Amnd 0004 20R6018 Final.pdf

PDF 716 KB Posted

Attached to
Building 201 Repair by Replacement
Solicitation number
N6247020R6018
Issued by

View the file

Other files

File Type Posted
PART 6 A0_TOC REVISION 2.pdf PDF
PART 6 ATTACHMENT Q_BUILDING 201 EQUIPMENT.pdf PDF
Amnd 0005 20R6018 Final.pdf PDF
20-0002 PART 3 Buildings 115 and 201 Repair by Replacement Revision 2.pdf PDF
20-0002 PART 2 Rev 2.pdf PDF
PART 6 ATTACHMENT P_PAD DETAIL.pdf PDF
Amnd 0003 20R6018 Final.pdf PDF
20-0002 PART 3 Buildings 115 and 201 Repair by Replacement Revision 1.pdf PDF
PART 6 A0_TOC REVISION 1.pdf PDF
Amnd 0002 20R6018 Final.pdf PDF
PART 6 ATTACHMENT B_SITE PLAN REVISION 1.pdf PDF
20-0002 Part 4 Revision 1.pdf PDF
PART 6 ATTACHMENT O1_MCIEAST-MCB CAMLEJO 11320.2.pdf PDF
Part 2-Building 201 Repair by Replacement.pdf PDF
Part 6 ATTACHMENT H5- ASBESTOS INSPECTION REPORT.pdf PDF
PART 6 ATTACHMENT O2_MCO 11000.11A.pdf PDF
Part 5-Building 201 Repair by Replacement.pdf PDF
Amnd 0001 20R6018 Final.pdf PDF
20-0002 PART 2.pdf PDF
Master PPI Form Template.xls XLS spreadsheet
PART 6 ATTACHMENT A7_BLDG. 115 FIRE PROTECTION 2009 AS-BUILT.pdf PDF
20-0002 Part 4.pdf PDF
PART 6 ATTACHMENT K_EXAMPLE SCREEN WALL.pdf PDF
PART 6 ATTACHMENT G_DoD Minimum Antiterrorism Standards Checklist.pdf PDF
RFP N6247020R6018.pdf PDF
PART 6 ATTACHMENT D_MCBCL SIGNS STANDARDS-GRAPHICS.pdf PDF
PART 6 ATTACHMENT H2_Bldg. 201 FAP Information.pdf PDF
PART 6 ATTACHMENT B_SITE PLAN.pdf PDF
PART 6 ATTACHMENT A5_95-1466 - Renovate Bldg. 201 Fitness Center.pdf PDF
PART 6 ATTACHMENT H1_Bldg. 115 FAP Information.pdf PDF
PART 6 ATTACHMENT F_MCBCL BEAP.pdf PDF
PART 6 ATTACHMENT M_MCO 5530.14A.pdf PDF
PART 6 ATTACHMENT A4_05-6763 - Renovate Bldg. 115.pdf PDF
20-0002 PART 3 Buildings 115_201 Repair by Replacement.pdf PDF
Part 6 ATTACHMENT E -20-0002 GENERAL NOTES.pdf PDF
PART 6 ATTACHMENT A3_95-1468- Renovate Area Gyms (Bldgs.115 and 201).pdf PDF
PART 6 ATTACHMENT J_MCBCL ELEC DESIGN GUIDE 5.4.20.pdf PDF
PART 6 ATTACHMENT C_ADA CHECKLIST FOR EXISTING BLDGS.pdf PDF
PART 6 ATTACHMENT L_ELECTRICAL MECHANICAL DRAWINGS.pdf PDF
PART 6 ATTACHMENT A9_05-7682 RENOVATE STEAM SYSTEM BUILDING 201.pdf PDF
PART 6 ATTACHMENT N_MCBCL BASEWIDE MNS-FACP CONSTRUCTION REQUIREMENTS.pdf PDF
PART 6 ATTACHMENT I_MCBCL MECH DESIGN GUIDE 7.17.pdf PDF
PART 6 ATTACHMENT A2_09-0093 Fire Alarm System (Bldgs. 115 and 201).pdf PDF
20-0002 PART 5.pdf PDF
PART 6 ATTACHMENT A1_87-9299 BLDGS. 115 and 201.pdf PDF
PART 6 ATTACHMENT H3_ASBESTOS AND LEAD BASED MATERIALS ASSUMPTION.pdf PDF
PART 6 ATTACHMENT A8_P-1449B ENERGY EFFICIENCY IMPROVEMENTS (BLDG. 115).pdf PDF
PART 6 ATTACHMENT A6_86-5589-Construct Racquetball Courts(Bldg. 201andS204).pdf PDF
PART 6 A0_TOC.pdf PDF
PART 6 ATTACHMENT A10_P-1449B ENERGY EFFICIENCY IMPROVEMENTS (BLDG. 201).pdf PDF
Show 40 more

Latest 50 of 51 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

1. CONTRACT ID CODE

2. AMENDMENT/MODIFICAITON NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicble)

7. ADMINISTERED BY (If other than Item 6) CODE

STANDARD FORM 30 (REV. 10-83)

Prescribed by GSA FAR (48 CFR) 53.243

FACILITY CODE

9A. AMENDMENT OF SOLICIATION NO.

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NO.

10B. DATED (SEE ITEM 11)

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended, is not extended.

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a)By completing items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment your desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPIRATION DATA (If required)

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15C. DATE SIGNED

15A. NAME AND TITLE OF SIGNER (Type or print)

16C. DATE SIGNED

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

PAGE OF PAGES

6. ISSUED BY CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) (X)

CODE

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

NSN 7540-01-152-8070

Previous edition unusable

Building 201 Repair by Replacement Solicitation N6247020R6018 Marine Corps Base Camp Lejeune, North Carolina Amendment 0004

Block 14. DESCRIPTION OF AMENDMENT (cont.)

A. The following provides the Government’s responses to pre-award inquiries:

REFERENCE

QUESTION GOVERNMENT RESPONSE

Page Section Para.

Block 14, Factor 1

(a) Solicitation Submittal Requirements states to include proposed "testing and balancing (TAB) and performance verification plans". How many pages are allowed for these?

How much detail is required?

These plans can easily grow to several hundred pages. How should equipment that isn't fully designed be addressed?

See Evaluation Factor 1 for Submittal Requirements.

Site Plan for Bldg 201 shows UE going through the building. Does the electric serve other buildings?

The second UE (secondary electric line) does not go underneath building 201.

That line services building S-204 (racquetball building). Contractor shall field verify field utilities.

7, 11 Part 1 Price Part 1 of the RFP under “Price” lists Acknowledged Amendments as a submission item. Please confirm the preferred method for submittal of this information.

Would the Government like signed SF30s, the form provided on page 11 populated, or both?

Either option is acceptable.

n/a General n/a Please confirm that betterments within the Offeror's proposal are not allowed and will not be evaluated by the Government.

Betterments will not be evaluated.

4, 7, 9 Part 1 Submittal Require-ments/ Proposal

Should the Offeror elect to send hard copies via overnight mail as outlined under Solicitation Submittal Requirements, please confirm: is the correct address

Confirm.

Delivery Information for hard copy shipment the same as hand-delivery instructions to Building 1005 outlined on page 9 of the RFP?

Amend ment 2

Given the change in scope with Amendment 2 and outstanding requirements, please extend the due date for bids by 2 weeks.

Due to planned execution dates, the Government is unable to extend the due date for receipt of proposals.

Factor 2 – Manage ment

3 Schedule Please provide the anticipated Notice of Award/Notice to Proceed date to use for the schedule to be included in the proposal.

The Government anticipates award not later than 9/30/2020.

2 Part 3 Project Description

Is the General Contractor responsible for demolishing, relocating, protecting or storing fitness equipment that is located within the exterior yard of Building 201 and within the demolition and reconstruction LODs?

No, the Government plans to remove all fitness equipment prior to start of construction.

C-5 PART_6_

ATTACH

MENT

_B_SITE_

PLAN

As-builts What does the existing AmeriGas tank service that is located in the site perimeter of the 201 site? Is it anticipated that the new building will need a separate gas tank other than the typical building service? This utility is neither shown on the utility as-built nor referenced in the RFP.

The existing AmeriGas tank services the dryers. It is anticipated that the dryers will be connected to the natural gas line in the new building. Contractor shall locate and demolish all existing propane gas line.

AmeriGas tank will be removed by others. Please refer to revised Part 3.

C-5 PART_6_

ATTACH

MENT_

B_SITE_

PLAN

As-builts Please confirm or deny that the existing steam pits located within the 201 site perimeter are to be demolished under this contract?

If so what is the scope of work?

These items are not referenced in the RFP.

Contractor shall demolish existing steam pits, steam pipes and condensate pipe within boundary indicated on Part 6 Attachment B Site Plan Revision 1, page

65 Part 3 G101002 Tree Removal

This section states to remove trees by permit or waiver of Camp Lejeune but in an earlier section it mentions to remove all trees within 30' of the buildings.

Are special permits or exceptions to be considered for clearing trees on these project sites?

There are no special permits needed, however, the contractor must coordinate with MCB Camp Lejeune Environmental Management Division prior to removal.

68 Part 3 G201006 Resuracing

Is milling and overlay part of this work or is it simply an overlay?

Resuracing parking lot is not required in this project. Please refer to revised Part 3.

68 Part 3 G201006 Resuracing

What is the thickness of the overlay for the 201 parking areas?

Resuracing parking lot is not required in this project. Please refer to revised Part 3.

C-4 PART_6_

ATTACH

MENT_

B_SITE_P

LAN

As-builts It is understood that we are to overlay the existing parking lots and provide striping, wheel stops, etc. for building 201. However, what percentage or area of curb is to be demolished and replaced around the perimeter of the site?

Can it be assumed that we replace only the edge of the parking lot bordering the building site and thus containing sidewalks?

Resuracing/overlay and wheel stops for existing parking lot is not required for this project. Please refer to revised Part 3.

Confirmed, please assume to replace only the edge of the parking lot bordering the building site, including sidewalks, and other areas damaged during construction.

Part 6, Attachment 7

Hydrant flow data is provided on as-built drawings for Building 115 in Part 6 Attachment A7 as follows: Date – 9-2-08, Static – 55 psi, Residual – 45 psi, Flow – 1500 gpm. Please provide updated information for Building 201.

A recent flow test has not been performed for building 201. Contractor should perform the flow test. Flow test should be witnessed by the Contractor DOR Fire Protection Engineer.

69 Part 3 G204090

OTHER

SITE

IMPROVE

MENTS

Please confirm that a double dumpster enclosure is required at the 201 project site.

Confirmed. Refer to revise Part 3, Chapter 6 G204090.

73 Part 3 G402001

EXTERIOR

LIGHTING

FIXTURES

AND

CONTROLS

Building 201 Parking Lots: Is a new lighting study to be done for the parking areas, to include furnishing new light poles and bases or is the requirement to simply swap fixtures and lighting controls.

Please only change the fixtures and lighting controls for the parking lot.

7 Part 3 (Project Description)

4.B.1.e.6 The referenced section of the RFP requires roof insulation to be compliant with ASHRAE 90.1 - 2016. Please confirm this is a minimum prescriptive requirement and that it takes precedence over references to older versions of ASHRAE 90.1 and 289.1 in other portion of the RFP and UFCs.

ASHRAE 90.1 – 2016 is the minimum prescriptive requirement.

25 Part 3 (Room Requirements)

The D30 section of the Room Requirement for the Typical Mechanical / Electrical / Telecommunication Spaces indicates the mechanical / electrical rooms require an electric heating and mechanical ventilation. Is this accurate for mechanical rooms with chilled water pumps and cooling air handlers? Note that the MCBCL Mechanical Design Guide 7.17 states to provide dehumidification and no ventilation.

For mechanical rooms, follow MCBCL Mechanical Design Guide 7.17. "Do not ventilate cold equipment rooms. Cold equipment rooms are those rooms with chilled water pumping, cooling air handlers, etc. These rooms should be unvented and with small dehumidifier. Drain condensate to floor drain or other disposal location.

Summer dew point ranges from low to high 70’s at Camp Lejeune causing condensation on equipment and piping.

Dehumidifier should be wall mounted with wheels removed and hard wired with disconnect (no pigtail with plug) to discourage theft/relocation.

Dehumidifier should be hard piped to drain to avoid drainage blockage."

40 Part 3 (D20 Plumbing)

D20 D20 states " Remove and dispose of entire plumbing system in all buildings included in this RFP unless noted otherwise". Please clarify if underground piping is to be abandoned in place, used to the extent possible, or demolished in entirety?

Remove and dispose of entire plumbing system in all buildings including underground piping.

Please refer to revise Part 3 Chapter 6 D20.

10 Part 3 4.E.2.a) Part 3 requires an emergency eyewash in the janitors closet.

Please indicate if this is accurate.

Confirmed. Please provide an emergency eyewash in the janitor’s closet.

44 Part 3

(D30 HVAC)

D30 General System Requirements and D304008

Please confirm total energy recovery systems are only to be used if determined to be life cycle cost effective.

Utilize total energy recovery cores for high occupant load areas.

Please refer to Part 3 Chapter 6 D304008.

46 Part 3

(D30 HVAC)

D3070 D3070 requires the system to be TAB'd. Please confirm the system is required to be DALT'd as well.

DALT is required per

SECTION 23 05 93 -

TESTING, ADJUSTING, AND

BALANCING FOR HVAC.

27 Part 3 A10 A10 indicates subsurface soil information and geotechnical report is included in the RFP. No information was found - Please provide geotechnical information.

Refer to revised Part 3, A10. Contractor to perform geotechnical evaluation.

7 Part 3 4.B.6 Paragraph references IBC 2009.

Please confirm if this should be

IBC 2018.

Please use the latest IBC edition.

29 Part 3 6 B10 Please confirm any type of roof framing can be utilized provided it is permitted in UFC 3-301-01.

The DOR is responsible for roof framing selection.

55 D503001 3 Per D503001 and Base specification 33 82 00, there appears to be the ability to use PE-89 copper telephone cable in lieu of the PE-39 mentioned in

Confirmed, please use PE-

39. Refer to specification 33 82 00 in Part 5.

both locations. Please confirm the use of PE-39 over PE-89 copper telephone cable.

53 D501002 2 D501002 calls for a meter at the pad mounted transformer secondary. It also is calling for a digital meter at the main switchboard. Is a meter required at both locations?

Meter is required at transformer per specifications provided. If Service Entrance equipment is switchboard construction a meter is required in switchboard. If SE equipment is panel board construction, a meter is not required in the panel board.

73 G401009 1 Are electric meters to be connected to base wide SCADA system?

Electric Utility meters do not require SCADA connection.

72 G401002 2 Is the pad mounted transformer required to have Stainless Steel base, tank and enclosure?

Yes. Refer to specifications provided in part 5.

74 G403002 1 Please provide point of connection for CATV system.

This project provides CATV system inside building and conduits with pull strings from head end equipment to the building exterior.

Tenant is responsible to get CATV service from provider into building.

70 Part 3 – G3030

STORM

SEWER

All We have a very limited project footprint for the building replacement (less than 1 acre) and current SOW calls for replacing a 11,946 SFT bldg. with a 26,221 SFT building and there is not a lot of on-site room for integrating LID stormwater quality and volume reduction control measures. Please confirm what level of on-site stormwater management will be required for regulatory

On-site treatment must be provided per NC DEQ requirements. Credits from the existing impervious area can be used to offset total new impervious area.

If requirements cannot be met within the current site boundary, propose an extended site boundary to accommodate.

compliance and alternate locations for LID features as there is insufficient area on site for EISA Section 438 required LID compliance measures.

70 Part 3 – G3030

STORM

SEWER

All As designated project area for Bldg 201 is less than 1-acre please confirm if any project specific North Carolina DEQ erosion control or stormwater permits will be required.

Permits are required per NC DEQ. The existing impervious area can be used as a credit towards the total new impervious.

71 Part 3 – G303007

STORM

WATER

MANAGE

MENT

All Please confirm what level of on-site stormwater management will be required for regulatory compliance and alternate locations for LID features as there is insufficient area on site for EISA Section 438 required LID measures.

On-site treatment must be provided per NC DEQ requirements. Credits from the existing impervious area can be used to offset total new impervious area.

If requirements cannot be met within the current site boundary, propose an extended site boundary to accommodate.

Part 3 –

Part 3, 4 Building Requirements, B. Exterior Character

b) and c) Paragraph b) states: “The existing design identified the buildings as gymnasiums. The new design must incorporate those distinctive exterior features.”

Paragraph c) states: “The design shall be in conformance with the most current edition of the MCB Camp Lejeune Base Exterior Architecture Plan (BEAP).

Including but not limited to…gable on hip and hip roofs.”

The roof at existing building 201 is a gable form, which does not meet the requirements of the BEAP for Hadnot Point. Please confirm that a gable roof is acceptable at the new building 201.

Please provide the roofline to match the BEAP (gable on hip and hip roof).

Part 3 –

Part 3, 4 Building Requirements, B. Exterior Character

d) Main Exterior Features,

4. Siding

Please note that “siding” is not included in the details commonly associated with the Georgian and Colonial Revival styles in Hadnot Point as outlined by the BEAP.

Please confirm that siding is not required to be included at the new building 201 exterior.

Siding will not be required when providing gable on hip and hip roof.

Part 3 –

Part 3, 4 Building Requirements, B. Exterior Character,

d) Main Exterior Features

d) Main Exterior Features,

5. Medallions at exterior pilasters

Please note that “medallions” are not included in the details commonly associated with the Georgian and Colonial Revival styles in Hadnot Point as outlined by the BEAP. Please confirm that medallions are not required to be included at the new building 201 exterior.

Medallions are Required.

Final configuration (size and motif) should be approved by the Government.

Amd002 Part 3 Chp4

E.1(a) &

E.1(b)

Amd002 states “There are approximately 4 items (washers and 2 dryers) that will need to be moved…” Please provide a basis of design for this equipment or actual manufacturer and model number(s) of existing equipment so required infrastructure and vibration isolation/attachment to structure can be accommodated in the bid price.

"The manufacture and model numbers for the washers are Unimac model number UCN030HN20U1001 and model number

UCNO4OHN20U1001.

Amd002 Part 3 Chp5

- Typical and Open Office Spaces & Massage Room/ Paragraph C301003 Wall Finish indicates a requirement for Acoustic Wall Panels, however, there is no additional information on location and/or size requirements for this wall finish. Please provide additional location and size design criteria for this wall finish to obtain a more accurate bid price.

Please refer to revised Part 3 Chapter 5

Amd002 Part

3 ESR

C103014 pg 37 Entrance Floor Grilles and Mats states “Provide recessed floor mats at main building entrances. Provide recessed floor pats at other building entrances shown in plan.” Is the intent of this statement that new Building 201 should have recessed floor mats at all building exterior doors excluding utility spaces?

Non-concur. The new building will not require recessed floor mats. Please refer to revise Part 3 Chapter 6 ESR C103014.

Part 3 Chp4 E.2(o) States to provide (2) new 8ft x 8ft saunas. Part 3/ Chapter 5 Room Requirements sheet for Sauna sate the sauna(s) are optional. Please confirm if saunas are part of the base bid or should be priced as an option?

Saunas are required and should be a part of the base bid. Part 3/Chapter 5 Room Requirements sheet has been revised.

Part 3 Chp5 - Laundry/E20 Furnishings states to storage shelves for laundry supplies. Please provide a quantity/lineal feet.

"DOR to determine built-in shelves sizing and quantity based on new laundry room layout.

Part 3 E(f) States "1 Combined Mechanical and Electrical room, minimum of 30 foot x 20 foot. Room should include the following but not limited to: gas-fired water heater(s), boilers, hydronic pumps, hydronic accessories air handling and electrical equipment."

RFP Part 6_I MCBCL Mechanical Design Guideance (4) states " If possible separate fuel fired equipment and other heat producing equipment from air handlers and other equipment that has a cool surface temperature into different mechanical rooms."

Please refer to revised Part 3.

Please confirm that mechanical and electrical rooms shall be separate spaces.

Amendment

Amendment 2 removed building 115 and associated spaces, but maintained Bldg 201 as roughly 24,000sf of space. However, spaces are only programmed by room data sheets and the RFP for less than half of that. Please provide additional information and requirements on what the remainder of the building is to be used for and how it's to be programmed.

The intent is to have as much space for the open fitness floor as possible.

Amendment

Because of the change in square footage of Bldg 201 from the existing building, and the site constraints due to utilities and roads, the building is a large rectangle. With the BEAP requirements for architectural aesthetics including roof slope, this will mean the new building is likely to be a large box with a 20’ roof height on it. Please confirm that strict compliance with the RFP and BEAP language is required.

Provide options to evaluate in the CDW. The options must take into consideration and be an acceptable compromise of the criteria to take into consideration such as the BEAP, Precedent, Adjacent Structures, etc.

NA D40 NA Please provide proper hydrant flow test data for building 201 in accordance with NFPA 291 for bidding purposes. We understand the successful contractor will conduct a new flow test on award; however, flow test data is needed to bid the project to ensure that a fire pump is not needed and to estimate sizes of sprinkler piping.

If this data cannot be provided should the contractor assume

Flow test/analysis shall be included in contract. No further information available.

that a pump is not required since no data would be available to confirm?

Page 8 Part 3- Statement of Work/Project Program

Per Part 3 C. Page 8 - "Interior Character" it is noted that use of Ground Face CMU is encouraged.

Ground Face CMU is not noted in the Room Requirements. Please verify where Ground Face is desired.

Please refer to the revised Part 3.

Atch. 1 & 5 The existing drawings include the large Gym space but the RFP does not explain the new requirements. Please provide complete Program requirements or at least required Square Footage, clear height requirement, and finishes.

Please refer to Part 3 Chapter 4.E.2.g and Chapter 5 Room Requirements: OPEN

FITNESS/ EXERCISE/

WEIGHT SPACE.

Atch. 1 & 5 Is the new room-by-room square footage to match the square footage we scale off of the existing drawings or will you be providing a total building Program Summary with the required room square footage?

Non-concur. Please see revised Part 3 Chapter 5 Room Requirements.

Please confirm whether in the gymnasium whether there will be a sports program so we can consider court and clearance requirements, striping, etc.

Building 201 will be consider a fitness center. A basketball/racquet court is not required for this project.

So it is clear what parts of the BEAP apply please confirm the district where building is.

Hadnot Point.

11 20-002 Part 3A thru G

Interiors Requirements

In the room getting treadmills please provide a Program that confirms whether recessed floor electrical receptacles are acceptable to provide flexibility for equipment layout.

The end-users have going issues with recessed floor electrical receptacles, we would like to have all outlets in the wall. Other than the treadmills, they will be approx. 20 powered equipment.

Are the design requirements for the new canopies to match the height and width of the existing Arcades? If not, please define Program requirements.

DOR should provide three options of an aesthetically pleasing design for new canopies. Please refer to Part 2 01 31 19.05 20 1.4.B.f

Atch. 1 & 5 The existing drawings show a Sports Medicine Room but there is not one shown in a new Program and there is not a Room Data Sheet for it. Please clarify Program requirement that at a minimum includes square footage, clear height, and finishes information that could impact pricing.

The new building does not require a new sports medicine room.

14 20-002 Part 3A thru G

Room Requirements

Please confirm flooring for Lobby and Corridors. In accordance with UFC_4_740_02 florring for Lobby and Corridors shall be stained concrete, stone, terrazo, or porcelain tile

Flooring shall be followed per the Room Requirements.

Atch. 1 & 5 "Existing staff toilet shows 2 showers, 3 urinals, 2 toilet stalls and 2 sinks. Please confirm whether that is to be duplicated in the new design. Is there a Program driven requirement to establish a Male: Female ratio? "

Please refer to Part 4.E.2.n for unisex restroom requirements.

Atch. 1 & 5 Existing Toilet 106 appears to be for use for both staff and patrons and it is part of Auditorium.

Does the RFP require the new design to provide a single toilet room to replace that existing one? Please clarify Program requirements regarding toilet

Please refer to Part 4.E.2.n for unisex restroom requirements. Unisex restroom will be utilized by patrons when main restroom is closed for cleaning.

operation, public / private, shared unisex rooms, etc.

Provide full list of equipment, including number and type of weight racks.

The Government does not have an updated list of equipment. The equipment selection will vary based on the new proposed layout. The Government can provide a list of previous equipment list during the design review process.

Provide Program requirements for all fitness activities at the new building.

This facility will not have any group classes or fitness activities. This facility will be available to users for regular fitness and weight lifting.

Please define the number of users the fitness area will require to service at any given time.

The facility have an average of 1,300 users a day. Approx. 60-150 users per hour.

Please confirm it this is a 24-hour facility.

Non-concur, this is not a 24-hour facility.

Atch. 1 & 5 The existing drawings show a Managers Room but there is not one shown in a new Program and there is not a Room Data Sheet for it. Please clarify Program requirement that at a minimum includes square footage, clear height, and finishes information that could impact pricing.

Provide office count per

RFP.

Is a Personal Trainer office required? There is not one shown in a new Program and there is not a Room Data Sheet for it. Please clarify Program requirement that at a minimum includes square footage, clear

Provide office count per

RFP.

height, and finishes information that could impact pricing.

Atch. 1 & 5 In the Existing building drawings, Dressing Room is shown as separate either off the toilet or locker room. Is RFP intent to nearly duplicate that room relationship in-kind, separate, or consider it as a part of Locker Rooms?

Locker room, dressing room and bathroom shall be connected.

Atch. 1 & 5 Outside of providing exits in the new Floor Plan in accordance with Code requires, please confirm there is no user Program associated with the existing space called Fire Exit Hall. If there is, please clarify Program requirement that at a minimum includes square footage, clear height, and finishes information that could impact pricing.

Confirm. No additional exits are needed.

Please confirm all Program size requirements for space like Storage and Closet.

Please see revised Part 3 Chapter 5 Room Requirements.

Atch. 1 & 5 Is separate room/office required for Fitness Director?

Provide office count per

RFP.

Please clarify Program requirement for Massage Rooms that at a minimum includes number of Rooms required, square footage, clear height, and number of tables that could impact pricing.

Please see revised Part 3.

Is a Basketball Court with recommended clearance around the court and striping part of the Program for the new building? If yes, is an NCAA court size required in accordance with

UFC_4_740_02?

A basketball/racquet court is not required for this project.

Please clarify Program requirement for the Storage room that serves the Exercise Area. At a minimum include square footage, clear height, and finishes information.

Please see revised Part 3.

Please clarify Program requirement for the Structured Activity Space. At a minimum include square footage, clear height, and finishes information.

This facility will not have any group classes or fitness activities. This facility will be available to users for regular fitness and weight lifting.

Please clarify Program requirement for HITT Center. At a minimum include square footage, clear height, and finishes information.

This facility will not have any group classes or fitness activities. This facility will be available to users for regular fitness and weight lifting.

Please clarify Program requirement for Equipment Repair room. At a minimum include square footage, clear height, and finishes information.

The new building does not require an equipment repair room.

In accordance with UFC_4_740_02, are any retail/vending food and beverage sales required?

No, vending machines are not required.

In accordance with UFC_4_740_02, is break room or cafeteria required?

Refer to revised Part 3.

In accordance with UFC_4_740_02, is indoor cycling in the program?

There are no indoor cycling programs but will plan to have some type of cycles in our equipment layout plan for patrons to have access to use.

In accordance with UFC_4_740_02, is blood pressure

No, blood pressure monitor and flat display are not required.

monitor and flat display required in locker rooms?

11 20-002 Part 3A thru G

Interiors Requirements

"Provide support/mount for television by each exterior door"

- Please clarify requirement for TVs by each exterior door.

TVs will be a 42" monitors.

5 Part 3 3.B.e The RFP calls for all shrubs and trees within 30 ft from the building to be removed and replaced with sod, but para 3 calls for drought tolerant plants -are there any landscape requirements?

Provide sod around facility.

5 Part 3 3.B.i The program here is stating where practical install rain leaders that spill to the ground for LID - is that the intent to only use downspout disconnect to meet the LID requirements?

To be determined by DOR.

3 Part 3 1.A.3 The program calls for repair by replacement and calls for the bldg footprint to be increased -what is the intent from a stormwater perspective. Are we to only consider the increase in impervious for stormwater calculations or are we to meet the full intent of EISA 438?

The existing impervious area can be used as a credit towards the total new impervious. Permits are required per NC DEQ.

70 Part 3 G3010 The program calls for meters -but since the demolition only extends 5' beyond the building, can we assume that existing meters will be intact and reused?

Please refer to revise Part 3 1.7.d (Utilities shall be removed and replaced from the buildings back to the main). Please assume to provide a new meter.

71 Part 3 G303007 On page 5 it calls for rain leaders to spill to the ground in reference to LID practices, however, her it mentions bioretention swales, infiltration trenches,… Is your

To be determined by DOR.

intent to only use downspout disconnect to meet LID?

70 Part 3 G3020 The program calls for a post installation TV inspection - are we to TV the 5' of new sewer main?

All utilities shall be inspected and approved by the DOR. TV inspection is one of the method of inspection but is not required. Refer to revised Part 3.

68 Part 3 G201005 Can we assume the existing parking area has wheel stops and bollards to meet this requirement? Can we also assume that the signage is intact and acceptable?

The existing parking lot (within the site boundary) does not have wheel stops and bollards. Wheel stops for this parking lot is not required. Please refer to revised Part 3. Non-concur, please assume to provide new signage.

68 Part 3 G204004 Can we assume that as existing passive barrier system is existing for the current facility?

Passive barrier system is not required for this project. Please see revised Part 3.

5 Part 3 3.B.h Are we to assume all sidewalks need to be replaced to meet the ADA/ABA requirements?

Confirmed. Assume all sidewalks within the site boundary will need to be replaced to meet ADA/ABA requirements.

12 Part 3 (o) Plumbing - Please confirm that a floor drain is not required in Unisex Restroom.

A floor drain is not required in Unisex Restroom.

17 Part 3 Table HVAC - D30 references FC 4-740- 02N. Should this reference be UFC 4-740-02 (Change 1, 30 May 2019), the current UFC edition for Fitness Center design?

Reference UFC 4-740-02 (Change 1, 30 May 2019), the latest approved.

20 Part 3 Table D201004

Is floor drain required in Massage/Office (as specifed in

UFC 4-740-02)?

A floor drain is not required in Massage/Office.

46 Part 3 D306001 1.1

HVAC - Will the building HVAC DDC system be required to communicate with a remote Base Wide EMCS? If so what points are required to be visible and which points are required to be controllable from the EMCS?

Yes. Refer to Part 6 drawings and specification 23 09 23.13 for requirements.

B. Incorporate the following updated attachments:

1. 20-0002 PART 2 Rev 2

2. 20-0002 PART 3 Buildings 115 and 201 Repair by Replacement Revision 2

C. All other contract terms and conditions remain unchanged.

Amnd 0004 20R6018
Untitled
Untitled

Pg2 Amnd 0004 20R6018

IDCode:
Page: 1
Pages: 19
AmendNo: AMENDMENT NO. 0004
EffDate: 07/17/20
ReqNo:
ProjNo: 20-0002
IssCode: ROICC81
IssuedBy: OFFICER IN CHARGE OF CONSTRUCTION FLORENCE

NAVAL FACILITIES ENGINEERING COMMAND ATLANTIC

1121 HAMMOND ROAD

CAMP LEJEUNE, NC 28547-2521

AdmCode:
AdminBy: See Item 6
ContName:
ContStrt:
ContCnty:
ContSt:
ContZIP:
Code:
FacCode:
SolChgYs: Yes
SolChgNo: Off
SolAmdNo: N6247020R6018
AmendDate: 06/15/20
ModNo:
ModDate:
NoCopies: 1
Amended: Yes
OffrExt: Off
OffrNoEx: No
ApprData:
ChgeOrd: Off
ChgeOrder:
Modify: Off
SuppAgre: Off
SuppAuth:
ModOthr: Off
OthrSpec:
NoReq: Off
Require: Off
Copies:
Descript:

N6247020R6018 Building 201 Repair by Replacement, Marine Corps Base Camp Lejeune, NC