This document is an amendment to the specifications for HYDRAULIC FREIGHT ELEVATORS to be installed as part of the FFG-62 Land Based Engineering Site (LBES) renovation project at the Philadelphia Navy Yard Annex.

The key details include:

  • Provides technical specifications for the design, materials, equipment, and installation of hydraulic freight elevators, including requirements for pump units, hydraulic controls and piping, microprocessor controllers, operating panels, hoistway/car enclosures, and testing/commissioning.
  • The elevators must comply with ASME A17.1/CSA B44 safety codes and NEI-1 performance standards.
  • Submittals required include shop drawings, product data, design calculations, maintenance documentation, and certification of welder qualifications and elevator controller compliance.
  • The elevators must be installed by qualified and certified personnel and include a one-year warranty with monthly service.
  • Acceptance inspection, testing, and commissioning by a third-party qualified elevator inspector is required prior to final acceptance.

View the file

Other files

File Type Posted
AMENDMENT 0006.pdf PDF
Amend0005 - BLDG 77H West Low Bay Labs Redacted.pdf PDF
Amendment 0005 - 1678622 DWG 01of01.pdf PDF
Amend0005 B480 Photos 1of4.pdf PDF
Amend0005 B480 Photos 2of4.pdf PDF
Amend0005 - BLDG 77H East Substation Redacted.pdf PDF
Amend0005 - BLDG 77H General Building Spaces Redacted.pdf PDF
Amend0005 B480 Photos 3of4.pdf PDF
Amend0005 B480 Photos 4of4.pdf PDF
Amend0005 PPI 118 547 Paint B633 High Bay Interior Spec.pdf PDF
Amendment 0005 - AFFF Fire Extinguisher System As Built.pdf PDF
Amend0005 - BLDG 77H Diesel Test Facility Redacted.pdf PDF
Amendment 0005 - DDG51 Test Site Control House Complex Recorded.pdf PDF
Amendment 0005 Phila Naval Business Center Sprinklers -As Built.pdf PDF
AMENDMENT 0005.pdf PDF
Amendment 0005 - Automatic Fire Sprinkler System For Prefab Enclosure.pdf PDF
Amend0005 - BLDG 77H East Low Bay Labs Redacted.pdf PDF
Amend0005 PPI 116 FFG-62 MASW-Report.pdf PDF
Amend0005 - Bldg 77H MEP 77H Site and 480 Photos Redacted.pdf PDF
Amendment 0005 - BLDG 77H 756 Fire Alarm AsBuilts.pdf PDF
Amend0005 - BLDG 77H South Exterior Redacted.pdf PDF
Amendment 0005 - Integrated Ship Control Diagnostic Facility.pdf PDF
Amendment 0005 Small Component Electronic Cooling Water CWAS - As Built.pdf PDF
Amend0005 PPI 115 FFG-62 and Design Mod soil lab reports.pdf PDF
Amend0005 - BLDG 77H East Electrical MDP Redacted.pdf PDF
Amend0005 - BLDG 77H South Sprinkler Risers.pdf PDF
Amendment 0005 - DDG-51 Control House Extension 06101997.pdf PDF
Amendment 0004 - Cooling Water System - Controls Hardware.pdf PDF
Amendment 0004 - Fuel Oil System - Modifications to Existing Panel CP-FOPV.pdf PDF
Amendment 0004 - Cooling Tower System - As-Built Drawings.pdf PDF
Amendment 0004 - PPI 84 - NSWC Building 77H Roof Repair record drawings.pdf PDF
Amendment 0004 - Fuel Oil System - Control Panel CP-FOPV As-Built Drawings.pdf PDF
Amendment 0004 - FFG-62 Specifications.pdf PDF
Amendment 0004.pdf PDF
Amendment 0004 - FFG-62 Drawings Signed.pdf PDF
Amend0003 049 - BLDG077H - WEAPONS ELEVATOR - 2078005.pdf PDF
Amend0003 011 - BLDG077H - DIESEL TEST CELLS - 2163659.pdf PDF
Amend0003 010 - BLDG077H - DIESEL TEST CELLS - 2163658.pdf PDF
Amend0003 PPI 46_FFG62 Repair 77H Exterior SWYard Existing Photos DistroA.pdf PDF
Amend0003 7625158 R- D04-10-25_Redacted.pdf PDF
Amend0003 30041555 R- APPROVED 2021-08-11 ZONE 1 GENL ARR_Redacted.pdf PDF
Amend0003 PW-31 5400C246.pdf PDF
AMENDMENT 0003.pdf PDF
Amend0003 052 - BLDG077H - WEAPONS ELEVATOR - 2078009.pdf PDF
Amend0003 PW-30 5400C249.pdf PDF
Amend0003 1705955_DEMO_DWG_FULL SET.pdf PDF
Amend0003 050 - BLDG077H - WEAPONS ELEVATOR - 2078007.pdf PDF
Amend0003 30041586 R1 2021-08-12 SITE EQUIPMENT ARR_Redacted.pdf PDF
Amend0003 051 - BLDG077H - WEAPONS ELEVATOR - 2078008.pdf PDF
Amend0003 PW-32 5400C247.pdf PDF
Show 40 more

Latest 50 of 79 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FFG- 62 LBES - Repai r Package 1705955

SECTI ON 14 24 13

HYDRAULI C FREI GHT ELEVATORS

05/ 16

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN SOCI ETY OF MECHANI CAL ENGI NEERS ( ASME)

ASME A17. 1/ CSA B44 ( 2019) Saf et y Code f or El evat or s and Escal at or s

ASME A17. 2 ( 2020) Gui de f or I nspect i on of El evat or s, Escal at or s, and Movi ng Wal ks I ncl udes I nspect i on Pr ocedur es f or El ect r i c Tr act i on and Wi ndi ng Dr um El evat or s, Hydr aul i c El evat or s, and Escal at or s and Movi ng Wal ks

ASME B16. 9 ( 2018) Fact or y- Made Wr ought But t wel di ng Fi t t i ngs

ASME B16. 11 ( 2016) For ged Fi t t i ngs, Socket - Wel di ng and Thr eaded

AMERI CAN WELDI NG SOCI ETY ( AWS)

AWS D1. 1/ D1. 1M ( 2020; Er r at a 1 2021) St r uct ur al Wel di ng Code - St eel

ASTM I NTERNATI ONAL ( ASTM)

ASTM A53/ A53M ( 2022) St andar d Speci f i cat i on f or Pi pe, St eel , Bl ack and Hot - Di pped, Zi nc- Coat ed, Wel ded and Seaml ess

ASTM A106/ A106M ( 2019a) St andar d Speci f i cat i on f or Seaml ess Car bon St eel Pi pe f or Hi gh- Temper at ur e Ser vi ce

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE C62. 41 ( 1991; R 1995) Recommended Pr act i ce on Sur ge Vol t ages i n Low- Vol t age AC Power Ci r cui t s

I NTERNATI ONAL CODE COUNCI L ( I CC)

I CC I BC ( 2021) I nt er nat i onal Bui l di ng Code

SECTI ON 14 24 13 Page 1 Jul y 24, 2024

NATI ONAL ELEVATOR I NDUSTRY, I NC. ( NEI I )

NEI I - 1 ( 2000; R t hr u 2017) Bui l di ng Tr anspor t at i on St andar ds and Gui del i nes, i ncl udi ng t he Per f or mance St andar ds Mat r i x f or New El evat or I nst al l at i on

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 70 ( 2020; TI A 22- 1; ERTA 1 2022) Nat i onal El ect r i cal Code

NFPA 70E ( 2021) St andar d f or El ect r i cal Saf et y i n t he Wor kpl ace

NFPA 72 ( 2022) Nat i onal Fi r e Al ar m and Si gnal i ng Code

NFPA 101 ( 2021; TI A 21- 1) Li f e Saf et y Code

U. S. DEPARTMENT OF DEFENSE ( DOD)

UFC 3- 560- 01 ( 2017; wi t h Change 2, 2019) Oper at i ons and Mai nt enance: El ect r i cal Saf et y

U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)

36 CFR 1191 Amer i cans wi t h Di sabi l i t i es Act ( ADA) Accessi bi l i t y Gui del i nes f or Bui l di ngs and Faci l i t i es; Ar chi t ect ur al Bar r i er s Act ( ABA) Accessi bi l i t y Gui del i nes

1. 2 SUBMI TTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" or " S" c l assi f i cat i on. Submi t t al s not havi ng a " G" or " S" c l assi f i cat i on ar e f or i nf or mat i on onl y. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00

SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

El evat or Syst em; G

El evat or Component s; G

El evat or Machi ne; G

El evat or Cont r ol l er ; G

Wi r i ng Di agr ams; G

SD- 03 Pr oduct Dat a

El evat or and Accessor i es; G

El evat or Component s; G

Dat a Sheet s; G

SECTI ON 14 24 13 Page 2

El evat or Mi cr opr ocessor Cont r ol l er ; G

SD- 05 Desi gn Dat a

Emer gency Power Syst ems; G

Heat Loads; G

React i on Loads; G

SD- 07 Cer t i f i cat es

El evat or Par t s and Component s pr i ce l i s t s; G

War r ant y

Endor sement Let t er

Wel der s ' Qual i f i cat i ons; G

El evat or Cont r ol l er Cer t i f i cat i on; G

SD- 10 Oper at i on and Mai nt enance Dat a

El evat or , Dat a Package 4; G

Mai nt enance Cont r ol Pr ogr am ( MCP) ; G

Sof t war e and Document at i on; G

Submi t i n accor dance wi t h Sect i ons 01 78 23 OPERATI ON AND MAI NTENANCE DATA and 01 78 24. 00 20 FACI LI TY ELECTRONI C OPERATI ON AND MAI NTENANCE SUPPORT I NFORMATI ON ( eOMSI ) .

1. 2. 1 Shop Dr awi ng Requi r ement s

Pr ovi de assembl y and ar r angement of el evat or s, accessor i es, and el evat or component s as wel l as ot her equi pment ( HVAC, el ect r i cal et c. ) . Show l ocat i on of el evat or machi ne i n el evat or machi ne r oom ( MR) . Show l ocat i on of el evat or cont r ol l er i n el evat or machi ne r oom or el evat or cont r ol r oom ( CR) . Pr ovi de det ai l s f or mat er i al s and equi pment , i ncl udi ng but not l i mi t ed t o oper at i ng and si gnal f i x t ur es, door s, door and car f r ames, car encl osur e, cont r ol l er s, mot or s, gui de r ai l s and br acket s, l ayout of hoi st way i n pl an and el evat i on, and ot her l ayout i nf or mat i on and cl ear ance di mensi ons.

1. 2. 2 Pr oduct Dat a Requi r ement s

Pr ovi de manuf act ur er s ' pr oduct dat a f or al l el evat or component s, i ncl udi ng but not l i mi t ed t o t he f ol l owi ng: el evat or cont r ol l er , hydr aul i c pump uni t , hydr aul i c pump and mot or , hydr aul i c cyl i nder , hydr aul i c pi pi ng and f i t t i ngs, car and hal l f i x t ur e but t ons and swi t ches, cab and machi ne r oom or cont r ol r oom communi cat i on devi ces, door oper at or , door pr ot ect i on syst em, car r ol l er gui des, and buf f er s. For dat a sheet s, pr ovi de document i dent i f i cat i on number or bul l et i n number , publ i shed or copyr i ght ed pr i or t o t he dat e of cont r act bi d openi ng. Pr ovi de cont r ol l er manuf act ur er ' s publ i shed pr ocedur es f or per f or mance of each and al l t est i ng r equi r ed by

ASME A17. 1/ CSA B44.

SECTI ON 14 24 13 Page 3

1. 2. 3 Desi gn Dat a

1. 2. 3. 1 React i on Loads

Pr ovi de cal cul at i ons by r egi st er ed pr of essi onal engi neer f or r eact i on l oads i mposed on bui l di ng by el evat or syst em. Demonst r at e cal cul at i ons compl yi ng wi t h ASME A17. 1/ CSA B44

1. 2. 3. 2 Heat Loads

Pr ovi de cal cul at i ons f r om el evat or manuf act ur er , or by r egi st er ed pr of essi onal engi neer , f or t ot al ant i c i pat ed heat l oads gener at ed by al l of t he el evat or equi pment .

1. 2. 3. 3 Emer gency Power Syst ems

Wher e t he f aci l i t y does have an emer gency power syst em, conf i r m t he el evat or s t hat wi l l be connect ed t o t he emer gency power syst em. Conf i r m t he compl et e emer gency power syst em and sequence of oper at i on f or al l el evat or s, i ncl udi ng oper at i on of t he el evat or l obby manual sel ect i on swi t ch. Pr ovi de wi r i ng di agr ams f or bui l di ng emer gency power i nt er f ace wi t h el evat or cont r ol s. For el evat or s not suppl i ed by an emer gency power syst em, pr ovi de manuf act ur er s ' pr oduct dat a f or auxi l i ar y power syst ems t o del i ver t he el evat or t o t he l owest l andi ng and open t he el evat or door s t o al l ow passenger s t o saf el y exi t t he el evat or dur i ng a l oss of power .

1. 2. 4 Wel der s ' Requi r ement s

Compl y wi t h AWS D1. 1/ D1. 1M, Sect i on 5. I ncl ude cer t i f i ed copi es of f i el d wel der s ' qual i f i cat i ons. Li st wel der s ' names wi t h cor r espondi ng code mar ks t o i dent i f y each wel der ' s wel di ng wor k.

1. 2. 5 Mai nt enance Cont r ol Pr ogr am ( MCP)

For each el evat or , pr epar e and pr ovi de a wr i t t en Mai nt enance Cont r ol Pr ogr am ( MCP) t hat compl i es wi t h ASME A17. 1/ CSA B44 Sect i on 8. 6, i ncl udi ng wr i t t en document at i on t hat det ai l s t he t est pr ocedur es f or each and ever y t est t hat i s r equi r ed t o be per f or med by ASME A17. 1/ CSA B44. Assembl e al l MCP document at i on, and suppor t i ng t echni cal at t achment s, i n a s i ngl e MCP package and pr ovi de i n bot h el ect r oni c and har d copy. Assembl e ent i r e har d copy MCP i n 3- r i ng bi nder s. For each el evat or pr ovi ded, t he MCP must i ncl ude onl y document at i on and i nst r uct i on t hat appl y t o t he el evat or speci f i ed.

For each el evat or , pr ovi de an addi t i onal , separ at e bi nder t hat i ncl udes al l mai nt enance, r epai r , r epl acement , cal l back, and ot her r ecor ds r equi r ed by ASME A17. 1/ CSA B44. The r ecor ds bi nder must be kept i n t he el evat or mechani cal r oom, mai nt ai ned by el evat or mai nt enance and ser vi ce per sonnel , and be avai l abl e at al l t i mes t o aut hor i zed per sonnel .

Pr ovi de det ai l ed i nf or mat i on r egar di ng emer gency ser vi ce pr ocedur es and el evat or i nst al l at i on company per sonnel cont act i nf or mat i on. Pr ovi de a l i s t i ng of al l t ool s t o be pr ovi ded t o t he Cont r act i ng Of f i cer as component s of t he el evat or syst em.

SECTI ON 14 24 13 Page 4

1. 3 QUALI TY ASSURANCE

1. 3. 1 Qual i f i cat i on

Pr ovi de a desi gned and engi neer ed el evat or syst em by an el evat or cont r act or r egul ar l y engaged i n t he i nst al l at i on of el evat or syst ems.

Pr ovi de el evat or component s manuf act ur ed by compani es r egul ar l y engaged i n t he manuf act ur e of el evat or component s. Ut i l i ze onl y l i censed and cer t i f i ed el evat or per sonnel f or t he i nst al l at i on, adj ust i ng, t est i ng, and ser vi c i ng of t he el evat or s.

1. 3. 1. 1 El evat or Cont r act or ' s El evat or Techni c i ans

For el evat or i nst al l at i ons i n t he Uni t ed St at es, i ncl udi ng Uni t ed St at es t er r i t or i es, per f or m al l el evat or r el at ed wor k under t he di r ect gui dance of a st at e cer t i f i ed el evat or t echni c i an wi t h a mi ni mum of t hr ee year s of exper i ence i n t he i nst al l at i on of el evat or syst ems of t he t ype and compl exi t y speci f i ed i n t he cont r act document s. Pr ovi de an endor sement l et t er f r om t he el evat or manuf act ur er , cer t i f y i ng t hat t he el evat or speci al i st i s qual i f i ed. Al l el evat or t echni c i ans must car r y a cur r ent cer t i f i cat i on i ssued by one of t he f ol l owi ng or gani zat i ons:

a. Nat i onal Associ at i on of El evat or Cont r act or s ( NAEC)

b. Nat i onal El evat or I ndust r y Educat i on Pr ogr am ( NEI EP)

1. 3. 2 Manuf act ur er s ' Techni cal Suppor t

Pr ovi de el evat or component s f r om manuf act ur er s t hat pr ovi de f act or y t r ai ni ng and onl i ne and l i ve t el ephone el evat or t echni cal suppor t t o any el evat or i nst al l at i on, ser vi ce, and mai nt enance cont r act or . Pr ovi de el evat or component s f r om manuf act ur er s t hat guar ant ee accessi bi l i t y t o al l r epl acement and r epai r par t s and component s t o any el evat or i nst al l at i on, ser vi ce, and mai nt enance cont r act or . Use onl y el evat or component manuf act ur er s t hat pr ovi de cur r ent publ i shed pr i ce l i s t s f or al l el evat or par t s and component s.

1. 3. 3 Oper at i on and Mai nt enance Dat a

Assembl e al l shop dr awi ng and pr oduct dat a mat er i al i nt o O&M Dat a Packages i n accor dance wi t h Ar t i c l e SUBMI TTALS. Pr ovi de t wo compl et e O&M Dat a Packages i n har d copy and t wo compl et e el ect r oni c O&M dat a packages on separ at e CDs, i n PDF f or mat . Pr ovi de al l O&M Dat a Packages t o Cont r act i ng Of f i cer . I ncl ude cont r ol l er di agnost i c document at i on and sof t war e as r equi r ed under Ar t i c l e CONTROL EQUI PMENT.

1. 3. 4 Wi r i ng Di agr ams

Pr ovi de compl et e wi r i ng di agr ams and sequence of oper at i ons, whi ch show el ect r i cal connect i ons and f unct i ons of el evat or syst ems. Pr ovi de one set ( 11 i nch by 17 i nch mi ni mum si ze) of wi r i ng di agr ams, wi t h i ndi v i dual sheet s l ami nat ed i n pl ast i c and assembl ed i n bi nder , t o be st or ed i n t he machi ne r oom or cont r ol r oom cabi net . Pr ovi de one addi t i onal har d copy set and t wo compl et e el ect r oni c set s on separ at e CDs, i n PDF f or mat .

Pr ovi de al l wi r i ng di agr am set s t o t he Cont r act i ng Of f i cer . Coded di agr ams ar e not accept abl e unl ess f ul l y i dent i f i ed.

SECTI ON 14 24 13 Page 5

1. 3. 5 Machi ne Room/ Cont r ol Room Cabi net

For st or age of O&M Dat a Packages and Wi r i ng Di agr ams, pr ovi de l ocki ng met al cabi net wi t h a mi ni mum si ze of 20 i nch W by 12 i nch D by 30 i nch H.

Cabi net must be si zed l ar ge enough t o accommodat e al l O&M Dat a and har dwar e r equi r ed i n par agr aphs OPERATI ON AND MAI NTENANCE DATA and WI RI NG DI AGRAMS. Secur e cabi net t o machi ne r oom or cont r ol r oom wal l .

1. 4 NEW I NSTALLATI ON SERVI CE

Pr ovi de el evat or war r ant y ser vi ce i n accor dance wi t h t he manuf act ur er ' s mai nt enance pl an, war r ant y r equi r ement s and appl i cabl e saf et y codes, f or a per i od of 12 mont hs af t er t he dat e of accept ance by Cont r act i ng Of f i cer .

Per f or m t hi s wor k dur i ng r egul ar wor ki ng hour s. Pr ovi de suppl i es and par t s t o keep el evat or syst em i n oper at i on. Per f or m ser vi ce onl y by f act or y t r ai ned per sonnel . Pr ovi de Mont hl y ser vi ces t o i ncl ude r epai r s, adj ust ment s, gr easi ng, oi l i ng, and cl eani ng. Pr ovi de ser vi ce l og i n el evat or machi ne r oom or cont r ol r oom and updat e Mont hl y, t hr oughout t he one- year war r ant y per i od.

Pr ovi de 24- hour emer gency ser vi ce, wi t h one hour on- si t e r esponse t i me, dur i ng t hi s per i od wi t hout addi t i onal cost t o t he Gover nment .

1. 4. 1 Per i odi c El evat or Cer t i f i cat i on I nspect i on and Test i ng

Pr ovi de el evat or mechani c t o suppor t QEI Cer t i f i ed El evat or I nspect or i n t he per i odi c s i x- mont h and t he annual Cat egor y 1 el evat or cer t i f i cat i on i nspect i on and t est i ng. Per f or m Cat egor y 1 i nspect i on and t est i ng no gr eat er t han 30 days pr i or t o t he end of t he war r ant y per i od. Per f or m al l el evat or cer t i f i cat i on t est i ng i n t he pr esence of QEI Cer t i f i ed El evat or I nspect or .

I n conj unct i on wi t h t he t est i ng not ed above, t est syst ems f or Emer gency Power Oper at i on, Ear t hquake Emer gency Oper at i on, and Hospi t al Emer gency Commandeer i ng Ser vi ce Oper at i on, as appl i cabl e. Schedul e so t hat t est i ng does not i nt er f er e wi t h bui l di ng oper at i ons.

1. 5 FI RE PROTECTI ON SYSTEM

Coor di nat e i nt er f ace bet ween bui l di ng f i r e pr ot ect i on syst em and el evat or cont r ol s.

Addi t i onal f i r e pr ot ect i on r equi r ement s ar e l ocat ed i n: Sect i on 28 31 76 I NTERI OR FI RE ALARM AND MASS NOTI FI CATI ON SYSTEM, ADDRESSABLE; Sect i on 21 13 13 WET PI PE SPRI NKLER SYSTEMS, FI RE PROTECTI ON; and Sect i on 26 20 00

I NTERI OR DI STRI BUTI ON SYSTEM.

1. 5. 1 Fi r e Al ar m I ni t i at i ng Devi ces

Fi r e al ar m i ni t i at i ng devi ces ar e speci f i ed i n Sect i on 28 31 76 I NTERI OR FI RE ALARM AND MASS NOTI FI CATI ON SYSTEM, ADDRESSABLE , i ncl udi ng condui t and wi r i ng f r om each det ect or t o f i r e pr ot ect i on addr essabl e modul es i n el evat or machi ne r oom or cont r ol r oom.

1. 5. 2 Fi r e Spr i nkl er s

Pr ovi de f i r e spr i nkl er s i n accor dance wi t h al l appl i cabl e saf et y codes and wi t h Sect i on 21 13 13 WET PI PE SPRI NKLER SYSTEMS, FI RE PROTECTI ON. Pr ovi de shut of f val ve, check val ve, and non- adj ust abl e, zer o t i me- del ay f l ow

SECTI ON 14 24 13 Page 6 swi t ch, i n each spr i nkl er l i ne i mmedi at el y out si de of each machi ne r oom, cont r ol r oom, and hoi st way, as appl i cabl e. Pr ovi de i nspect or s ' t est val ve f or per i odi c t est i ng of f l ow swi t ch and shunt t r i p di sconnect .

Pi pe spr i nkl er pi pi ng ser vi ng t hese spaces i n a ser i es manner wi t h no l at er al s. Locat e i nspect or s ' t est connect i on at t he end of pi pe r uns such t hat oper at i on of t he t est connect i on wi l l pur ge ai r f r om syst em pi pi ng.

1. 5. 3 Shunt Tr i p Di sconnect

Pr ovi de f l ow swi t ches speci f i ed i n par agr aph FI RE SPRI NKLERS t o compl y wi t h ASME A17. 1/ CSA B44 and NFPA 72 f or shunt t r i p of t he mai n l i ne power suppl y. For each el evat or , pr ovi de cont r ol wi r i ng connect i ng t he f l ow swi t ch t o a shunt t r i p equi pped ci r cui t br eaker l ocat ed i n t he el evat or machi ne r oom or cont r ol r oom. Upon f l ow of wat er , f l ow swi t ch wi l l i nst ant aneousl y cause openi ng of t he shunt - t r i p c i r cui t br eaker and r emove power f r om t he el evat or . Fl ow swi t ch must al so send a s i gnal t o f i r e al ar m cont r ol panel t o i ndi cat e wat er f l ow condi t i on.

PART 2 PRODUCTS

2. 1 ELEVATOR DESCRI PTI ON

Pr ovi de el evat or syst em t hat compl i es wi t h ASME A17. 1/ CSA B44 i n i t s ent i r et y, ASME A17. 2 i n i t s ent i r et y, and addi t i onal r equi r ement s speci f i ed her ei n. Pr ovi de el evat or syst em t hat meet s or exceeds t he NEI I - 1 Ri de Qual i t y Per f or mance St andar ds Mat r i x ( RQPSM) . Compl y wi t h t he RQPSM " I nt er medi at e Per f or mance" cr i t er i a.

Pr ovi de and i nst al l el evat or s i n accor dance wi t h 36 CFR 1191 - ABAAS, I CC I BC, I EEE C62. 41, NFPA 70 and NFPA 101 r equi r ement s.

2. 1. 1 El evat or Desi gn Par amet er s

a. Type: I n- Gr ound Di r ect Pl unger

b. Rat ed l oad: 6, 500 l b.

c. Rat ed Speed: 125 f pm

d. Car I nsi de Di mensi ons: 7 f t . 8 i n. wi de, 8 f t . 2. 5 i n. deep and 8 f t .

0 i n. hi gh

e. Hoi st way Door Type & Si ze: Power oper at ed Ver t i cal Bi - Par t i ng 7 f t . 8 i n. wi de and 8 f t . 0 i n. hi gh f . Car Gat e Type: Power oper at ed, sol i d Ver t i cal Ri s i ng

g. Loadi ng Type: Cl ass C- 3, Desi gned f or passenger use.

2. 1. 2 Cab Encl osur e and Hoi st way Ent r ance Assembl i es

Pr ovi de f i ni shes as l i s t ed bel ow:

a. Fl oor ; 1/ 4" al umi num di amond pl at e, pai nt wi t h MPI ( Mast er Pai nt er ' s I nst i t ut e) #82 compl i ant epoxy- based f l oor pai nt ( Gr ay) .

b. Shel l : Pr ovi de a br ushed st ai nl ess st eel cab manuf act ur ed f r om 14- gauge sheet st eel and pai nt ed wi t h epoxy- based pai nt , Pr oper l y

SECTI ON 14 24 13 Page 7 Jul y 24, 2024

Flynn, Britton Cloud br ace and suppor t cab wal l s. Wi dt h and l engt h of t he cab shal l be desi gned t o mat ch t he exi st i ng pl at f or m. Desi gn f r ont s t o mat ch hoi st way ent r ances. Desi gn cab f or maxi mum al l owabl e hei ght under cr osshead. Col or as sel ect ed by t he Cont r act i ng Of f i cer . Pr ovi de sound- deadeni ng mast i c t o ext er i or .

c. Cei l i ng: Pr ovi de new 12- gauge br ushed st ai nl ess st eel . Ar r ange f or hi nged emer gency exi t per code r equi r ement s.

d. Li ght i ng: Pr ovi de r ecessed l i ght i ng mount ed i n t he cei l i ng. Ut i l i ze ener gy ef f i c i ent LED Li ght i ng syst em.

2. 2 ELEVATOR OPERATI ON

ASME A17. 1/ CSA B44, I nt r oduct i on, Sect i on 3, Def i ni t i ons.

2. 2. 1 Si ngl e, Two- St op, Aut omat i c Oper at i on

Pr ovi de Si ngl e Two- St op Aut omat i c Oper at i on.

2. 3 SPECI AL OPERATI ON AND CONTROL

Pr ovi de t he f ol l owi ng speci al oper at i ons and cont r ol syst ems.

2. 3. 1 Keys f or El evat or Key Swi t ches

Pr ovi de a mi ni mum of t wel ve keys per uni que cyl i nder used on al l key swi t ches f or a s i ngl e el evat or . I f t her e i s mor e t han one el evat or , addi t i onal keys wi l l not be r equi r ed unl ess t her e ar e addi t i onal uni que l ock cyl i nder s. Pr ovi de keys wi t h br ass or f i ber gl ass t ags mar ked " PROPERTY OF THE U. S. GOVERNMENT" on one si de wi t h f unct i on of key or appr oved code number on t he ot her s i de.

2. 3. 2 Fi r ef i ght er s ' Emer gency Oper at i on ( FEO)

Pr ovi de FEO equi pment and si gnal i ng devi ces. The desi gnat ed l evel f or t he FEO Phase I key oper at ed swi t ch i s t he gr ound f l oor . I n t he FEO Phase I f i x t ur e, pr ovi de FEO Oper at i ng I nst r uct i ons.

2. 3. 2. 1 Fi r ef i ght er s ' Emer gency Oper at i on ( FEO) Key Box

Pr ovi de f l ush mount ed, l ocki ng, FEO Key Box of a mi ni mum si ze of 5 i nch W by 9 i nch H by 1. 5 i nch D. I nst al l at a hei ght of 6 f eet above f l oor l evel and di r ect l y above t he FEO Phase I key swi t ch. Pr ovi de box equi pped wi t h l ock t hat uses t he FEO K1 key.

2. 3. 3 Hoi st way Access Oper at i on

Pr ovi de hoi st way access oper at i on wi t h swi t ches at t op and bot t om t er mi nal l andi ngs. Locat e swi t ch 6 f eet above f l oor l evel , wi t hi n 12 i nches of el evat or hoi st way ent r ance f r ame or wi t h t he f er r ul e exposed when l ocat ed i n t he el evat or ent r ance f r ame.

2. 3. 4 I n- Car I nspect i on Oper at i on

Pr ovi de I n- Car I nspect i on Oper at i on.

SECTI ON 14 24 13 Page 8

2. 3. 5 I ndependent Ser vi ce

Pr ovi de exposed key- oper at ed swi t ch i n car oper at i ng panel t o enabl e i ndependent ser vi ce and si mul t aneousl y di sabl e i n- car s i gnal s and l andi ng- cal l r esponses. Pr ovi de i ndi cat or l i ght s t hat aut omat i cal l y i l l umi nat e dur i ng i ndependent ser vi ce.

2. 3. 6 El evat or Auxi l i ar y Power Oper at i ng Syst em

Pr ovi de el evat or emer gency auxi l i ar y power oper at i ng syst em f or el evat or .

Pr ovi de a separ at e bat t er y power ed uni t t hat senses l oss of power . Bat t er y shal l be 12- vol t mi ni mum, seal ed ni ckel cadmi um or gel cel l const r uct i on.

When l oss of power occur s, el evat or shal l descend t o l owest l andi ng and open door s aut omat i cal l y. Af t er a pr edet er mi ned t i me, t he door s shal l c l ose, and t he el evat or shal l r emai n i noper at i ve unt i l nor mal power i s r est or ed. The door open but t on shal l oper at e under bat t er y power .

2. 4 ELEVATOR DRI VE SYSTEM

Pr ovi de hydr aul i c el evat or dr i ve syst em, i ncl udi ng pump uni t , pi pi ng, cyl i nder / pl unger assembl y, and associ at ed equi pment , whi ch wi l l oper at e at a maxi mum wor ki ng pr essur e of 500 psi or l ess. Pr ovi de compl et e el evat or syst em t hat meet s or exceeds t he NEI I - 1 Ri de Qual i t y St andar d, i ncl udi ng el evat or r i de qual i t y and noi se l evel s i n car and i n el evat or machi ne r oom and machi ner y space. Ar r ange equi pment i n machi ne r oom t o meet al l NEC cl ear ances. Pr ovi de a s i ght gl ass mount ed i n t he s i de of t he t ank and appr opr i at e mar ks f or oi l l evel .

2. 4. 1 Hydr aul i c Pump Uni t

Pr ovi de sel f - cont ai ned pump uni t , i ncl udi ng oi l - hydr aul i c el evat or pump, el ect r i c mot or , suct i on- l i ne oi l st r ai ner , and st r uct ur al st eel out er base wi t h t ank suppor t s and i sol at i on pads. Pr ovi de oi l t ank capaci t y f or f ul l pl unger di spl acement pl us at l east 10 gal l ons. Pr ovi de means t o mai nt ai n oi l t emper at ur e bet ween 100 and 130 degr ees F r egar dl ess of ambi ent t emper at ur e i ncl udi ng necessar y di sconnect i ng means f or oi l cool er / heat er .

Li mi t acoust i c out put i n el evat or machi ne r oom and machi ner y space t o 80 dbA.

2. 4. 1. 1 Pump Mot or

Pr ovi de i nt er mi t t ent - dut y pump mot or r at ed at 120 st ar t s/ hour . Pr ovi de mot or t hat i s s i zed so t hat t he mot or amper age does not exceed t he mot or dat a t ag amper age i n any oper at i ng condi t i on, excl usi ve of accel er at i on and decel er at i on. Pr ovi de mi ni mum of one mega ohm i nsul at i on r esi st ance bet ween conduct or s and mot or f r ame. Pr ovi de mot or and pump namepl at e and dat a t ags per manent l y mount ed on t he out si de of t he pump uni t f r ame, wi t h al l dat a v i ewabl e wi t hout t he use of mi r r or s or ot her t ool s. Cont r act or shal l ver i f y t hat t he el ect r i cal r equi r ement s have been pr oper l y account ed f or el evat or equi pment .

2. 4. 2 Hydr aul i c Cont r ol s and Equi pment

Pr ovi de cont r ol val ve, over speed saf et y val ve, bl owout - pr oof muf f l er , and hydr aul i c pump di schar ge st r ai ner i n t he hydr aul i c oi l suppl y l i ne.

Pr ovi de t wo 1/ 4 t ur n, bal l val ve t ype manual shut of f val ves. Pr ovi de one i n t he el evat or hoi st way pi t and one i n t he el evat or machi ne r oom or machi ner y space. Basi s of desi gn: Maxt on.

SECTI ON 14 24 13 Page 9

a. Shal l have t he f ol l owi ng val ves, capabl e of bei ng ext er nal l y adj ust ed:

r el i ef val ve, up- st ar t val ve, up- l evel val ve, down val ve.

b. Shal l be equi pped wi t h a check val ve capabl e of suppor t i ng f ul l y l oaded car .

c. Shal l be equi pped wi t h manual l ower i ng val ve t o l ower car i n t he event of power f ai l ur e/ equi pment f ai l ur e.

d. Shal l have a manual shut - of f val ve t o i sol at e oi l t o adj ust el evat or wi t hout r emovi ng oi l f r om t ank.

e. Shal l be equi pped wi t h a l ow- pr essur e swi t ch.

f . Shal l have st eel s l eeve i nser t s i n t he val ve body.

g. Shal l have t hr eaded l i ne connect i ons.

h. Shal l have f eedback cont r ol f or st al l f r ee oper at i on.

i . Shal l have i ndi v i dual i zed adj ust ment s.

j . Shal l have hi gh ef f i c i ency sol enoi ds.

k. Val ve shal l be f act or y t est ed and have a t wo- year war r ant y.

2. 4. 2. 1 Hydr aul i c Cont r ol Val ve

Pr ovi de const ant - vel oci t y, down- speed r egul at ed, cont r ol val ve.

Down- speed r egul at ed cont r ol val ve al l ows t he car t o t r avel at t he same speed i n t he down di r ect i on, r egar dl ess of t he l oad on t he el evat or . I n addi t i on, t he hydr aul i c cont r ol val ve must have bui l t - i n adj ust ment capabi l i t y t o oper at e t he el evat or at 140 per cent of r at ed speed t o f aci l i t at e per i odi c t est i ng of t he over speed saf et y val ve.

2. 4. 2. 2 Hydr aul i c Over speed Saf et y Val ve

Pr ovi de over speed saf et y val ve i n hydr aul i c oi l suppl y l i ne, di r ect l y adj acent t o t he hydr aul i c cyl i nder . Pr ovi de t hr eaded pi pe connect i ons bet ween t he hydr aul i c cyl i nder and t he over speed val ve. Pr ovi de val ve equi pped wi t h manuf act ur er ' s manual shut of f f eat ur e. Over speed val ve must not be equi pped wi t h a manual or aut omat i c l ower i ng f eat ur e. Pr ovi de adj ust abl e val ve wi t h means t o seal adj ust ment af t er i nspect i on and t est i ng by cer t i f i ed el evat or i nspect or .

2. 4. 2. 3 Hydr aul i c Oi l Scavenger Pump

Pr ovi de a new scavenge oi l r eser voi r wi t h st r ai ner and t r ansf er pump.

Pr ovi de a manual - r eset pi t f l ood swi t ch t o pr event pump oper at i on i f pi t i s f l ooded. Anchor pump and r eser voi r t o pi t f l oor .

2. 4. 3 Hydr aul i c Pi pi ng and Accessor i es

Pr ovi de ASTM A53/ A53M or ASTM A106/ A106M, Schedul e 80, bl ack st eel pi pi ng wi t h ASME B16. 9 or ASME B16. 11 f i t t i ngs f or suppl y pi pi ng. Ext end schedul e 80 pi pi ng f r om t he pump cont r ol val ve body, i nsi de t he pump uni t , t o t he hydr aul i c cyl i nder i n t he hoi st way. Pr ovi de wel ded or t hr eaded f or ged pi pe f i t t i ngs f or al l f i t t i ngs and component s of t he hydr aul i c oi l suppl y l i ne. For i n- gr ound di r ect pl unger cyl i nder s, pr ovi de di el ect r i c

SECTI ON 14 24 13 Page 10 uni on or i sol at i on coupl i ngs at each end of t he hydr aul i c oi l suppl y l i ne. Pr ovi de hanger s or suppor t s f or al l pi pi ng and component s.

2. 4. 3. 1 Cont ai nment of Hydr aul i c Oi l Suppl y Li ne

Pr ot ect al l por t i ons of hydr aul i c oi l suppl y l i ne t hat ar e i nst al l ed bel ow gr ound, i ncl udi ng por t i ons encapsul at ed i n concr et e or cover ed by const r uct i on, wi t h cont i nuous, Schedul e 80, PVC. I nsi de di amet er of PVC must be 3 i nches l ar ger t han t he out si de di amet er of t he hydr aul i c oi l suppl y l i ne pi pe and coupl i ngs. Pi pi ng ( Shut - of f Val ves and I so- Uni ons)

a. Pr ovi de t wo bal l val ves - One l ocat ed i n machi ne r oom and one i n el evat or pi t .

i . Bal l val ves shal l be f ul l por t , ¼ t ur n val ves.

i i . Bal l val ves shal l be st ai nl ess st eel , sui t abl e f or use wi t h hydr aul i c oi l .

b. Pr ovi de t wo i so- uni ons - One l ocat ed i n t he machi ne r oom and one i n el evat or pi t .

2. 4. 4 Hydr aul i c El evat or Type

Pr ovi de a i n- gr ound di r ect pl unger t ype hydr aul i c el evat or . El evat or wi t h t el escopi c or i nver t ed cyl i nder - pl unger s ar e not accept abl e and may not be used. Rope hydr aul i c el evat or desi gn i s not accept abl e and may not be used.

2. 4. 4. 1 Cyl i nder - Pl unger ( Jack) Uni t

Pr ovi de a s i ngl e- st age pl unger of seaml ess st eel const r uct i on. Pr ovi de cyl i nder wi t h sel f - st abi l i z i ng mount t hat wi l l suppor t and hol d cyl i nder pl umb wi t hout t he need f or st abi l i zat i on means at t he bot t om of t he cyl i nder . Pr ovi de a t hr eaded, 1/ 4 i nch bl eeder val ve at t he t op of t he cyl i nder , j ust bel ow packi ng gl and. Wel d a st op pl at e t o t he bot t om of t he pl unger t o act as a posi t i ve st op when ext endi ng t he pl unger f ul l y .

The cyl i nder head shal l cont ai n a sui t abl e gui de bear i ng and packi ng gl and. Pr ovi de t he t op of t he cyl i nder wi t h a cyl i nder head i ncl udi ng dr i p r i ng t o col l ect any oi l seepage as wel l as an i nt er nal gui de r i ng and sel f - adj ust i ng packi ng. Tr eat t he exposed out er sur f ace of t he cyl i nder wi t h r ust i nhi bi t i ng and cor r osi on r esi st ant compound. Pr ovi de an auxi l i ar y saf et y bul khead i n t he l ower end of t he cyl i nder . I ncl ude a st eel packi ng gl and wi t h a phenol i c gui de bear i ng, wi per r i ng, and packi ng especi al l y desi gned f or hydr aul i c el evat or ser vi ce. I f pr ovi di ng mul t i pl e sect i on j acks, shal l have machi ned t hr eaded coupl i ngs wi t h O- Ri ng seal s t o pr event l eakage. The ext er i or sur f ace of i n- gr ound hydr aul i c cyl i nder s must be f act or y ?ni shed wi t h a mi ni mum 50 mi l s coat i ng of ei t her Appl i ed Ext r uded Coat i ng or Epoxy Resi n. The t op of t he j ack shal l i ncl ude a namepl at e wi t h t he manuf act ur er , t ype and model , and year of manuf act ur e.

2. 4. 5 Cyl i nder Wel l Syst em

For di r ect pl unger , i n- gr ound t ype hydr aul i c el evat or , pr ovi de a dr y, seal ed cyl i nder wel l syst em.

2. 4. 5. 1 Wel l Casi ng

Locat e and dr i l l wel l f or t he cyl i nder wel l syst em. Li ne wel l wi t h st eel casi ng, mi ni mum 1/ 4 i nch wal l wi t h wel ded 1/ 2 i nch st eel bot t om. Set casi ng pl umb.

SECTI ON 14 24 13 Page 11

2. 4. 5. 2 PVC or HDPE Li ner

Pr ovi de Schedul e 80 PVC or HDPE l i ner wi t h bot t om cap and coupl i ngs;

j oi nt s seal ed wat er t i ght usi ng pi pe manuf act ur er ' s r ecommended adhesi ve or heat wel di ng met hods. Pr ovi de l i ner i nsi de di amet er not l ess t han 3 i nches l ar ger t han el evat or cyl i nder maxi mum out si de di amet er . Li ner may be pr ovi ded as a cyl i nder manuf act ur e' s appl i ed l i ner or as a separ at e component . For separ at e l i ner , set l i ner pl umb i n wel l casi ng, l ocat ed f or cyl i nder i nst al l at i on. Pr ovi de dr y, sal t - f r ee sand bel ow and ar ound l i ner t o t op of wel l casi ng.

2. 4. 5. 3 Cyl i nder I nst al l at i on

Remove al l moi st ur e f r om i nsi de of l i ner . I nst al l cyl i nder pl umb, i nsi de l i ner . Pr ovi de a 1/ 4 i nch copper evacuat i on t ube i nsi de t he l i ner . The bot t om of t he evacuat i on t ube must be wi t hi n 6 i nch of t he bot t om of t he l i ner . Top of evacuat i on t ube must ext end at l east 6 i nch above pi t f l oor . Pr ovi de t op of t est t ube wi t h r emovabl e cap t o excl ude f or ei gn mat t er . Pr ovi de ai r i nl et pr essur e f i t t i ng i n t op of l i ner and accessi bl e i n pi t , f or per f or mance of ai r pr essur e t est . Secur e Li ner / Cyl i nder Assembl y as r ecommended by cyl i nder manuf act ur er .

2. 4. 5. 4 Cyl i nder Li ner Moi st ur e Sensor Syst em

Pr ovi de moi st ur e and oi l sensor s i nsi de t he cyl i nder l i ner f or det ect i on of oi l and wat er at t he bot t om of t he cyl i nder l i ner . Pr ovi de sensor moni t or i ng syst em t hat wi l l act uat e audi bl e and vi sual al ar ms and i dent i f y t he pr esence of wat er and i dent i f y t he pr esence of oi l i nsi de t he l i ner .

2. 4. 5. 5 Seal Top of Wel l Casi ng

Upon successf ul t est and cer t i f i cat i on of Li ner / Cyl i nder assembl y, seal gap bet ween st eel wel l casi ng and l i ner wi t h f oam i nser t st r ong enough t o r et ai n and suppor t f i nal gr out i ng. Pr ovi de 3000 psi gr out t o a mi ni mum of 4 i nch t hi ckness and l evel t op of f i nal gr out i ng wi t h pi t f l oor .

2. 5 CONTROL EQUI PMENT

Encl ose al l el evat or cont r ol equi pment i n f act or y- pr i med and baked- enamel coat ed sheet - met al cabi net s wi t h vent i l at i on l ouver s and r emovabl e or hi nged door s. Mount cabi net s at a hei ght of 10 i nches above machi ne r oom or cont r ol r oom f i ni sh f l oor .

2. 5. 1 Mot or Cont r ol Equi pment

Pr ovi de el evat or mot or cont r ol wi t h el ect r oni c, sof t - st ar t mot or st ar t er .

Basi s of Desi gn: Si emens Sol i d St at e Mot or St ar t er .

a. Uni t shal l be capabl e of pr event i ng hi gh i nr ush and el i mi nat e vol t age di ps when power uni t st ar t s.

b. Shal l have phase pr ot ect i on ( phase r ever sal & phase l oss)

c. Adj ust abl e cur r ent l i mi t ( 10% t o 450% of st ar t er r at i ng)

d. Be equi pped wi t h an LCD scr een and keypad f or di agnost i c i nf or mat i on.

e. Hand- Hel d mPAC user I nt er f ace al so be pr ovi ded.

SECTI ON 14 24 13 Page 12

2. 5. 2 El evat or Mi cr opr ocessor Cont r ol l er

For each i ndi v i dual el evat or cont r ol l er , and f or each gr oup cont r ol l er , pr ovi de a mi cr opr ocessor cont r ol l er t hat compl i es wi t h t he f ol l owi ng par agr aphs. Pr ovi de cont r ol l er ( s) package t hat i ncl udes al l har dwar e and sof t war e r equi r ed f or t he i nst al l at i on, mai nt enance, and ser vi ce of t he el evat or , i n i t s ' ent i r et y. Pr ovi de ver i f i cat i on of t echni cal suppor t ser vi ce t hat t he cont r ol l er manuf act ur er pr ovi des t o any l i censed el evat or i nst al l at i on, ser vi ce, and mai nt enance company. The cont r ol l er must be manuf act ur ed and sol d by an el evat or cont r ol l er manuf act ur er t hat does not engage i n i nst al l at i on, ser vi ce, or mai nt enance of el evat or s. Basi s of desi gn: Mot i on Cont r ol s Engi neer i ng, I nc.

Pr ovi de an el evat or cont r ol l er f r om a manuf act ur er t hat pr ovi des compr ehensi ve f act or y t r ai ni ng t o i ncl ude cont r ol l er i nst al l at i on, adj ust ment , ser vi ce, and mai nt enance. The t r ai ni ng must be i dent i f i ed as avai l abl e t o any l i censed el evat or cont r act or . Pr ovi de ver i f i cat i on of an est abl i shed and document ed t r ai ni ng schedul e, wi t h pr i c i ng, f or f act or y t r ai ni ng cl asses t hat manuf act ur er has pr ovi ded f or a mi ni mum per i od of one year pr i or t o cont r act awar d dat e.

The el evat or cont r ol l er must be i dent i f i ed as avai l abl e f or pur chase and i nst al l at i on by any l i censed el evat or cont r act or . Al l component s, par t s, di agnost i c t ool s, and sof t war e must be avai l abl e f or pur chase and i nst al l at i on and use by any l i censed el evat or cont r act or ; " exchange- onl y" pr ovi s i ons f or t he pur chase of spar e par t s ar e not accept abl e. The el evat or cont r ol l er manuf act ur er must publ i sh an i ndust r y compet i t i ve pr i ce l i s t i ng f or al l cont r ol l er par t s, di agnost i c t ool s, and sof t war e.

Pr ovi de ver i f i cat i on of t el ephone and i nt er net based t echni cal suppor t ser vi ce t hat t he el evat or cont r ol l er manuf act ur er pr ovi des t o any l i censed el evat or i nst al l at i on, ser vi ce, and mai nt enance company at an i ndust r y compet i t i ve pr i ce. The ser vi ce must i ncl ude l i ve t el ephone based t echni cal suppor t f or i nst al l at i on, adj ust ment , mai nt enance, and t r oubl eshoot i ng of t he el evat or cont r ol l er and r el at ed el evat or component s. The ser vi ce must be avai l abl e dur i ng st andar d wor ki ng hour s.

Pr ovi de an el evat or cont r ol l er t hat i s desi gned t o aut omat i cal l y r eest abl i sh nor mal el evat or oper at i on f ol l owi ng any t empor ar y l oss of power , r egar dl ess of dur at i on.

a. Cont r ol l er shal l be capabl e of bei ng t i ed i n BAS.

b. Hi gh or Low Speed I nspect i on Sel ect i on

c. Pr ogr ammabl e door oper at i on

d. Cal l r egi st r at i on t hr ough on- boar d LCD, Keypad, or HMI .

e. Level i ng wi t hi n 3/ 16" f . Pr ogr ammabl e Fi r e Code Opt i ons/ Fi r e Fl oor s

g. Mot or Li mi t Ti mer

h. Val ve Li mi t Ti mer i . Vi scosi t y Cont r ol

SECTI ON 14 24 13 Page 13 j . Out of ser vi ce t i mer

k. Bat t er y Lower i ng Devi ce

2. 5. 2. 1 El evat or Cont r ol l er I nt er f ace Cabi net

For each i ndi v i dual el evat or mi cr opr ocessor cont r ol l er , pr ovi de a separ at e el evat or cont r ol cabi net wi t h an i nt egr at ed human i nt er f ace syst em. For gr oup el evat or i nst al l at i ons, a s i ngl e cabi net and i nt er f ace syst em wi t h f ul l access t o each el evat or cont r ol l er may be ut i l i zed. The separ at e cont r ol l er i nt er f ace cabi net must be suppl i ed by t he el evat or cont r ol l er manuf act ur er and i ncl ude a mi ni mum 12 i nch wi de keyboar d and a mi ni mum 10 i nch moni t or . The el evat or cont r ol l er i nt er f ace cabi net must compl y wi t h ar c- f l ash pr ot ect i on r equi r ement s of NFPA 70E and UFC 3- 560- 01. I nt er f ace syst em must connect di r ect l y t o cont r ol l er and not use wi f i or bl uet oot h t o connect .

2. 5. 2. 1. 1 El evat or Mi cr opr ocessor Human I nt er f ace

The i nt er f ace syst em must pr ovi de compl et e el evat or cont r ol l er i nt er f ace capabi l i t y and must i ncl ude t he el evat or cont r ol l er manuf act ur er ' s compr ehensi ve package of i nst al l at i on and di agnost i c sof t war e. The mi cr opr ocessor i nt er f ace syst em must pr ovi de unr est r i ct ed access t o al l par amet er s, al l l evel s of adj ust ment , and al l f l ags necessar y f or i nst al l at i on, adj ust ment , mai nt enance, and t r oubl eshoot i ng of each el evat or and f or t he el evat or gr oup. Al l sof t war e pr ogr ammi ng must be st or ed i n non- vol at i l e memor y. The el evat or cont r ol l er f aul t l og must pr ovi de non- vol at i l e memor y f aul t l og st or age of al l f aul t s, t r oubl e cal l s, and f aul t hi st or y f or a mi ni mum of one year and t he abi l i t y t o downl oad or pr i nt t he f aul t l og. The cont r ol l er i nt er f ace must al so pr ovi de t he capabi l i t y t o di spl ay and di agnose t r oubl e cal l s, f aul t s, and shut downs. Expi r i ng sof t war e, degr adi ng oper at i on, and " key" access cont r ol s ar e not accept abl e.

2. 5. 2. 2 Sof t war e and Document at i on

Pr ovi de t hr ee copi es of t he manuf act ur er ' s mai nt enance and ser vi ce di agnost i c sof t war e, wi t h compl et e sof t war e document at i on, t hat wi l l enabl e t he same l evel of unr est r i ct ed access t o al l cont r ol l er s of t he same make and model , r egar dl ess of t he i nst al l at i on dat e or l ocat i on.

Pr ovi de si gned cer t i f i cat i on, f r om t he manuf act ur er ' s cor por at e headquar t er s, t hat guar ant ees t hat t he mi cr opr ocessor sof t war e and access syst em wi l l not t er mi nat e t he unl i mi t ed and unr est r i ct ed access at any f ut ur e dat e.

2. 5. 2. 3 El evat or Cont r ol l er Cer t i f i cat i on

For el evat or i nst al l at i ons i n t he Uni t ed St at es, i ncl udi ng Uni t ed St at es t er r i t or i es, pr ovi de an el evat or mi cr opr ocessor cont r ol l er t hat has a cur r ent cer t i f i cat e of saf et y code compl i ance i ssued by t he Techni cal St andar ds and Saf et y Aut hor i t y ( TSSA) , Tor ont o, Canada.

2. 6 OPERATI NG PANELS, SI GNAL FI XTURES, AND COMMUNI CATI ONS CABI NETS

For al l panel s and f i xt ur es, pr ovi de i dent i cal and uni f or m panel and f i xt ur e desi gn, mat er i al , f i ni sh, and component s f or al l el evat or s. For al l panel s and f i xt ur es, l egi bl y and i ndel i bl y i dent i f y al l but t ons, devi ces, and al l oper at i ng posi t i ons f or each devi ce. Use engr avi ng and

SECTI ON 14 24 13 Page 14 backf i l l i ng, not phot o et chi ng, f or but t on and devi ce desi gnat i ons. Do not use at t ached si gns. Pr ovi de el evat or manuf act ur er s ' st andar d gr ade f or al l key swi t ches unl ess ot her wi se speci f i ed. Al l i l l umi nat i ng panel s and f i xt ur e component s must ut i l i ze LED l i ght i ng f or ener gy ef f i c i ency.

Basi s of Desi gn: I nnovat i on I ndust r i es, I nc.

2. 6. 1 Car and Hal l But t ons

For al l cab and l andi ng f i xt ur e but t ons, pr ovi de i ndust r y- st andar d, vandal r esi st ant push but t ons wi t h posi t i ve- st op assembl y desi gn. But t ons must be mi ni mum 3/ 4 i nch di amet er , sat i n- f i ni sh st ai nl ess st eel , wi t h i l l umi nat i ng LED hal o.

2. 6. 1. 1 Hal l St at i on Door - Oper at i ng But t ons

Pr ovi de hal l st at i on door - oper at i ng but t ons, i dent i cal i n s i ze and desi gn t o hal l cal l but t ons, but not i l l umi nat i ng. Pr ovi de communi cat i on f ai l ur e i ndi cat or as r equi r ed by code. Pr ovi de an " Out of Ser vi ce" l i ght i n t he hal l st at i on as wel l as f r ei ght door oper at i ng but t ons i n hal l f i x t ur es.

2. 6. 2 Fr ei ght Car - Oper at i ng Panel

Pr ovi de each car wi t h one car oper at i ng panel t hat cont ai ns oper at i on cont r ol s and communi cat i on devi ces. Pr ovi de exposed, f l ush mount ed but t ons f or t he cont r ol s i dent i f i ed i n subpar agr aph OPERATOR CONTROLS.

Pr ovi de a l ockabl e ser vi ce cabi net f or t he cont r ol s l i s t ed i n subpar agr aph SERVI CE CONTROLS. Use engr avi ng and backf i l l i ng not phot o et chi ng f or but t on and swi t ch desi gnat i ons. Do not use at t ached si gns.

2. 6. 2. 1 Oper at or Cont r ol s

I n addi t i on t o ASME A17. 1/ CSA B44 r equi r ement s, pr ovi de t he f ol l owi ng oper at i ng cont r ol s, i dent i f i ed as i ndi cat ed:

a. I l l umi nat i ng car - cal l but t ons i dent i f i ed t o cor r espond t o l andi ngs ser ved by t he el evat or .

b. " DOOR OPEN" and " DOOR CLOSE" but t ons. For f r ont and r ear openi ngs at t he same f l oor , i ncl ude t he i dent i f i cat i on " F" and " R" f or each openi ng.

c. Red, i l l umi nat i ng " ALARM" but t on.

d. Key- oper at ed " I ndependent Ser vi ce" swi t ch.

e. " Hel p" communi cat i on devi ce t o i ncl ude communi cat i on bet ween el evat or cab and el evat or machi ne r oom or cont r ol r oom.

f . Emer gency t wo- way communi cat i on. Pr ovi de moment ar y pr essur e, s i ngl e i l l umi nat i ng pushbut t on oper at ed communi cat i on devi ce t hat compl i es wi t h ASME A17. 1/ CSA B44, UFAS, and t he Amer i cans wi t h Di sabi l i t i es Act .

g. Voi ce annunci at or . Pr ovi de a new voi ce annunci at or manuf act ur ed by CE El ect r oni cs, I nc. Uni t t o mat ch st y l e and model t hat has been pr evi ousl y i nst al l ed on ot her el evat or s i n bui l di ng. Pr ovi de a uni t wi t h t he f ol l owi ng voi ce messages i n a f emal e voi ce.

1. Fi r st f l oor , second f l oor , et c.

SECTI ON 14 24 13 Page 15

2. Goi ng up.

3. Goi ng down.

4. Thi s el evat or i s now i n f i r e r et ur n. When t he door s open, pl ease exi t t he bui l di ng i n a saf e and or der l y manner .

5. Pl ease st and cl ear of t he c l osi ng door s.

6. Thi s el evat or i s now on i ndependent ser vi ce.

7. Thi s el evat or i s i n over l oad st at us. Pl ease r emove par t of t he l oad t o r esume ser vi ce.

8. Thi s car i s now on i nspect i on ser vi ce.

9. Thi s el evat or i s needed because of an emer gency. Pl ease exi t t he el evat or when t he door s open.

2. 6. 2. 2 Ser vi ce Cont r ol s

I n addi t i on t o ASME A17. 1/ CSA B44 r equi r ement s, pr ovi de t he f ol l owi ng oper at i ng cont r ol s, i dent i f i ed as i ndi cat ed:

a. Pr ovi de a key- oper at ed, t hr ee- posi t i on swi t ch f or " I n car I nspect i on Oper at i on" and " Hoi st way Access" . The cent er swi t ch posi t i on wi l l pr ovi de nor mal , aut omat i c oper at i on.

b. " Car Li ght " swi t ch.

c. " Car Fan" swi t ch wi t h t wo speed set t i ngs i dent i f i ed.

d. 120- vol t ac 60 Hz si ngl e- phase dupl ex el ect r i cal out l et of gr ound- f aul t - c i r cui t - i nt er r upt ( GFCI ) desi gn.

2. 6. 2. 3 Cer t i f i cat e Wi ndow

Pr ovi de a mi ni mum 4 i nch wi de by 6 i nch hi gh cer t i f i cat e wi ndow f or el evat or i nspect i on cer t i f i cat e. Locat e wi ndow i n t he Ser vi ce Cont r ol s door of t he Car Oper at i ng Panel .

2. 6. 2. 4 Emer gency Si gnal i ng Devi ces

Pr ovi de an audi bl e s i gnal i ng devi ce, oper abl e f r om t he Car Oper at i ng Panel but t on mar ked " ALARM" . The audi bl e s i gnal i ng devi ce must have a sound pr essur e r at i ng bet ween 80 and 90 dBA at 10 f t . Pr ovi de bat t er y backup power capabl e of oper at i ng t he audi bl e s i gnal i ng devi ce f or at l east 1 hour .

2. 6. 3 El evat or I n- Car Posi t i on I ndi cat or s

For al l el evat or s, pr ovi de i l l umi nat i ng posi t i on i ndi cat or i n t he Car Oper at i ng Panel .

2. 6. 4 El evat or I n- Car Di r ect i on I ndi cat or s

For 2- st op el evat or i nst al l at i ons, pr ovi de vi sual di r ect i on i ndi cat or s and audi bl e car ar r i val s i gnal i n t he el evat or car door j amb, i n accor dance wi t h ABA St andar ds. Vi sual i ndi cat or s must be vi s i bl e f r om t he hal l cal l f i x t ur e.

2. 6. 5 Hal l Cal l Landi ng Fi xt ur es

Pr ovi de a hal l cal l f i x t ur e adj acent t o each el evat or . Pr ovi de a s i ngl e push- but t on f or t er mi nal l andi ngs.

SECTI ON 14 24 13 Page 16

2. 6. 5. 1 Desi gnat ed Landi ng Hal l Cal l Fi xt ur e

2. 6. 5. 1. 1 Locat i on of COMMUNI CATI ON MEANS FAI LURE ( CMF) Vi sual Si gnal

When r equi r ed by ASME A17. 1/ CSA B44, pr ovi de an el evat or CMF audi bl e and i l l umi nat i ng s i gnal , and r eset swi t ch, i n t he FEO Desi gnat ed Landi ng hal l cal l f i x t ur e. Mount t he s i gnal and r eset swi t ch at a mi ni mum of 7 i nches above t he " UP" hal l cal l but t on.

2. 6. 5. 1. 2 COMMUNI CATI ON MEANS FAI LURE ( CMF) Vi sual and Audi bl e Si gnal Oper at i on

Pr ovi de a CMF vi sual and audi bl e s i gnal syst em t hat conf or ms t o ASME A17. 1/ CSA B44. Pr ovi de cont i nuous ver i f i cat i on of oper abi l i t y of t he t el ephone l i ne and i mmedi at e act i vat i on of audi bl e and vi sual s i gnal s when ver i f i cat i on means det er mi nes t hat t he t el ephone l i ne i s not f unct i oni ng.

Pr ovi de i l l umi nat i on of v i sual s i gnal at one second i nt er val s. Pr ovi de a mi ni mum of 65 dBA audi bl e s i gnal at 30 second i nt er val s.

2. 6. 5. 1. 3 Fi r ef i ght er s ' Emer gency Oper at i on Phase I Swi t ch and Vi sual Si gnal

When r equi r ed by ASME A17. 1/ CSA B44, pr ovi de an el evat or Fi r ef i ght er s ' Emer gency Oper at i on Phase I swi t ch and i l l umi nat i ng v i sual s i gnal i n t he FEO Desi gnat ed Landi ng hal l cal l f i x t ur e. Pr ovi de FEO Phase I v i sual s i gnal t hat i s desi gned wi t h i nt er mi t t ent , f l ashi ng, i l l umi nat i on when act uat ed by t he machi ne r oom, cont r ol r oom or hoi st way f i r e al ar m i ni t i at i ng devi ce. Locat e FEO Phase I key swi t ch above t he CMF vi sual s i gnal wi t h a mi ni mum of 6 i nches ver t i cal bet ween t he cent er l i nes of t he CMF si gnal and t he FEO Phase I key swi t ch. Locat e FEO Phase I v i sual s i gnal di r ect l y above t he Phase I swi t ch. I n addi t i on, l ocat e El evat or Cor r i dor Cal l St at i on Pi ct ogr aph at t op of hal l cal l f i x t ur e.

2. 6. 6 Desi gnat ed Landi ng El evat or I dent i f i cat i on Fi xt ur e

Pr ovi de a separ at e el evat or i dent i f i cat i on f i x t ur e f or each el evat or , wi t h i dent i f i cat i on engr aved and backf i l l ed wi t h a cont r ast i ng col or . Number el evat or s f r om l ef t t o r i ght , as seen dur i ng pr i mar y appr oach f r om bui l di ng mai n ent r ance t o el evat or l obby.

2. 6. 7 Emer gency or St andby Power

When emer gency or st andby power i s pr ovi ded f or el evat or oper at i on, pr ovi de an el evat or emer gency power v i sual i ndi cat or t hat conf or ms t o ASME A17. 1/ CSA B44. Locat e t he v i sual s i gnal i n t he Fi r ef i ght er s Emer gency Oper at i on f i x t ur e f or each si mpl ex el evat or and f or each el evat or gr oup. When an emer gency power sel ect or swi t ch i s r equi r ed, pr ovi de swi t ch i n a separ at e, f l ush mount ed f i xt ur e l ocat ed at t he desi gnat ed l evel , i n v i ew of al l el evat or ent r ances.

2. 7 CAR DOOR EQUI PMENT

2. 7. 1 Car Door Oper at or

Pr ovi de el evat or door oper at or equi pment and ci r cui t r y t hat i s desi gned and i nst al l ed as di scr eet communi cat i on. Ser i al communi cat i on must not be used f or t hi s syst em.

SECTI ON 14 24 13 Page 17

2. 7. 2 I nf r a- r ed Cur t ai n Uni t

Pr ovi de I nf r a- r ed Cur t ai n Uni t ( I CU) wi t h mul t i pl e i nf r a- r ed beams t hat pr ot ect t o t he f ul l hei ght and wi dt h of t he door openi ng. Pr ovi de door nudgi ng oper at i on.

2. 7. 3 Saf et y Edges

Pr ovi de car gat es wi t h f ul l wi dt h pr ot ect i ve devi ce whi ch pr oj ect s beyond t he l eadi ng edge of t he gat e. Gat e shal l aut omat i cal l y r et ur n t o open posi t i on i f i t t ouches a per son or obj ect whi l e c l osi ng.

2. 8 FREI GHT ELEVATOR GUI DES, PLATFORM, AND ENCLOSURE

2. 8. 1 Gui des

Pr ovi de coi l - spr i ng l oaded r ol l er gui de assembl i es i n adj ust abl e mount i ngs on each si de of car f r ames i n accur at e al i gnment at t op and bot t om of f r ames.