Amen01 FC571 ACM REPORT.pdf
PDF 284 KB Posted
- Solicitation number
- N4008526R9018
About this file
This is an Asbestos Inspection Report for Building FC571, a Bachelor Enlisted Quarters (BEQ) facility located at MCB Camp Lejeune, dated March 19, 2026. The building was constructed in 1986 and currently holds a Hazard Rank 3/Green classification as of March 2023. The report documents the identification and tracking of asbestos-containing materials (ACM) through multiple inspection cycles dating back to 2002, with the most recent survey completed in March 2023.
The building contains only non-friable ACM, with no friable materials identified. Current ACM in the structure includes: residual mastic remnants of HM01 mastic located at doorways and potential areas under new flooring throughout (1 SF, identified 12/9/2013), and roofing sealant in gray color located in the attic at the old roof perimeter and parapet flashings (2,700 SF, identified 5/18/2010 and reconfirmed 9/18/2019). Extensive historical sampling data is provided documenting materials tested as non-ACM or removed since 2002, including various floor tiles, ceiling materials, duct sealants, exterior caulking, and roofing components. The report emphasizes that intact and undisturbed ACM does not pose a significant health hazard to occupants. Building occupants are instructed to avoid disturbing ACM materials and to report any damage or debris to the Asbestos Program Manager at (910) 451-5837. Periodic inspections will continue to monitor any changes in material condition, with the Camp Lejeune Asbestos Program Manager maintaining records of the survey.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS INSPECTION REPORT of:
Building # FC571
MCB CAMP LEJEUNE
Thursday, March 19, 2026
Print Date
Thursday, March 19, 2026 Page 1 of 8Print Date:
INSPECTION SUMMARY
BLDG #:
OCCUPANT:
YEAR BUILT:
BUILDING COMMENTS:
FC571
BEQ
HAZ RANK 3/GREEN [MAR2023]
ROOFING SEALANT
MAR2023
ACM REMAINS
SEPT2019
NO CHANGES, ADDL SAMPLING
JUN2016
ACM REMAINS
DEC2013
ACM ROOFING REMAINS, ADDL SAMPLING, ACM INCLUDES:
RESIDUAL MASTIC
MAY2010
PVS. TILE AND MASTIC REPLACED, CONFIRMATIONS TEM/ PLM. ADDL FULL SAMPLING, ACM IDENTIFIED INCLUDES:
ROOFING SEALANT, GRAY
SEPT05
PVS. ACM TILE AND MASTIC REMAINS.
INSPECT JUL02- AES
HOMO GROUPING, FC525, FC555 PRIMARY FOR AREA BEQS. ACM INCLUDES:
12" BEIGE TILE AND MASTIC
ASBESTOS MANAGER: 910-451-5837
Friable ACM(s) identified
Non-friable ACM(s) identified
NOTICE: The following asbestos-containing materials have been identified in this structure. Refer to survey findings for additional information or contact the Asbestos Program Manager. Please note ACM that is intact and undisturbed is not considered a significant health hazard to building occupants.
DESCRIPTION LOCATION Date Quantity
DESCRIPTION LOCATION Date Quantity
No friable ACM records found in database
NOTIFICATION OF ACM IN BUILDING
RESIDUAL MASTIC 1 SFREMNANTS OF HM01 MASTIC AT "NEW"
DOORWAYS TO ROOMS; POTENTIAL
UNDER NEW FLOORING THROUGHOUT
12/9/2013
ROOFING SEALANT, GRAY 2,700 SFATTIC [OLD ROOF] PERIMETER
PARAPET FLASHINGS
5/18/2010
ROOFING SEALANT, GRAY 2,700 SFATTIC [OLD ROOF] PERIMETER
PARAPET FLASHINGS
9/18/2019
Thursday, March 19, 2026 Page 2 of 8Print Date:
Tested Non ACM or REMOVED Materials
DESCRIPTION LOCATION Date
RESIDUAL MASTIC 1 SFREMNANTS OF HM01 MASTIC AT "NEW"
DOORWAYS TO ROOMS; POTENTIAL
UNDER NEW FLOORING THROUGHOUT
9/18/2019
ROOFING SEALANT, GRAY 2,700 SFATTIC [OLD ROOF] PERIMETER
PARAPET FLASHINGS
12/9/2013
ROOFING SEALANT, GRAY 2,700 SFATTIC [OLD ROOF] PERIMETER
PARAPET FLASHINGS
6/9/2016
RESIDUAL MASTIC 3 SFREMNANTS OF HM01 MASTIC AT "NEW"
DOORWAYS TO ROOMS; POTENTIAL
UNDER NEW FLOORING THROUGHOUT
6/9/2016
ROOFING SEALANT, GRAY 2,700 SFATTIC [OLD ROOF] PERIMETER
PARAPET FLASHINGS
3/28/2023
RESIDUAL MASTIC 1 SFREMNANTS OF HM01 MASTIC AT "NEW"
DOORWAYS TO ROOMS; POTENTIAL
UNDER NEW FLOORING THROUGHOUT
3/28/2023
TAR PAPER, BLACK ATTIC [OLD ROOF] PERIMETER
FLASHINGS AND MEMBRANE
5/18/2010
12" BEIGE FLOOR TILE AND ADHESIVE SECOND FLOOR LOUNGE (UNDER
CARPET)
7/18/2002
TEXTURED CEILING MATERIAL OFFICES AND LIVING QUARTERS
THROUGHOUT
7/18/2002
MUDDED FITTING(S) MECHANCIAL ROOMS AND CENTER
PIPE CHASES
7/18/2002
12" BEIGE FLOOR TILE AND ADHESIVE THIRD FLOOR LOUNGE 7/18/2002
DUCT SEALANT, RED MECHANICAL ROOMS AND CENTER
PIPE CHASES
7/18/2002
12" CREAM FLOOR TILE AND ADHESIVE CENTRAL HALLWAYS 9/20/2005
EXTERIOR CAULKING, DOORS AND BRICK JOINTS 9/20/2005
DUCT SEALANT, GRAY CHASES AND ATTIC/ OLD ROOF DUCTS
THROUGHOUT
9/20/2005
BUILT-UP ROOFING ATTIC [OLD ROOF] MAIN MEMBRANE 5/18/2010
DUCT SEALANT, TAN NORTH AND SOUTH WING
MECHANICAL ROOMS HVAC DUCTS
5/18/2010
DUCT SEALANT, WHITE NORTH AND SOUTH WING
MECHANICAL ROOMS HVAC DUCTS
5/18/2010
CLOTH EXPANSION JOINT MATERIAL, THIN NORTH AND SOUTH WING
MECHANICAL ROOMS AHU UNITS
5/18/2010
DRYWALL AND JOINT MATERIAL DORM ROOM CEILINGS AT HEADS
THROUGHOUT
5/18/2010
LAGGING PAPER ON FIBERGLASS FIRST FLOOR NORTH MECHANICAL
ROOM TANK
5/18/2010
Thursday, March 19, 2026 Page 3 of 8Print Date:
ACM only presents a health hazard when asbestos fibers are airborne and inhaled.
Avoid disturbance which will release fibers. The presence of asbestos does not constitute a health hazard.
HEALTH ASPECTS:
Do not disturb or cause damage to ACM. Do not sand, grind or abrade materials or cause damage with any type of equipment.
CONDITIONS TO AVOID:
Report any damage, dust or debris that may come from ACM or suspect ACM, or any change in the condition of materials, or accidental disturbance to the Asbestos
Program Manager.
REPORTS OF DAMAGE:
Corrective action initiated to minimize fiber release and protect personnel. RESPONSE ACTION:
ACM will be inspected periodically to evaluate any changes in condition.INSPECTION:
The Camp Lejeune Asbestos Program Manager maintains a copy of the survey for the building.
RECORDKEEPING:
CAMP LEJEUNE Asbestos Program Manager: Phone: (910) 451-5837
ROOFING SEALANT, BLACK ATTIC [OLD ROOF] PERIMETER
FLASHINGS
5/18/2010
12" BEIGE FLOOR TILE AND ADHESIVE THROUGHOUT OFFICES, LIVING
QUARTERS, AND LOUNGES (HM01, 02
TILES)
7/18/2002
12" BLACK FLOOR TILE AND ADHESIVE CENTRAL LOUNGES 7/18/2002
12" WHITE FLOOR TILE AND ADHESIVE CENTRAL LOUNGES 7/18/2002
2'x2' CEILING TILE, OFFICES AND CENTRAL LOUNGES 7/18/2002
TAR PAPER, BLACK ATTIC [OLD ROOF] PERIMETER
FLASHINGS AND MEMBRANE
9/18/2019
TEXTURED CEILING MATERIAL OFFICES AND LIVING QUARTERS
THROUGHOUT
9/20/2005
TEXTURED CEILING MATERIAL OFFICES AND LIVING QUARTERS
THROUGHOUT
5/18/2010
EXTERIOR CAULKING, DOORS AND BRICK JOINTS 5/18/2010
DUCT SEALANT, GRAY CHASES AND ATTIC/ OLD ROOF DUCTS
THROUGHOUT
5/18/2010
12" BEIGE FLOOR TILE AND ADHESIVE REPLACED HM03 PRIMARY TILE
THROUGHOUT OFFICES, LIVING
QUARTERS, AND LOUNGES (HM01. 02
TILES)
5/18/2010
Thursday, March 19, 2026 Page 4 of 8Print Date:
SAMPLES COLLECTED
Sample Sample
Date
HA Sample Location Chr
Amo
Oth
Description
FC525-01-01 7/18/200201 1ST FL LOUNGE FC525 0 0 012" BLACK FLOOR TILE
AND ADHESIVE
FC525-01-02 7/18/200201 1ST FL LOUNGE FC525 0 0 012" BLACK FLOOR TILE
AND ADHESIVE
FC525-02-03 7/18/200202 1ST FL LOUNGE FC525 0 0 012" WHITE FLOOR TILE
AND ADHESIVE
FC525-02-04 7/18/200202 1ST FL LOUNGE FC525 0 0 012" WHITE FLOOR TILE
AND ADHESIVE
FC525-03-05 7/18/200203 1ST FL LOUNGE FC525 8 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE I
FC525-03-06 7/18/200203 1ST FL LOUNGE FC525 8 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE I
FC571-03-00RI05 9/20/200503 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
TYPE I
FC525-04-07 7/18/200204 1ST FL LOUNGE FC525 0 0 02'x2' CEILING TILE, FC525-04-08 7/18/200204 1ST FL LOUNGE FC525 0 0 02'x2' CEILING TILE, FC525-05-09 7/18/200205 2ND FL LOUNGE FC525 10 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE II
FC571-05-00RI05 9/20/200505 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
TYPE II
FC525-06-10 7/18/200206 3RD FL LOUNGE FC525 10 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC571-06-00RI05 9/20/200506 N/A 9 9 912" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC571-06-20 5/18/201006 1ST FL SOUTH, SE ROOM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC571-06-20tem 5/18/201006 1ST FL SOUTH, SE ROOM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC571-06-21 5/18/201006 1ST FL NORTH, NW ROOM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC571-06-22 5/18/201006 2ND FL NORTH, NE ROOM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC571-06-22tem 5/18/201006 2ND FL NORTH, NE ROOM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC571-06-23 5/18/201006 2ND FL SOUTH, SW ROOM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
Thursday, March 19, 2026 Page 5 of 8Print Date:
HA Sample Location Chr
Amo
Oth
Description
FC571-06-24 5/18/201006 3RD FL SOUTH, SE ROOM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC571-06-24tem 5/18/201006 3RD FL SOUTH, SE ROOM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC571-06-25 5/18/201006 3RD FL NORTH, NW ROOM 0 0 012" BEIGE FLOOR TILE
AND ADHESIVE
TYPE III
FC525-07-11 7/18/200207 1ST FL MECH ROOM FC525 0 0 0DUCT SEALANT, RED
FC525-08-12 7/18/200208 1ST FL MECH ROOM FC525 0 0 0MUDDED FITTING(S)
FC525-08-13 7/18/200208 3RD FL MECH ROOM FC525 0 0 0MUDDED FITTING(S)
FC525-09-14 7/18/200209 1ST FL OFFICE 0 0 0TEXTURED CEILING
MATERIAL
FC525-09-15 7/18/200209 1ST FL OFFICE 0 0 0TEXTURED CEILING
MATERIAL
FC571-09-1110 9/20/200509 1ST FL LAUNDRY 0 0 0TEXTURED CEILING
MATERIAL
FC571-09-1310 9/20/200509 2ND FL WEST CNTR RM 0 0 0TEXTURED CEILING
MATERIAL
FC571-09-20 5/18/201009 1ST FL SOUTH, SE ROOM 0 0 0TEXTURED CEILING
MATERIAL
FC571-09-21 5/18/201009 1ST FL NORTH, NW ROOM 0 0 0TEXTURED CEILING
MATERIAL
FC571-09-22 5/18/201009 2ND FL NORTH, NE ROOM 0 0 0TEXTURED CEILING
MATERIAL
FC571-09-23 5/18/201009 2ND FL SOUTH, SW ROOM 0 0 0TEXTURED CEILING
MATERIAL
FC571-09-24 5/18/201009 3RD FL SOUTH, SE ROOM 0 0 0TEXTURED CEILING
MATERIAL
FC571-09-25 5/18/201009 3RD FL NORTH, NW ROOM 0 0 0TEXTURED CEILING
MATERIAL
FC525-10-10 9/20/200510 1ST FL CNTR HALL 0 0 012" CREAM FLOOR TILE
AND ADHESIVE
FC555-11-10 9/20/200511 DOORS 0 0 0EXTERIOR CAULKING, GRAY
FC571-11-20 5/18/201011 2ND FL SOUTH, EAST MR
DOOR
0 0 0EXTERIOR CAULKING, GRAY
FC571-11-21 5/18/201011 2ND FL EAST CNTR BRICK
JOINT
0 0 0EXTERIOR CAULKING, GRAY
Thursday, March 19, 2026 Page 6 of 8Print Date:
HA Sample Location Chr
Amo
Oth
Description
FC571-11-22 5/18/201011 3RD FL EAST CNTR BRICK
JOINT
0 0 0EXTERIOR CAULKING, GRAY
FC571-12-10 9/20/200512 PIPE CHASE 0 0 0DUCT SEALANT, GRAY
FC571-12-20 5/18/201012 2ND FL SOUTH CHASE,
SOUTH
0 0 0DUCT SEALANT, GRAY
FC571-12-21 5/18/201012 3RD FL NORTH CHASE,
NORTH
0 0 0DUCT SEALANT, GRAY
FC571-20-20 5/18/201020 1ST FL SOUTH MECH RM 0 0 0DUCT SEALANT, TAN
FC571-20-21 5/18/201020 3RD FL NORTH MECH RM 0 0 0DUCT SEALANT, TAN
FC571-21-20 5/18/201021 1ST FL SOUTH MECH RM 0 0 0DUCT SEALANT, WHITE
FC571-21-21 5/18/201021 3RD FL NORTH MECH RM 0 0 0DUCT SEALANT, WHITE
FC571-22-20 5/18/201022 1ST FL SOUTH MECH RM 0 0 0CLOTH EXPANSION
JOINT MATERIAL, THIN
BLACK
FC571-22-21 5/18/201022 3RD FL NORTH MECH RM 0 0 0CLOTH EXPANSION
JOINT MATERIAL, THIN
BLACK
FC571-23-20 5/18/201023 1ST FL SOUTH, SE ROOM 0 0 0DRYWALL AND JOINT
MATERIAL
FC571-23-21 5/18/201023 1ST FL NORTH, NW ROOM 0 0 0DRYWALL AND JOINT
MATERIAL
FC571-23-22 5/18/201023 2ND FL NORTH, NE ROOM 0 0 0DRYWALL AND JOINT
MATERIAL
FC571-23-23 5/18/201023 2ND FL SOUTH, SW ROOM 0 0 0DRYWALL AND JOINT
MATERIAL
FC571-23-24 5/18/201023 3RD FL SOUTH, SE ROOM 0 0 0DRYWALL AND JOINT
MATERIAL
FC571-23-25 5/18/201023 3RD FL NORTH, NW ROOM 0 0 0DRYWALL AND JOINT
MATERIAL
FC571-24-20 5/18/201024 1ST FL NORTH MECH ROOM 0 0 0LAGGING PAPER ON
FIBERGLASS
FC571-25-00ri13 12/9/201325 N/A 9 9 9ROOFING SEALANT, GRAY
FC571-25-00ri16 6/9/201625 N/A 9 9 9ROOFING SEALANT, GRAY
FC571-25-00ri19 9/18/201925 N/A 9 9 9ROOFING SEALANT, GRAY
Thursday, March 19, 2026 Page 7 of 8Print Date:
HA Sample Location Chr
Amo
Oth
Description
FC571-25-00ri23 3/28/202325 N/A 9 9 9ROOFING SEALANT, GRAY
FC571-25-20 5/18/201025 ATTIC/ ROOF, NORTH CNTR 0 0 0ROOFING SEALANT,
GRAY
FC571-25-21 5/18/201025 ATTIC/ ROOF, SOUTH CNTR 5 0 0ROOFING SEALANT,
GRAY
FC571-26-20 5/18/201026 ATTIC/ ROOF, NORTH CNTR 0 0 0ROOFING SEALANT,
BLACK
FC571-26-21 5/18/201026 ATTIC/ ROOF, SOUTH CNTR 0 0 0ROOFING SEALANT,
BLACK
FC571-27-20 5/18/201027 ATTIC/ ROOF, NORTH CNTR 0 0 0TAR PAPER, BLACK
FC571-27-21 5/18/201027 ATTIC/ ROOF, SOUTH CNTR 0 0 0TAR PAPER, BLACK
FC571-27-40 9/18/201927 ATTIC, NO. CNTR
UNDERLAYMENT
0 0 0TAR PAPER, BLACK
FC571-28-20 5/18/201028 ATTIC/ ROOF, NORTH CNTR 0 0 0BUILT-UP ROOFING BLACK
FC571-28-21 5/18/201028 ATTIC/ ROOF, SOUTH CNTR 0 0 0BUILT-UP ROOFING BLACK
FC571-30-00ri16 6/9/201630 N/A 9 9 9RESIDUAL MASTIC BLACK
FC571-30-00ri19 9/18/201930 N/A; 2ND FL NE 9 9 9RESIDUAL MASTIC BLACK
FC571-30-00ri23 3/28/202330 N/A 9 9 9RESIDUAL MASTIC BLACK
FC571-30-30 12/9/201330 2ND FL, NE ROOM DOORWAY 2 0 0RESIDUAL MASTIC BLACK
FC571-30-40 9/18/201930 2ND FL, NO. EAST CNTR 0 0 0RESIDUAL MASTIC BLACK
FC571-30-41 9/18/201930 3RD FL, SO. WEST CNTR 0 0 0RESIDUAL MASTIC BLACK
Thursday, March 19, 2026 Page 8 of 8Print Date:
File details come from the government source that posted it. Updated .