This document is an Amendment to Solicitation N4008524R2536 for a Design-Bid-Build contract to renovate Building 77H at the Philadelphia Navy Yard to establish a Land Based Engineering Test Site (LBETS) for the FFG-62 Constellation Class Machinery Plant Test and Evaluation Program. Key details include:
The amendment provides responses to pre-proposal inquiries, reference drawings, and an updated wage determination. It also revises some drawings, including the door schedule and control house first floor plan. The solicitation number is N4008524R2536, and the proposal due date remains unchanged as July 22, 2024. The renovation work includes control rooms, industrial staging areas, shop areas, utility service upgrades, fire protection systems, and demolition of an existing building. The contract will be awarded by the Department of the Navy Naval Facilities Engineering Command.
View the file
Other files
Show 40 more
Latest 50 of 79 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
SOLICITATION NO. N4008524R2536, DESIGN-BID-BUILD, RENOVATE BLDG. 77H, FFG-62 LAND BASED ENGINEERING SITE, PHILADELPHIA
NAVY YARD, PHILADELPHIA, PENNSYLVANIA
The proposal due date of 22 July 2024 NLT 2:00 PM EDT remains unchanged.
See Continuation Page(s).
1. CONTRACT ID CODE PAGE OF PAGES
J 1 24
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 02-Jul-2024
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X N4008524R2536
X 9B. DATED (SEE ITEM 11)
22-May-2024
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
02-Jul-2024
CODE
NAVFACSYSCOM MID-ATLANTIC
CONTRACTING CORE
9324 VIRGINIA AVENUE
NORFOLK VA 23511-3095
N40085 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
N4008524R2536
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)
The following have been added by full text:
AMENDMENT 0003
The purpose of this amendment is to provide the following:
1. Pre-Proposal Inquiry (PPI) Responses
2. Provide reference drawings.
3. Updated Wage Determination
Pre-Proposal Inquiry Responses:
Question # Reference
Question Government Response Page Section
Paragrap h
4 01 91 00 1.1 Who is the independent Commissioning Firm that the Government has hired?
Summer Consultants
5 26 20 00
Are mechanical connections acceptable in lieu of exothermic welds for grounding connections to steel receiving SSPC SP 6 preparation? Exothermic welds are often proven unable to bond to steel with this preparation technique.
If exothermic welds fail, then mechanical connections are an acceptable alternative.
6 05 12 00
Can Torsion Control bolts and direct tension washers be used interchangeably throughout the project?
Generally yes, tension control bolts and DTI washers can be used interchangeably throughout the project.
However, only one type may be used for any given connection.
7 01 31 23 1.6.1
Can the CUI (Controlled Unclassified Information) designation for meeting minutes, schedules, daily reports, invoices, etc. be reclassified as U (Unclassified)? A special secured server location and handling requirements are prescribed for documents possessing the CUI designation under NIST SP 800- 171 protocols.
A thorough review of the detailed information presented in meeting minutes, schedules, daily reports, invoices, etc. is required for the designation to be reclassified from CUI (Controller Unclassified Information) to U (Unclassified).
8 28 31 70
For fire alarm devices with no "subscript" or denotion, is it assumed that these devices are wall mounted?
In general, yes for the notification devices.
9 2P152 Please provide sheet notes for #'s 2-4 on sheet 2P152.
Refer to General Sheet Notes 3 & 4 for Keynotes on plan labeled 3 & 4 respectively
10 General General General
Please advise if there is any restricted off-hour shift time frames. For example, is any time outside of the normal work hours of 7am - 4:30pm acceptable with approval from the Contracting Officer?
A specific reason/net benefit to the customer is required for approval of work outside of normal working hours (i.e.
10–12-hour days and/or weekend work). Escorts are required for off-hours access, and must be coordinated with C/102 at least a week in advance.
11 Div. 21 - 28
Please advise if any of the HVAC/Plumbing/Controls equipment will be pre-purchased by others. If so, please provide the specific equipment. Otherwise, the assumption is that all MEP equipment will be provided by the Contractor.
Assumption is correct. All equipment must be provided by the Contractor.
12 Div. 22 - 23
HVAC/Plumbing equipment schedules and specifications do not provide a basis of design for the manufacturer or model. Who is the basis of design manufacturer/vendor for the scheduled equipment? Or is the intent to provide a manufacturer/vendor that supports the performance specifications provided?
Submitted products are not limited by manufacturer. The only requirement is that the submitted products meet the criteria indicated in the contract documents.
2SD103
/4
Note 7 indicates reference package was provided with solicitation.
Please provide said reference package.
Reference package included with Amendment 0003
14 28 10 05
The access control details do not indicate a type of conduit to be used, nor do the specifications.
There is indication that EMT can be used for interior applications and PVC for underground applications but it does not specifically indicate for access control wiring. Please advise.
Refer to Paragraph 2.5.3 ESS Transmission for conduit requirements related to access control
15 2E503
Existing MCC-09 shown on drawing 2E503 calls for new 100A breakers per keynote #1. Please provide the manufacturer and AIC rating of the existing MCC that the circuit breaker must match.
Existing MCC is Square D Model 6 MCC and has an AIC rating of 65 kAIC.
16 2E504
Existing southwest substation shown on drawing 2E504 calls for a new 500A breaker per keynote #10. Please provide the existing substation manufacturer and required AIC rating that the circuit breaker must match.
Existing Southwest Substation is a Square D substation and has an AIC rating of 65 kAIC.
17 2E505
Drawing 2E505 calls for a number of new bus duct circuit breakers per keynote #2. Please provide the existing manufacturer and required AIC rating of the existing bus duct.
The manufacturer of the bus duct will need to be verified in the field. It is believed to be Cooper Busduct with an AIC rating of 65 kAIC.
18 31 62 00 3.4 What is the wait time between pouring test micropiles to testing test piles?
Grout within micropiles must achieve the required design strength before the micropiles can be loaded.
19 2E602
Drawing 2E602 calls for 'cast-in-place' concrete test wells for the grounding system. Please clarify if the intent is to have 'cast-in-place' concrete test wells for the grounding system or if 'pre-cast' test wells are acceptable.
The intent is to have 'cast-in-place' test wells at both interior and exterior locations.
20 2A603 Please clarify door types "XX" and
"WW"
Door 102 should be Door Type A, not XX. Door 105 should be Door Type C, not
WW.
21 2A603
Please clarify construction of door
204. Door schedule calls for Glass/Aluminum construction, The detail 2A603 C1 does not depict any glass in door construction
There is no detail C1 on 2A603, refer to Head (H2), Jamb (J2 &J3), and Sill (S2) details indicated
1E011
2E506
On sheets 1E011 and 2E506, there are items stated as 'By Others'.
Please confirm that this will be outside of the Contractor's scope of work. This would include the 8-way routed ductbank, six way S&C Vista switch, 2-way routed ductbanks, spare ductbanks, etc.
Additionally, please confirm if the Contractor would be responsible for digging the trenches at the ductbank locations (by Others) or building the pad for the six-way S&C Vista switch (By Others).
The Contractor will not be responsible for the 8-way ductbank, the six-way S&C Vista Switch or the 2-way ductbank from the six-way switch to the pad mounted transformer. The Contractor is not responsible for digging the trenches for these two ductbanks or providing the pad for the six-way switch.
01 45 00.00 20 & 21 13
Schedule of FP System Inspections by FP QC Specialist & 1.2.1.2
Please confirm the FPQC and QFPE hold the same job responsibilities. Can it be assumed that the QFPE is the education/experience foundation for the FPQC to build on?
Yes, the intent is that the FPQC in Spec 01 45 00 is the same role as the QFPE in Spec 21 13 13 and Spec 28 31
76. There should only be one qualified fire protection engineer hired by a construction contractor to perform all fire protection and life safety systems inspections/tests during the construction phase.
2E002
2E706
Drawing 2E002, general note #41, along with general note #2 on multiple panel schedule drawings calls for temporary power for certain critical loads. For example, drawing 2E706 indicates that all four panels will have critical loads that require temporary power or minimum downtime. Please clarify what is considered minimum down time. If temporary power is required for these critical loads, please advise where temp. power can be pulled from.
The amount of minimum downtime will need to be coordinated with NSWC prior to any power interruptions.
Temporary power could be derived from other active panelboards in the space with available capacity or could be provided by means of a temporary generator set of other temporary power provisions.
25 General General General
Is there a maximum number of single phase circuits allowed in one conduit? If so, what is that max number?
Refer to General Note #18 on sheet 2E002. A maximum of three single phase circuit are permitted in one conduit.
2ED50
Panels L30B, L27B, L25B, L24B, & L21B are fed from new bus plugs on an existing 400A Northeast Bus Duct, however, there is no indication as to where this bus duct is located on the plans.
Please confirm location in relation to these panels.
The section of northeast busduct is located past Column B24. A feeder extends to a pull box at column B24 that feeds the section of bus duct.
2ED50
4 & 2E504
Panel L25B appears on the single line drawings 2ED504 & 2E504, however, there is no panel schedule for L25B provided in the documents. Can a panel schedule for L25B be provided?
Panel schedules will need to be issued as part of an Amendment.
28 2E505
Panels L13D, L21D, & L10D as shown on single line drawing 2E505 have no associated panel schedules included in the drawings.
Since the existing branch circuits will need to be extended from these panels, can you please provide panel schedules?
Refer to sheet 2E708 for Panel L10D schedule. The additional panel schedules will need to be issued as part of an Amendment.
2T501
2T503
Drawing 2T503 detail C1 indicates a surface mounted box below the raised floors in the control house, however, the electrical drawings refer you to detail A1 on drawing 2T501 which indicates this is an in-slab box. Please clarify what is required.
The below floor boxes in rooms 104, 105, 204, and 205 are per detail D3 on sheet 2T501 and are to be above the slab so they may be moved by the user. The floor boxes in Conference Room 107 are to be mounted in the floor slab and are per detail A1 on sheet 2T501. The description and symbol for the "Semi-Flush Floor Quad Receptacle" on the electrical legend on sheet 2E001 must be updated/revised.
1B101 - 1B610
31 62 00
Please provide the Geological assessment report that was performed for these WRA borings shown on the plan sheets Vol2 (sheets 1B101, 1B102, 1B601 to 1B610).
A geotechnical assessment report was performed by WRA for the Navy's use.
Pertinent data from the report, borings, site investigation, etc.
is indicated in the drawings and specifications. The geotechnical and geological data provided with the solicitation is made available so that bidders can make their own interpretations.
31 31 62 00
Pleas provide results of material testing, compressive strength, friction angles (appropriate Geotech design variables needed and/or used to design micropiles for this project).
All of the soil laboratory material test results performed for geotechnical design will be provided.
32 31 62 00
Please provide the geotech’s recommendations/analysis for the Conetec, Inc geophysical survey surface waves (MASW) inside building 77H.
The ConeTec geophysical survey (MASW) report dated Jan. 20, 2023 will be provided.
33 1B610 31 62 00
Cone Penetration Test Summary on plan sheet 1B610 lists the Phreatic line at 13.6-ft and 12.4-ft? Is this the depth from surface? If it is depth, then what surface elevation was used by the GPS receiver?
The ConeTec CPT report states that depths are referenced to the existing ground surface. The ground surface elevations at test locations are provided on plan sheet 1B101.
34 31 62 00 1.3
Please provide more details on requirements for the Methane Mitigation Plan for bidding accuracy.
Methane has been encountered within the soil. A mitigation plan is required to be submitted and approved by the government indicating how the Contractor will handle encountering methane.
35 31 62 00 3.4
Can contractor perform tension load testing (in accordance with D3689/D3689m) as an alternative to compression load testing?
Micropile tension load testing is allowed as an alternative to compression load testing if the test micropile and central reinforcing bar can safely resist the required compressive test load.
36 01 14 00 1.5.1.3
For bidding and schedule purposes, what is the approval time from submission of SECNAV 5512 to NAVFAC until NAVFAC's notification to the ktr of approval?
Allow a minimum of 10 days for approval.
37 01 14 00 1.5.1.3
For bidding and schedule purposes, what are the hours of operation for ktr badge pick up at Security (Building 29)?
Hours of Operation for the Security Office (BLDG 29) are Monday through Friday from 0730-1500.
38 59 Solicitation
FAR
52.217-7
Please clarify the proposal price validity requirements for CLINs 0002 - 0012 as noted in the bid schedule Attachment G. What is the time period after bid submission that the Prime Contractor's proposal must remain valid?
120 days as shown on PG. 1 of RFP document (Form 1442)
39 1C103 Please provide detail for the anchorage of the exterior historical marker.
Refer to specification section 10 14 00.10
40 09 69 13 2.2.5 Please clarify where "plenum divider" is located on the building drawings.
The raised access floor does not require plenum divider accessories. The plenums are separated by the partitions extending below the Raised Access Floor. See 2A154 & 2A155
41 2I402
Please provide more detail on the requirements for the Laser Cut Brushed Aluminum Sign with Backlight located in the fishbowl break area.
The sign is 6'-4"L X 2'-8"H.
Propose shop drawings for review.
2S502
2S504
Structural drawings indicated a depressed trench drain within the slab of Building 77H, however, nothing is shown on the plumbing drawings. Please advise if any plumbing connections are required for the trench drain.
Trench and sump pits in Part C and Part D portions of the slab are for containment only and do not have any plumbing connections.
43 2H101 Please provide a bid quantity for removal of asbestos containing translucent wall panel caulk.
Refer to other disciplines drawings for work that may affect translucent wall panels.
It is anticipated that this abatement will either be minimal or not required.
44 2H101 Please provide a bid quantity for removal of lead paint.
Assume all existing steel paint is lead. All work disturbing the paint of the existing steel may require lead abatement.
45 2I601 09 29 00
Please clarify the location of any "critical lighting" in the control house as referenced in spec 09-29- 00 3.3. Also please clarify if paint with eggshell finish as called for in drawing 2I601 classifies as "flat paint" as referenced in spec 09-29- 00 3.3.
"Eggshell" paint finish as called out on finish schedule should not be classified as "flat" paint.
Can photos of the exterior work areas on the west side of Building 77H please be provided? The Government did not grant access to this area during the pre-bid site walk.
Photos included with Amendment 0003.
Can photos of the interior (high bay area and lean-to) column lines 1-12 of Bldg. 77H be provided?
Photos of the existing condition would be useful to bidding subcontractors unable to attend the pre-bid visit.
Photos must undergo security process and currently in review.
Can photos of Building 77H north of CL 12, the occupied space on the north side of the dust barrier, for purposes of the fire protection scope, please be provided? The Government did not grant access to this area during the pre-bid site walk. Being that this area is occupied, and a significant amount of overhead work is scheduled, bidding this area sight unseen would be unwise for the Government.
Photos must undergo security process and currently in review.
In what locations is EMT conduit acceptable for the automation scope of work? Specification is silent on conduit requirements for BAS and controls.
Refer to Section 3.2.8 under 23 09 00.00 20 for requirements regarding routing wiring in conduits.
In what locations, if any, is Galvanized Rigit Conduit necessary for the automation scope of work? Specification is silent on
Refer to Section 3.2.8 under 23 09 00.00 20 for requirements regarding routing wiring in conduits.
conduit requirements for BAS and controls.
Please confirm compression fittings are required for all outdoor conduit installation. Specification is silent on conduit requirements for BAS and controls.
Refer to Section 3.2.8 under 23 09 00.00 20 for requirements regarding routing wiring in conduits.
Please advise the closest connection point for the existing Building Automation System for tie-in purposes.
There are multiple tie-in points for the existing Building Automation System distributed within the repair boundary.
53 28 10 05 1.3.4.2
The specs call for 2 years’ experience as an installer of the Lenel ESS or similar system. If experience with many different ESS systems, but not Lenel, is possessed, will this experience be acceptable?
Requirement is for experience of Lenel OR SIMILAR.
Similar experience is acceptable.
2I103/2
I601
Please confirm what flooring will be used in Mech 103, Jan 202 of control house. The finish plans call for epoxy flooring, but schedule calls for resilient tile.
Please proceed with epoxy, as shown on finish plans.
2A162/ 2I601
Please confirm location of exposed ceiling for Control Room 205.
Schedule calls for Exposed, GWB, SCG-1.
Control Room 205 has no exposed ceiling. Refer to RCP Sheet 2A162.
56 2A801 09 67 23.13 3.1
Please clarify the existing conditions of substrate in B485, Are repairs to concrete substrate to be expected? Is there any preexisting coatings to the floor or floor coverings?
Significant repairs to the concrete are not anticipated (other than at the locations where concrete pads are demolished or at the trench locations). There is an existing coating on the floor.
57 2I601 09 67 23.
3.2.2
Please clarify the proposed thickness of the epoxy coating. The specs call for a nominal thickness of 3/16 inch, while the Stonhard MR called for in 2I601 recommends a nominal thickness of 30-40 mil.
Please proceed with manufacturer's suggested thickness of the basis of design product.
Note
8/2S001
Please indicate where ASTM A143 subcritical annealing of hot-dip galvanized HSS members is required.
Provide thermal treatment in accordance with ASTM A143 for all hot-dip galvanized HSS square and rectangular members, and for any other hot-dip galvanized shapes, plates, and hardware with an inside cold bend radius less than 3 times its thickness.
59 28 Solicitation
FAR
52.211-14
Considering that the national supply chain remains strained with lead times for fabrication and delivery of mechanical and electrical equipment and many construction commodities, can the Government consider increasing the DPAS rating of this project from DO to DX?
The DPAS rating for this project will remain DO-C2.
At locations where existing fire alarm devices are indicated to be removed, patched, and painted, clarify extent of painting required to be deemed acceptable by the Government.
Paint area behind where device was removed and an additional 4" all around.
61 2A603 08-39-21 2.2.1.2
Clarify dimensions of vision lites for doors 101A & 101C. Drawing 2A603 states that the doors are type "B" which on detail C2 of the same page is depicted as having a 3'-4" vision lite. However, the product listed under spec section 08-39-21 " PS Flood Barriers TM model Hydro1-PD520" is not offered with this size of vision lite.
Provide 5" x 20" vision lite per manufacturer's standards.
1442-
13 A
We request that the project sealed offer due date of 22 July 2024 be changed to 05 September, or there about, to provide more preparation time.
Proposal due date of 22 July 2024 remains unchanged.
The following information has been revised:
DRAWINGS:
On NAVFAC Drawing No. 12900955 (1G002):
REPLACE the following drawing in the DRAWING INDEX under the corresponding discipline and drawing number. This drawing accompanies this Amendment:
2A603 12901177 DOOR SCHEDULE & DETAILS – REPLACE SHEET
On NAVFAC Drawing No. 12900956 (1G003):
2P152 12901342 CONTROL HOUSE – FIRST FLOOR PLAN – REPLACE SHEET
On NAVFAC Drawing No. 12900957 (1G004):
ADD the following drawing in the DRAWING INDEX under the corresponding discipline and drawing number.
This drawing accompanies this Amendment:
2E713 12901512 SCHEDULES – ADD SHEET
On NAVFAC Drawing No. 12901020 (2G002):
2A603 12901177 DOOR SCHEDULE & DETAILS – REPLACE SHEET
On NAVFAC Drawing No. 12901021 (2G003):
2P152 12901342 CONTROL HOUSE – FIRST FLOOR PLAN – REPLACE SHEET
On NAVFAC Drawing No. 12901022 (2G004):
ADD the following drawing in the DRAWING INDEX under the corresponding discipline and drawing number.
This drawing accompanies this Amendment:
2E713 12901512 SCHEDULES – ADD SHEET
On NAVFAC Drawing No. 12901177 (2A603):
DOOR SCHEDULE DELETE Door Number 102 Type XX and REPLACE with Type A, Delete Door Number 105 Type WW and REPLACE with Type C
On NAVFAC Drawing No. 12901342 (2P152):
GENERAL SHEET NOTES DELETE notes:
3. “3/4" CONDENSATE DISCHARGE DOWN, TIGHT TO WALL, TO WALL MOUNTED
CONDENSATE PUMP.”
4. “2" CONDENSATE DRAIN DOWN TO APPROXIMATELY 36" ABOVE FINISHED FLOOR.
EXTEND THROUGH WALL AND TERMINATE WITH ELBOW DOWN, DISCHARGING
TO GRADE.”
SHEET KEYNOTES ADD notes:
2: “NOT USED.”
3: “3/4" CONDENSATE DISCHARGE DOWN, TIGHT TO WALL, TO WALL MOUNTED
CONDENSATE PUMP.”
4. “2" CONDENSATE DRAIN DOWN TO APPROXIMATELY 36" ABOVE FINISHED FLOOR.
EXTEND THROUGH WALL AND TERMINATE WITH ELBOW DOWN, DISCHARGING
TO GRADE.”
On NAVFAC Drawing No. 12901512 (2E713):
ADD Sheet including Panel L25B, L21D, & L13D Schedules
SPECIFICATIONS:
DOCUMENT 00 01 15 LIST OF DRAWINGS
1.2 CONTRACT DRAWINGS
DELETE and REPLACE the following drawings as of 6/27/2024. These drawings accompany this Amendment.
DRAWING NO. REVISION NO. NAVFAC DWG NO. TITLE
2A603 1 12901177 DOOR DETAILS & SCHEDULES
2P152 1 12901342 CONTROL HOUSE – FIRST FLOOR PLAN
ADD the following drawing as of 6/27/2024. This drawing accompanies this Amendment.
DRAWING NO. REVISION NO. NAVFAC DWG NO. TITLE
2E713 1 12901512 SCHEDULES
ATTACHMENTS:
1. Amendment 0003 – Reference Drawing Package to include:
a. Amend0003 - 010 – BLDG077H – DIESEL TEST CELLS – 2163658.pdf
b. Amend0003 - 011 – BLDG077H – DIESEL TEST CELLS – 2163659.pdf
c. Amend0003 - 049 – BLDG077H – WEAPONS ELEVATOR – 2078005.pdf
d. Amend0003 - 050 – BLDG077H – WEAPONS ELEVATOR – 2078007.pdf
e. Amend0003 - 051 – BLDG077H – WEAPONS ELEVATOR – 2078008.pdf
f. Amend0003 - 052 – BLDG077H – WEAPONS ELEVATOR – 2078009.pdf
g. Amend0003 - 1705955_DEMO_DWG_FULL SET.pdf
h. Amend0003 - 7625158 R-D04-10-25_Redacted.pdf
i. Amend0003 - 7625160 R-D04-09-16_Redacted.pdf
j. Amend0003 - 30041555 R-APPROVED 2021-08-11 ZONE 1 GENL ARR_Redacted.pdf
k. Amend0003 - 30041586 R1 2021-08-12 SITE EQUIPMENT ARR_Redacted.pdf
l. Amend0003 - Automatic Fire Sprinkler System for Prefab Enclosure 12031990.pdf
m. Amend0003 - PW-30 5400C249.pdf
n. Amend0003 - PW-31 5400C246.pdf
o. Amend0003 - PW-32 5400C247.pdf
2. Amendment 0003 – FFG-62 Drawings Signed
3. Amendment 0003 – PPI 46 FFG62 Repair 77H Exterior SW Yard Existing Cond Photos DistroA
SECTION 01 00 00 - GENERAL REQUIREMENTS
The following have been modified:
WAGE DETERMINATION
"General Decision Number: PA20240003 06/21/2024
Superseded General Decision Number: PA20230003
State: Pennsylvania
Construction Type: Building
County: Philadelphia County in Pennsylvania.
BUILDING CONSTRUCTION PROJECTS (does not include single family homes or apartments up to and including 4 stories).
Note: Contracts subject to the Davis-Bacon Act are generally required to pay at least the applicable minimum wage rate required under Executive Order 14026 or Executive Order 13658.
Please note that these Executive Orders apply to covered contracts entered into by the federal government that are subject to the Davis-Bacon Act itself, but do not apply to contracts subject only to the Davis-Bacon Related Acts, including those set forth at 29 CFR 5.1(a)(1).
|If the contract is entered |. Executive Order 14026 | |into on or after January 30, | generally applies to the | |2022, or the contract is | contract. | |renewed or extended (e.g., an |. The contractor must pay | |option is exercised) on or | all covered workers at | |after January 30, 2022: | least $17.20 per hour (or | | | the applicable wage rate | | | listed on this wage | | | determination, if it is | | | higher) for all hours | | | spent performing on the | | | contract in 2024. |
|If the contract was awarded on|. Executive Order 13658 | |or between January 1, 2015 and| generally applies to the | |January 29, 2022, and the | contract. | |contract is not renewed or |. The contractor must pay all| |extended on or after January | covered workers at least | |30, 2022: | $12.90 per hour (or the | | | applicable wage rate listed| | | on this wage determination,| | | if it is higher) for all | | | hours spent performing on | | | that contract in 2024. |
The applicable Executive Order minimum wage rate will be adjusted annually. If this contract is covered by one of the Executive Orders and a classification considered necessary for performance of work on the contract does not appear on this wage determination, the contractor must still submit a conformance request.
Additional information on contractor requirements and worker protections under the Executive Orders is available at http://www.dol.gov/whd/govcontracts.
Modification Number Publication Date 0 01/05/2024 1 01/12/2024 2 01/19/2024 3 02/23/2024 4 05/10/2024 5 05/17/2024 6 05/24/2024 7 05/31/2024 8 06/21/2024
ASBE0014-001 05/01/2024
Rates Fringes
Asbestos Workers/Insulator Includes the application of all insulating materials, protective coverings, coatings, and finishes to all types of mechanical systems..........$ 59.37 45.78
BOIL0013-001 01/01/2024
Rates Fringes
BOILERMAKER......................$ 52.10 35.38
BRPA0001-006 05/01/2024
Rates Fringes
BRICKLAYER.......................$ 48.70 31.61
BRPA0001-008 05/01/2024
Rates Fringes
TILE SETTER......................$ 51.36 30.02
BRPA0001-011 05/01/2024
Rates Fringes
MASON - STONE....................$ 48.40 31.95
BRPA0001-015 05/01/2024
Rates Fringes
Pointer, caulker and cleaner.....$ 50.00 30.70
CARP0158-001 05/01/2023
Rates Fringes
Carpenter/Lather.................$ 52.64 29.27
CARP0219-005 05/01/2023
Rates Fringes
MILLWRIGHT.......................$ 51.60 35.81
CARP0251-001 05/01/2023
Rates Fringes
FLOOR LAYER: Carpet.............$ 53.93 30.27
CARP0474-004 05/01/2023
Rates Fringes
PILEDRIVERMAN....................$ 46.73 41.69
ELEC0098-003 05/02/2022
Rates Fringes
ELECTRICIAN......................$ 65.76 61%+1.98
ELEC0098-014 05/02/2022
ELECTRICIAN (Sound and Communication Technician) (Installation of Voice Data, IT Network, Wifi))...............$ 63.97 30.40
ELEV0005-001 01/01/2024
Rates Fringes
ELEVATOR MECHANIC................$ 68.97 37.885+a+b
FOOTNOTES FOR ELEVATOR MECHANICS:
A. PAID VACATION: Employer contributes 8% of basic hourly rate for 5 years or more of service or 6% for 6 months to 5 years of service.
B. Eight Paid Holidays (provided employee has worked 5 consecutive days before and the working day after the holiday): New Years's Day; Memorial Day; Independence Day;
Labor Day; Veteran's Day; Thanksgiving Day and the Friday after Thanksgiving Day, and Christmas Day.
* ENGI0542-002 05/01/2024
Rates Fringes
Power equipment operators:
GROUP 1.....................$ 53.36 33.65+A
GROUP 1a....................$ 56.37 34.53+A
GROUP 2.....................$ 53.11 33.58+A
GROUP 2a....................$ 56.13 34.45+A
GROUP 3.....................$ 49.03 32.37+A
GROUP 4.....................$ 48.73 32.28+A
GROUP 5.....................$ 47.00 31.78+A
GROUP 6.....................$ 46.02 31.48+A
FOOTNOTE: A. PAID HOLIDAYS: New Year's Day; Memorial Day;
Independence Day; Labor Day; Thanksgiving Day and Christmas Day
***TOXIC/HARARDOUS WASTE REMOVAL***
Add 20 per cent to basic hourly rate for all classifications
BOOM LENGTH PAY:
On all machines with booms, jibs, masts and leads, including tower cranes, 100 ft. from ground up, fifty cents ($.50) per hour additional will be paid for each increment of 25
ft. over 100 ft. On cranes with booms (including jibs, masts and leads) 200 ft. and over, two (2) operators will be required. When two (2) operators are employed, no Oiler will be required. Booms to be measured from the ground up.
Tower cranes calculated from ground up and out for purpose of boom pay.
POWER EQUIPMENT OPERATORS CLASSIFICATIONS
GROUP 1: Handling steel and stone in connection with erection, cranes doing hook work, any machine handling machinery, helicopters, concrete pumps building machines similar to the above, including remote, robotic or laser control equipment.
GROUP 1a: Machines handling steel, or the functional equivalent, and stone in connection with erection 15 ton and over factory rating; Cranes doing hook work 15 ton and over factory rating; Any machines handling machinery; HIgh Rail/Burro Crane 15 ton and over factory rating; Rail Loader (Winch Boom Type) 15 ton and over factory rating;
Concrete Pumps (Building) 120 feet of Boom length or less (200 yard pour or less); Machines similar to above, including remote, robotic or laser control equipment;
Equipment in this Wage Group that does not require an oiler.
GROUP 2: All types of cranes, All types of backhoes, Cableways, Draglines, Keystones, all types of shovels, Derricks, Pavers 21E and over, Trenching machines, Trench shovel, Gradalls, Front-End loaders, Boat Captain, Pippin type backhoes, Tandems scrapers, Towers type crane operation erecting, Dismantling, Jumping or Jacking, Drills (self-containes), (drillmaster type) forklift (20 ft. and over), Moter patrols (fine grade), Batch plant with mixer, Carryalls, Scraper, Trounapulls, Roller (Hith Grade Finishing), Spreaders (asphalt), Bulldozers and Tractors, Mechanic welder, Conveyor loaders (euclid-type wheel), Concrete pump, Milling Machines, Hoist with two towers, Building hoist double drum (unless used as a single drum), Mucking machines in tunnel, All auto grade and concrete finishing machines, Bundle pullers/extractors (tublar), bobcat. side broom, directional boring machines, vermeer saw type machines(other than than hand held tractor mounted hydro axe, chipper with boom, all) machine similar to the above including remote, robotic or laser control equipment.
GROUP 2a: Crawler backhoes and Crawler gradalls over one cubic yard factory rating; Hydraulic backhoes over one cubic yard factory rating; All types of cranes 15 ton and over factory rating; Cherry picker type machinery and equipment 15 ton and over factory rating; Concrete Pumps (Heavy/Highway); Machines similar to above, including remote, robotic or laser control equipment; Equipment in this Wage Group that does not require an oiler.
GROUP 3: Asphalt plant engineers, Well drillers, Ditch witch (small trencher), Motor patrols, Fine grade machines, Ten-ton roller (grade fill stone base), Concrete breaking machines, Guilloline only, Stump grinder, Conveyors (except building conveyors), Fork lift trucks of all types, High pressure boliers Elevator Operator (New Construction) Machine similar to the above,including remote, robotic or laser control equipment
GROUP 4: Seaman, Pulverzer form line grader, Farm tractors, road finishing, Concrete spreader, Power broom (self-contained), Seed spreader, Grease truck, toxic/hazardous wate removal rate 20 per cent added to all classifications and machiines similar to the above including remote, robotic or laser control equipment.
GROUP 5: Compressors pumps, Well point pumps, Welding machines Tireman, Power equipment, Maintenance engineer (power boats),Elevator Operators (Renovations) and machine similar to the above including remote, robotic or laser control equipment.
GROUP 6: Fireman, Oilers and deck hands (personnel boats), grease truck. Machines similar to the above including remote, robotic or laser control equipment.
IRON0401-002 07/01/2023
Rates Fringes
IRONWORKER, STRUCTURAL AND
ORNAMENTAL.......................$ 51.20 40.60
IRON0405-002 07/01/2023
Rates Fringes
IRONWORKER, REINFORCING..........$ 48.29 34.17
The following holidays shall be observed and when work is performed thereon it shall be paid for at twice the base rate: New Year's Day, Memorial Day, Independence Day, Labor Day, Thanksgiving Day, and Christmas Day. Employees shall be off Christmas Eve Day and receive four hours pay.
Employees who have to work on Christmas Eve Day shall work four hours and be paid for eight hours pay for the holiday.
Any time worked beyond fours hours shall be paid at the double time rate plus the four hours holiday pay. To receive holiday pay, the employee must work the day before Christmas Eve and the first working day after Christmas Day.
IRON0405-004 07/01/2023
Rates Fringes
IRONWORKER (Rigger and Machinery Mover).................$ 48.29 34.17
The following holidays shall be observed and when work is performed thereon it shall be paid for at twice the base rate: New Year's Day, Memorial Day, Independence Day, Labor Day, Thanksgiving Day, and Christmas Day. Employees shall be off Christmas Eve Day and receive four hours pay.
Employees who have to work on Christmas Eve Day shall work four hours and be paid for eight hours pay for the holiday.
Any time worked beyond fours hours shall be paid at the double time rate plus the four hours holiday pay. To receive holiday pay, the employee must work the day before Christmas Eve and the first working day after Christmas Day.
LABO0332-001 05/01/2023
Rates Fringes
LABORER
GROUP 1....................$ 36.45 26.29
GROUP 2....................$ 36.55 26.29
GROUP 3....................$ 36.60 26.29
GROUP 4....................$ 36.75 26.29
GROUP 5....................$ 36.80 26.29
GROUP 6....................$ 36.59 26.29
GROUP 7....................$ 37.70 26.29
GROUP 8....................$ 37.85 26.29
GROUP 9....................$ 38.00 26.29
GROUP 10....................$ 38.25 26.29
GROUP 11....................$ 36.82 26.29
LABORERS CLASSIFICATIONS
GROUP 1: Building site work; Stripping and dismantling concrete form work; loading, unloading, carrying and handling of all reinforced steel and steel mesh; handling lumber and other building materials; operating jackhammers, paving breakers and all other pneumatic tools; building scaffolds; raking, shoveling and tamping of asphalt;
spading and concrete pit work; grading; form pinning;
shoring; demolition except burners; laying conduits and ducts; sheathing; lagging; laying non-metallic pipe and caulking; all other types of laborers; pouring concrete;
operating vibrator; free air tunnels: miners.
GROUP 2: Power buggies; burners on demolition
GROUP 3: Wagon drill operator (single)
GROUP 4: Powdermen; wagon drill operator (multiple);
circular caisson excavation; underpinning excavation
GROUP 5: Caisson bottom man
GROUP 6: Yard workers
GROUP 7: Trackmen; brakemen; groutmen; bottom shaft men;
all other men in free air tunnels
GROUP 8: Form setters
GROUP 9: Miners bore driver; blasters; drillers; pneumatic shield operators
GROUP 10: Welders and burners
GROUP 11: Mason Tender
LABO0332-002 05/01/2023
Rates Fringes
LABORER (Asbestos Abatement, Toxic and Hazardous Waste Removal, Lead Based Paint Removal).........................$ 37.95 26.64
LABO0413-004 05/01/2023
Rates Fringes
Landscape Laborer Farm Tractor Driver, Hydroseeder Nozzleman and Mulcher Nozzleman...........$ 29.45 23.55+A
FOOTNOTE:
A. PAID HOLIDAYS: Independence Day, Labor Day, and Thanksgiving Day.
MARB0001-003 05/01/2021
Rates Fringes
MARBLE FINISHER..................$ 25.10 20.75
TERRAZZO FINISHER................$ 27.03 20.58
TILE FINISHER....................$ 25.10 20.75
MARB0003-002 05/01/2021
Rates Fringes
MARBLE SETTER....................$ 44.90 30.75
TERRAZZO WORKER/SETTER...........$ 48.01 28.67
PAIN0021-001 05/01/2021
Rates Fringes
Painters:
Brush, Roller...............$ 41.24 28.10 Spray, Steel and Swing......$ 42.49 28.10
PAIN0021-012 05/01/2023
Rates Fringes
DRYWALL FINISHER/TAPER...........$ 41.80 31.36
PAIN0252-001 06/01/2021
Rates Fringes
Window Tinter....................$ 25.02 13.06
PAIN0252-006 05/01/2022
Rates Fringes
GLAZIER..........................$ 46.09 34.83
PLAS0008-001 05/01/2022
Rates Fringes
PLASTERER........................$ 41.97 32.20
PLAS0592-011 05/01/2023
Rates Fringes
CEMENT MASON/CONCRETE FINISHER...$ 44.20 32.76
PLUM0420-008 05/01/2024
Rates Fringes
Steamfitter......................$ 70.32 42.78
PLUM0690-002 05/01/2023
Rates Fringes
PLUMBER..........................$ 64.73 37.21
ROOF0030-001 05/01/2022
Rates Fringes
Roofers:
Composition.................$ 41.48 33.37+A Shingles....................$ 31.25 21.75+A Slate and Tile..............$ 34.25 21.75+A
FOOTNOTE (Composition Roofer only):
A. PAID HOLIDAY: Election Day
SFPA0692-001 05/01/2024
SPRINKLER FITTER.................$ 66.81 33.66
SHEE0019-008 05/01/2024
Rates Fringes
SHEET METAL WORKER...............$ 59.22 49.06
SHEE0019-023 07/15/2023
Rates Fringes
SHEET METAL WORKER (Sign Makers & Hangers)................$ 31.76 24.63
TEAM0107-001 05/01/2024
Rates Fringes
TRUCK DRIVER (BUILDING
CONSTRUCTION)
GROUP 1.....................$ 36.795 22.5495+a+b GROUP 2.....................$ 36.895 22.5495+a+b GROUP 3.....................$ 37.145 22.5495+a+b
TRUCK DRIVER (SITE
PREPARATION, PAVING AND
UTILITIES ON BUILDING
CONSTRUCTION)
GROUP 1.....................$ 36.14 21.555+a+b GROUP 2.....................$ 36.24 21.555+a+b GROUP 3.....................$ 36.49 21.555+a+b
TRUCK DRIVERS CLASSIFICATIONS (BUILDING CONSTRUCTION)
GROUP 1 - Stake body truck (single axle), 11/2 ton and under vehicles
GROUP 2 - Truck driver over 11/2 tons, dump trucks, tandem and batch trucks, semi-trailers, agitator mixer trucks and dumcrete type vehicle, asphalt distributors, farm tractors when used for transportation, stake body truck (tandem)
GROUP 3 - Euclid type, off-highway equipment - back or belly dump trucks and double-hitched equipment, straddle (ross) carrier, lowbed trailers
TRUCK DRIVERS CLASSIFICATIONS (SITE PREPARATION, PAVING AND
UTILITIES ON BUILDING CONSTRUCTION)
GROUP 1 - Stake body truck (single axle), dumpster
GROUP 2 - Dump trucks, tandem and batch trucks, semi-trailers, agitator mixer trucks, and dumpcrete type vehicles, asphalt distributors, farm tractor when used for transportation, stake body truck (tandem)
GROUP 3 - Euclid type, off-highway equipment or bell dump trucks and double hitched equipment, staddle (ross) carrier, low-bed trailers
FOOTNOTE:
a. PAID HOLIDAYS: Memorial Day, Independence Day, Labor Day, Thanksgiving Day and five personal holidays provided employee works at least one day in the three work days before and at least one day in the three work days after the said holiday. Emloyee earns a personal holiday every two months, provided employee has worked twenty-six day in each consecutive two month period, up to a maximum of five per calendar year. After 130 work days the employee is entitled to all five personal holidays.
b. PAID VACATION: Employee will earn one vacation day for every two months, provided employee has worked twenty-six day in each consecutive two month period, up to a maximum of five vacation days per calendar year. After 130 workdays the employee is entitled to all five days of vacation. Employees with 5 years of seniority, earn an additional week of vacation, accrued in the same way.
WELDERS - Receive rate prescribed for craft performing operation to which welding is incidental.
Note: Executive Order (EO) 13706, Establishing Paid Sick Leave for Federal Contractors applies to all contracts subject to the Davis-Bacon Act for which the contract is awarded (and any solicitation was issued) on or after January 1, 2017. If this contract is covered by the EO, the contractor must provide employees with 1 hour of paid sick leave for every 30 hours they work, up to 56 hours of paid sick leave each year.
Employees must be permitted to use paid sick leave for their own illness, injury or other health-related needs, including preventive care; to assist a family member (or person who is like family to the employee) who is ill, injured, or has other health-related needs, including preventive care; or for reasons resulting from, or to assist a family member (or person who is like family to the employee) who is a victim of, domestic violence, sexual assault, or stalking. Additional information on contractor requirements and worker protections under the EO is available at https://www.dol.gov/agencies/whd/government-contracts.
Unlisted classifications needed for work not included within the scope of the classifications listed may be added after award only as provided in the labor standards contract clauses (29CFR 5.5 (a) (1) (iii)).
The body of each wage determination lists the classification and wage rates that have been found to be prevailing for the cited type(s) of construction in the area covered by the wage determination. The classifications are listed in alphabetical order of ""identifiers"" that indicate whether the particular rate is a union rate (current union negotiated rate for local), a survey rate (weighted average rate) or a union average rate (weighted union average rate).
Union Rate Identifiers
A four letter classification abbreviation identifier enclosed in dotted lines beginning with characters other than ""SU"" or ""UAVG"" denotes that the union classification and rate were prevailing for that classification in the survey. Example:
PLUM0198-005 07/01/2014. PLUM is an abbreviation identifier of the union which prevailed in the survey for this classification, which in this example would be Plumbers. 0198 indicates the local union number or district council number where applicable, i.e., Plumbers Local 0198. The next number, 005 in the example, is an internal number used in processing the wage determination. 07/01/2014 is the effective date of the most current negotiated rate, which in this example is July 1, 2014.
Union prevailing wage rates are updated to reflect all rate changes in the collective bargaining agreement (CBA) governing this classification and rate.
Survey Rate Identifiers
Classifications listed under the ""SU"" identifier indicate that no one rate prevailed for this classification in the survey and the published rate is derived by computing a weighted average rate based on all the rates reported in the survey for that classification. As this weighted average rate includes all rates reported in the survey, it may include both union and non-union rates. Example: SULA2012-007 5/13/2014. SU indicates the rates are survey rates based on a weighted average calculation of rates and are not majority rates. LA indicates the State of Louisiana. 2012 is the year of survey on which these classifications and rates are based. The next number, 007 in the example, is an internal number used in producing the wage determination. 5/13/2014 indicates the survey completion date for the classifications and rates under that identifier.
Survey wage rates are not updated and remain in effect until a new survey is conducted.
Union Average Rate Identifiers
Classification(s) listed under the UAVG identifier indicate that no single majority rate prevailed for those classifications; however, 100% of the data reported for the classifications was union data. EXAMPLE: UAVG-OH-0010 08/29/2014. UAVG indicates that the rate is a weighted union average rate. OH indicates the state. The next number, 0010 in the example, is an internal number used in producing the wage determination. 08/29/2014 indicates the survey completion date for the classifications and rates under that identifier.
A UAVG rate will be updated once a year, usually in January of each year, to reflect a weighted average of the current negotiated/CBA rate of the union locals from which the rate is based.
State Adopted Rate Identifiers
Classifications listed under the ""SA"" identifier indicate that the prevailing wage rate set by a state (or local) government was adopted under 29 C.F.R §1.3(g)-(h). Example: SAME2023-007 01/03/2024. SA reflects that the rates are state adopted. ME refers to the State of Maine. 2023 is the year during which the state completed the survey on which the listed classifications and rates are based. The next number, 007 in the example, is an internal number used in producing the wage determination.
01/03/2024 reflects the date on which the classifications and rates under the ?SA? identifier took effect under state law in the state from which the rates were adopted.
WAGE DETERMINATION APPEALS PROCESS
1.) Has there been an initial decision in the matter? This can be:
* an existing published wage determination
* a survey underlying a wage determination
* a Wage and Hour Division letter setting forth a position on a wage determination matter
* a conformance (additional classification and rate) ruling
On survey related matters, initial contact, including requests for summaries of surveys, should be with the Wage and Hour National Office because National Office has responsibility for the Davis-Bacon survey program. If the response from this initial contact is not satisfactory, then the process described in 2.) and 3.) should be followed.
With regard to any other matter not yet ripe for the formal process described here, initial contact should be with the Branch of Construction Wage Determinations. Write to:
Branch of Construction Wage Determinations
Wage and Hour Division U.S. Department of Labor 200 Constitution Avenue, N.W.
Washington, DC 20210
2.) If the answer to the question in 1.) is yes, then an interested party (those affected by the action) can request review and reconsideration from the Wage and Hour Administrator (See 29 CFR Part 1.8 and 29 CFR Part 7). Write to:
Wage and Hour Administrator U.S. Department of Labor 200 Constitution Avenue, N.W.
Washington, DC 20210
The request should be accompanied by a full statement of the interested party's position and by any information (wage payment data, project description, area practice material, etc.) that the requestor considers relevant to the issue.
3.) If the decision of the Administrator is not favorable, an interested party may appeal directly to the Administrative Review Board (formerly the Wage Appeals Board). Write to:
Administrative Review Board U.S. Department of Labor 200 Constitution Avenue, N.W.
Washington, DC 20210
4.) All decisions by the Administrative Review Board are final.
END OF GENERAL DECISION”
(End of Summary of Changes)