This is an Asbestos Inspection Report for Building #FC574 (a Barracks/Enlisted Quarters facility) at MCB Camp Lejeune, printed March 19, 2026. The building was constructed in 1986 and holds a Hazard Rank 0/BLUE classification as of September 2019. The report documents a comprehensive history of asbestos-containing materials (ACM) assessments dating back to July 2002, with major renovations conducted in 2014-2015 during which all known ACM was removed and the roofing system was stripped and replaced.
The inspection identifies one non-friable ACM currently present in the building: membrane-type roofing material located in the main roofing system at the perimeter flashings, measuring approximately 800 square feet and identified on 9/17/2019. No friable ACM records are found in the current database. The report documents extensive historical sampling data from multiple inspection dates (2002, 2005, 2008, 2012, 2013, and 2019) identifying previously tested and removed materials including 12-inch beige floor tile with adhesive, textured ceiling materials, various roofing sealants, duct sealants, and transite panel debris. Key guidance provided includes avoiding disturbance of remaining ACM materials and reporting any damage or changes in condition to the Camp Lejeune Asbestos Program Manager at 910-451-5837. The building is subject to periodic inspections to monitor changes in ACM condition.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS INSPECTION REPORT of:
Building # FC574
MCB CAMP LEJEUNE
Thursday, March 19, 2026
Print Date
Thursday, March 19, 2026 Page 1 of 9Print Date:
INSPECTION SUMMARY
BLDG #:
OCCUPANT:
YEAR BUILT:
BUILDING COMMENTS:
FC574
BEQ
HAZ RANK 0/BLUE [AH SEPT2019]
NO KNOWN ACM ID'D
SEPT2019
NO CHANGES, NO ACM ID'D
JUN2016
MAJOR RENOVATIONS 2014/15, ALL KNOWN ACM REMOVED; ROOFING SYSTEM STRIPPED AND REPLACED
DEC2013
TPM DEBRIS REMOVED/ NOT ID'D, ACM ROOFING MATERIALS REMAIN
SEPT2012
MAJOR RENOVATIONS, ACM ROOFING MATL'S REMAIN, ADDL ACM ID'D INCLUDES:
TRANSITE PANEL MATERIAL DEBRIS
NOV08:
PVS. ACM REMAINS, ADDL ACM INCLUDES:
THRESHOLD MASTIC
ROOFING SEALANTS, GRAY, BLACK
SEPT05:
PVS. ACM REMAINS, NO SAMPLING
INSPECT JUL02 AES
NON FRIABLE ACM INCLUDES:
12" BEIGE FLOOR TILE AND ADHESIVE (VARIOUS TYPES)
ASBESTOS MANAGER: 910-451-5837
Friable ACM(s) identified
Non-friable ACM(s) identified
Tested Non ACM or REMOVED Materials
DESCRIPTION LOCATION Date
NOTICE: The following asbestos-containing materials have been identified in this structure. Refer to survey findings for additional information or contact the Asbestos Program Manager. Please note ACM that is intact and undisturbed is not considered a significant health hazard to building occupants.
DESCRIPTION LOCATION Date Quantity
DESCRIPTION LOCATION Date Quantity
No friable ACM records found in database
NOTIFICATION OF ACM IN BUILDING
MEMBRANE-TYPE ROOFING 800 SFMAIN ROOFING SYSTEM AT PERIMETER
FLASHINGS (SEE ALSO HM32, 34, 38)
9/17/2019
Thursday, March 19, 2026 Page 2 of 9Print Date:
ROOFING SEALANT, BLACK ROOF VENTS AND PERIMETER
FLASHINGS (SEE ALSO HM34, 36, 38)
11/5/2008
TEXTURED CEILING MATERIAL THROUGHOUT HOMOGENOUS
BUILDINGS
9/20/2005
MISCELLANEOUS SEALANT MECHANICAL ROOMS AND CHASES ON
HVAC DUCTS
11/5/2008
DUCT SEALANT, GRAY MECHANICAL ROOMS AND CHASES ON
HVAC DUCTS
11/5/2008
ROOFING MATERIAL, ROOF SYSTEM EXPANSION JOINT
SEAMS
11/5/2008
MEMBRANE-TYPE ROOFING MAIN ROOFING SYSTEM AT PERIMETER
FLASHINGS (SEE ALSO HM32, 34, 38)
11/5/2008
JOINT MATERIAL WALLS THROUGHOUT 11/5/2008
12" BEIGE FLOOR TILE AND ADHESIVE THIRD FLOOR LOUNGE 7/18/2002
DUCT SEALANT, RED MECHANICAL ROOMS, PIPE CHASES 7/18/2002
PITCH POCKET TAR ROOF CONDUIT PENETRATIONS 11/5/2008
HVAC DUCT INSULATION DORM ROOMS HVAC HEAT-AC UNITS
INTERNAL INSULATION
11/5/2008
FLOOR TILE PIPE CHASE ENTRANCE 11/5/2008
CONCRETE EXPANSION JOINT MATERIAL AROUND EXTERIOR DECKING OF
HOMOGENOUS BUILDINGS
9/20/2005
EXTERIOR CAULKING, DOORS TO CHASES THROUGHOUT 9/20/2005
DUCT SEALANT, GRAY CHASES AND ATTIC/OLD ROOF DUCTS
THROUGHOUT HOMOGENOUS
BUILDINGS
9/20/2005
MISCELLANEOUS SEALANT MECHANICAL ROOMS AND CHASES AT
CABLE/ PIPE PENETRATIONS
11/5/2008
FIBROUS DEBRIS THIRD FLOOR NORTH PIPE CHASE 11/5/2008
INTERIOR CAULKING, DORM ROOMS 11/5/2008
FIBROUS DEBRIS FIRST FLOOR SOUTH PIPE CHASE 11/5/2008
MISCELLANEOUS FLOOR COVERINGS, DORM ROOMS 11/5/2008
DUCT SEALANT, BROWN MECHANICAL ROOMS AND CHASES ON
HVAC DUCTS
11/5/2008
ROOFING SEALANT, GRAY ROOF SYSTEM EXPANSION JOINT
SEAMS PATCHING (SEE ALSO HM32, 34,
36)
11/5/2008
CONCRETE EXPANSION JOINT MATERIAL EXTERIOR BRICK JOINTS 11/5/2008
TEXTURED CEILING MATERIAL OFFICES AND LIVING QUARTERS
THROUGHOUT
7/18/2002
ROOFING SEALANT, BLACK ROOFING WALK PADS 11/5/2008
VINYL THRESHOLD MATERIAL CENTER CORRIDORS AT LAUNDRY/
UTILITY
11/5/2008
ROOFING SEALANT, GRAY ROOF PARAPET WALL PATCHING (SEE
ALSO HM32, 36, 38)
11/5/2008
MUDDED FITTING(S) MECH ROOMS, PIPE CHASES 7/18/2002
Thursday, March 19, 2026 Page 3 of 9Print Date:
ACM only presents a health hazard when asbestos fibers are airborne and inhaled.
Avoid disturbance which will release fibers. The presence of asbestos does not constitute a health hazard.
HEALTH ASPECTS:
Do not disturb or cause damage to ACM. Do not sand, grind or abrade materials or cause damage with any type of equipment.
CONDITIONS TO AVOID:
CLOTH LAGGING MATERIAL THROUGHOUT THIS AND
HOMOGENOUS BUILDINGS IN CHASE
9/20/2005
TRANSITE PANEL MATERIAL NORTHWEST EXTERIOR GROUND
DEBRIS UNCOVERED DURING
RENOVATION EXCAVATIONS;
ADDITIONAL DEBRIS MAY BE PRESENT
AROUND EXTERIOR
9/5/2012
12" BLACK FLOOR TILE AND ADHESIVE CENTRAL LOUNGES 7/18/2002
12" WHITE FLOOR TILE AND ADHESIVE CENTRAL LOUNGES 7/18/2002
12" BEIGE FLOOR TILE AND ADHESIVE THROUGHOUT OFFICES, LIVING
QUARTERS, AND LOUNGES (UNDER
OTHER)
7/18/2002
2'x2' CEILING TILE, OFFICES, LOUNGES 7/18/2002
12" BEIGE FLOOR TILE AND ADHESIVE SECOND FLOOR LOUNGE (UNDER
CARPET/ TILE)
7/18/2002
12" BEIGE FLOOR TILE AND ADHESIVE THROUGHOUT OFFICES, LIVING
QUARTERS, AND LOUNGES (UNDER
OTHER)
9/21/2005
12" BEIGE FLOOR TILE AND ADHESIVE 2ND FLOOR LOUNGE (UNDER
CARPET/TILE)
11/5/2008
12" BEIGE FLOOR TILE AND ADHESIVE 3RD FLOOR LOUNGE 11/5/2008
12" BEIGE FLOOR TILE AND ADHESIVE 2ND FLOOR LOUNGE (UNDER
CARPET/TILE)
9/21/2005
12" BEIGE FLOOR TILE AND ADHESIVE 3RD FLOOR LOUNGE 9/21/2005
12" BEIGE FLOOR TILE AND ADHESIVE THROUGHOUT OFFICES, LIVING
QUARTERS, AND LOUNGES (UNDER
OTHER)
11/5/2008
ROOFING SEALANT, GRAY ROOF SYSTEM EXPANSION JOINT
SEAMS PATCHING (SEE ALSO HM32, 34,
36)
12/9/2013
ROOFING SEALANT, BLACK ROOF VENTS AND PERIMETER
FLASHINGS (SEE ALSO HM34, 36, 38)
9/5/2012
ROOFING SEALANT, GRAY ROOF PARAPET WALL PATCHING (SEE
ALSO HM32, 36, 38)
9/5/2012
MEMBRANE-TYPE ROOFING MAIN ROOFING SYSTEM AT PERIMETER
FLASHINGS (SEE ALSO HM32, 34, 38)
9/5/2012
ROOFING SEALANT, BLACK ROOF VENTS AND PERIMETER
FLASHINGS (SEE ALSO HM34, 36, 38)
12/9/2013
ROOFING SEALANT, GRAY ROOF PARAPET WALL PATCHING (SEE
ALSO HM32, 36, 38)
12/9/2013
MEMBRANE-TYPE ROOFING MAIN ROOFING SYSTEM AT PERIMETER
FLASHINGS (SEE ALSO HM32, 34, 38)
12/9/2013
ROOFING SEALANT, GRAY ROOF SYSTEM EXPANSION JOINT
SEAMS PATCHING (SEE ALSO HM32, 34,
36)
9/5/2012
Thursday, March 19, 2026 Page 4 of 9Print Date:
Do not disturb or cause damage to ACM. Do not sand, grind or abrade materials or cause damage with any type of equipment.
CONDITIONS TO AVOID:
Report any damage, dust or debris that may come from ACM or suspect ACM, or any change in the condition of materials, or accidental disturbance to the Asbestos
Program Manager.
REPORTS OF DAMAGE:
Corrective action initiated to minimize fiber release and protect personnel. RESPONSE ACTION:
ACM will be inspected periodically to evaluate any changes in condition.INSPECTION:
The Camp Lejeune Asbestos Program Manager maintains a copy of the survey for the building.
RECORDKEEPING:
CAMP LEJEUNE Asbestos Program Manager: Phone: (910) 451-5837
Thursday, March 19, 2026 Page 5 of 9Print Date:
SAMPLES COLLECTED
Sample Sample
Date
HA Sample Location Chr
Amo
Oth
Description
FC574-01-01 7/18/200201 1ST FL LOUNGE 0 0 012" BLACK FLOOR TILE
AND ADHESIVE
FC574-01-02 7/18/200201 1ST FL LOUNGE 0 0 012" BLACK FLOOR TILE
AND ADHESIVE
FC574-02-03 7/18/200202 1ST FL LOUNGE 0 0 012" WHITE FLOOR TILE
AND ADHESIVE
FC574-02-04 7/18/200202 1ST FL LOUNGE 0 0 012" WHITE FLOOR TILE
AND ADHESIVE
FC574-03-00ri05 9/21/200503 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
TYPE I
FC574-03-00ri07 11/5/200803 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
TYPE I
FC574-03-05 7/18/200203 1ST FL LOUNGE 8 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE I
FC574-03-06 7/18/200203 1ST FL LOUNGE 8 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE I
FC574-04-07 7/18/200204 1ST FL LOUNGE 0 0 02'x2' CEILING TILE, FC574-04-08 7/18/200204 1ST FL LOUNGE 0 0 02'x2' CEILING TILE, FC574-05-00ri05 9/21/200505 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
TYPE II
FC574-05-00ri07 11/5/200805 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
TYPE II
FC574-05-09 7/18/200205 2ND FL LOUNGE (UNDER
CARPET)
10 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE II
FC574-06-00ri05 9/21/200506 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC574-06-00ri07 11/5/200806 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC574-06-10 7/18/200206 3RD FL LOUNGE 10 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC574-07-11 7/18/200207 1ST FL MR 0 0 0DUCT SEALANT, RED
FC574-08-12 7/18/200208 1ST FL MR 0 0 0MUDDED FITTING(S)
FC574-08-13 7/18/200208 3RD FL MR 0 0 0MUDDED FITTING(S)
Thursday, March 19, 2026 Page 6 of 9Print Date:
HA Sample Location Chr
Amo
Oth
Description
FC574-09-14 7/18/200209 1ST FL OFFICE 0 0 0TEXTURED CEILING
MATERIAL
FC574-09-15 7/18/200209 1ST FL OFFICE 0 0 0TEXTURED CEILING
MATERIAL
FC574-10-10 9/20/200510 1ST FLOOR TOILET 0 0 0CLOTH LAGGING
MATERIAL
BLUE/ WHITE RUBBERY
FC574-11-10 9/20/200511 SW RESTROOM WALL 0 0 0EXTERIOR CAULKING, GRAY
FC574-12-10 9/20/200512 PIPE CHASE 0 0 0DUCT SEALANT, GRAY
FC574-13-10 9/20/200513 1ST FL OFFICE 0 0 0TEXTURED CEILING
MATERIAL
FC574-14-10 9/20/200514 1ST FL CENTER OFFICE 0 0 0CONCRETE EXPANSION
JOINT MATERIAL
GRAY
FC574-20-20 11/5/200820 1ST FL NORTH CHASE 0 0 0FLOOR TILE BLACK
FC574-21-20 11/5/200821 1ST FL NORTH WING, SW
ROOM
0 0 0INTERIOR CAULKING, WHITE
FC574-21-21 11/5/200821 1ST FL SOUTH WING, CNTR
ROOM
0 0 0INTERIOR CAULKING, WHITE
FC574-21-22 11/5/200821 1ST FL NORTH WING, NE
ROOM
0 0 0INTERIOR CAULKING, WHITE
FC574-22-20 11/5/200822 1ST FL SOUTH CHASE 0 0 0FIBROUS DEBRIS
FC574-23-20 11/5/200823 1ST FLOOR 0 0 0MISCELLANEOUS
FLOOR COVERINGS,
BROWN w/ADHESIVE
FC574-24-20 11/5/200824 1ST FL CNTR OFFICES 0 0 0JOINT MATERIAL
FC574-24-21 11/5/200824 1ST FL SE ROOM 0 0 0JOINT MATERIAL
FC574-24-22 11/5/200824 1ST FL NE ROOM 0 0 0JOINT MATERIAL
FC574-24-23 11/5/200824 2ND FL NW ROOM 0 0 0JOINT MATERIAL
FC574-24-24 11/5/200824 2ND FL SW ROOM 0 0 0JOINT MATERIAL
FC574-24-25 11/5/200824 2ND FL SE ROOM 0 0 0JOINT MATERIAL
FC574-24-26 11/5/200824 3RD FL CNTR OFFICE 0 0 0JOINT MATERIAL
FC574-24-27 11/5/200824 3RD FL NW ROOM 0 0 0JOINT MATERIAL
FC574-24-28 11/5/200824 3RD FL SE ROOM 0 0 0JOINT MATERIAL
Thursday, March 19, 2026 Page 7 of 9Print Date:
HA Sample Location Chr
Amo
Oth
Description
FC574-25-20 11/5/200825 1ST FL SOUTH MR 0 0 0DUCT SEALANT, BROWN
FC574-25-21 11/5/200825 2ND FL NORTH MR 0 0 0DUCT SEALANT, BROWN
FC574-26-20 11/5/200826 1ST FL SOUTH MR 0 0 0MISCELLANEOUS
SEALANT
WHITE
FC574-26-21 11/5/200826 2ND FL NORTH MR 0 0 0MISCELLANEOUS
SEALANT
WHITE
FC574-27-20 11/5/200827 1ST FL SW MR 0 0 0DUCT SEALANT, GRAY
FC574-28-20 11/5/200828 1ST FL SE ROOM 0 0 0HVAC DUCT
INSULATION
INTERNAL
FC574-29-20 11/5/200829 2ND FL UTILITY 2 0 0VINYL THRESHOLD
MATERIAL
BROWN
FC574-30-20 11/5/200830 3RD FL NORTH MR 0 0 0MISCELLANEOUS
SEALANT
GRAY
FC574-31-20 11/5/200831 3RD FL NORTH CHASE,
SOUTH
0 0 0FIBROUS DEBRIS
FC574-32-00ri12 9/5/201232 N/A 9 9 9ROOFING SEALANT, BLACK
METAL VENTS
FC574-32-00ri13 12/9/201332 N/A 9 9 9ROOFING SEALANT, BLACK
METAL VENTS
FC574-32-20 11/5/200832 NORTH STAIR ROOF
PERIMETER
0 0 0ROOFING SEALANT,
BLACK
METAL VENTS
FC574-32-21 11/5/200832 CENTER ROOF VENT 6 0 0ROOFING SEALANT,
BLACK
METAL VENTS
FC574-33-20 11/5/200833 SOUTH CENTER PAD 0 0 0ROOFING SEALANT,
BLACK
FC574-34-00ri12 9/5/201234 N/A 9 9 9ROOFING SEALANT, GRAY
FC574-34-00ri13 12/9/201334 N/A 9 9 9ROOFING SEALANT, GRAY
FC574-34-20 11/5/200834 NW PARAPET, CNTR 4 0 0ROOFING SEALANT,
GRAY
FC574-35-20 11/5/200835 FLAT ROOF,NORTH 0 0 0PITCH POCKET TAR
FC574-36-00ri12 9/5/201236 N/A 9 9 9MEMBRANE-TYPE
ROOFING
BLACK
FC574-36-00ri13 12/9/201336 N/A 9 9 9MEMBRANE-TYPE
ROOFING
BLACK
Thursday, March 19, 2026 Page 8 of 9Print Date:
HA Sample Location Chr
Amo
Oth
Description
FC574-36-20 11/5/200836 SOUTH STAIR ROOF 0 0 0MEMBRANE-TYPE
ROOFING
BLACK
FC574-36-21 11/5/200836 WEST CENTER ROOF 2 0 0MEMBRANE-TYPE
ROOFING
BLACK
FC574-36-40 9/17/201936 ATTIC, SOUTH CNTR 0 0 0MEMBRANE-TYPE
ROOFING
BLACK
FC574-37-20 11/5/200837 ROOF EAST CENTER 0 0 0ROOFING MATERIAL, BLACK
FC574-38-00ri12 9/5/201238 N/A 9 9 9ROOFING SEALANT, GRAY
FC574-38-00ri13 12/9/201338 N/A 9 9 9ROOFING SEALANT, GRAY
FC574-38-20 11/5/200838 ROOF EAST CENTER 10 0 0ROOFING SEALANT,
GRAY
FC574-39-20 11/5/200839 3RD FL WEST CNTR 0 0 0CONCRETE EXPANSION
JOINT MATERIAL
GRAY
FC574-40-00ri12 9/5/201240 N/A 9 9 9TRANSITE PANEL
MATERIAL
GRAY
Thursday, March 19, 2026 Page 9 of 9Print Date: