The amendment adds security references including ICD/ICS 705 Ver 1.5.1, ICS 705-1, ICS 705-02, CNASSAM TEMPEST/1-13, DoDM 5200.01-V3, SECNAVINST 5510.36B, UFC 4-010-05 CH-1, and DODM 5205.07-V3 to the applicable codes and standards section. Cybersecurity requirements are updated to specify control system criticality levels: Mechanical/DDC systems and ESS (Energy Storage Systems) at Mission Support L-L-L criticality, FLS (Fire Life and Safety) as None, and Electrical systems at Mission Support L-L-L criticality, with contractors required to provide deliverables per UFC 4-010-06 and UFGS 25 05 11 including a hygiene checklist. The demolition scope is significantly modified, changing from salvaging existing linear supply diffusers and return air grilles for reinstallation to complete demolition of VAV-35W and VAV-34E low pressure supply ductwork from boxes including supports and linear supply diffusers in multiple areas (Charts W226 and E226, and Shared Controlled Area Space E227). Additionally, the amendment adds four required documents: NAS Building 145 As-Built Drawings in pdf, NAS Building 145 Fire Alarm As-Built in pdf, NAS Building 145 Fire Alarm Shop Drawings, and NAS Building 145 Fire Pump Test Full Report in pdf. Unit pricing for ESS will be issued separately as Amendment 0002.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 145 – CONVERT INTEL SPACES TO CONTROLLED AREA
NAS Oceana, Virginia Beach VA
Amendment 0001
07 JUNE 2026
1) In PART 3, 2.1 APPLICABLE CODES AND STANDARDS: Page 2:
Add the following:
“SECURITY REFERENCES
ICD/ICS 705 Ver 1.5.1
ICS 705-1
ICS 705-02
CNASSAM TEMPEST/1-13
DoDM 5200.01-V3
SECNAVINST 5510.36B
UFC 4-010-05 CH-1
DODM 5205.07-V3”
2) In PART 3, 2.1 2.4 CYBERSECURITY: Page 2:
Add the following:
CRITICALITY OF CONTROL SYSTEM TYPE
Mechanical/DDC: Mission Support: L-L-L FLS (Fire Life and Safety): None ESS: Mission Support: L-L-L Electrical (Transformer/Lighting): Mission Support: L-L-L
The Contractor provides deliverables as defined in UFC 4-010-06 and UFGS 25 05 11 including hygiene checklist.
3) In PART 3, D3040 DISTRIBUTION SYSTEMS AND D3050 TERMINAL &
PACKAGED UNITS, DEMOLITION: Page 16:
Delete the following:
CHART W226 - Remove and save in undamaged condition existing linear supply diffuser for reinstallation in new ceiling. Remove and save in undamaged condition existing return air grille for reinstallation in new ceiling.
Add the following:
Demolish VAV-35W low pressure supply ductwork from box complete including supports and linear supply diffuser.
BUILDING 145 – CONVERT INTEL SPACES TO CONTROLLED AREA
NAS Oceana, Virginia Beach VA
Amendment 0001
07 JUNE 2026
4) In PART 3, D3040 DISTRIBUTION SYSTEMS AND D3050 TERMINAL & PACKAGED UNITS, DEMOLITION: Page 17:
CHART E226 - Remove and save in undamaged condition existing linear supply diffuser for reinstallation in new ceiling. Remove and save in undamaged condition existing return air grille for reinstallation in new ceiling.
Add the following:
Demolish VAV-35W low pressure supply ductwork from box complete including supports
AHARED CONTROLLED AREA SPACE E227 - Remove and save in undamaged condition existing linear supply diffuser for reinstallation in new ceiling. Remove and save in undamaged condition existing return air grille for reinstallation in new ceiling.
Add the following:
Demolish VAV-34E low pressure supply ductwork from box complete including supports
5) Add the following:
1. NAS Building 145 As-Built Drawings in pdf.
2. NAS Building 145 Fire Alarm As-Built in pdf
3. NAS Building 145 Fire Alam Shop Drawings
4. NAS Building 145 Fire Pump Test Full Report in pdf
6) UNIT PRICING for ESS to issued at a later date as Amendment 0002.