P693_Drawings_Final_Vol14.6_20241007.pdf
PDF 6 MB Posted
- Solicitation number
- N6274225R1301
About this file
This document is a pre-solicitation notice for a federal contract opportunity related to the construction (design-bid-build) of a Guam Defense Radar System Command Center, power generation facility, switchgear building, fuel storage facility, entry control facility, and associated equipment.
The project is estimated to cost between $250,000,000 and $500,000,000. Key details include:
- The work includes demolition, civil site work, concrete construction, antenna tower installation, security infrastructure, electrical/telecom systems, and other construction activities.
- Four pre-priced options are available for additional generators, redundancy, and uninterruptible power supply.
- The contract completion period is anticipated to be 1,323 calendar days.
- The solicitation will be posted on the System for Award Management (SAM) website, with a pre-proposal site visit scheduled for 11 December 2024.
- Offerors must meet specified experience, small business utilization, safety, management, and past performance criteria for evaluation.
- The request for proposal (RFP) will be available on or around 30 October 2024.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
07-OCT-2024
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
10/17/2024
Evan Mizue
07-OCT-2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024
10/3/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024 via email
9/24/2024
SECTION ELEVATION
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024 via email
9/24/2024
CAPT Troy Brown, JRM J4 via email
9/24/2024
FACP
CACP
CACP ASP
ASP
A O
A O
A O
A O
A O
A O
NAC
1 2
A
B
C
102101
FACP-14PP53101
ASP-14PP53102
ASP-14PP53101
CACP-14PP52102
CACP-14PP52101
ASP-2
ASP-1
K
K
TS
KNOX BOX LOCATION
WITH TAMPER SWITCH
AIR SAMPLING SYSTEM ZONE
ROOM 101 AND 102
ROOM 103 AND 104
ASP-1
ASP-2
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
JC
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
AWK/DMK
9/
/2
4:
:1
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-FA112
PO
W
ER
P
LA
NT
FI
RE
A
LA
RM
P
LA
N -A
RE
A
A
GSB
17324497
JAB THF
G
UA
M
PP
-F A1
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
A B C
1/8" = 1'-0" 0 8' 16' 24'4'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEY PLAN
SHEET KEYNOTES
PLAN
NORTH
SHEET NAMING CONVENTION
SCALE: 1/8" = 1'-0"A1 FIRE ALARM PLAN - AREA A
A. FOR FIRE PROTECTION ABBREVIATIONS, SYMBOLS, AND LEGEND, SEE
SHEET 14GI-F-001.
B. PROVIDE A FULLY ADDRESSABLE FIRE ALARM SYSTEM IN ACCORDANCE
WITH UFC 3-600-01 AND NFPA 72 AND SPECIFICATIONS.
01. FIELD ROUTE CONDUIT TO CO DETECTION IN EACH GENERATOR
ENCLOSURE. CONTRACTOR MUST PROVIDE SIGNALING LINE CIRCUIT AND
ALL NECESSARY CONNECTIONS TO MONITOR GENERATOR ENCLOSURE
CO DETECTORS. INITIATING DEVICES WITHIN GENERATOR ENCLOSURE
AND CONDUIT PENETRATION IS PROVIDED BY OTHERS.
02. FIELD ROUTE CONDUIT TO IR FLAME DETECTORS IN EACH GENERATOR
ENCLOSURE. CONTRACTOR MUST PROVIDE SIGNALING LINE CIRCUIT AND
ALL NECESSARY CONNECTIONS TO MONITOR GENERATOR ENCLOSURE IR
FLAME DETECTORS. INITIATING DEVICES WITHIN GENERATOR
ENCLOSURE AND CONDUIT PENETRATION IS PROVIDED BY OTHERS.
OPTICAL FLAME
DETECTORS
FULL COVERAGE THROUGHOUT THE
SWITCHGEAR BUILDING AND COMMS
BUILDING. MOUNT DETECTORS IN
ACCORDANCE WITH MANUFACTURER LISTING
AND APPROXIMATELY 7 FT - 10 IN ABOVE
FINISHED FLOOR.
DUCT DETECTOR
(AHU-01PP41101, AHU-01PP41102,
AHU-01PP41103, AHU-01PP41104). SUPPLY SIDE
OF AHU, DOWNSTREAM OF FILTER(S) AND
UPSTREAM OF BRANCH CONNECTIONS.
AIR SAMPLING SYSTEM
SWITCHGEAR BUILDING SIDE A, SWITCHGEAR
BUILDING SIDE B, AND COMMS 105 AS
INDICATED ON DRAWINGS
SMOKE DETECTOR
ABOVE FIRE ALARM CONTROL UNIT, CLEAN
AGENT CONTROL PANEL, REMOTE POWER
SUPPLIES, ROOMS PROTECTED BY CLEAN
AGENT SYSTEM
TAMPER SWITCH KNOX BOX LOCATION(S)
MANUAL FIRE ALARM
PULL STATION WITHIN 5 FEET OF ALL EXTERIOR DOORS
DEVICE LOCATION
INITIATING DEVICE CRITERIA
NO NOTIFICATION REQUIRED
VISIBLE NOTIFICATION REQUIRED
AUDIBLE NOTIFICATION REQUIRED
AUDIBLE AND VISIBLE NOTIFICATION REQUIRED
PATTERN DEVICE COVERAGE CRITERIA
FIRE ALARM SYSTEM DESIGN CRITERIA
LEGEND
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
10/17/2024
4GI-F-001
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
FACP-14PP53101
(POWER PLANT)
BATT
INITIATING DEVICES SLC
NACNOTIFICATION DEVICES
FTR
M
M
M
ASP(TYP OF 2)
M
M
M
M
ALARM
TROUBLE
SUPERVISORY
(TYP OF 2) (CLEAN AGENT
SYSTEM RELEASE)
NOTIFICATION
INITIATING
K O A
PRE-ALARM M
CACP
120 VAC
SPD
FACP-14CC53101
(CC)
SEE SHEET
14CC-FA604
BATT
NETWORK SWITCH
FOP FOP
NETWORK SWITCH
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
JC
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
AWK/DMK
9/
/2
4:
:1
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-FA601
PO
W
ER
P
LA
NT
FI
RE
A
LA
RM
S
EQ
UE
NC
E
OF
O
PE
RA
TI
ON
S
SC
HE
MA
TI
C
GSB
17324498
JAB THF
G
UA
M
PP
-F A6
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET KEYNOTES
SHEET NAMING CONVENTION
26 AIR SAMPLING SYSTEM
(TROUBLE ALARM) X X X
25 CLEAN AGENT SYSTEM
(TROUBLE ALARM) X X X
24 FIRE ALARM CONTROL PANEL
AC POWER FAILURE X X X
26 FIRE ALARM CONTROL PANEL
SUPERVISED COMPONENT FAILURE X X X
22 FIRE ALARM CONTROL PANEL
CIRCUIT FAULT X X X
21 FIRE ALARM CONTROL PANEL
LOW BATTERY VOLTAGE X X X
20 NAC GROUND X X X
19 NAC SHORT X X X
18 NAC OPEN X X X
17 SLC GROUND X X X
16 SLC SHORT X X X
15 SLC OPEN X X X
TROUBLE CONDITIONS
14 DUCT SMOKE DETECTOR X X X X
13 AIR SAMPLING SYSTEM
(ALARM LEVEL - ALERT) X X X
12 CLEAN AGENT SYSTEM
(SUPERVISORY ALARM) X X X
11 TAMPER SWITCH (FD KNOXBOX) X X X
SUPERVISORY SIGNALS
10 IR OPTICAL FLAME DETECTORS (GENSET
ENCLOSURES) X X X
9 IR OPTICAL FLAME DETECTORS X X X X
8 CARBON MONOXIDE DETECTOR (GENSET
ENCLOSURES) X X X X
7 AIR SAMPLING SYSTEM (ALARM LEVEL - FIRE) X X X X
6 CLEAN AGENT SYSTEM - AGENT DISCHARGE (PER
ROOM) X X X X
5 CLEAN AGENT SYSTEM - ALARM (PER ROOM) X X X X
4 CLEAN AGENT SYSTEM - PRE-ALARM (PER ROOM) X X X
3 SPOT TYPE SMOKE DETECTOR IN SPACE
PROTECTED WITH CLEAN AGENT SYSTEM X X X X
2 SMOKE DETECTOR (ABOVE CONTROL PANELS) X X X X
1 MANUAL PULL STATIONS X X X X
FIRE ALARMS A B C D E F G H I J K
A
UD
IO
-V
IS
UA
L F
IR
E
AL
AR
M
IN
DI
CA
TI
ON
B
Y
DE
VI
CE
A
UD
IO
-V
IS
UA
L C
OM
MO
N
S
UP
ER
VI
SO
RY
IN
DI
CA
TI
ON
A
UD
IO
-V
IS
UA
L C
OM
MO
N
T
RO
UB
LE
IN
DI
CA
TI
ON
F
IR
E
AL
AR
M
SI
GN
AL
B
Y D
EV
IC
E
TY
PE
S
UP
ER
VI
SO
RY
S
IG
NA
L (
GE
NE
RA
L)
TR
OU
BL
E
SI
GN
AL
(G
EN
ER
AL
F
IR
E
AL
AR
M
SI
GN
AL
B
Y D
EV
IC
E
S
UP
ER
VI
SO
RY
S
IG
NA
L B
Y D
EV
IC
E
T
RO
UB
LE
S
IG
NA
L B
Y D
EV
IC
E
SH
UT
DO
W
N
AP
PL
IC
AB
LE
S
UP
PL
Y
FA
N
AC
TI
VA
TE
A
UD
IO
-V
IS
UA
L A
LA
RM
S
TH
RO
UG
HO
UT
B
UI
LD
IN
G
ANNUNCIATION AT
LOCAL PANEL
TRANSMIT SIGNALS TO
FIRE STATION
TRANSMIT SIGNAL TO
COMMAND CENTER
FACP
AUXILIARY
FUNCTIONS
ALARM
SIGNALS
FIRE ALARM SEQUENCE OF OPERATIONS
SCALE: NTSA1 FIRE ALARM SCHEMATIC
A. FOR FIRE PROTECTION ABBREVIATIONS, SYMBOLS, AND LEGEND, SEE
SHEET 14GI-F-001.
01. FIRE ALARM RADIO TRANSMITTER COMPATIBLE WITH EXISTING AAFB
RECEIVING EQUIPMENT (MONACO).
02. SEE ES SITE PLAN DRAWINGS FOR WIDE AREA MNS SPEAKER ASSEMBLY
LOCATIONS.
TRANSMISSION ZONES
ZONE 1 - MANUAL FIRE ALARM STATION
ZONE 2 - SMOKE DETECTOR (INCLUDES AIR SAMPLING)
ZONE 3 - IR OPTICAL FLAME DETECTOR
ZONE 4 - CARBON MONOXIDE DETECTOR
ZONE 5 - CLEAN AGENT ALARMS
ZONE 6 - SUPERVISORY - GENERAL
ZONE 7 - TROUBLE - GENERAL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
10/17/2024
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
JC
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
AWK/DMK
9/
/2
4:
:1
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-FA602
PO
W
ER
P
LA
NT
CL
EA
N
AG
EN
T
SE
QU
EN
CE
O
F
OP
ER
AT
IO
NS
GSB
17324499
JAB THF
G
UA
M
PP
-F A6
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
A. FOR FIRE PROTECTION ABBREVIATIONS, SYMBOLS, AND LEGEND, SEE
SHEET 14GI-F-001.
14 CONTROL PANEL - AC POWER FAILURE X X
13 CONTROL PANEL - COMPONENT FAILURE X X
12 CONTROL PANEL - CIRCUIT FAULT X X
11 CONTROL PANEL - LOW BATTERY/MISSING BATTERY X X
10 OPEN, SHORT OR GROUND IN ANY CIRCUIT X X X
TROUBLE SIGNALS
9 REMOVAL OF CLEAN AGENT SOLENOID X X
8 ACTIVATION OF KEY DISCONNECT SWITCH X X X X
7 RELEASE OF SYSTEM ABORT SWITCH X
6 ACTIVATION OF SYSTEM ABORT SWITCH X X X
SUPERVISORY SIGNALS
5 CLEAN AGENT RELEASE PRESSURE SWITCH ACTIVATE X X X X
4 AIR SAMPLING IN ALARM MODE AND SPOT TYPE DETECTOR
IN SPACE PROTECTED WITH CLEAN AGENT SYSTEM X X X X
3 SPOT TYPE SMOKE DETECTOR IN SPACE PROTECTED WITH
CLEAN AGENT SYSTEM X X X X
2 AIR SAMPLING SYSTEM - ALARM LEVEL "FIRE" X X X
1 CLEAN AGENT ROOM MANUAL RELEASE STATION X X X X X X
ALARM SIGNALS A B C D E F G H I J K L M N O P Q R
AC
TI
VA
TE
V
IS
UA
L A
ND
A
UD
IB
LE
A
LA
RM
A
NN
UN
CI
AT
OR
AC
TI
VA
TE
V
IS
UA
L A
ND
A
UD
IB
LE
S
UP
ER
VI
SO
RY
A
NN
UN
CI
AT
OR
AC
TI
VA
TE
V
IS
UA
L A
ND
A
UD
IB
LE
T
RO
UB
LE
A
NN
UN
CI
AT
OR
AC
TI
VA
TE
A
UD
IB
LE
N
OT
IF
IC
AT
IO
N
AP
PL
IA
NC
ES
IN
S
PA
CE
IN
IT
IA
TE
A
GE
NT
P
RE
-R
EL
EA
SE
C
OU
NT
DO
W
N
SE
QU
EN
CE
AC
IV
AT
E
RE
D
AG
EN
T
PR
E-
RE
LE
AS
E 'C
OU
NT
DO
W
N' B
EA
CO
NS
IN
P
RO
TE
CT
ED
S
PA
CE
RE
SU
ME
A
GE
NT
P
RE
-R
EL
EA
SE
C
OU
NT
DO
W N
SE
QU
EN
CE
AC
TI
VA
TE
B
LU
E
BE
AC
ON
S
OU
TS
ID
E
PR
OT
EC
TE
D
SP
AC
E
DI
SC
HA
RG
E
CL
EA
N
AG
EN
T
DI
SA
BL
E
SO
LE
NO
ID
B Y
OP
EN
IN
G
SO
LE
NO
ID
C
IR
CU
IT
PR
EV
EN
T
CL
EA
N
AG
EN
T
SY
ST
EM
A
CT
IV
AT
IO
N
CL
OS
E
AL
L F
IR
E/
SM
OK
E
DA
MP
ER
S
AN
D
MO
TO
R
OP
ER
AT
ED
D
AM
PE
RS
IN
D
UC
T
PE
NE
TR
AT
IN
G
PR
OT
EC
TE
D
SP
AC
E
TR
AN
SM
IT
'C
LE
AN
A
GE
NT
S
YS
TE
M
AC
TI
VA
TI
ON
S
TA
TO
N'
TR
AN
SM
IT
'C
LE
AN
A
GE
NT
S
YS
TE
M
SU
PE
RV
IS
OR
Y'
TR
AN
SM
IT
'C
LE
AN
A
GE
NT
S
YS
TE
M
TR
OU
BL
E'
TR
AN
SM
IT
'C
LE
AN
A
GE
NT
S
YS
TE
M
DI
SC
HA
RG
E'
TR
AN
SM
IT
C
LE
AN
A
GE
NT
'2
ND
R
EL
EA
SI
NG
Z
ON
E
AL
AR
M'
TR
AN
SM
IT
"1
ST
R
EL
EA
SI
NG
Z
ON
E
AL
AR
M
- C
LE
AN
A
GE
NT
P
RE
-R
EL
EA
SE
CO
UN
TD
OW
N
PE
ND
IN
G.
ANNUNCIATION AT
LOCAL CONTROL
PANEL
AUXILIARY FUNCTIONS BY LOCAL CONTROL PANEL SIGNAL TRANSMISSION TO BUILDING FACP
CLEAN AGENT SEQUENCE OF OPERATIONS
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
10/17/2024
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
JC
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
AWK/DMK
9/
/2
4:
:2
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-FA603
PO
W
ER
P
LA
NT
AI
R
SA
MP
LIN
G
SE
QU
EN
CE
O
F
OP
ER
AT
IO
NS
GSB
17324500
JAB THF
G
UA
M
PP
-F A6
FINAL DESIGN SUBMITTAL
A. FOR FIRE PROTECTION ABBREVIATIONS, SYMBOLS, AND LEGEND, SEE
SHEET 14GI-F-001.
10 AIR FLOW ISSUE X X
9 DIRTY FILTERS OR CHANGE FILTER X X
8 CONTROL PANEL - AC POWER FAILURE X X
7 CONTROL PANEL - COMPONENT FAILURE X X
6 CONTROL PANEL - CIRCUIT FAULT X X
5 CONTROL PANEL - LOW BATTERY/MISSING BATTERY X X
4* AIR SAMPLING SYSTEM - ALARM LEVEL "ALERT" X X
TROUBLE SIGNALS
3 AIR SAMPLING SYSTEM - ALARM LEVEL "ACTION" X X
SUPERVISORY SIGNALS
2 AIR SAMPLING SYSTEM - ALARM LEVEL "FIRE 1" X X
1 AIR SAMPLING SYSTEM - ALARM LEVEL "FIRE 2" X X
ALARM SIGNALS A B C D E F G H
AC
TI
VA
TE
V
IS
UA
L A
ND
A
UD
IB
LE
'A
LE
RT
' A
NN
UN
CI
AT
OR
AC
TI
VA
TE
V
IS
IB
LE
A
ND
A
UD
IB
LE
'A
CT
IO
N'
A
NN
UN
CI
AT
OR
AC
TI
VA
TE
V
IS
IB
LE
A
ND
A
UD
IB
LE
'F
IR
E 1'
AN
NU
NC
IA
TO
R
AC
TI
VA
TE
V
IS
IB
LE
A
NN
UN
CI
AT
OR
'F
IR
E 2'
AN
NU
NC
IA
TO
R
AC
TI
VA
TE
V
IS
IB
LE
A
ND
A
UD
IB
LE
T
RO
UB
LE
A
NN
UN
CI
AT
OR
TR
AN
SM
IT
'A
IR
S
AM
PL
IN
G
SY
ST
EM
A
LA
RM
' T
O
FA
CP
TR
AN
SM
IT
'A
IR
S
AM
PL
IN
G
SY
ST
EM
S
UP
ER
VI
SO
RY
' T O
FA
CP
TR
AN
SM
IT
'A
IR
S
AM
PL
IN
G
SY
ST
EM
T
RO
UB
LE
' T O
FA
CP
ANNUNCIATION AT LOCAL CONTROL PANEL SIGNAL TRANSMISSION
AIR SAMPLING SEQUENCE OF OPERATIONS
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
10/17/2024
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
1 2
A
B
C
103104
CA-2
CA-1 CLEAN AGENT ZONE:
ROOM 101 AND 102
ROOM 103 AND 104
CA-1
CA-2
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
JC
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
AWK/DMK
9/
/2
4:
:1
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-FX112
PO
W
ER
P
LA
NT
FI
RE
P
RO
TE
CT
IO
N
PL
AN
AR
EA
A
GSB
17324501
JAB THF
G
UA
M
PP
-F X1
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
A B C
1/8" = 1'-0" 0 8' 16' 24'4'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEY PLAN
SHEET KEYNOTES
LEGEND
PLAN
NORTH
SHEET NAMING CONVENTION
SCALE: 1/8" = 1'-0"A1 FIRE PROTECTION PLAN - AREA A
A. FOR FIRE PROTECTION ABBREVIATIONS, SYMBOLS, AND LEGEND,
SEE SHEET 14GI-F-001.
B. ALL SYSTEMS MUST BE DESIGNED IN ACCORDANCE WITH NFPA 2001 FOR
CLASS C ENERGIZED ELECTRICAL EQUIPMENT.
C. SYSTEM AGENT MUST BE FK 5-1-12.
D. DESIGN ROOM TEMPERATURE MUST BE BASED UPON 77 DEG F.
E. SYSTEM DESIGN MUST REMOVE VOLUME OF EQUIPMENT FROM ROOM
SPACES.
F. SYSTEM DESIGN MUST PROTECT THE ENTIRE ADJUSTED VOLUME OF THE
ROOM.
01. CLEAN AGENT CYLINDERS (TYP)
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
10/17/2024
4GI-F-001
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024 via email
9/24/2024
1 2 3
A
B
C
AREA B
(NOT USED)
AREA A
14PP-P-102
AREA C
(NOT USED)
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEET 14GI-P-001.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:0
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-P-101
PO
W
ER
P
LA
NT
UN
DE
RS
LA
B
PL
UM
BI
NG
P
LA
N -O
VE
RA
LL
MAM
17324505
JAB THF
G
UA
M
PP
-P -1
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
A B C
1/16" = 1'-0" 0 16' 32' 48'8'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEY PLAN
PLAN
NORTH
SHEET NAMING CONVENTION
SCALE: 1/16" = 1'-0"A1 UNDERSLAB PLUMBING PLAN - OVERALL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-P-001
14PP-P-102
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
1 2
B
C
M
AT
C H
L
IN
E N
O N
E
6" RV (UP)
REFER TO CIVIL FOR
CONTINUATION
14ST-CU106
3/4" PW (UP)
INV EL. = -7' - 8" BFFE
3/4" PW
6" RV
6" RV
6" RV
1 1/2" PW
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEET 14GI-P-001.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:2
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-P-102
PO
W
ER
P
LA
NT
UN
DE
RS
LA
B
PL
UM
BI
NG
P
LA
N -A
RE
A
A
MAM
17324506
JAB THF
G
UA
M
PP
-P -1
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
A B C
1/8" = 1'-0" 0 8' 16' 24'4'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEY PLAN
SHEET KEYNOTES
PLAN
NORTH
SHEET NAMING CONVENTION
SCALE: 1/8" = 1'-0"A1 UNDERSLAB PLUMBING PLAN - AREA A
01. PROVIDE RESTRAINED COUPLING AT INTERFACE BETWEEN
BUILDING SYSTEM AND SITE SYSTEM
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-P-001
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
1 2 3
B
C
AREA B
(NOT USED)
AREA A
14PP-P-112
AREA C
(NOT USED)
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEET 14GI-P-001.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:1
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-P-111
PO
W
ER
P
LA
NT
FI
RS
T
FL
OO
R
PL
UM
BI
NG
P
LA
N
-O
VE
RA
LL
MAM
17324507
JAB THF
G
UA
M
PP
-P -1
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
A B C
1/16" = 1'-0" 0 16' 32' 48'8'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEY PLAN
PLAN
NORTH
SHEET NAMING CONVENTION
SCALE: 1/16" = 1'-0"A1 FIRST FLOOR PLUMBING PLAN - OVERALL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-P-001
14PP-P-112
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
1 2
B
C
HB-2FCU-14PP41102
FCU-14PP41101
3/4" PW
M
AT
C H
L
IN
E N
O N
E
6" RV (UP)
BFP-14PP12101
1 1/4" CD
1 1/4" CD
EEW-14PP12101
EEW-14PP12102
HB-2
AHU-14PP41102
AHU-14PP41101
3/4" PW (DN)
MAU-14PP41101
3/4" CD
MAU-14PP41102
3/4" CD
HB-2
HB-2
3/4" CD
3/4" CD
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEET 14GI-P-001.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:3
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-P-112
PO
W
ER
P
LA
NT
FI
RS
T
FL
OO
R
PL
UM
BI
NG
P
LA
N
-A
RE
A A
MAM
17324508
JAB THF
G
UA
M
PP
-P -1
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
A B C
1/8" = 1'-0" 0 8' 16' 24'4'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEY PLAN
SHEET KEYNOTES
PLAN
NORTH
SHEET NAMING CONVENTION
SCALE: 1/8" = 1'-0"A1 FIRST FLOOR PLUMBING PLAN - AREA A
01. ROUTE CONDENSATE DRAIN TO EXTERIOR OF BUILDING
WITH DISCHARGE AT GRADE. DISCHARGE MUST BE
PROVIDED WITH INSECT SCREEN.
02. FAN COIL UNIT IS ABOVE THE DOOR.
03. ROUTE THE BACK FLOW PREVENTER RELIEF DISCHARGE TO
EXTERIOR SPLASH BLOCK.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-P-001
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
HB
WATER OUTLET
4'-0"
OFF FLOOR
ISOLATION VALVE
(TYP)
UNION
WALL PIPE
SUPPORT
AIR GAP
DRAIN
STRAINER
REDUCED PRESSURE
BACKFLOW
PREVENTER
WALL PIPE
SUPPORT
WATER INLET
SPLASH BLOCK
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEET 14GI-P-001.
GRADE
BUILDING
EXTERIOR WALL
ISOLATION VALVE
DRAIN VALVE
W/ HOSE
CONNECTION
FINISHED FLOOR
PIPE SLEEVE
PW
FOOTING
FOUNDATION
WALL
PW TO BUILDING
SYSTEM SEE PLANS
FOR SIZE
PW
SEE CIVIL
PLANS
FOR SIZE
PIPE ADAPTER
AS REQUIRED
12" MIN FOOTING
TO TOP OF PIPE
SEE PLANS FOR
SIZE
AB
OV
E
FL
OO
R
WALL SUPPORT BRACKETS AT 48"
O.C. MIN BUT NOT LESS THAN TOP,
BOTTOM AND CENTER.
ISOLATION VALVE
COLD WATER RISER
EDGE OF WALL
OR COLUMN
NOTES:
1. COORDINATE MOUNTING HEIGHT OF HOSE BIBB WITH STRANDS AND/OR
GUARDRAIL. WHEN CONDITIONS ALLOW, ROTATE WALL FAUCET
CONNECTIONS (APPROX 90°) TO LIMIT INTERFERENCE IN DECK.
WALL SUPPORT
BRACKETS AT 48" O.C. MIN
BUT NOT LESS THAN TOP,
BOTTOM AND CENTER.
EDGE OF WALL
OR COLUMN
PIPE GUARD (WHERE
REQUIRED)
GROUND
CONDENSATE LINES SHALL BE SLOPED
FROM UNIT TO SPLASH BLOCK OF NOT
LESS THAN 1/8 INCH PER FOOT.
AIR GAP (MINIMUM 1")
CONCRETE SPLASH BLOCK
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:3
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-P-501
PO
W
ER
P
LA
NT
PL
UM
BI
NG
D
ET
AI
LS
MAM
17324509
JAB THF
G
UA
M
PP
-P -5
FINAL DESIGN SUBMITTAL
SCALE: NTSD3 BACKFLOW PREVENTER DETAIL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
SCALE: NTSA3 WATER ENTRY DETAIL
SCALE: NTSD1 HOSE BIBB DETAIL - RISER
SCALE: NTSA1 HOSE BIBB DETAIL - WALL MOUNTED
SCALE: NTSC1 CONDENSATE DRAIN DETAIL - SPLASH BLOCK
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-P-001
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEET 14GI-P-001.
EXTERIOR WALL
GRADE OUTSIDE
BUILDING FOUNDATION WALL
PRESSURE
MONITORING/WARNING
CONCRETE FLOOR
SIZE #57 AGGREGATE
(1/2" - 1" DIAMETER)
CAPPED PIPE
EARTH/DIRT
PVC PIPE WITH 3/4" PERFORATIONS (10
EVERY 12" MINIMUM). PIPING SLOPED AT 1/8"
PER FOOT AWAY (FOR THE FIRST 5 FEET)
FROM VENT RISER. REFER TO PLANS FOR
PIPE SIZE. PIPING MUST BE A MINIMUM 240
FEET IN TOTAL LENGTH PER LOCATION.
ROOF STRUCTURE
RAIN COVER
VAPOR BARRIER
PROVIDE PERFORATION AT THE
END OF PIPING FOR DRAINAGE
4" M
IN
IM
U M
2" M
IN
IM
U M
NOTES:
1. RADON FAN TO BE INSTALLED BY OTHERS POST CONSTRUCTION IF
RADON LEVELS DETERMINE NECESSITY BASED ON EPA
REQUIREMENTS.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:4
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-P-502
PO
W
ER
P
LA
NT
PL
UM
BI
NG
D
ET
AI
LS
MAM
17324510
JAB THF
G
UA
M
PP
-P -5
FINAL DESIGN SUBMITTAL
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
SCALE: NTSA1 RADON SYSTEM DETAIL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-P-001
DISCHARGE MUST BE A
MINIMUM OF 10'-0" ABOVE THE
ROOF LINE AND A MINIMUM OF
30'-0" FROM ANY OUTDOOR AIR
INTAKE.
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEET 14GI-P-001.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:1
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-P-701
PO
W
ER
P
LA
NT
PL
UM
BI
NG
S
CH
ED
UL
ES
MAM
17324511
JAB THF
G
UA
M
PP
-P -7
FINAL DESIGN SUBMITTAL
HB-2 HOSE BIBB 3/4" - - - - - DETACHABLE KEY HANDLE
TAG DESCRIPTION
COLD
WATER
SIZE
HOT
WATER
SIZE
SANITARY
OUTLET
VENT
SIZE V / PH / A FLOW/ FLUSH
VOLUME REMARKS
PLUMBING FIXTURE SCHEDULE
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
1. SELF-CONTAINED EMERGENCY EYEWASH WITH AUDIBLE/VISUAL ALARM.
REMARKS:
EEW-14PP12102 ROOM 104 AMBIENT 15 MINUTES @ 0.4 GPM 120 1
EEW-14PP12101 ROOM 101 AMBIENT 15 MINUTES @ 0.4 GPM 120 1
EQUIPMENT TAG LOCATION
TEPID WATER
OUTPUT
(°F)
TEPID WATER
DELIVERY
DURATION
V REMARKS
EMERGENCY EYEWASH SCHEDULE
REMARKS:
BFP-14PP12101 MECHANICAL YARD REDUCED PRESSURE ZONE 3/4 5 14 -
TAG LOCATION TYPE SIZE (IN.)
DESIGN
FLOW
RATE
(GPM)
MAXIMUM
PRESSURE
DROP
(PSIG)
REMARKS
BACKFLOW PREVENTER SCHEDULE
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-P-001
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
FCU-14PP41101
6" RVFCU-14PP41102
1 1/4" CD
3/4" CD
AHU-14PP41101
AHU-14PP41102
MAU-14PP41101
3/4" CD
MAU-14PP41102
3/4" CD
6" RV
6" RV
6" RV
3/4" CD
1 1/4" CD
TO GRADE
TO GRADE
TO GRADE
TO GRADE
TO GRADE
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEET 14GI-P-001.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:1
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-P-901
PO
W
ER
P
LA
NT
PL
UM
BI
NG
S
AN
IT
AR
Y
W
AS
TE
A
ND
V
EN
T
RI
SE
R
DI
AG
RA
M
MAM
17324512
JAB THF
G
UA
M
PP
-P -9
FINAL DESIGN SUBMITTAL
SCALE: NTSA1 PLUMBING SANITARY WASTE AND VENT RISER DIAGRAM
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-P-001
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024
HB-2
3/4" PW
REFER TO CIVIL
SHEET 14ST-CU106
FOR CONTINUATION
BFP-14PP12101
EEW-14PP12102
EEW-14PP12101
HB-2
3/4" PW
HB-2
HB-2
3/4" PW
3/4" PW
3/4" PW
A. FOR GENERAL NOTES, LEGENDS, AND ABBREVIATIONS SEE
SHEET 14GI-P-001.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
SY
S
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VF
AC
P
AC
IF
IC
M
A K
AL
AP
A , H
A W
AI
I
AS NOTED
PR
O
JE
C
T
SI
TE
C
O M
M
AN
D C
EN
TE
R
N
AV
FA
C
P
AC
IF
IC
1812861
KYM
JC
Jacobs/B&V, A Joint Venture (Federal Services) 1003 Bishop Street Suite 1340 Honolulu, HI 96813
A/E Task Order No. N6274223F0324
AN
DE
RS
EN
A
IR
F O
RC
E
BA
SE
LJE
AWK/DMK
9/
/2
9:
:2
PM
P6
_1
_1 4P
P_ M
_d et ac he d.
rv t
14PP-P-902
PO
W
ER
P
LA
NT
PL
UM
BI
NG
D
OM
ES
TI
C
W
AT
ER
R
IS
ER
D
IA
GR
AM
MAM
17324513
JAB THF
G
UA
M
PP
-P -9
FINAL DESIGN SUBMITTAL
SCALE: NTSA1 PLUMBING DOMESTIC WATER RISER DIAGRAM
14CC-A-101
SITE #
BUILDING ID DISCIPLINE
CONSECUTIVE NUMBERS
SITE #
SITE 01
SITE 02
SITE 14
BUILDING ID
AC - ACCESS CONTROL POINT
CC - COMMAND CENTER
FP - FIRE PUMP BUILDING
GI - GENERAL
PP - POWER PLANT
SF - SECURITY FORCE
ST - SITE
GENERAL SHEET NOTES
SHEET NAMING CONVENTION
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
14GI-P-001
Approved By
CAPT Troy Brown, JRM J4 via email
9/24/2024