Michael Blades & Associates, Ltd: Washington, DC ● New York ● Chicago ● Phoenix ● Jacksonville
NAVAL FACILITIES ENGINEERING COMMAND
VERTICAL TRANSPORTATION ASSESSMENT
VERTICAL TRANSPORTATION PROFILES
SAN DIEGO AREA
FY 2021-2025
CONTENTS
ELIN-001
BUILDING 322
62-20, 62-21
ELIN-002
BUILDING 1482
54-01
BUILDING 1482
54-02
ELIN 003
BUILDING 193
42-01
ELIN 004
BUILDING 1
40-01
BUILDING 11
40-03
BUILDING 11
40-04
BUILDING 17 A
40-10
BUILDING 11
40-09
BUILDING 50
40-08
BUILDING 52
40-02
BUILDING 564
40-05
BUILDING A3
40-06
BUILDING A3
40-07
BUILDING 564
40-05
ELIN 05
BUILDING 60
19-04,05
ELIN-007
BUILDING 3544
25-02
BUILDING 11
#86-09
BUILDING 14
#86-11
BUILDING 15
#86-05
BUILDING 17
#86-21
BUILDING 209
#86-10
BUILDING 210
#86-20
BUILDING 215
#86-14
BUILDING 217
#86-12
BUILDING 317
#86-16
BUILDING 320
#86-22
BUILDING 321
#86-23
BUILDING 323
#86-24
BUILDING 334
#86-18
BUILDING 401
#86-02
BUILDING 504
#86-03 #86-4
BUILDING 505
#86-06 #86-07
BUILDING 624
#86-08
BUILDING 631
#86-13
BUILDING 632
#86-19
BUILDING 633
#86-15
BUILDING 634
#86-17
ELIN-009
BUILDING 3
81-20
BUILDING 8
81-20
BUILDING 11
81-05
BUILDING 35
87-07
BUILDING 317
81-04
BUILDING 318
81-03
BUILDING 335
81-07
BUILDING 346
81-26
BUILDING 370
81-37
BUILDING 524
98-01
BUILDING 762
81-(28/29) 81-(30/31)
BUILDING 783
81-(15/16)
BUILDING 787
81-(18/19)
BUILDING 1401
81-(32/33/34)
BUILDING 1498
81-24
BUILDING 1507
81-38
BUILDING 2004
98-01
ELIN-010
BUILDING 3526
78-13, 78-14
ELIN-011
BUILDING 3362
01-(11-12-13)
BUILDING 3380
01-(14-15-16-17)
ELIN-012
46 FISHER HOUSE
01-25
FISHER HOUSE 47
01-27
BUILDING 3143
01-01
BUILDING 3187A
78-10
BUILDING 3187A
78-15
BUILDING 3280
01-04
BUILDING 3281
01-05
BUILDING 3281
01-06
BUILDING 3290
01-07
BUILDING 3290
01-08
BUILDING 3290
01-09
BUILDING 3292
01-10
BUILDING 3304
01-39
BUILDING 3304
01-40
BUILDING 3304
01-41
BUILDING 3382
01-18
BUILDING 3533
01-19
BUILDING 3654
01-28
BUILDING 3654
01-29
BUILDING 3662
01-30
BUILDING 3662
01-31
BUILDING 3663
01-32
BUILDING 3663
01-33
BUILDING 3663
01-34
BUILDING 3663
01-35
BUILDING 3187A
78-16
ELIN-013
BUILDING 3187A
78-(11-12)
ELIN-014
BUILDING 2
50-15
ELIN 015
BUILDING 71
98-01
BUILDING 72 MAIN LOBBY
98-02
BUILDING 72 SOUTH SIDE
98-03
BUILDING 73
98-04
ELIN-016
BUILDING 3278
36-01
BUILDING 3339
36-02
BUILDING 3278
36-03
BUILDING 3418
36-04
BUILDING 91
36-05
ELIN-017
BUILDING 1
07-20
BUILDING 1
07-(23-24-25-26)
BUILDING 1
07- 38
BUILDING 3
07-(32-33-34-35)
BUILDING 3
07-36
BUILDING 4
07-39
ELIN-018
75-01
BUILDING 140
75-02
BUILDING 301
75-03
BUILDING 302
75-04
BUILDING 303
75-05
BUILDING 304
75-06
BUILDING 544
75-09
BUILDING 601
75-10
BUILDING 603
75-11, 75-12
BUILDING 633
75-14
BUILDING 633
75-15
BUILDING 530
75-16
BUILDING 635
75-17, 75-18
BUILDING 139
75-19
ELIN-019
BUILDING 127
13-02
ELIN 020
BUILDING 60032
81-23
BUILDING 610023
81-35
BUILDING 610024
81-36
ELIN-021
BUILDING 26
05-14,15,16,17
BUILDING 26
05-18,19,20,21
BUILDING 4
05-60
BUILDING 5
05-61
BUILDING 14
05-57
BUILDING 18
05-(71/72)
BUILDING 19
05-(67/68/69)
BUILDING 21
05-34
BUILDING 801
50-18
ELIN 023
BUILDING 6300
45-(13-14)
ELIN 024
BUILDING 40
07-17
BUILDING 40
07-18
BUILDING 40
07-44
BUILDING 50
07-03
BUILDING 111
07-14
BUILDING 600
07-11
BUILDING 600
07-12
BUILDING 600
07-10
BUILDING 605
07-13
BUILDING 606
07-15
BUILDING 609
07-16
ELIN-025
BUILDING 2
07-(28-29-30-31)
BUILDING 8
07-37
ELIN-026
BUILDING 3509
75-01
ELIN 027
BUILDING 1606
28-01
ELIN 028
BUILDING 8
05-58
BUILDING 8
05-59
ELIN 029
BUILDING 2360
94-30
BUILDING 2378
94-13
BUILDING 2386
94-44
BUILDING 2396
94-45
BUILDING 2399
94-20
BUILDING 23100
94-19
BUILDING 23104
94-106
BUILDING 23123
94-25
BUILDING 23170
94-26
BUILDING 23170
94-27
BUILDING 23194
94-32
BUILDING 23195
94-29
BUILDING 23215
94-55
BUILDING 23670
94-122
DEFENSE DISTRIBUTION DEPOT CENTER (DDDC) REVIEW DATE 2/24/2020
ADDRESS 322 CUMMINGS RD NO. OF ELEVATORS 2
CITY San Diego STATE: CA
ELIN ELIN-001 BLD. NUMBER BUILDING 322
ID 62-20, 62-21 TEST DATE 5/28/2019
SERVICE TYPE FREIGHT ELEVATOR TYPE GEARED
INSTALL/MODERNIZATION 1953/1998 SPEED: 100
MANUFACTURER: MONTGOMERY/MCE CAPACITY: 10,000
OPENINGS FRONT 2 OPENINGS REAR 1
MACHINE ROOM
CONTROLLER: MCE MACHINE TYPE: OVERHEAD GEARED
TYPE COMPUTERIZED MOTOR TYPE DC MOTOR
DRIVE TYPE MOTORGENERATOR MACHINE MNFCTR. MONTGOMERY
OPERATION SAPB MACHINE CONDITION ACCEPTABLE
CONTROLLER
MAINTAINABILITY
NEARING END OF LIFE
5 YEARS
CABLE CONDITION ACCEPTABLE
GOVERNOR YES SIZE CABLES 5/8 INCH
HOISTWAY
CAR GUIDES SLIDE GUIDES C/W GUIDES SLIDE GUIDES
SAFETY INSTANT SELECTOR VANES AND SWITCHES
DOOR SYSTEM
SIZE OF DOORS 9’8” X 10' 0" DOOR OPERATOR PEELE
CONFIGURATION BI-PARTING DOOR DEVICE PHOTO EYES
GENERAL OPERATION ACCEPTABLE MAINTAINABLE YES
HOISTWAY DOOR EQUIPMENT MAINTAINABLE CAR DOOR EQUIPMENT MAINTAINABLE
DOOR TIMES COMPLIANT N/A RESTRICTOR N/A
CAR INTERIOR
INTERIOR AREA 9’ 8” X 19’ 4” ADA COMPLIANT N/A
CAR FIXTURES STAINLESS ADA COMPLIANT YES
COMMUNICATION HANDS FREE ADA COMPLIANT YES
WALL PANELS NO CEILING CUSTOM STEEL MESH
CONDITION GOOD LIGHTING FLOURESCENT
HALL FIXTURES
HALL FIXTURES STAINLESS ADA COMPLIANT YES
VANDAL PROOF YES SIGNAGE YES
FIREMAN SERVICE YES CODE COMPLIANT YES
CAR LANTERNS NO HALL LANTERNS NO
JAMB BRAILLE NO ADA COMPLIANT YES
PIT AREA
BUFFERS SPRING
PIT LADDER
COMPLIANT
YES
COMPENSATION N/A PISTONS ACCEPTABLE N/A
CHANNELS STEEL FORMED PACKING GOOD N/A
RELATED WORK
DISCONNECTS COMPLIANT YES SPRINKLERS YES
FLOW SWITCHES/HEATS YES SUMP PUMP NO
COOLING NO HEATING NO
MAINTENANCE
MACHINE ROOM ACCEPTABLE MACHINES ACCEPTABLE
CONTROLLERS ACCEPTABLE LUBRICATION ACCEPTABLE
CARTOPS ACCEPTABLE CAR DOORS ACCEPTABLE
PISTON N/A HALL DOORS ACCEPTABLE
PACKING N/A PIT CONDITION GOOD
PERFORMANCE ACCEPTABLE DOOR OPERATION ACCEPTABLE
LEVELING ACCEPTABLE NOISE LEVEL ACCEPTABLE
RECOMMENDED UPGRADES
MACHINES/PUMP UNIT YES FIRE ALARM NO
CONTROLLERS YES HVAC YES
DOOR OPERATORS YES ELECTRICAL NO
PISTONS NO SUMP PUMPS NO
CABS NO LIGHTING YES
FIXTURES YES MACHINE ROOM CODE YES
ELEVATOR BUDGET RELATED WORK
BUDGET
SCHEDULE 3-5 YEARS TOTAL PER ELEVATOR
MAINTENANCE DEFICIENCIES
CLEAN BOTH GOVERNORS OF GREASE
62-20 REPLACE PEDESTAL SEAL AND WORM SEAL. LEAKING
LOOSE WIRING FROM CONTROLLER EXPOSED IN LB FOR BOTH CARS. LAND WIRES IN CONDUIT
REMOVE OLD DATA TAGS ON FLOOR BY GOVERNOR
PROVIDE FREIGHT CLASS LOADING IN CABS. SHOULD HAVE C-1 LOADING
REPLACE BAD FLUORESCENT BULBS IN CAB LIGHTING. INSTALL PROPER COVERS ON FIXTURES
NOTES
RECOMMEND PROVIDE MORE LIGHTING IN MACHINE ROOM TO ACHIEVE CODE COMPLIANCE.
RECOMMEND FAN TO BE INSTALLED AND WORKING WITH THERMOSTATIC CONTROL.
RECOMMEND UPGRADE IN LIGHTING IN CABS. NEW LED TYPE TO ACHIEVE CODE COMPLIANCE
RECOMMEND ONLY 1 ELEVATOR TO BE MODERNIZED. USE OF REAR FREIGHT 62-20 IS MARGINAL. NEW MODERNIZATION IN 3-5 YEARS DUE TO OBSOLETE MG CONTROLS AND DATED MOTOR GENERATOR. KEEP
SPARE CONTROLS AND PARTS FOR REAR FREIGHT.
DEFENSE MEGA CENTER (DMC) REVIEW DATE 2/27/2020
ADDRESS 1482 READ ROAD NO. OF ELEVATORS 1
CITY CORONADO STATE: CA
ELIN ELIN-002 BLD. NUMBER BUILDING 1482
ID 54-01 TEST DATE 2/5/2020
SERVICE TYPE SERVICE ELEVATOR TYPE IN-GROUND HYDRAULIC
INSTALL/MODERNIZATION 1986 SPEED: 100
MANUFACTURER: MONTGOMERY CAPACITY: 8,000
OPENINGS FRONT 2 OPENINGS REAR 0
MACHINE ROOM
CONTROLLER: MONTGOMERY MACHINE TYPE: HYDRAULIC
TYPE COMPUTERIZED TYPE ABOVE OIL TANK
DRIVE TYPE LINE START MACHINE MNFCTR. MONTGOMERY
OPERATION SIMPLEX MACHINE CONDITION ACCEPTABLE
CONTROLLER
MAINTAINABILITY ACCEPTABLE CABLE CONDITION NOT APPLICABLE
GOVERNOR NOT APPLICABLE SIZE CABLES NOT APPLICABLE
HOISTWAY
CAR GUIDES SLIDE GUIDES C/W GUIDES N/A
SAFETY N/A SELECTOR VANES AND SWITCHES
DOOR SYSTEM
SIZE OF DOORS 5’ 0” X 8’ 0” DOOR OPERATOR MONTGOMERY
CONFIGURATION CENTER OPENING DOOR DEVICE SCAN
GENERAL OPERATION GOOD MAINTAINABLE YES
HOISTWAY DOOR EQUIPMENT MAINTAINABLE CAR DOOR
EQUIPMENT MAINTAINABLE
DOOR TIMES COMPLIANT YES RESTRICTOR YES
CAR INTERIOR
INTERIOR AREA 9'7" X 7'1" ADA COMPLIANT YES
CAR FIXTURES STAINLESS ADA COMPLIANT YES
COMMUNICATION HANDS FREE ADA COMPLIANT YES
WALL PANELS YES CEILING SUSPENDED PANELS
LEXAN
CONDITION ACCEPTABLE LIGHTING FLOURESCENT
HALL FIXTURES
HALL FIXTURES STAINLESS ADA COMPLIANT YES
VANDAL PROOF YES SIGNAGE YES
FIREMAN SERVICE YES CODE COMPLIANT YES
CAR LANTERNS NO HALL LANTERNS YES
JAMB BRAILLE YES ADA COMPLIANT YES
BUFFERS SPRING PIT LADDER
COMPLIANT YES
COMPENSATION N/A PISTONS ACCEPTABLE YES
CHANNELS STEEL FORMED PACKING GOOD YES
RELATED WORK
DISCONNECTS COMPLIANT YES SPRINKLERS YES
FLOW SWITCHES/HEATS YES SUMP PUMP NO
COOLING NO HEATING NO
MAINTENANCE
MACHINE ROOM ACCEPTABLE MACHINES ACCEPTABLE
CONTROLLERS ACCEPTABLE LUBRICATION ACCEPTABLE
CARTOPS ACCEPTABLE CAR DOORS ACCEPTABLE
PISTON ACCEPTABLE HALL DOORS ACCEPTABLE
PACKING ACCEPTABLE PIT CONDITION GOOD
PERFORMANCE ACCEPTABLE DOOR OPERATION ACCEPTABLE
LEVELING ACCEPTABLE NOISE LEVEL ACCEPTABLE
RECOMMENDED UPGRADES
MACHINES/PUMP UNIT YES FIRE ALARM NO
CONTROLLERS YES HVAC YES
DOOR OPERATORS YES ELECTRICAL NO
PISTONS NO SUMP PUMPS NO
CABS YES MACHINE ROOM CODE YES
FIXTURES YES
ELEVATOR BUDGET RELATED WORK
BUDGET
SCHEDULE 3-5 YEARS TOTAL PER ELEVATOR
MAINTENANCE DEFICIENCIES
1. COMPLETE LIFE SAFETY UPGRADE IN PROCESS. WIRING IS NOT INSTALLED AND UNDER REPAIR.
2. CONDUIT FOR TELEPHONE LINE IN MACHINE ROOM. CODE ITEM
NOTES
EXISTING ELEVATOR IS IN GOOD CONDITION AND RUNNING WELL FOR ITS AGE. DATED CONTROLLER AND
AGING EQUIPMENT WILL REQUIRE REPLACEMENT IN THE 3-5 YEAR RANGE.
CONTINUED PREVENTIVE MAINTENANCE WILL PROVIDE FOR EXTENDED USEFUL LIFE
DEFENSE MEGA CENTER (DMC) REVIEW DATE 2/27/2020
ADDRESS 1482 READ ROAD NO. OF ELEVATORS 1
CITY CORONADO STATE: CA
ELIN ELIN-002 BLD. NUMBER BUILDING 1482
ID 54-02 TEST DATE 2/5/2020
SERVICE TYPE SERVICE ELEVATOR TYPE IN-GROUND HYDRAULIC
INSTALL/MODERNIZATION 1986 SPEED: 125
MANUFACTURER: MONTGOMERY CAPACITY: 3,000
OPENINGS FRONT 2 OPENINGS REAR 0
MACHINE ROOM
CONTROLLER: MONTGOMERY MACHINE TYPE: HYDRAULIC
TYPE COMPUTERIZED TYPE ABOVE OIL TANK
DRIVE TYPE LINE START MACHINE MNFCTR. MONTGOMERY
OPERATION SIMPLEX MACHINE CONDITION ACCEPTABLE
CONTROLLER
MAINTAINABILITY ACCEPTABLE CABLE CONDITION NOT APPLICABLE
GOVERNOR NOT APPLICABLE SIZE CABLES NOT APPLICABLE
HOISTWAY
CAR GUIDES SLIDE GUIDES C/W GUIDES N/A
SAFETY N/A SELECTOR VANES AND SWITCHES
DOOR SYSTEM
SIZE OF DOORS 3’ 6” X 7’ 0” DOOR OPERATOR MONTGOMERY
CONFIGURATION CENTER OPENING DOOR DEVICE SCAN
GENERAL OPERATION GOOD MAINTAINABLE YES
HOISTWAY DOOR EQUIPMENT MAINTAINABLE CAR DOOR
EQUIPMENT MAINTAINABLE
DOOR TIMES COMPLIANT YES RESTRICTOR YES
CAR INTERIOR
INTERIOR AREA 4' 8" X 6' 8" ADA COMPLIANT YES
CAR FIXTURES STAINLESS ADA COMPLIANT YES
COMMUNICATION HANDS FREE ADA COMPLIANT YES
WALL PANELS YES CEILING SUSPENDED PANELS
LEXAN
CONDITION ACCEPTABLE LIGHTING FLOURESCENT
HALL FIXTURES
HALL FIXTURES STAINLESS ADA COMPLIANT YES
VANDAL PROOF YES SIGNAGE YES
FIREMAN SERVICE NO CODE COMPLIANT YES
BUFFERS SPRING PIT LADDER
COMPLIANT YES
COMPENSATION N/A PISTONS ACCEPTABLE YES
CHANNELS STEEL FORMED PACKING GOOD YES
RELATED WORK
DISCONNECTS COMPLIANT YES SPRINKLERS YES
FLOW SWITCHES/HEATS YES SUMP PUMP NO
COOLING NO HEATING NO
MAINTENANCE
MACHINE ROOM ACCEPTABLE MACHINES ACCEPTABLE
CONTROLLERS ACCEPTABLE LUBRICATION ACCEPTABLE
CARTOPS ACCEPTABLE CAR DOORS ACCEPTABLE
PISTON ACCEPTABLE HALL DOORS ACCEPTABLE
PACKING ACCEPTABLE PIT CONDITION GOOD
PERFORMANCE ACCEPTABLE DOOR OPERATION ACCEPTABLE
LEVELING ACCEPTABLE NOISE LEVEL ACCEPTABLE
RECOMMENDED UPGRADES
MACHINES/PUMP UNIT YES FIRE ALARM NO
CONTROLLERS YES HVAC YES
DOOR OPERATORS YES ELECTRICAL NO
PISTONS NO SUMP PUMPS NO
CABS YES MACHINE ROOM CODE YES
FIXTURES YES
ELEVATOR BUDGET RELATED WORK
BUDGET
SCHEDULE 3-5 YEARS TOTAL PER ELEVATOR
MAINTENANCE DEFICIENCIES
1. COMPLETE LIFE SAFETY UPGRADE IN PROCESS. WIRING IS NOT INSTALLED AND UNDER REPAIR.
2. DDC POWER IS FOREIGN EQUIPMENT AND BY CODE IS NOT ALLOWED IN MACHINE ROOM.
NOTES
EXISTING ELEVATOR IS IN GOOD CONDITION AND RUNNING WELL FOR ITS AGE. DATED CONTROLLER AND
AGING EQUIPMENT WILL REQUIRE REPLACEMENT IN THE 3-5 YEAR RANGE.
CONTINUED PREVENTIVE MAINTENANCE WILL PROVIDE FOR EXTENDED USEFUL LIFE
EXPLOSIVE ORDINANCE DISPOSAL (EOD) REVIEW DATE 11/18/2020
ADDRESS 1498 13TH STREET NO. OF ELEVATORS 1
CITY Imperial Beach STATE: CA
ELIN: ELIN 003 BLD. NUMBER BUILDING 193
ID 42-01 TEST DATE 9/1/2020
SERVICE TYPE PASSENGER ELEVATOR TYPE IN-GROUND HYDRAULIC
INSTALL/MODERNIZATION 1999 SPEED: 150
MANUFACTURER: THYSSENKRUPP CAPACITY: 2500
OPENINGS FRONT 3 OPENINGS REAR 1
MACHINE ROOM
CONTROLLER: MCE HMC 1000 MACHINE TYPE: HYDRAULIC
TYPE COMPUTERIZED TYPE ABOVE OIL TANK
DRIVE TYPE WYE-DELTA MACHINE MNFCTR. INDEPENDENT PUMP
UNIT
OPERATION SIMPLEX MACHINE CONDITION ACCEPTABLE
CONTROLLER
MAINTAINABILITY ACCEPTABLE CABLE CONDITION NOT APPLICABLE
GOVERNOR NOT APPLICABLE SIZE CABLES NOT APPLICABLE
HOISTWAY
CAR GUIDES SLIDE GUIDES C/W GUIDES N/A
SAFETY N/A SELECTOR VANES AND SWITCHES
DOOR SYSTEM
SIZE OF DOORS 3’ 6” X 7’ 0” DOOR OPERATOR ECI
CONFIGURATION (FRONT AND
REAR) SINGLE SLIDE DOOR DEVICE SCAN
GENERAL OPERATION GOOD MAINTAINABLE YES
HOISTWAY DOOR EQUIPMENT MAINTAINABLE CAR DOOR
EQUIPMENT MAINTAINABLE
DOOR TIMES COMPLIANT YES RESTRICTOR YES
CAR INTERIOR
INTERIOR AREA 6'10" X 4'5" ADA COMPLIANT YES
CAR FIXTURES STAINLESS ADA COMPLIANT YES
COMMUNICATION HANDS FREE ADA COMPLIANT YES
WALL PANELS YES CEILING EGG CREATE
CONDITION ACCEPTABLE LIGHTING FLOURESCENT
HALL FIXTURES
HALL FIXTURES STAINLESS ADA COMPLIANT YES
VANDAL PROOF YES SIGNAGE YES
FIREMAN SERVICE YES CODE COMPLIANT YES
CAR LANTERNS YES HALL LANTERNS NO
PIT AREA
BUFFERS SPRING PIT LADDER
COMPLIANT YES
COMPENSATION N/A PISTONS ACCEPTABLE YES
CHANNELS STEEL FORMED PACKING GOOD YES
RELATED WORK
DISCONNECTS COMPLIANT YES SPRINKLERS YES
FLOW SWITCHES/HEATS YES SUMP PUMP NO
COOLING NO HEATING NO
MAINTENANCE
MACHINE ROOM ACCEPTABLE MACHINES ACCEPTABLE
CONTROLLERS ACCEPTABLE LUBRICATION ACCEPTABLE
CARTOPS ACCEPTABLE CAR DOORS ACCEPTABLE
PISTON ACCEPTABLE HALL DOORS ACCEPTABLE
PACKING ACCEPTABLE PIT CONDITION GOOD
PERFORMANCE ACCEPTABLE DOOR OPERATION ACCEPTABLE
LEVELING ACCEPTABLE NOISE LEVEL ACCEPTABLE
RECOMMENDED UPGRADES
MACHINES/PUMP UNIT NO FIRE ALARM NO
CONTROLLERS NO HVAC NO
DOOR OPERATORS NO ELECTRICAL NO
PISTONS NO SUMP PUMPS NO
CABS NO MACHINE ROOM CODE NO
FIXTURES NO
ELEVATOR BUDGET RELATED WORK
BUDGET
SCHEDULE IMMEDIATE TOTAL PER ELEVATOR
MAINTENANCE DEFICIENCIES
EXISTING ELEVATOR IS IN GOOD CONDITION AND RUNS WELL. NO MAJOR REPAIRS OR MODERNIZATION REQUIRED IN THE 5 YEAR LOOK AHEAD. CONTINUED PREVENTIVE MAINTENANCE WILL PROVIDE FOR
EXTENDED USEFUL LIFE
HARBOR DRIVE ANNEX REVIEW DATE 11/18/2020
ADDRESS 33150 DESTROYER
LANE NO. OF ELEVATORS 1
CITY San Diego STATE: CA
ELIN: ELIN 004 BLD. NUMBER BUILDING 1
ID 40-01 TEST DATE 9/1/2020
SERVICE TYPE PASSENGER ELEVATOR TYPE IN-GROUND HYDRAULIC
INSTALL/MODERNIZATION 1984 MOD 2005 SPEED: 125
MANUFACTURER: US ELEVATOR CAPACITY: 2500
OPENINGS FRONT 4 OPENINGS REAR 0
MACHINE ROOM
CONTROLLER: MCE HMC 1000 MACHINE TYPE: HYDRAULIC
TYPE COMPUTERIZED TYPE DRY
DRIVE TYPE SCR MACHINE MNFCTR. US ELEVATOR
OPERATION SIMPLEX MACHINE CONDITION ACCEPTABLE
CONTROLLER
MAINTAINABILITY ACCEPTABLE CABLE CONDITION NOT APPLICABLE
GOVERNOR NOT APPLICABLE SIZE CABLES NOT APPLICABLE
HOISTWAY
CAR GUIDES SLIDE GUIDES C/W GUIDES N/A
SAFETY N/A SELECTOR VANES AND SWITCHES
DOOR SYSTEM
SIZE OF DOORS 3’ 6” X 7’ 0” DOOR OPERATOR GAL MOVFR
CONFIGURATION SINGLE SLIDE DOOR DEVICE SCAN
GENERAL OPERATION GOOD MAINTAINABLE YES
HOISTWAY DOOR EQUIPMENT MAINTAINABLE CAR DOOR
EQUIPMENT MAINTAINABLE
DOOR TIMES COMPLIANT YES RESTRICTOR YES
CAR INTERIOR
INTERIOR AREA 4' 3" X 6' 8" ADA COMPLIANT YES
CAR FIXTURES STAINLESS ADA COMPLIANT YES
COMMUNICATION HANDS FREE ADA COMPLIANT YES
WALL PANELS YES CEILING STAINLESS
CONDITION ACCEPTABLE LIGHTING FLOURESCENT
HALL FIXTURES
HALL FIXTURES STAINLESS ADA COMPLIANT YES
VANDAL PROOF NO SIGNAGE YES
FIREMAN SERVICE YES CODE COMPLIANT YES
BUFFERS SPRING PIT LADDER
COMPLIANT YES
COMPENSATION N/A PISTONS ACCEPTABLE YES
CHANNELS STEEL FORMED PACKING GOOD YES
RELATED WORK
DISCONNECTS COMPLIANT YES SPRINKLERS YES
FLOW SWITCHES/HEATS YES SUMP PUMP NO
COOLING YES HEATING NO
MAINTENANCE
MACHINE ROOM ACCEPTABLE MACHINES ACCEPTABLE
C