20R1334-Amd 0004 Spec 02 41 00 - Attach A.pdf
PDF 4 MB Posted
- Attached to
- FY21 MCAF P-3001/AJJY203001, APSI - STANDOFF WEAPONS COMPLEX, MSA2, ANDERSEN AIR FORCE BASE, GUAM
- Solicitation number
- N6274220R1334
About this file
This hazardous material survey report documents the findings of an inspection conducted at Building 51109 on Andersen Air Force Base in Guam. The inspection targeted areas to be disturbed by renovations and additions for the FY21 MCAF P-3001/AJJY203001 project to construct an adequately sized missile maintenance and assembly complex. Analytical testing identified one asbestos-containing material (2% chrysotile sealant) and found no lead-based or arsenic-containing materials. The report provides location details of hazardous materials, sampling methodology, laboratory results, and recommendations for asbestos control during work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 20R1334-Note8.pdf | ||
| 20R1334 AMD 0006.pdf | ||
| 20R1334-AMD 0005.pdf | ||
| 20R1334-Note7.pdf | ||
| 20R1334-Note6.pdf | ||
| 20R1334-Amd 0004.pdf | ||
| 20R1334-Note5.pdf | ||
| 20-R-1334-Amd 0003.pdf | ||
| 20R1334-Note4.pdf | ||
| 20R1334-AMD2.pdf | ||
| 20R1334-Note3.pdf | ||
| 20R1334-SV SignIn.PDF | ||
| 20R1334-AMD1.pdf | ||
| 20R1334-Note2.pdf | ||
| 20R1334-Note1.pdf | ||
| 20R1334-Specs_Part2of2.pdf | ||
| 20R1334-JAs.zip | ZIP file | |
| 20R1334-RFP.pdf | ||
| 20R1334-Specs_Part1of2.pdf | ||
| 20R1334-Dwgs.pdf |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
16-643 Kipimana Street, Suite 12, Keaau, Hawaii, USA 96749 • 808.769.4221 99-1046 Iwaena Street, Suite 210A, Aiea, Hawaii, USA 96701 • 808.484.9214
T H M S R
FY21 MCAF P-3001/AJJY203001
APSI-S W C MSA 2
B 51109 A A F B , G
NAVFAC C N62742-17-D-0003
MNA P 2735_1
M 29, 2020
Environmental Studies and Consulting Services
Attachment A
This page is intentionally left blank.
Jacobs - Targeted Hazmat Survey Report for FY21 MCAF P-3001, APSI-Standoff Weapons Complex, MSA 2, Bldg. 51109, Andersen AFB, Guam
2735_1 iii Myounghee Noh & Associates, L.L.C.
Jacobs Government Services Company 777 Main Street Fort Worth, Texas 76102
TARGETED HAZARDOUS MATERIAL SURVEY REPORT
FOR
FY21 MCAF P-3001/AJJY203001, APSI
STANDOFF WEAPONS COMPLEX, MSA 2
BUILDING 51109
ANDERSEN AIR FORCE BASE, GUAM 96538
NAVFAC Contract N6242-17-D-0003 MNA Project 2735_1
May 29, 2020
Brad Wolfe, Unitek Environmental Guam Kristin Cabanila Building Inspector Report Writer (ON-4644-938-122619, Exp. 12/26/2020)
Myounghee Noh, CIH, CSP Principal
Myounghee Noh & Associates, L.L.C.
Environmental Studies and Consulting Services 99-1046 Iwaena Street, Suite 210A, Aiea, HI 96701 Tel (808) 484-9214 www.noh-associates.com http://www.noh-associates.com/
FY21 MCAF P-3001, APSI-Standoff Weapons Complex, MSA 2, Bldg 51109, Andersen AFB, Guam
2735_1 ii Myounghee Noh & Associates, L.L.C.
TABLE OF CONTENTS
EXECUTIVE SUMMARY ........................................................................................................ IV
1.0 INTRODUCTION
2.0 SAMPLING AND SURVEY METHODS
2.1 Identifying Homogeneous Materials
2.2 Building Material Sampling
3.0 LABORATORY INFORMATION
4.0 ASBESTOS RESULTS
5.0 LEAD RESULTS
6.0 ARSENIC RESULTS
7.0 SUMMARY OF SURVEY RESULTS
8.0 RECOMMENDATIONS FOR RENOVATION AND CONSTRUCTION WORK
8.1 Asbestos-Containing Materials
8.2 Lead-Containing Paints
10.3 Arsenic-Containing Materials
9.0 LIMITATIONS
APPENDIX A: INSPECTOR CERTIFICATIONS ..................................................................A
APPENDIX B: HOMOGENEOUS MATERIALS IDENTIFIED AND SAMPLE TYPES
COLLECTED ...............................................................................................................................B
APPENDIX C: SAMPLE AND HAZARDOUS MATERIAL LOCATION DRAWINGS....C
APPENDIX D: PHOTOGRAPHS...............................................................................................D
APPENDIX E: LABORATORY ANALYTICAL REPORTS .................................................E
FIGURE
Figure 1. Vicinity Map
TABLES
Table 1. Anticipated Design Scope of Work Table 2. Summary of Sampling and Results Table 3. Asbestos-Containing Material Determination
2735_1 iii Myounghee Noh & Associates, L.L.C.
CONTRIBUTORS
Project Coordinator Bryan Chinaka Certified Inspector Brad Wolfe, Unitek Environmental Guam Data Quality Control Bryan Chinaka Report Writer/Drafter Kristin Cabanila Technical Editor/QC Jessica Walsh
2735_1 iv Myounghee Noh & Associates, L.L.C.
EXECUTIVE SUMMARY
In July 2019, Myounghee Noh & Associates, L.L.C. (MNA), was retained by Jacobs, to conduct a targeted hazardous material survey at Building 51109 located on Andersen Air Force Base, Guam. Targeted were those areas anticipated to be disturbed during the planned construction of an addition to the existing Missile Assembly Shop (Building 51109).
The objective of the survey was to identify the presence, extent, and conditions of hazardous materials in and on the building in the areas anticipated to be disturbed, so that the information can be incorporated in the design.
On 14 May 2020, MNA, with field support from Unitek Environmental Guam, conducted this hazardous material survey and identified 14 suspect building materials. Based on sampling and analysis of 30 asbestos/bulk and eight lead/paint chip samples, MNA provides the following summary:
One asbestos-containing material (ACM), off-white sealant on concrete wall.
No lead-containing paint (LCP) were found in the project area.
No suspected arsenic-containing material were observed in the project area.
Based on the visual survey and sampling and analysis of suspect bulk materials and paints, special hazard control measures are warranted for work involving asbestos. These control measures are briefly described in Section 8 Recommendations for Renovation and Construction Work. General dust and runoff controls and environmental protection are also warranted.
Contractors must verify, prior to bidding, the location and volumes of potentially hazardous materials and determine the appropriate dust and hazard control measures based on the area and material to be disturbed. Quantities of materials provided in this report are based on visual approximations only during the survey and should not be used for bidding purposes.
Analytical results provided in this report do not meet the requirements for waste characterizations.
Contractor must coordinate with permitted landfills for required waste characterizations.
Any ACM disturbance exceeding 3 square feet or 3 linear feet of friable ACM or generating 0.5 cubic feet of ACM debris is considered a regulated activity. Contractors are required to comply with 29 CFR 1926.1101(k)(3)(i) to identify the presence, location, and quantity of ACM before any work is begun.
2735_1 1 Myounghee Noh & Associates, L.L.C.
1.0 INTRODUCTION
Myounghee Noh & Associates, L.L.C. (MNA), under an agreement with Jacobs Government Services Company, conducted a targeted hazardous material survey for the MCAF P- 3001/AJJY203001, APSI-Standoff Weapons Complex, MSA 2, Building 51109, located on Andersen Air Force Base, Guam. Unitek Environmental Guam was a subcontractor to MNA to support the field survey due to the 2020 COVID-19 pandemic travel restrictions. The survey was conducted in support of the planned building modification project. Targeted were those areas anticipated to be disturbed by the renovation and construction work, including hazardous building materials due to the suspected presence of asbestos, lead, or arsenic (Table 1):
Table 1. Anticipated Design Scope of Work Room Work Anticipated Building 51109
Construction of an addition to the building, including access and transportation pavements, grading and drainage improvements, and supporting utility infrastructure.
2.0 SAMPLING AND SURVEY METHODS
On 14 May 2020, a State of Arizona-certified building inspector, Brad Wolfe of Unitek Environmental Guam conducted the hazardous material survey on behalf of MNA. The inspector performed a visual assessment of the project site, identified materials suspected of containing asbestos, lead, or arsenic, and collected samples of these materials. Inspector certifications are presented in Appendix A.
2.1 Identifying Homogeneous Materials
The inspector identified building materials with the same appearance, color, and substrate as homogeneous materials. Interior homogeneous materials are considered unique per building and building floor, while exterior building materials are considered unique per structure. Building materials with the same characteristics (appearance, color, and substrate), as an identified homogeneous material, should be considered to possess the same hazard characteristics, unless specifically identified as otherwise in the report. As an example, if cream paint on concrete is found to be lead-based paint (LCP), then all identical cream paint on concrete in the survey area should be treated as LCP. Table 2 provides an overview of sampling and a summary of hazardous materials identified.
Myounghee Noh &
Associates, L.L.C.
Figure 1. Vicinity Map
FY21 MCAF P-3001/AJJY203001 APSI
Standoff Weapons Complex, MSA 2
Andersen Air Force Base, Guam
Map Area
Scale (ft.)
0 400 800 1,200
East Perimeter Road
51109
North Runway
Taxilane Charlie
T a x iw a y K ilo
2735_1 3 Myounghee Noh & Associates, L.L.C.
Table 2. Summary of Sampling and Results
Materials Sampled
Samples Submitted/ Inspected
Suspect Material Locations Identified Hazardous
Materials
Building 51109
Asbestos in bulk material or paint 30 Ceilings, floor, walls 1 ACM
(2% Chrysotile) Lead in paint 8 Bracing, conduit, emergency exit doors, walls None
Arsenic in bulk 0 --- None ACM – Asbestos-Containing Material
2.2 Building Material Sampling
Bulk and paint samples were collected using a decontaminated chisel, razor, or hammer in a manner that minimized airborne dust. The inspector collected triplicate samples for asbestos and duplicate samples for lead. No suspected arsenic-containing building materials were identified.
Samples were placed in sealable plastic bags, labeled with a unique identification number, and recorded on a chain-of-custody. For each sample, the date, sample appearance, analyte, and sample location were recorded on a field data form. All samples were transported under chain-of-custody to Hawaii Analytical Laboratory in Honolulu, Hawaii.
3.0 LABORATORY INFORMATION
Hawaii Analytical Laboratory analyzed the asbestos samples by polarized light microscopy using the Environmental Protection Agency (EPA) Method 600/R-93/116 and the lead samples by flame atomic absorption spectroscopy using the EPA Method 7082m. Hawaii Analytical Laboratory, Honolulu, is certified by:
National Voluntary Laboratory Accreditation Program (NVLAP), certification 200655-0 State of Hawaii Department of Health (HDOH), certification L-14-002 American Industrial Hygienist Association (AIHA) Environmental Lead Laboratory
Accreditation Program (ELLAP), certification 101812
4.0 ASBESTOS RESULTS
Materials determined to contain greater than, or equal to, 1% asbestos are considered regulated asbestos-containing material (ACM) under the National Emission Standards for Hazardous Air Pollutants (NESHAP) as specified in 40 Code of Federal Regulations (CFR) Part 61 Subpart M.
The U.S. Occupational Safety and Health Administration (OSHA) Asbestos General Industry and Construction Standards also define ACM as 1% asbestos or more by volume under 29 CFR
1910.1001 and 29 CFR 1926.1101, respectively. However, any measurable levels of asbestos fibers are considered to be a health concern, in an uncontrolled work environment.
2735_1 4 Myounghee Noh & Associates, L.L.C.
Ten homogeneous materials suspected of containing asbestos were identified and sampled, generating 30 samples for analysis. One ACM, off-white sealant on concrete, was confirmed in the survey area, with a result of 2% chrysotile asbestos (Table 3).
Table 3. Asbestos-Containing Material Determination
Rooms Locations
HM
ID
Material Color
Material Substrate Result Condition Estimated Quantity
Unit
121 Floor 5 White with gray streaks
12" x 12" Vinyl tile Mastic Concrete ND Good 1,400 sq. ft.
121 Wall 6 Gray Cove base Mastic Concrete ND Good 40 ln. ft.
121 Ceiling 7 White 2' x 2' Acoustic tile None ND Good 200 sq. ft.
118, 120, 121 Walls 8 Gray Skim coat Concrete ND Good 3,500 sq. ft.
119 Ceiling, walls 9 Beige Joint compound Drywall ND Good 210 sq. ft.
119 Ceiling 10 Beige Painted drywall None ND Good 210 sq. ft.
Exterior Walls 11 Gray Skim coat Concrete ND Good 5,400 sq. ft.
Exterior Wall 12 Off-white Sealant Concrete
ACM 2%
Chrysotile
Good 70 ln. ft.
Exterior Floor 13 Black Expansion joint Concrete ND Fair 180 ln. ft.
Exterior Walls 14 Blue/gray Joint tape Concrete ND Good 240 ln. ft.
Bold values indicate results above the reporting limit.
Good – Material is in an "as installed" condition. It is usable as is and may show cosmetic wear and tear or fading.
Fair – Material is functional for its installed purpose but shows initial signs of deterioration beyond the cosmetic.
Abbreviations and Acronyms ACM – Asbestos-Containing Material HM ID – Homogeneous Material Identifier
ln. ft. – Linear Feet ND – Not Detected
sq. ft. – Square Feet
The suspected ACM descriptions and identifiers are provided in Appendix B. Sample and hazardous material location drawings are provided in Appendix C. Photographs of suspected materials are presented in Appendix D. Laboratory analytical reports, chain-of-custody, and field data forms are provided in Appendix E.
5.0 LEAD RESULTS
The U.S. Department of Housing and Urban Development (HUD) and the EPA define paint containing 5,000 milligrams per kilogram (mg/kg), or 0.5% by weight, or more of lead to be lead-based paint (LBP). Paint containing any measurable concentration of lead is considered to be LCP and a health concern. When lead is detected in a multi-layer sample, it is assumed that all layers represented by the sample contain lead at the same concentration.
2735_1 5 Myounghee Noh & Associates, L.L.C.
Four suspected lead paints were identified and sampled, generating eight paint chip samples.
Laboratory analytical results indicated no measurable levels of lead. Therefore, it is concluded that no lead paints are present in the project area.
Suspected LCP descriptions and identifiers are provided in Appendix B. Sample location drawings are in Appendix C. Photographs of suspected LCP are presented in Appendix D. Laboratory analytical reports, chain-of-custody, and field data forms are provided in Appendix E.
6.0 ARSENIC RESULTS
The disturbance of arsenic-containing materials is regulated by the OSHA Inorganic Arsenic General Industry Standard under 29 CFR 1910.1018.
No suspected arsenic-containing materials were observed; therefore, no samples were collected during this survey.
7.0 SUMMARY OF SURVEY RESULTS
A targeted hazardous material survey was conducted at Building 51109, on Andersen Air Force Base, Guam. The survey was conducted in support of the planned building modification project (design scope in Table 1).
Based on the analysis of 30 asbestos-suspected samples and eight lead-suspected samples, MNA provides the following summary:
Summary of Hazardous Material Findings ACM LCP LBP Arsenic PCB Mercury
Building 51109 Room 118 Room 119 Room 120 Room 121 Exterior ◙
◙ indicates presence of hazardous material ACM – Asbestos-Containing Material LCP – Lead-Containing Paint, <5,000 mg/kg LBP – Lead-Based Paint, ≥5,000 mg/kg PCB – Polychlorinated Biphenyls
8.0 RECOMMENDATIONS FOR RENOVATION AND CONSTRUCTION WORK
It is required that properly trained employees perform demolition and construction work that disturbs hazardous materials, in a manner protective of the site workers, facility users, and the environment. The following recommendations address OSHA and other applicable federal requirements. These recommendations provide guidance for the management of hazardous building materials and control of occupational and environmental hazards associated with operations, maintenance, renovation, and demolition. These recommendations are based on
2735_1 6 Myounghee Noh & Associates, L.L.C.
information gathered during the hazardous materials survey. These recommendations are not intended to constitute a formal work plan but are intended to provide a starting point for the development of a work plan.
8.1 Asbestos-Containing Materials
Employees involved in demolition and construction activities that disturb asbestos must conduct work in accordance with 29 CFR 1926.1101, the OSHA Asbestos Construction Standard. Work practices that would trigger these requirements include, but are not limited to, repair, maintenance, or renovation of structures containing asbestos, as well as removal or encapsulation of materials containing asbestos. For each project, the contractor must determine the appropriate safety measures based on the area to be disturbed, the type, volume, and condition of asbestos materials.
Applicable work practice guidelines involving the disturbance of asbestos materials are summarized, but are not limited to:
Employees must anticipate hazards and utilize appropriate engineering controls and personal protective equipment (PPE).
Employers must provide and require the use of appropriate PPE for any employee exposed to airborne concentrations of asbestos that exceed OSHA regulatory limits, or for which a required negative exposure assessment is not produced (29 CFR 1926.1101[i][1]).
Employees must utilize respiratory protection until the initial exposure monitoring assessment documents safe working levels of airborne asbestos (29 CFR 1926.1101[f] and [h]). Additional periodic exposure monitoring may be required.
An initial exposure monitoring assessment should be carried out when workers are disturbing asbestos to ensure that they are not exposed to airborne asbestos concentrations greater than the Permissible Exposure Limit (PEL) of 0.1 fibers per cubic centimeter (f/cc) of air as an 8-hour time-weighted average (TWA), and the Excursion Limit of 1.0 f/cc over a 30-minute sampling period.
The work site must be maintained as a controlled regulated area and supervised by a competent person at all times.
Employees must implement stringent dust control procedures to prevent asbestos in any airborne or settled dust.
Employees must clean the work area thoroughly using wet methods and a high-efficiency particulate air (HEPA) vacuum. Dry sweeping or air blowing of asbestos-containing debris and dust must be avoided.
Waste and dust containing asbestos must be collected separately from other construction debris. Workers must conduct prompt and controlled clean up and disposal of asbestos wastes and debris in leak-tight containers.
Asbestos-containing waste must be wet, packaged, labeled, stored, and disposed of in accordance with applicable regulations.
2735_1 7 Myounghee Noh & Associates, L.L.C.
Visually inspect the work area to ensure that all asbestos-containing debris and dust has been properly removed.
Conduct clearance in accordance with contract specifications.
8.2 Lead-Containing Paints
Based on the sampling and analysis of four suspected lead paints in Building 51109, no LCP were identified in the project area during this survey. Therefore, no special lead control measures are provided; however, Contractors must review the Safety Data Sheet of the existing paint coatings to determine all appropriate demolition or renovation procedures, and design and implement engineering controls to prevent any releases of the potential contaminants in the paint coatings.
10.3 Arsenic-Containing Materials
No suspected arsenic-containing materials were identified in the project areas during this survey.
Therefore, no special arsenic control measures are provided.
9.0 LIMITATIONS
Industry standard effort was made to identify suspected hazardous building materials during the survey at the project area. However, this does not imply a guarantee that all suspected building materials and hazardous materials were identified by this assessment because certain building materials and/or surfaces may be hidden by walls, flooring/concrete slab, partitions, other building components, or existing equipment or furniture. If any previously unforeseen suspected materials become known, such as any hazardous chemicals in the lead-free paint coatings, additional assessment may be required prior to the planned building modification project.
Material quantities provided in this report are based on visual approximations taken at the time of the survey only and should not be used for bidding purpose. It is the Contractor’s responsibility to verify the material quantities and volume of waste prior to bidding.
Analytical results provided in this report do not meet the requirements for waste characterizations.
Contractor must coordinate with permitted landfills for required waste characterizations.
Any ACM disturbance exceeding 3 square feet or 3 linear feet of friable ACM or generating 0.5 cubic feet of ACM debris is considered a regulated activity. Contractors are required to comply with 29 CFR 1926.1101(k)(3)(i) to identify the presence, location, and quantity of ACM before any work is begun.
2735_1 8 Myounghee Noh & Associates, L.L.C.
This page is intentionally left blank.
2735_1 A Myounghee Noh & Associates, L.L.C.
APPENDIX A: INSPECTOR CERTIFICATIONS
Brad Wolfe, Unitek Environmental Guam
Brad Wolfe
AHERA Building Inspector Refresher
December 26, 2019
ON-4644-938-122619
26-Dec-2019
26-Dec-2020 http://www.tcpdf.org
2735_1 B Myounghee Noh & Associates, L.L.C.
APPENDIX B: HOMOGENEOUS MATERIALS IDENTIFIED AND
SAMPLE TYPES COLLECTED
Homogeneous Materials Identified and Sample Types Collected
FY21 MCAF P-3001, APSI-Standoff Weapons Complex, MSA 2, Bldg. 51109, Andersen AFB, Guam
HM
ID
Rooms Locations
Material
Color Material Substrate Asb Pb Result
1 118, 120, 121 Walls Cream Paint Concrete X <40 mg/kg
2 120 Emergency exit doors Gray Paint Metal X <40 mg/kg
3 Exterior Walls Beige Paint Concrete X <40 mg/kg
4 Exterior Bracing, conduit Beige Paint Metal X <40 mg/kg
5 121 Floor White with gray streaks
12" x 12" Vinyl tile
Mastic Concrete X ND
6 121 Wall Gray Cove base
Mastic Concrete X ND
7 121 Ceiling White 2' x 2' Acoustic tile None X ND
8 118, 120, 121 Walls Gray Skim coat Concrete X ND
9 119 Ceiling, walls Beige Joint compound Drywall X ND
10 119 Ceiling Beige Painted drywall None X ND
11 Exterior Walls Gray Skim coat Concrete X ND
12 Exterior Wall Off-white Sealant Concrete X
ACM 2%
Chrysotile
13 Exterior Floor Black Expansion joint Concrete X ND
14 Exterior Walls Blue/gray Joint tape Concrete X ND
Bold values indicate results above the reporting limit.
Abbreviations and Acronyms
Asb - Asbestos mg/kg - milligrams per kilogram, equivalent to parts per million
ACM - Asbestos-Containing Material ND - Not Detected
HM ID - Homogeneous Material Identifier Pb - Lead
2735_1 B-1 Myounghee Noh & Associates, L.L.C.
2735_1 C Myounghee Noh & Associates, L.L.C.
APPENDIX C: SAMPLE AND HAZARDOUS MATERIAL
LOCATION DRAWINGS
List of Drawings Asbestos and Lead Sample and Hazardous Material Locations - Exterior C-1 and C-2
Asbestos and Lead Sample and Hazardous Material Locations - Interior C-3 and C-4
Sheet Number
C - 1
Asbestos Sample Locations
Standoff Weapons Complex, Building 51109 Exterior
Andersen AFB, Guam
Building 51109
Exterior
HM ID Locations Color Material Substrate Results
12 Wall Gray Sealant Concrete ACM 2%
Legend and Notes
Bold values indicate results above the detection limit.
ACM - Asbestos-Containing Material
HM ID - Homogeneous Material Identifier
ND - None Detected
Visual Extent of Asbestos-Containing Material
2735-A7A: ND
2735-A7B: ND
2735-A7C: ND
HM ID: 11 (Gray skim coat on concrete wall)
2735-A8A: ACM 2% Chrysotile
2735-A8B: Stop positive
2735-A8C: Stop positive
HM ID: 12 (Gray sealant on concrete wall)
2735-A9A: ND
2735-A9B: ND
2735-A9C: ND
HM ID: 13 (Black expansion joint on concrete floor)
2735-A10A: ND
2735-A10B: ND
2735-A10C: ND
HM ID: 14 (Black and gray joint tape on concrete wall)
Scale (ft.)
0 10 20 30
Sheet Number
C - 2
Lead Paint Sample Locations
Standoff Weapons Complex, Building 51109 Exterior
Andersen AFB, Guam
Building 51109
Exterior
2735-P1A: <40 mg/kg
HM ID: 1 (Cream paint on concrete wall)
2735-P1B: <40 mg/kg
HM ID: 1 (Cream paint on concrete wall) 2735-P2A: <40 mg/kg
2735-P2B: <40 mg/kg
HM ID: 2 (Gray paint on metal emergency exit door)
Legend and Notes
HM ID - Hazardous Material Identifier mg/kg - milligrams per kilogram (equivalent to ppm- parts per million)
Scale (ft.)
Sheet Number
C - 3
Asbestos Sample and Hazardous
Material Locations
Standoff Weapons Complex, Building 51109 Interior
Andersen AFB, Guam
Building 51109
Interior
120 119
HM ID - Homogeneous Material Identifier
ND - None Detected
Legend and Notes
2735-A1A-Floor tile: ND
2794-A1A-Mastic: ND
2735-A1B-Floor tile: ND
2794-A1B-Mastic: ND
2735-A1C-Floor tile: ND
2794-A1C-Mastic: ND
HM ID: 5 (White 12" x 12" vinyl tile with mastic on concrete floor)
2735-A2A-Baseboard: ND
2794-A2A-Mastic: ND
2735-A2B-Baseboard: ND
2794-A2B-Mastic: ND
2735-A2C-Baseboard: ND
2794-A2C-Mastic: ND
HM ID: 6 (Gray cove base and mastic on concrete wall)
2735-A3A: ND
2735-A3B: ND
2735-A3C: ND
HM ID: 7 (White 2' x 2' acoustic tile on ceiling)
2735-A4A: ND
2735-A4B: ND
2735-A4C: ND
HM ID: 8 (Gray skim coat on concrete wall)
2735-A5A: ND
2735-A5B: ND
2735-A5C: ND
HM ID: 9 (Beige joint compound on drywall ceiling)
2735-A6A-Drywall: ND
2735-A6A-Joint compound: ND
2735-A6B: ND
2735-A6C-Drywall: ND
2735-A6C-Joint compound: ND
HM ID: 10 (Beige painted drywall wall)
Scale (ft.)
Sheet Number
C - 4
Lead Paint Sample Locations
Standoff Weapons Complex, Building 51109 Interior
Andersen AFB, Guam
Legend and Notes
HM ID - Hazardous Material Identifier mg/kg - milligrams per kilogram (equivalent to ppm- parts per million)
Scale (ft.)
0 10 20 30
Building 51109
Interior
120 119
2735-P3B: <40 mg/kg
HM ID: 3 (Beige paint on concrete wall)
2735-P3A: <40 mg/kg
HM ID: 3 (Beige paint on concrete wall)
2735-P4A: <40 mg/kg
HM ID: 4 (Beige paint on metal bracing)
2735-P4B: <40 mg/kg
HM ID: 4 (Beige paint on metal conduit)
2735_1 D Myounghee Noh & Associates, L.L.C.
APPENDIX D: PHOTOGRAPHS
2735_1 D-1 Myounghee Noh & Associates, L.L.C.
HM ID: 1
Room 120 Cream paint on concrete east wall.
Non-LCP 2735-P1A: <40 mg/kg 2735-P1B: <40 mg/kg
HM ID: 2
Room 120 Gray paint on metal emergency exit door.
Non-LCP 2735-P2A: <40 mg/kg 2735-P2B: <40 mg/kg
HM ID: 3
Exterior Beige paint on concrete wall.
Non-LCP 2735-P3A: <40 mg/kg 2735-P3B: <40 mg/kg
2735_1 D-2 Myounghee Noh & Associates, L.L.C.
HM ID: 4
Exterior Beige paint on metal bracing.
Non-LCP 2735-P4A: <40 mg/kg 2735-P4B: <40 mg/kg
HM ID: 5
Room 121 White 12” x 12” vinyl tile with gray streaks and mastic on concrete floor.
Non-ACM 2735-A1A-Floor tile: ND 2735-A1A-Mastic: ND 2735-A1B-Floor tile: ND 2735-A1B-Mastic: ND 2735-A1C-Floor tile: ND 2735-A1C-Mastic: ND
HM ID: 6
Room 121 Gray cove base and mastic on concrete east wall.
Non-ACM 2735-A2A-Baseboard: ND 2735-A2A-Mastic: ND 2735-A2B-Baseboard: ND 2735-A2B-Mastic: ND 2735-A2C-Baseboard: ND 2735-A2C-Mastic: ND
2735_1 D-3 Myounghee Noh & Associates, L.L.C.
HM ID: 7
Room 121 White 2’ x 2’ acoustic tile on ceiling.
Non-ACM
2735-A3A: ND
2735-A3B: ND
2735-A3C: ND
HM ID: 8
Room 120 Gray skim coat on concrete east wall.
Non-ACM
2735-A4A: ND
2735-A4B: ND
2735-A4C: ND
HM ID: 9
Room 119 Beige joint compound on drywall wall.
Non-ACM
2735-A5A: ND
2735-A5B: ND
2735-A5C: ND
2735_1 D-4 Myounghee Noh & Associates, L.L.C.
HM ID: 10
Room 119 Beige painted drywall wall.
Non-ACM 2735-A6A-Drywall: ND 2735-A6A-Joint compound: ND
2735-A6B: ND
2735-A6C-Drywall: ND 2735-A6C-Joint compound: ND
HM ID: 11
Exterior Gray skim coat on concrete wall.
Non-ACM
2735-A7A: ND
2735-A7B: ND
2735-A7C: ND
HM ID: 12
Exterior Gray sealant on concrete wall.
ACM
2735-A8A: ACM 2% Chrysotile 2735-A8B: Stop positive 2735-A8C: Stop positive
2735_1 D-5 Myounghee Noh & Associates, L.L.C.
HM ID: 13
Exterior Black expansion joint on concrete floor.
Non-ACM
2735-A9A: ND
2735-A9B: ND
2735-A9C: ND
HM ID: 14
Exterior Blue and gray joint tape on concrete wall.
Non-ACM
2735-A10A: ND
2735-A10B: ND
2735-A10C: ND
2735_1 E Myounghee Noh & Associates, L.L.C.
APPENDIX E: LABORATORY ANALYTICAL REPORTS
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
5/26/2020
| FY21 P-3001/AJJY203001: APSI - Standoff Weapons Complex (MSA 2) - Final Design - HAZMAT Survey Report |
| Table of Contents |
| EXECUTIVE SUMMARY |
| 1.0 INTRODUCTION |
| 2.0 SAMPLING AND SURVEY METHODS |
| 2.1 Identifying Homogeneous Materials |
| 2.2 Building Material Sampling |
| 3.0 LABORATORY INFORMATION |
| 4.0 ASBESTOS RESULTS |
| 5.0 LEAD RESULTS |
| 6.0 ARSENIC RESULTS |
| 7.0 SUMMARY OF SURVEY RESULTS |
| 8.0 RECOMMENDATIONS FOR RENOVATION AND CONSTRUCTION WORK |
| 8.1 Asbestos-Containing Materials |
| 8.2 Lead-Containing Paints |
| 10.3 Arsenic-Containing Materials |
| 9.0 LIMITATIONS |
| APPENDIX A: INSPECTOR CERTIFICATIONS |
| APPENDIX B: HOMOGENEOUS MATERIALS IDENTIFIED AND SAMPLE TYPES COLLECTED |
| APPENDIX C: SAMPLE AND HAZARDOUS MATERIAL LOCATION DRAWINGS |
| APPENDIX D: PHOTOGRAPHS |
| APPENDIX E: LABORATORY ANALYTICAL REPORTS |
File details come from the government source that posted it. Updated .