20R1334-Note7.pdf
PDF 29 KB Posted
- Attached to
- FY21 MCAF P-3001/AJJY203001, APSI - STANDOFF WEAPONS COMPLEX, MSA2, ANDERSEN AIR FORCE BASE, GUAM
- Solicitation number
- N6274220R1334
About this file
This document includes a solicitation for the construction of facilities at Andersen Air Force Base in Guam to support standoff weapons. The work includes alterations and construction of additions to existing buildings to support missile maintenance and preloading of rotary launchers. It also includes improving roadways to support loaded munitions trailers, constructing a powered trailer maintenance facility, and building two new earth covered magazines for weapons storage. The solicitation was issued by the Naval Facilities Engineering Command Pacific. The opportunity type is listed as a solicitation, with no further pricing or response deadline details provided.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 20R1334-Note8.pdf | ||
| 20R1334 AMD 0006.pdf | ||
| 20R1334-AMD 0005.pdf | ||
| 20R1334-Note6.pdf | ||
| 20R1334-Amd 0004 Spec 02 41 00 - Attach A.pdf | ||
| 20R1334-Amd 0004.pdf | ||
| 20R1334-Note5.pdf | ||
| 20-R-1334-Amd 0003.pdf | ||
| 20R1334-Note4.pdf | ||
| 20R1334-AMD2.pdf | ||
| 20R1334-Note3.pdf | ||
| 20R1334-SV SignIn.PDF | ||
| 20R1334-AMD1.pdf | ||
| 20R1334-Note2.pdf | ||
| 20R1334-Note1.pdf | ||
| 20R1334-Specs_Part2of2.pdf | ||
| 20R1334-JAs.zip | ZIP file | |
| 20R1334-RFP.pdf | ||
| 20R1334-Specs_Part1of2.pdf | ||
| 20R1334-Dwgs.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE NAVY
NAVAL FACILITIES ENGINEERING COMMAND, PACIFIC
258 MAKALAPA DR., STE. 100
PEARL HARBOR, HI 96860-3134
Notice No. 7 10 November 2020
PRE-PROPOSAL QUESTIONS & ANSWERS
RFP N62742-20-R-1334
FY21 MCAF P-3001/AJJY203001 APSI – STANDOFF WEAPONS COMPLEX,
MSA2, ANDERSEN AIR FORCE BASE, GUAM
NOTE: The following questions and answers are provided for INFORMATION ONLY. The RFP remains unchanged unless it is amended in writing on a Standard Form 30.
83. Specifications, Part 1 of 2, Section 01 14 00, para 1.4.8, Limitations with Munitions Storage Areas. In the specifications section 01 14 00 under paragraph 1.4.8, it states “Staging areas are provided within the Munitions Storage Area (MSA2). Storage of hazardous and combustible materials is prohibited with the MSA 2. Refueling operations are not permitted within the MSA
2. Access routes to the project site must minimize obstructions to munitions operations.”
Please provide the locations of the areas for the refueling of equipment (e.g. light towers run by gen set, payloader, excavator, cranes, etc.)
ANSWER: Refueling of equipment will be permitted in the Contractor’s Staging/Laydown Area in Free Zone 1B. Specification Section 01 14 00, Para. 1.4.8 will be clarified in a forthcoming Amendment
84. Specifications, Part 1 of 2, Section 01 57 19.03, JRM MEC. In the Specifications section 01 57 19.03, under paragraph JRM MEC, it indicates “ Risk Decision Letter Commander, Joint Region Marianas Letter to Commander Naval Facilities Engineering Command Pacific titled MEC Risk Decision on FY19 MCAF Project P-83003/AJJY183003 Hayman Munitions Storage Igloos, MSA 2 at Andersen Air Force Base dated 24 June 2019.
Please provide a copy of this letter as it may affect the MEC/MPPEH operation for estimating purposes.
In addition, please clarify if this supersedes JRM-ESS Amendment No. 7.
ANSWER: The “Risk Decision Letter Commander, Joint Region Marianas letter to Commander Naval Facilities Engineering Command Pacific titled MEC Risk Decision on FY19 MCAF Project P-83003/AJJY183003 Hayman Munitions Storage Igloos, MSA 2 at Andersen Air Force Base dated 24 June 2019” does not apply and will be removed from the Specifications in a forthcoming Amendment.
85. RFP SF 1442 and Specifications, Part 1 of 2, Section 01 57 19.03, Solicitation Price Proposal Schedule, Note 4. On the SF 1442 Price Proposal Schedule, the Notes 4 found on page 3 states “Price for SLIN 0001AB shall cover all costs to perform Full Clearance Ahead of Construction for MEC/MPPEH in accordance with section 01 57 19.03, including but not limited to all costs associated with the MEC/UXO response team. The MEC/UXO response team shall consist of a minimum of nine (9) personnel: a Senior UXO Supervisor, a UXO Safety Officer/Quality Control Specialist, a UXO Technician III, and six (6) UXO Technicians II/I.”
However, the specification section 01 57 19.03 or the JRM-ESS Amendment #07 does not specifically require the number of MEC teams as noted above.
Please confirm if we are required to provide the MEC Teams as mentioned under the Notes 4.
ANSWER: The Contractor is responsible for determining the number of personnel and teams required to complete the MEC clearance work in the required timeframe.
86. Notice No 4, Pre-Proposal Questions & Answers, Page 3, Question and Answer No. 42. RFI Question- Reference Specification 01 57 19.01 20 paragraph 3.4.1 requires full clearance of MEC ahead of construction in areas with High-Likelihood of Encountering MEC/MPPEH.
Please clarify locations on the project site that meet this criteria.
NAVFAC Answer – Unless otherwise directed by the Contracting Officer, the whole project site is located in areas that are likely to encounter MEC/MPPEH.
Please confirm if the additional excavation at bottom of the existing AC Pavement and its base course (to accommodate the 13” thick PCCP and 8” base course), which is considered undisturbed, will require FULL MEC CLEARANCE.
ANSWER: Unless otherwise directed by the Contracting Officer, the whole project site is located in areas that are likely to encounter MEC/MPPEH. Refer to Specification Section 01 57
19.01 20, Para. 3.4.1.
87. Notice No 4, Pre-Proposal Questions & Answers, Pages 2 and 3, Question and Answer No.
41. Night work will be allowed for MEC pending proper coordination and approvals from the Contracting Officer. The Specifications will be clarified in a forthcoming Amendment.
Please confirm if equipment is required to be hooded during MEC night work.
ANSWER: Confirmed.
88. Drawings, Page 124, 130 & 144, SF131, S-331 and S-535, Section B1 Typical Precast Double Tee Detail. Local Manufacturer can only fabricate 8 ft. wide 32 in. Double Tees and not 10 ft wide as shown on the drawing S-535 Section B1 Typical Precast Double Tee Detail.
Please confirm if 8 ft. wide 32 in. Double Tees are acceptable to the Government.
ANSWER: Confirmed (8 ft. wide 32 in. double tees are acceptable).
89. Specifications, Part 1 of 2, Section 01 14 00, Page 2, para 1.3 Special Scheduling Requirements/Page 5, para 1.4.4 Exclusionary Period/Section 01 32 17.00 20, Page 12, para
1.10.2.9 Anticipated Restricted Delays.
States in the specifications, under section 01 14 00, paragraph 1.3 Special Scheduling Requirements, Item j: “The contractor must allow for work delays totaling 20 workdays per calendar year (may not be consecutive). These delays may be due to Government/36 MUNS operations, exercises, etc.”
States in the specifications, under section 01 14 00, paragraph 1.4.4 Exclusionary Period that “Work performed during the months of February (every year) and September (even numbered years) may be restricted and/or stopped without prior notification from the Contracting Officer.”
States in the specifications, under section 01 32 17.00 20, paragraph 1.10.2.9 Anticipated Restricted Delays that “Unless otherwise noted or defined in Section 01 14 00 Work Restrictions, allow in the schedule two lost work days for every two months of project duration for instances where base access is not permitted or where work areas are temporarily not accessible for security reasons which causes a delay in the work.”
Please confirm if the 20 workdays delay is already included the Exclusionary Period and Anticipated Restricted Delay.
ANSWER: Yes, 20 workdays/calendar year delays are included in the Exclusionary Period (FEB 2022 & 2023) and Anticipated Restricted Delay (SEP 2022).
Specification Section 01 14 00 will be clarified in a forthcoming Amendment.
Specification Section 01 32 17.00 20, Para. 1.10.2.9 will be deleted in a forthcoming Amendment.
90. Drawing, Page 143, S-532, Section A1/Note 1. Note 1 states see A1/S-531 for Ifoundation Reinforcing. What is the intent of this reference?
ANSWER: The “I” in “IFOUNDATION” is a typographical error. Note 1 will be corrected to read “RE: A1/S-531 FOR FOOTING REINFORCEMENT.” in a forthcoming Amendment.
91. Drawing, Page 143, S-532, Section A1/Note 2. Note 2 states RE: plumbing for trench catch basins – what is the intent of this note as it has no reference point in Section A1/Note 2?
ANSWER: Note 2 identifies element as a trench catch basin and refers viewer to plumbing drawings.
92. Drawing, Page 122, SB-131, Section A1/PTMX Foundation Plan. What does the wall along line A to the left of line 1 sit on and what is the base elevation of the wall here since there is no footing/grade beam to build off or reference to?
ANSWER: The wall shown extending along column line A to the left of column line 1 is a drafting error and drawing will be revised in a forthcoming Amendment
93. Drawing, Page 5, GB-100, Scope of Work, General Note A. Please confirm buildings 51258 and 51259 can be found labeled on drawing B-100 and CD-100, for example.
ANSWER: Confirmed.
94. Drawing, Page 149, AD110, Keynote 011 and 007. Please confirm that once the equipment referenced by these keynotes is removed, it will not be necessary to provide temporary HVAC to the spaces they currently serve to heat and cool.
ANSWER: Temporary HVAC is not required for the spaces with demolished mechanical equipment. New HVAC equipment should be installed in coordination with electrical equipment installation to ensure spaces are conditioned when power is activated.
95. Section 31 23 00.00 20, Amendment 0004, Page 12, Section 3.3.4. For disposition of surplus material not required or suitable for backfilling what should the proposer assume for the Munitions of Explosive Concern condition of the surplus material. Is the material to be considered full clearance ahead of construction (screened to 20mm) or limited clearance ahead of construction (screened to 60 mm)?
ANSWER: Refer to Specification Sections 01 57 19.01 20 and 01 57 19.03.
96. Drawing (AMD 0003)/Section 01 14 00. Drawing 005 (GB-100), Free Zone Notes on drawing and Section 01 14 00, paragraph 1.3.f. Free Zone 1B – Are the 144 working days on drawing GB100 all the working days that will be allowed to construct the powered trailer maintenance facility? In other words, once the Free Zone 1B is set up in accordance with section 014 14 00 will it be required to be taken down upon the contractor expending 144 working days in Free Zone 1B? What is meant by “may be used during entire construction” duration?
ANSWER: The Contractor will have use/control of Free Zone 1B and Free Zone 3 for the entire construction period; AAFB/36 MUNS access to at least one end/vehicle entrance of the “DRIVE-THRU MUNITIONS STORAGE MAGAZINES” must be provided at all times.
97. Drawing (AMD 0003/Section 01 14 00. Drawing 005 (GB-100), Free Zone Notes on drawing and Section 01 14 00, paragraph 1.3.f. Free Zone 3 – Are the 178 working days on drawing GB100 all the working days that will be allowed to construct the two ECMs? In other words, once the Free Zone 3 is set up in accordance with section 014 14 00 will it be required to be taken down upon the contractor expending 178 working days in Free Zone 3 for the ECMs?
What is meant by “may be used during entire construction” duration?
ANSWER: The Contractor will have use/control of Free Zone 1B and Free Zone 3 for the entire construction period; AAFB/36 MUNS access to at least one end/vehicle entrance of the “DRIVE-THRU MUNITIONS STORAGE MAGAZINES” must be provided at all times.
98. Drawing (AMD 0003)/Section 01 14 00. Drawing 005 (GB-100), Free Zone Notes on drawing and Section 01 14 00, paragraph 1.3.f. Free Zone 3 – Are the 168 working days on drawing GB100 all the working days that will be allowed to construct the Missile Assembly Shop (MSA)? In other words, once the Free Zone 3 is set up in accordance with section 014 14 00 will it be required to be taken down upon the contractor expending 168 working days in Free Zone 3 for the ECMs? What is meant by “may be used during entire construction” duration?
ANSWER: The Contractor will have use/control of Free Zone 1B and Free Zone 3 for the entire construction period; AAFB/36 MUNS access to at least one end/vehicle entrance of the “DRIVE-THRU MUNITIONS STORAGE MAGAZINES” must be provided at all times.
99. Drawing (AMD 0003)/Section 01 14 00. Drawing 005 (GB-100), Free Zone Notes on drawing and Section 01 14 00, paragraph 1.3.f. In Zone 3 there are multiple work areas (e.g.
Roads, ECMs, MSA). Can each work are have its own Free Zone rather than one large Free Zone encompassing all of them? Can each work zone run concurrently?
ANSWER: The Contractor will have use/control of Free Zone 1B and Free Zone 3 for the entire construction period; AAFB/36 MUNS access to at least one end/vehicle entrance of the “DRIVE-THRU MUNITIONS STORAGE MAGAZINES” must be provided at all times.
100. Drawing 117 (S-002), Foundation Note K MASM and PTMX. Will concrete for the foundation’s grade beams on SB111 and SB131 be allowed to be cast against the earth rather than formed as indicated by Note K?
ANSWER: No. Form sides of foundation beams as indicated in MASM & PTMX Foundation Note L on Drawing S-002. Do not use earth forms.
101. Note A on A250 states that “Five identical ECM’s are being constructed as part of this project scope; refer to civil for ECM Site position and orientation”. CS100 shows only 2 ECM’s as part of this contract. Please confirm that only 2 ECM’s are to be constructed
ANSWER: Confirmed. Note A on Drawing A-250 will be revised to state “Two identical ECM’s are being constructed as part of this project scope…” in a forthcoming Amendment.
102. Reference Drawing Sheets S-002 & S-008, Notes P.1 states “Support the building on shallow spread footing and/or continuous footing resting on either the moderately hard to hard native coralline limestone or a layer of uniform, densely compacted limestone sand/gravel soil fill as recommended above.” A Specification Section 31 32 23, Foundation Drilling and Grouting is provided but no drill size, drill depth and number of hole per footing is provided.
Please clarify.
ANSWER: Foundation Note R on S-002 provides hole size, depth, and number of holes.
103. This project requires a large volume of excess excavated soil (approximately over 30,000 CY). Will there be a site on base where we can spread the excess excavated materials?
ANSWER: No.
104. HVAC Equipment Schedule, Sheet M-631 - PTMX HVAC Schedule. For area MS-3 SUPPORT 107 and MS-4 OFFICE 105, it is requesting for a 9k horizontal concealed. By horizontal concealed we can only assume that they will be talking about a ducted split as in the plans it does seem to be printed as a ducted split. However, we are not aware of any US manufacturer that offers any ducted split in this size as the CFM is not strong enough to push through a duct system. Is the space a specific space that requires it to be a ducted split? Is the space designed specifically for a ducted split? Or will a wall mount be a viable system to replace the ducted split with?
ANSWER: The space is designed to be a ducted split system, and a wall mounted system is not acceptable. Please provide ducted split system as specified.
105. HVAC CONTROLS, Sheet M-1801. Specification calls for DOAU and all HVAC Equipment be connected to a DDC control system. Is the purpose of this for full control of the systems via DDC panel or simply just "on" and "off" capabilities?
ANSWER: The DDC control system must provide full control as required by the Sequence of Operations on Drawing MI802.
106. Also noted in this controls portion is an ATFP Emergency HVAC shutdown switch. Does this mean a shutdown switch to shut down all the units at one time? Or for individual switches to shutdown each one separately?
ANSWER: The ATFP Emergency HVAC shutdown switch must shut down all the units at one time.
107. Specification 03 31 30, paragraph 2.7.1, Reinforcement. Reinforcing Bars. With all of the high grade reinforcing types such as Grade ASTM A276, SS bars; ASTM A767 Class 1 Galvanized, ASTM A955 Stainless Steel bars; ASTM A1035 MMFX2 bars; and ASTM A934 Epoxy coated, the fact that ASTM A615 bars with the marked “A” seems out of place with the exception of the phrase “…bars marked A”. Please clarify the significance of that phrase, and what it does to the nominal grading A615 black resteel.
ANSWER: Response is deferred and will be answered in a subsequent Notice.