Install pressure relief valve
Install pressure relief valve
CURRENT GENERATOR MUST REMAIN IN SERVICE BETWEEN DECEMBER
1st AND MAY 1st OR NEWLY INSTALLED GENERATOR MUST BE IN SERVICE PRIOR TO DECEMBER 1st.
Provide removed generator to NPS.
T
T
11 7
IRH-2
IRH-3
Emergency shutdown - Provide 10A fuse at generator battery. Provide ¾” conduit with 3#12 from battery to LPT-1 at building. Provide ¾” conduit with 3#12 from LPT-1 at building to LPT-1 at tank. Provide ¾” conduit with 3#12 from LPT-1 at tank to solenoid near PRV-2 at tank (For location of LPT-1 and generator refer to sheet M3. For location of PRV-2 refer to detail 1 on sheet M8). Each LPT-1 emergency stop button shall be rated NEMA 4 and shall have a normally closed contact. Emergency stop buttons shall be wired in series with PRV-2 solenoid to open solenoid on loss of power.