant/N ernie-Lanbda
RATING 300 Watt
VOLTAGE Input 230/1/60 Output 24 V DC
DESIGNATION ESW300-24
NOTE:
1) Indication of satisfactory performance is provided by an "OUTPUT POWER ON" LED (Item 9) located on the front ofthe PSU.
2) If this indicator is extinguished, the supply fuse on the PSU and the supply fuses F I 0, F II, F 16 and F 17, within the steering gear starter and control box, need to be checked and possibly replaced.
FR\772
PP 991C 88
LITHO IN USA
SECTION THREE PAGE 9
3) The output voltage from this device is factory set at 24 V. This can be checked and if required adjusted via the voltage trimmer (Item 1 0) located on the front, just above the "OUTPUT POWER ON" LED.
4) For further details, see manufacturers technical data at end of this section.
5) Steering Motor Thermistor Trip Amplifier (1 oft) Drg. HED 5766 Ell2 Line 23
This unit provides, to the programmable controller, an alarm signal of overheat of the steering motor windings.
MANUFACTURER T elemecanique
RATING 120°C setpoint (2.6 KOHM)
VOLTAGE 24 VDC
DESIGNATION LT2-SCOOBD
NOTE:
1) This unit has been factory set and requires no adjustment.
2) Replace the complete unit if it is suspected to be faulty .
6) Thruster Rotor Shaft Bearing Temperature Thermocouple Trip Amplifier (1 oft) Drg. HED 5766 E 112 Line 3 I
This unit provides, to the programmable controller alarm signal of overheat of the thruster rotor shaft thrust bearing.
MANUFACTURER Rochester
RATING 70°C setpoint
VOLTAGE 24 VDC
INPUT 'K' type thermocouple
DESIGNATION ET7204(W)R
FR\772
PP 991C 88
LITHO IN USA
SECTION THREE PAGE 10
NOTE:
1) This unit has been factory set and should not require any adjustment. A faulty unit or removal of field wiring into the unit will activate THRUST
BEARING HIGH TEMPERATURE ALARM.
2) The temperature can be checked, when the power is on, by measuring the DC voltage across terminals 6 and 9. Full bandwidth is 0-5 VDC (0- 1000C). The setpoint should read 3.5 VDC (70°C).
3) Activation of the output relay is indicated by the illumination of a red
LED.
4) If the relay fails to activate when the setpoint is reached, refer to calibration instructions in the manufacturer's technical data at end of this section.
7) Steering Motor Insulation Resistance Monitor ( 1 Off) Drg. HED 5766 E 113 Line 18
MANUFACTURER Marine-Safe Electronics
RATING 3 Megohm Initial Setpoint
DESIGNATION MGM-600
NOTE:
1) This unit provides early warning of insulation breakdown on the windings ofthe steering motor.
2) Activation of the alarm output relay is indicated by the illumination of a red LED on the unit.
3) Ifthe relay fails to activate when the setpoint is reached, refer to test and reset instructions in the manufacturer's technical data at end of this section.
4) Unit has three setting levels 3, 1 and 0.5 Megohm. If alarm is still activating at 0.5 Megohm setting, steering motor must be inspected and/or rebuilt.
PP991C88
LITHO IN USA
SECTION THREE PAGE 11
8) Multifunction Control And Alarm Programmable Controller (I oft) Drg. HED 5766 El02 To EI13
This programmable controller unit, comprising a power supply, CPU (central processing unit) and multiple I/0 (input/output) modules, controls all aspects of the thruster control logic and alarm functions. This control and alarm logic has been prepared by Elliott Turbomachinery Limited and has been "burned in" on a 4K EEPROM (Electrically Erasable Programmable Read Only Memory) chip fitted to the central processing unit.
MANUFACTURER Allen-Bradley
DESIGNATION SLC500
The controller unit is installed in a 10 slot 1746-AIO rack unit, installed in the top of the steering motor starter and control box.
COMPONENT PARTS
FROM LEFT TO RIGHT
SLOTO
SLOT I, 4
SLOT 2, 3
SLOT 5
SLOT 6,7,8
SLOT 9
I x Link Coupler
I747-AIC
I x Power Supply Unit
24 VDC- 1747-P3
1 X SLC 5/01
C.P.U. with 4K Memory I747-L514, with 4K EEPROM 1747-M2 and Lithium Battery Pack
1747-BA
24 YDC Input Module I6 Points I746-I V16
24 VDC Output Module 16 Points 1746-0W16
24 VDC Output Module 8 points 1746-0W8
24 VDC Analogue Input Module l746-NI4
Analogue Output Module 1746-N04V
PP 991C 88
LITHO IN USA
SECTION THREE PAGE 12
NOTE:
1) This unit has been factory programmed and tested and should not require further adjustment.
2) Upon power being applied to the steering gear starter and control box, this programmable controller will start and self-test automatically. Upon completion of self-test, the "POWER" LED on the controller's power supply unit should be illuminated, together with the "PC RUN" LED on the CPU unit. No other LEDs on the CPU should be illuminated or flashing.
3) If any other LEOs are illuminated or flashing, please review the TROUBLESHOOTING section contained in the manufacturer's technical data at the end of this section.
IMPORTANT:
DURING THE POST DELIVERY WARRANTY PERIOD OF THIS
VESSEL, ANY FAULTS ON THIS PROGRAMMABLE CONTROLLER
MAY NORMALLY BE CURED BY THE REPLACEMENT OF SPECIFIC
MODULES OF THE CONTROLLER, AS DETAILED ON THE
MANUFACTURER'S TROUBLESHOOTING CHARTS.
ANY OTHER FAULTS, NOT CURED BY MODULE REPLACEMENT
AND REQUIRING THE AMENDMENT OF THE LOGIC PROGRAMME
WITHIN THE EEPROM, MUST BE IMMEDIATELY NOTIFIED TO
ELLIOTT TURBO MACHINERY SO THAT AN INVESTIGATION CAN
BE UNDERTAKEN AND THE EEPROM MODULE MODIFIED AS
NECESSARY.
r
FR\772
PP991C88
LITHO IN USA
SECTION THREE PAGE 13
UPON COMPLETION OF THE EQUIPMENT WARRANTY PERIOD, A
FULL PROGRAMME LISTING WILL BE PROVIDED TO THE VESSEL
OPERATOR TO ENABLE OPERATORS TO IDENTIFY CONTROL
PROGRAMME FAULTS.
9) Thrust Direction Indicator
This thrust direction indicator gauge is driven directly from a dedicated potentiometer fitted to the thruster steering gear. (For transmitter details, see
SECTION TWO).
MANUFACTURER Stork-Kwant
TYPE ASA.l
DIAL 360° 70 mm diameter
VOLTAGE 24 VDC
LIGHTING 24 VDC 2 W
NOTE:
1) This unit has been factory preset and should not reqmre further adjustment.
2) If indicator reading becomes erratic, check voltage outputs from dedicated potentiometer in conformance with chart shown on Sterk Kwant Drg. 4A0101353 .
3) If potentiometer voltage outputs are in accordance with chart, indicator gauge can be returned for repair or replacement of internal printed circuit boards and recalibration.
1 0) Thrust Magnitude Indicator
This thrust magnitude gauge is driven directly from the thruster main electric drive motor control cubicle.
MANUFACTURER Anders
TYPE DLM 96 With Special Scale
PP 991C 88
LITHO IN USA
SECTION THREE PAGE 14
11) Controllers For Steering Motor Anti-Condensation Heaters
MANUFACTURER RS Components
TYPE 340-358 5 A, 4 pole, 24 V DC coil
Controller For Starter And Control Box Anti-Condensation Heater
MANUFACTURER Rittal
TYPE Heater type SK3116 120 W, 240 V
Thermostat type SK3 112
12) Supply Fuses
All fuses are cartridge type, in removable holders.
HOLDER MANUFACTURER
FUSE TYPE/RATING
GEC type RS20H
GEC type NIT20 20A Fuse rating Fl, F2, F3
GEC type NIT 1 0 1 OA fuse rating FlO, F11
GEC type NIT 4 4A fuse rating F16, F17
GEC type NIT 2 2A fuse rating F4,F5 , F6,F7, F8 F9, F12, F13 , F14, F15
SECTION THREE PAGE 15
C4 OPERATIONAL NOTES
FR\772
PP 991C 88
LITHO IN USA
READ IN CONJUNCTION WITH DRG. HED 5766 E100 TO El23 AND HED 5766
M201 AND M202.
(i) CONTROL STATION SELECTION
1) With the control selector switch (Item 13) on the local steering gear starter and control box switched to position, 'OFF', control functions are not available.
2) With the control selector switch (Item 13) on the local steering gear starter and control box switched to position, 'LOCAL' control is available at this box only. This is confirmed by the illumination ofthe 'STARTER PANEL CONTROL' lamp (Item l 0) on this box and on the remote Bridge Control panel.
3) By switching the control selector switch (Item 1 0) on the steering gear starter and control box from 'LOCAL' to 'REMOTE', control is offered to the remote station. This is indicated to an operator at this station by the flashing of the 'TAKE OVER ON SERVICE' illuminated pushbutton (Item 9) on each of the panels. As long as this illuminated pushbutton continues to flash, control is maintained at the steering gear starter and control box.
4) To take control on this remote panel, the 'TAKE OVER ON SERVICE' illuminated pushbutton (Item 9) has to be pressed. This will then change the state of the illuminated pushbutton from flashing to that of steady illumination. The 'BRIDGE MASTER CONTROL' location light on all panels will be also illuminated.
5) Control can be taken back to the steering gear starter and control box at any time, simply by switching the selector switch (Item 13) from the 'REMOTE' position to the 'LOCAL' position.
6) To enable the ship's "JOYSTICK SYSTEM" to take control of the thruster, control mustbe at the Bridge control panel. Upon selection of the thruster by the JOYSTICK SYSTEM control panel, the appropriate control location light on all panels will be illuminated.
FR\772
PP991C88
LITHO IN USA
SECTIONTHREE PAGE 16
NOTE:
CONTROL CAN ONLY BE TAKEN AWAY TO THE REMOTE
BRIDGE CONTROL PANEL FROM THE SHIP'S JOYSTICK
SYSTEM BY SWITCHING OUT FROM THE JOYSTICK
SYSTEM CONTROL PANEL.
CONTROL CAN BE TAKEN BY THE LOCAL STEERING
MOTOR STARTER AND CONTROL BOX BY SWITCHING
CONTROL SELECTOR SWITCH (ITEM 17) TO "LOCAL".
(ii) ALARMS
1) Any alarms that occur will cause an audible and visual warning on both of the control stations. This is in the form of a horn for the audible alarm and a flashing lamp for the alarm. The appropriate alarm lamp will flash at both control stations, however, ifthe selector switch (Item 13) is in the 'LOCAL' position, the audible alarm will only sound at the steering gear starter and control box if the selector switch (Item 13) is in the 'LOCAL' position. If selector switch is in 'REMOTE' position, audible alarm will sound at the remote bridge station. Both the audible and visual alarms will continue until the alarm has been acknowledged by the operator.
2) Acknowledgement of the alarm can only be done at the station that has control, although the control position can be changed so as to accept control and acknowledge the alarm. It is achieved by pressing the 'ALARM ACCEPT' pushbutton (Item 8) which silences the audible alarm and changes the state of the visual alarm from flashing to that of steady illumination.
3) Action is now required to rectify the problem that has illuminated the visual alarm lamp(s). Once the problem has been discovered and rectified, the alarm system then needs to be reset to clear the visual warning(s) .
4) This can only be achieved at the steering gear starter and control box and only when it is in control. Thus, by switching the selector switch (Item
13) back to LOCAL and then by pressing the ALARM RESET pushbutton (Item 9), the alarm system will reset, extinguishing the visual alarm lamp(s) . However, they will not extinguish if fault prevails.
5) Shutdown of the thrust motor is incorporated if the thruster lubrication oil pressure drops to a level that causes the 'THRUST BEARING LOW LOW OIL PRESSURE' alarm (Item 4) to occur. The 'THRUST BEARING LOW OIL PRESSURE' alarm (Item 3) gives early warning of the problem.
PP991C88
LITHO IN USA
SECTION THREE PAGE 17
SPECIAL NOTE
If the LOW or the LOW LOW oil pressure alarms have been actuated, the procedure for resetting these alarms is as follows :-
Check that the fault has been cleared, then start the main drive motor (see section V). Once the start-up procedure has been completed then the alarm reset pushbutton (Item 9) can be pressed.
(iii) THRUST DIRECTION CONTROL
FR\772
1) On the remote Bridge Control panel, thrust directional signals are given to the bow thruster by an operator rotating the 360° control head to the direction in which the vessel's bow is required to move. An integral potentiometer on the control head gives a proportional signal equal to the required azimuth angle of the bow thruster. By comparing this signal with a signal generated by a discharge deflector positional feedback transmitter on the thruster steering shaft, the P.L.C. unit within the starter and control box releases the steering gear brake, and starts the steering gear motor, rotating the thruster discharge deflector, in the correct direction, to the required azimuth angle.
As the required discharge deflector azimuth setting is reached, the positional feedback transmitter output matches that output from the discharge deflector's control head setting. The P.L.C. unit senses this equalisation, stopping rotation of the steering gear motor and setting the motor brake to hold the discharge deflector in the required position.
Confirmation that the thrust direction demand has been followed is given through the illumination ofthe 'AZIMUTH IN LINE' light (Item 11).
2) On the local steering motor starter and control box, thrust direction control is achieved through the operation of the 'CLOCKWISE' and 'COUNTER-CLOCKWISE' rotation pushbuttons (Items 19 and 20).
These cause the deflector plate to turn in the required direction. The actual direction feedback is shown on the 'THRUST DIRECTION INDICATOR' (Item 14). Thus, the 'CLOCKWISE' or 'COUNTER CLOCKWISE' pushbuttons are held down until the 'THRUST DIRECTION INDICA TOR' indicates the direction in which the vessel's bow will move. These pushbuttons only operate when cubicle is in LOCAL control.
FR\772
PP991C88
LITHO IN USA
SECTION THREE PAGE 18
(iv) THRUST MAGNITUDE CONTROL
l) On the remote Bridge Control panel thrust magnitude (main drive motor rpm) is set by a speed setting level on the top of the control head. The speed setting range and equivalent percentages of maximum thrust are engraved on the top of the control head, with a pointer mounted off the control lever showing the set thrust magnitude position. The control lever directly drives a integral potentiometer on the control head which provides a speed setting signal to the main drive motor controller, via the P .L.C. unit within the starter control box.
THRUST MAGNITUDE %
100% 90% 75% 50% 25% 0%
MAIN DRIVE/MOTOR RPM
An actual speed output return from the main drive motor controller drives a thrust magnitude indicator/tachometer (Item l 0) on the control panel, showing that the main drive motor has responded to the set thrust magnitude/rpm position of the lever. The speed setting lever on the control head is limited in operation by an adjustable end stop.
2) On the local steering motor starter and control box, control is achieved through the operation of the 'INCREASE THRUST' and 'DECREASE THRUST' pushbuttons (Item 22 and 23). The actual speed feedback is shown on the 'THRUST MAGNITUDE INDICA TOR' (Item 18). Thus, the pushbuttons are held down until the required thrust magnitude setting is achieved on the 'THRUST MAGNITUDE INDICATOR'. these pushbuttons only operate when cubicle is in LOCAL control.
3) At the remote Bridge Control panel, any thrust magnitude demand signals attempted on the control head are ignored until a) the main drive motor has been started, and b) the 'THRUSTER READY FOR SERVICE' pushbutton (Item 13) has been pressed on the panel. Only after this has been done will the thruster main drive motor respond to thrust magnitude demand signals from the control head.
PP 991C 88
LITHO IN USA
SECTION THREE PAGE 19
(v) START SEQUENCE AT BOTH CONTROL LOCATIONS
1) First, control has to be taken at the required station. This has been outlined in part 1.
2) The operator should then check that no alarms are present on the control panel and any motor control panel. Thus, all alarm lamps and illuminated pushbuttons should be extinguished.
3) The 'STOP' illuminated pushbutton on the panel should currently be illuminated indicating the stopped status of the thruster.
4) The 'START' illuminated pushbutton on the panel can now be pressed, initiating the start sequence. This is confirmed to the operator by flashing of the 'START' illuminated pushbutton. It also extinguishes the 'STOP' illuminated pushbutton, indicating that the thruster is no longer in the stopped mode.
5) If no shutdown alarms occur and the thrust motor cabinet is ready, then the start sequence is completed. This is confirmed by the 'START' illuminated pushbutton changing state from flashing to that of steady illumination.
6) The 'THRUSTER READY FOR SERVICE' illuminated pushbutton (Item
14) on the panel then starts to flash informing the operator that the thruster is ready for operation. This can now be pressed giving the operator full control as outlined in part 6. By pressing the 'THRUSTER READY FOR SERVICE' illuminated pushbutton, the illumination becomes steady confirming the system's readiness.
7) Once selected, the 'THRUSTER READY FOR SERVICE' illuminated pushbutton should only be extinguished when a) the thruster is stopped either normally or in emergency or b) if the main drive motor has a fault and the ready signal is lost from the main drive also causing a shutdown.
FR\772
PP 991C 88
LITHO IN USA
SECTION THREE PAGE 20
(ix) STOP SEQUENCE AT BOTH LOCATIONS
1) The 'START' illuminated pushbutton on the panel should currently be illuminated indicating the running status of the thruster.
2) The 'STOP' illuminated pushbutton on the panel can then be pressed initiating a normal shutdown. This is confirmed by extinguishing the 'START' illuminated pushbutton and causing the 'STOP' illuminated pushbutton to start flashing. At the same time, the 'THRUSTER READY FOR SERVICE' illuminated pushbutton will also be extinguished.
3) Once the stop sequence has been completed, the 'STOP' illuminated pushbutton will cease to flash and will become steady.
(vii) EMERGENCY STOP SEQUENCE AT BOTH LOCATIONS
1) The 'EMERGENCY STOP' illuminated pushbutton (Item 33) can be pressed at any time in this location. Once pressed, it latches in and can they only be detached from that position.
2) Once an emergency stop has been initiated, it cannot be prevented.
3) Confirmation of an emergency stop as having been initiated is provided by the immediate illumination of the 'EMERGENCY STOP' illuminated pushbutton (Item 19).
4) In addition, the 'STOP' illuminated pushbutton (Item 20) is also illuminated in steady state, confirming the stopped status of the thruster.
OTHER CONTROL FUNCTIONS AT STEERING MOTOR STARTER AND
CONTROL CUBICLE
(viii) THRUSTER LUBRICATION PUMP SELECTION
1) Start of the thruster main drive will also start the electric motor driven thruster lubrication oil pump.
3) If pump fails or there is a loss of pressure in lub. oil circuit, loss of pressure will activate first stage lub. oil pressure alarm and subsequent second stage shutdown of main drive motor.
FR\772
PP 991C 88
LITHO IN USA
SECTION THREE PAGE 21
(ix) ZERO THRUST (CONTINUOUS ROTATION) FACILITY
(x)
1) This is selected and deselected by pressing the 'CONTINUOUS ROT A TION' illuminated pushbutton (Item 15). This can only be achieved once the THRUSTER READY FOR SERVICE illuminated pushbutton (Item 13) has been selected.
2) Upon selection of this option, the illuminated pushbutton has a steady illumination confirming the selection. This is extinguished when the function is deselected.
3) The CONTINUOUS ROTATION function is also deselected if the station that is in control is changed or ifthe main drive 'STOP' pushbutton (Item 19) is operated. In either case, CONTINUOUS ROTATION will have to be reselected.
4) The zero thrust facility is provided by rotating the deflector plate continuously in the anti-clockwise direction at 6 rpm.
ALIGNMENT CHECK
1) This illuminated pushbutton (Item 25 on the thruster steering gear starter and control box) is pressed and latched in to check the thrust alignment.
2) The deflector can then be turned by means of the pushbuttons until the illuminated pushbutton comes on. When this occurs, the thrust direction can be read from the 'THRUST DIRECTION' indicator. This reading should be zero degrees. For full details, refer to SECTION ONE, Initial Alignment.
(xi) HEATER ON
This lamp (Item 24 on the thruster steering gear starter and control box) simply provides visual confirmation that the heaters has been switched on by means of the heater selector switch (item 29).
(xii) CONTROL POWER ON
This lamp (Item 32) provides visual confirmation to the operator that control power is available.
FR\772
PP 991C 88
LITHO IN USA
SECTION THREE PAGE 22
(xiii) REMOTE BRIDGE CONTROL PANEL FAULT LOCATION
1) SYMPTOM
FAULT
2) SYMPTOM
FAULT
Some or all of the lights and pushbuttons are not operating on this remote panel.
Check the plug and socket arrangement located under the appropriate panel to see that it has not become loose or fallen out.
None of the pushbuttons, except TAKE OVER ON SERVICE, operate when the panel is in control.
Relay 5K4, within the steering gear starter and control box, should be checked for satisfactory operation. If faulty, replace.
SECTION THREE PAGE 23
C5 SPARE PARTS IDENTIFICATION
FR\772
PP 991C 88
LITHO IN USA
For precise identification of spare parts requirements, please refer to the following relevant Function and Wiring Diagrams enclosed in Section C6.
ORDERING OF SPARE PARTS
Comprehensive constructional records are held of each control box and panel supplied.
Please quote thruster unit's serial number and type in all correspondence and, when ordering spare parts, please quote:
Serial Number Function Or Wiring Drawing Number Code Or Item Number Or Drawing Line Number Description Ofltem Including Any Markings Shown On Item, Dimensions And Materials
Quantity Required
DEVELOPMENT
Due to manufacturer's policy of continuous research and development, the Specification, Part Numbers, Drawings, Materials and Manufacturers may be liable to alteration without notice.
ELLIOTT TURBOMACHINER Y LIMITED,
120 Thornycroft Industrial Estate, Worting Road, Basingstoke, Hampshire, RG21 lSD, ENGLAND.
Telephone No.
Telefax No.
Telex No.
(44) 1256 54334
(44) 1256 22464 858565
SECTION THREE PAGE 24
C6 CIRCUIT DRAWINGS AND PANEL GENERAL ARRANGEMENT DRAWINGS:
FR\772
PP 991C 88
LITHO IN USA
CABLE BLOCK DIAGRAM DRG. NO. HED 5766 ElOO
INTERCONNECTION DIAGRAM FOR CABLES DRG. NO. 5766 ElOl TO DRG NO. HED 5766 EllO, HED 5766 E126 TO DRG NO. HED 5766 E133 (E128
DELETED)
WIRING DIAGRAM FOR STEERING MOTOR STARTER PANEL DRG. NO.
HED 5766 Elll TO DRG. NO. HED 5766 E125
GENERAL ARRANGEMENT OF STEERING MOTOR STARTER AND
CONTROL BOX DRG. NO. HED 5766 M201
GENERAL ARRANGEMENT FOR BRIDGE CONTROL STATION DRG. NO.
HED 5766 M202
WIRING DIAGRAM FOR THRUST DIRECTION INDICATOR 4A0101353
THRUST DIRECTION INDICATOR 4A0101751
STORK KWANT CONTROL UNIT 'RSCU' 4A0102062
APPENDIX "A"
APPENDIX "B"
APPENDIX "C"
APPENDIX "D"
ROCHESTER INSTRUMENTS ET7204(W)R
INSTRUCTION MANUAL
ALLEN-BRADLEY SLC 500 CONTROLLER
INSTRUCTION MANUAL
NEMIC-LAMBDA POWER SUPPY UNIT
INSTRUCTION MANUAL
FAIL-SAFE MGM-600 INSULATION MONITOR
DATA SHEET
_r
AZIMUTH INDICATOR
TYPE ASA1
l l l I
SUPPLY 8- 2t.V FOR DIAL IlLUMINATION
SUPPLY 24 V de
8: TYPE ASA1 I.P.V. t.A010\34t. AK 12-7-94
A : TABLE 18 _ 10-93 NJV
4X1.5 rr r r I I I I
11 I 2 I l I "
E)
TRANSMITTER
TYPE ·.
SFCPSOA- 1,517
OR EQUIVALENT
AZIMUTH INDICATOR
TYPE ASA 1
4X1.5
J
SUPPLY IL2t.V FOR
DIAL ILLUMINATION
NOTE: MAX. 10 INDICATORS MAY BE
CONNECTED TO ONE TRANS
MITTER (NO READJUSTING).
t.X 1. 5
VOLTAGE ON TERMINALS Lt.
1 2 3 " AH . o•t. 100"/ • 50"1. 100"1.
SB 0, 100 .,. 100"1. 50"1.
AS 0"1. 100"1. 50"1. 0"1.
PS o·s. 100 '· o•s. 5o•s.
GENERAL CABLE DIAGRAM I PROJ. METHODE
~A_z_IM_U_T_H __ I_N_DI_C_A_TI_N_G __ S_YS_T_E_M ______________________ ~w-;-JZL. -A~-~~1-+_0~-1~3-+_5~3~~--£:1
STCRK·KWANT
STORK- KWNrr B.V. SNEEK HOLLAND GET. NJV D.O. 2L L 93 GEZ. \_)\d)J. , HET AUTEUASRECHT WORDT VOORBEHOUDEN OVEREENKOMSTIG DE WET SCHAAL : I BLAO. /
• ' . 1
.j ., . ' l -, .... · ._.;
r
PS 58
·9 ® go-
PANEL MOUNTING SPRING
PANEL CUT-OUT 92x92
AZIMUTH INDICATOR ASAl · 4 A 0
~l!R~~~v~!:!e~o~T
WIJZ.
GET. V.O ..
. HET AUT£URSRECHT WOROT VOORBEHOUOEN OVEREENKOMSTIG DE WET ICHAAL :
CD
Ol
CD
Ol
O.D.
kAI).
PROJ .• METHOOE
7 5 1 -@}·- 20-8 ~ 93. au.
Potentiometer Specification
Model No. : SFCP50A-4517
Mechanism : Single-turn potentiometer, film element
Total resistance value: 2.5 Kohm ( Expansion, 10 Kohm )
Resistance value tolerance: +-15%
Independent linearity: +-0.075%
Resolution: Essentially infinite
Output smoothness: Below 1% against input voltage
Wiper current: MAX 10 uA
Power rating: 3W
Electrical rotating angle: 360° (2 x 180°) (Endless)
Mechanical rotating angle: 360° (Endless)
Insulation resistance: Over 100 Mohm at SOOV D.C.
Dielectric strength: 1 minute at 500V A.C.
Starting torque: Below 40gf.cm
Resistance temperature coefficient: +-400 p.p.m./°C
Operating temperature range: -55°C +125°C
Life expectancy: 50,000,000 shaft revolution
Phase angle of wiper: 90° +-1°
End play: 0.050 mm
Radial play: 0.050 mm
Shaft runout: 0.003 mm/mm
Pilot diameter runout: 0.040 mm
Lateral runout: 0.005 mm/mm
Operating max. speed: 400 rpm
STM OA TE DESCRIPTION APPD. DESIGNED DRAWN CHECKED APPROVED TITLE
J. T k .$ DA1EZZ.JEf.J9qz JflO ANGLE PROJECTION DWG. NO.
l 4 Z - 4 5 I r1 - I f---t--1----t---t fcF\ SAKAE TSUSHIN KOGYO CO .• LTD. 1--,..----.,-~----r~::-------i
~'1Jd K~AWA JAPAN SCALE / •Ts.lututs mml s"EET I Of Z
REFERENCE TRANSMITTER
CONNECTION- DIAGRAM
+I Cl'
'----T--2 ---+--5
Lll C>
I + C> N
-+ I l.ll
N d +I
'-0
N
N resistance between terminals 1 and 3 is 2500 Ohms.
cp 4 7. 62 5- 8.025
.. , ¢6 -0·8'6" r -0 :!
C"i . .
C> +I r- 1.11
I f I
I. ¢ 50.8 t1 rn N . .... l.ll
VI
-a 0 c c ·e E Ql Ql ..... -
V'l 0 N
. I"JJ
~ ~--f-
J
.I
CLAMP+ SCREW M3
C> N N
HOUSING: AIMg 2.5
C>
D
LEVER: AISI 316
PArJ~L CUT-OUT
> . FULL
PROTECTION COVER: Polycarbonite GRIP: Polyamide PROTECTION CLASS IPS!.
CONTROL UNIT R S C U 1
4 A 0
STORK-KWANT WIJZ
ST::li';K · K",;>..:J-iT B.V. Sl.;EEK HOLLANO GET . V.D. [) [) 2Q_ 1 ~94 GEZ
HET AUTEW1SF.ECHT >'10i'iJ7 VC::>RBEHOuCEN OVEREE"'KOMSTIG 0~ V.ET SC><AAL : - BLAO .