This pre-solicitation notice describes a federal construction contract opportunity with the Department of Veterans Affairs. The contract is for construction and renovation services at the Robert J. Dole VA Medical Center in Wichita, Kansas. Services include vertically expanding an existing building by two stories and renovating patient rooms in another building. The general scope of work involves structural work, MEP systems installation and replacement, interior finishes, medical equipment setup, and other construction and renovation activities according to provided drawings and specifications. The period of performance is 730 calendar days from notice to proceed. The project cost range is between $5-10 million. The solicitation will utilize the best value lowest price technically acceptable source selection process. The NAICS code is 236220 and it is a total SDVOSB set-aside. The solicitation package will be available on October 20, 2020 with proposals due approximately 30 days after issuance. Interested parties should monitor the specified website and attend the scheduled site visit.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ROOF PLAN GENERAL NOTES
A
B
C
D
E
F
G
ROOF PLAN NOTES #
ROOFING SUPPLIERS, MANUFACTURERS, & INSTALLERS SHALL REVIEW ALL
ROOFING DETAILS & ADVISE THE ARCHITECT ON ANY RECOMMENDED
CHANGES.
UNLESS NOTIFIED OTHERWISE, ROOFING SUPPLIERS, MANUFACTURERS
AND INSTALLERS WILL BE ASSUMED TO HAVE REVIEWED AND APPROVED
THE DETAILS SHOWN.
PROVIDE FLASHING AND SEALANT PER ROOFING MANUFACTURER
RECOMMENDATION AT ALL CONDUIT & HVAC LINES PENETRATING THE
ROOF.
CONTRACTOR & ALL SUBTRADES SHALL BE AWARE & EXERCISE THE
NECESSARY CARE TO PREVENT DAMAGE TO OR PUNCTURE OF THE ROOF.
THIS SHALL INCLUDE ALL MATERIALS, TOOLS, DELETERIOUS MATERIALS.
REFERENCE STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION AND
ELECTRICAL FOR ITEMS. COORDINATE AS REQUIRED INCLUDING
NECESSARY FRAMING, BLOCKING, ETC.
VERIFY EXISTING FIELD CONDITIONS PRIOR TO BEGINNING WORK, AND
REPORT DISCREPANCIES IMMEDIATELY
REMOVE EXISTING ROOFING MATERIAL AND SAW CUT ROOF DECK AS
REQUIRED FOR INSTALLATION OF NEW EXHAUST FANS.
TAPERED ROOF INSULATION - 1/4" PER FT.
ROOF SCUPPER AND DOWNSPOUT. REFER TO DETAL 4/AE201.
FULLY ADHERED WHITE TPO ROOFING MEMBRANE AND ASSEMBLY, SLOPE
@ 1/4" PER FT.
30' X 30" WALK PADS.
EXISTING MECHANICAL EQUIPMENT TO BE REINSTALLED ON NEW ROOF.
SEE MECHANICAL DRAWINGS.
PROVIDE PIPE PORTAL, SEE MECHANICAL DRAWINGS.
CLEARANCE AREA FOR RTU OUTSIDE AIR INTAKE.
2ND FLOOR
ADDITION
SHADE INDICATES
EXISTING AREA BEYOND
PRIMARY SCOPE OF
WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR
ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
AE201
AE201
AE311
AE301
REMOVABLE
ROOF PANEL
AE301
AE301
AE321
AE105
AE105
7HIGH
LOW
AE105
AE105
HIGH
LOW
1/4":12"
1/4":12"
1/4":12"
8 AE105
AE105
TYP.
TYP.
1C-RTU
1C-CU1
1C-CU2
EXISTING 4TH FLOOR
TO REMAIN
EXISTING 4TH FLOOR
TO REMAIN
8" M
IN
GASKET
SHEET METAL COVER
SURFACED CAP SHEET
INTERPLY
3/4" PROTECTION BOARD
6" MIN TAPERED RIGID INSULATION
WOOD BLOCKING
CANT STRIP
ROOFING MEMBRANE
METAL DECK
RE: STRUCTURAL
3/4" COVER BOARD
6" MIN TAPERED RIGID
INSULATION
WOOD BLOCKING
METAL DECK,
RE: STRUCTURAL
INTERPLY
ROOFING MEMBRANE
CAPPED, GASKETED
FASTENERS
SLOPE PIPE AWAY FROM
HOOD,
RE: MECHANICAL
SHEET METAL ENCLOSURE
2"
EXISTING
CONSTRUCTION
NEW COPING
EXISTING STONE BANDING BELOW TO REMAIN.
WHERE BANDING INTERFERES WITH NEW
CONSTRUCTION, REMOVE A PORTION TO
ACCOMMODATE
NEW STONE
BANDING BELOW
ROOF SURFACE
2" BELLOWS EJ COVER. TO EXTEND UP
ADJACENT EXISTING CONSTRUCTION AND
UNDER NEW PARAPET COPING
2" BELLOWS EJ COVER. TO EXTEND UP
ADJACENT EXISTING CONSTRUCTION AND
UNDER NEW PARAPET COPING
EXISTING
CONSTRUCTION
EXISTING STONE BANDING BELOW TO REMAIN.
WHERE BANDING INTERFERES WITH NEW
CONSTRUCTION, REMOVE A PORTION TO
ACCOMMODATE
NEW STONE BANDING BELOW
ROOF SURFACE
2"
2" BELLOWS EJ COVER. TO EXTEND UP
ADJACENT EXISTING CONSTRUCTION AND
UNDER NEW PARAPET COPING
1/4"
FIRE SAFING
INSULATION
FACE BRICK VENEER TO MATCH EXISTING SIZE AND
COURSING
(1) LAYER 5/8"
EXTERIOR
SHEATHING AND
(2) LAYERS 5/8"
TYPE 'X' GWB
(INTERIOR SIDE)
ON 6" MTL STUDS
@ 16"O.C.
FLUID APPLIED AIR BARRIER
FOIL FACED BATT INSULATION R-13 MIN.
MASONRY TIES
RIGID CONT. INSULATION R-13 MIN.
5 3 /4"
1'
- 4
1/ 4"
1'
- 1
0"
ROOF MEMBRANE
NEW STONE
COPING
NEW STONE
BANDING BELOW
EXISTING GUTTER
TO REMAIN
ROOF SURFACE
NEW METAL
COPING
STEP DOWN BELOW
GUTTER TO MEET
NEW WALL. SEE
4/AE301.
ROOF SURFACE
NEW STONE
BANDING BELOW
2" BELLOWS EJ
COVER. TO EXTEND
UP ADJACENT
EXISTING
CONSTRUCTION AND
UNDER NEW
PARAPET COPING
2"
FIRE SAFING
INSULATION
2' - 0"
1' - 4 1/4" 7 3/4"FACE BRICK VENEER TO
MATCH EXISTING SIZE
AND COURSING
(1) LAYER 5/8" EXTERIOR
SHEATHING AND (2) LAYERS 5/8"
TYPE 'X' GWB (INTERIOR SIDE) ON
6" MTL STUDS @ 16"O.C.
FLUID APPLIED AIR
BARRIER FOIL FACED BATT INSULATION
R-13 MIN.
MASONRY TIES
RIGID CONT. INSULATION
R-13 MIN.
ROOF MEMBRANE
BEYOND PROJECT BOUNDARY, NIC
ARCHITECTURAL ROOF PLAN LEGEND
ROOF EXHAUST FAN C.U. = CONDENSING UNIT
ROOF WALKING PAD
R.T.U. = ROOF TOP UNIT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE105
4TH FLOOR AND ROOF PLAN
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317)-800-6388
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
(502)-326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1" = 100'-0"
KEYPLAN ISOMETRIC
SCALE: 1/8" = 1'-0"AE105
1 4TH FLOOR AND ROOF PLAN
SCALE: 1 1/2" = 1'-0"AE105
4 TYPICAL ROOF CURB DETAIL
SCALE: 1 1/2" = 1'-0"AE105
5 TYPICAL THROUGH ROOF PIPING DETAIL
SCALE: 1 1/2" = 1'-0"AE105
6 ROOF CONNECTION TO ELEVATOR DETAIL - HIGH
SCALE: 1 1/2" = 1'-0"AE105
7 ROOF CONNECTION TO ELEVATOR DETAIL - LOW
SCALE: 1 1/2" = 1'-0"AE105
8 ROOF CONNECTION @ SLOPE DETAIL - HIGH
SCALE: 1 1/2" = 1'-0"AE105
9 ROOF CONNECTION @ SLOPE DETAIL - LOW
NOT TO SCALEAE105
3 PERSPECTIVE @ ROOF - EAST
NOT TO SCALEAE105
2 PERSPECTIVE @ ROOF - SOUTH
AE301
AE311
AE321
AE321
SIM.
AE321
AE321
Revisions: Date:
REFLECTED CEILING PLAN GENERAL NOTES
REFLECTED CEILING PLAN SPECIFIC NOTES
MODIFY EXISTING CEILING GRID AND TILE INTO NEW AREA FOR A SEAMLESS
TRANSITION.
ADJUST LOCATION OF CURVED CEILING BULKHEAD AS REQUIRED TO MAINTAIN
INDICATED RELATIONSHIP TO COLUMN CENTERLINES AS INDICATED.
COORDINATE WITH COR AND ARCHITECT.
APPROXIMATE LOCATION OF CENTER OF RADIUS OF INDICATED ELEMENTS.
ALIGN EDGES OF BULKHEADS AS INDICATED.
REFER TO DETAIL 2/AE111 FOR BULKHEAD CONDITION.
NO CEILING IN THIS AREA.
SEE MEP DRAWINGS FOR ABOVE CEILING WORK. CONTRACTOR IS REQUIRED
TO REMOVE PORTIONS OF CEILINGS AS REQUIRED TO ACCOMMODATE
DEMOLITION AND NEW WORK, AND PROVIDE NEW CEILINGS AND FINISH TO
MATCH EXISTING EXACTLY UPON COMPLETION OF ABOVE CEILING WORK.
MATCH TYPICAL PATIENT ROOM CEILING 9/AE501.
PROVIDE BULKHEAD ABOVE CABINETS.
PROVIDE ACCESS PANEL, COORDINATE EXACT LOCATION WITH ENGINEERING
DRAWINGS AND VA.
A
B
C
D
E
F
G
H
THE ARCHITECTURAL REFLECTED CEILING PLAN SHALL GOVERN THE LAYOUT
OF ALL CEILING ELEMENTS, HEIGHTS AND/OR PENETRATIONS. COORDINATION
OF THE ARCHITECTURAL AND ENGINEERING ELEMANTS ARE THE
RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS TO VERIFY FIELD
CONDITIONS AND REPORTS ANY DISCREPANCIES TO ARCHITECT AND COR.
SHOWN SIZES OF MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT ARE
FOR REFERENCE ONLY. REFER TO ENGINEERING PLANS FOR ADDITIONAL
INFORMATION. COORDINATE SCOPE OF WORK WITH ENGINEERING DRAWINGS,
UNLESS OTHERWISE NOTED.
ACOUSTIC PANEL CEILING SHALL BE CENTERED IN THE ROOM AND INSTALLED
TO ELIMINATE NARROW CUT STRIPS OF PANELS ALONG THE EDGES OF WALLS
AND BULKHEADS, UNLESS OTHERWISE NOTED. COORDINATE WITH THE
LIGHTING LAYOUT. THE LIGHTING SHALL BE CENTERED IN ROOMS.
CEILING MOUNTED ITEMS (SPRINKLER HEADS, MOUNTING DEVICES, ETC.)
SHALL BE CENTERED IN THE CEILING PANELS UNLESS NOTED OTHERWISE.
ABOVE CEILING WORK REQUIRED BEYOND THE SCOPE OF THE WORK SHALL BE
COORDINATED WITH PATIENT SAFETY, INFECTION CONTROL, AND COR.
CEILING TILE REMOVED IN ORDER TO COMPETE ABOVE CEILING WORK SHALL
BE STORED IN A SAFE DRY LOCATION. DAMAGED OR BROKEN CEILING TILES
SHALL BE REPLACED. DRYWALL CEILINGS SHALL BE PATCHED, PREPPED AND
NEW FINISH APPLIED TO MATCH EXISTING.
REFER TO FINISHES SHEETS AND SPECIFICATIONS FOR INFORMATION ON
GYPSUM BOARD PAINT FINISH.
WHERE NEW CEILINGS ARE INSTALLED AND SPRINKLERS ARE EXISTING TO
REMAIN, SPRINKLERS SHALL BE ADJUSTED TO NEW CEILING HEIGHTS, WHEN
APPLICABLE.
A
TYPE GRAPHIC DESCRIPTION
B 2x2 ACOUSTICAL CEILING TILE (AP2)
GYPSUM BOARD CEILING. CEILING PAINT.
REFLECTED CEILING PLAN LEGEND
C 2x4 ACOUSTICAL WASHABLE GASKETED
CEILING TILE (AP1)
PT-9A
1' - 6"
1'
- 6
1'
- 6
CHASE
PT-9A
2ND FLOOR
ADDITION
SHADE INDICATES
EXISTING AREA BEYOND
PRIMARY SCOPE OF
WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR
ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
2'
- 0
1"
5/8" GYPSUM
BOARD
3 5/8" METAL
STUD @ 16" O.C.
CEILING (AP-1) - SEE
REFLECTED CEILING
PLANS
EXISTING WINDOW
EXISTING STRUCTURE
1' - 5"
8"
6" M
IN
VA
RI
ES
2 1/2" METAL STUD BRACING ON BOTH
SIDES AT 48" O.C. - MIN. 3 LOCATIONS.
ANCHOR TO STRUCTURE ABOVE
5/8" TYPE "X" GYPSUM BOARD
4 7/8"
3-5/8" METAL STUD FRAMING AT 16"
O.C. ANCHOR TO STRUCTURE ABOVE
BOTTOM OF BULKHEAD
VARIES
BOTTOM OF CEILING
VARIES
REFER TO REFLECTED CEILING PLAN
VARIES
2 1/2" METAL STUD BRACING AT 32"
O.C. ANCHOR TO STRUCTURE ABOVE
5/8" TYPE "X" GYPSUM
BOARD
3-5/8" METAL STUD FRAMING AT 16"
O.C. ANCHOR TO STRUCTURE ABOVE
TYPICAL WALL CONSTRUCTION,
RE: FLOOR PLAN AND WALL
TYPES FOR ADDITIONAL
INFORMATION
BOTTOM OF BULKHEAD
VARIES
BOTTOM OF CEILING
VARIES
A
CT
O
NL
Y
6" M
IN
VA
RI
ES
2 1/2" METAL STUD BRACING AT 32"
O.C. ANCHOR TO STRUCTURE
ABOVE
5/8" TYPE "X" GYPSUM
BOARD
3-5/8" METAL STUD FRAMING AT 16"
O.C. ANCHOR TO STRUCTURE
ABOVE
VA
RI
ES
6"
M
IN
REFER TO REFLECTED CEILING PLAN
VARIES
BOTTOM OF BULKHEAD
VARIES
BOTTOM OF CEILING
VARIES
5/8" TYPE "X" GYPSUM BOARD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE111
2ND FLOOR CEILING PLAN
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317)-800-6388
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
(502)-326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1/8" = 1'-0"AE111
1 2ND FLOOR CEILING PLAN
SCALE: 1" = 100'-0"
KEYPLAN ISOMETRIC
SCALE: 1 1/2" = 1'-0"AE111
2 TYPICAL IN-ROOM BULKHEAD AT WINDOW
SCALE: 1 1/2" = 1'-0"AE111
3 TYPICAL BULKHEAD DETAIL - SINGLE STUD
SCALE: 1 1/2" = 1'-0"AE111
4 TYPICAL BULKHEAD DETAIL
SCALE: 1 1/2" = 1'-0"AE111
5 TYPICAL BULKHEAD DETAIL
J
REFLECTED CEILING PLAN GENERAL NOTES
REFLECTED CEILING PLAN SPECIFIC NOTES
MODIFY EXISTING CEILING GRID AND TILE INTO NEW AREA FOR A SEAMLESS
TRANSITION.
ADJUST LOCATION OF CURVED CEILING BULKHEAD AS REQUIRED TO MAINTAIN
INDICATED RELATIONSHIP TO COLUMN CENTERLINES AS INDICATED.
COORDINATE WITH COR AND ARCHITECT.
APPROXIMATE LOCATION OF CENTER OF RADIUS OF INDICATED ELEMENTS.
ALIGN EDGES OF BULKHEADS AS INDICATED.
REFER TO DETAIL 2/AE111 FOR BULKHEAD CONDITION.
NO CEILING IN THIS AREA.
SEE MEP DRAWINGS FOR ABOVE CEILING WORK. CONTRACTOR IS REQUIRED
TO REMOVE PORTIONS OF CEILINGS AS REQUIRED TO ACCOMMODATE
DEMOLITION AND NEW WORK, AND PROVIDE NEW CEILINGS AND FINISH TO
MATCH EXISTING EXACTLY UPON COMPLETION OF ABOVE CEILING WORK.
MATCH TYPICAL PATIENT ROOM CEILING 9/AE501.
PROVIDE BULKHEAD ABOVE CABINETS.
PROVIDE ACCESS PANEL, COORDINATE EXACT LOCATION WITH ENGINEERING
DRAWINGS AND VA.
A
B
C
D
E
F
G
H
THE ARCHITECTURAL REFLECTED CEILING PLAN SHALL GOVERN THE LAYOUT
OF ALL CEILING ELEMENTS, HEIGHTS AND/OR PENETRATIONS. COORDINATION
OF THE ARCHITECTURAL AND ENGINEERING ELEMANTS ARE THE
RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS TO VERIFY FIELD
CONDITIONS AND REPORTS ANY DISCREPANCIES TO ARCHITECT AND COR.
SHOWN SIZES OF MECHANICAL, ELECTRICAL AND PLUMBING EQUIPMENT ARE
FOR REFERENCE ONLY. REFER TO ENGINEERING PLANS FOR ADDITIONAL
INFORMATION. COORDINATE SCOPE OF WORK WITH ENGINEERING DRAWINGS,
UNLESS OTHERWISE NOTED.
ACOUSTIC PANEL CEILING SHALL BE CENTERED IN THE ROOM AND INSTALLED
TO ELIMINATE NARROW CUT STRIPS OF PANELS ALONG THE EDGES OF WALLS
AND BULKHEADS, UNLESS OTHERWISE NOTED. COORDINATE WITH THE
LIGHTING LAYOUT. THE LIGHTING SHALL BE CENTERED IN ROOMS.
CEILING MOUNTED ITEMS (SPRINKLER HEADS, MOUNTING DEVICES, ETC.)
SHALL BE CENTERED IN THE CEILING PANELS UNLESS NOTED OTHERWISE.
ABOVE CEILING WORK REQUIRED BEYOND THE SCOPE OF THE WORK SHALL BE
COORDINATED WITH PATIENT SAFETY, INFECTION CONTROL, AND COR.
CEILING TILE REMOVED IN ORDER TO COMPETE ABOVE CEILING WORK SHALL
BE STORED IN A SAFE DRY LOCATION. DAMAGED OR BROKEN CEILING TILES
SHALL BE REPLACED. DRYWALL CEILINGS SHALL BE PATCHED, PREPPED AND
NEW FINISH APPLIED TO MATCH EXISTING.
REFER TO FINISHES SHEETS AND SPECIFICATIONS FOR INFORMATION ON
GYPSUM BOARD PAINT FINISH.
WHERE NEW CEILINGS ARE INSTALLED AND SPRINKLERS ARE EXISTING TO
REMAIN, SPRINKLERS SHALL BE ADJUSTED TO NEW CEILING HEIGHTS, WHEN
APPLICABLE.
A
TYPE GRAPHIC DESCRIPTION
B 2x2 ACOUSTICAL CEILING TILE (AP2)
GYPSUM BOARD CEILING. CEILING PAINT.
REFLECTED CEILING PLAN LEGEND
C 2x4 ACOUSTICAL WASHABLE GASKETED
CEILING TILE (AP1)
2ND FLOOR
ADDITION
SHADE INDICATES
EXISTING AREA BEYOND
PRIMARY SCOPE OF
WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR
ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
AE112
AE112
TYP.
5 5
PT-9A
PT-9A
PT-7 PT-7
PT-1
PT-1
PT-1
PT-4
PT-4
PT-4
PT-9A
PT-9A
PT-7
PT-7
PT-7
PT-7
PT-7
PT-9A PT-9A
PT-1
PT-1
PT-1
PT-1
PT-4
PT-9A
PT-4
PT-9A
PT-9A
PT-9A
PT-9A
PT-1
PT-3
PT-3
PT-4
PT-4
PT-7
PT-7
PT-7
PT-7
PT-7
PT-1
PT-9A
PT-7
PT-4
AE111
TYP.
AE112
AE112
AE501
CHASE
7' - 2"
PT-1
PT-1
PT-1
AE804
3'
- 0
PT-3
PT-4
3' - 0"
1/
4" 4'
- 2 1/
2"
10' - 8" 3' - 1 3/4"
EQ
EQ
3' - 0
5'
- 8
3/ 4"
1'
- 0
4' - 2" 2' - 1" 2' - 2"
5'
- 5
3/ 4"
9' - 3 3/4"
EQ
EQ 3' - 0"
PT-4
PT-3
10 3/4"
1" 1'
- 6
1' - 5"
5/8" GYPSUM
BOARD
3 5/8" METAL
STUDS @ 16" O.C.
CEILING (AP-1) -
SEE
REFLECTED
CEILING PLANS
EXISTING WINDOW
EXISTING
STRUCTURE
8"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE112
3RD FLOOR CEILING PLAN
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317)-800-6388
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
(502)-326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1" = 100'-0"
KEYPLAN ISOMETRIC
SCALE: 1/8" = 1'-0"AE112
1 3RD FLOOR CEILING PLAN
SCALE: 1/4" = 1'-0"AE112
2 ENLARGED CEILING PLAN - ABOVE NURSE STATION 1
SCALE: 1/4" = 1'-0"AE112
3 ENLARGED CEILING PLAN - ABOVE NURSE STATION 2
SCALE: 1 1/2" = 1'-0"AE112
4 CEILING BULKHEAD AT CORRIDOR
EXTERIOR ELEVATION LEGEND
DESCRIPTIONCODE
FACE BRICK TO MATCH EXISTING, SEE SPECIFICATIONS.
PROVIDE MR-1.
BR-1
QUIONS TO MATCH EXISTINGQU-1
CAST STONE BANDING TO MATCH EXISTINGCS-1
EXISTING ARCHITECTURAL METAL PANEL, USED TO
PATCH/REPAIR AS REQUIRED, OR FOR BID DEDUCT SEE GI102.
MP-1
CONTROL JOINT LOCATION, VERIFY IN FIELD EXACT LOCATIONCJ
2" BELLOWS TYPE EXPANSION JOINT LOCATIONEJ
AE301
EX
IS
TI
NG
AD
DI
TI
ON
EXISTING ADDITION
BR-1
BR-1
QU-1, TYP.
CS-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
± 4' - 6"± 18' - 8"± 18' - 8"± 4' - 6"
CJ CJ CJEJ
TOOTH IN NEW
BRICK WHERE
WINDOWS WERE
REMOVED
AE301
AE301
EX
IS
TI
NG
AD
DI
TI
ON
BR-1
BR-1
QU-1, TYP.
CS-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
W-1
STRUCTURAL
BRACE
LOCATIONS,
REFER TO
DETAIL
5/AE322
± 16' - 0" ± 4' - 8" ± 20' - 0"
CJ CJCJ
EJ
AD301
2ND FLOOR
ADDITION
SHADE INDICATES
EXISTING AREA BEYOND
PRIMARY SCOPE OF
WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR
ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
FACE BRICK VENEER TO MATCH
EXISTING SIZE AND COURSING
5/8" GLASS MAT FACED GYPSUM
SHEATHING
FLUID APPLIED AIR BARRIER
MASONRY TIES
RIGID CONT. INSULATION
R-13 MIN.
1' - 3"
TOP OF COPING
143' - 5 1/2"
2' - 0"
PROFILED STONE BAND.
MATCH EXISTING STONE BAND
5/8" GLASS MAT FACED
GYPSUM SHEATHING
6" METAL STUDS @16" O.C.
6" MIN. TAPERED RIGID
INSULATION SLOPED 1/4" PER
FOOT TO SCUPPER(R-30 MIN.)
PROTECTION BOARD
STRUCTURAL DECK,
SEE STRUCTURAL
DRAWINGS. PROVIDE 2
HR RATING, +/-2 1/4"
THICKNESS OF SPRAY
APPLIED FIRE
RESISTIVE MATERIAL
BASIS OF DESIGN UL
P701
STRUCTURAL BEAM,
SEE STRUCTURAL
DRAWINGS
2'
- 8
TOP OF BRICK
142' - 8 1/2"
PROFILED STONE COPING.
MATCH EXISTING
METAL FLASHING
FULLY ADHERED
MEMBRANE ROOFING
SYSTEM
TERMINATION BAR AND
SEALANT
1' - 7 1/4"
CONTINUOUS 2X FRT
WOOD BLOCKING
EXTEND ROOFING
MEMBRANE UP AND
OVER WOOD BLOCKING
8 3 /4"
(2) LAYERS 5/8" TYPE X GYPSUM
BOARD ON 6" METAL STUDS @ 16 O.C.
PINS (MIN) 3 PER STONE
COPING SECURED TO WOOD
BLOCKING
7 3 /4"
SCUPPER
CONTINUOUS
SEALANT
METAL COUNTER FLASHING
METAL SCUPPER SLEEVE
WITH DRIP EDGE
ALUMINUM
DOWNSPOUT
1' - 4"6 3 /4"
FACE BRICK VENEER TO MATCH
EXISTING SIZE AND COURSING
5/8" GLASS MAT FACED GYPSUM
SHEATHING
FLUID APPLIED AIR BARRIER
MASONRY TIES
RIGID CONT. INSULATION
R-13 MIN.
1' - 3"
TOP OF COPING
143' - 5 1/2"
2' - 0"
PROFILED STONE BAND.
MATCH EXISTING STONE BAND
5/8" GLASS MAT FACED
GYPSUM SHEATHING
6" METAL STUDS @16" O.C.
6" MIN. TAPERED RIGID
INSULATION SLOPED 1/4" PER
FOOT TO SCUPPER(R-30 MIN.)
PROTECTION BOARD
STRUCTURAL DECK,
SEE STRUCTURAL
DRAWINGS. PROVIDE 2
HR RATING, +/-2 1/4"
THICKNESS OF SPRAY
APPLIED FIRE
RESISTIVE MATERIAL
BASIS OF DESIGN UL
P701
STRUCTURAL BEAM,
SEE STRUCTURAL
DRAWINGS
2'
- 8
TOP OF BRICK
142' - 8 1/2"
PROFILED STONE COPING.
MATCH EXISTING
METAL FLASHING
FULLY ADHERED
MEMBRANE ROOFING
SYSTEM
TERMINATION BAR AND
SEALANT
1' - 7 1/4"
CONTINUOUS 2X FRT
WOOD BLOCKING
EXTEND ROOFING
MEMBRANE UP AND
OVER WOOD BLOCKING
8 3 /4"
(2) LAYERS 5/8" TYPE X GYPSUM
BOARD ON 6" METAL STUDS @ 16 O.C.
PINS (MIN) 3 PER STONE
COPING SECURED TO WOOD
BLOCKING
7 3 /4"
CONTINUOUS
SEALANT
METAL COUNTER FLASHING
METAL OVERFLOW SCUPPER
SLEEVE WITH DRIP EDGE,
INSTALL 2" ABOVE SCUPPER
LINE FLOW
1' - 4"
6 3 /4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE201
BUILDING ELEVATIONS
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317)-800-6388
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
(502)-326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1/8" = 1'-0"AE201
1 BUILDING ELEVATION - NORTH
SCALE: 1/8" = 1'-0"AE201
2 BUILDING ELEVATION - WEST
SCALE: 1" = 100'-0"
KEYPLAN ISOMETRIC
NOT TO SCALEAE201
3 PERSPECTIVE MASSING - NEW
SCALE: 1 1/2" = 1'-0"AE201
4 WALL SECTION DETAIL - PARAPET SCUPPER AND DOWNSPOUT
SCALE: 1 1/2" = 1'-0"AE201
5 WALL SECTION DETAIL - PARAPET OVERFLOW SCUPPER
AE311
EXISTING 1ST FLOOR TO REMAIN
EXISTING RENOVATED 2ND FLOOR
EXISTING RENOVATED 3RD FLOOR
AE311
AE301
AE301
AE321
10 AE311
TYP.
AE311
NEW METAL COPING
NEW STONE COPING
BUILDING
ADDITION
EXISTING
BUILDING
EXPANSION JOINT
EXPANSION JOINT
EXISTING
BUILDING
BUILDING
ADDITION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE301
BUILDING SECTIONS
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317)-800-6388
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
(502)-326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1/8" = 1'-0"AE301
1 EAST/WEST BUILDING SECTION 1
SCALE: 1/8" = 1'-0"AE301
3 NORTH/SOUTH BUILDING SECTION
SCALE: 1/8" = 1'-0"AE301
2 EAST/WEST BUILDING SECTION 2
NOT TO SCALEAE301
4 BUILDING CONNECTION ISOMETRIC
NOT TO SCALEAE301
5 BUILDING CONNECTION ISOMETRIC 2
AE321
AE321
EXISTING
1ST FLOOR
TOP OF COPING
143' - 4 3/4"
AE321
4" FRAME DEPTH ARCHITECTURAL
GRADE EXTERIOR WINDOW W/
INSULATED GLAZING, SEE
ELEVATIONS, TYP.
AE321
TYP.
AE321
TYP.
AE201
AE201
ALIGN FACE OF NEW
BRICK WITH FACE OF
EXISTING BELOW
SIM.
SIM.
EXISTING
1ST FLOOR
EXISTING
1ST FLOOR
NEW COMPRESSIVE
INSULATION
EXISTING STRUCTURAL
ELEMENTS
NEW METAL DECK, RE:
STRUCTURAL
AE321
AE321
TOP OF EXISTING COPING
+/- 143' - 4 3/4"
EXISTING
STRUCTURE
NEW STRUCTURAL DECK, SEE
STRUCTURAL DRAWINGS
CONTINUOUS COMPRESSIBLE
INSULATION AT EJ PERIMETER
2 HR. EXPANSION JOINT
COVER - BASIS OF DESIGN
AL-200HD BY CONSTRUCTION
SPECIALTIES
CEILING, SEE
CEILING PLANS
FOR TYPES AND
LOCATIONS
2 HR. CEILING EXPANSION JOINT
COVER
WALL EXPANSION
JOINT COVER
BEYOND
AE321
PROVIDE NEW JOINT COVER
IN EXISTING SLABS
NEW STEEL SUPPORT
ANGLE ACROSS NEW
OPENING AND SET INTO
BRICK EITHER SIDE,
REFER TO STRUCTURAL
EXISTING BRICK VENEER
9 1 /2"
AP
PR
OX
IM
AT
E
EXISTING
1ST FLOOR
EXISTING
1ST FLOOR
AE321
TYP.
NEW
SHAFT
EXISTING
SHAFT
NEW
SHAFT
AE321
AE321
AE322
EXISTING
STRUCTURE
NEW STRUCTURAL
DECK, SEE
STRUCTURAL
DRAWINGS
CONTINUOUS
COMPRESSIBLE
INSULATION AT EJ
PERIMETER
2 HR. EXPANSION
JOINT COVER - BASIS
OF DESIGN AL-200HD
BY CONSTRUCTION
SPECIALTIES
CONTINUOUS
COMPRESSIBLE
INSULATION AT EJ
PERIMETER
2 HR.EXPANSION JOINT COVER -
BASIS OF DESIGN AL-200HD BY
CONSTRUCTION SPECIALTIES
DOOR TO ROOF, SEE
DOOR SCHEDULE
EXISTING
CONSTRUCTION
1:12 RAMP TO LEVEL OUT NEW
CONSTRUCTION IN 1C AND
EXISTING BUILDING 1
2"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE311
WALL SECTIONS
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317)-800-6388
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
(502)-326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 3/4" = 1'-0"AE311
1 EXTERIOR WALL SECTION
SCALE: 3/4" = 1'-0"AE311
2 INTERIOR WALL SECTION
SCALE: 3/4" = 1'-0"AE311
3 INTERIOR SHAFT WALL SECTION
SCALE: 3/4" = 1'-0"AE311
5 WALL SECTION @ ELEVATOR LOBBY
EXISTING
1ST FLOOR
8" H. PROFILED STONE WINDOW SILL
VENEER - MATCH EXISTING SIZE AND
COURSING
(1) LAYER 5/8" EXTERIOR SHEATHING
FLUID APPLIED AIR BARRIER
FOIL FACED BATT
INSULATION R-13 MIN.RIGID CONT. INSULATION R-13 MIN.
EXISTING CONCRETE SLAB,
RE: STRUCT
EXISTING FACE BRICK AND
STONE BANDING
2X FRT BLOCKING AS REQUIRED
PROVIDE WEEP VENTS @ 24" O.C.
(2) LAYERS 5/8" TYPE
'X' GWB ON 6" MTL
STUDS @ 16"O.C.
MORTAR NET
THRU WALL FLASHING EXTENDED
6" ABOVE MORTAR NET
HEMMED DRIP EDGE
1' - 3"
FACE BRICK VENEER TO MATCH
EXISTING SIZE AND COURSING
3/4" SOLID SURFACE
SILL1/4"
CONT. SEALANT
2X WOOD FRT BLOCKING
CONT. SEALANT
ALUM. FLASHING W/ HEMMED
EDGE OVER SILL
FULLY ADHERED SEAM TAPE
OVER BLOCKING, ONTO
SHEATHING, AND UP 6" MIN.
BOTH SIDES OF JAMB
4" FRAME DEPTH
ARCHITECTURAL GRADE
EXTERIOR WINDOW W/
INSULATED GLAZING, SEE
ELEVATIONS, TYP.
1/2" 2' - 0"
5 1/2"
SEE GI101 FOR WALL
RATING AND UL
REFERENCE
FACE BRICK VENEER TO MATCH
EXISTING SIZE AND COURSING
5/8" GLASS MAT FACED GYPSUM
SHEATHING
FLUID APPLIED AIR BARRIER
FOIL FACED BATT INSULATION R-13 MIN.
MASONRY TIES
RIGID CONT. INSULATION R-13 MIN.
(2) LAYERS 5/8"
TYPE 'X' GWB ON
6" MTL STUDS @
16"O.C.
1' - 4 1/4"
9" 7 1/4" 2' - 0"
STRUCTURAL FLOOR,
SEE STRUCTURAL
DRAWINGS. PROVIDE 2
HR RATING, +/-3/4"
THICKNESS OF SPRAY
APPLIED FIRE
RESISTIVE MATERIAL
BASIS OF DESIGN UL
D703
SEE CEILING PLAN
FOR CEILING
TYPES AND
LOCATIONS
PROVIDE WEEP VENTS @ 24" O.C.
MORTAR NET
THRU WALL FLASHING EXTENDED
6" ABOVE MORTAR NET
HEMMED DRIP EDGE
4" FRAME DEPTH
ARCHITECTURAL GRADE
EXTERIOR WINDOW W/
INSULATED GLAZING, SEE
ELEVATIONS, TYP.
STRUCTURAL BEAM,
SEE STRUCTURAL
DRAWINGS. PROVIDE
2 HR RATING, +/-1 1/2"
THICKNESS OF
SPRAY APPLIED FIRE
RESISTIVE MATERIAL
BASIS OF DESIGN UL
X701
5 1/2" 1' - 3"
FACE BRICK VENEER TO MATCH
EXISTING SIZE AND COURSING
5/8" GLASS MAT FACED GYPSUM
SHEATHING
FLUID APPLIED AIR BARRIER
FOIL FACED BATT
INSULATION R-13 MIN.
MASONRY TIES
RIGID CONT. INSULATION R-13 MIN.
1' - 3"
TOP OF COPING
143' - 5 1/2"
2' - 0"
PROFILED STONE BAND.
MATCH EXISTING STONE BAND
5/8" GLASS MAT FACED
GYPSUM SHEATHING
6" METAL STUDS @16" O.C.
6" ROOF INSULATION
(R-30 MIN.)
TAPERED ROOF
INSULATION DIRECTING
DRAINAGE TO SCUPPER
STRUCTURAL DECK,
SEE STRUCTURAL
DRAWINGS. PROVIDE 2
HR RATING, +/-2 1/4"
THICKNESS OF SPRAY
APPLIED FIRE
RESISTIVE MATERIAL
BASIS OF DESIGN UL
P701
STRUCTURAL BEAM,
SEE STRUCTURAL
DRAWINGS
2'
- 8
TOP OF BRICK
142' - 8 1/2"
PROFILED STONE COPING.
MATCH EXISTING
MEMBRANE FLASHING
FULLY ADHERED
MEMBRANE ROOFING
SYSTEM
COVERBOARD
TERMINATION BAR AND
SEALANT
1' - 7 1/4"
CONTINUOUS 2X FRT
WOOD BLOCKING
EXTEND ROOFING
MEMBRANE UP AND
OVER WOOD BLOCKING
8 3 /4"
(2) LAYERS 5/8" TYPE X GYPSUM
BOARD ON 6" METAL STUDS @ 16 O.C.
PINS (MIN) 3 PER STONE
COPING SECURED TO WOOD
BLOCKING
7 3 /4"
3"
EXISTING
STRUCTURE
NEW STRUCTURAL
DECK, SEE
STRUCTURAL
DRAWINGS
CONTINUOUS COMPRESSIBLE
INSULATION AT EJ PERIMETER
EXPANSION JOINT
COVER - BASIS OF
DESIGN AL-200HD BY
CONSTRUCTION
SPECIALTIES
STRUCTURAL FLOOR, SEE
STRUCTURAL DRAWINGS.
PROVIDE 2 HR RATING, +/-3/4"
THICKNESS OF SPRAY APPLIED
FIRE RESISTIVE MATERIAL BASIS
OF DESIGN UL D703
REMOVE A PORTION OF THE EXISTING
STRUCTURAL SLAB TO INSTALL
EXPANSION JOINT COVER
STRUCTURAL BEAM, SEE
STRUCTURAL DRAWINGS.
PROVIDE 2 HR RATING, +/-1
1/2" THICKNESS OF SPRAY
APPLIED FIRE RESISTIVE
MATERIAL BASIS OF DESIGN
UL X701
EXISTING PROFILED STONE
BANDING
3-5/8" METAL STUDS @ 24" O.C.
TERMINATION BAR AND
SEALANT
ROOFING MEMBRANE,
EXTEND UP PARAPET
6" ROOF INSULATION
(R-30 MIN.)
2" BILLOWS EXPANSION
JOINT COVER - BILCO
BRBS-1-2-CSE
STRUCTURAL DECK, SEE
STRUCTURAL DRAWINGS.
PROVIDE 2 HR RATING, +/-2 1/4"
THICKNESS OF SPRAY APPLIED
FIRE RESISTIVE MATERIAL BASIS
OF DESIGN UL P701
STRUCTURAL BEAM, SEE
STRUCTURAL DRAWINGS. PROVIDE
2 HR RATING, +/-1 1/2" THICKNESS
OF SPRAY APPLIED FIRE
RESISTIVE MATERIAL BASIS OF
DESIGN UL X701
5/8" GLASS MAT FACED
GYPSUM SHEATHING
V.
I.F
1'
- 1 1/
2"
EXISTING STONE CAP
COVERBOARD
MEMBRANE FLASHING
4"
COMPRESSIBLE
INSULATION
TERMINATION BAR AND
SEALANT
EXISTING STONE
BANDING AND GUTTER
CONSTRUCTION TO
REMAIN
2" BILLOWS EXPANSION
JOINT COVER - BILCO
BRBS-1-2-CSE
FULLY ADHERED
MEMBRANE ROOFING
SYSTEM
1'
- 8
1/ 4"
STRUCTURAL DECK, SEE STRUCTURAL
DRAWINGS. PROVIDE 2 HR RATING, +/-2 1/4"
THICKNESS OF SPRAY APPLIED FIRE
RESISTIVE MATERIAL BASIS OF DESIGN UL
P701
STRUCTURAL BEAM, SEE
STRUCTURAL DRAWINGS.
PROVIDE 2 HR RATING, +/-1
1/2" THICKNESS OF SPRAY
APPLIED FIRE RESISTIVE
MATERIAL BASIS OF
DESIGN UL X701
COVERBOARD
MEMBRANE FLASHING
3-5/8" METAL STUDS @
16" O.C.
5/8" GLASS MAT FACED
GYPSUM SHEATHING
6" ROOF INSULATION
DEFLECTION TRACK
STEEL BENT PLATE
4"
TERMINATION BAR AND
SEALANT
2" BILLOWS EXPANSION
JOINT COVER - BILCO
BRBS-1-2-CSE
FULLY ADHERED
MEMBRANE ROOFING
SYSTEM
STONE BANDING TO BE
CUT AS REQUIRED TO
ACCOMMODATE NEW
CONSTRUCTION
COUNTER FLASHING W/
HEMMED EDGE OVER
TERMINATION BAR
STRUCTURAL DECK, SEE
STRUCTURAL DRAWINGS.
PROVIDE 2 HR RATING, +/-2 1/4"
THICKNESS OF SPRAY APPLIED
FIRE RESISTIVE MATERIAL BASIS
OF DESIGN UL P701
6" ROOF INSULATION
COVERBOARD
MEMBRANE FLASHING
3-5/8" METAL STUDS @
24" O.C.
5/8" GLASS MAT FACED
GYPSUM SHEATHING
LAP SEALANT
LAP SEALANT
4"
EXISTING
1ST FLOOREXISTING
1ST FLOOR
EXISTING
STRUCTURE
PROVIDE NEW
EXPANSION JOINT
COVER - BASIS OF
DESIGN AL-200HD BY
CONSTRUCTION
SPECIALTIES
REMOVE A PORTION OF THE EXISTING
CONSTRUCTION TO INSTALL
EXPANSION JOINT COVER
EXISTING STRUCTURE
NEW FLOORING
NEW COMPRESSIBLE
INSULATION
PROVIDE ALL REQUIRED INFILL
CONSTRUCTION TO PROVIDE A
SUITABLE CONDITION FOR
JOINT COVER
CONTINUOUS COMPRESSIBLE
INSULATION AT EJ PERIMETER
EXPANSION JOINT COVER -
BASIS OF DESIGN AL-200HD BY
CONSTRUCTION SPECIALTIES
EXISTING
STRUCTURAL SLAB
EXISTING 1ST
FLOOR
CONCRETE LANDING
NEW STRUCTURAL DECK, SEE
STRUCTURAL DRAWINGS
EXPANSION JOINT COVER -
BASIS OF DESIGN AL-200HD BY
CONSTRUCTION SPECIALTIES
STRUCTURAL FLOOR, SEE
STRUCTURAL DRAWINGS.
PROVIDE 2 HR RATING, +/-3/4"
THICKNESS OF SPRAY
APPLIED FIRE RESISTIVE
MATERIAL BASIS OF DESIGN
UL D703
REMOVE A PORTION OF THE
EXISTING STRUCTURAL SLAB
TO INSTALL EXPANSION JOINT
COVER.
STRUCTURAL BEAM, SEE
STRUCTURAL DRAWINGS. PROVIDE
2 HR RATING, +/- 1 1/2" THICK SPRAY
APPLIED FIRE RESISTIVE MATERIAL.
BASIS OF DESIGN UL X701.
3"
CONTINUOUS COMPRESSIBLE
INSULATION AT EJ PERIMETER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE321
WALL SECTION DETAILS
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317)-800-6388
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
(502)-326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1 1/2" = 1'-0"AE321
1 WALL SECTION DETAIL - 2ND FLOOR EXTERIOR
SCALE: 1 1/2" = 1'-0"AE321
2 WALL SECTION DETAIL - 3RD FLOOR EXTERIOR
SCALE: 1 1/2" = 1'-0"AE321
8 WALL SECTION DETAIL - PARAPET
SCALE: 1 1/2" = 1'-0"AE321
4 WALL SECTION DETAIL - 3RD FLOOR INTERIOR
SCALE: 1 1/2" = 1'-0"AE321
7 WALL SECTION DETAIL - INTERIOR PARAPET 1
SCALE: 1 1/2" = 1'-0"AE321
10 WALL SECTION DETAIL - ROOF TRANSITION
SCALE: 1 1/2" = 1'-0"AE321
9 WALL SECTION DETAIL - INTERIOR PARAPET 2
SCALE: 1 1/2" = 1'-0"AE321
3 WALL SECTION DETAIL - 2ND FLOOR INTERIOR
SCALE: 1 1/2" = 1'-0"AE321
5 WALL SECTION DETAIL - 2ND FLOOR TRANSITION
SCALE: 1 1/2" = 1'-0"AE321
6 WALL SECTION DETAIL - 3RD FLOOR TRANSITION
NEW 5/8" GWB
EXISTING 6" METAL
STUDS
EXISTING 5/8" GYP.
SHEATHING
EXISTING WEATHER
BARRIER
EXISTING 3/4" GALV.
SUBGIRT
EXISTING 1 1/2" METAL
PANEL
STRUCTURAL DECK, SEE
STRUCTURAL DRAWINGS. PROVIDE 2
HR RATING, +/-2 1/4" THICKNESS OF
SPRAY APPLIED FIRE RESISTIVE
MATERIAL BASIS OF DESIGN UL P701
5/8" GYPSUM DECK
BOARD
RIGID INSULATION
COVERBOARD
ROCKWOOL
BATT INSULATION
4" BILLOWS
EXPANSION JOINT
COVER - BILCO
BRBS
LAP SEALANT
TPO ROOF MEMBRANE
LAP SEALANT
STRUCTURAL BEAM, SEE
STRUCTURAL DRAWINGS.
PROVIDE 2 HR RATING, +/- 1 1 /2"
THICKNESS OF SPRAY APPLIED
FIRE RESISTIVE MATERIAL,
BASIS OF DESIGN UL X701
STRUCTURAL BEAM, SEE
STRUCTURAL DRAWINGS.
PROVIDE 2 HR RATING, +/- 1 1 /2"
THICKNESS OF SPRAY APPLIED
FIRE RESISTIVE MATERIAL,
BASIS OF DESIGN UL X701
METAL FLASHING
4"
11"
4"
5/8" TYPE "X" GYPSUM BOARD
3-5/8" METAL STUD
FRAMING
AT 16" O.C.
FRAME CONCEALED BY
FEATHERED JOINT
COMPOUND
EXPANSION JOINT ASSEMBLY
5 1/8" 5 1/8"
VERIFY WITH MANUFACTURER'S INSTRUCTIONS
1' - 2 1/4"
COORDINATE FRAMING
REQUIREMENTS WITH
MANUFACTURES
INSTRUCTIONS
WALL FRAMING BEYOND
BASIS OF DESIGN:
CONSTRUCTION SPECIALTIES
FLUSH TWINLINE MODEL SGW
EXPANSION JOINT
ASSEMBLY
4" ACOUSTICAL PANEL CEILING
ANCHOR TIES TO
STRUCTURAL DECK ABOVE
BASIS OF DESIGN:
CONSTRUCTION SPECIALTIES
FLUSH THINLINE MODEL FCF
20 GA. METAL STUDS
WRAPPED WITH 20 GA.
TRACK ON BOTH SIDES -
CONTINUOUS FROM
FLOOR TO DECK
CORNER BEAD AT ALL
OUTSIDE CORNERS
(TYPICAL)
STRUCTURAL
BRACING BEHIND
GWB ENCLOSURE,
REFER TO
STRUCTURAL
EXTERIOR
WINDOW, SEE
ELEVATIONS
PROVIDE METAL STUD AND GWB
ENCLOSURE FOR STRUCTURAL
BRACING AS INDICATED, INTENT IS
TO LEAVE AS OPEN AS POSSIBLE
FOR WINDOW.
PROVIDE HEADER
AS HIGH AS
POSSIBLE
4 m m (7
1/ 2"
6 m m (6
1/ 4"
2,5 m m
(1
MI
N
5 m m
(1 7 3
/4"
DEPTH = 205 mm (8 1/4") 345 mm (13 3/4")
H
A
E
F
C
G I
B
K J
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE322
BUILDING DETAILS
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317)-800-6388
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
(502)-326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1 1/2" = 1'-0"AE322
1 WALL SECTION DETAIL - ROOF TO LOBBY
SCALE: 3" = 1'-0"AE322
2 2HR. RATED EXPANSION JOINT COVER - WALL
SCALE: 3" = 1'-0"AE322
3 EXPANSION JOINT COVER - CEILING
SCALE: 3" = 1'-0"AE322
4 TYPICAL CORNER FRAMING DETAIL
SCALE: 3/8" = 1'-0"AE322
5 WINDOW AND BRACING COORDINATION DETAIL
SCALE: NTSAE322
6 PATIENT LIFT TRACK LOCK SYSTEM DETAIL
SCALE: NTSAE322
7 DOOR HEADER HOIST PASSTHROUGH
SCALE: NTSAE322
8 PATIENT LIFT TRACK HOIST DETAIL
SCALE: NTSAE322
9 PATIENT LIFT TRACK SLING DETAIL
J
AE801
13' - 2 1/2"
11 1/2" 10' - 10 3/4" 1' - 4 1/4"
9 1 /2"
6'
- 5
3/ 4"
9'
- 6
1/ 2"
3'
- 0
4' - 9"
2'
- 6
1/ 2"
3'
- 2
AE801
AE801
AE801
TYP. OF 9
TYP. OF 6
9'
- 4
1'
- 0
6' - 6 3/4"
1'
- 1
0"
AE801
TYP. OF (4)
O2, AIR
AE311
AE801
1 AE801
SIM24
AD301
SIM
SIM
SIM 4
MECHANICAL
CHASE
MECHANICAL
CHASE
TYP.
17' - 3 1/4" 3' - 5 1/2" 20' - 6" 1' - 3" 3' - 0 1/2"
2'
- 0
6 1
/2" 6'
- 4 3/
4"
5 3 /4"
2" 1'
- 0 3/
4"
AE801
AE803
1'
- 6
5'
- 4
1'
- 6
5'
- 3
EQ
EQ
CENTERLINE
OF BED
TYP.
TYP.
5'-0" CLEAR MIN.
+/- 8' - 9 1/2" +/- 5' - 8 3/4"
ALIGN WITH
EXISTING
AE104
SLOPE FLOOR TO
DRAINS AS
INDICATED, TYP.
SEE SECTION
CUT SLOPE FLOOR
FROM DOOR
OPENING INTO
ROOM. SEE
SECTION CUT
SLOPE FLOOR TO
DRAINS AS
INDICATED, TYP.
SEE SECTION
CUT
9'
- 1
3/ 4"
ADDITIONAL
BLOCKING REQUIRED.
9'
- 5
AE801
SIM23
2'
- 8
HAND SANITIZER OUTSIDE OF ROOM
NEAR DOOR, TYPICAL IN PAITENT
ROOMS. COORDINATE EXACT LOCATION
WITH VA.
AE801
AE801
3' - 11" 3' - 10 3/4"
7'
- 8
1'
- 8 3/
4"
1'
- 0
AE801
SIM
3' - 0"
O.
C.
O.C.
39" - 41"
3' - 6" 1' - 0"
TO
R
EF
L E
CT
IV
E 3'
- 4 " M
AX
7" - 9" O.C.
2' - 0"
1 1 /2"
M
IN
TO
T
OP
3'
- 0
6" 3' - 0"
MA
X
TO
B
UT
TO
N
" M
AX
TA7TA2
TA3
TA1
TA5
TA4
TA9
TA6
MA
X
TO
O
UT
LE
T
" M
AX
TA8
MOUNTING HEIGHTS ARE TYPICAL AND APPLY TO FIXTURES INSTALLED IN
NEW RESTROOMS. VERIFY MOUNTING HEIGHTS WITH VENDOR SPECIFIC
MOUNTING HEIGHTS.
TYPICAL MOUNTING HEIGHTS AND INTERIOR ELEVATIONS ARE FOR USE IN
COORDINATION OF FIXTURES. NOTE NOT EVERY FIXTURES MAY BE
REPRESENTED IN INTERIOR ELEVATIONS. COORDINATE PROJECT
REQUIREMENTS WITH THE FLOOR PLAN AND ENLARGED FLOOR PLANS.
COORDINATE INSTALLATION OF EQUIPMENT WITH PLUMBING FIXTURES
AND PLUMBING DRAWINGS. REFER TO PLUMBING PLANS FOR
INFORMATION ON PLUMBING ACCESSORIES AND FIXTURES.
PROVIDE EACH SINK WITHIN SCOPE WITH A PAPER TOWEL DISPENSER
AND SOAP DISPENSER.
PROVIDE UNDER LAVATORY GUARD AT WALL MOUNTED HAND
LAVATORIES IN SCOPE.
PROVIDE IN WALL BLOCKING FOR WALL MOUNTED TOILET ACCESSORIES.
PROVIDE IN WALL BLOCKING FOR WALL MOUNTED SWING GRAB BAR FOR
SECURE INSTALLATION.
TYPICAL TOILET ACCESSORY MOUNTING HEIGHTS
SCALE: 1/4" = 1'-0"
TOILET ACCESSORY GENERAL NOTES
A
B
C
D
E
F
G
" M
IN
TO
P
OF
B
AR
3'
- 0
TA12
1' - 6"
2'
- 9
1' - 6"
DASH LINE INDICATES NURSE STATION WALL BELOW WORKING COUNTER
OR TRANSACTION COUNTER
DIMENSION CROSS REFERENCES TO RADIUS / DIAMETER OF NURSE
STATION WALL / PEDESTAL BELOW
FILE CABINET BELOW - SEE INTERIOR ELEVATIONS
SINGLE RAIL J-TRACK PATIENT LIFT SYSTEM - MIN. 770 LB CAPACITY, SEE
DETAIL 10/AE503.
TRAVERSE RAIL PATIENT LIFT SYSTEM - MIN. 770 LB CAPACITY, SEE DETAIL
5/AE503.
ENLARGED PLANS NOTES
FOR LEGEND REFERENCE OF FURNITURE / EQUIPMENT TAGS, SEE
SHEETS QH101 AND / OR QH102
AE801
O2, AIR
6'
- 7
1/ 4"
2" 7'
- 4 3/
4"
11' - 1"
5' - 0" 4' - 11 3/8"
FA
CE
O F
FI
NI
SH
5'
- 0 " C
LE
AR
1'
- 6
5'
- 4
1'
- 6
CENTERLINE
OF BED
1' - 6"
2' - 6"
EQ
EQ
EQ
.E
.Q
BLANK
BLANK
SLIDE
POWER
POWER
POWER
E POWER
E POWER
E POWER
CODE BLUE
MED AIR
LIGHTING CONTROLS
OXYGEN
OXYGEN
VACUUM
VITAL SIGNS MONITOR
DATA
E POWER
3' - 3"
1' - 0 1
/2"
1' - 1"
2' - 1"
BENT PLANT OUTSIDE CORNER
3 5/8" METAL STUDS
AT 16" O.C.
PORCELAIN
TILE, T-1
PORCELAIN
TILE, T-1
B.4
FULL HEIGHT &
WIDTH INSULATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE501
ENLARGED PLANS AND TOILET
ACCESSORY SCHEDULEGUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317)-800-6388
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
(502)-326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020 JDF JDJ
BID DOCUMENTS
SCALE: 1/4" = 1'-0"AE501
4 ENLARGED FAMILY SPACE
SCALE: 1/4" = 1'-0"AE501
1 ENLARGED STAFF LOUNGE AND TOILET
SCALE: 1/4" = 1'-0"AE501
3 ENLARGED RT SHARED OFFICE
SCALE: 1/4" = 1'-0"AE501
5 2ND FLOOR ENLARGED PLAN - MED TEAM
SCALE: 1/4" = 1'-0"AE501
2 ENLARGED TYPICAL PATIENT ROOM
SCALE: 1/4" = 1'-0"AE501
6 ENLARGED PUBLIC TLT 329
SCALE: 1/4" = 1'-0"AE501
7 ENLARGED STAFF TLT / SHWR C215A
TOILET ACCESSORY SCHEDULE
MARK DESCRIPTION MANUFACTURER MODEL
RESPONSIBLE
PARTY COMMENTS
TA1 42" HORIZONTAL GRAB BAR BOBRICK WASHROOM EQUIPMENT, INC B-6806 x 42 CFCI TA2 36" HORIZONTAL GRAB BAR BOBRICK WASHROOM EQUIPMENT, INC B-6806 x 36 CFCI TA3 18" VERTICAL GRAB BAR BOBRICK WASHROOM EQUIPMENT, INC B-6806 x 18 CFCI
TA4 TOILET PAPER DISPENSER - SURFACE
MOUNTED
BOBRICK WASHROOM EQUIPMENT, INC B-4288
TA5 SANITARY NAPKIN DISPOSAL TOUGH GUY 2NXW1 OFCI
TA6 TOILET SEAT COVER DISPENSER BOBRICK WASHROOM EQUIPMENT, INC B-221 OFCI Mounted at 2'-0" O.C. AFF. Refer to ADA front end sheet for dimensional constraints.
TA7 SOAP DISPENSER BOBRICK WASHROOM EQUIPMENT, INC 818615
TA8 PAPER TOWEL DISPENSER BOBRICK WASHROOM EQUIPMENT, INC B-4262
TA9 18"x36" MIRROR BOBRICK WASHROOM EQUIPMENT, INC B-2908
TA10 GARMENT HOOK BOBRICK WASHROOM EQUIPMENT, INC B-6727 CFCI
TA12 SWING UP GRAB BAR BOBRICK WASHROOM EQUIPMENT, INC B-4998 CFCI
SCALE: 1/4" = 1'-0"AE501
8 ENLARGED SOILED AND STORAGE
SCALE: 1/2" = 1'-0"AE501
11 2ND FLOOR RAMP PLAN
SCALE: 1/4" = 1'-0"AE501
9 TYPICAL ENLARGED PATIENT ROOM CEILING PLAN
SCALE: 1 1/2" = 1'-0"AE501
10 TYPICAL HEADWALL ELEVATION
SCALE: 1 1/2" = 1'-0"AE501
12 PLAN DETAIL - TLT 369
10' - 6" 1' - 5 3/4"
3'
- 1
1 1 /2"
4'
- 1
0"
11' - 11" 5' - 9"
2' - 0 1/2"
6'
- 1
1 1 /4"
8'
- 1
3/
4" AE801
3'
- 4
3/ 4"
5'
- 6
3/ 4"
1'
- 3
3/ 4"
2' - 10 1/2"
3' - 6"
AE801
1' - 3 3/4" 5' - 10 1/4"
3'
- 1
0 3 /4"
4'
- 1
0 1 /4"
8' - 2 1/2"
AE311
AE801
AD301
AE801
SIM
O.H.
AE801
9' - 6 1/4" 6' - 8 1/4" 7' - 7 3/4"
8"
6 3
/4"
CHASE
AE801
AE801
AE801
AE801
AE804
7"
2'
- 1
2'
- 1 1/
2"
CENTER OF
RADIUS
AE802
2'
- 0
1/ 4"
2'
- 1
1 1 /2"
6' - 3 1/4"
CENTER OF
RADIUS
4' - 2" 4' - 0 1/4"
1 1 /2"
7'
- 3
1/ 2"
5' - 8 1/4"
6 3 /4"
3' - 1"
TYP.
1'
1 3
/4"
AE802
AE802
- 3
3/ 4" 8"
TYP.
6'
- 2
1/ 4"
6' - 8 1/4"
3'
- 0
3'
- 0
2'
- 8
3/ 4"
AE804
AE802
AE802
2' - 9" 13' - 9 1/2" 3' - 3 1/2"
3'
- 7
3/ 4"
1' - 8"
AE803
PROVIDE FILTER WITH ICE
AND WATER MACHINE AS
NOTED.
7' - 10 3/4" 2'
- 7
1/ 2"
1/
2"
3'
- 7
3/ 4"
3'
- 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
AE502
ENLARGED PLANS
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317)-800-6388
CMTA CONSULTING ENGINEERS
10411 MEETING STREET
PROSPECT, KY 40059
(502)-326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
5/22/2020
BID DOCUMENTS
SCALE: 1/4" = 1'-0"AE502
2 ENLARGED BARIATRIC PATIENT ROOM
SCALE: 1/4" = 1'-0"AE502
3 ENLARGED PATIENT ROOM
SCALE: 1/4" = 1'-0"AE502
4 ENLARGED STAFF TLT
SCALE: 1/4" = 1'-0"AE502
5 ENLARGED PHYSICAL THERAPY
SCALE: 3/8" = 1'-0"AE502
6 ENLARGED NURSE STATION 1
SCALE: 3/8" = 1'-0"AE502
7 ENLARGED NURSE STATION 2