Part_7_-_Toe_Seep_Modifications_Plans_and_Specs_4-7-2015.pdf

PDF 1 MB Posted

Attached to
Summitville Dam - TOE SEEP MODIFICATIONS - SV-103
Solicitation number
DQ1 FAAA FEEA2015000000000001 4
Issued by
Rio Grande County, Denver City, Colorado

About this file

This file is a user manual for Magelis XBT GT and XBT GK human-machine interface (HMI) touchscreen and keypad panels manufactured by Schneider Electric, dated August 2007. The manual provides comprehensive technical documentation for a series of industrial control interface products operating at 24 VDC, available in multiple screen sizes ranging from 3.8 inches to 15.0 inches with various display technologies including STN and TFT LCD options. The XBT GT series includes 21 different model variations, while the XBT GK series offers 3 keypad-based models. Products are designed for hazardous industrial locations in compliance with Class I, Division 2 standards, feature IP65 front-panel protection ratings for indoor use, and operate across ambient temperatures from 0°C to 50°C. The manual details installation requirements, electrical specifications with power consumption ranging from 7W to 50W depending on model, and comprehensive connectivity options including serial interfaces (RS232C/RS485), Ethernet (10Base-T or 100Base-TX), USB ports, and CompactFlash card slots for data storage and transfer.

The technical specifications address display resolutions from 320x240 to 1024x768 pixels, touch panel resolution of 1024x1024 with analog typing capability, memory configurations ranging from 8MB to 64MB application flash storage, and backup SRAM with lithium battery support providing approximately 60 days of backup power with full charge. Interface specifications include serial COM1 and COM2 ports supporting transmission speeds from 2,400 to 187.5 Kbps, optional AUX connectors for external reset, alarm output, buzzer output, and sound output functions on larger models, and support for multiple PLC connections including Modicon M340, Mitsubishi, Omron, and Siemens platforms. The manual includes detailed dimensional drawings, installation fastener specifications, and accessory information for optional components such as USB cables, CF memory cards, communication modules, and screen protection sheets. Products are UL, CSA, and CE certified with environmental compliance to IEC 61131-2, UL 508, UL 1604, and CISPR 11 standards.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

www.telemecanique.com

Magelis

XBT GT, XBT GK

User Manual 8/2007

Table of Contents

Safety Information About the Book

Part I XBT GT and XBT GK Panels Chapter 1 XBT GT and XBT GK Panels

XBT GT and GK Series of Panels Package Contents UL and CSA Conformity CE Marking Notes

Chapter 2 Device Connectivity System Design Accessories

Chapter 3 Specifications

3.1 General Specifications

Electrical Specifications Environmental Specifications Structural Specifications

3.2 Functional Specifications

Display Specifications Memory, Clock, and Touch Panel Industrial Pointer, Keypads and LEDs Insert Labels XBT GK Serial Interface

3.3 Interface Specifications

Specifications of Serial Interface COM1 Specifications of Serial Interface COM2 Other Interfaces

3.4 Part Numbers and Functions

Parts Identification and Functions Terminal Configuration Switches

3.5 Dimensions

XBT GT1000 Series Dimensions XBT GT1005 Series Dimensions XBT GT2000 Series Dimensions XBT GT4000 Series Dimensions XBT GT5000 Series Dimensions XBT GT6000 Series Dimensions XBT GT7000 Series Dimensions XBT GK2000 Series Dimensions XBT GK5330 Dimensions Panel Cut Dimension Installation Fasteners

Chapter 4 Installation and Wiring

4.1 Installation

4.2 Wiring Principles

Connecting the Power Cord Connecting the Power Supply Grounding Input/Output Line Placement

4.3 Tool Port Connector

Making Tool Port Connections USB Driver Installation

4.4 Ethernet Cable Connector

4.5 CF Card

4.6 USB Port

Important Considerations When Using the USB Port USB Data Transfer Cable (XBT ZG935) - USB Driver Installation USB Clamp USB Holder

4.7 AUX Connector

Part II Setting and Debugging At a Glance

Chapter 5 Settings

5.1 Settings

Types of Settings Offline Settings System Settings

Chapter 6 Troubleshooting Troubleshooting Checklists Self Test List

Chapter 7 Maintenance Regular Cleaning Periodic Check Points Replacing the Backlight

Index

35010372 9/2007 7

Safety Information

NOTICE Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

© 2007 Schneider Electric. All Rights Reserved.

The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.

DANGER

WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.

WARNING

CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.

CAUTION

Safety Information

8 35010372 9/2007

35010372 9/2007 9

About the Book

At a Glance

Document Scope This manual describes how to use the Magelis XBT GT and XBT GK devices.

Validity Note The data and illustrations found in this book are not binding. We reserve the right to modify our products in line with our policy of continuous product development. The information in this document is subject to change without notice and should not be construed as a commitment by Schneider Electric.

Product Related Warnings

Schneider Electric assumes no responsibility for any errors that may appear in this document. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us. No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without the express written permission of Schneider Electric. All rights reserved.

All pertinent state, regional and local safety regulations must be observed when installing and using this product. For reasons of safety and to assure compliance with documented system data, only the manufacturer should perform repairs to components.

User Comments We welcome your comments about this document. You can reach us by e-mail at techpub@schneider-electric.com

About the Book

10 35010372 9/2007

35010372 9/2007 11

I XBT GT and XBT GK Panels

At a Glance

Overview This part presents XBT GT and XBT GK Panels.

What's in this Part?

This part contains the following chapters:

Chapter Chapter Name Page

1 XBT GT and XBT GK Panels 13

2 Device Connectivity 21

3 Specifications 31

4 Installation and Wiring 137

XBT GT and XBT GK Panels

12 35010372 9/2007

35010372 9/2007 13

XBT GT and XBT GK Panels

At a Glance

Overview This chapter presents series of XBT GT and XBT GK Panels and connectable devices.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

XBT GT and GK Series of Panels 14

Package Contents 17

UL and CSA Conformity 19

CE Marking Notes 20

14 35010372 9/2007

XBT GT and GK Series of Panels

Introduction The following presents the XBT GT touchscreen and XBT GK keypad series of human-machine interface (HMI) products. These products have an operating voltage of 24 VDC. The products offered in this series have various features and benefits listed below:

Screen size Screen resolution Screen technology and color Communication ports

XBT GT Part Numbers

The following table presents the different XBT GT products:

STN: scan twisted pneumatic, also known as passive matrix.

TFT: thin film transistors, also known as active matrix.

Part number Screen size Pixel resolution

Mono/Color Screen technology

Video port Ethernet port

XBT GT1100 9,6 cm (3.8 in) QVGA Amber STN No No

XBT GT1105 9,6 cm (3.8 in) QVGA Amber STN No No

XBT GT1130 9,6 cm (3.8 in) QVGA Amber STN No Yes

XBT GT1135 9,6 cm (3.8 in) QVGA Amber STN No Yes

XBT GT1335 9,6 cm (3.8 in) QVGA Color TFT No Yes

XBT GT2110 14,4 cm (5.7 in) QVGA Blue Mode STN No No

XBT GT2120 14,4 cm (5.7 in) QVGA Monochrome STN No No

XBT GT2130 14,4 cm (5.7 in) QVGA Monochrome STN No Yes

XBT GT2220 14,4 cm (5.7 in) QVGA Color STN No No

XBT GT2330 14,4 cm (5.7 in) QVGA Color TFT No Yes

XBT GT4230 19,1 cm (7.5 in) VGA Color STN No Yes

XBT GT4330 19,1 cm (7.5 in) VGA Color TFT No Yes

XBT GT4340 19,1 cm (7.5 in) VGA Color TFT Yes Yes

XBT GT5230 26,4 cm (10.4 in) VGA Color STN No Yes

XBT GT5330 26,4 cm (10.4 in) VGA Color TFT No Yes

XBT GT5340 26,4 cm (10.4 in) VGA Color TFT Yes Yes

XBT GT6330 30,7 cm (12.1 in) SVGA Color TFT No Yes

XBT GT6340 30,7 cm (12.1 in) SVGA Color TFT Yes Yes

XBT GT7340 38,1 cm (15.0 in) XGA Color TFT Yes Yes

35010372 9/2007 15

XBT GK Part Numbers

The following table presents the different XBT GK products:

STN: Scan Twisted Nematic also known as passive matrix.

TFT: Thin Film Transistors also known as active matrix.

Critical systems, alarms and handling Requirements

Critical alarm indicators and system functions require independent and redundant protection hardware and/or mechanical interlocks.

When you cycle power, wait at least 10 seconds before restoring the power to the HMI unit after it has been turned off. Switching the power OFF and ON quickly can damage the unit.

In the event of backlight or other unit failure, it may be difficult or impossible to identify a function. Functions that may present a hazard if not immediately executed, such as emergency stop, must be provided independently of the unit. The machine’s control system design must take into account the possibility of the backlight failing and the operator being unable to control the machine or making errors in the control of the machine.

Part number Screen size Pixel resolution

Mono/Color Screen technology

Video port Ethernet port

XBT GK2120 14,4 cm (5.7 in) QVGA Monochrome STN No No

XBT GK2330 14,4 cm (5.7 in) QVGA Color TFT No Yes

XBT GK5330 26,4 cm (10.4 in) VGA Color TFT No Yes

UNINTENDED EQUIPMENT OPERATION

Do not use the unit as the only means of control for critical system functions such as motor start/stop or power disconnect Do not use the unit as the only notification device for critical alarms, such as device overheating or overcurrent

Failure to follow these instructions can result in death, serious injury, or equipment damage.

WARNING

16 35010372 9/2007

Handling the LCD panel

The following characteristics are specific to the LCD unit and are considered normal behavior:

LCD screen may show unevenness in the brightness of certain images or may appear different when seen from outside the specified viewing angle. Extended shadows, or crosstalk may also appear on the sides of screen images.

LCD screen pixels may contain black and white colored spots and color display may seem to have changed.

When the same image is displayed on the unit’s screen for a long period, an afterimage may appear when the image is changed. If this happens, turn OFF the unit, wait 10 sec and then restart the unit.

Note: Change the screen image periodically and try not to display the same image for a long period of time.

SERIOUS EYE AND SKIN INJURY

The LCD panel’s liquid contains an irritant. Avoid direct skin contact with the liquid.

Wear gloves when you handle a broken or leaking unit.

Do not use sharp objects or tools in the vicinity of the LCD touch panel or to operate its buttons.

Handle the LCD panel carefully to prevent puncture, bursting, or cracking of the panel material.

If the panel is damaged and any liquid comes in contact with your skin, immediately rinse the area with running water for at least 15 min. If the liquid gets in your eyes, immediately rinse your eyes with running water for at least 15 min and consult a doctor.

Failure to follow these instructions can result in injury or equipment damage.

35010372 9/2007 17

Package Contents

Make sure all items listed here are present in your unit’s package:

2 3

5a

Quick Reference

Guide

1b1a

6 7

1c

12 13

5b

18 35010372 9/2007

1a or 1 b or 1c Human Machine Interface 2 Installation Gasket 3 Power Plug (for XBT GT1000/1005/2000/4000 series, XBT GK2000 series) 4 Power Plug (for XBT GT5000/6000/7000 series, XBT GK5000 series) 5a USB Holder (for XBT GT2000 series) 5b USB Holder (for XBT GK series) 6 USB Cable Clamp (for XBT GT2000 series, XBT GK series) 7 RCA-BNC Convertor (for XBT GT4340/5340/6340/7340) 8 USB Holder, 1 set (for XBT GT1005/4000/5000/6000/7000 series) 9 AUX Connector (for XBT GT4000/5000/6000/7000 series, XBT GK5000 series) 10 Screw installation fasteners (XBT GT1005/2000/4000/5000/6000 series: x4, XBT GT7000 series: x8, XBT GK series: none) 11 Spring Clip (for XBT GK2000 series: x10, XBT GK5000 series: x12) 12 "Insert Labels" set (for XBT GK series: contains 2 sets of premarked labels and 4 blank labels) 13 Quick Reference Installation guide

Revision You can identify the product version (PV), revision level (RL), and the software version (SV) from the product label sticker pasted on the unit.

The following diagram show a typical representation of label sticker:

35010372 9/2007 19

UL and CSA Conformity

Introduction The XBT GT and XBT GK series of panels are cULus listed and CSA certified.

The XBT GT and XBT GK series have been developed to conform with the following standards:

IEC/EN 61131-2 Programmable controllers UL 508 for Industrial Control Equipment UL 1604 Electrical Equipment for Use in Class I and Class II Division 2 and Class III Hazardous Locations, except XBT GT series 1005 and the XBT GK series UL 60950 Standard for Safety of Information Technology Equipment, CAN/CSA-C22.2, No.14, No.213, and No. 60950 Industrial Control Equipment Miscellaneous Apparatus - For Hazardous Locations.

CISPR 11

UL50/NEMA 250 4X, indoor use only EN 60079-15 and IEC 61241-1 for XBT GT series only

UL 1604

Conditions of Acceptability and Handling Cautions

The XBT GT series (except the XBT GT 1005 series) has been designed to operate in hazardous locations in accordance with Class 1, Division 2 standards. All relevant local, state, and regional codes must be followed.

EXPLOSION

Compatibility: Power, input and output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods Do not perform substitution of components that may impair compliance to Class I, Division 2.

Confirm that the location is not subject to any risk of explosion before connecting or disconnecting equipment, replacing or wiring modules.

Confirm that the externally connected unit and each interface (COM1, COM2, EXT1, EXT2, CF Card, AUX) and the CF Card Cover and the AUX Connector have been securely locked.

Confirm that the power supply has been turned OFF before disconnecting, replacing or wiring modules.

Before turning ON, sweep front panel with a damp cloth.

Failure to follow these instructions will result in death or serious injury.

DANGER

20 35010372 9/2007

CE Marking Notes

Introduction The units are CE marked, EMC compliant products.

These units also conform to EN55011 Class A, EN61000-6-2 directives. For detailed CE marking information, contact your local distributor.

Environment Standards

Compliance with standards

IEC 61131-2, IEC61000-6-2, CISPR11(Class A), UL 508, UL1604, CSA C22.2 no. 14 and 213

Product certification CE, cULus, CSA, UL Class 1 Div 2 T4A or T5

Operating temperature 0 °C + 50 °C (32 °F 122 °F)

Storage temperature -20 °C + 60 °C (-4 °F 140 °F)

Protection (front panel) IP 65 - (IEC 60529) Enclosure type, 4X indoor use with screw installation fasteners only for XBT GT series and with spring clips fasteners only for XBT GK series.

Protection (rear panel) IP 20 - (IEC 60529)

ESD withstand IEC 61000 - 4 - 2, IEC61131- 2 4 kV contact, 8 kV air

Radiated radio frequency electromagnetic field

IEC 61000 - 4 - 3, IEC61131- 2

10 V / m

Electrical fast transient burst

IEC 61000- 4 - 4, IEC 61131- 2

2 kV (power supply and I/O) 1 kV other ports

High Energy Surges IEC 61000 - 4 - 5 1 kV (Differential Mode on power supply) 2 kV (Common Mode on power supply)

Shocks IEC 60068 - 2 - 27 1/2 sinusoidal pulse for 11 ms, 15 g on 3 axes

Vibration Immunity IEC 60068 - 2 - 6

3.5 mm 5 to 9 Hz 1 g. 9 to 150 Hz

Pollution Degree 2

35010372 9/2007 21

Device Connectivity

At a Glance

Introduction This chapter presents the equipment connectable to each XBT GT and XBT GK unit.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

System Design 22

Accessories 26

Device Connectivity

22 35010372 9/2007

System Design

Introduction The following diagrams represent the main selection of equipment connectable to the units.

XBT GT1000

Series Edit Mode Peripherals

(1) Not available on XBT GT1100

XBT GT1005/

2000/4000/5000/ 6000/7000 Series and

XBT GK2000/

5000 Series Edit Mode Peripherals

(1) Not available on XBT GT1105/2110/2120/2220 and XBT GK2120

(2) Not available on XBT GT1105/1135/1335/2110

XBT GT1000 series unit Personal computer

Vijeo Designer

To Ethernet network (1)

Data transfer cable XBT ZG915 or

XBT ZG925 (USB)

Tool connector

To Ethernet Network (1)

XBT GT / XBT GK unit

Vijeo Designer

USB Connector

Personal Computer

CF Card (2)

Data Transfer Cable

XBT ZG935 (USB)

USB Memory Stick

35010372 9/2007 23

XBT GT1000

Series Run Mode Peripherals

(1) Not available on XBT GT1100

To Ethernet Network (1)

XBT GT1000 Series Unit

PLC

XBT Z***

24 35010372 9/2007

XBT GT1005/

2000/4000/5000/ 6000/7000 and

XBT GK2000/

5000 Series Run Mode Peripherals

Ethernet

XBTZ***

USB

COM1

COM2

XBTZ***

XBTZ915

10 11

12 13

35010372 9/2007 25

1 Ethernet network connection (not available on XBT GT1105/2110/2120/2220 and

XBT GK2120)

2 Serial bar code reader (validated with Gryphon range of Datalogic) 3 USB hub (commercial type) 4 Serial printer

5 PLC

6 Parallel printer (printer function validated with EPSON and HP models; details available on

Vijeo Designer documentation) 7 CF Card (not available on XBT GT1105/1135/1335/2110) 8 USB Mouse 9 USB Keyboard 10 Camera (available on XBT GTxx40 products only, and VijeoDesigner Version higher than

V4.3) 11 Flashing light (not available on XBT GT1005/2000 series, and XBT GK2000 series) 12 Microphone (available on XBT GTxx40 products only, and VijeoDesigner Version higher than V4.3) 13 Speaker (not available on XBT GT1005/2000 series, and XBT GK2000 series) 14 USB Memory Stick) 15 PLC with USB Terminal port (Modicon M340) 16 Communication Gateway (Modbus Plus or Fipio)

26 35010372 9/2007

Accessories

Serial Interface Items

Product Number

Product name Description XBT GT/GK series

XBT Z915 Cable Connects COM1 port to a serial printer. All XBT GK models, XBT GT2000 and higher

XBT Z9780 XBT Z cable Connects COM1 on XBT GT1000/1005 series and COM2 on XBT GK and XBT GT2000 and higher series to Premium, Micro, Twido PLC

All

XBT Z9980 XBT Z cable Connects COM1 on XBT GT1000/1005 series and COM2 on XBT GK and XBT GT2000 and higher series to Modicon M340

All

VW3A8306 XBT Z cable Connects COM1 on XBT GT1000/1005 series and COM2 on XBT GK and XBT GT2000 and higher series to derivation box TSXSCA62

All

VW3A8306R10 XBT Z cable Connects COM1 on XBT GT1000/1005 series and COM2 on XBT GK and XBT GT2000 and higher series to ATV Drives or to Hub LU9GC3 or to Fieldbus Tap TWDXCAT3RJ, TWDXCAISO

All

STBXCA4002 XBT Z cable Connects COM1 port to Advantys STB All XBT GK models, XBT GT2000 and higher

TSXPCX1031 XBT Z cable Connects COM1 port to Premium, Micro, Twido All XBT GK models, XBT GT2000 and higher

XBT ZG909 XBT Z adapter Cable adapter COM1 D-Sub9 RS485 All XBT GK models, XBT GT2000 and higher

XBT ZG919 XBT Z adapter Cable adapter COM1 D-Sub9 RS232 All XBT GK models, XBT GT2000 and higher

XBT ZG939 XBT Z adapter Cable adapter COM1 RJ45 XBT GT1000/1005

XBT Z968

XBT Z9680

XBT Z9681

XBT Z cable Connects COM1 port with XBTZ adapter to Premium, Micro, Twido PLC

All

XBT Z9710 XBT Z cable Connects COM1 port with XBTZ adapter to Quantum PLC

All

XBT Z9711 XBT Z cable Connects COM1 port with XBTZ adapter to Momentum PLC

All

XBT Z908 XBT Z cable Connects COM1 port with XBTZ adapter to derivation box TSXSCA62

All XBT GK models, XBT GT2000 and higher

35010372 9/2007 27

XBT Z938 XBT Z cable Connects COM1 port with XBTZ adapter to ATV drives or to Hub LU9GC3 or to Fieldbus Tap

TWDXCAT3RJ, TWDXCAISO

All XBT GK models, XBT GT2000 and higher

XBT Z918 XBT Z cable Connects COM1 port with XBTZ adapter to Premium SCY

All

XBT Z988 XBT Z cable Connects COM1 port with XBTZ adapter to Advantys STB

All

XBT ZGI232 XBT Z

isolation

Connects COM1 port to an equipment and provide isolation

All XBT GK models, XBT GT2000 and higher

XBT ZGI485 XBT Z

isolation

Connects COM1 port to an equipment and provide isolation

All XBT GK models, XBT GT2000 and higher

XBT ZGCOM1 Port adapter Connects COM1 port to optional RS422 equipment All XBT GK models, XBT GT2000 and higher

XBT ZGCOM2 Port adapter Connects COM2 port to optional RS485 equipment All XBT GK models, XBT GT2000 and higher

XBT ZG9731 XBT Z cable Connects COM1 to Mitsubishi PLC A series link unit or to Rockwell DF1 Logix PLC

All XBT GK models, XBT GT2000 and higher

XBT ZG9772 XBT Z cable Connects COM1 to Mitsubishi PLC Q series link unit

All XBT GK models, XBT GT2000 and higher

XBT ZG9773 XBT Z cable Connects COM1 to Mitsubishi PLC A series CPU All XBT GK models, XBT GT2000 and higher

XBT ZG9774 XBT Z cable Connects COM1 to Mitsubishi PLC Q series CPU All XBT GK models, XBT GT2000 and higher

XBT ZG9775 XBT Z cable Connects COM1 to Mitsubishi PLC FX series CPU All XBT GK models, XBT GT2000 and higher

XBT ZG9740 XBT Z cable Connects COM1 to Omron PLC Sysmac Link series

All XBT GK models, XBT GT2000 and higher

XBT ZG9722 XBT Z cable Connects COM1 to RS422 devices All XBT GK models, XBT GT2000 and higher

XBT ZG9778 XBT Z cable Connects COM1 with port adapter to Mitsubishi PLC with Melsec 2 port adapter

All XBT GK models, XBT GT2000 and higher

XBT ZG979 Adapter All XBT GK models, XBT GT2000 and higher

XBT ZG949 Adapter Terminal RS422 block to connect XBT GT COM1 with port adapter to RS422 devices

All XBT GK models, XBT GT2000 and higher

XBT ZG9721 XBT Z cable Connects COM1 or COM2 to Siemens PPI PLC All

XBT ZG9292 XBT Z cable Connects COM1 to Siemens MPI PLC All XBT GK models, XBT GT2000 and higher

Product Number

Product name Description XBT GT/GK series

28 35010372 9/2007

XBT GT Tool Port Items

USB Interface Items

Software

XBT Z9730

XBT Z9731

XBT Z cable Connects COM1 with XBT Z adapter to Rockwell

DF1 PLC

XBT GT1000/1005

XBT Z9732 XBT Z cable Connects COM1 with XBT Z adapter to Rockwell

DH485 PLC

All

XBT Z9740 XBT Z cable Connects COM1 with XBT Z adapter to Omron PLC Sysmac Link series

XBT GT1000/1005

XBT Z9720 XBT Z cable Connects COM1 with XBT Z adapter to Siemens

3964/RK512

All

Product Number

Product name Description XBT GT/GK series

Product Number Product name Description XBT GT series XBT ZG915 (for PC Serial Port) XBT ZG925 (for PC USB Port)

Cable Connects the XBT GT to a personal computer.

Transfers screen data and user program(s).

XBT GT1000

Product Number Product name Description XBT GT/GK series XBT ZG935 Cable Connects the panel to a personal computer.

Transfers screen data and user program

XBT GT1005/2000,

XBT GK2000

XBT ZGUSB Cable Extends a USB host interface on a cabinet with waterproofness

All XBT GK models, XBT GT1005 and higher

XBT ZGUMP Gateway Connects panels to Modbus Plus Fieldbus All XBT GK models, XBT GT2000 and higher

TSXCUSBFIP Gateway Connects panels to Fipio Fieldbus All XBT GK models, XBT GT2000 and higher

BMXXCAUSB018 Cable Connects the panel to a USB terminal port of a PLC (Modicon M340)

All XBT GK models, XBT GT1005 and higher

Product name Description

Vijeo Designer (version 4.3 or higher for XBT GT, Version 4.6 or higher for XBT GK)

Software used to create HMI unit project data. It is installed in a personal computer.

35010372 9/2007 29

Screen Protection Sheets

Spring Clip Fasteners

Communication Modules

Compact Flash Memory Card Interface

The Compact Flash memory card is used for XBT GT 2000 series and higher except XBT GT2110 units and all XBT GK models.

This slot accepts any of the following Compact Flash (CF) memory cards:

XBT ZGM128 (128 Mb) XBT ZGM256 (256 Mb) MPCYN00CFE00N (512 Mb) MPCYN00CF100N (1 Gb)

Product Number Description XBT GT/GK series XBT ZG60 Dirt-resistant sheet

The touch panel can be operated with this cover sheet attached 5 sheets/pack

XBT GT1005

XBT ZG61 XBT GT1000

XBT ZG62 XBT GT2000

XBT ZG64 XBT GT4000

XBT ZG65 XBT GT53xx

XBT ZG66 XBT GT6000,

XBT GT52xx

MPCYK50SPSKIT XBT GT7000

XBT ZG68 XBT GK2000

XBT ZG69 XBT GK5000

Product Number Description XBT GT/GK series

XBT Z3002 Fasteners attach the panel to a mounting surface for IP65 protection on XBT GT and IP65/Nema4 on XBT GK: 12 clips/pack

All

Product Number

Product Name

Description XBT GT/GK series

XBT ZGPDP Profibus DP module

These modules are used to connect XBT GT/GK to Fieldbus. They are piggy back modules for the XBT GT/GK panels.

All XBT GT/GK models except XBT GT1000 and 1005 series.

XBT ZGDVN Device Net module

30 35010372 9/2007

Maintenance Options

Product Number Product name Description XBT GT/GK series

XBT ZGFIX Screw installation fastener

Fasteners to attach the panel to a mounting surface. (4 fasteners/pack)

All

XBT ZG51 Installation gasket Provides a moisture resistant seal. Same as the seal included in the original package.

XBT GT1000/1005

XBT ZG52 XBT GT2000

XBT ZG54 XBT GT4000

XBT ZG55 XBT GT53xx

XBT ZG56 XBT GT6000 and XBT GT52xx

XBT ZG57 XBT GT7000

XBT ZG58 XBT GK2000

XBT ZG59 XBT GK5000

XBT ZGAUX Auxiliary connector Interface to control external reset, alarm output, buzzer output, and sound output.

XBT GK5000 and XBT GT4000 and higher

XBT ZGCLP1 USB clamp Fastens onto a USB interface and prevents the USB cable from being disconnected.

XBT GT 2000

XBT ZGCLP2 USB holder XBT GT except

XBT GT1000/2000

XBT ZGCLP3 USB clamp XBT GK

XBT ZGPWS1 Power connector Supplies power to the unit. XBT GT1000/1005 and

XBT GT/GK2000

XBT ZGPWS2 XBT GK5000 and XBT GT 4000 and higher

XBT LYGK2 Sheets of changeable labels

Removable labels for identifying function keys.

XBT GK2000

XBT LYGK5 XBT GK5000

35010372 9/2007 31

Specifications

At a Glance

Overview This chapter presents the XBT GT and XBT GK specifications:

What's in this Chapter?

This chapter contains the following sections:

Section Topic Page

3.1 General Specifications 32

3.2 Functional Specifications 37

3.3 Interface Specifications 53

3.4 Part Numbers and Functions 62

3.5 Dimensions 94

Specifications

32 35010372 9/2007

3.1 General Specifications

At a Glance

Overview This section presents XBT GT and XBT GK general specifications:

What's in this Section?

This section contains the following topics:

Topic Page Electrical Specifications 33

Environmental Specifications 34

Structural Specifications 36

35010372 9/2007 33

Electrical Specifications

Specification XBT GT1000 series

XBT GT1005

series

XBT GT2000

XBT GK2000

series

XBT GT4000

series

XBT GT5000,

XBT GT6000,

XBT GK5000

series

XBT GT7000

series

Input Voltage 24 VDC

Rated Voltage 19.2 VDC to 28.8 VDC

Acceptable Voltage Drop

1 ms 5 ms (except for

XBT GT2110:

10 ms)

10 ms

Power Consumption 7 W 13 W 26 W (except for

XBT GT2110:

18 W)

28 W 50 W (except for

XBT GT5230:

26 W)

42 W

In-Rush Current 50 60 30

Voltage endurance between power terminal and frame ground (FG)

AC 500 V 20 mA for 1 min

Insulation Resistance between power terminal and FG.

20 M or higher at 500 VDC 10 M or higher at 500 VDC

Note: For in-rush current, the FWHM (full-width, half maximum) value is approximately 50 s. (When exceeding 25 A)

34 35010372 9/2007

Environmental Specifications

Note: (1) The front face of the unit, installed in a solid panel, has been tested using conditions equivalent to the standards shown in the specification. Therefore, prior to installing the unit, be sure to confirm the type of conditions that will be present in the operating environment. If the installation gasket is removed from the panel, the original protection level cannot be guaranteed. To maintain the original protection level, replace the installation gasket every year.

Specification XBT GT1000, XBT GT1005, XBT GT2000, XBT GT4000, XBT GT5000, XBT GT6000, XBT GK2000, XBT GK5000 series

XBT GT7000 series

Ambient operating temperature (cabinet interior & panel face)

0 °C to +50 °C (32 °F to 122 °F) (1)

Storage temperature -20 °C to + 60 °C (-4 °F to 140 °F)

Operating humidity 10% RH to 90% RH (Non condensing, wet bulb temperature: 39 °C)

Storage humidity 10% RH to 90% RH (Non condensing, wet bulb temperature: 39 °C)

Air purity (dust) 0.1 mg/m3 (non-conductive levels)

Pollution degree Pollution degree 2

Corrosive gases Free of corrosive gases

Atmospheric endurance (XBT GT operation altitude)

800 hPa to 1,114 hPa (2,000 m [6561 ft] or lower)

Vibration immunity IEC61131-2 compliant Industry:

5 Hz to 9 Hz 3.5 mm, 9 Hz to 150 Hz 1 g.

Noise immunity (via noise simulator)

Noise voltage: 1000 Vp-p.

Pulse duration: 1 s Rise time:1 ns

Noise voltage: 1500 Vp-p.

Pulse duration: 1 s Rise time: 1 ns

Electrostatic discharge immunity

6 kV contact, 8 kV air (complies with EN 61000-4-2 level 3)

Note: (1) The LCD display’s contrast STN color and monochrome models (see

p. 38) may decrease when displays are used for hours at over 40°C [104°F] ambient operating temperature. After the temperature returns to normal, the display’s contrast will be restored to normal. The unit’s operation will not be affected even though the display’s contrast is reduced.

35010372 9/2007 35

Do not store the HMI unit in an area where the temperature is lower than that recommended in the unit's specifications. Doing so may cause the LCD display's liquid to freeze, which can damage the LCD. Also, if the storage area's temperature becomes higher than the specified level, the LCD's liquid may cause irreversible damage to the LCD. Therefore, only store the unit in areas where temperatures are within the unit's specifications. Do not restrict nor block the unit's rear-face ventilation slots.

Air quality requirements

Do not operate or store the unit where chemicals evaporate, or where chemicals are present in the air:

Corrosive chemicals: Acids, alkalines, liquids containing salt.

Flammable chemicals: Organic solvents.

Do not allow water, liquids, metal, and wiring fragments to enter the HMI unit's case.

Do not use the unit in an environment continually exposed to flammable gases.

36 35010372 9/2007

Structural Specifications

Specification XBT GT1000/1005 series XBT GT2000 series XBT GT4000 series

Grounding Observe local codes and standards. The ground connection must have a resistance 100 and the ground wire must have a cross section of at least 2 mm2 (AWG 14).

Rating (For front panel or installed unit) IP65 (IEC 60529) (1) NEMA # 250 Type 4X/13,indoor use only

External dimensions W130 mm (5.12 in) x H104 mm (4.09 in) x D41 mm (1.61 in)

W167.4 mm (6.60 in) x H135 mm (5.32 in) x D59.5 mm (2.34 in)

W215 mm (8.46 in) x H170 mm (6.69 in) x D60 mm (2.36 in)

Weight 0.4 kg (0.9 lbs) 1.0 kg (2.20 lbs) 1.8 kg (4.0 lbs)

Cooling Method Natural air circulation

Specification XBT GT5000 series except for

XBT GT5230

XBT GT6000 series, XBT GT5230

XBT GT7000 series

Grounding Observe local codes and standards. The ground connection must have a resistance 100 and the ground wire must have a cross section of at least 2 mm2 (AWG 14).

Rating (For front panel or installed unit)

IP65 (IEC 60529) (1) NEMA # 250 Type 4X/13, indoor use only

External dimensions W270.5 mm (10.65 in) x H212.5 mm (8.37 in) x D57 mm (2.24 in)

W313 mm (12.32 in) x H239 mm (9.41 in) x D56 mm (2.20 in)

W395 mm (15.55 in) x H294 mm (11.57 in) x D60 mm (2.36 in)

Weight 2.5 kg (5.5 lbs) 3.0 kg (6.6 lbs) 5.6 kg (12.3 lbs)

Cooling Method Natural air circulation

Specification XBT GK2000 series XBT GK5330

Grounding Observe local codes and standards. The ground connection must have a resistance 100 and the ground wire must have a cross section of at least 2 mm (14AWG).

Rating (For front panel or installed unit) IP65 (IEC 60529) (1) NEMA # 250 Type 4X/13, indoor use only

External dimensions W220.3 mm (8.66 in) x H265 mm (10.34 in) x D60.3 mm (2.374 in)

W296 mm (11.65 in) x H332 mm (13.07 in) x D72.7 mm (2.862 in)

Weight 1.8 kg (4.0 lbs) 3.7 kg (6.0 lbs)

Cooling Method Natural air circulation

35010372 9/2007 37

3.2 Functional Specifications

At a Glance

Overview This section presents the XBT GT and XBT GK functional specifications of the display, memory and interfaces.

What's in this Section?

This section contains the following topics:

Topic Page

Display Specifications 38

Memory, Clock, and Touch Panel 43

Industrial Pointer, Keypads and LEDs 45

Insert Labels XBT GK 48

Serial Interface 51

38 35010372 9/2007

Display Specifications

STN Displays

Specification XBT GT1100

XBT GT1130

XBT GT1105

XBT GT1135

XBT GT2110 XBT GT2120

XBT GT2130

XBT GK2120

XBT GT2220 XBT GT4230 XBT GT5230

Type Monochrome

LCD

Monochrome (Blue mode)

LCD

Monochrome

(B&W) LCD

Color

Resolution (pixels)

320 x 240 640x480

Active Display Area WxH (mm) WxH (in.)

76.7 x 57.5

3.02 x 2.26

115.2 x 86.4

4.54 x 3.40

153.7x115.8 6.05x4.56

215.2x162.3 8.43x6.39

Colors 8 levels of gray 16 gradations 4.096 colors

Backlight (1) LED Backlight (Color: Amber;

Service life:

50,000 h. [half of original brightness]) (Color: Red;

Service life:10,000 h.

[half of original brightness])

CFL Backlight (Service life:

58,000 h. at 25°C and continuous operation [half of original brightness])

CFL Backlight (Service life:

75,000 h. at 25°C and continuous operation [half of original brightness])

CFL Backlight (Service life:

54,000 h. at 25°C and continuous operation [half of original brightness])

CFL Backlight (Service life:

54,000 h. at 25°C and continuous operation [half of original brightness])

Contrast Adjustment

8 levels of adjustment available via touch panel.

Brightness Adjustment

2 levels of adjustment for

XBT GT1000

and 8 levels of adjustment for

XBT GT1005

available via touch panel.

8 levels of adjustment available via touch panel.

35010372 9/2007 39

TFT Displays

System Embedded Language Fonts (2)

ASCII: (Code page 850) Alphanumeric (including European characters) Chinese: (GB2312-80 codes) simplified Chinese fonts Japanese (except for XBT GT1000 series): ANK 158, Kanji: 6,962 (JIS Standards 1 & 2) (including 607 non-kanji characters) Korean: (KSC5601 - 1992 codes) Hangul fonts Taiwanese: (Big 5 codes) traditional Chinese fonts

Character Sizes (2)

8 X 8, 8 X 16, 16 X 16 and 32 X 32 pixels fonts

Font Sizes Width can be expanded 1 to 8 times. Height can be expanded 1/2 and 1 to 8 times.

8 x 8 pixels 40 Char. per row, x 30 rows 80 Char. per row x 60 rows

8 x 16 pixels 40 Char. per row, x 15 rows 80 Char. per row x 30 rows

16 x 16 pixels 20 Char. per row x 15 rows 40 Char. per row x 30 rows

32 x 32 pixels 10 Char.per row x 7 rows 20 Char. per row x 15 rows

Specification XBT GT1100

XBT GT1130

XBT GT1105

XBT GT1135

XBT GT2110 XBT GT2120

XBT GT2130

XBT GK2120

XBT GT2220 XBT GT4230 XBT GT5230

Note:

(1) Among backlight units there may be slight variations in illumination color, however, this does not affect the performance or quality of the unit.

(2) The display font will differ depending on which (language) character, or which size you select. Also, if Vijeo Designer 4.3 or later software is used, additional high quality fonts are available with 16x16 or larger characters.

Specification XBT GT1335 XBT GT2330

XBT GK2330

XBT GT4330

XBT GT4340

XBT GT5330

XBT GT5340

XBT GK5330

XBT GT6330

XBT GT6340

XBT GT7340

Type TFT Color LCD

Resolution (pixels) 320 x 240 640x480 800x600 1024x768

Active Display Area WxH (mm) WxH (in.)

76.7 x 57.5

3.02 x 2.26

115.2x86.4 4.54x3.40

153.7x115.8 6.05x4.56

211.2x158.4 8.31x6.24

248x186.5 9.76x7.34

306.2x230.1 12.06x9.06

Colors 256 colors 65.536 colors

40 35010372 9/2007

Backlight (1) CFL Backlight (Service life:

50,000 h. at 25°C and continuous operation [half of original brightness])

CFL Backlight (Service life:

54,000 h. at 25°C and continuous operation [half of original brightness])

CFL Backlight (Service life: 50,000 h. at 25°C and continuous operation [half of original brightness])

Contrast Adjustment 8 levels of adjustment available via touch panel

Not available. 8 levels of adjustment available via touch panel

Not available.

Brightness Adjustment

8 levels of adjustment available via touch panel.

System Embedded Language Fonts (2)

ASCII: (Code page 850) Alphanumeric (including European characters) Chinese: (GB2312-80 codes) simplified Chinese fonts Korean: (KSC5601 - 1992 codes) Hangul fonts Taiwanese:

(Big 5 codes) traditional Chinese fonts

Character Sizes (2) 8 X 8, 8 X 16, 16 X 16 and 32 X 32 pixel fonts

Font Sizes Width can be expanded 1 to 8 times. Height can be expanded 1/2 and 1 to 8 times.

8 x 8 pixels 40 Char. per row, x 30 rows 80 Char. per row, x 60 rows 100 Char. per row, x 75 rows

128 Char. per row, x 96 rows

8 x 16 pixels 40 Char. per row, x 15 rows 80 Char. per row, x 30 rows 100 Char. per row x 37 rows

128 Char. per row, x 48 rows

16 x 16 pixels 20 Char. per row x 15 rows 40 Char. per row, x 30 rows 50 Char. per row x 37 rows

64 Char. per row, x 48 rows

32 x 32 pixels 10 Char.per row x 7 rows 20 Char. per row x 15 rows 25 Char. per row x 18 rows

32 Char. per row, x 24rows

Specification XBT GT1335 XBT GT2330

XBT GK2330

XBT GT4330

XBT GT4340

XBT GT5330

XBT GT5340

XBT GK5330

XBT GT6330

XBT GT6340

XBT GT7340

Note:

(1) Among backlight units there may be slight variations in illumination color, however, this does not effect the performance or quality of the unit.

(2) The display font will differ depending on which (language) character, or which size you select. Also, if Vijeo Designer 4.3 or later software is used, additional high quality fonts are available with 16x16 or larger characters.

35010372 9/2007 41

Display Viewing Angle and Brightness

Model Viewing angle Brightness

Schneider Upper Lower Left Right Unit Contrast (CR) Actual Products Min Typ Min Typ Min Typ Min Typ Typ Unit

XBT GT1100 20 - 30 - 40 - 40 - degrees CR 2 87/51 cd/m

XBT GT1130

XBT GT1105

XBT GT1135

XBT GT1335

XBT GT2110 20 - 40 - 45 - 45 - degrees CR 2 216 cd/m

XBT GT2120

XBT GT2130

XBT GT2220 - 65 - 70 - 55 - 55 degrees CR 2 298 cd/m

XBT GT2330 60 65 35 40 60 65 60 65 degrees CR 5 422 cd/m

XBT GT4230 - 20 - 40 - 40 - 40 degrees CR 2 167 cd/m

XBT GT4330 - 50 - 70 - 70 - 70 degrees CR 5 213 cd/m

XBT GT4340

XBT GT5230 - 20 - 35 - 45 - 45 degrees CR 2 172 cd/m

XBT GT5330 35 40 55 70 60 70 60 70 degrees CR 10 311 cd/m

XBT GT5340

XBT GT6330 30 50 40 70 45 70 45 70 degrees CR 10 170 cd/m

XBT GT6340

XBT GT7340 60 75 50 55 60 80 60 80 degrees CR 2 220 cd/m

XBT GK2120 20 - 40 - 45 - 45 - degrees CR 2 216 cd/m

XBT GK2330 60 65 35 40 60 65 60 65 degrees CR 5 422 cd/m

XBT GK5330 35 40 55 70 60 70 60 70 degrees CR 10 311 cd/m

42 35010372 9/2007

The definition of viewing angle:

-X -X+X +X

+Y +Y

Lower

Upper

Left Right

-Y -Y

Z Z

35010372 9/2007 43

Memory, Clock, and Touch Panel

Memory

Clock Variations in operating conditions and battery life can cause a clock error from -380 to +90 seconds per month.

Monitor and adjust the time as needed to satisfy the system requirements. For time-dependent applications, refer to the Vijeo-Designer Help for information on synchronizing the unit’s clock with the PLC clock. To preserve processing time, do not synchronize continually. The clocks can be synchronized approximately twice/ day.

Touch Panel and Function Keys

Memory XBT GT1100

XBT GT1130

XBT GT1105

XBT GT1135

XBT GT1335

XBT GT2110 XBT GT2120

XBT GT2130

XBT GT2220

XBT GT2330

XBT GK2120

XBT GK2330

XBT GT4230

XBT GT4330

XBT GT5230

XBT GT5330

XBT GT6330

XBT GK5330

XBT GT4340

XBT GT5340

XBT GT6340

XBT GT7340

Application Flash

EPROM

8 MB 16 MB 16 MB 16 MB 32 MB 32 MB

Data Backup SRAM uses a lithium battery (1)

512 KB 512 KB 128 KB 512 KB 512 KB 512 KB

Application run

DRAM

16 MB 16 MB 32 MB 32 MB 32 MB 64 MB

Legend:

(1) A lithium battery life is:

10 years when the battery's ambient temperature is 40 °C (104 °F.).

10 years when the unit's ambient temperature is 25 °C (77 °F.).

When used for backup (without main power):

Approximately 60 days, with a fully charged battery.

Approximately 6 days, with a 10% charged battery.

Specification XBT GT1000 XBT GT1005/2000/4000/5000/6000/7000 series

Touch panel resolution

8 x 6 matrix 1 or 2 point push, selectable

Analog typing system 1024x1024 resolution, (Single point push selectable)

Function keys 6 -

44 35010372 9/2007

XBT GK

Function Keys

1 Static Function Keys

2 Dynamic Function Keys

Specification XBT GK2000 series XBT GK5000 series Touch panel resolution Analog typing system

1024x1024 resolution, (Single point push selectable)

Analog typing system 1024x1024 resolution, (Single point push selectable)

Static Function keys (Fi) 10 12

Dynamic Function keys (Ri) 14 18

Note: Static keys (Fi) can be customized by printing text or pictograms on the insert labels using label design templates in Vijeo-Designer. Dynamic keys (Ri) can be linked to labels or images on the screen using tools in Vijeo-Designer.

35010372 9/2007 45

Industrial Pointer, Keypads and LEDs

Introduction XBT GK units come with an industrial pointer device and keypads in addition to the touch screen feature. They are useful for environments where touch screen applications are inappropriate. For example, operators who handle abrasive or corrosive material may damage displays due to the residue left on their fingers or gloves. The pointer and keypad provide an alternate method of interacting with the units.

Industrial Pointer Device

The industrial pointer device moves a pointer on the panel. When the pointer is positioned over an object, you can click the pointer button to interact with the object.

Clicking an object with the pointer has the same effect as touching it on the panel with your finger. The pointer changes shape when positioned over an active object or area.

All XBT GK units have 2 pointer buttons. They both have the same effect, so you can use either one, for example, in the case of left-handed or right-handed operators.

An operator can interact with the unit in one of four ways:

Industrial Pointer Device only Touch-screen only Both Neither Touch-screen nor Industrial Pointer Device. Interaction with the unit is only possible through the function keys.

You specify how an operator interacts with the unit in Vijeo-Designer.

Keypads Besides function keys (static and dynamic), XBT GK units come with an alphanumeric keypad to facilitate operator input. The alphanumeric keypad consists of two parts: the cursor keys and the alphanumeric keys.

46 35010372 9/2007

Cursor Keys

Alphanumeric Keys

Key Description Backspace Deletes the digit to the left of the cursor position in a data input field.

Esc Remove the cursor from a data input field without modifying the previous value.

Enter Validate data entered into a data input field.

Clr (Shift + Back Space) Deletes everything in the active data input field.

System (Shift + Esc) Opens the system configuration panel.

Print (Shift + Enter) Takes a snapshot of the current panel. See the SNAPSHOT function in the Vijeo-Designer help.

Increment Sets focus from one object to another in a list of objects Increases or decreases the variable value in a graphical tool or object Increases or decreases the numerical value in a numerical input field

Decrement

Moves the cursor left or right in a data input field.

Key Shift + Key Description

7ABC 7abc Each press of the key cycles through a character that can be entered with that key.

For example, the "7ABC" key:

1 press: input = 7 2 presses: input = A 3 presses: input = B 4 presses: input = C

To get lower case alphabetical characters, hold Shift down while you press the keys.

For example, the "7ABC" key:

shift + 2 presses: input = a shift + 3 presses: input = b shift + 4 presses: input = c

8DEF 8def

9GHI 9ghi

4JKL 4jkl

5MNO 5mno

6PQR 6pqr

1STU 1stu

2VWX 2vwx

3YZ_ 3yz_

0 0

35010372 9/2007 47

Fine Tuning For numerical values in a data input field, use the Increment and Decrement keys on the edition keypad to increase or decrease the value. The fine tuning feature controls the rate at which the value increases or decreases. The following examples show how to use fine tuning with the Increment key, but work exactly the same for the Decrement key as well.

Each press of the Increment key increases the value by one, to the next least significant digit. For example, after a key press, the value 2 increments to 3, after a second key press, the value increments to 4, and so on.

Press and hold the key to increment the value automatically. The value increases by the least significant digit as before.

Continue to hold the key:

After ten increments, the value starts to increase in multiples of 10. For example, the value 12 increments to 22, then 32, then 42, and so on.

After 10 more increments, the value increases in multiples of 100. For example, the value 112 becomes 212, 312, 412, and so on.

10 increments more, and the value increase in multiples of 1000. For example, the value 1112 becomes 2112, 3112, 4112, and so on. This is the highest increment rate.

When you reach the maximum value specified for the data input, the increment key becomes inactive.

Release the Increment key to go back to increasing the value by one. Hold the key again to restart the fine tuning feature.

LEDs Each function key has a corresponding LED. The behavior of the LEDs are programmable at the application level. For example, a LED can start blinking to highlight possible choices or indicate ongoing action as determined by the PLC.

LEDs can light up in one of three colors: orange, red, and green.

LEDs can be in one of four states: off, steady on, blinking (about 1 Hz), fast blinking (>1 Hz).

48 35010372 9/2007

Insert Labels XBT GK

Overview XBT GKs are delivered with an insert label sheet providing the following label types to assign different texts or symbols to the function keys:

function key labels blank labels

All labels are pre-cut and just have to be pressed out of the label sheet.

The ready-to-use function key labels can directly be inserted into the XBT GK as described below (see p. 48).

Printing Insert Labels

You can print our your own text or symbols on the blank labels. Make sure to remove the protective layer from the label sheet before printing. To print your own labels, use Vijeo-Designer and one of the following laser printers:

Laser printer Epson 6200L Copier Lexmark X852e

Inserting Insert Labels

Insert the labels into the device carefully. Make sure that they indicate the correct functions on the panel. The labels can be replaced as needed. The following describes the procedures of inserting insert labels into the XBT GK.

UNINTENDED EQUIPMENT OPERATION

Make sure that the text/symbols on your insert label always correspond to what is configured for the XBT GK in Vijeo Designer. Otherwise the keys of your unit will not initiate the actions indicated on them.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

WARNING

WATER DAMAGE

Be sure to insert the labels properly and slide the flap correctly into the chassis slit.

Do not pinch the flap between the product and the panel.

Failure to follow these instructions can result in injury or equipment damage.

35010372 9/2007 49

Graphical Representation of Correctly Inserting Labels into the XBT GK

50 35010372 9/2007

Inserting Labels into the XBT GK Step Action

1 Press the pre-cut insert label of your choice out of the insert label sheet.

2 Remove the XBT GK from any enclosures or mounts. Take the XBT GK and turn it around so that you can see its rear panel. At the bottom two corners of the rear panel, located directly behind the overlapping display, you will find the opening for the insert label.

3 Insert the insert label cautiously into this opening (as shown in the above figure) until the key symbols / texts on the wide part of the insert labels have disappeared and the wide part of the insert label is flush with the opening. There will be merely the small flap of the insert label with the double arrow being visible outside the unit.

4 Turn the XBT GK around and check the front that all symbols / texts are clearly visible at the keys. If the texts / symbols are not clearly visible, insert the insert label a bit further into the opening.

5 If the texts / symbols are clearly visible on the front of the unit, take the small part (with the double arrow sign) of the insert label that is still visible on the rear of the unit and slide this flap into the slit. The flap should now be flush with the rear of the unit.

If the insert label has not correctly been inserted into the XBT GK, the flap of the insert label will be too long to fit into this slit.

35010372 9/2007 51

Serial Interface

Introduction All XBT GT and XBT GK displays are provided with a serial interface and tool port or USB Interface.

Serial Tool Port The following table describes the tool port of XBT GT1100/1130

Serial Interface

COM1

The following table describes the serial interface COM1 of XBT GT1100/1130 and 1005 series units.

The following table lists the serial interface COM1 of XBT GT2000/4000/5000/6000/ 7000 and XBT GK series units.

Interface Description

Tool Port Asynchronous TTL level nonprocedural interface command Used for transferring data user program to and from Vijeo Designer and

XBT GT.

Interface Description

Serial interface COM1 RJ45

Asynchronous Transmission RS232C / RS485

Data Length 7 or 8 bits

Stop Bit 1 or 2 bits

Parity None, odd or even

Data Transmission Speed 2,400 to 115,200 bps

Interface Description

Serial interface COM1 D-Sub9

Asynchronous Transmission RS232C/RS422-485

Data Length 7 or 8 bits

Stop Bit 1 or 2 bits

Parity None, odd or even

Data Transmission Speed 2,400 to 115,200 bps

52 35010372 9/2007

Serial Interface

COM2

The following table lists the serial interface COM2 of XBT GT2000/4000/5000/6000/ 7000 and XBT GK series units.

Ethernet Interface

The following table lists the serial interface Ethernet available for XBT GT series and XBT GK series:

USB Interface and Memory Card

The following table lists the serial interface USB and memory card available for XBT GT and XBT GK series:

Interface Description

Serial interface COM2 RJ45

Asynchronous Transmission RS485

Data Length 7 or 8 bits

Stop Bit 1 or 2 bits

Parity None, odd or even

Data Transmission Speed 2,400 bps to 187.5Kbps

Interface Description Ethernet RJ45 IEEE802.3, 10Base-T/100Base-TX (except for XBT GT1100/1105/2110/

2120/2220 and XBT GK2120: none, and XBT GT1130: 10Base-T.)

Interface Description

USB TYPE-A x 1 USB 1.1 host I/F

CF card slot (TYPE-II (except XBT

GT1100/1130/1105/1135/1335/2110)

Compact Flash

35010372 9/2007 53

3.3 Interface Specifications

At a Glance

Overview This section presents the interface specifications of the units.

What's in this Section?

This section contains the following topics:

Topic Page Specifications of Serial Interface COM1 54

Specifications of Serial Interface COM2 58

Other Interfaces 59

54 35010372 9/2007

Specifications of Serial Interface COM1

Introduction This interface is used to connect:

XBT GT1000/1005 series to remote equipment, via an RS232C or RS485 cable.

The connector used is a RJ45-type connector.

XBT GT2000/4000/5000/6000/7000 series to remote equipment, via an RS232C or RS422-485 cable. The connector used is a 9-pin SUB-D connector.

XBT GK series to remote equipment, via an RS232C or RS422-485 cable. The connector used is a 9-pin SUB-D connector.

When using a long PLC cable to connect to the unit, it is possible the cable can be at a different electrical potential than the unit, even if both are connected to ground.

The unit’s serial port is not isolated. The SG (signal ground) and the FG (frame ground) terminals are connected inside the unit.

ELECTRIC SHOCK

When connecting an external device to the unit with the SG terminal, be sure to check that no short-circuit loop is created when you setup the system.

Connect the #8 SG terminal to remote equipment when the host (PLC) unit is not isolated. To reduce the risk of damaging the RS232C/RS485 circuit, make sure to connect the #8 SG terminal to the appropriate equipment.

Failure to follow these instructions will result in death or serious injury.

DANGER

35010372 9/2007 55

XBT GT1100/

1130 Serial Interface COM1

This interface is used to connect a RS-232C/RS485 serial cable. An RJ45 8-pin plug connector is used.

Any excessive weight or stress on communication cables may cause an equipment’s disconnection and unintended equipment operation.

Pin Connection Pin Signal Name Direction Meaning

1 RXD Input Receive Data

(RS232C)

2 TXD Output Send Data

(RS232C)

3 Not connected - -

4 D1 Output/Input Transfer Data

(RS485)

5 D0 Output/Input Transfer Data

(RS485)

6 RTS Output Request To Send

7 Not connected - -

8 SG - Signal Ground

LOSS OF…