This document contains questions and responses related to a solicitation for the USNS HUNTER (TSV-3) Docking Phased Maintenance Availability (DPMA). The solicitation seeks maintenance and repair services for various ship systems including an engine overhaul, tank and void surveys and repairs, a bow thruster inspection and repair, and hydro crane and galley sink installations. Bidders had questions on location details, missing references in the solicitation, and requests for additional technical manuals. The Navy provided location and technical document clarification or indicated documents would be sent via a future file transfer method. Eligible contractors can request the pricing workbook, statement of work, and milestone schedule by contacting the listed contracting officers.
View the file
Other files for this federal contract opportunity
Show all 42
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ITEM NO: Ship Check
TITLE: Soliciation
PARA. NO:
PAGE NO:
ITEM NO: 042-00-001
TITLE: Work Completion Certification
PARA. NO: 2.2
PAGE NO: 1 of 5
ITEM NO: 123-11-001
TITLE: ABS Survey and Repair of Tanks and Voids
PARA. NO: 2.29
PAGE NO: 2 of 7
ITEM NO: 233-11-001
TITLE: MDE 10,000 Hour Top End Overhaul
PARA. NO: 2.2, 2.6, 2.7, 2.8
PAGE NO: 1 of 7
ITEM NO: 568-11-001
TITLE: Bow Thruster; Inspect and Repair
PARA. NO: 2.13
PAGE NO: 1 of 5
ITEM NO: 589-11-001
TITLE: Hydro Pro Marine Crane; repair
PARA. NO: 2.2
PAGE NO: 1 of 5
ITEM NO: 651-11-002
TITLE: Galley Sink; install
PARA. NO: 2.2
PAGE NO: 1 of 2
CONTRACTOR QUESTION 1: Where will the USNS HUNTER be located for the ship check?
GOVERNMENT RESPONSE: HUNTERS SHIP CHECK LOCATION
WILL BE JEBLC, PIER 58.
CONTRACTOR QUESTION 2: Reference 2.2 Joint Fleet Maintenance Manual could not be found in the references provided. Please provide this reference.
CONTRACTOR POC:
REQUEST FOR SPECIFICATION CLARIFICATION
CONTRACTOR PHONE:
DATE OF REQUEST: 2/9/2021 SOLICITATION NO: N50054-21-R-0005
TITLE: USNS HUNTER (TSV-3) Drydock Phased Maintenance Availability (DPMA) MARMC POC: Veronica Johnson Amy Caraway
CONTRACTOR: MARMC PHONE: (757) 400-
0214 (757) 400-0173
GOVERNMENT RESPONSE: This document should be readily accessible to the company.
https://www.navsea.navy.mil/Portals/103/Documents/SUBMEPP/00_J FMM.pdf
CONTRACTOR QUESTION 3: Reference 2.29 810-4714432, Rev J, Std Pipe Hangers Fabrication Details & Installation Instructions could not be found in the references provided. Please provide this reference.
GOVERNMENT RESPONSE: Added to NEW drop
CONTRACTOR QUESTION 4: The following references could not be found in the references proviede. Please rpovide these references; 2.2 SEBU5561-01, Caterpillar Operation and Maintenance Manual, 2.6 S923- CJ-HBK-10, US Navy Diesel Engine Inspector Handbook, Part I, Inspection Procedures; With Changes A-e, 2.7 S9086-HB-STM-010/CH- 233, Diesel Engines, 2.8 S9086-GX-STM-030/CH220, Corrosion and contamination Control for Diesel Engine Cooling Water System.
GOVERNMENT RESPONSE: 2.2 will be deleted via errata, 2.6, 2.7,
2.8 will be sent via new drop
CONTRACTOR QUESTION 5: Reference 2.13 MIL-STD-271, Requirements for Non-destructive Teating Methods could not be found in the references provided. Please provide this reference.
GOVERNMENT RESPONSE: Verifed included in orginal drop
CONTRACTOR QUESTION 6: Reference 2.2 Hydro Pro Marine Crane Model HP40-18K, Owner's Manual could not be found in the references provided. Please provide this reference.
GOVERNMENT RESPONSE: Will be submitted in new drop
CONTRACTOR QUESTION 7: Reference 2.2 8171276, Berthing, Galley, Lounge, Pantry and Head Installtion could not be found in the references provided. Please provide this reference.
GOVERNMENT RESPONSE: See Errata
ITEM NO: 982-31-001
TITLE: Dock Trial, Fast Cruise and Sea Trial
PARA. NO: 2.2
PAGE NO: 1 of 2
ITEM NO: 992-11-001
TITLE: Temporary Services, provide PARA. NO: 2.2, 2.6, 2,7 and 2.8 PAGE NO: 1 of 8
ITEM NO: 992-31-002
TITLE: Cleaning and Pumping, accomplish
PARA. NO: 2.4
PAGE NO: 2 of 7
CONTRACTOR QUESTION 10: Reference 2.4 United Facilities Guide specifications-33 01 50.60, Cleaning Petroleum Storage Tanks could not be found in the references provided. Please provide this reference.
GOVERNMENT RESPONSE: Will be sent via DOD DROP
CONTRACTOR QUESTION 8: Reference 2.2 S9086-C4-STM-000/CH- 94, Trials could not be found in the references provided. Please provide this reference.
GOVERNMENT RESPONSE: Will be sent via DOD DROP
CONTRACTOR QUESTION 9: The following referecnes could not be found in the references provided. Please provide these referenes; 2.2 UFC 4-152-01, Unified Facilities Criteria (UFC), Design: Piers and Wharves,
2.6 NFPA Standard 30, Flammable and Combustable Liquids Code, 2.7
GOVERNMENT RESPONSE: ref 2.2 will be sent via DOD DROP.
2.6, 2.7, and 2.8 references can be found at https://www.nfpa.org/codes-and-standards/all-codes-and-standards/list-of-codes-and-standards/detail?code=30