18.1019.05 - Addendum 5 Dwgs - Pages 8-14.pdf
PDF 4 MB Posted
- Solicitation number
- 36C25520R0115
About this file
This is a pre-solicitation notice for a construction project at the Robert J. Dole VA Medical Center in Wichita, Kansas. The project involves vertically expanding an existing building by two stories and renovating patient rooms on the third floor of another building. The general scope of work includes general construction, demolition, new interior and exterior finishes, mechanical, electrical and plumbing systems, medical gas installation, casework and integration with existing building systems. The estimated cost range is $5-10 million. The NAICS code is 236220 and it is set aside for SDVOSBs. The period of performance is 730 calendar days from notice to proceed. The solicitation package will be available on or about October 20, 2020 with proposals due approximately 30 days later. An organized site visit will be scheduled. Interested offerors should monitor the Beta SAM website for any amendments and direct all questions to the point of contact listed by the deadline specified.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-703
P-413
P-530
P-530
P-413
P-703
P-413
P-703
P-530
P-413
P-530
P-402
P-530
P-703
P-413
P-530
P-413
P-703
P-530
P-530
P-413
P-703
P-703
P-413
P-703
P-530
P-413
P-530
P-703
P-413
P-413
P-703
P-530
IN ACCORDANCE TO THE VA STANDARDS, CHAPTER 4 "WATER
SUPPLY AND DISTRIBUTION", HOT WATER SUPPLY TO BE AS SHORT
AS POSSIBLE TO THE PLUMBING FIXTURE. FROM THE RECIRCULATION
LOOP TO FIXTURE TO HAVE A MAXIMUM WATER VOLUME OF 24 OZ.
FOR SHOWERS, LAVS AND SINKS.
1/2"
3/4"
3/4"
3/4"
3/4"
3/ 4"
3/ 4"
3/ 4"
3/ 4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/ 4"
1"
1"
1"1"
1"
1"
1"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1/
4"
1/
4"
1/
4"
1/
4"
1 1/4"
1 1/4"
1/
4"
1/
4"
1 1/2"
1 1/2"
1/
2"
1/
2"
1 1/2"
1 1/2"1 1/2"
1 1/2"1 1/2"
1/
2"
1/
2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
NC
NC
NC
NC
NC
NC
1/
2"
1/
2"
1 1/2"
1/
2" 1 1/
2"
NC
NC
NC
NC
NC
NC
NC
1/ 2"
E (H
W R
2" E
(H W
1 1/2"
1 1/2"
1/
2"
1 1/2" 1 1/2"
1 1/2"
1/
2"
1 1/2"
1 1/2"
1/
2"
1/
2"
1 1/2"
1 1/2"
1 1/2"
1/
2"
1/
2"
1 1/2"
1 1/2"
1/
2"
1/
2"
1 1/2"
1/
2"
1/
2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1/
2"
1/
2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1/
2"
1 1/2"
1 1/2"
1/
2"
1/
2"
1 1/2" 1 1/2"
1/
2"
1/
2"
1/
2"
1 1/2"
1 1/2"
1/
2"
1/
2"
1/
2"
1 1/2"
1/
2"
1/
2"
1 1/2"
1/
2"
1/
2"
1 1/2"
1 1/2"
1 1/2"
1 1/2"
1/
2"
1/
2"
1/
2"
1/
2"
1 1/2"
1 1/2"
1/
2"
1/
2"
1 1/2"
P-530
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
CMTA CONSULTING ENGINEERS, INC
10411 MEETING STREET
PROSPECT, KY 40059
FULLY SPRINKLERED
C U s e rs
\c h a d \D o c u m e n ts
\V K
M R
M E
C H
R c h a d c m ta e g rs
.c o m
.r v t
/2 /2
:5
:3
P M
PL302
DOMESTIC HOT WATER RISER
DIAGRAM - RENOVATED AREAGUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(502)326-3085(502)326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
05/22/2020
BID DOCUMENTS
Revisions: Date:
Addendum #5 11/24/2020
3'' V.T.R.
CO
P-103
P-402
FD-C
FD-C
P-809P-104
CO
P-530
P-530
P-530
P-809
P-809
FD-C
FD-C
P-413
P-413
CO
P-104
P-530
FD-C
FD-C
CO
P-413
P-103
P-104
P-413
P-104
FD-C
FD-C
P-809
FLOOR
SUMP
P-413
P-505
P-530
CO
P-104
FD-C
FD-C
P-413
P-530
P-809
P-809
P-530
P-530
P-530
P-402
FD-C
FD-C
P-413
P-104
P-809
P-530
CO
CO P-104
P-809
FD-C
FD-C
P-413
P-413
FD-C
FD-C
P-104
P-530
P-530
FD-C
FD-C
FD-C
FD-C
P-413
P-809
P-104
P-104
CO
P-809
P-530
3'' E(V.T.R.)
3'' E(V.T.R.)
3'' E(V.T.R.)
1/
2"
4"
3"
4" 2"
4"
4"
3"
2"
2"
1/ 2"
3"
3"
4"
2"
2"
2" 3"
1/
2"
1/ 2"
4" 3"
3"
4"
3"
3"
4"
4"
3"
2"
1/
2"
1/
2"
1/
2"
2"
3"
1/
2"
2"
3" 3"
2"
2"
2"
3"
4"
2"
2"
1/
2"
3"
2"
3"
3"
3"
3"
1/
2"
3"
1/ 2"2"
4"
4"
2"
4"
2"
2"
2"
4"
2"
1/
2"
3"
3" 1 1/2"
1/
2"
3"
3"
2"
2"
3"
3"
3"
2"
2"
4"
2"
4"
2"
2"
2"
1/ 2"
3"
2"
1/
2"
1/
2"
2"
3"
3"
3"
4"
4"
4"
2"
3"
4"
3" 3"
2"1 1/2"
1/
2"
2"
3"
3"
2"
1 1/2"
3"
3"
2"
1/
2"
3"
1/
2"
1 1/2"
1/
2"
2"
2"
2"
1/
2"
1/ 2"
2"
1/
2"
1/
2"
2"
2"
3"
2"
1/
2"
3"
2"
4"
4"
3"
3"
3"
1/
2"
2" 4"
4"
3"
2"
2" 2"
1/
2"
3"
2"
1/
2"
2"
1/
2" 1 1/
2" 2"
4"
2"
1/
2"
2"
3"
1/
2"
4"
2"
2"
2"
1/
2"
3"
1/
2"
1/ 2"
1/
2"
1/
2"
2"2"
4"
4"
2"
2"
2"
2"
4"
4"
2"
2"
3"
3"
2"
1/
2"
2"
2"
1/
2"
CO
1/
2" V
2" SAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
CMTA CONSULTING ENGINEERS, INC
10411 MEETING STREET
PROSPECT, KY 40059
FULLY SPRINKLERED
C U s e rs
\c h a d \D o c u m e n ts
\V K
M R
M E
C H
R c h a d c m ta e g rs
.c o m
.r v t
/2 /2
:5
:4
P M
PL306
SANITARY WASTE AND VENT
RISER DIAGRAM - RENOVATION
AREA
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(502)326-3085(502)326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
05/22/2020
BID DOCUMENTS
4' 8' 32'16'0
1/8" = 1'-0"
24'2'
SCALE:
SANITARY WASTE AND VENT RISER DIAGRAM
- RENOVATION AREA
Revisions: Date:
Addendum #5 11/24/2020
UP
UP
DN
DN
DN
DN
0.8 1.5 2.8 4.6
MM
K.2
J.3J.3
H.9H.9
F.8
F.8
6.9
6.9
6.1
6.1
E E
D D
C C
B B
A A
F F
G G
I I
HH
F.1 F.1
JJ
KK
LL
6 754
1 4.8
B.4 B.4
ICU NURSE MGR (OFA09)
C212
TOILET/SHOWER (TNPG1)
C215A
NOCTURNIST (OFA09)
C215
CHAPEL (RAS01)
C220
MED TEAM 2 (CFR02)
C204
STORAGE (SRSE1)
C201
MED TEAM 1 (CFR02)
C205
HSKP (JANC1)
FAMILY LOUNGE (WRF01)
CONSULT (OFCD2)
STAFF TLT (TNPG1)
228B
LOCKERS (LR001)
228A
STAFF LOUNGE (SL001)
PANTRY (NCWD1)
CHAPLAIN OFFICE (OFA07)
C219
RT EQUIPMENT STORAGE
C210
RT CLEAN
C211
ELEC
C207
DATA
C208
RT SOILED
C209
OAA
C217
CORR.
C2-03
CORR.
2CORR.
RT OFFICE (OFA09)
C203
RT SHARED OFFICE (OFA07)
C202
OFFICE ICU
C213
DAYTURNIST (OFA09)
C214
1-AC
2ND FLR NURSE MAN. & ASSIST.
C206
24"ø E(SA)
A6
FD
"x
E (R
A
"x
E A
A11
A10
FD
FD
36"x18" RA
S-3
"x
S A
S-2
S-2
S-2
S-1A
E-1A
S-1
S-2
S-2
S-3
S-2
E-2
E-1A
E-1
"x
S A
"x
S A
S-1
S-2
R-1
R-2
E-1
S-1
S-3
S-2
R-3
R-2
A17
20"x12" SA16"x12" SA
"x
S A
"x
S A
10"x14" SA
S-3
S-3
S-3
S-3
S-3
S-3
R-5
R-5
S-2
S-3
S-1
S-1
12"ø SA
R-1
R-3
S-1
12"x12" EA
"x
E A 1
"x
E A
"x
E A
14"x12" SA12"x12" SA
"x
S A
CLOSET
C216
R-2
R-2
FD
FD
S-2
"x
S A
S-5
"x
R A
26"x20" RA
"x
R A
"x
R A
14"x14" RA
S-2
R-4
"ø
S A
"x
R A
R-5
10"x8" RA
A18
8"x12" SA
"x
S A
R-2
R-2
R-3
1-V
2.1
1-V
2.2 1-V
2.3
1-V
2.5 1-V
2.6
1-V
2.8
1-V
2.7 1-V
2.12 1-V
2.13
1-V
2.11
1-V
2.10
1-V
2.15
1-V
2.14
1-V
2.4
"x
S A
"x
S A
S-1
A24
1-V
2.9
R-2
S-6
S-6
R-7
BAS PANEL
R-2
DSA37
DS
DS
A37
A37
A41
VAV TERMINAL
UNIT CLEARANCE.
TYPICAL.
8"x10" SA
2ND FLOOR
ADDITION
SHADE INDICATES
EXISTING AREA BEYOND
PRIMARY SCOPE OF
WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR
ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
BID DEDUCTIVE ALTERNATE 4
FOR THE 3RD FLOOR OF B1C, FULLY BUILD OUT ROOMS C306, C307, C308, C309 AND C310. FOR THE 2ND FLOOR OF B1C, FULLY
BUILD OUT ROOMS C207 AND C208. THE REMAINDER OF THE INTERIOR SPACES TO BE FINISHED WITH CARPET TILE, PAINT, AND ACT CEILINGS, WITH SMALL POWER POLES FOR ELECTRIC AND DATA. THE HVAC TO BE REDUCED TO 3 ZONES IN EACH
SPACE.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
CMTA CONSULTING ENGINEERS, INC
10411 MEETING STREET
PROSPECT, KY 40059
FULLY SPRINKLERED
C U s e rs \j ri g g s \D o c u m e n ts
\V K
M R
M
E C
H R jr ig g s S
B J M
N .r v t
/2 /2
:5
:2
P M
MH101
HVAC PLAN - SECOND FLOOR
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(502)326-3085(502)326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
05/22/2020
BID DOCUMENTS
4' 8' 32'16'0
1/8" = 1'-0"
24'2'
SCALE: 1/8" = 1'-0"
HVAC PLAN - SECOND FLOOR
TAGGED NOTES
A6 34" DIA. UP FROM BASEMENT. TRANSITION TO 26" DIA. AFTER
SECOND FLOOR TAKEOFF.
A10 CONNECT TO EXISTING 12"x12" EA DUCT. ROUTE 12"x12" EA UP
THRU THIRD FLOOR.
A11 CONNECT TO EXISTING 16"x12" ISOLATION EXHGAUST DUCT.
ROUTE UP THRU THIRD FLOOR.
A17 12" DIA. EA DUCT UP FROM FIRST FLOOR. PROVIDE FIRE
DAMPER AT FLOOR PENETRATION.
A18 14"x12" EA DUCT UP TO THIRD FLOOR. PROVIDE FIRE DAMPER
AT FLOOR PENETATION.
A24 24"x18" EA/RELIEF DUCT UP FROM FIRST FLOOR, CONTINUE
THRU THIRD FLOOR.
A37 DUCT SMOKE DETECTOR
A41 COORDINATE FLOOR PENETRATION WITH STRUCTURE.
OFFSET/SHIFT DUCT AS REQUIRED TO PENETRATE BETWEEN
STRUCTURAL JOISTS.
N
SCALE: NONE
KEYPLAN
GENERAL MECHANICAL NOTES:
A. REFER TO SHEET MM001 FOR GENERAL NOTES.
Revisions: Date:
Addendum #5 11/24/2020
TERMINAL UNIT
DUCT RUNOUT
SCHEDULE
MARK
INLET DUCT
SIZE
1-CV 08 8"
1-CV 10 10"
1-V 04 4"
1-V 05 5"
1-V 06 6"
1-V 07 7"
1-V 08 8"
1-V 09 9"
1-V 10 10"
1-V 16 16"
GRD RUNOUT
SCHEDULE
SYMBOL
RUNOUT DUCT
SIZE
S-1 6"Ø
S-1A 6"Ø
S-2 8"Ø
S-3 10"Ø
S-4 12"Ø
S-5 12"x8"
S-6 8"Ø
R-1 6"Ø
R-2 8"Ø
R-3 10"Ø
R-4 12"Ø
R-5 12"x8"
R-6 14"Ø
R-7 10"Ø
E-1 6"Ø
E-1A 6"Ø
E-2 8"Ø
E-2A 8"Ø
E-4 12"Ø
Refer to architectural sheet GI102. Plan indicates spaces for deductive Alternate No. 4. Spaces to be fully built out (1C) shall have HVAC as indicated on plans. The remaining “open” space (1C) shall be served by 3 vav terminal units providing 3 zones (approx. 900 cfm each terminal unit). Each unit shall be complete with HW piping, thermostats, low pressure supply and return duct, and grilles and diffusers to provide even airflow for space. Max. supply cfm per diffuser shall be 300 cfm. 1
DN
0.8 1.5 2.8 4.6
MM
K.2K.2
J.3J.3
H.9H.9
F.8F.8
6.9
6.9
6.1
6.1
E E
D D
C C
B B
A A
F F
G G
I I
13 14 15 16
HH
F.1 F.1
JJ
KK
LL
6 75
EXISTING 1ST
FLOOR ROOF
BELOW
EXISTING 2ND
FLOOR ROOF
BELOW
EXISTING 2ND
FLOOR ROOF
BELOW
UP
UP
INPATIENT OFFICE (OFA07)
C304
PSA OFFICE (OFA07)
C303
OFFICE (OFA07)
C302
STORAGE (SRSE1)
C301
PT TREATMENT
C307
NOD SUPER(OFA09)
C314
NOD SHARED (OFA09)
C315
HSKPG (JANC1)
CONFERENCE (CFR02)
C316
PUBLIC TLT (TNPG1)
CLEAN SUPPLY (LCCL2)
TLT (TSPG1)
355A
PATIENT ROOM (BRSM1)
PATIENT ROOM (BRSM1)
240 SF
TLT (TSPG1)
356A
PATIENT ROOM (BRSM1)
TLT (TSPG1)
357A
MOBILE X-RAY ALCOVE (XRM01)
TLT (TSPG1)
363B
AIRBORNE INF. ISO. PT RM (BRSM1)
SOILED UTILITY (SRSE1)
TLT (TSPG1)
366A
69 SF
PATIENT ROOM (BRSM1)
259 SF
PATIENT ROOM (BRSM1)
TLT (TSPG1)
367A
PATIENT ROOM (BRSM1)
TLT (TSPG1)
369A
PATIENT ROOM (BRSM1)
TLT (TSPG1)
372A
BARIATRIC PATIENT ROOM (BRMS1)
260 SF
CHARTING (OFA07)
BARIATRIC TLT (TSPG1)
371A
PATIENT ROOM (BRSM1)
NURSE STATION (NSTA1)
CONSULT (DL001)
FAMILY LOUNGE (WRF01)
CLEAN LINEN
STAFF TLT (TNPG1)
337B
LOCKERS (LR001)
337A
STAFF LOUNGE (SL001)
PANTRY (NCWD1)
GENERAL STORAGE
C305
CORR.
3-1
OFFICE
C311
ASSIST. MAN.
C312
NURSE MAN.
C313
OFFICE
C318
OFFICE
C319
CORR.
C3-02
OFFICE
C317
MED RM (MEDP1)
ELEC CLOSET
ANTE RM
363A
NOURISH (NCWD1)
360A
1-AC
DATA CLOSET
C310
ELEC CLOSET
C309
PROSTHETICS/LOGISTICS STORAGE
C308
WOUND OFFICE (4 STAFF)
C320
OFFICE
C306
26"x20" RA
WORKSTATION (OFA07)
NURSE STATION (NSTA1)
NURSE WORK ROOM (WRCH1)
EQUIP STOR
FD
30"x20" SA
"ø
S A
A5
A8
CORR.
3CORR.
CORR.
3-2
S-2
S-1
S-2
S-1
S-1
S-1A
S-3
S-3
S-1A
S-3
S-1A
S-3
S-2
S-3
S-3
S-1A
S-2
S-2
S-1A
S-1A
S-1
S-1
S-2
E-1A
S-1A
E-2A
E-1A
E-1A
E-1A
E-1A
S-3
275S-2
E-1
S-1A
E-2A
E-2A
S-2
E-1A
S-3
S-3
S-3
S-3
S-2
S-2
S-2
S-2
S-2
S-2
S-2
S-2
S-2
S-2
S-2
S-2
S-2
S-1
S-1
S-1
S-2
S-2
S-2
S-2
S-2
S-2
S-1
E-2
S-2
S-2
S-2
E-2
165E-1A
S-3
S-2
S-2
10"x12" SA
S-2
10"x12" SA
"ø
S A
S-1
"ø
S A
"ø
S A
10"x12" SA
10"x12" SA
1-V
3.32
1-CV
3.34
E-4
1-V
3.17
S-5
"x
S A
"x
S A
"x
S A
"x
S A
20"x16" SA
16"ø SA
"ø
S A
12"x10" SA BELOW
18"x12" SA
12"x10" SA
"ø
S A
"ø
S A
S-2
12"x10" SA
S-2
8"x6" SA
R-5
R-2
R-2
200 R-2
16"x14" RA
R-5
"ø
R A
R-2
10"x8" EA
R-2
R-2
E-1A
E-1A
STAFF TLT (TNPG1)
22"x18" SA
24"x20" RA
18"x12" SA
20"x16" RA
16"x16" EA
R-5
A16
R-2
"x
R A
"x
R A
S-2
S-2
20"x20" EA 30"x20" SA
8"x10" SA
10"ø SA
12"x10" SA
16"x12" SA
"x
S A
26"x20" RA
S-5
"x
S A
S-2
R-2
R-5
R-2
R-2
R-2
R-2
R-2
R-2
R-2
R-2
"x
R A
"x
R A
14"x12" RA
1-V
3.26
1-V
3.28
1-VAV
3.22
A19
FD
FD
A21
A20
A22 A23
"x
S A
12"x8" SA
24"x20" RA
10"x12" SA
HAC CLOSET
A28
TLT (TSPG1)
368A
R-2
R-2
R-3
R-2
FD
"x
R A
A29
14"x14" RA
"x
R A
E-1
R-3
8"x8" EA
"x
E A
8"x8" EA
A30
10"x14" EA
A32
A31
A31
R-2
1-V
3.12
1-V
3.13
1-V
3.3
1-V
3.16
1-V
3.15
1-V
3.35
1-V
3.18
1-V
3.31
1-V
3.30
1-V
3.27
1-V
3.29
1-V
3.11
1-V
3.14
1-V
3.21
1-V
3.23 1-V
3.24 1-V
3.25
1-CV
3.36
1-V
3.9
1-V
3.4
1-V
3.1
1-V
3.2
1-V
3.5
1-V
3.7
1-V
3.10
1-V
3.6
24"x20" SA
A35 A3614"x12" EA
S-2
S-2
FD
10"x8" EA
"x
E A1-V
3.8
1-V
3.33
R-2
8"x8" SA
1-V
3.19
"x
R A
1-V
3.20
20"x20" RA
A7
10"x10" SA
S-2
"x
R A
10"x10" RA
MEDGAS
FDFD
E-2
8"x8" EA
R-1A
BAS PANEL
BAS PANEL
A37 A37
DS DS
DS
DSA37
A37
A38
A38
A7
"x
R A
A41
VAV TERMINAL
UNIT CLEARANCE.
TYPICAL.
VAV TERMINAL
UNIT CLEARANCE.
TYPICAL.
"ø
S A
2ND FLOOR
ADDITION
SHADE INDICATES
EXISTING AREA BEYOND
PRIMARY SCOPE OF
WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR
ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
FOR THE 3RD FLOOR OF B1C, FULLY BUILD OUT ROOMS C306, C307, C308, C309 AND C310. THE REMAINDER OF THE INTERIOR
SPACE TO BE FINISHED WITH CARPET TILE, PAINT, AND ACT CEILINGS, WITH SMALL POWER POLES FOR ELECTRIC AND DATA.
THE HVAC TO BE REDUCED TO 3 ZONES IN THIS SPACE. FULLY BUILD OUT THE 2ND FLOOR.
BID DEDUCTIVE ALTERNATE 3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
CMTA CONSULTING ENGINEERS, INC
10411 MEETING STREET
PROSPECT, KY 40059
FULLY SPRINKLERED
C U s e rs \j ri g g s \D o c u m e n ts
\V K
M R
M
E C
H R jr ig g s S
B J M
N .r v t
/2 /2
:5
:3
P M
MH102
HVAC PLAN - THIRD FLOOR
GUIDON DESIGN INC.
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(502)326-3085(502)326-3085
VA WICHITA - MED/SURG BEDS
FOR PATIENT PRIVACY
WICHITA, KANSAS
589-701
1 & 1C
05/22/2020
BID DOCUMENTS
4' 8' 32'16'0
1/8" = 1'-0"
24'2'
SCALE: 1/8" = 1'-0"
HVAC PLAN - THIRD FLOOR
TAGGED NOTES
A5 26" DIA. UP FROM SECOND FLOOR.
A7 30"x30" RA DUCT UP TO 1-RTU-1 ON ROOF.
A8 28"x28" RA DUCT UP FROM SECOND FLOOR.
A16 12"x12" EA DUCT UP FROM SECOND FLOOR. CONNECT TO 16"x16" EA.
A19 20"x20" EA UP. TRANSITION TO 22" DIA. AND ROUTE THRUU
ROOF.
A20 26"x20" RA DUCT DN TO SECOND FLOOR.
A21 24"x16" SA DUCT DN TO SECOND FLOOR.
A22 50"x20" OA DUCT UP FROM FIRST FLOOR.
A23 ROUTE 50"x20" OVER AND UP THRU ROOF TO RELOCATED OA
INTAKE HOOD.
A28 16"x16" EA UP TO ATTIC. PROVIDE FIRE DAMPER AT FLOOR
PENETRATION.
A29 ROUTE 8" DIA. RA FROM BOTTOM OF DUCT TO RA GRILLE.
A30 12"x12" ISOLATION EXHAUST UP TO ATTIC. PROVIDE FIRE
DAMPER AT ATTIC FLOOR.
A31 10"x10" EA UP TO ATTIC. PROVIDE FIRE DAMPER AT ATTIC
FLOOR.
A32 16"x12" ISOLATION EXHAUST UP FROM THIRD FLOOR. PROVIDE
FIRE DAMPER AT ATTIC FLOOR.
A35 14"x12" EA UP FROM SECOND FLOOR. PROVIEDE FIRE DAMPER
AT FLOOR PENETRATION.
A36 14"x12" EA UP TO EF ON ROOF.
A37 DUCT SMOKE DETECTOR
A38 PROVIDE FIRE DAMPER AT FLOOR PENETRATION. PROVIDE
ACCESS PANEL IN WALL FOR ACCESS TO DAMPER.
A41 COORDINATE FLOOR PENETRATION WITH STRUCTURE.
OFFSET/SHIFT DUCT AS REQUIRED TO PENETRATE BETWEEN
STRUCTURAL JOISTS.
SCALE: NONE
KEYPLAN
N
GENERAL MECHANICAL NOTES:
A. REFER TO SHEET MM001 FOR GENERAL NOTES.
Revisions: Date:
Addendum #5 11/24/2020
TERMINAL UNIT
DUCT RUNOUT
SCHEDULE
MARK
INLET DUCT
SIZE
1-CV 08 8"
1-CV 10 10"
1-V 04 4"
1-V 05 5"
1-V 06 6"
1-V 07 7"
1-V 08 8"
1-V 09 9"
1-V 10 10"
1-V 16 16"
GRD RUNOUT
SCHEDULE
SYMBOL
RUNOUT DUCT
SIZE
S-1 6"Ø
S-1A 6"Ø
S-2 8"Ø
S-3 10"Ø
S-4 12"Ø
S-5 12"x8"
S-6 8"Ø
R-1 6"Ø
R-2 8"Ø
R-3 10"Ø
R-4 12"Ø
R-5 12"x8"
R-6 14"Ø
R-7 10"Ø
E-1 6"Ø
E-1A 6"Ø
E-2 8"Ø
E-2A 8"Ø
E-4 12"Ø
Refer to architectural sheet GI102. Plan indicates spaces for deductive Alternate No. 3. Spaces to be fully built out (1C) shall have HVAC as indicated on plans. The remaining “open” space (1C) shall be served by 3 vav terminal units providing 3 zones (approx. 700 cfm each terminal unit). Each unit shall be complete with HW piping, thermostats, low pressure supply and return duct, and grilles and diffusers to provide even airflow for space. Max. supply cfm per diffuser shall be 300 cfm. 1
DN
S
S
S
S
S
S
SD SD
SD
S S
S
SD
S
S
S
SD
DL
DL
PC
P C
S
F F
S
F
S
F
F
FF
F
S
S
S
S
F
F
F F
SD
CCC
C
C C
CC
CC
C C
F
ZL
F
S S S
S
S
SD
SS
S
S
CR
DS
CR
DS
C R
DS
DD
DD
DD
FS
TS
0.8 1.5 2.8 4.6
MM
K.2K.2
J.3J.3
H.9H.9
F.8
6.9
6.9
6.1
6.1
E E
D D
C C
B B
A A
F F
G G
I I
13 14 15 16
HH
F.1 F.1
JJ
KK
LL
6 754321
4.8
B.4 B.4
2D
2D
2D
2D
2D
2D
ICU NURSE MGR
(OFA09)
C212
TOILET/SHOWER
(TNPG1)
C215A
NOCTURNIST
(OFA09)
C215
CHAPEL (RAS01)
C220
RT SHARED OFFICE
(OFA07)
C202
RT OFFICE (OFA09)
C203
MED TEAM 2 (CFR02)
C204
STORAGE (SRSE1)
C201
MED TEAM 1 (CFR02)
C205
HSKP (JANC1)
229 FAMILY LOUNGE
(WRF01)
CONSULT (OFCD2)
STAFF TLT (TNPG1)
228B
LOCKERS (LR001)
228A
STAFF LOUNGE
(SL001)
PANTRY (NCWD1)
CHAPLAIN OFFICE
(OFA07)
C219
CORR.
C2-03
CORR.
C2-02
CORR.
2CORR.
ELEV. LOBBY
2-01
CORR.
2-02
ELEV.
1ELEV
TLT
282A
BEDROOM
TLT
280A
BEDROOM
MEDICATION PREP
BEDROOM
BEDROOM
STAIR
SOILED UTILITY
BEDROOM
HSK
BEDROOM
BEDROOM
TLT
256A
BEDROOM
TLT
254A
WARD SUPPLIES
LOUNGE
LAB
BEDROOM
BEDROOM
BEDROOM
TLT
ELEC. CLOSET
STAIR-E
EQUIP. ROOM
STAIR-C
ELEV.
2ELEV-2
I.T.
ELEV.
2ELEV-1
ELEC
C207
RT CLEAN
C211
RT SOILED
C209
RT EQUIPMENT
STORAGE
C210
OAA
C217
DATA
C208
CLOSET
C216
2ND FLR NURSE
MAN. & ASSIST.
C206
OFFICE ICU
C213
DAYTURNIST
(OFA09)
C214
CORR.
C2-01
2D
2D
2D
2D
2D .
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
T +5' - 0"
2D
2D
EL
ES501
2D
2D
2D
F
F
F F
2D
PRINTER
C
C
2D
T
+4' - 0"
PRINTER
2D
ES501
PT-B
P21P21
P21P21
STOR.
C219A
S15
S15
S14
1-ELLS3E-3
2ND FLOOR
ADDITION
SHADE INDICATES
EXISTING AREA BEYOND
PRIMARY SCOPE OF
WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR
ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
CMTA CONSULTING ENGINEERS, INC.
10411 MEETING STREET,
PROSPECT, KY 40059
(502)326-3085
GUIDON DESIGN, INC
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317) 800-6388
BID DOCUMENTS VA WICHITA - MED/SURG
BEDS FOR PATIENT PRIVACY
589-701
1 & 1C
05/22/2020 PDY RAH
C U s e rs \m le p p in g \D o c u m e n ts \V
K M
R
E L E
C R m le p p in g
E Z
J R
.r v t
/2 /2
:0
:2
P M
ES401
SECOND FLOOR PLAN - SYSTEMS
WICHITA, KANSAS
GENERAL NOTES (SYSTEMS):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,
AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL AND
CEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS
INDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3)
BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE
PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED
NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME
CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL
CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE
CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE
BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,
SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR
ADHESIVE LABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES,
ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE
AREAS. MARK INSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT
NUMBER.
D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND
SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF
EACH SYSTEM.
E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO
THE NEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS).
REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL
REQUIREMENTS.
F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT
BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH.
PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM
CABLING INSTALLATION.
4' 8' 32'16'0
1/8" = 1'-0"
24'2'
SCALE: 1/8" = 1'-0"
SECOND FLOOR PLAN - SYSTEMS
1" = 100'-0"
KEYPLAN
SECOND & THIRD FLOOR ALTERNATE OFFICE CUBICLE AREA
REFER TO THE ARCHITECTURAL PLANS FOR A PROPOSED ‘’OPEN OFFICE’’
AREA LAYOUT ON THE THIRD FLOOR. PROVIDE APPROXIMATELY (20) TYPE
“A2” 2X4 LIGHTS, (6) CEILING TYPE VACANCY SENSOR UNITS, (4) LOW
VOLTAGE LIGHT SWITCHES, (18) QUADRAPLEX RECEPTACLES, (4) FLOOR
FED FURNITURE POWER FEEDS, (4) FLOOR FED FURNITURE DATA FEEDS, (8)
‘4D’ DATA OUTLETS AND (2) FIRE ALARM AUDIO/VISUAL UNITS.
TAGGED NOTES
P21 PROVIDE ONE (1) 1-1/2" CONDUIT FOR DATA AND HDMI CONNECTIONS TO
TV MOUNTED ON WALL IN THIS AREA. CUT, TRENCH, AND PATCH FLOOR AS
REQUIRED. EXTEND CONDUIT TO NEAREST AVAILABLE CABLE PATH.
S14 PROVIDE FOUR (1) 2" CONDUIT SLEEVE(S) THROUGH WALL(S) INDICATED.
INSTALL SLEEVE(S) ABOVE SUSPENDED CEILING (WHERE APPLICABLE).
PROVIDE UL LISTED FIRE-RATED ASSEMBLY AT PENETRATION AS
REQUIRED. REFER TO SLEEVE PENETRATION DETAIL FOR ADDITIONAL
REQUIREMENTS (TYPICAL ALL PENETRATIONS).
S15 PROVIDE DUCT SMOKE DETECTOR. REFER TO FIRE ALARM RISER
DIAGRAM AND MECHANICAL DRAWINGS FOR ADDITIONAL REQUIREMENTS
AND INFORMATION.
Revisions: Date:
S
S S
S
S
S
S
S
S
SDS
S
S
S
S S S
S
S
S
DL
DL
DL
DL
ZL
ZL
DL
DL
DL
S
S
F
S
F
S F
F
F
F
S
F F
S
F
F
F F
SS
S
S
S
DL DL DL
PC
DL
M S
MS
S A
SA
C C
CC
CC
CC
C C
C C
C C
C C
C C
C C
S
S
S
SV
SV
SD S
CC ZL
SD
DL
ZL
CR
DS
DP
F
F F
F
SD
CR
DS
CR
DS
C R
DS
SD
SD
SD
F
S
CR
DS
F S
LPA
DD
DD
DD DD
FS
TS
F
FS
TS
0.8 1.5 2.8 4.6
MM
K.2K.2
J.3J.3
H.9H.9
F.8F.8
6.9
6.9
6.1
6.1
E E
D D
C C
B B
A A
F F
G G
I I
13 14 15 16
HH
F.1 F.1
JJ
KK
LL
6 75
2D
2D
2D
2D
T +5' - 0".
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
2D
T
+5' - 0"
T
+4' - 0"
2D
2D
2D
4D
2D/C
2D/C
2D/C
2D/C
2D/C
2D/C
2D/C
2D/C
2D/C
2D/C
2D
C
2D
2D
2D
ELEC CLOSET
C309
INPATIENT OFFICE
(OFA07)
C304
PSA OFFICE (OFA07)
C303
OFFICE (OFA07)
C302
STORAGE (SRSE1)
C301
PT TREATMENT
C307
NOD SUPER(OFA09)
C314
NOD SHARED
(OFA09)
C315
DATA CLOSET
C310
HSKPG (JANC1)
CONFERENCE
(CFR02)
C316
PUBLIC TLT (TNPG1)
CLEAN SUPPLY
(LCCL2)
TLT (TSPG1)
355A
PATIENT ROOM
(BRSM1)
PATIENT ROOM
(BRSM1)
TLT (TSPG1)
356A
PATIENT ROOM
(BRSM1)
TLT (TSPG1)
357A
NOURISH (NCWD1)
360A
MED RM (MEDP1)
STAFF TLT (TNPG1)
MOBILE X-RAY
ALCOVE (XRM01)
TLT (TSPG1)
363B
AIRBORNE INF. ISO.
PT RM (BRSM1)
SOILED UTILITY
(SRSE1)
TLT (TSPG1)
366A
PATIENT ROOM
(BRSM1)
PATIENT ROOM
(BRSM1)
TLT (TSPG1)
367A
PATIENT ROOM
(BRSM1)
TLT (TSPG1)
369A
PATIENT ROOM
(BRSM1)
TLT (TSPG1)
372A
BARIATRIC PATIENT
ROOM (BRMS1)
CHARTING (OFA07)
BARIATRIC TLT
(TSPG1)
371A
PATIENT ROOM
(BRSM1)
NURSE STATION
(NSTA1)
WORKSTATION
(OFA07)
NURSE WORK ROOM
(WRCH1)
NURSE STATION
(NSTA1)
CONSULT (DL001)
FAMILY LOUNGE
(WRF01)
CLEAN LINEN
STAFF TLT (TNPG1)
337B
LOCKERS (LR001)
337A
STAFF LOUNGE
(SL001)
PANTRY (NCWD1)
EQUIP STOR
TOILET
326A
OBSERVATION
ROOM
CORR.
3-1
OBSERVATION
ROOM
MED
TOILET
325A
EQUIP STOR
ELECT
CLEAN UTIL
ELEV
3ELEV-2
ELEV
3ELEV-1
STAIR
3STAIRC
BIOMED
STAIR
3-STAIR-E
CORR.
C3-02
CORR.
C3-01
CORR.
3CORR.
ELEV.
ELEV. LOBBY
3-01
CORR.
3-02
GENERAL STORAGE
C305
ANTE RM
363A
EQUIP STOR
OFFICE
C311
WOUND OFFICE (4
STAFF)
C320
ASSIST. MAN.
C312
NURSE MAN.
C313
OFFICE
C317
OFFICE
C318
OFFICE
C319
CORR.
3-2
CORR.
C3-03
OFFICE
C306
PROSTHETICS/LOGISTICS
STORAGE
C308
ELEC CLOSET
PT WORKSTATIONS
C307A
TLT (TSPG1)
368A
COPIER
4D
4D
4D
2D
PYXIS
2D S2
HAC CLOSET
ES501
REFER TO ENLARGED VIEWS OF
TYPICAL PATIENT ROOM
ELECTRICAL REQUIREMENTS FOR
SCOPE OF WORK IN HATCHED AREA
REFER TO ENLARGED VIEWS OF
TYPICAL PATIENT ROOM
ELECTRICAL REQUIREMENTS FOR
SCOPE OF WORK IN HATCHED AREA
REFER TO ENLARGED VIEWS OF
TYPICAL PATIENT ROOM
ELECTRICAL REQUIREMENTS FOR
SCOPE OF WORK IN HATCHED AREA
2D
PYXIS
EL
F
F
2D .
2D
F
F
F
F
2D/C
F
S14 S14
S14
S14
ES501
2D/C
1-ELLS3E-4
S17
1-ELLS3E-7
(SEE DETAIL)
1-ELLS3E-8
EXSITING
TELEMETRY/DATA
RACK TO REMAIN
C C C
C
C
C
C
C
C
C
C
C
C
2ND FLOOR
ADDITION
SHADE INDICATES
EXISTING AREA BEYOND
PRIMARY SCOPE OF
WORK, TYPICAL
1ST FLOOR
2ND FLOOR
3RD FLOOR
3RD FLOOR
ADDITION
AREA OF RENOVATION
BUILDING 1C
BUILDING 1
AREA OF RENOVATION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
CMTA CONSULTING ENGINEERS, INC.
10411 MEETING STREET,
PROSPECT, KY 40059
(502)326-3085
GUIDON DESIGN, INC
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317) 800-6388
BID DOCUMENTS VA WICHITA - MED/SURG
BEDS FOR PATIENT PRIVACY
589-701
1 & 1C
05/22/2020 PDY RAH
C U s e rs \m le p p in g \D o c u m e n ts \V
K M
R
E L E
C R m le p p in g
E Z
J R
.r v t
/2 /2
:0
:2
P M
ES402
THIRD FLOOR PLAN - SYSTEMS
WICHITA, KANSAS
4' 8' 32'16'0
1/8" = 1'-0"
24'2'
SCALE: 1/8" = 1'-0"
THIRD FLOOR PLAN - SYSTEMS
1" = 100'-0"
KEYPLAN
GENERAL NOTES (SYSTEMS):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,
AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL AND
CEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS
INDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3)
BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE
PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED
NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME
CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL
CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE
CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE
BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,
SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR
ADHESIVE LABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES,
ENGRAVE EMERGENCY DEVICE COVERPLATES IN PATIENT CARE
AREAS. MARK INSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT
NUMBER.
D. REFER TO "SYSTEM INSTALLATION MATRIX" (ON SYSTEMS LEGEND
SHEET) AND SPECIFICATIONS FOR CONTRACTOR REQUIREMENTS OF
EACH SYSTEM.
E. THE CONTRACTOR SHALL ROUTE ALL ''SYSTEM CONDUIT STUB-UPS'' TO
THE NEAREST CORRIDOR CABLING PATH (SEE ''STUB-UP'' DETAILS).
REFER TO CABLING PATH INSTALLATION DETAIL FOR ADDITIONAL
REQUIREMENTS.
F. CONTRACTOR SHALL PAINT ALL SYSTEMS CONDUIT STUB-UPS LIGHT
BLUE FOR SYSTEMS CABLING INTO THE CORRIDOR CABLING PATH.
PROVIDE PULL STRINGS IN ALL NEW CONDUIT RUNS FOR SYSTEM
CABLING INSTALLATION.
SECOND & THIRD FLOOR ALTERNATE OFFICE CUBICLE AREA
REFER TO THE ARCHITECTURAL PLANS FOR A PROPOSED ‘’OPEN OFFICE’’
AREA LAYOUT ON THE THIRD FLOOR. PROVIDE APPROXIMATELY (20) TYPE
“A2” 2X4 LIGHTS, (6) CEILING TYPE VACANCY SENSOR UNITS, (4) LOW
VOLTAGE LIGHT SWITCHES, (18) QUADRAPLEX RECEPTACLES, (4) FLOOR
FED FURNITURE POWER FEEDS, (4) FLOOR FED FURNITURE DATA FEEDS, (8)
‘4D’ DATA OUTLETS AND (2) FIRE ALARM AUDIO/VISUAL UNITS.
TAGGED NOTES
S2 ROUTE ONE (1) 1-1/4" CONDUIT FROM POKE-THRU TO STUB UP INSIDE
WALL FOR A/V, HDMI, DATA, ETC. CONNECTIONS BETWEEN POKE THRU
AND TV. COORDINATE EXACT POKE THRU AND TV LOCATION PRIOR TO
ROUGH-IN.
S14 PROVIDE FOUR (1) 2" CONDUIT SLEEVE(S) THROUGH WALL(S) INDICATED.
INSTALL SLEEVE(S) ABOVE SUSPENDED CEILING (WHERE APPLICABLE).
PROVIDE UL LISTED FIRE-RATED ASSEMBLY AT PENETRATION AS
REQUIRED. REFER TO SLEEVE PENETRATION DETAIL FOR ADDITIONAL
REQUIREMENTS (TYPICAL ALL PENETRATIONS).
S17 PROVIDE CONNECTION TO FIRE ALARM SYSTEM FOR AUTOMATIC
RELEASE OF ALL MECHANICALLY HELD DOORS UPON FIRE ALARM
SYSTEM ACTIVATION. REFER TO FIRE ALARM RISER DIAGRAM FOR
ADDITIONAL REQUIREMENTS AND INFORMATION.
Revisions: Date:
JJ
C B
S P C
J
S P C
P C
B I
J J
J J
S
P C
SD
SD
J
J
PC
SPC
CB
BI
SD
S
J J
J
PC
J
J
SPC
CB
BI
PC
S
SD
J J
J
J
J
PC
J
J
.Dc
D6-20(b)
D6-20(a)
D6-20(a)
D6-20(d)
.De
.Df,g
D3-10(e)
D3-10(e)
.Dd
.U
U1U2
(TYP)
L1
B2(f,g)
D6-20
.OS
ST(c)
ST(c)
DS-15
V1
.EL
L5 L5 g f
(TYP)
L12
Da
Dc
.Db
.Da
.Da
GFI/E
+3' - 0"
E
E +4' - 0"
E
E
PATIENT LIFT
CONNECTION
(TYP)
USB
EP
P6
P6
T +7' - 0"
PATIENT ROOM
(BRSM1)
P2
P4
P4
NP
(TYP)
P10
4' - 0"
S1
S1
2D
GFI/E
+3' - 0"
3D/1V
S16
E
D
F
G
I
13 14 15 16
F.1
1EF
1EF
1VFD
1EF12
D9
1-ELEQ3E-4
P23
1-ELEQ3E-5
TLT (TSPG1)
363B
AIRBORNE INF. ISO.
PT RM (BRSM1)
ANTE RM
363A
D6-20(a)
D6-20(d)
D6-20(a)
D6-20(b)
D3-10(e) D3-10(e)
.De .Df,g
B2(f,g) g f
D6-20(a)
.NL
.EL
.Da
.Dc
.Db
ST(c)
ST(c)
.OS
DS-15
D6-20
V1
.Dd
U1
U2 .U
L1
ST(c)
Da
Dc
L5
L5
.Da
Da
GFI/E
GFI/E
+3' - 0"
+3' - 0"
S1
S1
T
+7' - 0"
PATIENT LIFT
CONNECTION
(TYP)
E
E
P4P4
E
EP
P6
P6
NP
P2
E
+4' - 0"
4' - 0" 2D
3D/1V
S16
(TYP)
P10
B B
A A
13 14
E
GFI/E
GFI/E
E
T +7' - 0"
PATIENT LIFT
CONNECTION
(TYP)
S1 S1 E
+4' - 0"
USB
P2.
E
P4 P4
NP
3D/1V
S16
P6
P6
EP
(TYP)
P10
B B
A A
13 14 g f
Da
D6-20(a)
D6-20(b)
.EL
.NL
.Da .Db
.Dc
Db
ST(c)
ST(c)
D6-20(a)
Dc
U2
U2
.De .Da
.Df,g
B2(f,g)
D3-10(e)
D3-10(e)
.Dd
L5
L5
.OS
V1
DS-15
D6-20
D6-20(a)
D6-20(d)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
CMTA CONSULTING ENGINEERS, INC.
10411 MEETING STREET,
PROSPECT, KY 40059
(502)326-3085
GUIDON DESIGN, INC
1221 N PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
(317) 800-6388
BID DOCUMENTS VA WICHITA - MED/SURG
BEDS FOR PATIENT PRIVACY
589-701
1 & 1C
05/22/2020 PDY RAH
C U s e rs \m le p p in g \D o c u m e n ts \V
K M
R
E L E
C R m le p p in g
E Z
J R
.r v t
/2 /2
:0
:2
P M
ES502
ENLARGED PLANS
WICHITA, KANSAS
2' 4' 16'8'0
1/4" = 1'-0"
12'1'
SCALE: 1/4" = 1'-0"
ENLARGED 3RD FLOOR PLAN - TYPICAL
PATIENT ROOM - LIGHTING
2' 4' 16'8'0
1/4" = 1'-0"
12'1'
SCALE: 1/4" = 1'-0"
ENLARGED 3RD FLOOR PLAN - TYPICAL
PATIENT ROOM - POWER / SYSTEMS
GENERAL NOTES (ENLARGED AND TYPICAL):
A. ALL ROOM LAYOUTS ARE TYPICAL AND MAY VARY OR MIRROR OTHER
ASSOCIATED ROOMS. CONTRACTOR SHALL REFER TO ARCHITECTURAL
ELEVATIONS AND COORDINATE EACH ROOM PRIOR TO ROUGH-IN.
GENERAL NOTES (LIGHTING):
A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS,
AND CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL AND
CEILING MOUNTED ELECTRICAL DEVICES.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS
INDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3)
BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE
PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED
NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME
CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL
CURRENT CARRYING CONDUCTORS PER N.E.C. #310.15(B)(3), AND
UPSIZE CONDUIT AS REQUIRED PER N.E.C. #300.17 AND ANNEX
C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN N.E.C #100 / 210.4
(CIRCUITS SHARING A COMMON NEUTRAL CONDUCTOR) SHALL NOT BE
PERMITTED.
C. ALL DEVICE COVERPLATES SHALL BE #302 STAINLESS STEEL. IDENTIFY
THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES,
ETC. IN AREA OF CONSTRUCTION. ENGRAVE DEVICE COVERPLATES
FOR IDENTIFICATION. ALL JUNCTION BOXES (LABEL INTERIOR OF BOX
WHERE "IN WALL" SWITCHES AND OUTLET BOXES) SHALL BE LABELED
WITH THE VOLTAGE, PHASE, CIRCUIT NUMBER AND PANEL OF ORIGIN. A
BLACK MARKER SHALL BE ACCEPTABLE FOR JUNCTION BOX LABELING.
ALL CONDUCTORS IN A SINGLE CONDUIT / CONDUIT BODY SHALL
ORIGINATE FROM THE SAME PANEL. THE GROUND CONDUCTOR SHALL
BE BONDED TO THE BOX AT ANY DEVICE OR JUNCTION BOX WHICH HAS
CONNECTIONS IN IT.
D. LOCATE CHAIN-HUNG INDUSTRIAL FIXTURES IN MECHANICAL ROOMS TO
AVOID DUCTWORK AND PIPING, TO MAXIMIZE AVAILABLE LIGHT. SPACE
AROUND EQUIPMENT, AIR HANDLERS, ETC. TO PROVIDE ADEQUATE
LIGHTING TO ALL AREAS OF ROOM. PROVIDE ADDITIONAL FIXTURES OF
SAME TYPE AS NEEDED TO FULFILL THIS REQUIREMENT.
E. LOCATE EXIT SIGNS FOR MAXIMUM VIEWING AREA TO IDENTIFY EGRESS
PATHS AS INDICATED ON PLANS. COORDINATE LOCATIONS SUCH THAT
ARCHITECTURAL FEATURES OR EQUIPMENT FROM OTHER TRADES DO
NOT OBSTRUCT VIEW.
F. WHERE EXIT SIGNS OR EMERGENCY BATTERY PACKS ARE PROVIDED,
THEY SHALL BE CONNECTED TO AN UNSWITCHED LINE.
G. LUMINAIRES INDICATED WITH MULTI-LEVEL SWITCHING SHALL HAVE
SIMILAR LAMPS CONTROLLED TOGETHER, I.E. INBOARD AND OUTBOARD
LAMPS OR RIGHT AND LEFT HAND LAMPS.
H. ALL LIGHTING FIXTURE LENSES, PARABOLIC LOUVERS, DOWNLIGHTING
ALZAK CONES AND "PARACUBE" LOUVERS SHALL BE HANDLED WITH
COTTON GLOVES DURING INSTALLATION AND LAMPING TO AVOID
FINGERPRINTS OR DIRT DEPOSITS. IT IS PREFERRED THAT FIXTURES
BE SHIPPED AND INSTALLED WITH CLEAR PLASTIC BAGS TO PROTECT
LOUVERS. AT CLOSE OF PROJECT, AND AFTER CONSTRUCTION AIR
FILTERS ARE CHANGED, REMOVE BAGS. ANY LOUVER OR CONE
SHOWING DIRT OR FINGER PRINTS SHALL BE CLEANED WITH SOLVENT
RECOMMENDED BY THE MANUFACTURER, OR REPLACED AS
NECESSARY IN ORDER TO TURN OVER TO THE OWNER NEW FIXTURES
AT OCCUPANCY.
I. RECESSED LUMINAIRES SHALL BE SECURED SUCH THAT THE FORCE
REQUIRED INSERTING LAMPS, TRIMS, LENSES, LOUVERS, OR DOOR
FRAMES DOES NOT SHIFT HOUSING. ALL TRIMS SHALL BE COMPLETELY
FLUSH WITH FINISHED CEILINGS AT COMPLETION OF CONSTRUCTION.
J. CONTRACTOR SHALL PROVIDE UNSWITCHED CONDUCTOR TO ALL EXIT
SIGNS, EMERGENCY INVERTER BATTERY PACKS, AND NIGHT LIGHTS AS
REQUIRED.
GENERAL NOTES (POWER / SYSTEMS):
A. THIN SOLID LINES INDICATE EXISTING ITEMS TO REMAIN (U.O.N.) AND THICK
SOLID LINES INDICATE NEW WORK.
B. ALL NEW WIRING SHALL BE #12 WITH A #12 INSULATED GROUND WIRE (U.O.N.).
CONDUIT SHALL BE 3/4'' MINIMUM.
C. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND
CASEWORK DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILING
MOUNTED ELECTRICAL DEVICES.
D. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED
ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER
HOMERUN. EACH BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED
NEUTRAL CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE
CONSIDERED CURRENT CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN
THE SAME CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE
ALL CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE
CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE BRANCH
CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A COMMON
NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
E. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,
SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE
LABELS WITH BLACK LETTERING. IN HEALTHCARE FACILITIES, ENGRAVE
EMERGENCY DEVICE COVERPLATES IN PATIENT CARE AREAS. MARK INSIDES
OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBER.
F. RECEPTACLES THAT ARE CONTROLLED BY AN AUTOMATIC MEANS SUCH AS
OCCUPANCY SENSOR OR ENERGY MANAGEMENT SYSTEM SHALL BE MARKED
IN ACCORDANCE WITH NEC 406.3(E).
G. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL
BE COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO
ENSURE ACCESS AND WORKING CLEARANCE IS MAINTAINED PER NEC.
NOTIFY OTHER TRADES OF REQUIRED CLEARANCE AREAS TO AVOID
ROUTING OF OTHER SYSTEMS IN THESE AREAS. DO NOT INSTALL ELECTRICAL
EQUIPMENT OVER EQUIPMENT NAMEPLATES OR ACCESS PANELS OR
THROUGH ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER
TRADES.
H. NO CONDUIT SHALL BE INSTALLED UNDERGROUND, EXCEPT FOR
DISTRIBUTION EQUIPMENT FEEDERS, UNLESS REQUIRED FOR THE
APPLICATION (FLOOR BOXES, ISLANDS, ETC,) OR SPECIFICALLY INDICATED AS
SUCH IN CONSTRUCTION DOCUMENTS. NO CONDUIT SHALL BE INSTALLED
WITHIN CONCRETE SLABS.
I. ALL DEVICE COVERPLATES SHALL BE #302 STAINLESS STEEL. IDENTIFY THE
PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN
AREA OF CONSTRUCTION. ENGRAVE DEVICE COVERPLATES FOR
IDENTIFICATION. ALL JUNCTION BOXES (LABEL INTERIOR OF BOX WHERE "IN
WALL"SWITCHES AND OUTLET BOXES) SHALL BE LABELED WITH THE
VOLTAGE, PHASE, CIRCUIT NUMBER AND PANEL OF ORIGIN. A BLACK MARKER
SHALL BE ACCEPTABLE FOR JUNCTION BOX LABELING. ALL CONDUCTORS IN A
SINGLE CONDUIT / CONDUIT BODY SHALL ORIGINATE FROM THE SAME PANEL.
THE GROUND CONDUCTOR SHALL BE BONDED TO THE BOX AT ANY DEVICE
OR JUNCTION BOX WHICH HAS CONNECTIONS IN IT.
J. ALL CEILING MOUNTED DEVICES, FIXTURES, ETC. SHALL BE INSTALLED
COMPLETELY FLUSH WITH FINISHED CEILING. CAREFULLY COORDINATE WITH
DRYWALL CONTRACTOR TO ENSURE A FLUSH INSTALLATION. DRYWALL
CONTRACTOR SHALL TAPE, MUD, AND SAND AS NEEDED. NO GAP BETWEEN
DEVICE/FIXTURE AND CEILING WILL BE ACCEPTABLE. IF DEEMED THE ONLY
SOLUTION BY THE ARCHITECT OR ENGINEER, THIS CONTRACTOR SHALL
PROVIDE AN APPROVED SEALANT TO SEAL ANY SUCH GAPS THAT EXIST. A
FINAL WALK-THROUGH SHALL BE SCHEDULED WITH THE OWNER TO
APPROVE THE FINISHED CEILING CONDITION.
K. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS
CLEARANCES OF EQUIPMENT BY OTHER TRADES (I.E. VAV BOXES).
COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.
L. WHERE ANY RECEPTACLE IS LOCATED WITHIN 6'-0" OF SINK, CONTRACTOR
SHALL PROVIDE "GFCI" TYPE OUTLET OR CONNECT CIRCUIT TO A 20A/1P GFCI
TYPE CIRCUIT BREAKER. REFER TO ARCHITECTURAL PLANS FOR SINK
LOCATIONS.
M. PROVIDE COORDINATION DRAWINGS FOR REVIEW (BETWEEN FURNITURE
VENDOR, LAB EQUIPMENT VENDORS & CONTRACTOR) PRIOR TO ROUGH-IN(S).
TAGGED NOTES
D9 EXISTING EQUIPMENT INDICATED TO REMAIN AS IS.
L1 PROVIDE 120V/1Ø POWER FROM RECEPTACLE CIRCUIT SERVING
COUNTER TOP RECEPTACLES BELOW.
L5 REFER TO FLOOR PLANS FOR LIGHTING CIRCUIT CONTINUATION.
L12 REFER TO ARCHITECT'S DRAWINGS, DETAILS, ELEVATIONS, ETC. FOR
ADDITIONAL REQUIREMENTS, EQUIPMENT LOCATIONS, ETC. FOR ALL
TYPICAL PATIENT ROOMS.
P2 PROVIDE 120V/1Ø CONNECTION FOR PATIENT LIFT. VERIFY EXACT
REQUIREMENTS WITH MANUFACTURER'S RECOMMENDATIONS PRIOR TO
ROUGH-IN.
P4 JUNCTION BOX MOUNTED ABOVE ACCESSIBLE CEILING DIRECTLY ABOVE
PATIENT BED HEAD WALL UNIT. CONNECT NORMAL AND EMERGENCY
CRITICAL BRANCH POWER CIRCUITS TO HEAD WALL UNIT AS REQUIRED.
REFER TO ARCHITECT'S PATIENT HEADWALL UNIT DETAIL FOR
ADDITIONAL REQUIREMENTS AND INFORMATION.
P6 REFER TO FLOOR PLANS FOR POWER CIRCUITING CONTINUATION.
P10 REFER TO ARCHITECT'S DRAWINGS, DETAILS, ELEVATIONS, ETC. FOR
ADDITIONAL REQUIREMENTS, EQUIPMENT LOCATIONS, ETC. FOR ALL
TYPICAL PATIENT ROOMS.
P23 ROUTE THROUGH MANUFACTURER'S INTEGRAL DISCONNECT SWITCH.
REFER TO MECHANICAL SCHEDULES FOR ADDITIONAL REQUIREMENTS
AND INFORMATION.
S1 NURSE CALL PATIENT BED INTERFACE AND CODE BLUE STATION TO BE
INSTALLED IN PRE-MANUFACTURED HEAD WALL. COORDINATE EXACT
REQUIREMENTS WITH FINAL HEADWALL SELECTIONS AND
MANUFACTURER'S SPECIFICATIONS. REFER TO ARCHITECT'S PATIENT
HEADWALL UNIT DETAIL FOR ADDITIONAL REQUIREMENTS AND
INFORMATION.
S16 PROVIDE JUNCTION BOX MOUNTED ABOVE ACCESSIBLE CEILING
DIRECTLY ABOVE PATIENT BED HEAD WALL UNIT FOR DATA CONNECTION
AS REQUIRED. REFER TO ARCHITECT'S PATIENT HEADWALL UNIT DETAIL
FOR ADDITIONAL REQUIREMENTS AND INFORMATION.
GENERAL NOTES (ROOF):
A. REFER TO POWER, SYSTEMS, AND LIGHTING PLANS FOR GENERAL
NOTES APPLICABLE TO INTERIOR SPACES SHOWN ON THIS PLAN.
B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS
INDICATED ON THE FLOOR PLANS, WITH A MAXIMUM OF THREE (3)
BRANCH CIRCUITS PER HOMERUN. EACH BRANCH CIRCUIT SHALL BE
PROVIDED WITH A DEDICATED NEUTRAL CONDUCTOR. DEDICATED
NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT
CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME
CONDUIT WITH THOSE INDICATED, CONTRACTOR SHALL DERATE ALL
CURRENT CARRYING CONDUCTORS PER NEC 310.15(B)(3), AND UPSIZE
CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX C. MULTIWIRE
BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A
COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.
C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES,
SWITCHES, ETC. IN AREA OF CONSTRUCTION. PROVIDE ENGRAVED
LAMACOID LABLES FOR ALL EXTERIOR DEVICES. MARK INSIDES OF ALL
DEVICE BOXES WITH PANEL AND CIRCUIT NUMBER.
D. PROVIDE UNI-STRUT AS REQUIRED FOR MOUNTING OF ALL DEVICES ON
ROOF. COORDINATE WITH ROOFING CONTRACTOR PRIOR TO
CONSTRUCTION FOR ALL PENETRATIONS. SEAL PENETRATIONS AS
REQUIRED PER ROOFING CONTRACTOR AND ROOFING
MANUFACTURER'S RECOMMENDATIONS AS REQUIRED TO MAINTAIN
ROOF WARRANTY. PROVIDE CURBS AND/OR FLASHED BOOTS AT ALL
DEVICES AND PENETRATIONS.
E. CONDUITS SHALL PENETRATE ROOF FROM BELOW AS CLOSE TO FINAL
ROOF EQUIPMENT TERMINATION POINT AS POSSIBLE. SUPPORT ALL
ROOF MOUNTED CONDUITS AT INTERVALS NOT EXCEEDING 10 FEET
WITH STRUT-BASED SUPPORT SYSTEM. SUPPORT SYSTEM TO BE
CADDY PYRAMID ST SERIES OR APPROVED EQUAL.
F. ALL CONDUIT EXPOSED TO DIRECT SUNLIGHT SHALL BE AT LEAST 12''
ABOVE THE ROOF-TOP. NO CONDUIT SHALL BE EXPOSED TO DIRECT
SUNLIGHT BELOW THIS HEIGHT.
G. WHERE RACEWAY OR CONDUCTORS ARE INSTALLED EXPOSED ON
ROOF, DERATE AMPACITY OF CONDUCTORS IN ACCORDANCE WITH
NEC.
H. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS
SHALL BE COORDINATED WITH MECHANICAL AND PLUMBING
CONTRACTORS TO ENSURE ACCESS AND WORKING CLEARANCE IS
MAINTAINED PER NEC. NOTIFY OTHER TRADES OF REQUIRED
CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE
AREAS. DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT
NAMEPLATES OR ACCESS PANELS OR THROUGH
ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER
TRADES.
I. PROVIDE MAINTENANCE RECEPTACLE WITHIN 25 FT OF EACH
MECHANICAL UNIT AS REQUIRED BY NEC. COORDINATE INSTALLATION
LOCATIONS WITH FINAL EQUIPMENT LAYOUT PROVIDE BY MECHANICAL
CONTRACTOR.
J. CONDUIT FOR ROOF MOUNTED EQUIPMENT SHALL BE ROUTED IN
CEILING SPACE BELOW ROOF DECK UNO.
4' 8' 32'16'0
1/8" = 1'-0"
24'2'
SCALE: 1/8" = 1'-0"
ATTIC PLAN - ELECTRICAL
Revisions: Date:
Addendum #5 11/24/2020
2' 4' 16'8'0
1/4" = 1'-0"
12'1'
SCALE: 1/4" = 1'-0"
ENLARGED 3RD FLOOR PLAN - TYPICAL
ISOLATION PATIENT ROOM - LIGHTING
2' 4' 16'8'0
1/4" = 1'-0"
12'1'
SCALE: 1/4" = 1'-0"
ENLARGED 3RD FLOOR PLAN - TYPICAL
ISOLATION PATIENT ROOM - POWER /
SYSTEMS
2' 4' 16'8'0
1/4" = 1'-0"
12'1'
SCALE: 1/4" = 1'-0"
ENLARGED 3RD FLOOR PLAN - TYPICAL
BARIATRIC PATIENT ROOM - POWER /
SYSTEMS
2' 4' 16'8'0
1/4" = 1'-0"
12'1'
SCALE: 1/4" = 1'-0"
ENLARGED 3RD FLOOR PLAN - TYPICAL
BARIATRIC PATIENT ROOM - LIGHTING
| Sheets |
| GI000 - COVER SHEET |
| AE104 - 3RD FLOOR ARCHITECTURAL PLAN |
| AI601 - FINISH SCHEDULE |
File details come from the government source that posted it. Updated .