Drawings for Question 7 of Q A
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Emergency shutdown - Provide 10A fuse at generator battery. Provide ¾” conduit with 3#12 from battery to LPT-1 at building. Provide ¾” conduit with 3#12 from LPT-1 at building to LPT-1 at tank. Provide ¾” conduit with 3#12 from LPT-1 at tank to solenoid near PRV-2 at tank (For location of LPT-1 and generator refer to sheet M3. For location of PRV-2 refer to detail 1 on sheet M8). Each LPT-1 emergency stop button shall be rated NEMA 4 and shall have a normally closed contact. Emergency stop buttons shall be wired in series with PRV-2 solenoid to open solenoid on loss of power.