This is a Government Baseline Building Performance Report Guide for a construction project to build a new fire apparatus bay at Naval Weapons Station Yorktown Cheatham Annex in Williamsburg, Virginia (Project P1476U, WON 1832581). The guide establishes baseline energy performance parameters and simulation inputs following ASHRAE 90.1 2019 Appendix G standards.

The facility comprises 3,046.5 square feet of conditioned space distributed across six areas: an Apparatus Bay/Fire Riser (2,398.6 sqft), Corridor (71.1 sqft), EMT Secure Storage (96.2 sqft), Mechanical Room (108.3 sqft), PPE Gear Storage/Maintenance/Decontamination Area (210.9 sqft), and Protective Equipment Laundry (161.3 sqft). The baseline HVAC system is specified as Climate Zone 4A System 3—a packaged rooftop air conditioner with constant volume direct expansion cooling and fossil fuel furnace heating. Indoor design conditions vary by space type, ranging from 55°F to 78°F for heating and 68°F to 85°F for cooling. The baseline service hot water system uses natural gas; however, the proposed design incorporates a split-system heat pump water heater achieving 36.8% energy savings. Lighting power densities follow ASHRAE 90.1-2019 standards, ranging from 0.38 W/sqft for storage areas to 0.86 W/sqft for the low-bay apparatus area. Weather data is derived from Newport News Williamsburg International Airport (Station ID: ICAO_KPHF), with summer design conditions of 91°F dry bulb and 76°F wet bulb (1% occurrence) and winter design conditions of 23°F (99% occurrence). Utility rates are established at $0.1068/kWh for electricity and $0.961/Therm for natural gas. The baseline annual energy cost is $51,307, while the proposed systems design achieves 60.9% site energy savings and 24.4% cost savings through elimination of natural gas consumption and reduced cooling and fan energy requirements.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P1476U Construct New Fire Apparatus Bay at CAD 119 Naval Weapons Station Yorktown Cheatham Annex, Williamsburg, VA

WON 1832581

PART SIX - ATTACHMENTS

Attachment 7 – Government_Baseline_Building_Performance_Report_Guide-REV 1

NEW APPARATUS BAY − PART 6 ATTACHMENTS

PART SIX - ATTACHMENTS

THIS PAGE LEFT INTENTIONALLY BLANK

Government Baseline Building Performance Report Guide

Government Baseline Simulation Inputs:

The following list is outlined the same as Table G3.1 of ASHRAE 90.1 2019 Appendix G.

1. Design Model

Include number of floors and floor area of all conditioned spaces.

Apparatus Bay/Fire Riser – 2398.6 sqft

Corridor -71.1 sqft

EMT Secure Storage -96.2 sqft

Mechanical -108.3 sqft

PPE Gear Storage/Maintenance/ Utility Decon restroom- 210.9 sqft

Protective Equipment Laundry -161.3 sqft

2. Additions and Alterations

P1476U will be an Apparatus Bay addition for a Satellite Structural Station enclosed in a pre-engineered metal building of size, shape, height, fenestration, siting, and configuration indicated in the RFP. The facility will be adjacent to CAD119 and connected by a covered walkway.

3. Space Use Classification

Apparatus Bay/Fire Riser -Space Type: Low Bay Area Miscellaneous: Manufacturing.

Hazardous materials not used.

Corridor -Space Type: Corridor: General Corridor

EMT Secure Storage -Space Type: Storage Room-Medium size: General Occupiable storage room (liq/gel)

Mechanical -Space Type: Electrical/Mechanical Room: Miscellaneous: Telephone closet

PPE Gear Storage/Maintenance/ Utility Decon restroom- Space Type: Locker Room:

User Defined

Protective Equipment Laundry -Space Type: Laundry-Hotel: Hotel/Motel/Resort/Dorm:

Laundry room. central

4. Schedules

See “Hourly Schedule Input” Data.

Indoor Design Conditions Cooling

Protective Equipment Laundry, PPE Gear Storage\Maintenance, Decon, and Secure Storage, and restroom – 78°F; 50% RH

Apparatus Bay, Mechanical Room, and Fire Riser – Not to be cool o Will provide outdoor air ventilation to cool the apparatus bay to within 10° F of design outdoor temperature.

Heating

Protective Equipment Laundry, PPE Gear Storage\Maintenance, Decon, and Secure Storage Rooms and restroom – 68°F

Apparatus Bay – 68°F

Mechanical and Fire Riser closet– 55°F

Outdoor Design Conditions

Weather Station Newport News Williamsburg, VA

Station ID: ICAO_KPHF

• Summer 91° F DB, 76°F WB (1% Occurrence DB Temperature)

• Winter 23°F (99% Occurrence DB Temperature)

Note: Design Conditions uses weather data from Newport News Williamsburg, VA as there isn’t any weather data for Yorktown. Please see “Yorktown weather data”.

The following are all rates.

Electric Rate Schedule: $0.1068/kWh

Fuel Rate Schedule: $0.961/Therm

Include occupancy and usage schedules.

Number of People

• Apparatus Bay: 142.9 sqft/person

• PPE Geart Storage/Maintenance: 100 sqft/person

• Protective Equipment Laundry: 100 sqft/person

5. Building Envelope

Approximation of total envelope surface area.

6. Lighting

Used ASHRAE Standard 90.1-2019 Space by Space Lighting Method

Apparatus Bay: Manufacturing Facility: Low Bay area 0.86 W/sqft

Corridor: Corridor 0.41 W/sqft

EMT Secure Storage: Storage Room >=50ft2 0.38 W/sqft

Mechanical: Electrical/Mechanical Room 0.43 W/sqft

PPE Gear Storage/Maintenance: Locker Room 0.52 W/sqft

Protective Equipment Laundry: Laundry/Washing Area 0.53 W/sqft

7. Thermal Blocks—HVAC Zones Designed

Mechanical Room must be a separate zone

Fire Riser must be a separate zone

Apparatus Bay must be a separate zone

Secure Storage/EMT Storage

Room must be a separate Zone

Protective Equipment Laundry

Room/PPE Gear

Storage/Maintenance, Decontamination Room, and

Unisex restroom must be in another zone.

8. Thermal Blocks—HVAC Zones Not Designed

Include approximation of each zone area and gross surface areas off outside walls, floors and roofs.

N/A

9. Thermal Blocks—Multifamily Residential Buildings

10. HVAC Systems

Include baseline selections based on climate zone. State climate zone.

Climate Zone: 4A- System 3- PSZ-AC.

Packaged rooftop air conditioner; Constant Volume, Direct expansion, Fossil fuel furnace.

11. Service Hot-Water Systems

Baseline service hot water: Natural Gas. Proposed Heat Pump water heater provides 36.8% in energy saving using Split system Heat Pump water heater.

12. Receptacle and Other Loads

Include the loads used in the baseline building simulation.

Apparatus Bay: 20 W/sqft

Mechanical: 5W/sqft

PPE Gear Storage/Maintenance: 3W/sqft

Protective Equipment Laundry: 7.5W/sqft

13. Modeling Limitations to the Simulation Program

14. Exterior Conditions

Include exterior conditions used in the baseline building simulation.

15. Distribution Transformers

Baseline Simulation Outputs:

Fill in the ASHRAE 90.1 2013 Performance Rating Method Compliance Report to provide baseline outputs.

Project information:

Station: Yorktown, VA, USA.

Principle heating source: Natural Gas furnace

Space Summary:

Input conditioned and unconditioned air for each zone. Make sure the required zones per

ASHRAE 90.1 are included and the same as the HVAC LCCA best value selection analysis.

All spaces are conditioned. See “Design Load Space Summary Report”.

Advisory Messages:

Enter not met hours: Zero

Simulation General:

See “Baseline Air System Inputs” sheet.

Energy and Cost Summary by Fuel Type

Energy Summary by End Use See “Energy Budget by System and Energy Type”.

THIS PAGE LEFT INTENTIONALLY BLANK

[B] ASHRAE 90.1 Baseline - System 3 Input Data Project: P1476U HAP 05/11/2026

Prepared by: NAVFAC 12:26 PM

1. General Details:

Air System Name [B] ASHRAE 90.1 Baseline - System 3 Equipment Type Packaged Rooftop Units Air System Type Single Zone CAV Space Model: [B] Default Space Model - Single Zone Notes:

2. System Components:

Ventilation Air Data:

Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 2 %

Air-to-Air Energy Recovery Data:

Recovery Type Sensible and Latent Heat Thermal Efficiency 50 % Input kW 0.000 kW Schedule JFMAMJJASOND

Central Cooling Data:

Supply Air Temperature 58.0 F Cooling Source Air-Cooled DX Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:

Supply Temperature 95.0 F Heating Source Combustion - Natural Gas Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:

Fan Type Forward Curved Configuration Draw-thru Fan Performance 2.00 in wg Overall Efficiency 54 % Fan Control 1-speed, cooling and heating

Duct System Data:

Supply Duct Data:

Duct Leakage 3 %

Return Duct or Plenum Data:

Return Air Via Ducted Return

Return Fan Data:

Fan Type Forward Curved Fan Performance 2.00 in wg Overall Efficiency 54 %

3. Zone Components:

Assigned Zones:

Zone Zone Name

1 Zone 1

Number of zones 1

Thermostats and Zone Data:

Zone

Cooling T-Stat Occ.

Cooling T-Stat Unocc.

Heating T-Stat Occ.

Heating T-Stat Unocc.

T-Stat Throttling

Range Diversity

Factor

Direct Exhaust

Fan

(F) (F) (F) (F) (F) (%) (kW)

1 78.0 80.0 68.0 65.0 1.50 100 0.0

Thermostat Schedule Default Fan/Thermostat Schedule Unoccupied Cooling is Available

Hourly Analysis Program 6.2 Page 1 of 2

[B] ASHRAE 90.1 Baseline - System 3 Input Data Project: P1476U HAP 05/11/2026

Prepared by: NAVFAC 12:26 PM

Supply Terminals Data:

Zone Terminal Type Air

Distribution

Air Distribution

Effectiveness Specification

Air Distribution

Effectiveness Minimum Airflow

Design Supply Temp. Fan Perf.

Fan Efficiency

Diffuser (no reheat)

Ceiling supply / ceiling return Not Used - 0.00 CFM/person - - -

4. Sizing Data (Computer-Generated):

System Sizing Data:

Sizing Data:

Cooling Supply Temperature 58.0 F Supply Fan Airflow 10943.9 CFM Ventilation Airflow 642.8 CFM Heating Supply Temperature 95.0 F

Hydronic Sizing Specifications:

Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F

Safety Factors:

Cooling Sensible 0 % Cooling Latent 0 % Heating 0 %

Zone Sizing Data:

Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil FPMBX Fan

(CFM) (MBH) (MBH) (CFM)

1 10615.6 - - -

5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load 321.7 MBH Design OADB 95.0 F Design EWB 67.0 F Equipment Sizing (Auto-Sized) 321.7 MBH Capacity Oversizing Factor 0 % AHRI Performance Rating 11.000 EER DX System Configuration 1-stage, 1 compressor, 1 circuit Low Temperature Cutoff OAT 0.0 F

Central Heating Unit - Combustion Estimated Maximum Load 134.7 MBH Equipment Sizing (Auto-Sized) 134.7 MBH Capacity Oversizing Factor 0 % Average Efficiency 85.0 % Misc. Electric 0.000 kW

Hourly Analysis Program 6.2 Page 2 of 2

Zone Sizing Summary for [B] ASHRAE 90.1 Baseline - System 3 (In Alternative: [B] ASHRAE 90.1 Baseline)

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Air System Information Air System Name [B] ASHRAE 90.1 Baseline - System 3 Equipment Class PKG ROOF Air System Type SZCAV

Number of zones 1 Floor Area 3046.5 sqft Location Newport News Williamsburg, VA, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

Zone 1 10616 10616 3.48 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

Zone 1 226.5 August 16:00 142.7 3046.5

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

Zone 1

Apparatus Bay 204.1 August 16:00 9466 111.0 2398.6 3.95

Corridor 2.9 July 16:00 135 3.6 71.1 1.90

EMT Secure Storage 1.4 July 16:00 114 3.3 96.2 1.19

Mechanical 4.6 July 15:00 273 7.9 108.3 2.52

PPE Gear Storage/Maintenance 5.5 July 16:00 254 7.0 210.9 1.20

Protective Equipment Laundry 8.1 August 16:00 374 9.8 161.3 2.32

Hourly Analysis Program 6.2 Page 1 of 22

Zone Heat Balance Summary for [B] ASHRAE 90.1 Baseline - System 3

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Zone Zone 1

DESIGN COOLING - AUGUST 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 3155 sqft 17182 - 3155 sqft 10735 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 472 sqft 5446 - 472 sqft 6101 - Floor Convection 3046 sqft 12048 - 3046 sqft 12460 - Interior Wall Convection 2442 sqft 6880 - 2442 sqft 2530 - Ceiling Convection 3046 sqft 27506 - 3046 sqft 24649 - Overhead Lighting Convection 1600 W 2424 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 50355 W 128865 - 0 W 0 - People Convection 21 2162 11254 0 0 0 Infiltration 1561 CFM 23978 34005 1820 CFM 86193 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change - 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 226490 45258 - 142669 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room air. Therefore, the effect of solar heat gain is found in the surface convection line items.

Hourly Analysis Program 6.2 Page 2 of 22

Space Heat Balance Summary for [B] ASHRAE 90.1 Baseline - System 3

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space Apparatus Bay in Zone Zone 1

DESIGN COOLING - AUGUST 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 78.0 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 2387 sqft 15148 - 2387 sqft 8575 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 452 sqft 5258 - 452 sqft 5851 - Floor Convection 2399 sqft 10935 - 2399 sqft 10102 - Interior Wall Convection 992 sqft 4454 - 992 sqft 1651 - Ceiling Convection 2399 sqft 24403 - 2399 sqft 23052 - Overhead Lighting Convection 1392 W 2109 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 47971 W 122764 - 0 W 0 - People Convection 17 1888 10491 0 0 0 Infiltration 1119 CFM 17188 25989 1305 CFM 61816 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change 0.0F 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 204148 36479 - 111048 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 3 of 22

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space Corridor in Zone Zone 1

DESIGN COOLING - JULY 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 78.0 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 48 sqft 245 - 48 sqft 196 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 20 sqft 190 - 20 sqft 249 - Floor Convection 71 sqft 324 - 71 sqft 357 - Interior Wall Convection 243 sqft 964 - 243 sqft 386 - Ceiling Convection 71 sqft 579 - 71 sqft 279 - Overhead Lighting Convection 20 W 30 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 0 W 0 - 0 W 0 - People Convection 0 0 0 0 0 0 Infiltration 38 CFM 582 799 44 CFM 2091 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change 0.0F 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 2914 799 - 3558 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 4 of 22

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space EMT Secure Storage in Zone Zone 1

DESIGN COOLING - JULY 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 78.0 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 82 sqft 101 - 82 sqft 203 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 96 sqft 53 - 96 sqft 268 - Interior Wall Convection 316 sqft 166 - 316 sqft 106 - Ceiling Convection 96 sqft 303 - 96 sqft 206 - Overhead Lighting Convection 25 W 37 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 0 W 0 - 0 W 0 - People Convection 0 0 0 0 0 0 Infiltration 46 CFM 710 719 54 CFM 2547 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change 0.0F 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 1370 719 - 3331 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 5 of 22

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space Mechanical in Zone Zone 1

DESIGN COOLING - JULY 15:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 78.0 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 210 sqft 479 - 210 sqft 609 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 108 sqft 126 - 108 sqft 486 - Interior Wall Convection 210 sqft 243 - 210 sqft 97 - Ceiling Convection 108 sqft 461 - 108 sqft 263 - Overhead Lighting Convection 31 W 48 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 542 W 1386 - 0 W 0 - People Convection 0 0 0 0 0 0 Infiltration 117 CFM 1819 2032 137 CFM 6485 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change 0.0F 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 4562 2032 - 7941 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 6 of 22

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space PPE Gear Storage/Maintenance in Zone Zone 1

DESIGN COOLING - JULY 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 78.0 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 174 sqft 360 - 174 sqft 432 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 211 sqft 271 - 211 sqft 589 - Interior Wall Convection 426 sqft 554 - 426 sqft 168 - Ceiling Convection 211 sqft 902 - 211 sqft 462 - Overhead Lighting Convection 74 W 112 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 633 W 1619 - 0 W 0 - People Convection 2 155 432 0 0 0 Infiltration 97 CFM 1495 1775 113 CFM 5369 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change 0.0F 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 5468 2207 - 7019 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 7 of 22

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space Protective Equipment Laundry in Zone Zone 1

DESIGN COOLING - AUGUST 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 78.0 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 255 sqft 871 - 255 sqft 721 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 161 sqft 344 - 161 sqft 656 - Interior Wall Convection 255 sqft 503 - 255 sqft 122 - Ceiling Convection 161 sqft 853 - 161 sqft 387 - Overhead Lighting Convection 58 W 87 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 1210 W 3097 - 0 W 0 - People Convection 2 119 331 0 0 0 Infiltration 143 CFM 2196 2696 167 CFM 7886 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change 0.0F 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 8070 3027 - 9772 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 8 of 22

Zone Sizing Summary for Apparatus Bay (In Alternative: Proposed Systems)

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Air System Information Air System Name Apparatus Bay Equipment Class SPLT AHU Air System Type SZCAV

Number of zones 1 Floor Area 2469.7 sqft Location Newport News Williamsburg, VA, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

Zone 2 3804 3804 1.54 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area Zone Name (MBH) Cooling Load (MBH) (sqft)

Zone 2 0.0 September 23:00 110.8 2469.7

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

Zone 2

Apparatus Bay 0.0 September 23:00 3686 107.3 2398.6 1.54

Corridor 0.0 July 23:00 118 3.4 71.1 1.66

Hourly Analysis Program 6.2 Page 9 of 22

Zone Heat Balance Summary for Apparatus Bay

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Zone Zone 2

DESIGN COOLING - SEPTEMBER 23:00 DESIGN HEATING

OA DB / WB 78.0 F / 71.8 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 85.0 F OCCUPIED T-STAT 68.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 2435 sqft 2737 - 2435 sqft 6542 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 472 sqft -6385 - 472 sqft 5991 - Floor Convection 2470 sqft 26572 - 2470 sqft 10044 - Interior Wall Convection 1235 sqft 5261 - 1235 sqft 1972 - Ceiling Convection 2470 sqft -5817 - 2470 sqft 22302 - Overhead Lighting Convection 71 W 107 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 2399 W 6138 - 0 W 0 - People Convection 0 0 0 0 0 0 Infiltration 1188 CFM -57554 -1194 1349 CFM 63907 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change - 28941 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 0 -1194 - 110759 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 10 of 22

Space Heat Balance Summary for Apparatus Bay

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space Apparatus Bay in Zone Zone 2

DESIGN COOLING - SEPTEMBER 23:00 DESIGN HEATING

OA DB / WB 78.0 F / 71.8 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 85.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 121.7 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 2387 sqft 2604 - 2387 sqft 6397 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 452 sqft -6363 - 452 sqft 5747 - Floor Convection 2399 sqft 26024 - 2399 sqft 9700 - Interior Wall Convection 992 sqft 4679 - 992 sqft 1615 - Ceiling Convection 2399 sqft -6032 - 2399 sqft 22047 - Overhead Lighting Convection 70 W 105 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 2399 W 6138 - 0 W 0 - People Convection 0 0 0 0 0 0 Infiltration 1149 CFM -56008 -1194 1305 CFM 61816 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change -33.5F 28850 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 0 -1194 - 107321 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 11 of 22

Space Heat Balance Summary for Apparatus Bay

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space Corridor in Zone Zone 2

DESIGN COOLING - JULY 23:00 DESIGN HEATING

OA DB / WB 80.0 F / 72.8 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 85.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 115.6 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 48 sqft 136 - 48 sqft 145 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 20 sqft -21 - 20 sqft 244 - Floor Convection 71 sqft 552 - 71 sqft 345 - Interior Wall Convection 243 sqft 563 - 243 sqft 357 - Ceiling Convection 71 sqft 216 - 71 sqft 255 - Overhead Lighting Convection 1 W 1 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 0 W 0 - 0 W 0 - People Convection 0 0 0 0 0 0 Infiltration 39 CFM -1539 0 44 CFM 2091 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change -7.1F 91 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 0 0 - 3438 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 12 of 22

Zone Sizing Summary for Heating and Ventilation

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Air System Information Air System Name Heating and Ventilation Equipment Class SPLT AHU Air System Type SZCAV

Number of zones 1 Floor Area 108.3 sqft Location Newport News Williamsburg, VA, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

Zone 1 109 109 1.01 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area Zone Name (MBH) Cooling Load (MBH) (sqft)

Zone 1 0.0 January 23:00 4.7 108.3

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

Zone 1

Mechanical 0.0 January 23:00 109 4.7 108.3 1.01

Hourly Analysis Program 6.2 Page 13 of 22

Zone Heat Balance Summary for Heating and Ventilation

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Zone Zone 1

DESIGN COOLING - JANUARY 23:00 DESIGN HEATING

OA DB / WB 58.6 F / 58.6 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 85.0 F OCCUPIED T-STAT 55.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 210 sqft 393 - 210 sqft 193 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 108 sqft 464 - 108 sqft 302 - Interior Wall Convection 210 sqft 880 - 210 sqft -203 - Ceiling Convection 108 sqft 451 - 108 sqft -152 - Overhead Lighting Convection 2 W 2 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 27 W 69 - 0 W 0 - People Convection 0 0 0 0 0 0 Infiltration 126 CFM -2393 -56 137 CFM 4556 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change - 134 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 0 -56 - 4696 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 14 of 22

Space Heat Balance Summary for Heating and Ventilation

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space Mechanical in Zone Zone 1

DESIGN COOLING - JANUARY 23:00 DESIGN HEATING

OA DB / WB 58.6 F / 58.6 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 85.0 F OCCUPIED T-STAT 55.0 F

INDOOR DB 75.7 F INDOOR DB 55.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 210 sqft 393 - 210 sqft 193 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 108 sqft 464 - 108 sqft 302 - Interior Wall Convection 210 sqft 880 - 210 sqft -203 - Ceiling Convection 108 sqft 451 - 108 sqft -152 - Overhead Lighting Convection 2 W 2 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 27 W 69 - 0 W 0 - People Convection 0 0 0 0 0 0 Infiltration 126 CFM -2393 -56 137 CFM 4556 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change -6.9F 134 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 0 -56 - 4696 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 15 of 22

Zone Sizing Summary for Split System Heat Pump with ERV

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Air System Information Air System Name Split System Heat Pump with ERV Equipment Class SPLT AHU Air System Type SZCAV

Number of zones 1 Floor Area 372.2 sqft Location Newport News Williamsburg, VA, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

Zone 4 1060 1060 2.85 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area Zone Name (MBH) Cooling Load (MBH) (sqft)

Zone 4 22.9 July 16:00 16.1 372.2

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

Zone 4

PPE Gear Storage/Maintenance 11.1 July 16:00 516 6.7 210.9 2.45

Protective Equipment Laundry 11.7 August 16:00 544 9.4 161.3 3.37

Hourly Analysis Program 6.2 Page 16 of 22

Zone Heat Balance Summary for Split System Heat Pump with ERV

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Zone Zone 4

DESIGN COOLING - JULY 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 428 sqft 1439 - 428 sqft 708 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 372 sqft 978 - 372 sqft 1203 - Interior Wall Convection 681 sqft 4109 - 681 sqft 221 - Ceiling Convection 372 sqft 7452 - 372 sqft 745 - Overhead Lighting Convection 132 W 200 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 1843 W 4715 - 0 W 0 - People Convection 4 274 763 0 0 0 Infiltration 240 CFM 3692 5132 280 CFM 13254 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change - 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 22858 5895 - 16131 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 17 of 22

Space Heat Balance Summary for Split System Heat Pump with ERV

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space PPE Gear Storage/Maintenance in Zone Zone 4

DESIGN COOLING - JULY 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 78.0 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 174 sqft 494 - 174 sqft 267 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 211 sqft 504 - 211 sqft 569 - Interior Wall Convection 426 sqft 2601 - 426 sqft 132 - Ceiling Convection 211 sqft 4139 - 211 sqft 408 - Overhead Lighting Convection 74 W 112 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 633 W 1619 - 0 W 0 - People Convection 2 155 432 0 0 0 Infiltration 97 CFM 1495 2144 113 CFM 5369 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change 0.0F 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 11120 2576 - 6744 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 18 of 22

Space Heat Balance Summary for Split System Heat Pump with ERV

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space Protective Equipment Laundry in Zone Zone 4

DESIGN COOLING - AUGUST 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 78.0 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 255 sqft 947 - 255 sqft 441 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 161 sqft 473 - 161 sqft 634 - Interior Wall Convection 255 sqft 1509 - 255 sqft 89 - Ceiling Convection 161 sqft 3314 - 161 sqft 337 - Overhead Lighting Convection 58 W 87 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 1210 W 3097 - 0 W 0 - People Convection 2 119 331 0 0 0 Infiltration 143 CFM 2196 2988 167 CFM 7886 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change 0.0F 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 11742 3319 - 9387 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 19 of 22

Zone Sizing Summary for Split System Heat Pump with ERV(1)

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Air System Information Air System Name Split System Heat Pump with ERV(1) Equipment Class SPLT AHU Air System Type SZCAV

Number of zones 1 Floor Area 96.2 sqft Location Newport News Williamsburg, VA, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Sum of space airflow rates Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

Zone 3 219 219 2.27 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area Zone Name (MBH) Cooling Load (MBH) (sqft)

Zone 3 4.7 July 16:00 3.4 96.2

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

Zone 3

EMT Secure Storage 4.7 July 16:00 219 3.4 96.2 2.27

Hourly Analysis Program 6.2 Page 20 of 22

Zone Heat Balance Summary for Split System Heat Pump with ERV(1)

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Zone Zone 3

DESIGN COOLING - JULY 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 82 sqft 182 - 82 sqft 135 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 96 sqft 171 - 96 sqft 274 - Interior Wall Convection 316 sqft 1808 - 316 sqft 232 - Ceiling Convection 96 sqft 1811 - 96 sqft 196 - Overhead Lighting Convection 25 W 37 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 0 W 0 - 0 W 0 - People Convection 0 0 0 0 0 0 Infiltration 46 CFM 710 1031 54 CFM 2547 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change - 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 4719 1031 - 3384 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 21 of 22

Space Heat Balance Summary for Split System Heat Pump with ERV(1)

Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:21 AM

Table 1. Heat Balance Loads for Space EMT Secure Storage in Zone Zone 3

DESIGN COOLING - JULY 16:00 DESIGN HEATING

OA DB / WB 92.0 F / 76.1 F OA DB / WB 24.3 F / 20.4 F

OCCUPIED T-STAT 78.0 F OCCUPIED T-STAT 68.0 F

INDOOR DB 78.0 F INDOOR DB 68.0 F

Space Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 82 sqft 182 - 82 sqft 135 - Roof Convection 0 sqft 0 - 0 sqft 0 - Window Convection 0 sqft 0 - 0 sqft 0 - Skylight Convection 0 sqft 0 - 0 sqft 0 - Door Convection 0 sqft 0 - 0 sqft 0 - Floor Convection 96 sqft 171 - 96 sqft 274 - Interior Wall Convection 316 sqft 1808 - 316 sqft 232 - Ceiling Convection 96 sqft 1811 - 96 sqft 196 - Overhead Lighting Convection 25 W 37 - 0 W 0 - Task Lighting Convection 0 W 0 - 0 W 0 - Electric Equipment Convection 0 W 0 - 0 W 0 - People Convection 0 0 0 0 0 0 Infiltration 46 CFM 710 1031 54 CFM 2547 0 Miscellaneous Equipment - 0 0 - 0 0 Air Internal Energy Change 0.0F 0 - 0 0 Safety Factor 0% / 0% 0 0 0% 0 0 >> Total Space Loads - 4719 1031 - 3384 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 22 of 22

Energy Budget by System Component - [B] ASHRAE 90.1 Baseline Project: P1476U HAP 05/14/2026

Prepared by: NAVFAC 7:23 AM

1. Annual Coil Loads

Component Load

(kBTU) (kBTU/sqft)

Cooling Coil Loads 581,735 190.955

Heati…