VTE_Condition_Assessment_06142021.pdf

PDF 4 MB Posted

Attached to
Elevator Maintenance & Repair Services for various locations in Southern California
Solicitation number
N6247321R0018
Issued by

View the file

Other files

Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Michael Blades & Associates, Ltd: Washington, DC ● New York ● Chicago ● Phoenix ● Jacksonville

NAVAL FACILITIES ENGINEERING COMMAND

VERTICAL TRANSPORTATION ASSESSMENT

VERTICAL TRANSPORTATION PROFILES

SAN DIEGO AREA

FY 2021-2025

CONTENTS

ELIN-001

BUILDING 322

62-20, 62-21

ELIN-002

BUILDING 1482

54-01

BUILDING 1482

54-02

ELIN 003

BUILDING 193

42-01

ELIN 004

BUILDING 1

40-01

BUILDING 11

40-03

BUILDING 11

40-04

BUILDING 17 A

40-10

BUILDING 11

40-09

BUILDING 50

40-08

BUILDING 52

40-02

BUILDING 564

40-05

BUILDING A3

40-06

BUILDING A3

40-07

BUILDING 564

40-05

ELIN 05

BUILDING 60

19-04,05

ELIN-007

BUILDING 3544

25-02

BUILDING 11

#86-09

BUILDING 14

#86-11

BUILDING 15

#86-05

BUILDING 17

#86-21

BUILDING 209

#86-10

BUILDING 210

#86-20

BUILDING 215

#86-14

BUILDING 217

#86-12

BUILDING 317

#86-16

BUILDING 320

#86-22

BUILDING 321

#86-23

BUILDING 323

#86-24

BUILDING 334

#86-18

BUILDING 401

#86-02

BUILDING 504

#86-03 #86-4

BUILDING 505

#86-06 #86-07

BUILDING 624

#86-08

BUILDING 631

#86-13

BUILDING 632

#86-19

BUILDING 633

#86-15

BUILDING 634

#86-17

ELIN-009

BUILDING 3

81-20

BUILDING 8

81-20

BUILDING 11

81-05

BUILDING 35

87-07

BUILDING 317

81-04

BUILDING 318

81-03

BUILDING 335

81-07

BUILDING 346

81-26

BUILDING 370

81-37

BUILDING 524

98-01

BUILDING 762

81-(28/29) 81-(30/31)

BUILDING 783

81-(15/16)

BUILDING 787

81-(18/19)

BUILDING 1401

81-(32/33/34)

BUILDING 1498

81-24

BUILDING 1507

81-38

BUILDING 2004

98-01

ELIN-010

BUILDING 3526

78-13, 78-14

ELIN-011

BUILDING 3362

01-(11-12-13)

BUILDING 3380

01-(14-15-16-17)

ELIN-012

46 FISHER HOUSE

01-25

FISHER HOUSE 47

01-27

BUILDING 3143

01-01

BUILDING 3187A

78-10

BUILDING 3187A

78-15

BUILDING 3280

01-04

BUILDING 3281

01-05

BUILDING 3281

01-06

BUILDING 3290

01-07

BUILDING 3290

01-08

BUILDING 3290

01-09

BUILDING 3292

01-10

BUILDING 3304

01-39

BUILDING 3304

01-40

BUILDING 3304

01-41

BUILDING 3382

01-18

BUILDING 3533

01-19

BUILDING 3654

01-28

BUILDING 3654

01-29

BUILDING 3662

01-30

BUILDING 3662

01-31

BUILDING 3663

01-32

BUILDING 3663

01-33

BUILDING 3663

01-34

BUILDING 3663

01-35

BUILDING 3187A

78-16

ELIN-013

BUILDING 3187A

78-(11-12)

ELIN-014

BUILDING 2

50-15

ELIN 015

BUILDING 71

98-01

BUILDING 72 MAIN LOBBY

98-02

BUILDING 72 SOUTH SIDE

98-03

BUILDING 73

98-04

ELIN-016

BUILDING 3278

36-01

BUILDING 3339

36-02

BUILDING 3278

36-03

BUILDING 3418

36-04

BUILDING 91

36-05

ELIN-017

BUILDING 1

07-20

BUILDING 1

07-(23-24-25-26)

BUILDING 1

07- 38

BUILDING 3

07-(32-33-34-35)

BUILDING 3

07-36

BUILDING 4

07-39

ELIN-018

75-01

BUILDING 140

75-02

BUILDING 301

75-03

BUILDING 302

75-04

BUILDING 303

75-05

BUILDING 304

75-06

BUILDING 544

75-09

BUILDING 601

75-10

BUILDING 603

75-11, 75-12

BUILDING 633

75-14

BUILDING 633

75-15

BUILDING 530

75-16

BUILDING 635

75-17, 75-18

BUILDING 139

75-19

ELIN-019

BUILDING 127

13-02

ELIN 020

BUILDING 60032

81-23

BUILDING 610023

81-35

BUILDING 610024

81-36

ELIN-021

BUILDING 26

05-14,15,16,17

BUILDING 26

05-18,19,20,21

BUILDING 4

05-60

BUILDING 5

05-61

BUILDING 14

05-57

BUILDING 18

05-(71/72)

BUILDING 19

05-(67/68/69)

BUILDING 21

05-34

BUILDING 801

50-18

ELIN 023

BUILDING 6300

45-(13-14)

ELIN 024

BUILDING 40

07-17

BUILDING 40

07-18

BUILDING 40

07-44

BUILDING 50

07-03

BUILDING 111

07-14

BUILDING 600

07-11

BUILDING 600

07-12

BUILDING 600

07-10

BUILDING 605

07-13

BUILDING 606

07-15

BUILDING 609

07-16

ELIN-025

BUILDING 2

07-(28-29-30-31)

BUILDING 8

07-37

ELIN-026

BUILDING 3509

75-01

ELIN 027

BUILDING 1606

28-01

ELIN 028

BUILDING 8

05-58

BUILDING 8

05-59

ELIN 029

BUILDING 2360

94-30

BUILDING 2378

94-13

BUILDING 2386

94-44

BUILDING 2396

94-45

BUILDING 2399

94-20

BUILDING 23100

94-19

BUILDING 23104

94-106

BUILDING 23123

94-25

BUILDING 23170

94-26

BUILDING 23170

94-27

BUILDING 23194

94-32

BUILDING 23195

94-29

BUILDING 23215

94-55

BUILDING 23670

94-122

DEFENSE DISTRIBUTION DEPOT CENTER (DDDC) REVIEW DATE 2/24/2020

ADDRESS 322 CUMMINGS RD NO. OF ELEVATORS 2

CITY San Diego STATE: CA

ELIN ELIN-001 BLD. NUMBER BUILDING 322

ID 62-20, 62-21 TEST DATE 5/28/2019

SERVICE TYPE FREIGHT ELEVATOR TYPE GEARED

INSTALL/MODERNIZATION 1953/1998 SPEED: 100

MANUFACTURER: MONTGOMERY/MCE CAPACITY: 10,000

OPENINGS FRONT 2 OPENINGS REAR 1

MACHINE ROOM

CONTROLLER: MCE MACHINE TYPE: OVERHEAD GEARED

TYPE COMPUTERIZED MOTOR TYPE DC MOTOR

DRIVE TYPE MOTORGENERATOR MACHINE MNFCTR. MONTGOMERY

OPERATION SAPB MACHINE CONDITION ACCEPTABLE

CONTROLLER

MAINTAINABILITY

NEARING END OF LIFE

5 YEARS

CABLE CONDITION ACCEPTABLE

GOVERNOR YES SIZE CABLES 5/8 INCH

HOISTWAY

CAR GUIDES SLIDE GUIDES C/W GUIDES SLIDE GUIDES

SAFETY INSTANT SELECTOR VANES AND SWITCHES

DOOR SYSTEM

SIZE OF DOORS 9’8” X 10' 0" DOOR OPERATOR PEELE

CONFIGURATION BI-PARTING DOOR DEVICE PHOTO EYES

GENERAL OPERATION ACCEPTABLE MAINTAINABLE YES

HOISTWAY DOOR EQUIPMENT MAINTAINABLE CAR DOOR EQUIPMENT MAINTAINABLE

DOOR TIMES COMPLIANT N/A RESTRICTOR N/A

CAR INTERIOR

INTERIOR AREA 9’ 8” X 19’ 4” ADA COMPLIANT N/A

CAR FIXTURES STAINLESS ADA COMPLIANT YES

COMMUNICATION HANDS FREE ADA COMPLIANT YES

WALL PANELS NO CEILING CUSTOM STEEL MESH

CONDITION GOOD LIGHTING FLOURESCENT

HALL FIXTURES

HALL FIXTURES STAINLESS ADA COMPLIANT YES

VANDAL PROOF YES SIGNAGE YES

FIREMAN SERVICE YES CODE COMPLIANT YES

CAR LANTERNS NO HALL LANTERNS NO

JAMB BRAILLE NO ADA COMPLIANT YES

PIT AREA

BUFFERS SPRING

PIT LADDER

COMPLIANT

YES

COMPENSATION N/A PISTONS ACCEPTABLE N/A

CHANNELS STEEL FORMED PACKING GOOD N/A

RELATED WORK

DISCONNECTS COMPLIANT YES SPRINKLERS YES

FLOW SWITCHES/HEATS YES SUMP PUMP NO

COOLING NO HEATING NO

MAINTENANCE

MACHINE ROOM ACCEPTABLE MACHINES ACCEPTABLE

CONTROLLERS ACCEPTABLE LUBRICATION ACCEPTABLE

CARTOPS ACCEPTABLE CAR DOORS ACCEPTABLE

PISTON N/A HALL DOORS ACCEPTABLE

PACKING N/A PIT CONDITION GOOD

PERFORMANCE ACCEPTABLE DOOR OPERATION ACCEPTABLE

LEVELING ACCEPTABLE NOISE LEVEL ACCEPTABLE

RECOMMENDED UPGRADES

MACHINES/PUMP UNIT YES FIRE ALARM NO

CONTROLLERS YES HVAC YES

DOOR OPERATORS YES ELECTRICAL NO

PISTONS NO SUMP PUMPS NO

CABS NO LIGHTING YES

FIXTURES YES MACHINE ROOM CODE YES

ELEVATOR BUDGET RELATED WORK

BUDGET

SCHEDULE 3-5 YEARS TOTAL PER ELEVATOR

MAINTENANCE DEFICIENCIES

CLEAN BOTH GOVERNORS OF GREASE

62-20 REPLACE PEDESTAL SEAL AND WORM SEAL. LEAKING

LOOSE WIRING FROM CONTROLLER EXPOSED IN LB FOR BOTH CARS. LAND WIRES IN CONDUIT

REMOVE OLD DATA TAGS ON FLOOR BY GOVERNOR

PROVIDE FREIGHT CLASS LOADING IN CABS. SHOULD HAVE C-1 LOADING

REPLACE BAD FLUORESCENT BULBS IN CAB LIGHTING. INSTALL PROPER COVERS ON FIXTURES

NOTES

RECOMMEND PROVIDE MORE LIGHTING IN MACHINE ROOM TO ACHIEVE CODE COMPLIANCE.

RECOMMEND FAN TO BE INSTALLED AND WORKING WITH THERMOSTATIC CONTROL.

RECOMMEND UPGRADE IN LIGHTING IN CABS. NEW LED TYPE TO ACHIEVE CODE COMPLIANCE

RECOMMEND ONLY 1 ELEVATOR TO BE MODERNIZED. USE OF REAR FREIGHT 62-20 IS MARGINAL. NEW MODERNIZATION IN 3-5 YEARS DUE TO OBSOLETE MG CONTROLS AND DATED MOTOR GENERATOR. KEEP

SPARE CONTROLS AND PARTS FOR REAR FREIGHT.

DEFENSE MEGA CENTER (DMC) REVIEW DATE 2/27/2020

ADDRESS 1482 READ ROAD NO. OF ELEVATORS 1

CITY CORONADO STATE: CA

ELIN ELIN-002 BLD. NUMBER BUILDING 1482

ID 54-01 TEST DATE 2/5/2020

SERVICE TYPE SERVICE ELEVATOR TYPE IN-GROUND HYDRAULIC

INSTALL/MODERNIZATION 1986 SPEED: 100

MANUFACTURER: MONTGOMERY CAPACITY: 8,000

OPENINGS FRONT 2 OPENINGS REAR 0

MACHINE ROOM

CONTROLLER: MONTGOMERY MACHINE TYPE: HYDRAULIC

TYPE COMPUTERIZED TYPE ABOVE OIL TANK

DRIVE TYPE LINE START MACHINE MNFCTR. MONTGOMERY

OPERATION SIMPLEX MACHINE CONDITION ACCEPTABLE

CONTROLLER

MAINTAINABILITY ACCEPTABLE CABLE CONDITION NOT APPLICABLE

GOVERNOR NOT APPLICABLE SIZE CABLES NOT APPLICABLE

HOISTWAY

CAR GUIDES SLIDE GUIDES C/W GUIDES N/A

SAFETY N/A SELECTOR VANES AND SWITCHES

DOOR SYSTEM

SIZE OF DOORS 5’ 0” X 8’ 0” DOOR OPERATOR MONTGOMERY

CONFIGURATION CENTER OPENING DOOR DEVICE SCAN

GENERAL OPERATION GOOD MAINTAINABLE YES

HOISTWAY DOOR EQUIPMENT MAINTAINABLE CAR DOOR

EQUIPMENT MAINTAINABLE

DOOR TIMES COMPLIANT YES RESTRICTOR YES

CAR INTERIOR

INTERIOR AREA 9'7" X 7'1" ADA COMPLIANT YES

CAR FIXTURES STAINLESS ADA COMPLIANT YES

COMMUNICATION HANDS FREE ADA COMPLIANT YES

WALL PANELS YES CEILING SUSPENDED PANELS

LEXAN

CONDITION ACCEPTABLE LIGHTING FLOURESCENT

HALL FIXTURES

HALL FIXTURES STAINLESS ADA COMPLIANT YES

VANDAL PROOF YES SIGNAGE YES

FIREMAN SERVICE YES CODE COMPLIANT YES

CAR LANTERNS NO HALL LANTERNS YES

JAMB BRAILLE YES ADA COMPLIANT YES

BUFFERS SPRING PIT LADDER

COMPLIANT YES

COMPENSATION N/A PISTONS ACCEPTABLE YES

CHANNELS STEEL FORMED PACKING GOOD YES

RELATED WORK

DISCONNECTS COMPLIANT YES SPRINKLERS YES

FLOW SWITCHES/HEATS YES SUMP PUMP NO

COOLING NO HEATING NO

MAINTENANCE

MACHINE ROOM ACCEPTABLE MACHINES ACCEPTABLE

CONTROLLERS ACCEPTABLE LUBRICATION ACCEPTABLE

CARTOPS ACCEPTABLE CAR DOORS ACCEPTABLE

PISTON ACCEPTABLE HALL DOORS ACCEPTABLE

PACKING ACCEPTABLE PIT CONDITION GOOD

PERFORMANCE ACCEPTABLE DOOR OPERATION ACCEPTABLE

LEVELING ACCEPTABLE NOISE LEVEL ACCEPTABLE

RECOMMENDED UPGRADES

MACHINES/PUMP UNIT YES FIRE ALARM NO

CONTROLLERS YES HVAC YES

DOOR OPERATORS YES ELECTRICAL NO

PISTONS NO SUMP PUMPS NO

CABS YES MACHINE ROOM CODE YES

FIXTURES YES

ELEVATOR BUDGET RELATED WORK

BUDGET

SCHEDULE 3-5 YEARS TOTAL PER ELEVATOR

MAINTENANCE DEFICIENCIES

1. COMPLETE LIFE SAFETY UPGRADE IN PROCESS. WIRING IS NOT INSTALLED AND UNDER REPAIR.

2. CONDUIT FOR TELEPHONE LINE IN MACHINE ROOM. CODE ITEM

NOTES

EXISTING ELEVATOR IS IN GOOD CONDITION AND RUNNING WELL FOR ITS AGE. DATED CONTROLLER AND

AGING EQUIPMENT WILL REQUIRE REPLACEMENT IN THE 3-5 YEAR RANGE.

CONTINUED PREVENTIVE MAINTENANCE WILL PROVIDE FOR EXTENDED USEFUL LIFE

DEFENSE MEGA CENTER (DMC) REVIEW DATE 2/27/2020

ADDRESS 1482 READ ROAD NO. OF ELEVATORS 1

CITY CORONADO STATE: CA

ELIN ELIN-002 BLD. NUMBER BUILDING 1482

ID 54-02 TEST DATE 2/5/2020

SERVICE TYPE SERVICE ELEVATOR TYPE IN-GROUND HYDRAULIC

INSTALL/MODERNIZATION 1986 SPEED: 125

MANUFACTURER: MONTGOMERY CAPACITY: 3,000

OPENINGS FRONT 2 OPENINGS REAR 0

MACHINE ROOM

CONTROLLER: MONTGOMERY MACHINE TYPE: HYDRAULIC

TYPE COMPUTERIZED TYPE ABOVE OIL TANK

DRIVE TYPE LINE START MACHINE MNFCTR. MONTGOMERY

OPERATION SIMPLEX MACHINE CONDITION ACCEPTABLE

CONTROLLER

MAINTAINABILITY ACCEPTABLE CABLE CONDITION NOT APPLICABLE

GOVERNOR NOT APPLICABLE SIZE CABLES NOT APPLICABLE

HOISTWAY

CAR GUIDES SLIDE GUIDES C/W GUIDES N/A

SAFETY N/A SELECTOR VANES AND SWITCHES

DOOR SYSTEM

SIZE OF DOORS 3’ 6” X 7’ 0” DOOR OPERATOR MONTGOMERY

CONFIGURATION CENTER OPENING DOOR DEVICE SCAN

GENERAL OPERATION GOOD MAINTAINABLE YES

HOISTWAY DOOR EQUIPMENT MAINTAINABLE CAR DOOR

EQUIPMENT MAINTAINABLE

DOOR TIMES COMPLIANT YES RESTRICTOR YES

CAR INTERIOR

INTERIOR AREA 4' 8" X 6' 8" ADA COMPLIANT YES

CAR FIXTURES STAINLESS ADA COMPLIANT YES

COMMUNICATION HANDS FREE ADA COMPLIANT YES

WALL PANELS YES CEILING SUSPENDED PANELS

LEXAN

CONDITION ACCEPTABLE LIGHTING FLOURESCENT

HALL FIXTURES

HALL FIXTURES STAINLESS ADA COMPLIANT YES

VANDAL PROOF YES SIGNAGE YES

FIREMAN SERVICE NO CODE COMPLIANT YES

BUFFERS SPRING PIT LADDER

COMPLIANT YES

COMPENSATION N/A PISTONS ACCEPTABLE YES

CHANNELS STEEL FORMED PACKING GOOD YES

RELATED WORK

DISCONNECTS COMPLIANT YES SPRINKLERS YES

FLOW SWITCHES/HEATS YES SUMP PUMP NO

COOLING NO HEATING NO

MAINTENANCE

MACHINE ROOM ACCEPTABLE MACHINES ACCEPTABLE

CONTROLLERS ACCEPTABLE LUBRICATION ACCEPTABLE

CARTOPS ACCEPTABLE CAR DOORS ACCEPTABLE

PISTON ACCEPTABLE HALL DOORS ACCEPTABLE

PACKING ACCEPTABLE PIT CONDITION GOOD

PERFORMANCE ACCEPTABLE DOOR OPERATION ACCEPTABLE

LEVELING ACCEPTABLE NOISE LEVEL ACCEPTABLE

RECOMMENDED UPGRADES

MACHINES/PUMP UNIT YES FIRE ALARM NO

CONTROLLERS YES HVAC YES

DOOR OPERATORS YES ELECTRICAL NO

PISTONS NO SUMP PUMPS NO

CABS YES MACHINE ROOM CODE YES

FIXTURES YES

ELEVATOR BUDGET RELATED WORK

BUDGET

SCHEDULE 3-5 YEARS TOTAL PER ELEVATOR

MAINTENANCE DEFICIENCIES

1. COMPLETE LIFE SAFETY UPGRADE IN PROCESS. WIRING IS NOT INSTALLED AND UNDER REPAIR.

2. DDC POWER IS FOREIGN EQUIPMENT AND BY CODE IS NOT ALLOWED IN MACHINE ROOM.

NOTES

EXISTING ELEVATOR IS IN GOOD CONDITION AND RUNNING WELL FOR ITS AGE. DATED CONTROLLER AND

AGING EQUIPMENT WILL REQUIRE REPLACEMENT IN THE 3-5 YEAR RANGE.

CONTINUED PREVENTIVE MAINTENANCE WILL PROVIDE FOR EXTENDED USEFUL LIFE

EXPLOSIVE ORDINANCE DISPOSAL (EOD) REVIEW DATE 11/18/2020

ADDRESS 1498 13TH STREET NO. OF ELEVATORS 1

CITY Imperial Beach STATE: CA

ELIN: ELIN 003 BLD. NUMBER BUILDING 193

ID 42-01 TEST DATE 9/1/2020

SERVICE TYPE PASSENGER ELEVATOR TYPE IN-GROUND HYDRAULIC

INSTALL/MODERNIZATION 1999 SPEED: 150

MANUFACTURER: THYSSENKRUPP CAPACITY: 2500

OPENINGS FRONT 3 OPENINGS REAR 1

MACHINE ROOM

CONTROLLER: MCE HMC 1000 MACHINE TYPE: HYDRAULIC

TYPE COMPUTERIZED TYPE ABOVE OIL TANK

DRIVE TYPE WYE-DELTA MACHINE MNFCTR. INDEPENDENT PUMP

UNIT

OPERATION SIMPLEX MACHINE CONDITION ACCEPTABLE

CONTROLLER

MAINTAINABILITY ACCEPTABLE CABLE CONDITION NOT APPLICABLE

GOVERNOR NOT APPLICABLE SIZE CABLES NOT APPLICABLE

HOISTWAY

CAR GUIDES SLIDE GUIDES C/W GUIDES N/A

SAFETY N/A SELECTOR VANES AND SWITCHES

DOOR SYSTEM

SIZE OF DOORS 3’ 6” X 7’ 0” DOOR OPERATOR ECI

CONFIGURATION (FRONT AND

REAR) SINGLE SLIDE DOOR DEVICE SCAN

GENERAL OPERATION GOOD MAINTAINABLE YES

HOISTWAY DOOR EQUIPMENT MAINTAINABLE CAR DOOR

EQUIPMENT MAINTAINABLE

DOOR TIMES COMPLIANT YES RESTRICTOR YES

CAR INTERIOR

INTERIOR AREA 6'10" X 4'5" ADA COMPLIANT YES

CAR FIXTURES STAINLESS ADA COMPLIANT YES

COMMUNICATION HANDS FREE ADA COMPLIANT YES

WALL PANELS YES CEILING EGG CREATE

CONDITION ACCEPTABLE LIGHTING FLOURESCENT

HALL FIXTURES

HALL FIXTURES STAINLESS ADA COMPLIANT YES

VANDAL PROOF YES SIGNAGE YES

FIREMAN SERVICE YES CODE COMPLIANT YES

CAR LANTERNS YES HALL LANTERNS NO

PIT AREA

BUFFERS SPRING PIT LADDER

COMPLIANT YES

COMPENSATION N/A PISTONS ACCEPTABLE YES

CHANNELS STEEL FORMED PACKING GOOD YES

RELATED WORK

DISCONNECTS COMPLIANT YES SPRINKLERS YES

FLOW SWITCHES/HEATS YES SUMP PUMP NO

COOLING NO HEATING NO

MAINTENANCE

MACHINE ROOM ACCEPTABLE MACHINES ACCEPTABLE

CONTROLLERS ACCEPTABLE LUBRICATION ACCEPTABLE

CARTOPS ACCEPTABLE CAR DOORS ACCEPTABLE

PISTON ACCEPTABLE HALL DOORS ACCEPTABLE

PACKING ACCEPTABLE PIT CONDITION GOOD

PERFORMANCE ACCEPTABLE DOOR OPERATION ACCEPTABLE

LEVELING ACCEPTABLE NOISE LEVEL ACCEPTABLE

RECOMMENDED UPGRADES

MACHINES/PUMP UNIT NO FIRE ALARM NO

CONTROLLERS NO HVAC NO

DOOR OPERATORS NO ELECTRICAL NO

PISTONS NO SUMP PUMPS NO

CABS NO MACHINE ROOM CODE NO

FIXTURES NO

ELEVATOR BUDGET RELATED WORK

BUDGET

SCHEDULE IMMEDIATE TOTAL PER ELEVATOR

MAINTENANCE DEFICIENCIES

EXISTING ELEVATOR IS IN GOOD CONDITION AND RUNS WELL. NO MAJOR REPAIRS OR MODERNIZATION REQUIRED IN THE 5 YEAR LOOK AHEAD. CONTINUED PREVENTIVE MAINTENANCE WILL PROVIDE FOR

EXTENDED USEFUL LIFE

HARBOR DRIVE ANNEX REVIEW DATE 11/18/2020

ADDRESS 33150 DESTROYER

LANE NO. OF ELEVATORS 1

CITY San Diego STATE: CA

ELIN: ELIN 004 BLD. NUMBER BUILDING 1

ID 40-01 TEST DATE 9/1/2020

SERVICE TYPE PASSENGER ELEVATOR TYPE IN-GROUND HYDRAULIC

INSTALL/MODERNIZATION 1984 MOD 2005 SPEED: 125

MANUFACTURER: US ELEVATOR CAPACITY: 2500

OPENINGS FRONT 4 OPENINGS REAR 0

MACHINE ROOM

CONTROLLER: MCE HMC 1000 MACHINE TYPE: HYDRAULIC

TYPE COMPUTERIZED TYPE DRY

DRIVE TYPE SCR MACHINE MNFCTR. US ELEVATOR

OPERATION SIMPLEX MACHINE CONDITION ACCEPTABLE

CONTROLLER

MAINTAINABILITY ACCEPTABLE CABLE CONDITION NOT APPLICABLE

GOVERNOR NOT APPLICABLE SIZE CABLES NOT APPLICABLE

HOISTWAY

CAR GUIDES SLIDE GUIDES C/W GUIDES N/A

SAFETY N/A SELECTOR VANES AND SWITCHES

DOOR SYSTEM

SIZE OF DOORS 3’ 6” X 7’ 0” DOOR OPERATOR GAL MOVFR

CONFIGURATION SINGLE SLIDE DOOR DEVICE SCAN

GENERAL OPERATION GOOD MAINTAINABLE YES

HOISTWAY DOOR EQUIPMENT MAINTAINABLE CAR DOOR

EQUIPMENT MAINTAINABLE

DOOR TIMES COMPLIANT YES RESTRICTOR YES

CAR INTERIOR

INTERIOR AREA 4' 3" X 6' 8" ADA COMPLIANT YES

CAR FIXTURES STAINLESS ADA COMPLIANT YES

COMMUNICATION HANDS FREE ADA COMPLIANT YES

WALL PANELS YES CEILING STAINLESS

CONDITION ACCEPTABLE LIGHTING FLOURESCENT

HALL FIXTURES

HALL FIXTURES STAINLESS ADA COMPLIANT YES

VANDAL PROOF NO SIGNAGE YES

FIREMAN SERVICE YES CODE COMPLIANT YES

BUFFERS SPRING PIT LADDER

COMPLIANT YES

COMPENSATION N/A PISTONS ACCEPTABLE YES

CHANNELS STEEL FORMED PACKING GOOD YES

RELATED WORK

DISCONNECTS COMPLIANT YES SPRINKLERS YES

FLOW SWITCHES/HEATS YES SUMP PUMP NO

COOLING YES HEATING NO

MAINTENANCE

MACHINE ROOM ACCEPTABLE MACHINES ACCEPTABLE

C