Attachment 8_Contractor Questions 2.pdf
PDF 740 KB Posted
- Attached to
- USS RUSHMORE (LSD-47) 7C1 SRA 52pkg
- Solicitation number
- N6264926R0011
About this file
This is a Contractor Questions form used by NAVSUP Fleet Logistics Center Yokosuka to process inquiries from contractors regarding solicitation N6264926R0011. The form is divided into two sections: an upper section for contractor submission and a lower section restricted for NAVSUP FLCY internal use only.
The contractor question pertains to socket welding requirements specified across 55 datasheets within the solicitation, specifically addressing pipe wall thickness of 0.1875 inches or less. The contractor inquires whether it is feasible to switch from socket welding to a Lock ring system and requests exclusion of Lock ring penetrations from the scope of work for areas requiring the same pipe wall thickness. The NAVSUP FLCY technical review explicitly does not concur with either proposed change, stating that the SRF (Source Review Form) does not support switching from socket welding to a lock ring system and does not support exclusions of these penetrations from the scope of work. The NAVSUP FLCY Response section remains blank in this document, indicating the response was either not yet provided or is to be completed separately.
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONTRACTOR QUESTIONS
DATE OF REQUEST: _________________________ SOLICITATION NO: __________________________ CONTRACTOR POC: _________________________ NAVSUP FLCY POC: _________________________ PHONE: ____________________________________ PHONE: ____________________________________ E-MAIL: ____________________________________ E-MAIL: ____________________________________ CONTRACTOR QUESTION(s):
DO NOT WRITE BELOW THIS LINE
(For NAVSUP FLCY Use Only)
TECHNICAL REVIEW:
NAVSUP FLCY RESPONSE:
| DATE OF REQUEST: |
| SOLICITATION NO: N6264926R0011 |
| CONTRACTOR POC: |
| NAVSUP FLCY POC: Miyuki Martone |
| PHONE: |
| PHONE_2: 0956-50-2853 |
| EMAIL: |
| EMAIL_2: miyuki.martone2.ln@us.navy.mil |
| CONTRACTOR QUESTIONs: With respect to the socket welding requirements outlined in multiple datasheets among the 55 specifications, specifically where the pipe wall thickness is 0.1875 inches or less, we would like to inquire if it is feasible to switch from socket welding to a Lock ring system. |
Furthermore, as Lock ring cannot be utilized for penetration areas that require the same pipe wall thickness, could we kindly request that these penetrations be excluded from the scope of work?
TECHNICAL REVIEW: SRF does NOT concur with switching from socket welding to a lock ring system.
SRF does NOT concur with these exclusions from the penetrations scope of work.