This is an Asbestos Inspection Report for Building FC520 at MCB Camp Lejeune, dated March 19, 2026. The building, constructed in 1978 and occupied by Ammo Co. 2nd Supply Battalion, has been assigned a Hazard Rank of 3/GREEN as of March 2023. The report documents the presence of one non-friable asbestos-containing material (ACM): tar sealant (3 square feet) located through floor fire pipe penetrations in the north wing mechanical rooms, identified on July 7, 2009. No friable ACM has been recorded in the database. The building's inspection history spans from 2002 through 2023, with multiple sampling events confirming various materials tested as non-ACM or removed, including roofing sealants, floor tiles and adhesives, ceiling materials, duct sealants, and other construction materials.

The report indicates that ACM intact and undisturbed does not present a significant health hazard to building occupants. Building personnel are instructed to avoid disturbance of ACM materials and to report any damage, dust, or debris to the Asbestos Program Manager at 910-451-5837. The Camp Lejeune Asbestos Program Manager maintains custody of the complete survey and will conduct periodic inspections to evaluate any changes in material condition. Corrective action protocols are in place to minimize fiber release and protect personnel in the event of accidental disturbance or damage to identified ACM materials.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ASBESTOS INSPECTION REPORT of:

Building # FC520

MCB CAMP LEJEUNE

Thursday, March 19, 2026

Print Date

Thursday, March 19, 2026 Page 1 of 9Print Date:

INSPECTION SUMMARY

BLDG #:

OCCUPANT:

YEAR BUILT:

BUILDING COMMENTS:

FC520

AMMO CO. 2ND SUPPLY

BATTALION

HAZ RANK 3/GREEN [MAR2023]

ACM ROOFING SEALANTS

MAR2023

ACM REMAINS

SEPT2019

ADDL SAMPLING, ACM ROOF SEALANT ID'D (RESIDUAL)

JUN2016

MAJOR RENOVATIONS; NO KNOWN ACM ID'D

DEC2013

ACM FLOORING AND ROOFING MATERIALS REMAIN, BUILDING SCHEDULED FOR MAJOR RENOVATIONS 2014

MAY2010

PVS. ACM REMAINS, NO CHANGES, ERRORS w/SIGNAGE

JUL09

ACM TILE AND MASTIC CONFIRMED TEM, ADDL SAMPLING, ACM INCLUDES:

FLOOR TILE AND MASTIC

FLOOR TILE AND MASTIC DEBRIS

RESIDUAL TILE MASTIC

LIGHT FIXTURE HEAT SHIELDING

TAR SEALANT AT PIPES

ROOFING SEALANT, GRAY (PATCHING)

SEP05:

PVS. ACM TILE AND MASTIC REMAIN, ADDL ACM TILE IDENTIFIED, DATA FROM FC525 USED.

AES2002

FC BARRACKS INSPECTED AS HOMOGENOUS GROUP. BUILDING MATERIALS COMMON. FC525/ 555 PRIMARY DATA USED.

ASBESTOS MANAGER: 910-451-5837

Friable ACM(s) identified

Non-friable ACM(s) identified

NOTICE: The following asbestos-containing materials have been identified in this structure. Refer to survey findings for additional information or contact the Asbestos Program Manager. Please note ACM that is intact and undisturbed is not considered a significant health hazard to building occupants.

DESCRIPTION LOCATION Date Quantity

DESCRIPTION LOCATION Date Quantity

No friable ACM records found in database

NOTIFICATION OF ACM IN BUILDING

TAR SEALANT 3 SFTHROUGH FLOOR FIRE PIPE

PENETRATIONS, NORTH WING

MECHANICAL ROOMS

7/7/2009

Thursday, March 19, 2026 Page 2 of 9Print Date:

Tested Non ACM or REMOVED Materials

DESCRIPTION LOCATION Date

ROOFING SEALANT, BLACK ROOFING SYSTEM VENT, ACCESS

HATCH, CENTER EXPANSION JOINT,

AND PERIMETER FLASHINGS

7/7/2009

ROOFING SEALANT, BLACK 380 SFROOFING SYSTEM CENTER LINE VENTS;

CENTER EXPANSION JOINT, AND

PERIMETER FLASHINGS

9/17/2019

TAR SEALANT 3 SFTHROUGH FLOOR FIRE PIPE

PENETRATIONS, NORTH WING

MECHANICAL ROOMS

5/25/2010

TAR SEALANT 3 SFTHROUGH FLOOR FIRE PIPE

PENETRATIONS, NORTH WING

MECHANICAL ROOMS

12/2/2013

ROOFING SEALANT, BLACK 380 SFROOFING SYSTEM CENTER LINE VENTS;

CENTER EXPANSION JOINT, AND

PERIMETER FLASHINGS

3/28/2023

TAR SEALANT 3 SFTHROUGH FLOOR FIRE PIPE

PENETRATIONS, NORTH WING

MECHANICAL ROOMS

3/28/2023

JOINT MATERIAL DORM ROOM BATH AREA CEILINGS

(SEE ALSO HM21)

7/7/2009

DRYWALL AND JOINT MATERIAL LOUNGES, OFFICES, DORM ROOMS AT

BATHROOM AREAS (WALLS AND

CEILINGS)

7/7/2009

BROWN VINYL BASE AND ADHESIVE, 4" THROUGHOUT BUILDING (ASSOCIATED

w/HM02, 03, 23 TILES)

7/7/2009

12" WHITE FLOOR TILE AND ADHESIVE CENTRAL LOUNGE AREAS 7/18/2002

12" BEIGE FLOOR TILE AND ADHESIVE PRIMARY TILE IN OFFICES, LOUNGES,

AND LIVING QUARTERS THROUGHOUT

7/18/2002

GASKET MATERIAL CENTRAL PIPE CHASES THROUGHOUT

(FLANGES)

9/20/2005

12" BLACK FLOOR TILE AND ADHESIVE CENTRAL LOUNGE AREAS 7/18/2002

FIBERGLASS INSULATION SEALANT MECHANICAL ROOMS AND PIPE

CHASES THROUGHOUT

7/18/2002

MUDDED FITTING(S) MECHANICAL ROOMS 7/15/2002

TEXTURED CEILING MATERIAL OFFICES AND LIVING QUARTERS

THROUGHOUT (ON CONCRETE)

7/18/2002

CONCRETE EXPANSION JOINT MATERIAL EXTERIOR PERIMETER CONCRETE

SLABS

9/20/2005

FLOOR LEVELING COMPOUND PATCHES AT [REMOVED] SHOWERS IN

MECHANCIAL ROOMS

7/7/2009

BUILT-UP ROOFING NORTH ROOF CENTER 7/7/2009

2'x2' CEILING TILE, CENTRAL LOUNGE AND COMMON

AREAS

7/18/2002

Thursday, March 19, 2026 Page 3 of 9Print Date:

CLOTH LAGGING MATERIAL THROUGHOUT BUILDING IN CENTRAL

PIPE CHASES

9/20/2005

12" Off WHITE w/ BEIGE FLOOR TILE AND

ADHESIVE

MIXED USE w/HM03 TILE THROUGHOUT

(PRIMARY FLOOR COVERING)

7/7/2009

LIGHT FIXTURE HEAT SHIELD CENTRAL JANITORS CLOSETS, THREE

FLOORS

7/7/2009

EXTERIOR CAULKING, DOORS TO CHASES THROUGHOUT 9/20/2005

DUCT SEALANT, GRAY CHASES AND ATTIC/ OLD ROOF DUCTS

THROUGHOUT

9/20/2005

ROOFING MATERIAL, BUCKET OF REPAIR TARS ON ROOF,

NORTH CENTER

7/7/2009

FLOOR TILE DEBRIS THIRD FLOOR SOUTH MECHANCIAL

(pvs. HM03/23 AREAS)

7/7/2009

DUCT SEALANT, RED MECHANICAL ROOMS AND CENTRAL

PIPE CHASES

7/7/2009

ROOFING SEALANT, GRAY ROOFING SYSTEM VENT, ACCESS

HATCH, CENTER EXPANSION JOINT

PATCHINGS

7/7/2009

EXTERIOR CAULKING, ROOFING SYSTEM PARAPET WALL CAP

METAL FLASHING JOINTS

7/7/2009

RESIDUAL MASTIC THIRD FLOOR SOUTH MECHANCIAL

(pvs. HM03/23 AREAS)

7/7/2009

EXTERIOR CAULKING, ROOF, CENTER MOUNTED A/C UNITS 5/25/2010

12" WHITE FLOOR TILE AND ADHESIVE CENTRAL LOUNGE AND OFFICE AEAS

(PATCHING)

7/7/2009

EXTERIOR CAULKING, ROOFING SYSTEM PARAPET WALL CAP

METAL FLASHING JOINTS

5/25/2010

ROOFING SEALANT, GRAY ROOFING SYSTEM VENT, ACCESS

HATCH, CENTER EXPANSION JOINT

PATCHINGS

5/25/2010

DUCT SEALANT, GRAY CHASES AND ATTIC/ OLD ROOF DUCTS

THROUGHOUT

7/7/2009

12" BEIGE FLOOR TILE AND ADHESIVE PRIMARY TILE IN OFFICES, LOUNGES,

AND LIVING QUARTERS THROUGHOUT

9/20/2005

12" BEIGE FLOOR TILE AND ADHESIVE PRIMARY TILE IN OFFICES, LOUNGES,

AND LIVING QUARTERS THROUGHOUT

(MIXED w/HM23)

7/7/2009

12" BEIGE FLOOR TILE AND ADHESIVE PRIMARY TILE IN OFFICES, LOUNGES,

AND LIVING QUARTERS THROUGHOUT

5/25/2010

RESIDUAL MASTIC THIRD FLOOR SOUTH MECHANCIAL

(pvs. HM02/03/23 AREAS)

5/25/2010

FLOOR TILE DEBRIS THIRD FLOOR SOUTH MECHANCIAL

(pvs. HM03/23 AREAS)

5/25/2010

12" Off WHITE w/ BEIGE FLOOR TILE AND

ADHESIVE

MIXED USE w/HM03 TILE THROUGHOUT

(PRIMARY FLOOR COVERING)

5/25/2010

LIGHT FIXTURE HEAT SHIELD CENTRAL JANITORS CLOSETS, THREE

FLOORS

5/25/2010

12" WHITE FLOOR TILE AND ADHESIVE CENTRAL LOUNGE AREAS 5/25/2010

Thursday, March 19, 2026 Page 4 of 9Print Date:

ACM only presents a health hazard when asbestos fibers are airborne and inhaled.

Avoid disturbance which will release fibers. The presence of asbestos does not constitute a health hazard.

HEALTH ASPECTS:

Do not disturb or cause damage to ACM. Do not sand, grind or abrade materials or cause damage with any type of equipment.

CONDITIONS TO AVOID:

Report any damage, dust or debris that may come from ACM or suspect ACM, or any change in the condition of materials, or accidental disturbance to the Asbestos

Program Manager.

REPORTS OF DAMAGE:

Corrective action initiated to minimize fiber release and protect personnel. RESPONSE ACTION:

ACM will be inspected periodically to evaluate any changes in condition.INSPECTION:

The Camp Lejeune Asbestos Program Manager maintains a copy of the survey for the building.

RECORDKEEPING:

CAMP LEJEUNE Asbestos Program Manager: Phone: (910) 451-5837

RESIDUAL MASTIC THIRD FLOOR SOUTH MECHANCIAL

(pvs. HM03/23 AREAS)

12/2/2013

FLOOR TILE DEBRIS THIRD FLOOR SOUTH MECHANCIAL

(pvs. HM03/23 AREAS)

12/2/2013

ROOFING SEALANT, GRAY ROOFING SYSTEM VENT, ACCESS

HATCH, CENTER EXPANSION JOINT

PATCHINGS

12/2/2013

12" BEIGE FLOOR TILE AND ADHESIVE PRIMARY TILE IN OFFICES, LOUNGES,

AND LIVING QUARTERS THROUGHOUT

12/2/2013

12" Off WHITE w/ BEIGE FLOOR TILE AND

ADHESIVE

MIXED USE w/HM03 TILE THROUGHOUT

(PRIMARY FLOOR COVERING)

12/2/2013

LIGHT FIXTURE HEAT SHIELD CENTRAL JANITORS CLOSETS, THREE

FLOORS

6/22/2011

LIGHT FIXTURE HEAT SHIELD CENTRAL JANITORS CLOSETS, THREE

FLOORS

12/2/2013

Thursday, March 19, 2026 Page 5 of 9Print Date:

SAMPLES COLLECTED

Sample Sample

Date

HA Sample Location Chr

Amo

Oth

Description

FC520-01-01 7/18/200201 1ST FL CNTR LOUNGE 0 0 012" BLACK FLOOR TILE

AND ADHESIVE

FC520-02-00ri09 5/25/201002 N/A 9 9 912" WHITE FLOOR TILE

AND ADHESIVE

FC520-02-02 7/18/200202 1ST FL CNTR LOUNGE 0 0 012" WHITE FLOOR TILE

AND ADHESIVE

FC520-02-20 7/7/200902 1ST FL NORTH WING, SW

OFFICE

5 0 012" WHITE FLOOR TILE

AND ADHESIVE

FC520-02-21 7/7/200902 2ND FL NORTH WING, WEST

CNTR RM223

2 0 012" WHITE FLOOR TILE

AND ADHESIVE

FC520-03-00ri05 9/20/200503 N/A 9 9 912" BEIGE FLOOR TILE

AND ADHESIVE

FC520-03-00ri09 5/25/201003 N/A 9 9 912" BEIGE FLOOR TILE

AND ADHESIVE

FC520-03-00ri13 12/2/201303 N/A 9 9 912" BEIGE FLOOR TILE

AND ADHESIVE

FC520-03-03 7/18/200203 1ST FL CNTR LOUNGE

(BOTTOM LAYER)

5 0 012" BEIGE FLOOR TILE

AND ADHESIVE

FC520-03-07 7/18/200203 3RD FL CNTR LOUNGE 5 0 012" BEIGE FLOOR TILE

AND ADHESIVE

FC520-03-20 7/7/200903 1ST FL RM 110 2 0 012" BEIGE FLOOR TILE

AND ADHESIVE

FC520-03-20tem 7/7/200903 1ST FL RM 110 18 0 012" BEIGE FLOOR TILE

AND ADHESIVE

FC520-04-04 7/18/200204 1ST FL CNTR LOUNGE 0 0 02'x2' CEILING TILE, FC520-05-05 7/18/200205 3RD FL LOUNGE/ OFFICE 0 0 0TEXTURED CEILING

MATERIAL

FC520-06-06 7/18/200206 1ST FL NORTH, EAST CNTR

MR

0 0 0FIBERGLASS

INSULATION SEALANT

WHITE

FC520-FC525-0812 7/18/200208 FC525 1ST FL MR 0 0 0MUDDED FITTING(S)

FC520-FC525-0813 7/18/200208 FC525 RD FL MR 0 0 0MUDDED FITTING(S)

FC520-FC555-1010 9/20/200510 FC555 1ST FL 0 0 0CLOTH LAGGING

MATERIAL

BLUE/WHITE RUBBERY

FC520-FC555-1110 9/20/200511 FC555 SOUTH 0 0 0EXTERIOR CAULKING, GRAY

Thursday, March 19, 2026 Page 6 of 9Print Date:

HA Sample Location Chr

Amo

Oth

Description

FC520-12-20 7/7/200912 1ST FL NORTH CHASE,

SOUTH END

0 0 0DUCT SEALANT, GRAY

FC520-FC555-1210 9/20/200512 FC555 CHASE 0 0 0DUCT SEALANT, GRAY

FC520-FC555-1310 9/20/200513 FC555 1ST FL OFFICE 0 0 0GASKET MATERIAL

FC520-14-10 9/20/200514 ROOM 216, BUILDING 565 0 0 0CONCRETE EXPANSION

JOINT MATERIAL

GRAY

FC520-FC555-1410 9/20/200514 FC555 EXTERIOR 0 0 0CONCRETE EXPANSION

JOINT MATERIAL

GRAY

FC520-20-20 7/7/200920 1ST FL LOUNGE WALL, EAST 0 0 0DRYWALL AND JOINT

MATERIAL

FC520-20-21 7/7/200920 1ST FL NORTH WING, SW

OFFICE WALL

0 0 0DRYWALL AND JOINT

MATERIAL

FC520-20-22 7/7/200920 2ND FL NORTH WING, WEST

CNTR RM 223 WALL

0 0 0DRYWALL AND JOINT

MATERIAL

FC520-20-23 7/7/200920 3RD FL NORTH WING, WEST

CNTR RM 327 WALL

0 0 0DRYWALL AND JOINT

MATERIAL

FC520-20-24 7/7/200920 3RD FL SOUTH WING, SE RM

302 CEILING

0 0 0DRYWALL AND JOINT

MATERIAL

FC520-21-20 7/7/200921 1ST FL SOUTH WING, NE RM

0 0 0JOINT MATERIAL

FC520-21-21 7/7/200921 2ND FL SOUTH WING, NE RM

0 0 0JOINT MATERIAL

FC520-22-20 7/7/200922 1ST FL SOUTH WING, NE RM

0 0 0BROWN VINYL BASE

AND ADHESIVE, 4"

FC520-23-00ri09 5/25/201023 N/A 9 9 912" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

FC520-23-00ri13 12/2/201323 N/A 9 9 912" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

FC520-23-20 7/7/200923 1ST FL NORTH WING, SE

OFFICE

2 0 012" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

FC520-23-20tem 7/7/200923 1ST FL NORTH WING, SE

OFFICE

12 0 012" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

FC520-23-21 7/7/200923 2ND FL SOUTH WING, NE RM

3 0 012" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

Thursday, March 19, 2026 Page 7 of 9Print Date:

HA Sample Location Chr

Amo

Oth

Description

FC520-23-22 7/7/200923 2ND FL NORTH WING, WEST

CNTR RM 223

2 0 012" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

FC520-23-23 7/7/200923 3RD FL NORTH WING, NW RM

2 0 012" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

FC520-23-24 7/7/200923 3RD FL SOUTH WING, SE RM

2 0 012" Off WHITE w/ BEIGE

FLOOR TILE AND

ADHESIVE

FC520-24-00ri09 5/25/201024 N/A 19 19 19LIGHT FIXTURE HEAT

SHIELD

SILVER on WHITE

FC520-24-00ri11 6/22/201124 N/A 9 9 9LIGHT FIXTURE HEAT

SHIELD

SILVER on WHITE

FC520-24-00ri13 12/2/201324 N/A 9 9 9LIGHT FIXTURE HEAT

SHIELD

SILVER on WHITE

FC520-24-20 7/7/200924 2ND FL CNTR JANITOR CL. 60 0 0LIGHT FIXTURE HEAT

SHIELD

SILVER on WHITE

FC520-24-21 7/7/200924 3RD FL CNTR JANITOR CL. 55 0 0LIGHT FIXTURE HEAT

SHIELD

SILVER on WHITE

FC520-25-00ri09 5/25/201025 N/A 9 9 9RESIDUAL MASTIC BLACK

FC520-25-20 7/7/200925 3RD FL SOUTH MR 5 0 0RESIDUAL MASTIC BLACK

FC5820-25-00ri13 12/2/201325 N/A 9 9 9RESIDUAL MASTIC BLACK

FC520-26-00ri09 5/25/201026 N/A 9 9 9FLOOR TILE DEBRIS BEIGE

FC520-26-00ri13 12/2/201326 N/A 9 9 9FLOOR TILE DEBRIS BEIGE

FC520-26-20 7/7/200926 3RD FL SOUTH MR 2 0 0FLOOR TILE DEBRIS BEIGE

FC520-27-20 7/7/200927 3RD FL SOUTH MR 0 0 0DUCT SEALANT, RED

FC520-27-21 7/7/200927 3RD FL SOUTH CHASE, CNTR 0 0 0DUCT SEALANT, RED

FC520-28-00ri13 12/2/201328 N/A 9 9 9ROOFING SEALANT, GRAY

FC520-28-20 7/7/200928 ROOF, SOUTH HATCH 0 0 0ROOFING SEALANT,

GRAY

FC520-28-21 7/7/200928 SOUTH ROOF, NORTH (OLD)

HVAC BOX

8 0 0ROOFING SEALANT,

GRAY

FC520-28-22 7/7/200928 ROOF EXPANSION JOINT,

CNTR

8 0 0ROOFING SEALANT,

GRAY

Thursday, March 19, 2026 Page 8 of 9Print Date:

HA Sample Location Chr

Amo

Oth

Description

FC520-28-23 7/7/200928 NORTH ROOF, NORTH CNTR

VENT

8 0 0ROOFING SEALANT,

GRAY

FC520-28-30 5/25/201028 ROOF, SOUTH CNTR

STAIRWELL

4 0 0ROOFING SEALANT,

GRAY

FC520-28-31 5/25/201028 ROOF, NORTH CNTR

PERIMETER

0 0 0ROOFING SEALANT,

GRAY

FC520-29-00ri23 3/28/202329 N/A 9 9 9ROOFING SEALANT, BLACK

FC520-29-20 7/7/200929 SOUTH ROOF, SW PERIMETER 0 0 0ROOFING SEALANT,

BLACK

FC520-29-21 7/7/200929 ROOF, CNTR EXPANSION

JOINT

0 0 0ROOFING SEALANT,

BLACK

FC520-29-22 7/7/200929 NORTH ROOF, NE PERIMETER 0 0 0ROOFING SEALANT,

BLACK

FC520-29-50 9/17/201929 ROOF, SOUTH CNTR VENT 3 0 0ROOFING SEALANT,

BLACK

FC520-30-20 7/7/200930 SOUTH ROOF, SOUTH CNTR 0 0 0EXTERIOR CAULKING, WHITE

FC520-30-30 5/25/201030 ROOF, CNTR NORTH A/C UNIT 0 0 0EXTERIOR CAULKING, WHITE

FC520-31-20 7/7/200931 ROOF, NORTH CNTR 0 0 0BUILT-UP ROOFING DEBRIS

FC520-32-20 7/7/200932 ROOF, NORTH CNTR 0 0 0ROOFING MATERIAL, TAR

FC520-33-20 7/7/200933 3RD FL NORTH MR 0 0 0FLOOR LEVELING

COMPOUND

GRAY

FC520-33-21 7/7/200933 2ND FL NORTH MR 0 0 0FLOOR LEVELING

COMPOUND

GRAY

FC520-34-00ri09 5/25/201034 N/A 9 9 9TAR SEALANT BLACK

FC520-34-00ri13 12/2/201334 N/A 9 9 9TAR SEALANT BLACK

FC520-34-00ri23 3/28/202334 N/A 9 9 9TAR SEALANT BLACK

FC520-34-20 7/7/200934 1ST FL NORTH MR 3 0 0TAR SEALANT BLACK

FC520-40-30 5/25/201040 ROOF, CNTR NORTH A/C UNIT 0 0 0EXTERIOR CAULKING, TAN

Thursday, March 19, 2026 Page 9 of 9Print Date: