001_Attachment L - PPI_Responses_27FEB24.pdf

PDF 701 KB Posted

Attached to
P602U MSRON TWO Combatant Craft Maintenance Facility
Solicitation number
N4008524R2592
Issued by

About this file

This attachment is related to a solicitation for a Combatant Craft Maintenance Facility project at Joint Expeditionary Base Little Creek - Fort Story in Virginia Beach, Virginia. The solicitation is being issued through the 8(a) Multiple Award Construction Contract (MACC) program primarily for contractors in the Hampton Roads area of Virginia. Only 8(a) MACC Contractors holding certain contract numbers with NAVFAC MID-ATLANTIC may submit a proposal for this P602U MSRON TWO Combatant Craft Maintenance Facility project. The solicitation was issued by the Department of the Navy Naval Facilities Engineering Command.

View the file

Other files

File Type Posted
0005_Attachment G-REV3 - VA20240167 21JUN24.pdf PDF
Amendment_0005.pdf PDF
Amendment_004.pdf PDF
003_Attachment R - DON_REA.pdf PDF
Amendment_003.pdf PDF
003_Attachment M - Price Proposal Form_rev1.pdf PDF
Amendment_002.pdf PDF
002_Attachment L - PPI Responses_29FEB24.pdf PDF
001_Attachment Q - S-505.pdf PDF
Amendment_001.pdf PDF
001_Attachment O - SiteVisitLog_27Feb24.pdf PDF
001_Attachment P - S-101.pdf PDF
001_Attachment G - VA20240167_23FEB24.pdf PDF
Attachment I - Site Location and Parking.pdf PDF
Attachment C - Schedule of Special Inspections.pdf PDF
Attachment K - ONE DAY PASS FORM.xls XLS spreadsheet
Attachment N - Solicitation Provisions.pdf PDF
Attachment L - Pre-Proposal Inquiry Form.xlsx XLSX spreadsheet
Attachment M - Price Proposal Form.pdf PDF
Attachment J - SECNAV 5512.pdf PDF
Attachment E - Utility Permit - P602.pdf PDF
Attachment G - VA20240167_05JAN2024.pdf PDF
24R2592 General Requirements.pdf PDF
Attachment D - Statement_of_Special_Inspections.pdf PDF
Attachment A - 1717512 SPEC COMPLETE.pdf PDF
Attachment H - CJA.pdf PDF
Attachment F - REGISTER.pdf PDF
Attachment B - 1717512 DRAWINGS.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B D E F G H I

Page Section Paragraph

02/20/24 13 2.4.1

This spec section indicates roof, wall and liner panel to be 24 gauge exposed fastener PBR panels. This would create an issue as you cannot provide the requested weathertight warranty for the roof with an exposed fastener roof panel. Would the government prefer an exposed fastener roof panel without weathertight warranty or change it to a standing seam roof panel w/weathertight warranty?

Provide standing seam roof in lieu of exposed fastener system. Provide roof warranty as specified.

02/20/24 S-505

The plans S-101 note 8 indicates the equipment mezzanine columns to be provided by the PEMB manufacturer. Sheet S-505 indicates the mezzanine supported by steel columns with masonry walls with bond beams placed between the columns. The plan provides perimeter beam size (12” ) and joist size (C12 x 3.5), but not the column size. Framing plan B2 on S-505 also indicates structural sections A2/sheet S-401 and C3/sheet S-401. The drawing set does not include a sheet S-401. Could you please confirm if this note is correct in refering to sheet S-401 and, if so, could that sheet be provided? Also, is the mezzanine meant to be free standing, or does it tie into the structural columns on the building?

The mezzanine is intended to be a free standing structure. Sheet S-401 is not included in the bid documents; References to Sheet S- 401 shall be superseded by S-505, which illustrates the framing of the mezzanine. See General Note 2, Sheet S-505 for PEB manufacturer requirements pertaining to mezzanine framing and design.

02/20/24 13 1.2.4.1 / 13 1.2.4.2

These spec sections call for R-19 roof and R-13 wall thermal insulation, however code is been R-30 roof and R-26 wall insulation. This is graphically indicated on the drawings but not specifically called out. Could you please confirm the correct R value for thermal insulation?

Provide R-30 roof and R-26 wall insulation as required by code.

02/22/24 DWGS S-101

& S-505

The plans S-101 note 8 indicates the equipment mezzanine columns to be provided by the PEMB manufacturer. BUT Sheet S-505 indicates the mezzanine supported by masonry walls with bond beams placed between steel columns and specifies perimeter beam size (12” ) and joist size (C12 x 3.5), but not the column size. What size is the columns?

equipment platform is to be designed by the pemb manufacturer per sheet s-001 "delegated design" note 3. Sheet S-100 new work keynote 6. Sheet S-101 new work keynote 8. Sheet S-505 general sheet notes 2. Sheet S-505 shows a platform for bidding purposes not for construction and to illustrate certain column placement and interaction between platform and cmu.

02/22/24 DWG S-505

Framing plan B2 on S-505 also indicates structural sections A2/sheet S- 401 and C3/sheet S-401. There is no drawing S-401. Please provide drawing S-401

References to Sheet S-401 shall be superseded by S-505, which illustrates the framing of the mezzanine. See General Note 2, Sheet S- 505 for PEB manufacturer requirements pertaining to mezzanine framing and design. 001

02/22/24 9/613 1.2.4.1 13 34 19 The specs and A-dwgs general notes call for R-19 roof thermal Insulation, code now has R-30 roof thermal insulation. Do we price the R-19 or the new code R-30?.

Provide R-30 roof and R-26 wall insulation as required by code.

02/22/24 9/613 1.2.4.2 13 34 19 The specs and A-dwgs general notes call for R-13 wall thermal Insulation, code now has R-26 wall thermal insulation. Do we price the R-13 or the new code R-26?.

Provide R-30 roof and R-26 wall insulation as required by code.

02/22/24 21/625 2.4.1 13 34 19

Specs indicate the roof, wall and liner panel to be 24 guage exposed fastener PBR panels. The problem is we can not provide the requested weathertight warranty for the roof with an exposed fastener roof panel, Please indicate which one is required, exposed fastener roof panel w/o weathertight warranty or change to standing seam roof panel w/weathertight warranty?

Provide standing seam roof in lieu of exposed fastener system. Provide roof warranty as specified.

Amend#

Pre-Proposal Inquiry Submission Form N4008524R2592, P602U MSRON TWO Combatant Craft Maintenance Facility

Date Submitted Government Response

Reference Question

RFP N4008524R2592_A001

Attachment L

PPI Submission Form